Installation
Template
Hanger
Special nut A
(large flange)
Special nut B
(large flange)
Coupler heat
insulation
(large)
Coupler heat
insulation
(small)
Nylon fastener
Auxiliary pipe
assembly
Drain hose
insulation
Indoor capillary tube
BR sheet
STANDARD PARTS
The following installation parts are furnished. Use them as
required.
INDOOR UNIT ACCESSORIES
Name and Shape Q’ty Application
1
4
4
4
2
1
1
1
1
1
2
For positioning the
indoor unit
For suspending the
indoor unit from ceiling
For suspending the
indoor unit from ceiling
For indoor side pipe joint
(large pipe)
For indoor side pipe joint
(small pipe)
For fixing the drain hose
For wiring conduit
(gas side) connection
Insulates the drain hose
and vinyl hose
connection
(This part is enclosed with
the 30,000 and 36,000 •
25,000 BTU/h versions.)
65 × 130 × T5
(This part is enclosed with
the 30,000 and 36,000 •
25,000 BTU/h versions.)
CONNECTION PIPE REQUIREMENT
Small Large
Diameter
45,000 BTU/h class 9.52 mm 19.05 mm
36,000 BTU/h class 9.52 mm 19.05 mm
30,000 BTU/h class 9.52 mm 15.88 mm
25,000 BTU/h class 9.52 mm 15.88 mm
ELECTRICAL REQUIREMENT
Table 1
• Use 0.7 mm to 1.2 mm thick pipe.
• Use pipe with water-resistant heat insulation.
• Use pipe that can withstand a pressure of 3,040 kPa.
MAX
MIN
Connection cord
(mm
2
)
2.5
1.5
••
••
•
Always use H07RN-F or equivalent to the connection cord.
••
••
•
Install the disconnection device with a contact gap of at least
3 mm nearby the units. (Both indoor unit and outdoor unit)
Table 2
Duct Type
This air conditioner uses new refrigerant HFC (R407C).
Right
side
Indoor unit
Strong and durable ceiling
Left
Fig. 1
side
WARNING
This mark indicates procedures which, if improperly performed, might lead to the death or serious
injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal
harm to the user, or damage to property.
6" (15 cm)
or more
12" (30 cm)
or more
unit and the ceiling will make work much easier.
(4) Install the unit where the drain pipe can be easily installed.
(5) Providing as much space as possible between the indoor
R407C
Refrigerant
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION SHEET
WARNING!
For authorized service personnel only.
(PART NO. 9363065022)
CAUTION!
set available from our standard parts.
only.
standard parts. This installation instruction sheet describes the correct connections using the installation
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available
with a flame, it produces a toxic gas.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel
4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact
5 Do not turn on the power until all installation work is complete.
serviced or moved.
• Be careful not to scratch the air conditioner when handling it.
• After installation, explain correct operation to the customer, using the operating manual.
• Let the customer keep this installation instruction sheet because it is used when the air conditioner is
SELECTING THE
MOUNTING POSITION
Decide the mounting position with the customer as follows:
so that it withstand against the weight of the indoor unit.
should be able to blow all over the room.
INDOOR UNIT
(1) Install the indoor unit on a place having a sufficient strength
(Fig.1).
(2) The inlet and outlet ports should not be obstructed; the air
(3) Leave the space required to service the air conditioner
Hanger
Ceiling
Pass the unit hangers over the bolts installed to the ceiling
and install the unit with the special nut B.
• Install the unit
Fig. 11
Special nut B
(60 to 70 mm)
2-3/8" to 2-3/4"
∅1/2" (1.27 mm)
Fig. 8
CAUTION
Ceiling
Ceiling
4. LEVELING
Base horizontal direction leveling on top of the unit.
Fig. 12
Level
Base vertical direction leveling on the unit (right and left).
Fig. 13
Level
Inlet
Outlet
air
air
5. SERVICE HOLE DIMENSIONS
It shall be possible to install and remove the control box metal.
Fig. 14
AIR
Unit: (mm)
Reference B
CAUTION
Service hole
200
Reference
A
Control box metal
500
Outlet air
50
500 mm from 50 mm below reference A
500 mm from 200 mm from the left from reference B
500
• Vertical dimension
• Horizontal dimension
Inlet air
the unit. Mark the bolt positions from the installation template.
With a concrete drill, drill
for 1/2" (12.7 mm) dia.
Fasten the unit securely with special nuts A and B.
3. INSTALLING THE HANGERS
Installation method (1)
• Install the bolts to the ceiling at a place strong enough to hang
Installation method (2)
A and B.
• Fasten the hanging bolts to the ceiling and install special nuts
Fig. 4
holes (Fig. 8).
Hanging bolt
Special nut A
Special nut B
• Install the hangers to the unit.
completely into the anchor bolts with a hammer.
• Insert the anchor bolts into the drilled holes, and drive the pins
Hanger
Fig. 5
Fig. 9
AIR
CAUTION
Left side
When fastening the hangers, make the bolt
positions uniform.
• Install the hangers to the unit.
Fig. 10
Outlet air
Left side
(Fig. 1)
(Example)
Hanger
Inlet air
Right side
(Fig. 1)
Left side
Left side
(Fig. 1)
When fastening the hangers, make the bolt
positions uniform.
(Example)
Unit
Hanger
Hanger bolt
• Hang the unit.
(1) Pass the hanging bolts through the hangers. (Four places)
Fig. 6
(2) Slide the unit in the arrow direction and fasten it.
