with -48 Volt Rectifiers, +24 Volt Converters,
and Pulsar Controller
Installation Guide
Installation Guide
LineagePower.com
Comcode CC848853515
Issue 2.0
June 2009
Infinity D Power System Installation Guide: -48V Plants H2007001
Notice:
The information, specifications, and procedures in this manual are subject to change
without notice. Lineage Power assumes no responsibility for any errors that may appear
in this document.
Infinity D Power System Installation Guide: -48V Plants H2007001
1. Introduction
Document Objectives
This manual provides installation and maintenance information for the Lineage Power
Infinity D power system:
• Safety Information
• Product Description
• Installation Procedures
• Test and Acceptance
• Troubleshooting, including Controller and Rectifier Operations
• Product Warranty
Audience
• Equipment Installers – Instructions for installation, test, and acceptance.
• Equipment Users – Plant basics and troubleshooting.
CAUTION: This unit must be installed, serviced, and operated only by
skilled and qualified personnel who have the necessary knowledge and
practical experience with electrical equipment and who understand the
hazards that can arise when working on this type of equipment.
Additional Product Documentation
• 2007001 Ordering Guide:
• Configuration and Ordering Information
• Specifications of System, Rectifiers, Converters, and Controller
• Spare and Maintenance Parts Lists
• Engineering Information, such as ac Service Breakers, Conduit and Wiring
Sizing, and dc Wiring Information
Applications
Infinity D represents the state-of-the-art high density power system with a 18x26x84 inch
footprint that are suited for sites ranging from 50A to 1200A power requirements. The 48Vdc power system provides 960 amperes at the 80% load capacity with a -48 to
+24Vdc converter shelf that provides four 75 ampere units for a total of 300 amps at
+24V.
Issue 2.0, June 3, 2009 5
Infinity D Power System Installation Guide: -48V Plants H2007001
Customer Service Contacts
Customer Service, Technical Support, Product Repair and
Return, and Warranty Service
For customers in the United States, Canada, Puerto Rico, and the US Virgin Islands, call
1-800-THE-1PWR (1-800-843-1797). This number is staffed from 7:00 am to 5:00 pm
Central Time (zone 6), Monday through Friday, on normal business days. At other times
this number is still available, for emergencies only. Services provided through this
contact include initiating the spare parts procurement process, ordering documents,
product warranty administration, and providing other product and service information.
For other customers worldwide the 800 number may be accessed after first dialing the
AT&T Direct country code for the country where the call is originating, or you may
contact your local field support center or your sales representative to discuss your
specific needs.
Customer Training
Lineage Power offers customer training on many Power Systems products. For
information call 1-972-284-2163. This number is answered from 8:00 a.m. until 4:30
p.m., Central Time Zone (Zone 6), Monday through Friday.
Downloads and Software
To download the latest product information, product software and software upgrades,
visit our web site at http://www.lineagepower.com/
Issue 2.0, June 3, 2009 6
Infinity D Power System Installation Guide: -48V Plants H2007001
[
2. Product Description
Overview
Shown here is an Infinity D equipment only frame made up of six Infinity D Power
Modules. Three different modules are shown: one Battery Connection Module, four
Rectifier System Modules and one Converter System Module. Principal elements are
Distribution
Circuit Breaker output
voltage
(Blue label is -48V)
Converter Distribution
Circuit Breaker output
voltage
(Orange label is +24V)
Converter module
output voltage(-48V to
+24V converters
shown with orange
marking)
Issue 2.0, June 3, 2009 7
Infinity D Power System Installation Guide: -48V Plants H2007001
Battery Connection Module
Batteries power the load equipment when ac input to the rectifiers is lost. The batteries
are connected to the Battery Connection Module at the top of the frame. An optional Low
Voltage Battery Disconnect (LVBD) contactor provides deep discharge protection if
desired. The System Shunt also resides in the Battery Connection Module.
Rectifier System Module
On the left side of each Rectifier System Module ac is supplied to front accessible
terminal blocks that feed each of the 4 rectifier positions.
The rectifier positions are labeled 1 through 4 from the bottom to the top. At product
introduction, all NE rectifiers operate from 208 to 240VAC nominal.
The DC Distribution provides 10 bullet circuit breaker positions per Rectifier System
module, with room to optionally add 10 more.
Pulsar Controller
The Pulsar system controller monitors and controls system operation. It is required for all
remote telemetry, dry contact alarm closures and precise control of battery voltage.
Converter System Module
The converter positions are labeled 1 through 4 from the bottom to the top. Converters for
this plant are available to convert from -48V to +24V.
The DC Distribution provides 10 bullet circuit breaker positions per Converter System
module. An alternative distribution will add 10 more for a total of 20.
Frame
By simply changing the door, this system can be configured to work with frame sizes of
19”, 23”, and 26” frameworks. Preconfigured part numbers for modules that fit into each
framework are available in the sizes common for most applications. Growth is achieved
by adding one of these supplementary modules. Installation instructions ship with each
module.
Frame Size19” 23” 26”
-48V Rectifier System Module
-48 to +24V Converter System Module
H2007001
G020E, or 20F
H2007001
G040E
H2007001
G020C, or 20D
H2007001
G040C
H2007001
G020A, or 20B
H2007001
G040A
Issue 2.0, June 3, 2009 8
Infinity D Power System Installation Guide: -48V Plants H2007001
Infinity D Block Diagram
Issue 2.0, June 3, 2009 9
Infinity D Power System Installation Guide: -48V Plants H2007001
Note on AC surge protection requirements: Our rectifier product Safety Approval is
performed to assure safe and reliable performance in IEC 60664-1 Installation Category
II environments. Building AC surge protection devices installed prior to the rectifiers
must provide this degree of protection.
Issue 2.0, June 3, 2009 10
Infinity D Power System Installation Guide: -48V Plants H2007001
3. Safety
Safety Statements
Please read and follow all safety instructions and warnings before installing, maintaining,
or repairing the Lineage power system:
• The CE Mark demonstrates compliance with the European Union Council Directives
for Low Voltage and EMC.
• This system is Underwriters Laboratories (UL) Listed per Subject 1801, Power
Distribution Centers for Telecommunications Equipment (UL 60950-1).
• Install only in restricted access areas (dedicated equipment rooms, equipment closets,
or the like) in accordance with articles 110.27 of the U.S. National Electric Code
(NEC), ANSI/NFPA No. 70, and pursuant to applicable local codes.
• Not for use in a computer room as defined in the Standard for the Protection of
o Ne peut être utilisé dans une salle d’ordinateurs telle que définie dans la
norme ANSI/NFPA 75 Standard for Protection of Electronic Computer/Data
Processing Equipment
• This equipment is to be used in controlled environments (an area where the humidity
is maintained at levels that cannot cause condensation on the equipment, the
contaminating dust is controlled, and the steady-state ambient temperature is within
the range specified).
• This equipment has been evaluated for continuous use in ambient temperature from
-40°C to 45°C. Maximum 45°C ambient for plant outputs not exceeding 960A charge
and 1200A discharge, otherwise maximum 40°C ambient.
• This equipment must not be installed over combustible surfaces.
• For installations in the United States, Listed compression connectors are to be used to
terminate Listed field-wired conductors where required. For all installations, the
appropriate connector is to be applied only to the correct size conductor as specified
by the connector manufacturer, using only the connector manufacturer's
recommended tooling or tooling approved for that connector.
• If the proper connector for the country of installation is not provided, obtain
appropriate connectors and follow manufacturers and all local requirements for
proper connections. All national and local rules and regulations should be followed
when making field connections.
• The main output voltage (less than 60Vdc for all configurations) meets SELV
requirements. Loads connected between -48 volts and +24 volts are not SELV and
therefore shall not be connected.
• Insulation on field-wired conductors should be rated no less than 90° Celsius. Wire
conductor size should be sized per electrical codes for 75° Celsius wire, and based on
the ampacity of the associated protection device. Wiring internal to enclosed
equipment cabinets should be rated at 105° Celsius (minimum).
Issue 2.0, June 3, 2009 11
Infinity D Power System Installation Guide: -48V Plants H2007001
• Torque electrical connections to the values specified on labels or in the product
documentation.
• Battery input cables must be dressed to avoid damage to the conductors (caused by
routing around sharp edges or routing in areas where wires could get pinched) and
undue stress on the connectors.
• Alarm contacts on the office alarm board are not fused; therefore, current limiting
protection for these contacts must be provided by external circuits. Maximum ratings
for alarm connections are 60Vdc and 0.5 amperes. Exceeding these maximum ratings
could result in fire or damage to the unit.
• Fuse and/or circuit breaker loads must not exceed 80% of the fuse and/or circuit
breaker current rating. Distribute loads across the panel.
• The short circuit current capability of the battery input to the distribution panel must
not exceed 10,000A.
• Wiring methods used for the connection of the equipment to the AC Mains Supply
shall be in accordance with the National Electric Code, ANSI/NFPA 70, and the
Canadian Electrical Code, Part 1, CSA C22.1. Maximum 20 A protective device is
required for each branch circuit powering one power supply. Maximum 40 A
protective device is required for each branch circuit powering two power supplies.
Refer to the equipment ratings to assure rating of equipment will not exceed 80% of
the value of the protector chosen.
• High leakage currents are possible due to contribution from simultaneous multiple ac
input connections. Earth ground connection is essential before connecting the ac
source to the shelf. This connection is achieved by bonding the AC grounding
conductor(s) to the AC grounding terminal(s).
• DC Ground System: Due to potentially high DC fault currents, the rack should first
be connected to the office DC ground system per the appropriate telecom industry
practices. This Ground connection should be made before any DC power or the AC
connections are made to avoid the possibility of damaging the AC ground if a DC
fault should occur.
• Readily accessible disconnect/protection device(s) must be incorporated in the
building installation wiring in order to remove power from the equipment in the event
of an emergency or required servicing.
• Disconnect all ac branch circuits prior to servicing. Multiple sources of ac may be
present.
• CAUTION – DOUBLE POLE/NEUTRAL FUSING o ATTENTION. Double pôle/fusible sur le neutre.
• Installing fuses or circuit breakers not specified for use in these distribution modules
may result in injury to service personnel or equipment damage. Use only replacement
parts listed in this manual and on the equipment drawings.
• The telecom-type (for example, GMT type) fuses can produce sparks during
interruption or clearing of a fault on a high energy circuit. Use only fuses provided
with safety caps for this type of circuit. Installing telecom-type fuses not equipped
with safety caps may result in injury to service personnel.
Issue 2.0, June 3, 2009 12
Infinity D Power System Installation Guide: -48V Plants H2007001
• While installing batteries, follow all safety precautions outlined in the appropriate
battery product manuals.
• The intra-building port(s) of the equipment or subassembly is suitable for connection
to intrabuilding or unexposed wiring or cabling only. The intra-building port(s) of the
equipment or subassembly MUST NOT be metallically connected to interfaces that
connect to the OSP or its wiring. These interfaces are designed for use as intrabuilding interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE,
Issue 4) and require isolation from the exposed OSP cabling. The addition of Primary
Protectors is not sufficient protection in order to connect these interfaces metallically
to OSP wiring. The Ethernet port is suitable for connection only to shielded intrabuilding cabling grounded at both ends.
