Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 0 Pa
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction port and measure.
*The maximum current and the maximum input value are the maximum values when operated within the operation (temperature) range.
°C
%RH
mm
01-01
DUCTED MODEL
AR A18LATN
230V 50Hz
198-264V 50Hz
Pipe typeCopper
6.35 ( 1 / 4 in.)
12.70 ( 1 / 2 in.)
Type
Model name
mm
Rated
Min-Max
Rated
Min-Max
Rated
Min-Max
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
kW/kW
Input power
Cooling
kW
Heating
Rated
Min-Max
Current
Cooling
A
Rated
Max
Rated
Max
Heating
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
mm
Weight
m3/h
Fan
Dimensions
( H × W × D )
mm
Airflow
rate
Enclosure
Heat exchanger type
Sound pressure level
dB(A)
Remote controller type
Drain pipe
Material
Size
Operation range
Cooling
kg(lb.)
Connection pipe
Size
INVERTER HEATPUMP
CoolingA
HeatingA
kW5.2
BTU/h17700
kW0.9 - 5.9
BTU/h3100 - 20100
kW6.0
BTU/h20500
kW0.9 - 7.5
BTU/h3100 - 25600
1.62
0.09 - 1.80
1.66
0.09 - 2.46
7.1
9.0
7.3
10.8
EER3.21
COP3.61
l/h (pints/h)2.0 ( 3.5 )
High820
Med720
Low610
Quiet550
High820
Med720
Low610
Quiet550
Type × Q'tySirocco × 2
Motor outputW60
Recommended static pressurePa0 to 90
High33
Med31
Low29
Quiet27
High33
Med31
Low29
Quiet27
Dimensions (H × W × D)294 × 700 × 39.9
Fin pich1.30
Rows x Stages3 × 14
Fin type Aluminium
MaterialSteel
Colour
Net217 × 953 × 595
Gross324 × 1075 × 686
Net23 ( 51 )
Gross27 ( 60 )
Liquid
Gas
MethodFlare
°C18 to 32
%RH 80 or less
Heating°C30 or less
mmOuter diameter: 26.0 / Inner diameter: 21.5
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 0 Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
-
Wired
PS
01-02
DUCTED MODEL
AR A24LATN
230V 50Hz
198-264V 50Hz
Pipe typeCopper
6.35 ( 1 / 4 in.)
15.88 ( 5 / 8 in.)
Type
Model name
mm
Rated
Min-Max
Rated
Min-Max
Rated
Min-Max
Power source
Available voltage range
Capacity
Cooling
Heating
European energy label
kW/kW
Input power
Cooling
kW
Heating
Rated
Min-Max
Current
Cooling
A
Rated
Max
Rated
Max
Heating
Cooling
Heating
Heating
Cooling
Moisture removal
Cooling
Heating
mm
Weight
m3/h
Fan
Dimensions
( H × W × D )
mm
Airflow
rate
Enclosure
Heat exchanger type
Sound pressure level
dB(A)
Remote controller type
Drain pipe
Material
Size
Operation range
Cooling
kg(lb.)
Connection pipe
Size
INVERTER HEATPUMP
CoolingA
HeatingA
kW7.1
BTU/h24200
kW0.9 - 8.0
BTU/h3100 - 27300
kW8.0
BTU/h27300
kW0.9 - 9.1
BTU/h3100 - 31000
2.21
0.09 - 2.62
2.21
0.09 - 2.77
9.7
11.5
9.7
12.2
EER3.21
COP3.61
l/h (pints/h)2.5 (4.4)
High1100
Med950
Low800
Quiet600
High1100
Med950
Low800
Quiet600
Type × Q'tySirocco × 2
Motor outputW115
Recommended static pressurePa30 to 150
High31
Med29
Low27
Quiet25
High31
Med29
Low27
Quiet25
Dimensions (H × W × D)294 × 1000 × 39.9
Fin pich1.40
Rows x Stages3 × 14
Fin type Aluminium
MaterialSteel
Colour
Net270 × 1135 × 700
Gross300 × 1300 × 790
Net38 ( 84 )
Gross45 ( 99 )
Liquid
Gas
MethodFlare
°C18 to 32
%RH 80 or less
Heating°C30 or less
mmOuter diameter: 38.0 / Inner diameter: 36.0
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 30 Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 30Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Sound pressure level : Install a 2m duct to the outlet port and a 1m duct to the suction poit and measure.
