Installation Manual of Room Air Conditioner
Read this manual before installation
Explain sufficiently the operating means to the user according to this manual.
Necessary Tools for Installation
1.Driver |
5.Torque wrench(17mm,22mm,26mm) |
9.Nipper |
12.Reamer |
2.Hacksaw |
6.Pipe cutter |
10.Gas leakage detector or |
|
3.Hole core drill |
7.Flaring tool |
soap-and-water solution |
|
4.Spanner(17,19 and 26mm) |
8.Knife |
11.Measuring tape |
|
Accessory parts
No. |
Accessory parts |
Number |
|
of |
|||
|
|
|
articles |
1 |
Remote controller |
1 |
|
2 |
R-03 dry battery |
2 |
|
3 |
|
|
1 |
|
|
Mounting plate |
|
4 |
|
Drain hose |
1 |
|
|
|
|
5 |
4X25 |
Plastic cap |
4 |
|
Screw |
|
|
6 |
|
Drain-elbow |
1 |
7 |
|
Cushion |
4 |
8 |
Change for |
1 |
|
|
|
||
|
fresh air box |
|
|
9 |
Change for |
1 |
|
fresh air tube(suit) |
|||
10 |
Outlet joint |
2 |
Drawing for the installation of indoor and outdoor units
The models adopt HFC free refrigerant R410A
more than 5cm
|
|
more |
than |
10cm |
Optional parts for piping |
|
|||
|
|
|||
|
|
|
||
|
|
|
|
|
Mark |
Parts name |
|
|
|
ANon-adhesive tape
BAdhesive tape
CSaddle(L.S) with screws
DConnecting electric cable for indoor and outdoor
EDrain hose
FHeating insulating material
GPiping hole cover
Arrangement of piping directions
Attention must be paid to the rising up of drain hose
G
more |
than |
10cm |
|
||
|
|
F
A
C
|
Rear left |
more |
|
|
|
|
Left |
Rear |
than |
|
|
than10cm |
|
|
10cm |
|
||||
|
right |
|
|
more |
|
|
|
Right |
|
|
|
|
|
|
Below |
|
|
|
|
|
9
10
D
E
|
than |
60cm |
more |
|
|
|
|
more |
than |
15cm |
|
||
|
|
|
The marks from A to G in the figure are the parts numbers. |
No.001051 |
The distance between the indoor unit and the floor should be |
more than 2m. |
256
|
|
|
|
|
|
|
|
|
|
|
|
140 |
|
500 |
|
|
140 |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
Floor fixing dimensions of the outdoor unit (Unit:mm)
Fixing of outdoor unit
Fix the unit to concrete or block with bolts(
10mm) and nuts firmly and horizontally.
When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails or wires in consideration of earthquake and strong wind.
If vibration may affect the house, fix the unit by attaching a vibration-proof mat.
Indoor Unit |
Selection of Installation Place Outdoor Unit |
Place, robust not causing vibration, where the body can be supported sufficiently.
Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed.
Place, possible to drain easily, where piping can be connected with the outdoor unit.
Place, where cold air can be spread in a room entirely.
Place, nearby a power receptacle, with enough space around. (Refer to drawings).
Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps can be left.
In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened.
Place, which is less affected by rain or direct sunlight and is sufficiently ventilated.
Place, possible to bear the unit, where vibration and noise are not increased.
Place, where discharged wind and noise do not cause a nuisance to the neighbors.
Place, where a distance marked
is available as illustrated in the above figure.
Power Source
Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.
Install an exclusive branch circuit of the power.
A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.
Selection of pipe
To this unit, both liquid and gas pipes shall be insulated |
|
|
as they become Iow temperature in operation. |
|
|
Use optional parts for piping set or pipes covered with |
|
|
equivalent insulation material. |
Liquid pipe( ) |
6.35mm(1/4") |
The thickness of the pipe must be 0.8 mm at least.
Gas pipe( ) |
9.52mm(3/8") |
2
Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
2.Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail.
3.Find the wall hole location A using a measuring tape
A=80mm |
35 |
|
Fit the level line
70mm |
70mm |
120mm
For the units with fresh air function
When the mounting plate is fixed side bar and lintel
Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten the plate to the fixed mounting bar.
Refer to the previous article, " When the mounting plate is first fixed ", for the position of wall hole.
2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 70 mm in diameter, slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation
Indoor side |
Outdoor side |
Wall hole |
Thickness |
70mm |
of wall |
|
(Section of wall hole) G Piping hole pipe
3.Installation of the Indoor Unit
Drawing of pipe
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials.
3