Issue 2.0, June 3, 2009 13
Infinity D Power System Installation Guide: -48V Plants H2007001
Warning Statements and Safety Symbols
The symbols may sometimes be accompanied by some type of statement; e.g.,
“Hazardous voltage/energy inside. Risk of injury. This unit must be accessed only by
qualified personnel.” Signal words as described below may also be used to indicate the
level of hazard.
Indicates the presence of a hazard that will cause death or severe
DANGER
WARNING
CAUTION
personal injury if the hazard is not avoided.
Indicates the presence of a hazard that can cause death or severe
personal injury if the hazard is not avoided.
Indicates the presence of a hazard that will or can cause minor
personal injury or property damage if the hazard is not avoided.
This symbol identifies the need to refer to the equipment
instructions for important information.
These symbols (or equivalent) are used to identify the presence of
hazardous ac mains voltage.
This symbol is used to identify the presence of hazardous ac or dc
voltages. It may also be used to warn of hazardous energy levels.
One of these two symbols (or equivalent) may be used to identify
the presence of rectifier and battery voltages. The symbol may
sometimes be accompanied by some type of statement, for example:
“Battery voltage present. Risk of injury due to high current. Avoid
contacting conductors with uninsulated metal objects. Follow safety
precautions.”
One of these two symbols may be used to identify the presence of a
hot surface. It may also be accompanied by a statement explaining
the hazard. A symbol like this with a lightning bolt through the hand
also means that the part is or could be at hazardous voltage levels.
This symbol is used to identify the protective safety earth ground for
the equipment.
This symbol is used to identify other bonding points within the
equipment.
This symbol is used to identify the need for safety glasses and may
sometimes be accompanied by some type of statement, for example:
“Fuses can cause arcing and sparks. Risk of eye injury. Always wear
safety glasses.”
Issue 2.0, June 3, 2009 14
Infinity D Power System Installation Guide: -48V Plants H2007001
Precautions
When working on or using this type of equipment, the following precautions should be
noted:
• This unit must be installed, operated, and serviced, only by qualified technical
personnel, who have the necessary knowledge and practical experience with electrical
equipment and who understand the hazards that can arise when working on this type
of equipment. Equipment in these locations will contain parts at HAZARDOUS
energy levels that can be directly accessed and are only protected by guarding and/or
warning.
• The equipment may be powered by multiple ac inputs. Disconnect all AC branch
circuits before servicing. Do not disconnect grounding, bonding conductors, or
permanent bonding provisions unless all ac inputs are disconnected.
• High leakage current exists. Grounding/Earth connection must be provided before
connecting supply.
• Batteries may be connected in parallel with the output of the rectifiers. Turning off
the rectifiers will not necessarily remove power from the bus. Make sure the battery
power is also disconnected and/or follow safety procedures while working on any
equipment that contains hazardous energy/voltage.
• Hazardous energy and voltages are present in the unit and on the interface cables that
can shock or cause serious injury. Follow all safety warnings and practices when
servicing this equipment. When equipped with ringer modules, hazardous voltages
will be present on the ringer output connectors.
In addition to proper job training and safety procedures, the following are some basic
precautions that should always be used:
• Use only properly insulated tools.
• Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).
• Wear safety glasses. Fuses can produce sparks. High energy levels on buses and
distribution components can produce severe arcing.
• Test circuits before touching.
• Lock out and tag circuit breakers/fuses when possible to prevent accidental turn on.
• Be aware of potential hazards before servicing equipment.
• Identify exposed hazardous electrical potentials on connectors, wiring, etc. (note the
condition of these circuits, especially wiring).
• Use care when removing or replacing covers; avoid contacting circuits.
Issue 2.0, June 3, 2009 15
Infinity D Power System Installation Guide: -48V Plants H2007001
Handling Batteries
• To direct attention to the possible source of danger from battery gases, post one or
more warning signs, lettered in large characters, in a conspicuous location near the
battery. For example:
• Fully brief anyone who is permitted access to battery areas on the hazards of handling
lead-acid batteries. Make it clear to anyone handling, unpacking, or installing leadacid batteries that they contain electrolyte (sulfuric acid and water). Everyone must
wear protective equipment such as rubber gloves, rubber aprons, full face mask, and
splash-proof goggles when performing any activity involving handling of batteries or
cells containing electrolyte.
• A storage battery gives no indication by its appearance of the potential energy stored
in it. All lead-acid storage cells/batteries have enormous short circuit capability which
can result in serious burns. Use extreme care to avoid shorting out cell and/or battery
terminals. Shorting a cell or battery with a non insulated tool can vaporize or throw
the tool.
• All lead-acid batteries generate hydrogen gas, even under open circuit conditions. If
not permitted to escape, this gas can build up to explosive concentrations. NEVER
tamper with or block the vent caps of the batteries. A damaged gas vent cap could
become clogged, resulting in an explosion due to internal pressure. Such an explosion
could short circuit other battery modules and result in a fire. ALWAYS place
batteries in a well-ventilated area. NEVER place battery modules in a sealed
environment.
• In case of electrolyte contact with the skin, remove the electrolyte immediately by
flushing the affected area with large amounts of plain tap water. In case of electrolyte
in the eye, pour water into the inner corner of the eye and allow at least one quart of
water to run over the eye and under the eyelid. Eye injuries should be treated by a
physician immediately.
Issue 2.0, June 3, 2009 16
Infinity D Power System Installation Guide: -48V Plants H2007001
Special Installation Notes
Deutsch
Installationsanleitung
Eingangsspannung ( Voltage ) :+24, -48
Eingangsstrom ( Current ) : Max 1200A
Eingangsleistung ( Watts ) :
Nennfrequenz ( Frequency ) : 50 / 60 Hz
Abmessungen sind nur zur Referenz : 660mm x 533.4mm x 2133.6mm
( Dimensions are for reference only )
Max. Umgebungstemperatur : max. 45 deg. C
( Max. Operation temperature )
Achtung: Für kontinuierlichen Feuerschutz sollte die Sicherung nur mit einer des
gleichen Types ersetzt werden.
Sicherungswert :
( Warning : For continued protection against fire replace with same type and rating of
fuse )
Das System ist ein Gerät der Schutzklasse I / Überspannungs Kategorie II
( Power Supply is a Class I equipment / overvlotage category II )
Ausgangsspannungen und -stöme: DC 58 V / SELV
( Output Voltage and Current )
--Das Gerät darf nur in Räumen mit beschränktem Zutritt aufgestellt werden.
( Nur ausgebildetes Personal )
--Nur für Aufstellung auf Boden oder einer anderen brennbaren Oberfläche
geeignet.
--Das Gerät hat keinen eigenen Ausschalter, es muß daher mit einem Ein- und
Ausschalter im Versorgungskreis versehen sein.
--Das Gerät ist für den Einbau in IT- Geräte in einem Rahmen bestimmt (siehe weitere
Anleitung)
--Beim Einbau des Gerätes ist daraf zu achten das alle Anforderungen gemäß EN60950
eingehalten werden.
ACHTUNG: HOHER ABLEITSTROM
VOR ANSCHLUSS AN DEN VERSORGUNGSSTROMKR EIS
UNBEDINGT ERDUNGSVERBINDUNG HERSTELLEN
Issue 2.0, June 3, 2009 17
Infinity D Power System Installation Guide: -48V Plants H2007001
Español
Notas especiales para instalaciones en países que hablan español.
• Instrucciones de instalación
(Installation Instructions)
• Voltaje (Voltage):
+24, -48
• Corriente (Current):
Max 1200 A
• Frecuencia (Frequency):
50/60Hz
• Voltaje y corriente de salida (Output Voltage and Current):
• Temperatura máxima de operación (Maximum Operation Temperature):
45°C (113°F)
• Sin cabina contra incendios, suelo no combustible
(No fire enclosure, non-combustible floor)
• Evaluado en EN60950
(Evaluated to EN60950)
Issue 2.0, June 3, 2009 18
Infinity D Power System Installation Guide: -48V Plants H2007001
UL Ratings as reflected in the UL Report in May 2009. Please note the available rectifier
output is reduced from the nameplate rating when converters are introduced to the system.
ELECTRICAL RATING:
J2008001
Model
H2007001
Type A(+)
H2007001
Type B(+)
H2007001
Type C(+)
H2007001
Type D(+)
(+) May be followed by –SD. When followed by –SD, the AC input will be up to 16 or 8 feeds rated:
(16)x 15 amps each feed or (8)x 30 amps each feed.
(++) The marked output voltage may be any voltage range or specified voltage as long as it is within
the range specified in the electrical rating table.
(+++) Maximum 45°C ambient for output rating not exceeding 960A charge and 1200A discharge.
Otherwise, 40°C ambient. The secondary (converter) input is a load for the primary (rectifier)
output. This must be considered when loading the plant to its maximum rated primary output.
Battery
Panel
L001, L002,
L005, or
L006
L003, L004,
L007, or
L008
L001, L002,
L005, or
L006
L003, L004,
L007, or
L008
L001, L002,
L005, or
L006
L003, L004,
L007, or
L008
L001, L002,
L005, or
L006
L003, L004,
L007, or
L008
V (50/60Hz) Current Vdc (++) Max Current(+++) Max Power
(+) - Includes all List options.
(++) - Maximum amps that the distribution section of the shelf is rated. Power supply output may be
(+++) - Plant ratings that exceed 640A charge and 800A discharge: top shelf adjacent to battery panel
(++++) - The J2007002 L051 shelf option is ten additional bullet-breaker positions located on right side
(+++++) - Plant ratings that exceed 640A charge and 800A discharge: top shelf adjacent to battery panel
400 charge
500 discharge
Lineage Power
rated less.
shall not exceed 336A charge and 400A discharge.
of shelf.
shall not use either a 150A 2-pole or 250A 3-pole circuit breaker.
QSGMT6
J2007002
L005
(++++)
57.6A total; 15A
rated fuse/position
3-70A 1-pole
100A 2-pole
R/C (QPQY2/8); uses
R/C fuse (JDYX2) by
SOC, Type AX1 or
Cumulative circuit
breaker ratings cannot
exceed 200A.
POWER SUPPLIES ALLOWED
Power Supply Model(#) Type Manufacturer Certification
NE075AC24 rectifier
NE030DC48 converter
NE100AC24 rectifier
NE050AC48 rectifier
NE075DC24 converter
(#) - May be provided with a non-safety affecting suffix.
IN H2007001 POWER DISTRIBUTION CENTER
Lineage Power
R/C (QQGQ2/QQGQ8)
AX1-B
Issue 2.0, June 3, 2009 20
Infinity D Power System Installation Guide: -48V Plants H2007001
4. Installation
Preparation
Safety
Please review all safety warnings in Section 3 before beginning the installation process.
Observe all warnings and labels on the equipment.
WARNING: Due to the possibility of working on energized circuits
during these procedures, all tools and test equipment must be insulated in
an approved manner. Proper ESD protection is required in order to prevent
ESD damage to the equipment.