Right side
Hanging bolt
Hanger
Fig. 7
(Fig. 1)
Special nut A
Special nut B
Front Outlet
INDOOR UNIT
INSTALLATION
INSTALLATION PROCEDURE
Install the air conditioner as follows:
1
Auxiliary pipe assembly
To top
PREPARATION
1. PIPING CONNECTION DIRECTION AND
• Select piping directions (Fig. 2).
Fig. 2
To side
To rear
To bottom
assembly.
• When bending the piping is difficult, use the auxiliary pipe
Drilling
position
for bolts
Installation template
INSTALLING THE BOLTS
(Fig. 3).
2. DRILLING HOLES FOR BOLTS AND
• Using the installation template, drill holes for bolts (four holes)
Fig. 3
Brazing (all around)
Fig. 21
Indoor
Indoor
unit side
unit side
Connection
pipe
Indoor capillary tube Indoor capillary tube
Connection
pipe
Outdoor unit side
Branch liquid pipe
Fig. 22
BR sheet
Connection
Coupler heat
insulation (large)
pipe
on the pipe
Indoor
capillary tube
Branch liquid pipe
Large pipe
Fig. 23
Tape
Binder
Tape
Fig. 24
Reference A
FOR GAS LEAKING
4. CHECKING THE PIPE CONNECTIONS
For both the indoor and outdoor unit sides, check the joints for
gas leaking by the use of a gas leakage detector without fail when
the pipes are connected.
Pipe
Cutter
Heat insulating
pipe
Fig. 17
where connecting pipes.
5. HEAT INSULATION ON THE PIPE JOINTS
insulation (large) to the pipe at the two places shown below.
• Stick coupler heat insulation (large and small) to the place
• When using auxiliary piping with large pipe, stick coupler heat
Fig. 20
Cut line
CAUTION
Be sure to apply the pipe against the port on the
When bending the pipe, do not
bend it as is. The pipe will be
collapsed. In this case, cut the
heat insulating pipe with a
sharp cutter as shown in Fig.
17, and bend it after exposing
the pipe. After bending the pipe
as you want, be sure to put the
heat insulating pipe back on
the pipe, and secure it with
tape.
3. CONNECTION PIPES
Detach the caps and plugs from the pipes.
indoor unit correctly. If the centering is
Front outlet
Coupler heat
CAUTION
improper, the flare nut cannot be tightened
smoothly. If the flare nut is forced to turn, the
threads will be damaged.
Centering the pipe against port on the indoor unit, turn the
flare nut with your hand.
Small pipe
Cover this portion with heat
insulating material also without fail.
Heat insulating pipe
CAUTION
No gap should remain.
insulation (small)
on the pipe
90˚
Torque wrench
Hold the torque wrench at its grip, keeping it in
the right angle with the pipe as shown in Fig. 19,
in order to tighten the flare nut correctly.
When the flare nut is tightened properly by your hand, use a
torque wrench to finally tighten it.
Fig. 18 Fig. 19
TUBE
versions.
6. CONNECTING AN INDOOR CAPILLARY
These instructions refer to the 25,000 • 30,000 and 36,000 BTU/h
Table 4 : Flare nut tightening torque
Pipe Tightening torque
branch liquid pipe) as shown in Fig. 21.
shown in Fig. 22.
with insulation (Fig. 23) and affix the insulation with tape.
Installation Procedure
(1) Braze each part (connection pipe, indoor capillary tube, and
(2) Wrap the two BR sheets around the indoor capillary tube as
(3) Cover the indoor capillary tube and the branch liquid pipe
•cm (73.5 to 78.4 N•m)
750 to 800 kgf
Large pipe
Large pipe
(9.52 mm dia.)
(15.88 mm dia.)
•cm (78.4 to 98 N•m)
800 to 1,000 kgf
•cm (30.4 to 34.3 N•m)
310 to 350 kgf
Small pipe
instruction sheet for the outdoor unit for details.
(4) Secure the insulation using the binders (Fig. 24).
• If the joint pipe must be installed, refer to the installation
CAUTION
(19.05 mm dia.)
Be sure to connect the large pipe after
connecting the small pipe completely.
CAUTION
CONNECTING THE PIPING
2
the units.
previous installations. Only use parts which
are delivered with the unit.
Prevent mineral oil from getting into the
system as this would reduce the lifetime of
1 Do not use mineral oil on flared part.
2 Never use piping which has been used for
nitrogen gas through them.
3 While welding the pipes, be sure to blow dry
Small (width across flats 22 mm)
Table 3
is not deformed.
the pipe and remove the burrs.
unit and assemble as shown in (Table 3) and insert the
flare nut onto the pipe, and flare with a flaring tool.
1. FLARE PROCESSING
(1) Cut the connection pipe with pipe cutters so that the pipe
(2) Holding the pipe downwards so that cuttings cannot enter
and that there are no cracks.
(3) Remove the flare nut from the indoor unit pipe and outdoor
(4) Check if the flared part “L” (Fig. 5) is spread uniformly
Large (width across flats 27 mm)
Pipe Flare nut
Small pipe (9.52 mm dia.)
Large pipe (15.88 mm dia.)
L dimension
Small pipe (9.52 mm dia.)
1.8 to 2.0 mm
Large pipe (15.88 mm dia.)
2.2 to 2.4 mm
Large pipe (19.05 mm dia.)
2.6 to 3.0 mm
Large (width across flats 36 mm)
Width across flats
Large pipe (19.05 mm dia.)
Fig. 15
NO
by unwinding it.
Extend the pipe
OK
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bent or stretched, the material will
harden, making it difficult to bend or stretch them any more.
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse
them.
Fig. 16
Do not bend or stretch the pipes more than three times.