The information, specifications, and procedures in this manual are
subject to change without notice. Lineage Power assumes no
responsibility for any errors that may appear in this document.
General Information 1 - 1
Customer Service Contacts 1 - 2
Customer Service, Technical Support,
Product Repair and Return, and Warranty Service 1 - 2
Customer Training 1 - 2
On-Line Power Systems Product Manuals 1 - 2
EasyView Software 1 - 2
2Product Description
Overview 2 - 1
Batteryless Operation 2 - 1
GCM2 or GCM3 Control Board 2 - 3
User Interface Control Panel 2 - 3
BLJ3 Terminal Connection Board 2 - 7
Control Signal Inputs 2 - 13
BLJ3 Power Connections 2 - 13
BTJ2/BTJ3 Termination Board 2 - 14
BTJ2/BTJ3 Fuses and Connectors 2 - 15
3Operation
Office Alarm Contacts 3 - 1
Alarm Descriptions 3 - 1
System Features 3 - 9
Battery Recharge Current limit 3 - 15
Battery Discharge Test 3 - 15
Plant Generator/Battery Test (PBT) 3 - 18
Remote Access and Monitoring 3 - 18
Remote Rectifier Standby 3 - 19
Dial-out On Alarm 3 - 19
Issue 4 January 2008 Table of Contents - 1
Galaxy Vector Controller GCM2, GCM3
4Installation and Configuration
Wiring 4 - 1
Front Panel Operation 4 - 5
View Active Alarms Mode 4 - 5
Configuration 4 - 6
Battery Discharge Test Results 4 - 11
Battery Discharge Test Enable 4 - 12
Shunt Type/Size 4 - 12
Shunt Size 4 - 13
System Float Mode Settings 4 - 13
Very Low Voltage Threshold 4 - 14
Battery Recharge Current Limit Settings 4 - 14
Battery Thermal Compensation Settings 4 - 14
Low Voltage Disconnect Contactor 1 and 2 Settings 4 - 15
Plant Boost Mode Settings 4 - 16
Converter Settings 4 - 17
Voltage Calibration 4 - 17
Reserve Operation Engine 4 - 18
Serial Bus Updating and Clearing 4 - 18
Software Release Information 4 - 18
5Troubleshooting
Replacing Circuit Packs 5 - 1
Checking the highest battery temperature 5 - 1
Inaccurate Plant Voltage Readings 5 - 2
Temperature Probe Alarm is present 5 - 3
Unexplained Rectifier Failure Alarm and Multiple
Rectifier Failure Alarm 5 - 3
Unexplained Converter Failure Alarm and Multiple Converter
Failure Alarm 5 - 3
Rectifier Id conflict alarm is asserted 5 - 3
Converter Id (Cid) 5 - 3
6Product Warranty
2 - Table of ContentsIssue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Appendix ACommunications
Modem A - 1
Port Settings A - 1
Logging in A - 2
Galaxy Gateway A - 4
Introduction A - 4
Preparation A - 5
Precautions A - 5
Tools/Equipment Required A - 6
Unpacking the Galaxy Gateway A - 6
Vector Controller Configuration A - 7
Gateway Installation for Vector Controller A - 7
Galaxy
Configuring Network Communications A - 10
Logging In to the Galaxy Gateway A - 10
Configuring Static Network Parameters A - 11
Logging Out of the Galaxy Gateway A - 12
Post Installation Procedures A - 13
Gateway Cable Connections A - 8
Appendix
Objects and Attributes B - 1
B
T1.317 Objects and Attributes
Commands B - 6
ala Report Active Alarms B - 6
bye Log-off B - 6
cha Change Value B - 7
login Login B - 7
ope Operate a Control B - 7
pas Change Passwords B - 7
sta Report Status B - 8
Error Messages B - 8
Appendix CRegulatory Statements
FCC Part 68 Regulatory Statement C - 1
Industry Canada Certification C - 2
Issue 4 January 2008 Table of Contents - 3
Galaxy Vector Controller GCM2, GCM3
List of Figures
Figure 2-1: Galaxy Vector Controller in a Typical GPS Plant 2 - 2
Figure 2-2: Galaxy Vector Controller in a Flexent Outdoor Plant 2 - 2
Table 3-A: Alarm Identification Standard Assignments 3 - 3
Table 3-B: Office Alarm Relay and Front Panel LED
Standard Assignments 3 - 4
Issue 4 January 2008 List of Tables - 1
Galaxy Vector Controller GCM2, GCM3
Table 4-A: Configuration Parameters 4 - 8
Table 5-A: Replacement Circuit Packs and Temperature Modules 5 - 1
Table B-1: Power System B - 2
Table B-2: DC Plant B - 2
Table B-3: Alarm Thresholds B - 2
Table B-4: Rectifier Management B - 2
Table B-5: Rectifiers (xx is 01 to 24) B - 3
Table B-6: Battery Reserve Management B - 3
Table B-7: Battery Sections B - 3
Table B-8: Controller Battery Temperature Channels B - 3
Table B-9: Converter Plant B - 4
Table B-10: Boost Management B - 4
Table B-11: Battery/Load Contactor B - 4
Table B-12: Slope Thermal Compensation B - 5
Table B-13: Call-Out B - 5
Table B-14: Serial Ports B - 5
Table B-15: Alarm Messages B - 6
Table B-16: Error Messages B - 8
2 - List of TablesIssue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
1Introduction
General
Information
This product manual describes the Lineage Power GCM2 and
GCM3 versions of the Galaxy Vector Controller. These
controllers are an integral part of various Lineage Power GPS
(Galaxy Power System) and OPS (Outdoor Power System)
series power plants. They provide control and alarm monitoring
functions over a digital serial interface that interconnects plant
rectifiers and converters. Control includes the setting of
converter output voltage, rectifier output voltage, current limit,
high voltage shutdown, rectifier restart, sequencing and boost
mode. This serial digital communication interface helps
automate the installation and setup process. For example, the
need to use potentiometers to separately set individual rectifier
and converter output voltage levels is eliminated. Versions of the
Vector Controller are available for both +24Vdc (GCM2) and 48Vdc (GCM3) plants, including the 24V Flexent Wireless™
indoor and outdoor systems and H569-453 (+24V) / H569-454
(-48V) OPS systems.