WARNING: Only qualified personnel should install and service the
power system and plug-in modules. Hazardous energy and voltages are
present in the unit and on the interface cables and will shock or cause
serious injury or death if safety precautions are ignored. Follow all safety
warnings and practices when servicing this equipment.
Installation Sequence
1. Anchor the Frame
2. Ground the Framework
3. Install Batteries
4. Connect ac Utility
5. Connect Central Office Ground
6. Connect External Battery Cables
7. Wire -48 V dc loads and circuit breakers
8. Wire +24 V dc loads and circuit breakers
9. Install Rectifiers and Converters
10. Install Battery Instrumentation
Wiring Guidelines
• All electrical connections should be made using the proper crimping tools and dies
and should be torqued to values specified.
• All building wiring should comply with the NEC and other applicable local codes.
• The temperature rating of the wire must be 90°C minimum. Wire gauge must be
sized based on 75°C wire and the ampacity of the associated branch-circuit
protection.
• Wiring internal to enclosed equipment cabinets must be rated no less than 105°
Celsius.
Issue 2.0, June 3, 2009 21
Infinity D Power System Installation Guide: -48V Plants H2007001
Packaging
• All packages should be opened with a box cutter with the blade minimally exposed so
that only the sealing tape is cut.
• Save all packaging material until the system has been powered up and all parts are
operating within specifications
.
Installation Tools
You will need the following tools to install and test the Infinity D.
• Wire cutters and strippers
• Heat shrink gun
• 5/16-inch (8 mm) hex driver
• Digital meter with an accuracy of
±0.02%
• Screw drivers (flat-blade and
Phillips)
• ESD wrist strap
• 48 or/and 24V test load
• Calibrated clamp-on dc current
meter (0.1 ADC sensitivity)
• Torque wrench
• Socket wrenches:
• 7/16” and 9/16” for load and
battery connections;
• 19 mm for anchor bolts;
• 12" extension for socket
• Masonry drill kit as required
• Compression for installation of
various compression lugs
• Protective canvas
• Insulating rubber mat
• Standard insulated installation tools,
screwdrivers, etc.
• Required Insulated Tool Kit 1000v
DC Telecom set to include ESD
protection
Issue 2.0, June 3, 2009 22
Infinity D Power System Installation Guide: -48V Plants H2007001
Anchor the Frame
Floor Mounted Frames
Mount the selected frame securely to the floor using floor anchors rated for the Seismic Zone of the site.
We sell a floor anchor kit (847135688) with 4 Hilti 12mm Cap bolts that may be appropriate for the frame
you have selected.
Step Action
Mark floor using template, frame itself, or measurements in Appendix B if 26” frame selected.
1.
Drill anchor holes.
2.
Caution: Follow safe floor drilling procedures to prevent possible asbestos exposure.
Place frame and install floor anchors according to manufacturer requirements.
3.
Battery or Battery Stand Mounted Half- and Third-Height
Frames:
Step Action
Place and secure frame to battery or battery stand per instructions provided with the battery
1.
stand or adapter.
Ground the Framework
Connect Frame Ground
Step Action
Select a Frame Ground landing on the top cross rail of the frame, or on the bottom or the rack
1.
rails depending on frame and site parameters.
Remove covering tape and clean. If required by local code or practice, treat with an oxidation
2.
inhibitor such as NO-OX.
Secure Frame Ground connection
3.
Use 7/16” socket. Torque to 65 in·lbs. (7 Nm)
Battery or Battery Stand Mounted Frames:
If required by local code or practice, battery or battery stand mounted frames may be
grounded to the frame or chassis of the other equipment. Select a Frame Ground landing
at the side of the frame and clean.
Step Action
Select a Frame Ground landing at the side of the frame and clean.
1.
2.
3.
Remove covering tape and clean. If required by local code or practice, treat with an oxidation
inhibitor such as NO-OX.
Secure Frame Ground connection.
Use 7/16” socket. Torque to 65 in·lbs. (7 Nm)
Issue 2.0, June 3, 2009 23
Infinity D Power System Installation Guide: -48V Plants H2007001
Install Batteries
WARNING: All batteries contain hazardous electrical energy. Lead-acid
batteries contain sulfuric acid and explosive hydrogen gas. Follow all
precautions noted in the literature accompanying the batteries. Use only
insulated tools.
CAUTION: Equipment frame anchoring, load rating, and seismic zone
rating should be verified before field installing trays and batteries.
Installing External Batteries
Step Action
Place batteries on battery trays, battery stands, or other satisfactory supporting surface and
1.
interconnect per manufacturer’s instructions to create 48V strings as required.
Yes - physically mount switch to an
2.
appropriate place and ensure it is in the OFF
position prior to making any connections.
Connect the battery hot conductor(s) to the line side of the disconnect switch and torque
3.
connection per manufacturer's specification.
Connect the load side conductor to the disconnect switch and torque connection per
4.
manufacturer's specification.
Is an external disconnect switch being used?
No – Finished.
Issue 2.0, June 3, 2009 24
Infinity D Power System Installation Guide: -48V Plants H2007001
Mount the Subframe System to the Frame or Cabinet
The Infinity D is provided in integrated Subframes. Each Subframe contains one Battery
Connection Module, one Pulsar Controller and one or more Rectifier System
Modules. Converter System Modules are not required to have a valid system and are
typically on the bottom of the power equipment stack in any given Subframe. Step 1
below shows the elements included in the smallest valid Subframe.
Step Action
Mount the Subframe to the rack.
1.
Use the fasteners and torque values provided by the frame supplier to secure flanges on the right
2.
and left hand frame rails. Use at least 2 rack screws per side for each element in the Subframe.
This Subframe requires at least 8 rack screws.
Issue 2.0, June 3, 2009 25
Infinity D Power System Installation Guide: -48V Plants H2007001
Wire the Subframe
Identify Areas for Each Type of Wiring
The Infinity D is designed for overhead wiring.
Step Action
Look at the framework from the top.
1.
Location
for
1” AC
Conduit
Drop
Battery Hot
Terminations
TOP VIEW
Alarm & Control
[secured near door hinge]
Infinity D Framework – Top View
Address: CO Grounding, AC wiring, Battery wiring, DC wiring and Alarm & Control wiring.
2.
CO Ground (RTN)
DC Distribution
Battery Return
Terminations
Issue 2.0, June 3, 2009 26
Infinity D Power System Installation Guide: -48V Plants H2007001
Connect ac Utility
Circled below is the part of the Block Diagram to be wired first.
Issue 2.0, June 3, 2009 27
Infinity D Power System Installation Guide: -48V Plants H2007001
WARNING: Disconnect all ac branch circuits prior to making ac
connections to the system. When connecting to utility source, ensure
compliance to all local and national wiring rules.
There are only 2 options for AC wiring: Four 20A AC circuit breakers per shelf or two 40A AC
circuit breakers per shelf .If you have 4 AC circuit breaker per shelf, one for each of the rectifier
positions, start at step 1 here. If you have 2 AC circuit breakers per shelf, one AC circuit
breaker for each pair of rectifiers, skip this procedure and go to the next procedure in this
section.
Step Action
Loosen the screws that secure the AC
1.
wiring cover.
Loosen
Screws
Remove the AC wiring cover.
2.
Remove the conduit knockout.
3.
At the AC service panel install a 20A double pole circuit breaker for each rectifier position. Choose
4.
the breaker size according to code for the wire type and environmental conditions for your site. Use
10 AWG wire for each rectifier.
Route two wires for each active rectifier position through 1 inch conduit and fitting, up to a total of
5.
8 active wires and one ground (PE), into the AC wiring compartment.
Terminate the PE (ground) wire to the
6.
chassis using a double hole lug (on 5/8 inch
centers) with a UL accepted crimp and tool.
Terminate
Ground Wire
Illustration of
wiring flow
through conduit
hole
Torque ground lug nuts to 65 inch·lbs or 7N·m using a 7/16 inch socket wrench.
7.
Strip 0.32 inches (8 mm) of insulation off the end of each AC wire.
8.
Examine the AC input terminal block provided in your shelf. Is the terminal block of single level
9.
configuration similar to that shown in the figure above?
Issue 2.0, June 3, 2009 28
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
Yes, insert each wire into the bottom of the
terminal block according to these diagrams:
R1 R2 R3 R4
L1 L2 L2 L3 L3 L1L1L2
200-240Vac Wiring Diagram for 3 Wire
+PE
R1 R2 R3 R4
L1 N L2 N L3 NL1N
200-240Vac Wiring Diagram for 3 Wire +
neutral +PE [NON-US ONLY]
R1 R2 R3 R4
L1 L2 L1 L2 L1 L2L1L2
200-240Vac Wiring Diagram for 2 Wire +
PE
Make sure all strands are captured in the appropriate wire clamp.
10.
Torque each wire clamp to 5-7 inch· lbs or 0.6-0.8 N·m.
11.
Secure conduit fitting.
12.
Replace AC Termination door.
13.
Tighten Screws to 5-7 inch·lbs or 0.6-0.8 N·m.
14.
No, the shelf has a tiered terminal block that can
accept up to 8 AWG wires. Insert each feed wire into
the bottom of the terminal block according to these
diagrams:
R1
L1
R1
L2
200-240Vac Wiring Diagram for 3 Wire +PE
R1
L1
R1
N
200-240Vac Wiring Diagram for 3 Wire + neutral
R1
L1
R1
L2
200-240Vac Wiring Diagram for 2 Wire + PE
R2
L2
R2
L3
R2
L2
R2
N
+PE [NON-US ONLY]
R2
L1
R2
L2
R3
L3
R3
L1
R3
L3
R3
N
R3
L1
R3
L2
R4
L1
R4
L2
R4
L1
R4
N
R4
L1
R4
L2
Issue 2.0, June 3, 2009 29
Infinity D Power System Installation Guide: -48V Plants H2007001
If you have one AC circuit breaker for each pair of rectifiers, start here.
Step Action
Loosen the screws that secure the AC
1.
wiring cover.
Loosen Screws
Remove the AC wiring cover.
2.
Remove the conduit knockout.
3.
At the AC service panel install a 40A double pole circuit breaker for each pair of rectifiers. Use 8
4.
AWG wire.
Route two 8 AWG wires for each pair of active rectifier positions through 1 inch conduit and
5.
fitting, and one 8AWG ground (PE), into the AC wiring compartment.
Terminate the PE (ground) wire to the
6.
chassis using a double hole lug (on 5/8 inch
centers) with a UL accepted crimp and tool.
Terminate
Ground Wire
Illustration of
wiring flow
through conduit
hole
Torque ground lug nuts to 65 inch·lbs or 7N·m using a 7/16 inch socket wrench.
7.
Break out the plastic dividers in 4 places as
8.
indicated in the diagram.
R1
L1
R1
L2
4 Locations where dividers are removed
R2
L1
R2
L2
R3
L1
R3
L2
R4
L1
R4
L2
Issue 2.0, June 3, 2009 30
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
Insert the provided jumpers in the 4
9.
locations where the dividers were removed.
Torque each of the 8 jumper retention screws to 10 inch·lbs or 1.1 N·m.
10.
Insert each feed wire into the bottom of the
11.
terminal block according to this diagram.
