General ARH18L, ARH18LUAD, AOH18LMAKL, ARH24L, ARH24LUAN Technical Manual

...
R410A
2.
DUCT TYPE :
AR 18LUAD, AR 24LUAN
AR 18LUAL
D2D_AR001E/06
2007.06.12
2-1. FEATURE
MODEL : AR 18LUAD / AO 18LMAKL AR 18LUAL / AO 18LMAKL AR 24LUAN / AO 24LMAKL
AR18 - AR24L
FEATURES
Installation styles (AR 24L)
AR18 - AR24L
Embedded in Ceiling
Hanging from Ceiling
Universal design indoor unit (AR 18L)
Since vertical and horizontal installation is possible, and the intake direction can also be selected from two directions, flexible installation is possible.
Ceiling concealed Floor concealed
Low static pressure mode function (AR 24L)
1. Low static pressure mode 1 air volume at 70Pa (fan speed:high)
2. Normal Mode Air volume at 100Pa (fan speed:high)
230V
/h)
3
1 2
When installed, normal middle static pressure mode, and low static pressure mode can be selected by switching over using DIP switch on the board in the control box. Therefore, these models can be operated under the wide range of conditions.
Slim & compact design (AR 24L)
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape is now united with main unit (DIP Switch is located on the internal substrate.)
One-touch operating and easy-to-install long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further compactification is attained by reducing 65 mm from the width with the flanking control box embedded inside the chassis.
Air volume (m
0 70 100
Static pressure (Pa)
- (02 - 01) -
EASY MAINTENANCE (AR 24L)
In the case of rear suction type, as seen from lower rear part.
AR18 - AR24L
Conventional model
1
3
4
New model
4
1
1. Control box
2. Fan casing
3. Fan
4. Motor
2
2
3
Bottom panel: 2 units
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and rear, and the internal fan casing is also made dismountable in two pieces namely, upper and lower ones. The motor and fan maintenance and dismounting can be made easily by removing the rear panel and lower part of the casing with the main chassis installed.
AR18 - AR24L
- (02 - 02) -
2-2. REMOTE CONTROLLER
2-2-1. WIRED REMOTE CONTROLLER
AR18 - AR24L
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.) Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible. Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in one unit.
controller
Built-in timers
Wired
remote
Weekly
timer
Setback timerWeekly timer
Setback
timer
AR18 - AR24L
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
Timer area
Operation area
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
24°C
0 3 6 9 12 15 18 21 Time
28°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable programming to match application.
- (02 - 03) -
European switch box
JIS box
AR18 - AR24L
FUNCTIONS
Display
2 7 8
9
10
11
12
Display panel
SET BACK
SUMOTUWETH FR
3 6 9
CLOCK ADJUST
DELETE SET
12 15 18 21
DAY
DAY OFF
1
START/STOP button
Pressed to start and stop operation.
2
Set temperature button
SA
13
1 3
ENERGY
SAVE
THERMO SENSOR
4
6
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
AR18 - AR24L
Turns the energy efficient mode on and off.
6
5
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
Set back button
Pressed to select the set back timer.
14
SUMOTUWETH FR
3 6 9
DIMENSION
120
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETE SET
3 6 9
SA
12 15 18 21
DAY
DAY OFF
12 15 18 21
ENERGY
SAVE
SA
THERMO SENSOR
15
1617 18
1920
[ Unit : mm ]
120
10
Set time button
Pressed to select the set back timer.
11
Delete button
The schedule of a weekly timer is deleted.
12
Set button
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
17
Central control display
18
Temperature display
19
Standby display Indicates during the oil recovery and defrosting operation.
20
Energy save display
Front View
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
- (02 - 04) -
2-3. SPECIFICATIONS
AR 18LUAD
AR 18LUAL
AO 18LMAKL AO 24LMAKL
Fin Pitch mm
1.3 1.3
Fin Pitch mm
1.45 1.45
6.35 (1/4 inc.) 9.52 (3/8 inc.)
12.70 (1/2 inc.) 15.88 (5/8 inc.)
ABS Steel
Outer diameter 26.0
Inner diameter 21.5
Outer diameter 38.0 Inner diameter 36.0
DUCT TYPE
INVERTER HEAT PUMP TYPE
MODEL NAME
OUTDOOR
INDOOR
AR 24LUAN
TYPE
230V 50Hz
CAPACITY
COOLING
RATED / *MAX.
HEATING
RATED / *MAX.
