MODEL :
AR 18LUAD / AO 18LMAKL
AR 18LUAL / AO 18LMAKL
AR 24LUAN / AO 24LMAKL
DUCT TYPE
AR18 - AR24L
FEATURES
Installation styles (AR 24L)
DUCT TYPE
AR18 - AR24L
Embedded in Ceiling
Hanging from Ceiling
Universal design indoor unit (AR 18L)
Since vertical and horizontal installation is possible, and the intake direction can also be selected
from two directions, flexible installation is possible.
Ceiling concealedFloor concealed
Low static pressure mode function (AR 24L)
1. Low static pressure mode 1 air volume at 70Pa (fan speed:high)
2. Normal Mode Air volume at 100Pa (fan speed:high)
230V
/h)
3
12
When installed, normal middle static pressure mode, and low static
pressure mode can be selected by switching over using DIP switch
on the board in the control box. Therefore, these models can be
operated under the wide range of conditions.
Slim & compact design (AR 24L)
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape
is now united with main unit (DIP Switch is
located on the internal substrate.)
One-touch operating and easy-to-install
long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further
compactification is attained by reducing 65 mm from the width with the
flanking control box embedded inside the chassis.
Air volume (m
070100
Static pressure (Pa)
- (02 - 01) -
EASY MAINTENANCE (AR 24L)
In the case of rear suction type, as seen from lower rear part.
DUCT TYPE
AR18 - AR24L
Conventional model
1
3
4
New model
4
1
1. Control box
2. Fan casing
3. Fan
4. Motor
2
2
3
Bottom panel: 2 units
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and
rear, and the internal fan casing is also made dismountable in two pieces namely,
upper and lower ones.
The motor and fan maintenance and dismounting can be made easily by removing
the rear panel and lower part of the casing with the main chassis installed.
DUCT TYPE
AR18 - AR24L
- (02 - 02) -
2-2. REMOTE CONTROLLER
2-2-1. WIRED REMOTE CONTROLLER
DUCT TYPE
AR18 - AR24L
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in
one unit.
controller
Built-in timers
Wired
remote
Weekly
timer
Setback timerWeekly timer
Setback
timer
DUCT TYPE
AR18 - AR24L
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen
after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
Timer
area
Operation
area
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
24°C
0 3 6 9 12 15 18 21 Time
28°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable
programming to match application.
- (02 - 03) -
European
switch box
JIS box
DUCT TYPE
AR18 - AR24L
FUNCTIONS
Display
2
7
8
9
10
11
12
Display panel
SET BACK
SUMOTUWETH FR
3 6 9
CLOCK ADJUST
DELETESET
12 15 18 21
DAY
DAY OFF
1
START/STOP button
Pressed to start and stop operation.
2
Set temperature button
SA
13
1
3
ENERGY
SAVE
THERMO
SENSOR
4
6
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
DUCT TYPE
AR18 - AR24L
Turns the energy efficient mode on and off.
6
5
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
Set back button
Pressed to select the set back timer.
14
SUMOTUWETH FR
3 6 9
DIMENSION
120
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETESET
3 6 9
SA
12 15 18 21
DAY
DAY OFF
12 15 18 21
ENERGY
SAVE
SA
THERMO
SENSOR
15
1617 18
1920
[ Unit : mm ]
120
10
Set time button
Pressed to select the set back timer.
11
Delete button
The schedule of a weekly timer is deleted.
12
Set button
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
17
Central control display
18
Temperature display
19
Standby display
Indicates during the oil recovery and defrosting operation.
20
Energy save display
Front View
SPECIFICATION
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT ( g )160
CABLE LENGTH ( m )
POWER ( V )
10
12
- (02 - 04) -
2-3. SPECIFICATIONS
AR 18LUAD
AR 18LUAL
AO 18LMAKLAO 24LMAKL
Fin Pitchmm
1.31.3
Fin Pitchmm
1.451.45
6.35 (1/4 inc.)9.52 (3/8 inc.)
12.70 (1/2 inc.)15.88 (5/8 inc.)
ABSSteel
Outer diameter 26.0
Inner diameter 21.5
Outer diameter 38.0
Inner diameter 36.0
DUCT TYPE
INVERTER HEAT PUMP TYPE
MODEL NAME
OUTDOOR
INDOOR
AR 24LUAN
TYPE
230V 50Hz
CAPACITY
COOLING
RATED / *MAX.
HEATING
RATED / *MAX.