The jumper straps from the previous steps
assure that rectifiers 2 and 4 are powered:
R1
L1
R1
L2/European N
200-240Vac Wiring Diagram for 2 Wire + PE
R2
R2
L2/ European N
R3
L1
R3
R4
R4
Photo indicating positions 1 and 3 are powered .
Strip 0.32 inches (8 mm) of insulation off the end of each AC wire.
12.
Make sure all strands are captured in the appropriate wire clamp.
13.
Torque each wire clamp to 5-7 inch·lbs or 0.6-0.8 N·m.
14.
Secure conduit fitting.
15.
Replace AC Termination door.
16.
Tighten Screws to 5-7 inch·lbs or 0.6-0.8 N·m.
17.
Issue 2.0, June 3, 2009 31
Infinity D Power System Installation Guide: -48V Plants H2007001
This page intentionally left balnk.
Issue 2.0, June 3, 2009 32
Infinity D Power System Installation Guide: -48V Plants H2007001
Wire the Battery Connection Module
Circled below is the part of the Block Diagram to be wired next.
Issue 2.0, June 3, 2009 33
Infinity D Power System Installation Guide: -48V Plants H2007001
Connect Central Office Ground (COG)
Step Action
1.
Locate CO Ground Termination
Busbar for DC Return.
Note: Landings are compatible with lugs
with 1” hole spacing for 3/8” hardware.
If required by local code or practice, treat
with an oxidation inhibitor such as
NO-OX.
Use 9/16” socket. Torque to 240 in·lbs (27
3.
Nm)
Issue 2.0, June 3, 2009 34
Infinity D Power System Installation Guide: -48V Plants H2007001
Connect External Battery Cables
Battery Cable landings are located at the top of the frame. The return is on your right and
the hot or -48V side is on your left. The extra plastic insulators around the battery bus
bars on the left confirm that this is the electrically hot side with respect to earth.
Step Action
Loosen the four screws that secure the Battery Hot Termination cover located on the left side of
1.
the Battery Connection Module.
Loosen Screws
Lift off the Battery Hot Termination Cover to reveal the -48V Battery lead termination bus bar.
2.
Issue 2.0, June 3, 2009 35
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
Secure the Hot Lead for each battery string, starting from the middle of the bay and working to
3.
the outside. Use a double hole lug with holes on 1 inch centers.
Hardware list for each termination is:
(2) 801273129 3/8-16 x 1in bolt
(2) 801829607 3/8-inch lockwasher
(2) 802841635 3/8-inch flatwasher
If required by local code or practice, treat with an oxidation inhibitor such as NO-OX.
Note: Landings are compatible with lugs with 1” hole spacing for 3/8” hardware.
Use 9/16” socket. Torque each bolt to 240 in·lbs or 27Nm
4.
Replace Cover
5.
Re-torque screws to ~6 in·lbs ( 0.5 Nm)
6.
Loosen the four screws that secure the Return Termination cover located on the right side of the
7.
Battery Connection Module.
Loosen
Issue 2.0, June 3, 2009 36
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
Lift off the Return Termination Cover to reveal the Battery Return lead termination bus bar.
8.
Secure the Return Lead for each battery string. Use the back bus bar, starting toward the middle
9.
of the bay and working to the outside. Use a double hole lug with holes on 1 inch centers.
Hardware list for each termination is:
(2) 801273129 3/8-16 x 1in bolt
(2) 801829607 3/8-inch lockwasher
(2) 802841635 3/8-inch flatwasher
If required by local code or practice, treat with an oxidation inhibitor such as NO-OX.
Note: Landings are compatible with lugs with 1” hole spacing for 3/8” hardware.
Use 9/16” socket. Torque each bolt to 240 in·lbs or 27Nm
10.
Replace Cover
11.
Issue 2.0, June 3, 2009 37
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
Re-torque screws to ~6 in·lbs ( 0.5 Nm)
12.
Battery Connection Module
(terminated with 1 representative battery string)
Issue 2.0, June 3, 2009 38
Infinity D Power System Installation Guide: -48V Plants H2007001
Wire -48V DC Loads
Circled below is the -48V Load Wiring part of the Block Diagram wired next.
Issue 2.0, June 3, 2009 39
Infinity D Power System Installation Guide: -48V Plants H2007001
Install dc Bullet Style Circuit Breaker Modules for -48V Loads
This plant makes use of a [circuit breaker]/[lug landing] assembly for each normal format
bullet style circuit breaker. This section illustrates how these are installed.
CAUTION: Ensure Circuit Breakers are in the OFF position prior to installation.
CAUTION: In order to meet UL Listing temperature limits in the event of overload,
high current rated Bullet Breaker locations must meet all of these layout restrictions:
• Maximum rating of 1-pole breakers is 70A.
• Maximum rating of 2-pole breakers is 100A.
• Maximum grouping of 250 A before skipping a circuit breaker position.
Step Action
1.
Open the Rectifier System Module door
2.
Locate Circuit Breaker (CB) mounting
panel.
Open door by pressing here
Locate CB mounting panel
Issue 2.0, June 3, 2009 40
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
3.
Insert a Circuit Breaker Termination module starting in the lowest position:
4.
Torque to 4 in lbs:
Issue 2.0, June 3, 2009 41
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
5.
Plug in Circuit Breaker:
6.
7.
8.
9.
10.
Mark the label to the left of the circuit breaker according to standard practice in your network.
Feed a wire pair from the top of the bay down to the desired location.
Locate and dress the pair to tie bars in the right back corner of the DC wiring area:
Terminate the feeding lead on the circuit breaker lug landing using the hardware provided.
Terminate the return on the return bus located on the back wall of the distribution area using the
hardware provided.
Issue 2.0, June 3, 2009 42
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
11.
Torque all fasteners to 65 in lbs (7 Nm) using an insulated extension at least 5 inches long.
Two-Pole and Three-Pole Breakers:
12.
13.
14.
15.
16.
17.
18.
19.
20.
Secure Two-Pole and Three-Pole Circuit Breaker and Lug Landing Assemblies in the same
fashion.
Mark the label to the left of the circuit breaker according to standard practice in your network.
Feed a wire pair from the top of the bay down to the desired location.
Locate and dress the pair to tie bars in the right back corner of the DC wiring area.
Terminate the send using a suitable lug with 5/16 inch holes on 1 inch centers using hardware
provided.
Torque the send lug nuts to 130 in·lbs (15 Nm) using a ½ inch socket.
Terminate the Return using a suitable lug with 1/4 inch holes on 5/8 inch centers using hardware
provided.
Torque the Return lug nuts to 65 in·lbs (7 Nm).
Returns for 4/0 cable should be terminated to the CO Ground bar in the Battery Termination
Module.
Issue 2.0, June 3, 2009 43
Infinity D Power System Installation Guide: -48V Plants H2007001
This page intentionally left blank.
Issue 2.0, June 3, 2009 44
Infinity D Power System Installation Guide: -48V Plants H2007001
Wire +24V DC Loads
Circled below is the +24V Load Wiring part of the Block Diagram wired next.
Issue 2.0, June 3, 2009 45
Infinity D Power System Installation Guide: -48V Plants H2007001
Install dc Bullet Style Circuit Breaker Modules for +24V Loads
This plant makes use of a [circuit breaker]/[lug landing] assembly for each normal format
bullet style circuit breaker. This section illustrates how these are installed.
CAUTION: Ensure Circuit Breakers are in the OFF position prior to installation.
CAUTION: In order to meet UL Listing temperature limits in the event of overload,
high current rated Bullet Breaker locations must meet all of these layout restrictions:
• Maximum rating of 1-pole breakers is 70A.
• Maximum rating of 2-pole breakers is 100A.
• Maximum grouping of 250 A before skipping a circuit breaker position.
Step Action
1.
Open the Converter System Module door
2.
Locate Circuit Breaker (CB) mounting
panel.
Open door by pressing here
Issue 2.0, June 3, 2009 46
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
3.
Insert a Circuit Breaker Termination module starting in the lowest position:
4.
Torque to 4 in lbs:
Issue 2.0, June 3, 2009 47
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
5.
Plug in Circuit Breaker:
6.
7.
8.
9.
10.
11.
Mark the label to the left of the circuit breaker according to standard practice in your network.
Feed a wire pair from the top of the bay down to the desired location.
Locate and dress the pair to tie bars in the right back corner of the DC wiring area:
Terminate the send on the circuit breaker lug landing using the hardware provided.
Terminate the return on the return bus located on the back wall of the distribution area using the
hardware provided.
Torque all fasteners to 65 in·lbs (7 Nm) using an insulated extension at least 5 inches long.
Secure DC Pairs Securely
to Tie Bars
Issue 2.0, June 3, 2009 48
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
Two-Pole and Three-Pole Breakers:
12.
13.
14.
15.
16.
17.
18.
19.
20.
Secure Two-Pole and Three-Pole Circuit Breaker and Lug Landing Assemblies in the same
fashion.
Mark the label to the left of the circuit breaker according to standard practice in your network.
Feed a wire pair from the top of the bay down to the desired location.
Locate and dress the pair to tie bars in the right back corner of the DC wiring area.
Terminate the send using a suitable lug with 5/16 inch holes on 1 inch centers using hardware
provided.
Torque the send lug nuts to 130 in·lbs (15 Nm) using a ½ inch socket.
Terminate the Return using a suitable lug with 1/4 inch holes on 5/8 inch centers using hardware
provided.
Torque the Return lug nuts to 65 in·lbs (7 Nm).
Returns for 4/0 cable should be terminated to the CO Ground bar in the Battery Termination
Module.
Issue 2.0, June 3, 2009 49
Infinity D Power System Installation Guide: -48V Plants H2007001
This page intentionally left blank.
Issue 2.0, June 3, 2009 50
Infinity D Power System Installation Guide: -48V Plants H2007001
p
Wire Loads served by GMT Type Fuses
Step Action
1.
Open the Converter or Rectifier System
Module door
2.
3.
4.
Locate Circuit Breaker (CB) mounting
panel.
Install a 6 position GMT type fuse holder
in 2 Circuit Breaker distribution positions
(see picture)
Terminate the return busbar according to
the instructions provided with the GMT
fuse holder kit.
Return
Termination
oints
5.
Complete installation and wiring
according to the instructions provided
with the kit.
Issue 2.0, June 3, 2009 51
Infinity D Power System Installation Guide: -48V Plants H2007001
Verify Previous Installation Steps
Perform the following verification checklist after installation of batteries and wiring:
Step Action
Verify cabinet is properly grounded (using Digital Multimeter (DMM)).
1.
Verify the ac equipment ground is properly connected.
2.
Verify the correct ground cable gauge is used. Use the standard grounding principles for your
3.
office.
Verify the ac voltage supplied matches the ac input voltage of the rectifiers.
4.
Verify all cables are properly installed for the distribution and marked with labels to identify
5.
them as 48 volt or 24 volt circuits.
Examine to assure no sharp corners are in contact with dressed wires. Modify to correct any
6.
problems found.
Check for conductor clearance within the bay associated with high power.
7.
Check that all breakers are off and all fuses not inserted.
