GE Industrial Solutions Power Break I 800-2000 Frames 240-600 VAC User Manual

Page 1
g
Power Break® Circuit Breakers 800–2000 A Frames, 240–600 Vac
User’s Guide
GEH–4693D
Page 2
Page 3
WARNINGS
CAUTIONS
NOTES
GEH–4693D
WARNINGS, CAUTIONS, AND NOTES
AS USED IN THIS PUBLICATION
Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other conditions that could cause personal injury or death are present in this equipment or may be associated with its use.
Warning notices are also used for situations in which inattention or lack of equipment knowledge could cause either personal injury or damage to equipment.
Caution notices are used for situations in which equipment might be damaged if care is not taken.
Notes call attention to information that is especially significant to understanding and operating the equipment.
This document is based on information available at the time of its publication. While efforts have been made to ensure accuracy, the information contained herein does not cover all details or varia­tions in hardware and software, nor does it provide for every possible contingency in connection with installation, operation, and maintenance. Features may be described herein that are not pres­ent in all hardware and software systems. GE Industrial Systems assumes no obligation of notice t o holders of this document with respect to changes subsequently made.
GE Industrial Systems makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warrantees of merchantability or fitness for purpose shall apply.
The following are trademarks of GE Company:
Power Break®, MicroVersaTrip Plus™ , MicroVersaTrip PM™, MagneTrip™, MicroVersaTrip®
© 1998 GE Company
All Rights Reserved
Page 4
Power Break® Circuit Breakers
Table of Contents
Chapter 1. Receiving and Installation
1–1 Overview................................................................................................................................1
1–2 Receiving the Breaker ............................................................................................................. 1
Storage ............................................................................................................................ 1
1–3 Installation............................................................................................................................. 1
Bolted Electrical Connections............................................................................................ 1
Breaker Mounting............................................................................................................. 1
Chapter 2. Breaker Operation
2–1 Standard Features................................................................................................................... 3
2–2 Operating Instructions............................................................................................................ 3
Sequence of Operations..................................................................................................... 3
Operating Instructions for Manually Charged Breakers........................................................ 4
Operating Instructions for Electrically Charged Breakers .....................................................4
Wiring Notes .................................................................................................................... 5
Application Notes ............................................................................................................. 6
2–3 Trip Unit Setup ...................................................................................................................... 6
MicroVersaTrip® and MicroVersaTrip® RMS-9 Trip Units.................................................. 6
MagneTrip™ Trip Units.................................................................................................... 9
MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units............................................... 9
Chapter 3. Accessories
3–1 Introduction .........................................................................................................................10
3–2 Circuit Breaker Cover.............................................................................................................10
Breaker Cover Removal ....................................................................................................10
Breaker Cover Reassembly ................................................................................................11
3–3 Shunt Trip Device..................................................................................................................12
Mounting Plate Removal ..................................................................................................12
Shunt Trip Installation.....................................................................................................13
Mounting Plate Installation ..............................................................................................13
3–4 Undervoltage Release Device ..................................................................................................14
UVR Installation..............................................................................................................14
3–5 Blown-Fuse Trip Device..........................................................................................................15
Blown-Fuse Trip Device Installation...................................................................................16
3–6 Auxiliary Switch.....................................................................................................................16
Auxiliary Switch Installation .............................................................................................17
3–7 Remote Close Solenoid and Remote Charge Indication ............................................................18
3–8 Optional Features ..................................................................................................................18
Limited Close Access Button.............................................................................................18
Padlock Function.............................................................................................................19
Chapter 4. Maintenance
4–1 Inspections............................................................................................................................20
4–2 Lubrication...........................................................................................................................20
ii
Page 5
Power Break® Circuit Breakers
List of Figures and Tables
Figures
1. Circuit breaker with lifting straps in place. ............................................................................................... 1
2. Location of mounting bolt inserts on 800 A frame breakers ....................................................................... 1
3. Location of mounting bolt inserts on 1600–2000 A frame breakers............................................................. 2
4. Manually charged breaker. ..................................................................................................................... 3
5. Motor operator-charged breaker. ............................................................................................................ 3
6. Motor operator charged breaker with the top cover removed..................................................................... 3
7. Bell alarm wiring to prevent continuous cycling of the automatic charging mechanism. .............................. 5
8. Wiring for optional bell alarm lockout applications................................................................................... 5
9. Tap changer cards. ................................................................................................................................6
10. Cover and trip unit removed from the breaker ......................................................................................... 7
11. Neutral CT connection for four-wire ground fault..................................................................................... 7
12. Wiring diagram for MicroVersaTrip and MicroVersaTrip RMS-9 trip units with ground fault on a
top-fed four-wire load. ............................................................................................................................ 8
13. Wiring diagram for MicroVersaTrip and MicroVersaTrip RMS-9 trip units with ground fault on a
bottom-fed four-wire load. ...................................................................................................................... 8
14. Releasing the trip unit interlock to remove or install the trip unit............................................................... 8
15. Aligning the trip unit to the mounting plate. ........................................................................................... 9
16. Adjusting the settings on a MagneTrip trip unit........................................................................................ 9
17. 800 A frame electrically operated breaker................................................................................................10
18. 1600–2000 A frame electrically operated breaker. ....................................................................................11
