Honeywell CTP Data Sheet

CTP Current Transmitters

FEATURES

• Split core loop-powered current transmitters for simple installation.
• High accuracy and linearity.
• Selectable scaling on most models for greater measurement accuracy.
• Fast response time.
• Integral DIN rail mounting flange.

APPLICATION

The CTP current transmitters monitor the current flow for various electrical equipment. Measured current level is converted into a linear and proportional 0 - 5/10 Vdc or 4-20 mA output signal, which can be monitored by a Building Management, DDC, or PLC controller. Current sensors with switch selectable current ranges provide optimal resolution for greater measuring accuracy. These current sensors should be used in load trending (current monitoring) type applications.
The split core design makes installations easy since no wires need to be disconnected during the installation process. May be mounted directly on the conductor (codes permitting) or fixed mount on DIN rail.
Typical load status applications include:
• Load trending
• Monitoring process motors and pumps
• Electric heater current monitoring
• Easy wiring, polarity sensitive output.
• Optional slide on command relay for unitary start­stop status.
• Limited 5-year warranty.

SPECIFICATIONS

Table 1. Specification by Product.
Product Number Output* Range Max Current
CTP-A-20A 4-20 mA 5/10/20 A 200 A
CTP-A-120A 4-20 mA 30/60/120 A 200 A
CTP-5V-20A 0-5 Vdc 5/10/20 A 100 A
CTP-10V-120A 0-10 Vdc 30/60/120 A 200 A
CTP-10V-200A 0-10 Vdc Fixed, 200 A 200 A
*Note: 0 - 5/10 Vdc output (induced power) 4-20 mA output (12-30 Vdc power source required)
PRODUCT DATA
Contents
Application ..................................................................................... 1
Features .......................................................................................... 1
Specifications ............................................................................... 1
31-00431-01
CTP CURRENT TRANSMIT TERS
Load Amps
Factory calibrated
0A
Sensor
Output
0 V 0 mA
5 V or 10 V
20 mA
Selected Range
Table 2. Specifications.
Specification Rating
Accuracy +/-2% F.S. over 10 to 100% range
Ambient Temperature Rating
Insulation Class
Sensor Power
Frequency Range 50/60Hz
Dimensions (LxWxH)
Sensor Aperture 0.75”
Environmental
600V RMS. For use on insulated conductors only!
Use minimum 75 °C insulated conductor
Induced, 12 to 30 Vdc max for loop powered
(1.4” H with optional relay module)
Pollution Degree 2 (non-conductive/non-
-15
~60 ° C
sensors
2.94” x 2.23” x 0.82”
condensing)
Analog current sensors output signal proportional to monitored current.
Fig. 1. Linear proportional output.
3PZS
E516382
RoHS Compliant
Honeywell Building Technologies
In the U.S.:
Honeywell
buildingcontrols.honeywell.com
® U.S. Registered Trademark © 2020 Honeywell International Inc. 31-00431—01 M.S. 10-20 Printed in United States