8.
Verify the battery contactors are open, if equipped. Manually operate them to the open position,
9.
if necessary, by pushing the contacts apart.
10.
11.
12.
13.
14.
15.
Verify the polarity of all battery cables (using DMM).
Verify no shorts are present between frame ground and the ac service. Measure resistance from
each ac input line terminal block position to frame ground.
Verify shelves and rectifier positions are properly identified. Label positions as necessary.
Verify battery negative cables are connected to the appropriate bus bar.
Verify battery positive cables are connected to the appropriate bus bar.
Visually verify the RS485 cables are properly installed and that shelf ID settings at the rear of
the frame are: [Shelf 1, Shelf 2, Shelf 3, etc.] from top to bottom.
Issue 2.0, June 3, 2009 52
Infinity D Power System Installation Guide: -48V Plants H2007001
Install Rectifiers and Converters
Circled here are the Rectifier and Converter Installation parts of the Block Diagram.
Issue 2.0, June 3, 2009 53
Infinity D Power System Installation Guide: -48V Plants H2007001
Rectifier/Converter Installation Procedure
Step Action
Slide the rectifier/converter partially into a
1.
slot.
Open the faceplate by sliding the black latch
2.
to the left to release the faceplate.
Push the unit firmly into the shelf until seated.
3.
Yes – Proceed to Step 4. No – Go to Step 5.
Install an air filter by placing it inside the faceplate.
4.
Swing the faceplate closed until it is secured
5.
by the latch.
Using optional air filter?
After 30 seconds, verify green LED and only green LED is on.
6.
If this isn’t the case, see the Troubleshooting section.
Rectifier/Converter Removal Procedure
Step[dmb1]Action
1.
2.
Open the faceplate to disengage the
rectifier/converter.
Remove the unit from the shelf.
Issue 2.0, June 3, 2009 54
Infinity D Power System Installation Guide: -48V Plants H2007001
Use the above rectifier installation procedure as needed in the following steps. Note: You
will be directed to use the Menu commands from the front of the Pulsar Controller.
Step Action
Turn on ac service circuit breakers to apply power to the system rectifier positions.
1.
Install a rectifier in an available rectifier position.
2.
Wait until the rectifier establishes communications with the controller (the red Fail LED stops
3.
flashing).
Verify green Norm LED is lit.
4.
Apply 10 amperes of load to the system.
5.
Verify (if equipped) the contactor closes and connects the battery strings.
6.
If an audible alarm is present, press the ENTER key to MUTE the audible alarm. Check all
7.
connections. If the alarm does not clear go to the troubleshooting section.
Verify all LEDs are green on the controller and the display is visible with the proper voltage
8.
shown.
Increase the system load current to 20 amperes.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
Install rectifier in the next position.
Wait until the rectifier establishes communications with the controller (the red Fail LED stops
flashing).
Verify green Norm LED is lit.
Verify the two rectifiers are present and verify the rectifier output currents by using the front
panel:
MENU > STATUS > RECTIFIERS > RECTIFIER CU R RENTS.
Increase the system load current to 50 amperes.
Continue to add rectifiers as required.
Verify the rectifiers share the load and the voltage regulation is correct. Rectifiers should load
share after 2 minutes to within 5% of the total average output.
Verify front panel display voltage is within 0.5% of the Float Setpoint.
Remove a rectifier and ignore the request to remove missing equipment.
Verify the controller identifies the rectifier as missing to verify that the Minor Communication
Fail alarm is operational.
Re-install the rectifier and verify that the alarm clears.
Repeat the above steps for converters in the Converter System Module.
For more information on the Infinity D Rectifiers and Converters, see the
Troubleshooting section.
Issue 2.0, June 3, 2009 55
Infinity D Power System Installation Guide: -48V Plants H2007001
This page intentionally left blank.
Issue 2.0, June 3, 2009 56
Infinity D Power System Installation Guide: -48V Plants H2007001
Install Battery Instrumentation
Circled here are the Battery Instrumentation Installation parts of the Block Diagram.
Issue 2.0, June 3, 2009 57
Infinity D Power System Installation Guide: -48V Plants H2007001
This page intentionally left blank.
Issue 2.0, June 3, 2009 58
Infinity D Power System Installation Guide: -48V Plants H2007001
Install Battery VT Probes
Install Battery VT Probes without Voltage Monitoring
The QS873A weatherized VT-Probe is provided with 2-pin and 3-pin receptacles and a
1/4-inch ring terminal.
VT-Probe Connections to Controller Connection (Lead Acid)
Step Action
1.
Insert the RJ-45 end of the 848719795 wireset into the Temp Connector on the controller.
Open door by pressing here
Using voltage monitoring?
2.
Yes – Proceed to Step 2. No – Go to Step 3.
Cut the brown voltage sense wire on the 848719795 at the 3-pin connector.
Issue 2.0, June 3, 2009 59
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
3.
4.
5.
6.
7.
8.
9.
10.
Insert the 3-pin connector end into
the receptacle on the closest VTProbe.
Snap the cover closed on the VT-probe.
Place the first probe to the battery post (as in the picture in Step 3).
Note: Probes are typically installed one per string, located in the center of the string.
Verify the number of probes (1) registered with the controller with command:
MENU > STATUS > BATTERIES > TEMP PROBES PRESENT.
Connect either the 848719803 (5-ft) or the 848719811 (10-ft) cable to the 2-position receptacle
of the first probe and to the 3-position receptacle of another probe.
Verify the number of probes (2) registered with the controller with command:
MENU > STATUS > BATTERIES > TEMP PROBES PRESENT.
Repeat Steps 7-8 for each probe until all probes are installed.
When all probes are installed, verify they are connected and operating with command:
MENU > STATUS > BATTERIES > TEMP PROBES PRESENT.
The controller is now ready to take thermal measurements in performing slope thermal
compensation and battery high temperature disconnect. Additional parameters may be set
on the controller to customize this feature.
Install Battery VT Probes with Voltage Monitoring
The figure below shows the interconnection of the maximum number of VT-Probes for
both voltage monitoring and thermal compensation.
All 16 batteries are shown as being monitored for thermal compensation and all four
strings are being monitored for voltage imbalance by the probes in the middle batteries of
all strings.
If your actual interconnection only requires monitoring one battery in each string, the
middle battery in each string should be used when both the voltage imbalance and
thermal compensation features are desired.
Issue 2.0, June 3, 2009 60
Infinity D Power System Installation Guide: -48V Plants H2007001
VT-Probe/Battery Voltage Monitor Connections to Controller (Optional)
Step Action
1.
2.
3.
4.
5.
6.
Insert one RJ-45 end of the 848652947 wireset into the J2 Connector on the controller and the
other end to the first ES771A Remote Voltage Monitor module. Set address switch to 01.
Verify the number of modules (1) registered with the controller with command:
MENU > STATUS > BATTERIES > NUM MIDPT MODULES.
If required, connect another ES771A by connecting an additional 848652947 wireset into RJ-45
receptacles on both modules. Set unique address to 02.
Verify the number of modules (2) registered with the controller with command:
MENU > STATUS > BATTERIES > NUM MIDPT MODULES.
Repeat Steps 3-4 until all required ES771A modules are installed.
When all modules are installed, verify they are connected and operating with command:
MENU > STATUS > BATTERIES > NUM MIDPT MODULES.
Issue 2.0, June 3, 2009 61
Infinity D Power System Installation Guide: -48V Plants H2007001
Step Action
Are the LEDs on the module(s) on (and not red) and are the number of registered modules the
same as the number used?
Yes – Go to Step 9. No – Proceed to Step 7.
7.
8.
9.
Check integrity of all cable connections.
Issue the Clear Events command: MENU > CONTROL / OPERATIONS > CLEAR
EVENTS.
(If the LEDs are still not lit green or if the number of registered modules still does not agree, call
your local field representative.)
Connect the 848719829 (10-ft) cable
to the 3-pin receptacle of the first
ES771A and to the 3-pin receptacle
of the first probe.
10.
11.
12.
13.
14.
15.
16.
Verify the number of probes (1)
registered with the controller with
command:
MENU > STATUS >
BATTERIES > TEMP PROBES
PRESENT.
Connect either the 848719803 (5-ft) or the 848719811 (10-ft) cable to the 2-pin receptacle of the
first probe and to the 3-pin receptacle of another probe.
Verify the number of probes(2) registered with the controller with command:
MENU > STATUS > BATTERIES > TEMP PROBES PRESENT.
Repeat Steps 11-12 until all probes are installed and connected to corresponding ES771A
modules.
When all probes are installed, verify they are connected and operating with command:
MENU > STATUS > BATTERIES > TEMP PROBES PRESENT.
Connect the discrete voltage sense wire from the corresponding Battery Voltage Sense Cable to
one of the three snap-fit pins on the corresponding ES771A module of each battery terminal
where voltage monitoring is required.
Note: 848719803, 848719811 and 848719829 Battery Voltage Sense Cables all come with a
discreet voltage sense wire.
Note: Each ES771A module supports up to three voltage monitoring leads, so if four battery
strings are required the fourth voltage monitor probe must be connected to the second ES771A
module.
Trim and insulate the unused voltage sense wires on all remaining Battery Voltage Sense Cables.
The system is now set to monitor both voltage and temperatures to support the battery
string voltage imbalance, battery high temperature disconnect, and slope thermal
compensation features.
Issue 2.0, June 3, 2009 62
Infinity D Power System Installation Guide: -48V Plants H2007001
Setup Pulsar Controller
Circled below is the controller part of the block diagram. Input & Output Office alarms
are wired to the controller by the customer as are LAN and Temperature Compensation
probes.
Issue 2.0, June 3, 2009 63
Infinity D Power System Installation Guide: -48V Plants H2007001
Install Controller Field Wiring
In addition to the temperature instrumentation, the controller has field connections for
Alarm Inputs, Alarm Outputs and a Local Area Network (LAN).
Step Action
1.
2.
3.
4.
5.
6.
Insert the terminated end of the Alarm Input wireset (CC848817651) into the Input Alarms
connector on the top edge of the controller.
Insert the terminated end of the Office Alarm Output wireset (CC848817635 or similar) into the
Office Alarm connector on the top edge of the controller.
Insert the terminated end of a 10/100Base-T CAT-5 LAN wireset into the LAN connector on the
top edge of the controller.
Open the door to the widest position.
Dress the field wiring using the tie points provided just behind the hinge to up and out the top of
the cabinet.
Check to make sure the door can open and close without straining the connectors.
Issue 2.0, June 3, 2008 64
Infinity D Power System Installation Guide: -48V Plants H2007001
Change LAN to Server Mode
To access the controller directly from a PC, you must first change LAN connection to
server mode.
Step Action
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
Warning: It is always safer to leave the controller in Client mode. This avoids LAN
conflicts should the controller ever be connected to a Local Area Network.
Press Menu or Accept key,
Press down arrow, ▼, to Configuration.
Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to Communications Ports.
Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to Network Settings.
P Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to highlight DHCP.
Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to toggle to SERVER.
Press save,
Press the Back Arrow, §, to return to the default screen.
Wait 2 minutes.