AVAILABLE VOLTAGE RANGE
198 - 264V
EUROPEAN ENERGY LABEL
POWER SOURCE
INPUT POWER
kW
CURRENT
A
dB(A)
OUTDOOR
FAN MOTOR OUTPUT
W
fin
OUTDOOR
Coil
Copper tube
fin
Rows × Stages
Rows × Stages
Coil
COMPRESSOR
TYPE
Copper tube
DC TWIN ROTARY(INVERTER)
STARTING METHOD
Permanent Starting Condenser Method
INDOOR
FAN SPEED
HEAT
EXCHANGER
TYPE
INDOOR
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
INDOOR
STARTING CURRENT
kW/kW
MOISTURE REMOVAL
AIR
CIRCULATION
COP
OUTDOOR
m3/h
INDOOR
EER
OUTDOOR
r.p.m
Galvanized steel sheet
Beige (10YR7.5 / 1.0NN)
CASING COLOR
OUTPUT
RECOMMENDED STATIC PRESSURE
FAN TYPE × Q'ty
DIMENSIONS
(H × W × D)
NET
mm
GROSS
WEIGHT
NET /
GROSS
kg(lbs)
PIPE
CONNECTION METHOD
MAX. HEIGHT
FLARE
SIZE
mm
MAX. LENGTH
REFRIGERANT
TYPE
R410A
REFRIGERANT OIL
TYPE
Synthetic (POE oil)
OPERATION(OUTDOOR)
°C
0 to 43
-10 to 24
REMOTE CONTROLLER
DRAIN PIPE
MATERIAL
SIZE
DUCT TYPE
AR18 - AR24L
COOLINGRATED / *MAX.1.70 / 1.992.53 / 2.96
HEATINGRATED / *MAX.1.90 / 2.402.43 / 2.93
COOLINGRATED / *MAX. 7.4 / 8.811.1 / 12.9
HEATINGRATED / *MAX. 8.3 / 10.510.6 / 12.8
High8001490
Med6401340
Low5001200
High28002800
Low--
High1040980
Med890890
Low750810
High780780
Low400400
INDOORSirocco × 2Sirocco × 2
OUTDOORPropeller × 1Propeller × 1
INDOOR4570
OUTDOOR6565
High38.0 / 38.034.0 / 34.0
Med34.0 / 34.032.0 / 32.0
Low30.0 / 30.029.0 / 29.0
COOLINGBC
kW5.20 / 5.907.10 / 8.00
BTU/h17800 / 2010024200 / 27300
kW 6.20 / 7.508.00 / 9.00
BTU/h21200 / 2560027300 / 30700
A10.010.0
3.062.81
3.263.29
l/h (pints/h)1.7 (3.6)1.5 (3.2)
Pa 0 to 40 30 to 150
50.0 / 52.052.0 / 54.0
DUCT TYPE
AR18 - AR24L
W13001300
Hydrophilic coatingHydrophilic coating
3 × 14 2 × 14
Coil Dimensions mm
Coil Dimensions mm
INDOOR
OUTDOOR
INDOOR217 × 953 × 595270 × 1135 × 700
OUTDOOR 650 × 830 × 320 650 × 830 × 320
INDOOR324 × 1075 × 686300 × 1300 × 790
OUTDOOR 743 × 984 × 413 743 × 984 × 413
INDOOR25 / 29 (55 / 64)41 / 48 (90 /106)
OUTDOOR54 / 58 (119 / 128)54 / 58 (119 / 128)
LIQUID
GAS
m2525
m1515
CHARGEg15001800
COOLING
HEATING
294 × 700 × 39.9294 × 1000 × 26.6
Hydrophilic coatingHydrophilic coating
2 × 30 2 × 30
630 × 901 × 36.38630 × 901 × 36.38
WIRED (AR-3TA1)WIRED (AR-3TA1)
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB, and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB, and outdoor temperature of 7°CDB/6°CWB.
Standard static pressure : 0 Pa (AR 18LUAD, AR 18LUAL) 30Pa (AR 24LUAN)
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction port and measure.
*The maximum current and the maximum input value are the maximum values when operated within the operation (temperature) range.
mm
- (02 -05) -
2-4. DIMENSIONS
2-4-1. OUTDOOR UNIT
MODEL : AO 18L, AO 24L
DUCT TYPE
AR18 - AR24L
Top view
(Unit : mm)
DUCT TYPE
AR18 - AR24L
MOUNTING POSITION
When there are obstacles at the
back or front sides.
Front view
Bottom view
When there are obstacles at the
back, side(s), and top.
600 mm or more
Side view
When there are obstacles at the
back, side with the installation of
more than one unit.
AIR
600 mm
or more
100 mm
or more
100 mm
or more
AIR
- (02 - 06) -
250 mm or more
(Service space)
300 mm
or more
250 mm
or more
AIR
250 mm
or more
300 mm
or more
2-4-2. INDOOR UNIT
MODEL : AR 18L
BRACKETS
DUCT TYPE
AR18 - AR24L
AIR FLOW OUTLET
DRAIN PORT
COUPLING PIPE ASSY
886
850
CONTROL BOX
(Unit : mm)
DUCT TYPE
AR18 - AR24L
390
953
920
600
150
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection
1
2
12
605
57520
150
85 75
364
194
217
3
- (02 - 07) -
MOUNTING POSITION
Strong and durable ceiling
Indoor unit
DUCT TYPE
AR18 - AR24L
Left
side
100mm
or more
Left
side
100mm
or more
Strong and durable floor
Right side
(PIPE side)
300mm
or more
300mm
or more
30mm
or more
Right
side
30mm
or more
DUCT TYPE
AR18 - AR24L
MAINTENANCE HOLE
Unit
100mm
or more
BOTTOM AIR INTAKE HOLE
Maintenance hole
Control box
300mm
or more
(Unit : mm)
- (02 - 08) -