19. 1600–2000 A frame electrically operated breaker with the outer cover removed..........................................11
20. Wire ties on the accessory leads and mounring plate insulator. .................................................................11
21. Crossbar hook engaging the drive hook. .................................................................................................11
22. Shunt trip device with cut-off switch........................................................................................................12
23. Shunt trip wiring diagram. ....................................................................................................................12
24. Locations of the mounting plate retaining screws, isolation barrier, and molded drive crank.......................12
25. Shunt trip coil position with no blown-fuse trip device..............................................................................13
26. Shunt trip coil position with blown-fuse trip device. .................................................................................13
27. Attaching the switch bracket to the arm stop. ..........................................................................................13
28. Undervoltage release device...................................................................................................................14
29. Dropping resistor supplied with 240–600 V UVRs.....................................................................................14
30. UVR wiring diagram. ............................................................................................................................14
31. Slide reset lever and spring on the mounting plate...................................................................................15
32. Positioning the UVR assembly on the mounting plate..............................................................................15
33. Installing the UVR mounting screw. .......................................................................................................15
34. Blown-fuse trip device accessory..............................................................................................................15
35. Blown-fuse trip device wiring diagram.....................................................................................................16
36. Auxiliary switch. ...................................................................................................................................16
37. Auxiliary switch wiring diagram. ............................................................................................................17
iii
Page 6
Power Break® Circuit Breakers
List of Figures and Tables
38. Trip unit removed from the breaker. ......................................................................................................17
39. Installing the auxiliary switch assembly. ..................................................................................................17
40. Securing the auxiliary switch assembly. ...................................................................................................17
41. Wiring diagram for remote charge indication. ........................................................................................18
42. Wiring diagram for remote charge indication with remote close solenoid..................................................18
43. Limited close access button....................................................................................................................18
44. OFF button padlock with panel door interlock. .......................................................................................19
45. Defeating the OFF button padlock. ........................................................................................................19
Tables
1. Weights of the various breaker frame sizes, with and without a motor operator............................................ 1
2. Bolt sizes and mounting torques for bus connections. ............................................................................... 1
3. Sequence of operations that may be performed with Power Break circuit breakers....................................... 4
3. Application data for control power.......................................................................................................... 5
4. Accessory lead color codes .....................................................................................................................10
5. Shunt Trip electrical characteristics........................................................................................................12
6. UVR electrical characteristics.................................................................................................................14
7. Auxiliary switch electrical characteristics.................................................................................................17
8. Catalog numbers and ratings for the remote close solenoid ......................................................................18
iv
Page 7
Power Break® Circuit Breakers
Chapter 1. Receiving and Installation
1–1 Overview
The Power Break® line of insulated-case circuit breakers is designed to protect low-voltage power circuits and equipment. Current models are offered with Magne­Trip™, MicroVersaTrip Plus™, and MicroVersaTrip PM™ trip units for fault detection.
1–2 Receiving the Breaker
Unpack the circuit breaker and inspect it for shipping damage. Ensure that the breaker has the proper current, voltage, and interruption ratings for the application.
The weights of the various frame sizes are listed in Table 1, for reference. Figure 1 shows a breaker with straps for lifting.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
its operating handle.
Table 1. Weights of the various breaker frame sizes, with and
::
Do not attempt to lift the circuit breaker by
Frame
Rating, A Type Weight, lbs
800
1600
2000
Manual
Electric
Manual
Electric
Manual
Electric
without a motor operator.
50 64
82 96
88
102
condensation, preferably by storage in a warm, dry room. Circuit breakers for outdoor equipment should be stored in that equipment only when power is available and heat­ers are in operation, to prevent condensation.
The breaker should be stored in a clean location, free from corrosive gases or fumes. In particular, protect the breaker from moisture and cement dust, as that combina­tion may be corrosive.
If the breaker is stored for any length of time, it should be inspected periodically to ensure good mechanical condi­tion.
1–3 Installation
Bolted Electrical Connections
Using an industry-accepted solvent, remove any foreign material from the line and load strap surfaces and the corresponding surfaces of connecting bus and terminal studs. Ensure that the mating surfaces are smooth and free of burrs and nicks.
Place the bus connections in position and align the mounting holes. Insert and fasten the mounting bolts and washers according to the specifications in Table 2.
Bus Connection
Breaker Frame, A Bolt Dia. Torque, in-lbs
800 (1) 1/2 in 300
1200–1600 (2) 1/2 in 300
2000 (4) 1/2 in 300
Figure 1. Circuit breaker with lifting straps in place.
Storage
The breaker should be placed in service immediately in its permanent location. However, if it must be stored for an indefinite period, it should be carefully protected against
Table 2. Bolt sizes and mounting torques for bus connections.
Breaker Mounting
For mounting the circuit breaker, use the four 1/4-20 x 1/2­inch-deep inserts in the back of the breaker. The locations of the inserts are shown in Figures 2 and 3 for the two frame sizes. Tighten the mounting bolts to 50 in-lb.
Figure 2. Location of mounting bolt inserts on 800 A frame breakers.
1
Page 8
Power Break® Circuit Breakers
Chapter 1. Receiving and Installation
Figure 3. Location of mounting bolt inserts on 1600–2000 A frame
breakers.
2
Page 9
2–1 Standard Features
Power Break circuit breakers are equipped with the follow­ing standard features. The letters are keyed to the breaker illustrations in Figures 4, 5, and 6.
AAAAIndicator ON – Red
CHG (manual) – yellow CHARGED (electrical) – yellow OFF – Green
BB
BB
ON button
CC
CC
OFF button
DDDDManual charging handle
EEEELockable manual charge engagement button (motor
operated only)
FFFFTerminal board (motor operator drive unit)
GGGGRemovable protective window
JJJJCT tap setting indicator (MicroVersaTrip only)
KKKKRemoval protective trip unit cover (Magnetrip™
only)
LLLLCover mounting screws (four)
MMMMMidcover mounting screws (three – motor operated
only)
NNNNMicroVersaTrip RMS-9 trip unit interchangeable rat-
ing plug
OOOOMotor operator control circuit fuses
PPPPMicroVersaTrip RMS-9 test set connection port
Power Break® Circuit Breakers
Chapter 2. Breaker Operation
Figure 5. Motor operator-charged breaker.
Figure 4. Manually charged breaker.
Figure 6. Motor operator charged breaker with the top cover
removed.
2–2 Operating Instructions
Sequence of Operations
The sequence of operations that may be performed on the circuit breaker is listed in Table 3.
3
Page 10
Power Break® Circuit Breakers
Chapter 2. Breaker Operation
Indicator
OFF Open Discharged Mechanism may be charged
CHARGED / CHG Open Fully Charged Contacts may be closed
ON Closed Discharged Contacts may be opened
Table 3. Sequence of operations that may be performed with Power Break circuit breakers.