Activate changes by removing the latching PWR connection, located on the lower right of the
controller, until the LEDs extinguish.
Reapply power by reinserting the PWR connection until latched.
Verify Server Mode by pressing Menu>Status>Network Settings>Port 1> to find 192.168.2.1 as
the network address.
■.
■.
■) to advance.
■) to advance.
■) to advance.
■) to advance.
Issue 2.0, June 3, 2008 65
Infinity D Power System Installation Guide: -48V Plants H2007001
Restore the LAN Connection to Client Mode
As good policy, always leave the controller in Client mode.
Step Action
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
Press Menu or Accept key,
Press down arrow, ▼, to Configuration.
Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to Communications Ports.
Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to Network Settings.
P Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to highlight DHCP.
Press the right arrow key, ► (or square “accept” key,
Press down arrow, ▼, to toggle to CLIENT.
Press save,
Press the Back Arrow, §, to return to the default screen.
Wait 2 minutes.
Activate changes by removing the latching PWR connection, located on the lower right of the
controller, until the LEDs extinguish.
Reapply power by reinserting the PWR connection until latched.
Verify Client Mode by pressing Menu>Configuration>Communications Ports>Network
Settings> to show Client mode.
■.
■.
■) to advance.
■) to advance.
■) to advance.
■) to advance.
Issue 2.0, June 3, 2008 66
Infinity D Power System Installation Guide: -48V Plants H2007001
Acceptance Testing
NOTE: The controller may report a limited recharge alarm during these tests.
NOTE: At any time you encounter difficulty with these steps, refer to the
Troubleshooting Section.
Communication with Rectifiers and Converters
Step Action
1.
2.
3.
4.
5.
6.
7.
8.
9.
Place external battery disconnect switches in the ON (connected) position if equipped.
Turn on all ac circuit breakers supplying rectifiers.
Adjust the contrast (if needed) for the site’s ambient condition by using the up and down arrow
keys at the Main Menu.
After approximately 30 seconds, are all lit LEDs on all components including rectifiers, the
controller, LVD control boards, and Aux Displays green?
Yes – Go to Step 7. No – Proceed to Step 4.
Initiate the “Clear Events” and “Uninstall Equipment” operations found under MENU >
CONTROL / OPERATIONS
Interface as needed.
If the controller appears not to be powered or not responsive, verify -48V between C and V2 test
points.
If all lit LEDs still aren’t green, review the installation procedure or refer to the Troubleshooting
section in this manual. The controller display should indicate “0 ALARMS”. The system float
voltage, total load current, and system operating mode should be observable as indicated for no
alarms and the system rectifier voltage should be displayed.
menu. Reference to Appendix A: Pulsar Controller User
If Slope Thermal Compensation (STC) is active, turn off STC using the front panel keypad to
follow this sequence: Menu>Configuration>Batteries>Battery Temp Management>Temperature
Comp>Disable> Save
Check the voltage readings on the controller display.
The Pulsar is factory configured with a rectifier Float voltage set-point of -54.50V
Note that if STC is active or if the connected batteries are not fully charged, the voltages may be
lower.
(If possible, open the external battery disconnect prior to making measurements to eliminate
these effects. If QS873 temperature probes have all ready been installed in the system, then STC
may be active. This will be indicated by the Plant Mode “FLOAT – TEMP COMP”.)
If no Thermal Probes are present, leave Slope Thermal Compensation disabled; otherwise,
Enable Slope Thermal Compensation using the front panel keypad to follow this sequence:
Menu>Configuration>Batteries>Battery Temp Management>Temperature Comp>Enable> Save
Remove and Replace Rectifier and Verify Results:
9.
10.
11.
12.
13.
14.
Remove a rectifier from its slot.
Verify the controller LED and display light amber and indicate a missing rectifier condition.
When the controller prompts to remove equipment press enter ■.
Verify the controller LED and display light green.
Replace the removed rectifier in its original slot.
Verify the controller LED and displays remain lit green.
Issue 2.0, June 3, 2008 67
Infinity D Power System Installation Guide: -48V Plants H2007001
Miscellaneous Alarms (Batteries must be connected)
Distribution Alarms
Step Action
Manually connect a piece of wire from the circuit breaker feed bus to the distribution alarm
1.
strip.
Verify an FAJ – Fuse Alarm Major is reported by the controller.
2.
Remove the wire. Verify the alarm clears.
3.
Repeat test for each distribution panel or sub-system.
ac Fail Alarms
Step Action
Turn off ac circuit breaker feeding a single rectifier.
1.
Verify ACF – ac Fail Minor is reported for the correct rectifier ID.
2.
Restore ac and verify alarms clear and the controller returns to Normal.
3.
Remove ac from two or more rectifiers.
4.
Verify MACF – Multiple ac Fail Major is reported for the correct rectifier IDs.
5.
Turn on all ac circuit breakers and verify alarms clear and the controller returns to Normal.
6.
Battery On Discharge Alarms (Batteries Connected)
Step Action
Change BD alarm to 2 volts below float voltage (MENU > CONFIGURATION > FLOAT
1.
SETTINGS > VOLTAGE ALARMS > BD).
Adjust the load to 50 amperes.
2.
Turn off ac to the system.
3.
Verify the BD alarm occurs when the system voltage decreases to BD threshold.
4.
Verify the BD alarm clears once the voltage has exceeded 0.5V above the BD alarm threshold.
5.
Restore the BD alarm threshold to its previous setting.
Adjust the float voltage to a value greater than this threshold (MENU > CONFIGURATION
2.
> FLOAT SETTINGS > SET POINT).
Verify an HV alarm is reported by the controller.
3.
Restore the float voltage back to its original setting.
4.
Restore the HV setting back to its original setting.
5.
Verify the alarms clear and the controller returns to Normal.
6.
Issue 2.0, June 3, 2008 68
Infinity D Power System Installation Guide: -48V Plants H2007001
Manual Contactor Control and Alarms
WARNING: If this is an operating plant with loads, skip this test.
Step Action
Open the contactor by controller command (MENU > CONTROL / OPERATIONS >
1.
DISCONNECTS).
Verify the controller reports a Contactor Open alarm.
2.
Close the contactor by controller command.
3.
Verify the alarms clear and the controller returns to Normal.
4.
Automatic Contactor Control and Alarms
WARNING: If this is an operating plant with loads, skip this test.
Step Action
Check the disconnect thresholds (MENU > CONTROL / OPERATIONS >
1.
DISCONNECTS).
Adjust the float voltage to a value less than this threshold (MENU > CONFIGURATION >
2.
FLOAT SETTINGS > SET POINT).
Disconnect the batteries in the plant.
3.
Verify the battery disconnect opens and the controller reports a Contactor Open alarm.
4.
Restore the plant voltage back to its original setting.
5.
Verify the contactor closes.
6.
Verify the alarms clear and the controller returns to Normal.
5.
Issue 2.0, June 3, 2008 69
Infinity D Power System Installation Guide: -48V Plants H2007001
This page intentionally left blank.
Issue 2.0, June 3, 2008 70
Infinity D Power System Installation Guide: -48V Plants H2007001
5. Troubleshooting
The Block Diagram below is a first step to troubleshooting an Infinity D -48V Plant.
Issue 2.0, June 3, 2008 71
Infinity D Power System Installation Guide: -48V Plants H2007001
Troubleshooting NE-Series Rectifiers/Converters
The status of an NE-Series rectifier or converter is provided by LEDs on their face, and
by extensive real time data, alarm and event history accessible through the system
controller.
Rectifier/Converter Status LEDs
LEDs Condition
Normal operation: No alarms, inputs and outputs are in their
normal range, communicating with the system controller.
Unpowered: No input or output voltage present.
1. Remove and reinsert unit.
2. Check input voltage with a voltmeter,
if input voltage is present, replace unit.
3. Check output bus voltage with a voltmeter,
if output bus voltage is present, replace unit.
Standby: The unit is okay, but has been placed in Standby by the
controller and is not delivering power.
Note: If a unit in standby loses communications with the controller
it will exit Standby mode and deliver power
Output Limit: The unit is okay and delivering maximum output
• At max rated output
• At configured current limit
• At thermal limit
If rectifiers/converters are equipped with optional air filters and
reporting thermal limiting, check air filters. Clean or replace all
filters if necessary.
View rectifier currents
STATUS > RECTIFIERS > RECTIFIER CURRENTS.
:
Issue 2.0, June 3, 2008 72
Infinity D Power System Installation Guide: -48V Plants H2007001
LEDs Condition
ACF [ac Fail]: Rectifier input is missing or out of range.
Correct ac fault.
In F [Input Fail]: Re-labeled LED on converter indicates
Converter input is out of range. Correct converter input fault.
Shutdown∗: The unit cannot deliver output.
• High Voltage Shutdown
• Thermal Shutdown
• Under Voltage Protect
• Component failure
1. Check rectifier or converter status on controller display to
determine cause of shutdown
2. Correct system output short, high temp, etc.
3. Remove and reinsert unit. If fault remains and other units are
functioning correctly, replace unit.
Communication Fail: Blinks to indicate the rectifier is not
communicating with a system controller.
Remove and reinsert unit. If fault remains and other units are
communicating correctly, replace unit.
∗ When a power unit senses an over- or under-voltage condition it will shutdown, wait 10
seconds, and then attempt to restart. If the over- or under-voltage condition remains it
will cycle again. If the rectifier is loaded more than 10%, after 3 restart attempts the
unit will lock out, and user intervention is required to restart.
Issue 2.0, June 3, 2008 73
Infinity D Power System Installation Guide: -48V Plants H2007001
Troubleshooting VT-Probes
Checking for Defective VT-Probes
(If a Voltage Channel Failure and/or Thermal Probe Failure alarm occurs)
Step Action
Disconnect the first probe from its RJ-45 terminal block.
1.
Run the command: MENU > CONTROL / OPERATIONS > UNINSTALL EQUIPMENT.
2.
Yes – Removed probe is defective. Replace it.
3.
Finished.
Remove the next probe.
4.
Go to Step 2. Repeat steps for all probes.
5.
Is the system controller green Normal LED lit?
No – Reinstall the removed probe. Proceed to
Step 4.
Issue 2.0, June 3, 2008 74
Infinity D Power System Installation Guide: -48V Plants H2007001
6. Product Warranty
A. Seller warrants to Customer only, that:
1. As of the date title to Products passes, Seller will have the right to
sell, transfer, and assign such Products and the title conveyed by
Seller shall be good;
2. During the warranty period stated in Sub-Article B below, Seller’s
Manufactured Products (products manufactured by Seller), which
have been paid for by Customer, will conform to industry
standards and Seller’s specifications and shall be free from
material defects;
3. With respect to Vendor items (items not manufactured by Seller),
Seller warrants that such Vendor items, which have been paid for
by Customer, will be free from material defects for a period of
sixty (60) days commencing from the date of shipment from
Seller’s facility.
B. The Warranty Period listed below is applicable to Seller’s Manufactured
Products furnished pursuant to this Agreement, commencing from date of
shipment from Seller’s facility, unless otherwise agreed to in writing:
Warranty Period
Product Type New Product Repaired Product*
Central Office Power
Equipment**
24 Months 6 Months
* The Warranty Period for a repaired Product or part thereof is six (6)
months or, the remainder of the unexpired term of the new Product
Warranty Period, whichever is longer.