*The maximum current and the maximum input value are the maximum values when operated within the operation (temperature) range.
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
01-06
AO A36LATLAO A45LATL
A15.015.0
1260 × 900 × 36.4
1260 × 900 × 36.4
Colour
Net
Gross
Motor output
Type
Charge
Type
Material
Motor output
Cooling
Heating
Dimensions (H × W × D)
Type
Model name
Power source
Available voltage range
1290 × 900 × 330
98 (216)
107 (236)
15.88 ( 5/8 in.)
Flare
-15 to 46
-15 to 24
1430 × 1050 × 445
9.52 ( 3/8 in.)
Copper
Aluminium
Steel sheet
Beige (10YR7.5/1.0NN)
Twin Rotary × 1
3750
R410A
POE
3350
INVERTER HEATPUMP
230V 50Hz
198-264V 50Hz
Propeller × 2
m
Connection pipe
Size
mm
Liquid
Gas
Method
Max. length
Max. height difference
Compressor
Refrigerant
Sound pressure level
Starting current
Cooling
Heating
Type × Q'ty
Refrigerant oil
Enclosure
Heat exchanger type
Fin pitch
Rows x Stages
Pipe type
Fin type
Type × Q'ty
mm
Weight
kg(lb.)
Dimensions
(H × W × D)
Net
Gross
°C
Operation range
Fan
Airflow
rate
m3/h
dB(A)
mm
Cooling
Heating
66006600
66006600
W103 × 2103 × 2
5455
5556
1.301.30
2 × 602 × 60
W
g
50 (chargeless : 20)50 (chargeless : 20)
3030
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
01-07
DUCT type
R410A
INVERTER
2 . DIMENSIONS
2. DIMENSIONS
MODEL : AR*A12LATN / AO*A12LACL
AR*A14LATN / AO*A14LACL
886
850
390
(Unit : mm)
1
2
Top view
953
920
600
150
Front view
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection
150
85 75
12
595
57520
364
Side view
194
217
3
Front view
Air flow
(Unit : mm)
Side view
Bottom view
02-01
MODEL : AR*A18LATN / AO*A18LACL
886
850
390
1
2
Top view
(Unit : mm)
953
920
600
150
Front view
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection
150
85 75
Side view
364
12
595
57520
194
217
3
(Unit : mm)
Front view
Air flow
Bottom view
Side view
02-02
MODEL : AR*A24LATN / AO*A24LACL
Front view
(Unit : mm)
Side view (L)
Front view
Top view
Rear view
Side view (R)
Refrigerant piping flare connection (Gas)
Refrigerant piping flare connection (Liquid)
Drain piping connection
Drain piping connection with cap.
Knock out hole for fresh air.
(Unit : mm)
Side view
Air flow
Bottom view
02-03
MODEL : AR*A36LATN / AO*A36LATL
AR*A45LATN / AO*A45LATL
Front view
(Unit : mm)
Side view (L)
Top view
Rear view
900
1290
7731
12330
Side view (R)
Refrigerant piping flare connection (Gas)
Refrigerant piping flare connection (Liquid)
Drain piping connection
Drain piping connection with cap.
Knock out hole for fresh air.
