GE Industrial Solutions Power Break II Undervoltage Release User Manual

g
GEH–6285C
Power Break® II Circuit Breaker Accessories
Undervoltage Release
Introduction
The Undervoltage Release (UVR) accessory, shown in Figure 1, can be installed in 800–4000 ampere frame Power Break® II circuit breakers. This accessory trips the circuit breaker when the input control voltage drops to 35–60% of its rated value and prevents an open breaker from closing until the input control voltage is greater than 8 0% of the rated value.
In addition to providing a trip signal to the breaker, the UVR accessory can be set up to interact with other Power Break II accessories, when used with a MicroVersaTrip Plus™ or MicroVersaTrip PM™ Trip Unit. DIP switches on the rear of the breaker Trip Unit can configure the UVR accessory to activate a Bell Alarm–Alarm Only accessory or a Bell Alarm with Lockout accessory when a UVR trip occurs. The Accessory Configuration section below describes how this can be done. If the breaker is equipped with a Power+™ Trip Unit, it is configured so that only protection trips will activate a Bell Alarm–Alarm Only or Bell Alarm with Lockout.
The catalog numbers for the UVR for various voltage applications are listed in Table 1.
Catalog
Number
SPUV012DC 12 Vdc 19 300
SPUV024DC 24 Vdc 15 140
SPUV048DC 48 Vdc 7.5 70
SPUV125DC 125 Vdc 3 30
SPUV250DC 250 Vdc 1.5 15
SPUV024AC 24 Vac 15 370
SPUV048AC 48 Vac 7.5 210
SPUV120AC 120 Vac 3 80
SPUV208AC 208 Vac 1.9 60
SPUV240AC 240 Vac 1.5 45
24–240 Vac devices are rated for 50/60 Hz.
Peak inrush current is present for 2–6 ms after activation. This number is provided so that fuses and supplies can be chosen appropriately.
Table 1. Catalog numbers and voltages for the Undervoltage Release.
Voltage
Rating
Peak Inrush
Current, A
Nominal RMS
Current, mA
Installation
Figure 1. Undervoltage Release.
Operation
Apply control voltage to terminals 29 and 30 of the terminal strip on the right side of the breaker. When the applied control voltage is above 80% of the UVR’s rated value, the breaker can be closed. When the voltage drops to 35–60% of the rated value, the UVR will trip the breaker.
WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the charging springs.
AVERTISSEMENT: Avant d’installer toute accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation, et décharger les ressorts d’armement.
The Undervoltage Release is installed in the accessory compartment through the front of the circuit breaker in the position shown in Figure 2.
Figure 2. Accessory compartment on front of circuit breaker, with
Undervoltage Release slot indicated.
Use the following procedure to install the UVR accessory into the UVR slot in the accessory compartment of the circuit breaker:
1. Open the hinged door over the accessory compartment and Trip Unit.
2. To remove an existing accessory module, loosen the accessory locking screw and pull the module out with the Rating Plug Removal Tool (catalog number TRTOOL).
3. Insert the UVR accessory into th e proper slot, as illustrated in Figure 3. The UVR accessory is keyed for the correct slot in the accessory compartment. If the accessory cannot be fully seated in the compartment, check that the compartment position is correct.
Unit. If the breaker is equipped with a Power+ Trip Unit, the factory default settings, listed in Table 2, can not be changed.
The UVR accessory can be configured to activate the Bell Alarm–Alarm Only or Bell Alarm with Lockout accessories if a UVR trip occurs. The configuration can be changed by removing the Trip Unit from the breaker, setting the DIP switches on the rear of the Trip Unit, and reinstalling the Trip Unit. Figure 4 illustrates the Trip Unit read DIP switches and their functions. Table 2 lists the switch functions and the factory settings for each.
Figure 4. Accessory switch on the rear of the MicroVersaTrip Plus™ or
MicroVersaTrip PM™ Trip Unit, showing the factory settings (solid
part indicates that the switch is pushed in on that side).
Figure 3. Inserting the Undervoltage Release into the accessory
compartment.
4. Tighten the locking screw on the front of the accessory until it is snug (torque of 9 in-lb.)
CAUTION: Overtightening the locking screw may damage or distort the case of the accessory.
ATTENTION: Le serrage excessif de la vis de verrouillage peut déformer le boîtier d’accessoire.
5. If the breaker is equipped with a MicroVersaTrip Plus or MicroVersaTrip PM Trip Unit, the UVR accessory can be configured to activate installed Bell Alarm–Alarm Only or Bell Alarm with Lockout accessories when a UVR trip occurs, with the procedure described in the Accessory Configuration section.
6. Connect the control wiring for the UVR to terminals 29 and 3 0 a t the terminal block on the right side of the breaker.
7. Te st the UVR to ensure proper operation, according to the procedures below.
8. Reconnect power to the circuit breaker and any other accessories.
9. Close and lock or seal the door over the accessory compartment and Trip Unit to prevent unauthorized changes to Trip Unit settings and to keep contaminants out of empty accessory slots.
Accessory Configuration
Switch
1 Disabled
2 Disabled
3 Enabled
4 Disabled
5 Disabled
6 Enabled
Factory Setting Function
Shunt trip activates Bell Alarm–Alarm
Only
UVR trip activates Bell Alarm–Alarm
Only
Protection trip activates Bell
Alarm–Alarm Only
Shunt trip activates Bell Alarm with
Lockout
UVR trip activates Bell Alarm with
Lockout
Protection trip activates Bell Alarm
with Lockout
Table 2. Accessory switch settings, including the factory defaults.
This section only applies if Bell Alarm–Alarm Only or Bell Alarm with Lockout accessories are installed in the breaker, along with a MicroVersaTrip Plus or MicroVersaTrip PM Trip
Loading...
+ 2 hidden pages