** The Warranty Period for Products ordered for Use in Systems or
equipment Manufactured by and furnished by Seller is that of the initial
System or equipment.
C. If, under normal and proper use during the applicable Warranty Period, a
defect or nonconformity is identified in a Product and Customer notifies
Seller in writing of such defect or nonconformity promptly after Customer
discovers such defect or nonconformity, and follows Seller's instructions
regarding return of defective or nonconforming Products, Seller shall, at
its option attempt first to repair or replace such Product without charge at
its facility or, if not feasible, provide a refund or credit based on the
original purchase price and installation charges if installed by Seller.
Where Seller has elected to repair a Seller’s Manufactured Product (other
than Cable and Wire Products) which has been installed by Seller and
Seller ascertains that the Product is not readily returnable for repair, Seller
will repair the Product at Customer’s site.
With respect to Cable and Wire Products manufactured by Seller which
Seller elects to repair but which are not readily returnable for repair,
Issue 2.0, June 3, 2008 75
Infinity D Power System Installation Guide: -48V Plants H2007001
whether or not installed by Seller, Seller at its option, may repair the cable
and Wire Products at Customer’s site.
D. If Seller has elected to repair or replace a defective Product, Customer
shall have the option of removing and reinstalling or having Seller remove
and reinstall the defective or nonconforming Product. The cost of the
removal and the reinstallation shall be borne by Customer. With respect to
Cable and Wire Products, Customer has the further responsibility, at its
expense, to make the Cable and Wire Products accessible for repair or
replacement and to restore the site. Products returned for repair or
replacement will be accepted by Seller only in accordance with its
instructions and procedures for such returns. The transportation expense
associated with returning such Product to Seller shall be borne by
Customer. Seller shall pay the cost of transportation of the repaired or
replacing Product to the destination designated by Customer.
E. Except for batteries, the defective or nonconforming Products or parts
which are replaced shall become Seller's property. Customer shall be
solely responsible for the disposition of any batteries.
F. If Seller determines that a Product for which warranty service is claimed is
not defective or nonconforming, Customer shall pay Seller all costs of
handling, inspecting, testing, and transportation and, if applicable,
traveling and related expenses.
G. Seller makes no warranty with respect to defective conditions or
nonconformities resulting from actions of anyone other than Seller or its
subcontractors, caused by any of the following: modifications, misuse,
neglect, accident, or abuse; improper wiring, repairing, splicing, alteration,
installation, storage, or maintenance; use in a manner not in accordance
with Seller’s or Vendor’s specifications or operating instructions, or
failure of Customer to apply previously applicable Seller modifications
and corrections. In addition, Seller makes no warranty with respect to
Products which have had their serial numbers or month and year of
manufacture removed, altered, or experimental products or prototypes or
with respect to expendable items, including, without limitation, fuses, light
bulbs, motor brushes, and the like. Seller’s warranty does not extend to
any system into which the Product is incorporated. This warranty applies
to Customer only and may not be assigned or extended by Customer to
any of its customers or other users of the Product.
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND ARE IN LIEU OF ALL
OTHER EXPRESS AND IMPLIED WARRANTIES, INCLUDING BUT NOT
LIMITED TO WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE. CUSTOMER’S SOLE AND EXCLUSIVE
REMEDY SHALL BE SELLER’S OBLIGATION TO REPAIR, REPLACE,
CREDIT, OR REFUND AS SET FORTH ABOVE IN THIS WARRANTY.
Issue 2.0, June 3, 2008 76
Infinity D Power System Installation Guide: -48V Plants H2007001
Appendix A: Pulsar Controller
User Interface Overview
The Galaxy Pulsar Plus NE843 family of controllers monitor and control system components
including rectifiers, converters, and distribution modules via a multi-drop RS485 digital
communications bus. System status, parameters, settings, and alarm thresholds can be viewed and
configured from the controller’s front panel display. Assignment and configuration of alarm
inputs and output relays can be performed from a laptop computer connected to a local RS-232 or
Ethernet port, or by remote access is through a network connection to the World Wide Web
(internet) or your enterprise network (intranet). An optional modem is also available.
This section describes the controller features, functions and alarms from perspective of a user
utilizing the front panel display. All these features are available through the remote interfaces
including EasyView and Web pages served by the controller. EasyView is the Lineage Power
Systems GUI provided for local serial port or remote MODEM access. It supports all Lineage
controllers and has been around for many years and will not be discussed in detail. The web
interface and front panel will be the interfaces of choice. This section focuses on describing the
controller from the front panel perspective since it is the most available interface and requires no
PC or computer hardware. The items contained in the front panel are applicable to respective
feature implementations in the web pages.
Plant Status LEDs
RS232 and Ethernet
Ports to plug in a PC
to use Web Pages
Voltage
Test Jacks
LCD
Display
Menu
Navigation
Figure 5-1: NE843A/NE843C Front Panel Main Display
This display shows the front panel display for a system with both rectifiers and converters. The
display (V1 versus V2) correlates with test jacks. The large font indicates the “Primary” or
rectifier dc bus; the smaller font shows the “Secondary” or converter dc bus. The NE843 will
automatically determine the appropriate fonts and test jack designations.
For systems with no converters only a single voltage/current pair will be displayed on the front
panel along with the correct test jack association. The other test jack will be unused and will have
near zero voltage.
Issue 2.0, June 3, 2008 77
Infinity D Power System Installation Guide: -48V Plants H2007001
Menu Navigation Buttons
The NE843 has six tactile buttons to use to navigate through a structured menu system. The
buttons serve multiple purposes depending on the screen a user is at. These functions are
summarized below.
Buttons Description
Display Contrast
Parameter Change
Direction Buttons
In the Main Display, the ▲▼ buttons increase or decrease
the display contrast.
Contrast adjustment is also available through the menus at
MenuÎConfigurationÎSystem Settings.
When changing a system parameter, the ▲▼ buttons
increase or decrease the value of the parameter.
In the Menus, the ◄▲▼► direction buttons navigate to
make a selection. A black box highlighting a menu item
indicates that the item has sub-menus.
Enter Button
ESC Button
Enters a sub-menu or confirms a parameter change. From the
Home Page only, goes to the top level Main menu.
Goes up one menu level or exits a parameter change without
saving.
System Status Display
LCD Backlight
The Pulsar Plus NE843 controller family incorporates an alarm sensitive back-light indicator to
help assist in providing a clear indication of the system status. Severities of alarms can be
configured through the remote interfaces. Following is a basic description of the backlight
functionality.
The incorporated display technology can support a wide
range of backlight colors. Present implementation supports
three basic colors to indicate the alarm severity present in
the system: Green, Amber, and Red
The highest severity in the system will take precedence.
Status Function Condition
Normal
Critical Alarm
Major Alarm
Minor Alarm
Normal operation, no alarms, inputs and outputs are in
their normal range.
Highest severity. Generally assigned to alarm to indicate a
Power affecting condition. Immediate attention required.
High severity. Generally assigned to alarm to indicate a
Power affecting condition. Immediate attention required.
Medium severity. Generally assigned to alarm to indicate a
non-power affecting condition. Attention eventually
required.
Issue 2.0, June 3, 2008 78
Infinity D Power System Installation Guide: -48V Plants H2007001
NE843 Status LEDs
The Pulsar Plus NE843 controller family provides three separate LED indicators to help assist in
providing more specific indications of the system status. These LEDs provide are used to provide
specific indication concerning the AC and DC system status as well as a separate indicator for a
Battery on Discharge state. These LEDs have factory assigned defaults as indicated in the table
below. However, the assignments to alarms can be customized in the field using the remote
interfaces.
LED Status Condition
AC input to all rectifiers is in range.
AC
DC
BD
AC input to one rectifier is missing or out of range.
AC input to two or more rectifiers is missing or out of
range.
DC output to all loads is normal.
One or more of the following alarms are present: Fuse
Minor 48, Fuse Minor 24
One or more of the following alarms are present: Open
String, LVBD Open, Fuse Major 48, Fuse Major 24
System above configured Battery on Discharge (BD)
threshold.
Blinks at an On/Off Rate of 1/2 second ON 1/4 second Off
to indicate a manual or automatic battery test in progress.
State not presently assigned.
System equal to or below configured Battery on Discharge
(BD) threshold.
Audible Alarm
The Pulsar NE843 has an integrated audible alarm located in its display assembly. This alarmwill sound when any Critical, Major, or Minor alarm is detected by the controller. Upon assertion of the audible alarm the default front panel will provide and indicator of the alarm as well as a quick link to temporary cut-off the alarm.
Pressing the arrow keyprovides a quick link to temporarily cut-off the audible alarm.
Issue 2.0, June 3, 2008 79
Infinity D Power System Installation Guide: -48V Plants H2007001
Once the audible cut-off is selected the alarms present in the system are listed. An indicator on the default front panel screen is provided to inform that the audible alarm cutoff is active. The audible alarmcan also be turned-back on following similar procedures.
The audible alarmmay be disabled altogether through proper configuration at the front panel or through remote means.
Voltage Test Jacks
The Pulsar Plus NE843 has three test jacks that allow you to measure the system output voltage
with a hand-held meter. The jacks are referenced with C (Common), V1 (Voltage One), and V2
(Voltage Two). The voltage references correspond to the voltage referenced on the default front
panel screen.
Thus, one system voltage can be measured between C and V1 and a second output
voltage can be measured between C and V2. A voltage will not be present on one of the
voltage test jacks if the controller resides in only a single voltage system.
Local and Remote Access Ports
The Pulsar Plus NE843 provides ports for both local and remote access. Access to these
ports depends on the specific NE843 configuration. The NE843A and NE843C have a
front panel located to the left of the test jacks that provide access to a local DB-9 RS232
asynchronous serial port in some configurations. There is also space allocated for an
RJ45 receptacle that will be used to access a second 10/100Base-T Ethernet port in the
future. NE843A and NE843B controller configurations provide an RJ45 located at the
side of the chassis to access Ethernet port that is integrated into all NE843 configurations.
NE843 configuration options also provide a standard RJ11 for the telephone line interface
located on the side of the slot-controllers or directly on the modem itself.
Issue 2.0, June 3, 2008 80
Infinity D Power System Installation Guide: -48V Plants H2007001
Port Description
Front Panel
J7
A laptop PC can be connected to standard DB9 connector J7 to provide a
ground-referenced RS-232 serial connection using EasyView for local access.
The port can also be configured to be used with an external modem.
A position (as shown below) is reserved for a second RJ45 Ethernet connection
in the future. It is covered for now.
J8
Side
J5
J6
An RJ-45 Ethernet connector, Connector J5, on side (slot-mounted) or top
(door-mounted) of unit, is provided for the integrated 10/100 Base-T network.
Connection. This connection can be used for remote monitoring or as a local
Craft port. In the remote monitoring mode, this port is compatible with Lineage
Power Galaxy Manager or other SNMP based programs used for web-based
remote access and network management.