(Unit : mm)
21
370
Drain cap mounting
places
9
Front view
650
Air flow
Bottom view
4-Ø12mm hole
02-04
400
Side view
151
170
196
99
DUCT type
R410A
INVERTER
3 . REFRIGERANT SYSTEM DIAGRAM
3. REFRIGERANT CIRCUIT
MODEL : AR*A12LATN / AO*A12LACL
Outdoor UnitIndoor Unit
MUFFLER
THHM
MUFFLER
Refrigerant Pipe
Ø9.52mm(3/8")
3-way
VALVE
4-Way
valve
THD
CONDENSEREVAPOLATOR
THC
ACCUMULATOR
COMPRESSOR
THO
THHO
THC
THD
THHM
THHO
THO
EXPANSION
VALVE
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
STRAINERSTRAINER
2-way
VALVE
Refrigerant Pipe
Ø6.35mm(1/4")
THR
THPI
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL
HEAT
03-01
MODEL : AR*A14LATN / AO*A14LACL
AR*A18LATN / AO*A18LACL
Outdoor UnitIndoor Unit
MUFFLER
THHM
MUFFLER
Refrigerant Pipe
Ø12.7mm(1/2")
3-way
VALVE
4-Way
valve
THD
CONDENSEREVAPOLATOR
THC
ACCUMULATOR
COMPRESSOR
THO
THHO
THC
THD
THHM
THHO
THO
EXPANSION
VALVE
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
STRAINERSTRAINER
2-way
VALVE
Refrigerant Pipe
Ø6.35mm(1/4")
THR
THPI
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL
HEAT
03-02
MODEL : AR*A24LATN / AO*A24LACL
Outdoor UnitIndoor Unit
MUFFLER
THHM
MUFFLER
Refrigerant Pipe
Ø15.88mm(5/8")
3-way
VALVE
4-Way
valve
THD
CONDENSEREVAPOLATOR
THC
ACCUMULATOR
COMPRESSOR
THO
THHO
THC
THD
THHM
THHO
THO
EXPANSION
VALVE
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
STRAINERSTRAINER
2-way
VALVE
Refrigerant Pipe
Ø6.35mm(1/4")
THR
THPI
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL
HEAT
03-03
MODEL : AR*30/ 36LUAN / AO*30/ 36LMAWL
Outdoor UnitIndoor Unit
THHM
HIGH PRESSURE
SWITCH
PRESSURE
CHECK VALVE
STRAINER
Refrigerant Pipe
Ø15.88mm(5/8")
Charging Valve
4-Way
CONDENSER
THD
valve
MUFFLER
THC
ACCUMULATOR
EVAPOLATOR
COMPRESSOR
THO
THR
THHO
EXPANSION
THPI
VALVE
STRAINER
STRAINER
Refrigerant Pipe
Ø9.52mm(3/8")
Charging Valve
THC
THD
THHM
THHO
THO
THERMISTOR(COMPRESSOR TEMP.)
THERMISTOR(DISCHARGE TEMP.)
THERMISTOR(HEAT EXCHANGER MED TEMP.)
THERMISTOR(HEAT EXCHANGER OUT TEMP.)
THERMISTOR(OUTDOOR TEMP.)
THR
THERMISTOR(ROOM TEMP.)
THPI
THERMISTOR(PIPE TEMP.)
COOL
HEAT
03-04
DUCT type
R410A
INVERTER
4 . CIRCUIT DIAGRAM
4. CIRCUIT DIAGRAM
MODEL : AR*A12/ 14/ 18LATN
04-01
MODEL : AR*A24/ 36/ 45LATN
COIL
04-02
MODEL : AO*A12/ 14/ 18/ 24LACL
04-03
MODEL : AO*A36/ 45LATL
04-04
DUCT type
R410A
INVERTER
5 . DESCRIPTION OF EACH
CONTROL OPERATION
5-1. COOLING OPERATION
5-1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2 degC higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5 degC lower than a set temperature, the compressor will be stopped.
* When the room temperature is between +2 degC to -2.5 degC of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outdoor air
temperature
34°C
30°C
19°C
10°C
0°C
A zone
B zone
C zone
D zone
E zone
F zone
When the room
temperature drops
minimum
frequency
18Hz
18Hz
18Hz70Hz
18Hz77Hz
maximum
frequency
113Hz
113Hz
When the room
temperature rises
36°C
32°C
21°C
12°C
2°C
80Hz
Fan speed mode
AR*A12LATN
AR*A14LATN
AR*A18LATN
AR*A24LATN
AR*A36LATN
AR*A45LATN
HiMeLoQuiet
A zone80Hz
B zone
C zone
D-F zone
A zone
B zone
C zone
D-F zone
A zone
B zone
C zone
D-F zone
A zone
B zone
C zone
D-F zone
A zone
B zone
C zone
D-F zone
A zone
B zone
C zone
D-F zone
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower 3 degC than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is higher 2.5 degC than a set temperature, the compressor
will be stopped.
* When the room temperature is between +2.5 degC to -3 degC of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on
the outdoor temperature.
The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Fig 3.