Main Breaker
Contacts
Condition of
Charging Springs Next Permissible Operating Function
Operating Instructions for Manually Charged Breakers
Charging the Mechanism Springs
Rotate the operating handle counter-clockwise until the handle stops (about 120° ). Rotate the handle clockwise back to its home position.
the contacts and turn the breaker ON.
display CHG.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
position by any of the following accessories, the mechanism springs will discharge at the end of the charging stroke and the breaker will revert to the OFF condition.
• The key interlock or padlock is in the locked OFF con-
dition.
• On a draw-out breaker, the draw-out interlock is
engaged with the carriage in any position except TEST or ENGAGED.
• The bell alarm lockout was not reset after an overcur­rent lockout.
• The undervoltage release is not energized.
These conditions must be corrected before the breaker can be closed. Failure to do so may result in equipment damage.
Closing the Breaker
Close the breaker contacts with either of the following methods:
• Depress the ON button on the breaker escutcheon.
• Energize the (optional) remote close accessory by
Opening the Breaker
Open the breaker contacts with either of the following methods:
• Depress the PUSH OFF button on the breaker
• Energize the (optional) shunt trip accessory or deen-
::
If the breaker latch is held in the tripped
connecting terminal 5 to terminal 6.
escutcheon.
ergize the (optional) undervoltage release accessory.
This operation will NOT close
The indicator will
Operating Instructions for Electrically Charged Breakers
Charging the Mechanism Springs
Charge the mechanism springs with either of the follow­ing methods:
Local
– Depress the lockable manual charge engagement
button until it is flush with the handle surface. Slight rotation of the handle may be necessary to fully depress the button in order to align the internal coupling.
– Hold the button down and rotate the operating
handle counter-clockwise until the handle stops (about 120°). Rotate the handle clockwise back to its home position.
the contacts and turn the breaker ON.
indicator will display CHARGED.
Remote
energize the motor operator mechanism.
Closing the Breaker
Close the breaker contacts with either of the following methods:
• Depress the ON button on the breaker escutcheon.
• Energize the (optional) remote close accessory by connecting terminal 5 to terminal 6.
Opening the Breaker
Open the breaker contacts with either of the following methods:
• Depress the PUSH OFF button on the breaker escutcheon.
• Energize the (optional) shunt trip accessory or deen­ergize the (optional) undervoltage release accessory.
Automatic Operation
For automatic closing of the breaker when the springs are charged, permanently connect terminal 5 to terminal 6. The breaker will close as soon as the charging cycle is complete.
For automatic charging of the closing springs, perma­nently connect terminal 3 to terminal 4. The springs will
– Connect terminal 3 to terminal 4 to
This operation will NOT close
The
4
Page 11
charge as soon as the breaker is opened, whether from a
g
fault trip or from being intentionally opened.
Power Break® Circuit Breakers
Chapter 2. Breaker Operation
CCCCAAAAUUUUTTTTIIIIOOOONN
NN
:::: Do not wire breakers for both automatic charge and automatic close unless a bell alarm with overcurrent lockout is incorporated. Otherwise, the breaker may repeatedly close into an overcurrent fault.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
::
The bell alarm lockout and undervoltage release both hold the breaker latch open when activated. To prevent continuous cycling (see Application Notes) when the breaker is wired for automatic charging, inter­connect the bell alarm switch to the motor operator ter­minal board as shown in Figures 7 and 8.
::
NNNNOOOOTTTTEEEE::
off control power if the OFF button is held depressed.
The motor operator contains a feature that shuts
Figure 8. Wiring for optional bell alarm lockout applications.
Thus, electrical operation is prevented if a key interlock or padlock accessory is applied in the breaker OPEN con­dition. If the breaker is equipped with a draw-out inter­lock (TPDO-1), electrical operation is permitted only if the draw-out carriage is in the ENGAGED or TEST posi­tion.
Wiring Notes
Observe the following notes when wiring the breaker for operation:
• Customer-supplied contacts (such as CHARGE and
CLOSE) should be momentary action, rated for 0.25
A at 125 Vdc for dc motor operators or rated for 3 A at 120 Vac for ac motor operators.
• Do not apply power to any terminal board point other than points 1 and 2.
• Observe the proper polarity for dc motor operators (point 1 is positive).
• When performing hi-pot or dielectric tests:
– Remove all power leads, both control and power.
– Short all motor operator terminal board points.
– Open the circuit breaker.
– Test between the motor operator terminal board
points and the load side of the breaker’s center pole (this pole is connected to the frame).
– Test at 2200 Vac for one minute using a current-
limited, nondestructive ac hi-pot tester with
Figure 7. Bell alarm wiring to prevent continuous cycling of the
maximum output of 20 mA.
automatic charging mechanism.
Operatin
Rated
Voltage
120 Vac 102–132 8 2.5 1.5 3.0 2 A 5.0 0.83 0.05 125 Vdc 100–140 10 2.5 1.5 3.5 2 A 6.0 0.83 0.05
72 Vdc 57–81 13 3.0 2.0 5.0 3 A 6.0 0.83 0.05 48 Vdc 38–58 20 5.0 2.5 6.6 4 A 6.0 0.83 0.05 24 Vdc 19–29 24 7.0 3.0 13.2 6.25 A 7.5 0.83 0.05
Voltage
Range
Motor Current, A
Locked
Rotor
Full
Load Average
Close Nominal Maximum Maximum
Solenoid,
peak A
Fuses (Slo Blo 125 V)
Charge
Time , s
Close
Time, s
Opening
Time, s
Table 3. Application data for control power.
5
Page 12
Power Break® Circuit Breakers
Chapter 2. Breaker Operation
Application Notes
• Size the control power source according to the information in Table 3. If a single source is to supply several motor operators, it must be sized appropri­ately. Where breakers are wired for automatic charge, it may be necessary to supply power to several motor operators simultaneously during start up.
• The control power source should be sized so that the drop in voltage from no load to full load does not exceed 7%.
• Acceptable dc power sources are the following:
– dc generator,
– battery,
– three-phase, full-wave rectified ac, or
– any other dc power source with a peak-to-peak
ripple voltage of not more than 15% of the rated voltage at motor full-load current.