NE843 controllers equipped with an optional modem provide a standard RJ11
(J6) for a telephone line connection.
Front Panel Menu Structure
Feature content at the front panel is functionally divided at the NE843’s Main Menu into the
following categories:
Alarms
Warnings
Status
Control/Operations
History
Configuration
Issue 2.0, June 3, 2008 81
Infinity D Power System Installation Guide: -48V Plants H2007001
(
)
Access to the main menu starts at the default front panel screen shown below.
Front Panel Default Menu
Plant Voltage
Test Jack
Reference
Plant Current
Load
The front panel default screen displays the
primary and secondary (if present) bus voltages
along with their respective total load in two
different fonts.
The operating mode of the system is also
displayed. The displayed operating modes
possible are: Float, Battery On Discharge, Boost,
etc.
Plant Voltage
(Converter)
Plant Current
(Converter)
An alarm soft-key as well as the backlight will
indicate when alarms are present. Pressing the Õ
will access the alarm cut-off as well as the alarms
and warnings present in the system.
Pressing the button accesses the main menu
Main Menu
and the feature categories previously listed.
Access to alarms, warnings, equipment status
detail, basic control and operations for
maintenance purposes, and system configuration
can be obtained.
Note: the NE843 has the ability to have a front
Panel Password that limits configuration as well
as some operations. A person with administrator
level access can enable this feature through the
remote interfaces. Standard NE843 controllers are
shipped from the factory with this feature
disabled.
Front Panel PIN
The Pulsar Plus NE843 has the ability to restrict certain types of access from the front panel of
the unit. It has the ability to enforce a four-digit Power Identification Number (PIN) requirement
for users of the front panel for certain control/operations and configurable items. This feature is
disabled in the factory in the standard NE843 controller offerings and must be enabled by a
remote user with administrator level privileges. When the front panel PIN feature is enabled, the
factory default for the PIN is 0000. Each position of the password is configurable between 0-9. A
sample screen like that following is required for PIN access.
Issue 2.0, June 3, 2008 82
Infinity D Power System Installation Guide: -48V Plants H2007001
The up, down, left and right arrows are used to enter the appropriate password. Upon entering a
correct PIN the following momentary screen shows up and then disappears leaving the user at the
menu location prior to entering the PIN.
A user must enter the PIN for items that generally are not deemed as functions of a typical
maintenance routine. It is assumed that the majority of the configured thresholds and system
operational features will not be changed through a maintenance routine. Thus, entering the correct
PIN will be required in order for these specific types of parameters or features to be modified in
the field. These same rules are implemented when accessing through the Craft port. In addition to
Configuration items, there are some Control/Operations that also require the PIN. These are
shown below.
1. Clear History
2. Clear Statistics
3. Disconnects – Manual disconnect/reconnect of any LVLD/LVBD
4. Enter Boost
Other Control/Operations features listed below do not require PIN access.
1. Lamp Test
2. Restart Rectifiers
3. Uninstall Equipment
4. Start Battery Test
5. Start Alarm Test
6. Load Factory Defaults
All configuration items from the front panel require PIN access except for the following:
1. Battery Type
2. String Battery Capacity (AH)
3. Number Of Battery Strings
4. Manual Discharge Test Type
5. Manual Test Duration
6. Manual Test Check Battery Alarm Voltage Threshold
7. Battery Test Rectifier Voltage
8. System Date Format
Issue 2.0, June 3, 2008 83
Infinity D Power System Installation Guide: -48V Plants H2007001
9. System Date
10. System Time Format
11. System Time
12. Automatic Daylight Savings Feature
13. Display Contrast
14. Temperature Display Units
15. Alarm Test Feature
16. Alarm Test Relay Duration and Relay
Once a user enters the PIN, total front panel access is allowed for:
• As long as the user remains in menus other than the default menu and/or
• The default display has remained on the front panel for more than user configurable time-
out value. The NE843 has a factory configured default of 120 minutes. This time is
adjustable between 1-120 minutes in 1 minute increments. 120 minutes is the factory
default.
• An internal counter shall be kept and reset if the user leaves the default menu and returns
to others menus before the time-out period is reached.
Front Panel Menu Flow
The following figures provide a menu flow map for each primary category. This information is
followed up with brief descriptions of each of the menu items. Alarms and Warnings are not
hierarchal mapped and are presented in chronological order of occurrence when they are present.
No Active Alarms or No Active Warnings will be displayed when they are no alarms or warnings
detected by the controller.
Issue 2.0, June 3, 2008 84
Infinity D Power System Installation Guide: -48V Plants H2007001
.
Figure 5-3: Status Menu
Issue 2.0, June 3, 2008 85
Infinity D Power System Installation Guide: -48V Plants H2007001
Figure 5-4: Control / Operations and History Menus
Issue 2.0, June 3, 2008 86
Infinity D Power System Installation Guide: -48V Plants H2007001
Figure 5-5: Configuration Menu (part 1)
Issue 2.0, June 3, 2008 87
Infinity D Power System Installation Guide: -48V Plants H2007001
Figure 5-6: Configuration Menu (part 2)
Issue 2.0, June 3, 2008 88
Infinity D Power System Installation Guide: -48V Plants H2007001
Appendix B: Reference Information
Pulsar Controller Field Wiring Connector Definitions
One-Wire Battery Peripheral Connector
Temp is a standard shielded RJ-45 receptacle provided for making connections to one-wire QS873
VT-Probes and or to the ES771A Remote Mid-string Voltage Monitor. Standard cable assemblies have
been designed and are available for different applications with the QS873 VT-Probes or ES771 Remote
Mid-string Voltage monitors that allow simple plug-n-play.
Pin # Signal
Name
1 reserved
2 reserved
3 SIG_RTN Protected signal return for 1-wire
4 reserved
5 1-Wire 1-wire communication signal
6 +5V Protected +5V Power utilized by ES771 modules
7 reserved
8 reserved
Input Alarms Connector
Input Alarms is 10-pin right angle header that provides a separate connection for auxiliary inputs.
Standard color coded cable assemblies are available. Comcodes for the 50’ and 150’ input cables are
CC848817651 and CC848817668, respectively. Contact technical field support for additional cable
options.
Pin #
(Wire Color)
1
(BK)
2
(BR)
3
(R)
4
(O)
5
(Y)
6
(G)
7
(BL)
8
(V)
9
(S)
10
(W)
Signal Name Description
Aux Input 1
(Aux1)
Aux Input 2
(Aux2)
Aux Power Major Input
(AMJ)
Plant Battery Test/ Group
Standby/TR
(GSTR)
Emergency Power Off
(EPO)
Aux Input 3
(Aux3)
Aux Input 4
(Aux4)
Aux Input Return
(Aux_R)
Plant Battery Test/ Group
Standby (TR)
Ret.(GSTR_R)
Emergency Power Off
Ret. (EPO_R)
Auxiliary input to monitor a contact closure or open to its respective return on pin 8,
Auxiliary Input Return. See Appendix E for alarm assignments
Auxiliary input to monitor a contact closure or open to its respective return on pin 8,
Auxiliary Input Return. See Appendix E for alarm assignments
Auxiliary input to monitor a contact closure to the non-grounded side of a dc bus
(±24V/-48V) to create the standard Auxiliary Power Major alarm. See Appendix E
for alarm assignments
Dedicated input to be monitored for a contact closure to its respective return on pin
9. Used for Plant Battery Test and Group Standby Feature. Factory default as the
Group Standby feature upon a contact closure.
Dedicated EPO input to be monitored for a contact closure to its respective return on
pin 10, Emergency Power Off Return.
Auxiliary input to monitor a contact closure or open to its respective return on pin 8.
See Appendix E for alarm assignments.
Auxiliary input to monitor a contact closure or open to its respective return on pin 8.
See Appendix E for alarm assignments.
Return for Auxiliary Inputs 1-4.
Return for Plant Battery Test and Group Standby.
Return for EPO input.
Description
Issue 2.0, June 3, 2008 89
Infinity D Power System Installation Guide: -48V Plants H2007001
Office Alarm Connector
All standard controller output alarm connections are available from the output connector. Connector J4
provides access to the primary customer alarm output interface. Connector J4 is a 20-pin right angle header
with latching capability. Standard color coded cable assemblies are available. Comcodes for the 50’ and
150’ input cables are CC848817635 and CC848817643, respectively. Contact technical field support for
additional cable options.
Pin #
(Wire Color)
1
(BL)
2
(O)
3
(G)
4
(BR)
5
(S)
6
(BL)
7
(O)
8
(G)
9
(BR)
10
(S)
Signal
Name
Twisted Pair
PCR &
PMJ &
PMN &
UR1 &
UR2 &
UR3 &
UR4 &
UR5 &
UR6 &
UR7 &
Pin #
(Wire Color)
11
(W)
12
(W)
13
(W)
14
(W)
15
(W)
16
(R)
17
(R)
18
(R)
19
(R)
20
(R)
Signal Name
PCR_C
PMJ_C
PMN_C
UR1_C
UR2_C
UR3_C
UR4_C
UR5_C
UR6_C
UR7_C
NE843 Standard
Defaults
PCR
(Power Critical)
PMJ
(Power Major)
PMN
(Power Minor)
BD
(Battery on Discharge)
VLV
(Very Low Voltage)
FAJ
(External Fuse Major)
ACF
(ac Fail)
RFA
(Rectifier Fail)
MRFA
(Multi Rectifier Fail)
HV
(High Voltage)
Note: Configuration jumpers for the alarm outputs have been set to provide an “Open” on alarm
from the factory. Alarm contact type can be changed – see Advanced Features User Guide.
Network (LAN) Connection (Optional)
The NE843 provides an Ethernet connection for a LAN and or Craft port connection. Connector LAN
provides a standard RJ45 shielded receptacle connection for a standard Cat-5 connection to the controller’s
10/100Base-T port. This port has two main modes of operation: Server mode, LAN mode (Static and
DCHP Client). In server mode the port can be used as a local Craft interface. In this mode, a local laptop
can be connected through LAN and its standard web browser used to directly access the controller by
typing in network address
and LAN while the controller is in Server mode.
http://192.168.2.1. A connection should never be made between the controller
In Static or DHCP Client modes of operation the controller is supplied an IP address and other
network parameters and can be remotely monitored and accessed through the LAN. This is
generally a permanent connection between the controller and LAN so a Shielded Cat-5 cable is
suggested. Use appropriate routing techniques to connect the controller to the LAN.
Default Passwords are lineage, super-user and administrator.
Issue 2.0, June 3, 2008 90
Infinity D Power System Installation Guide: -48V Plants H2007001
Reference Information for 26 inch Frame
(all dimensions in inches)
Issue 2.0, June 3, 2008 91
Infinity D Power System Installation Guide: -48V Plants H2007001
Revision History
Issue 2.0
June 3, 2009 – Added Safety section updates; Specified 20A and 40A circuit breakers in
AC wiring section; changed colors of AC wires from white to black to avoid confusion;
indicated that alarm wire set conductors are paired; added passwords for LAN access.
Corrected trouble shooting diagram.
Issue 1.0
October 3, 2008 – Initial release.
Issue 2.0, June 3, 2008 92
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.