AVAILABLE VOLTAGE RANGE
198 - 264V
EUROPEAN ENERGY LABEL
POWER SOURCE
INPUT POWER
kW
CURRENT
A
dB(A)
OUTDOOR
FAN MOTOR OUTPUT
W
fin
OUTDOOR
Coil
Copper tube
fin
Rows × Stages
Rows × Stages
Coil
COMPRESSOR
TYPE
Copper tube
DC TWIN ROTARY(INVERTER)
STARTING METHOD
Permanent Starting Condenser Method
INDOOR
FAN SPEED
HEAT EXCHANGER TYPE
INDOOR
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
INDOOR
STARTING CURRENT
kW/kW
MOISTURE REMOVAL
AIR CIRCULATION
COP
OUTDOOR
m3/h
INDOOR
EER
OUTDOOR
r.p.m
Galvanized steel sheet
Beige (10YR7.5 / 1.0NN)
CASING COLOR OUTPUT
RECOMMENDED STATIC PRESSURE
FAN TYPE × Q'ty
DIMENSIONS (H × W × D) NET
mm
GROSS
WEIGHT
NET / GROSS
kg(lbs)
PIPE
CONNECTION METHOD
MAX. HEIGHT
FLARE
SIZE
mm
MAX. LENGTH
REFRIGERANT TYPE
R410A
REFRIGERANT OIL
TYPE
Synthetic (POE oil)
OPERATION(OUTDOOR)
°C
0 to 43
-10 to 24
REMOTE CONTROLLER
DRAIN PIPE MATERIAL
SIZE
AR18 - AR24L
COOLING RATED / *MAX. 1.70 / 1.99 2.53 / 2.96
HEATING RATED / *MAX. 1.90 / 2.40 2.43 / 2.93
COOLING RATED / *MAX. 7.4 / 8.8 11.1 / 12.9
HEATING RATED / *MAX. 8.3 / 10.5 10.6 / 12.8
High 800 1490
Med 640 1340
Low 500 1200
High 2800 2800
Low - -
High 1040 980
Med 890 890
Low 750 810
High 780 780
Low 400 400
INDOOR Sirocco × 2 Sirocco × 2
OUTDOOR Propeller × 1 Propeller × 1
INDOOR 45 70
OUTDOOR 65 65
High 38.0 / 38.0 34.0 / 34.0
Med 34.0 / 34.0 32.0 / 32.0
Low 30.0 / 30.0 29.0 / 29.0
COOLING B C
kW 5.20 / 5.90 7.10 / 8.00
BTU/h 17800 / 20100 24200 / 27300
kW 6.20 / 7.50 8.00 / 9.00
BTU/h 21200 / 25600 27300 / 30700
A 10.0 10.0
3.06 2.81
3.26 3.29
l/h (pints/h) 1.7 (3.6) 1.5 (3.2)
Pa 0 to 40 30 to 150
50.0 / 52.0 52.0 / 54.0
AR18 - AR24L
W 1300 1300
Hydrophilic coating Hydrophilic coating
3 × 14 2 × 14
Coil Dimensions mm
Coil Dimensions mm
INDOOR
OUTDOOR
INDOOR 217 × 953 × 595 270 × 1135 × 700
OUTDOOR 650 × 830 × 320 650 × 830 × 320
INDOOR 324 × 1075 × 686 300 × 1300 × 790
OUTDOOR 743 × 984 × 413 743 × 984 × 413
INDOOR 25 / 29 (55 / 64) 41 / 48 (90 /106)
OUTDOOR 54 / 58 (119 / 128) 54 / 58 (119 / 128)
LIQUID
GAS
m 25 25
m 15 15
CHARGE g 1500 1800
COOLING
HEATING
294 × 700 × 39.9 294 × 1000 × 26.6
Hydrophilic coating Hydrophilic coating
2 × 30 2 × 30
630 × 901 × 36.38 630 × 901 × 36.38
WIRED (AR-3TA1) WIRED (AR-3TA1)
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27°CDB/19°CWB, and outdoor temperature of 35°CDB/24°CWB. Heating : Indoor temperature of 20°CDB/15°CWB, and outdoor temperature of 7°CDB/6°CWB. Standard static pressure : 0 Pa (AR 18LUAD, AR 18LUAL) 30Pa (AR 24LUAN) Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction port and measure. *The maximum current and the maximum input value are the maximum values when operated within the operation (temperature) range.
mm
- (02 -05) -
2-4. DIMENSIONS
2-4-1. OUTDOOR UNIT
MODEL : AO 18L, AO 24L
AR18 - AR24L
Top view
(Unit : mm)
AR18 - AR24L
MOUNTING POSITION
When there are obstacles at the back or front sides.
Front view
Bottom view
When there are obstacles at the back, side(s), and top.
600 mm or more
Side view
When there are obstacles at the back, side with the installation of more than one unit.
AIR
600 mm or more
100 mm or more
100 mm or more
AIR
- (02 - 06) -
250 mm or more
(Service space)
300 mm or more
250 mm or more
AIR
250 mm or more
300 mm or more
2-4-2. INDOOR UNIT
MODEL : AR 18L
BRACKETS
AR18 - AR24L
AIR FLOW OUTLET
DRAIN PORT
COUPLING PIPE ASSY
886 850
CONTROL BOX
(Unit : mm)
AR18 - AR24L
390
953
920
600
150
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection
1 2
12
605 57520
150
85 75
364
194
217
3
- (02 - 07) -
MOUNTING POSITION
Strong and durable ceiling
Indoor unit
AR18 - AR24L
Left side
100mm or more
Left side
100mm or more
Strong and durable floor
Right side (PIPE side)
300mm
or more
300mm or more
30mm
or more
Right side
30mm
or more
AR18 - AR24L
MAINTENANCE HOLE
Unit
100mm
or more
BOTTOM AIR INTAKE HOLE
Maintenance hole
Control box
300mm or more
(Unit : mm)
- (02 - 08) -