• Breakers built after approximately June 1978 are equipped with an anticycling circuit that will lock out the breaker if the latch fails to reset (such as due to a deenergized UVR). Lockout occurs if the charge time exceeds 20 seconds. Reset a locked-out breaker locally by pushing the OFF button or remotely by momentarily removing control power from the motor operator.
2222....Change the settings by twisting the indicator switches
to the desired values or multipliers. See GEH-4657 for definitions of MicroVersaTrip functions and GEH­5369 for MicroVersaTrip RMS-9 functions.
3333....Reinstall the window.
Rating Plugs
MicroVersaTrip RMS-9 trip units require the installation of a rating plug in accordance with GEH-5369 and GEH­5371 to set the maximum continuous current rating.
Tap Changer Card
Some MicroVersaTrip models include a tap changer card, shown in Figure 9. When provided, this function allows the customer to change the rating of the breaker frame.
Figure 9. Tap changer cards.
2–3 Trip Unit Setup
::
NNNNOOOOTTTTEEEE::
be changed per GEH-5369 and GEH-5371 without void­ing the UL listing. MicroVersaTrip trip units and tap changer cards may be installed or replaced per GEH­4657 and this manual without voiding the UL listing. MicroVersaTrip Plus and MicroVersaTrip PM trip units and rating plugs may be changed or replaced per GEH­6273 without voiding the UL listing.
MicroVersaTrip® and MicroVersaTrip® RMS-9 Trip Units
Trip settings are installed at the factory with minimum values on all functions. Customers will generally want to adjust settings to their own requirements.
Adjusting Trip Settings
Use the following procedure to adjust trip settings on these trip units:
MicroVersaTrip RMS-9 trip unit rating plugs may
1111....Remove the clear plastic protective window, shown in
Figure 4.
6
Page 13
All breakers provided with tap cards are shipped with both
HIGH (100% of the current rating Sensor Amp on the
breaker name plate) and low (50–75% of the current rating Sensor Amp on the breaker name plate). The low card is packed and supported on the breaker handle. The
high card is installed in the breaker frame. To change
settings use the following procedure:
Power Break® Circuit Breakers
Chapter 2. Breaker Operation
WWWWAAAARRRRNNNNIIIINNNNGGGG::
the electrical system before attempting any operations that involve removing the breaker’s cover.
1111....Turn the breaker off.
2222....Remove the four cover mounting screws and remove
the top cover. On motor operator-equipped breakers, remove only the top cover.
3333....Withdraw the card from the tap changer support and
replace with the other card, as shown in Figure 10. The print on the top of the card should be oriented the same as the breaker cover name plate.
4444....Trip units providing ground fault protection must
also have the tap setting changed on the tapped neu­tral CT (four-wire systems). Change the black wire lead from the high or low terminal to match the desired tap setting of the breaker frame, as shown in Figure 11.
5555....Replace the breaker cover.
6666....Operate the breaker manually through the
charge–close–open cycle to ensure that the breaker is
properly functioning mechanically before energizing or connecting it to the electrical system.
NNNNOOOOTTTTEEEE::
the mechanism to charge and close.
7777....Store the extra tap card in a convenient place.
::
The circuit breaker must be removed from
Figure 10. Cover and trip unit removed from the breaker.
::
A deenergized undervoltage release will not allow
Figure 11. Neutral CT connection for four-wire ground fault.
Neutral Current Transformer (Four-Wire Ground Fault System)
Ground fault protection is offered as an optional function of the MicroVersaTrip® trip unit. However, all MicroVer­saTrip-generation breaker frames are provided with ter­minal board points for connection to a neutral CT.
Do not short these terminals if there is no neutral CT connected.
Always match the rating of the CT to the rating of the cir­cuit breaker; specifically, use the following criteria:
Fixed-rated breaker frames
amp rating to the breaker sensor amp rating.
Tapped or high/low-rated breaker frames
the neutral CT amp rating to the high/low setting of the breaker sensor amp rating.
Note that MicroVersaTrip RMS-9-equipped breakers are
not
available with inverted construction (formerly desig­nated by Cat. No. suffix B). These breakers may be either top fed, as illustrated in Figure 12, or bottom fed, as illus­trated in Figure 13.
NNNNOOOOTTTTEEEE::
13 when the breaker is bottom (reverse) fed.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
to the tap setting, if provided, on the breaker frame.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
CT shell and the breaker frame.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
required (three-wire ground fault), ground fault terminal points on the breaker frame. Leave them open as supplied by the factory.
::
The neutral CT is mounted in reverse in Figure
::
Match the tapped terminal for the black lead
::
Observe the polarity markings on the neutral
::
When a neutral CT is not used or not
– match the neutral CT
– match
do not
short the
7
Page 14
Power Break® Circuit Breakers
Chapter 2. Breaker Operation
• High short-time or H-function trip units may not be used in frames that are not wired for H function (special CTs).
• Special trip units for AK breakers with the M (no instantaneous) function may not be used with Power Break breakers.
Refer to GEH-4657 for installation or replacement of MicroVersaTrip trip units with remote overload indication and for recommended wiring for zone-selective interlock.
To change or install trip units without remote indication, use the following procedure.
Figure 12. Wiring diagram for MicroVersaTrip and MicroVersaTrip
RMS-9 trip units with ground fault on a top-fed four-wire load.
Figure 13. Wiring diagram for MicroVersaTrip and MicroVersaTrip
RMS-9 trip units with ground fault on a bottom-fed four-wire load.
WWWWAAAARRRRNNNNIIIINNNNGGGG::
the electrical system before attempting any operations that involve removing the breaker’s cover.
1111....Remove the four cover-mounting screws and remove
the top cover. On motor-operated breakers, remove only the top cover to replace the trip unit.
2222....Remove the trip unit as follows:
aaaa....Push in the trip unit-cover interlock, as illustrated
bbbb....Lift the trip unit off the mounting plate and ter-
cccc....The trip unit-cover interlock will now swing out
::
The circuit breaker must be removed from
in Figure 14.
minal plug.
and lock over the base to prevent reinstallation of the breaker cover when no trip unit is installed.
MicroVersaTrip RMS-9 Trip Units
The trip units on MicroVersaTrip RMS-9-equipped break­ers are not interchangeable. The breaker rating may be adjusted by changing the rating plug installed in the face of the trip unit. See GEH-5369 and GEH-5371 for instruc­tions.
MicroVersaTrip Trip Units
MicroVersaTrip-equipped breakers were ordered complete or as a frame and trip unit only. Some trip units and frames have rejection schemes to prevent mismatching of functions.
The limits of interchangeability are as follows:
Figure 14. Releasing the trip unit cover interlock to remove or install
the trip unit.
8
Page 15
3333....Install the replacement trip unit as shown in Figure
15:
aaaa....Align the holes in the bottom of the trip unit with
the guide pins in the mounting plate. Lower the trip unit until it is fully down on the mounting plate and the connecting plug is secure.
bbbb....Push in the trip unit-cover interlock until it locks
in place, as shown in Figure 14.
Power Break® Circuit Breakers
Chapter 2. Breaker Operation
NNNNOOOOTTTTEEEE::
the trip unit-cover interlock locking spring.
NNNNOOOOTTTTEEEE::
the mechanism to charge and close.
::
The trip unit has a stud on the bottom to defeat
Figure 15. Aligning the trip unit to the mounting plate.
4444....Replace the top cover and secure with the four cover-
mounting screws.
5555....Operate the breaker manually through the
charge–close–open cycle to ensure that the breaker is
properly functioning mechanically before energizing or connecting it to the electrical system.
::
A deenergized undervoltage release will not allow
Figure 16. Adjusting the settings on a MagneTrip trip unit.
MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units
See GEH-6273 for detailed instructions for setting up MicroVersaTrip Plus and MicroVersaTrip PM trip units.
6666....For trip units with ground fault, a neutral CT must be
provided if a four-wire system is to be used. See the section on neutral CTs for instructions and precau­tions.
Do not
vided on the breaker frame if a neutral CT is not used.
short the ground fault terminals pro-
MagneTrip™ Trip Units
Use the following procedure to change trip settings on MagneTrip trip units:
1111....Remove the protective trip unit cover.
2222....Change the trip setting by rotating the plastic buttons
in the base with a screw driver, as shown in Figure 16.
3333....Replace the protective cover.
9
Page 16
Power Break® Circuit Breakers
Chapter 3. Accessories
3–1 Introduction
These instructions cover the field installation of internally mounted electrical accessories. They are UL listed for use in all 800–2000 A frame Power Break® circuit breakers with MicroVersaTrip® trip units. These accessories may also be installed in 800–1600 A frame Power Break break­ers with MagneTrip™ trip units, but the UL listing is voided.
The control leads of internally mounted accessories exit in pigtail form from the side of the breaker. These leads are terminated at the secondary disconnect points of draw-out breakers or at optional terminal blocks when specified for stationary-mounted breakers. All leads are color coded as listed in Table 4.
Accessory Lead Color
Shunt Trip Black 2 Undervoltage
Release
Auxiliary Switch
Bell Alarm (Overcurrent Lockout)
Blown-Fuse Trip (3-Coil Shunt Trip)
Closing Solenoid (Manual Breakers only)
Brown/White – CLOSED (NC)
Purple – CLOSED (NC)
Brown – OPEN (NO)
Line End Load End Phase
Red Brown-White A Blue White B
Yellow Black C
Black – remote indication
Orange – remote close
Blue 2
White – common
Red – OPEN (NO)
Yellow – common
White – common
No. of Leads
3 per
switch
3
6
3
::
NNNNOOOOTTTTEEEE::
All breakers are equipped with mechanical inter­locks that automatically trip the breaker when the cover is removed with the breaker closed.
Breaker Cover Removal
Manual Breaker
Use the following procedure to remove the cover of a manually operated breaker:
1111....Press the off button to open the circuit breaker.
2222....Remove the four cover-mounting screws.
3333....Remove the breaker cover.
Electrically Operated Breaker
Use the following procedure to remove the cover of an electrically operated breaker. An 800 A frame breaker is shown in Figure 17 and a 1600–2000 A frame breaker is shown in Figure 18.
1111....Press the off button to open the circuit breaker.
2222....Disconnect all external leads from the terminal
board.
3333....Remove the four cover mounting screws.
4444....Remove the outer cover.
5555....On 1600-2000 A framer breakers only, remove the two
inner-cover mounting screws, as shown in Figure 18.
6666....Loosen the captive inner-cover lock screw, as shown
in Figure 19.
7777....Remove the inner cover.
Table 4. Accessory lead color codes.
3–2 Circuit Breaker Cover
Before any accessories can be installed in a Power Break circuit breaker, the cover(s) must be removed, as described in the following sections.
WWWWAAAARRRRNNNNIIIINNNNGGGG::
de-energize the circuit breaker and disconnect it from the electrical circuit. This is mandatory, since the breaker must be ON during certain stages of installation and testing.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
loose parts may become lost.
::
Before installing any accessories, completely
::
Do not turn the breaker upside down, since
Figure 17. 800 A frame electrically operated breaker.
10
Page 17
Power Break® Circuit Breakers
Chapter 3. Accessories
Figure 18. 1600–2000 A frame electrically operated breaker.
Figure 19. 1600–2000 A frame electrically operated breaker with the
outer cover removed.
Breaker Cover Reassembly
Manually Operated Breakers
1111....Verify that all connections are secure and the breaker
is free of debris.
2222....Verify that the breaker is off.
Figure 20. Wire ties on the accessory leads and mounting plate
insulator.
Electrically Operated Breakers
1111....Verify that all connections are secure and the breaker
is free of debris.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
insulator is properly located, as shown in Figure 26.
2222....Slide the inner cover assembly onto the breaker base.
::
Verify that the accessory mounting plate
Ensure that the crossbar hook engages the drive stud, as shown in Figure 21.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::::
insulator, shown in Figure 20, is properly located so it will not be damaged when the cover is replaced. The cover phase barrier must pass to the right side of this insulator.
3333....Position the charging handle at the home position (6
o’clock) on the cover. Align the cover mounting screw holes with the breaker base and install the four cover screws. Tighten the screws to 50–60 in-lbs.
Verify that the accessory mounting plate
Figure 21. Crossbar hook engaging the drive hook.
3333....Tighten the inner cover lock screw, shown in Figure
19, to 10 in-lbs.
4444....On 1600–2000 A frame breakers only, replace the two
inner cover mounting screws and tighten to 50–60 in­lbs.
11
Page 18
Power Break® Circuit Breakers
Chapter 3. Accessories
5555....Position the charging handle at the home position (6
o’clock) on the outer cover. Align the outer cover­mounting screw holes with those on the inner cover and install the four cover-mounting screws. Tighten to 50–60 in-lbs.
NNNNOOOOTTTTEEEE::
::
Ensure that the control terminal board properly
engages the cover retaining slots.
6666....Connect the control and power wiring as per the
instructions supplied with the circuit breaker.
3–3 Shunt Trip Device
The shunt trip, shown in Figure 22, allows the breaker to be tripped electrically from a remote location. A cut-off switch is supplied as part of the shunt trip to automatically remove power from the shunt trip coil when the breaker is tripped. The electrical characteristics of the shunt trip are listed in Table 5. Figure 23 is the shunt trip wiring dia­gram.
Figure 23. Shunt trip wiring diagram.
Mounting Plate Removal
The mounting plate is used as the anchor position for the shunt trip, blown-fuse trip, and undervoltage release accessories. Breakers are shipped from the factory with either a mounting plate or an L-shaped bracket to retain the molded-plastic crank. A new mounting plate is pro­vided in the shunt trip kit, blown-fuse trip kit, undervol­tage release kit, and auxiliary switch kit.
• If the breaker was supplied with an L-shaped bracket, remove the two retaining screws, discard the bracket, and skip to the appropriate installation instructions.
• If the breaker was supplied with a mounting plate, remove it with the following procedure:
1111....Remove the three mounting plate retaining screws
and the isolation barrier, shown in Figure 24.
2222....Lift out the accessory mounting plate and remove the
molded drive crank.
3333....If a tap changer was supplied, remove the two screws
from the phenolic block before removing the mount­ing plate.
Figure 22. Shunt trip device with cut-off switch.
Catalog No.
TPST 12S
TPST13S
TPST7S 12 Vdc 4.00 TPST8S 24 Vdc 2.18
TPST9S 48 Vdc 1.09 TPST10S 125 Vdc 1.00 TPST11S 250 Vdc 0.21
Voltage
Rating
120 Vac 240 Vac
480 Vac 600 Vac
Max. Inrush
Current, A
2.25
4.50
1.64
2.05
Table 5. Shunt Trip electrical characteristics.
Figure 24. Locations of the mounting plate retaining screws, isolation
barrier, and molded drive crank.
12
Page 19
Shunt Trip Installation
Power Break® Circuit Breakers
Chapter 3. Accessories
NNNNOOOOTTTTEEEE::
defective coil, the cause of the initial failure should first be determined. If necessary, consult the factory for fur­ther guidance.
NNNNOOOOTTTTEEEE::
mounted in the position nearest the latch. These coils may not develop enough force to drive both the latch and the blown-fuse trip device.
::
If the shunt trip is being replaced because of a
1111....Assemble the coil to the mounting plate as shown in
Figure 25. If a blown-fuse trip device is also to be installed on the mounting plate, mount the shunt trip coil as shown in Figure 26.
2222....When a blown-fuse trip device is included, place the
shunt trip plunger stop nut in contact with the plunger of the blown-fuse trip device.
3333....Depress the actuator on the cut-off switch. Align the
tapped holes in the switch bracket with the holes in the arm stop (left pole) and secure with #8-32 × 9/16 screws and lock washers, as shown in Figure 27. Tighten to 23 in-lbs torque.
4444....Remove the knockouts in the side of the base, as
required. Each knockout will accommodate up to three bundles of wire. Remove all sharp edges with a file.
5555....Clean all debris from the inside of the breaker.
::
Shunt trip coils rated at 12 Vdc or 24 Vdc must be
Figure 26. Shunt trip coil position with blown-fuse trip device.
Figure 25. Shunt trip coil position with no blown-fuse trip device.
Mounting Plate Installation
1111....Replace the molded drive crank onto the mechanism
drive pin, as shown in Figure 24, engaging the roll pins into the slot in the drive crank.
Figure 27. Attaching the switch bracket to the arm stop.
2222....Place the mounting plate in position so that its two
operating studs engage the molded drive crank, as shown in Figure 24. Ensure that the isolating barrier is in place.
3333....Attach the three retaining screws. Tighten the two
small screws to 20 in-lbs and the large screw with tub­ing to 75 in-lbs.
4444....Attach wire ties to the leads and secure them to the
mounting plate, as shown in Figure 20.
5555....Insert the leads into the knockout in the base side
wall, ensuring that one tie is on the inside of the base and the other is on the outside.
6666....Apply the descriptive label to the front of the breaker
cover.
13
Page 20
Power Break® Circuit Breakers
Chapter 3. Accessories
3–4 Undervoltage Release Device
The undervoltage release device (UVR), shown in Figure 28, opens the circuit breaker when the supply voltage drops to 35–60% of its rated value. Figure 29 shows the dropping resistor supplied with 240–600 volt UVRs. The UVR electrical characteristics are listed in Table 6. The UVR wiring diagram is in Figure 30.
Figure 28. Undervoltage release device.
Figure 29. Dropping resistor supplied with 240–600 V UVRs.
Figure 30. UVR wiring diagram.
Catalog
Number
TPUV1S 120 Vac 25 none TPUV2S 240 Vac 25 5000 ?, 25 W TPUV2S 480 Vac 25 15,000 ?, 50 W TPUV6S 600 Vac 25 20,000 ?, 50 W TPUV7S 12 Vdc 211 none TPUV8S 24 Vdc 104 none
TPUV9S 48 Vdc 54 none TPUV10S 125 Vdc 24 none TPUV11S 250 Vdc 24 5000 ?, 25 W
* Ohmite Type 270
Voltage
Rating
Continuous
Current, mA
Dropping Resistor*
Table 6. UVR electrical characteristics.
UVR Installation
1111....Remove the circuit breaker cover(s) as described
above in
2222....The UVR assembles to a mounting plate. Not all
breakers are shipped from the factory with a mount­ing plate. Some breakers have only an L-shaped bracket to retain the molded-plastic crank. A mount­ing plate is provided in the UVR kit.
• If the breaker is supplied with an L-shaped
• If the breaker is supplied with a mounting plate,
3333....Remove the slide reset lever spring from the mount-
ing plate, as shown in Figure 31. Be careful not to nick or damage the spring in any way, since it will be needed for reassembly.
4444....Push the latch and slide reset lever forward to pro-
vide mounting clearance for the UVR assembly.
5555....Position the UVR assembly mounting bracket so that
its retaining hole engages the latch pivot post, as shown in Figure 32.
6666....Line up the UVR bracket’s mounting hole with the
tapped hole in the accessory mounting plate. Install the screw and lock washer, as shown in Figure 33. Tighten the screw to 9–11 in-lbs.
7777....Replace the slide reset lever spring, shown in Figure
31.
8888....Remove the knockouts in the side of the base, as
required. Each knockout will accommodate up to three bundles of wire. Remove all sharp edges with a file.
9999....Remove all debris from the inside of the breaker.
3–2 Circuit Breaker Cover
.
bracket, remove the two retaining screws and dis­card the bracket. Follow the
Installation
instructions and continue on to step
Mounting Plate
3.
continue with step 3.
14
Page 21
Power Break® Circuit Breakers
Chapter 3. Accessories
Figure 33. Installing the UVR mounting screw.
Figure 31. Slide reset lever and spring on the mounting plate.
Figure 32. Positioning the UVR assembly on the mounting plate.
11110000....Use the wire ties provided to secure the leads to the
mounting plate and to secure the wire bundle to the inside and outside of the breaker base, as shown in Figure 20.
11111111....Reassemble the breaker covers as described in
Breaker Cover Reassembly
11112222....Mount the dropping resistor (when supplied) and
MOV, shown in Figure 29. Wire these as shown in Figure 30.
.
11113333....Perform the following functional check of the UVR:
aaaa....Apply rated voltage to the UVR coil.
bbbb....Turn the breaker on.
cccc....Reduce the control voltage. The breaker should
trip when the voltage drops to 35–60% of its rated value.
11114444....Apply the UVR descriptive label to the left side of the
breaker near the lead-exit area.
3–5 Blown-Fuse Trip Device
The blown-fuse trip device (three-coil shunt trip), shown in Figure 34, is intended for applications with breakers and fuses in series. This accessory prevents single-phasing conditions by monitoring the fuses and automatically tripping the circuit breaker when a fuse blows. It does not protect from single-phasing of the power source.
15
Figure 34. Blown-fuse trip device accessory.
Page 22
Power Break® Circuit Breakers
Chapter 3. Accessories
Each coil of the blown-fuse trip device is wired across a fuse so that the voltage across an open fuse is fed back to the accessory coil. When the coil is energized, the solenoid core releases the spring-biased latch, allowing the slide to rotate the breaker latch, tripping the breaker. The fuse must be replaced and the breaker reset before the breaker can be reclosed.
If the breaker is closed on an open fuse, the blown-fuse trip device will automatically open the breaker.
Blown-Fuse Trip Device Installation
Installation of the blown-fuse trip device is similar to that of the shunt trip, described above.
1111....The blown-fuse trip device assembles to a mounting
plate. Not all breakers are shipped from the factory with a mounting plate. Some breakers have only an L-shaped bracket to retain the molded-plastic crank. A mounting plate is provided in the blown-fuse kit.
• If the breaker is supplied with an L-shaped bracket, remove the two retaining screws and dis­card the bracket.
• If the breaker is supplied with a mounting plate, follow the instructions under
Removal
2222....Assemble the blown-fuse trip device to the accessory
mounting plate as shown in Figure 26. If a shunt trip had previously been mounted as shown in Figure 25, it must be relocated as shown in Figure 26, with its plunger stop nut in contact with the plunger of the blown-fuse trip device.
3333....Follow the procedure for
4444....Perform the following installation checks:
aaaa....Replace the breaker cover as described above.
Close the breaker contacts.
bbbb....Apply 120 volts to one coil of the blown-fuse trip
device for not more than one second. The breaker must trip. Repeat the test for each coil.
5555....Attach the six lead wires from the blown-fuse trip
device across the three fuses, as shown in the wiring diagram in Figure 35.
6666....Apply the descriptive label to the front of the breaker.
7777....Reassemble the breaker cover(s) as described in
Breaker Cover Reassembly
.
Mounting Plate Installation
.
Mounting Plate
Figure 35. Blown-fuse trip device wiring diagram.
3–6 Auxiliary Switch
The auxiliary switch, shown in Figure 36, is used for remote indication of the breaker’s main contact posi­tion—open or closed. No distinction is made between open or tripped mode. A maximum of 12 switches can be installed per breaker. Each is single-pole, double-throw (AB-type) and rated as listed in Table 7. Two switch posi­tions must be devoted to each shunt trip accessory (if used) per breaker. The auxiliary switch wiring diagram is shown in Figure 37.
.
Figure 36. Auxiliary switch.
16
Page 23
Power Break® Circuit Breakers
Chapter 3. Accessories
Figure 37. Auxiliary switch wiring diagram.
Catalog Number
TPAS2ABx 1–12
* Replace x with a number from 1–12 for the number of switch elements.
Number of
Switch Elements
Maximum
Current Rating
6 A at 240 Vac .25 A at 250 Vdc .50 A at 125 Vdc
Table 7. Auxiliary switch electrical characteristics.
Auxiliary Switch Installation
1111....Remove the circuit breaker cover(s) as described in
Breaker Cover Removal
• If the breaker was supplied with an L-shaped bracket (see
Mounting Plate Removal
the two retaining screws, discard the bracket, and install the mounting plate provided in the kit (see
Mounting Plate Installation
2222....Both the left and right breaker poles can accept up to
six auxiliary switches. If the left pole contains a shunt trip, two of the six auxiliary switch positions must be used for the cut-out switches; thus, only four auxil­iary switches may be used in the left pole.
3333....If auxiliary switches are to be installed in the right
pole, remove the trip unit by depressing the lock release lever while lifting up on the trip unit. Remove the trip unit mounting plate, shown in Figure 38.
4444....Position the auxiliary switch assembly so that the
tapped mounting holes on its bracket line up with the through holes in the arm stop, as shown in Figure 39.
5555....Secure the auxiliary switch assembly to the arm stop
with two #8 × 9/16 screws and lock washers, as shown in Figure 40. Tighten the screws to 23 in-lbs.
.
), remove
).
Figure 38. Trip unit removed from the breaker.
Figure 39. Installing the auxiliary switch assembly.
Figure 40. Securing the auxiliary switch assembly.
6666....Remove knockouts in the side of the base, as
required. Each knockout will accommodate up to three bundles of wire. Remove all sharp edges with a file.
7777....Use the supplied wire ties to secure the leads as
shown in Figure 20.
8888....Replace the trip unit mounting plate and trip unit.
9999....Replace the breaker cover(s) as described in
Breaker Cover Reassembly
.
Circuit
11110000....Perform the following functional checks:
aaaa....With the breaker off, use a continuity tester to
verify continuity between the white and brown-
17
Page 24
Power Break® Circuit Breakers
g
Chapter 3. Accessories
white leads. Verify an open circuit between the red and white leads.
bbbb....With the circuit breaker on, the auxiliary switch
contacts should change sense.
11111111....Apply the auxiliary switch descriptive label to the
front of the breaker cover.
3–7 Remote Close Solenoid and Remote Charge Indication
The remote close solenoid is included with electrically operated breakers and may be ordered as a factory­installed option in manually operated breakers. Catalog numbers and specifications are listed in Table 8.
Remote charge indication provides for remote indication that the breaker closing springs are charged. Catalog numbers are TPXCAS and TSXCAS for 800–2000 A and for 3000–4000 A frames, respectively. The switch is rated at 15 A for 250 Vac and at 0.5 A for 125 Vdc. Figure 41 is the wiring diagram for remote charge indication. Figure 42 is the wiring diagram for remote charge indication with a remote close solenoid.
Figure 41. Wiring diagram for remote charge indication.
Figure 42. Wiring diagram for remote charge indication with remote
close solenoid.
Catalog No.
TPXCC12S 120 Vac 102–132 3.3 0.083 0.050 TPXCC14S 240 Vac 204–264 1.7 0.083 0.050
TPXCC08S 24 Vdc 19–29 13 0.083 0.050
* The power source must stay within the rated operating voltage range of the close solenoid from no load to the full peak current rating of the device.
Rated
Voltage
Table 8. Catalog numbers and ratings for the remote close solenoid.
Operatin
Range*, V
Current at Max.
Voltage, A
Maximum
Closing Time, s
Maximum
Operating Time, s
3–8 Optional Features
Special features may be ordered as specific accessories or as an integral part of the breaker catalog number. Refer to the BuyLog®, GEP-1100, for these features.
Limited Close Access Button
This accessory, shown in Figure 43, provides for limited manual access to the ON button. The breaker can be closed in an emergency for maintenance by inserting a
1
/8-inch diameter pin or rod into the hole in the center of the button. Manually operated breakers must be ordered with an accessory closing solenoid.
Figure 43. Limited close access button.
18
Page 25
Padlock Function
Handle Button Lock
A standard feature on motor-operated breakers that pre­vents manual charging of the mechanism, as shown in Figure 5.
OFF Button Padlock with Door Interlock
This accessory prevents opening of the panel door when the breaker is ON or CHARGED. It operates as follows:
• With the breaker OFF the paddle can be rotated
counterclockwise over the breaker nameplate to clear the enclosure panel door. Rotate the paddle clock­wise to lock the door, as shown in Figure 44.
• To defeat the interlock when the breaker is ON or
CHARGED, depress the spring and rotate the paddle
to clear the door, as shown in Figure 45.
Power Break® Circuit Breakers
Chapter 3. Accessories
Figure 45. Defeating the OFF button padlock.
Figure 44. OFF button padlock with panel door interlock.
19
Page 26
Power Break® Circuit Breakers
Chapter 4. Maintenance
WWWWAAAARRRRNNNNIIIINNNNGGGG::
disconnect the breaker from all voltage sources, both power and control, and ensure that the breaker is OFF.
::
Before beginning any maintenance work,
4–1 Inspections
Circuit breakers should be maintained through the implementation of a systematic maintenance program. A periodic inspection routine is recommended. The fre­quency of inspection should depend on the environ­mental conditions of each breaker. All circuit breakers should be inspected at least annually. It a breaker is oper­ated frequently or installed in an area of high humidity, dust, or dirt, the frequency of maintenance inspections should be increased. Under extremely adverse conditions, monthly inspections are recommended.
The maintenance inspection should begin with an overall visual check. If dirt, grease, or any other foreign material is found on or in the breaker, it should be thoroughly and carefully removed. Do not use solvents on insulating mate­rial.
A rotating program providing for a periodic withdrawal from service of each breaker in turn for inspection and maintenance is an excellent means of establishing a high level of service reliability. In such cases, one or more spare breakers and all accessories should be available during the maintenance inspection to replace any breaker that may be removed for repairs.
NNNNOOOOTTTTEEEE::
plete information from the breaker name plate, includ­ing the breaker’s serial number.
::
When ordering spare parts, always enclose com-
4–2 Lubrication
Moderate lubrication is all that is required for most circuit breakers. Mechanical bearing points and sliding surfaces should be lubricated at the regular inspection periods with a thin film of molybdenum disulfide (Molykote G) or Mobil 28 grease. GE recommends the use of kerosene for removing hardened grease and dirt from the latch and bearing surfaces. All excess lubricant should be removed to avoid any contamination of dirt or dust.
CCCCAAAAUUUUTTTTIIIIOOOONNNN::
applied to contact areas.
::
Under no circumstances should lubricant be
20
Page 27
Page 28
g
General Electric Company 41 Woodford Ave., Plainville, CT 06062
GEH4693 R05 0998 © 1998 General Electric Company
GE Industrial Systems
Loading...