The following Lineage Power rectifiers can interface with the
Galaxy Vector Controller:
Note: The Galaxy to Rectifier protocol supports many different
features and variables. Not all rectifiers support the complete
feature set.
Issue 4 January 2008 Introduction 1 - 1
Galaxy Vector Controller GCM2, GCM3
In addition to rectifier and converter control, the Vector
Controller provides:
•Visual alarm and plant status on the user front panel display
assembly
•Form C or transfer type contacts for the various alarm
conditions for external use
•Modem or network interface
•Low voltage battery disconnect
This manual describes the basic features, operation, installation
and configuration, acceptance testing, troubleshooting, and
repair of the Galaxy Vector Controller.
Customer Service Contacts
Customer Service,
Technical Support,
Product Repair and
Return, and
Warranty Service
For customers in the United States, Canada, Puerto Rico, and the
US Virgin Islands, call 1-800-THE-1PWR (1-800-843-1797).
This number is staffed from 7:00 am to 5:00 pm Central Time
(zone 6), Monday through Friday, on normal business days. At
other times this number is still available, but for emergencies
only. Services provided through this contact include initiating
the spare parts procurement process, ordering documents,
product warranty administration, and providing other product
and service information.
For other customers worldwide the 800 number may be accessed
after first dialing the AT&T Direct country code for the country
where the call is originating, or you may contact your local field
support center or your sales representative to discuss your
specific needs.
Customer TrainingLineage Power offers customer training on many Power Systems
products. For information call 1-972-284-2163. This number is
answered from 8:00 a.m. until 4:30 p.m., Central Time Zone
(Zone 6), Monday through Friday.
Downloads and
Software
To download the latest product information, product software
and software upgrades, visit our web site at
http://www.lineagepower.com
1 - 2 Introduction Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
2Product Description
OverviewThe Galaxy Vector Controller is mounted on the inside front
door of a GPS plant with the user interface panel accessible from
the front of the door. See Figure 2-1. In the Flexent Outdoor
system, the controller is installed behind a swing-out control/
display panel. See Figure 2-2. Basic controller specifications are
summarized in Table 2-A.
Form C Alarm contact ratings60V at 0.3A
Plant voltage measurement accuracy
(±.05% of full scale + 1 count)
Plant voltage measurement resolution.01V
Plant current measurement accuracy±1% of full scale
Plant current measurement resolution1A
Thermistor temperature measurement accuracy
Operating temperature range-40°C to +85°C
±30mV±40mV
• ±3°C for battery temperatures
from -5°C to +55°C
• ±5°C for battery temperatures
from -10°C to -5°C
• ±5°C for battery temperatures
from +55°C to +85°C+
Batteryless OperationThe Vector Controller is suitable for use in power plants with or
without batteries. In batteryless plants, the loss of ac power
causes an immediate loss of dc power to the controller and the
activation of all office alarm relays. When ac power is restored,
plant rectifiers will return to their last specified voltage set point,
and the controller will automatically return to its last
configuration.
Issue 4 January 2008 Product Description 2 - 1
Galaxy Vector Controller GCM2, GCM3
GCM
BLJ3
LCD Display
Assembly
Inside of Cabinet Door
Figure 2-1: Galaxy Vector Controller in a Typical GPS Plant
BTJ2 Board
Controller Display
(shown in open position)
Vector Controller
Figure 2-2: Galaxy Vector Controller in a Flexent Outdoor Plant
2 - 2 Product Description Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
GCM2 or GCM3
Control Board
Figure 2-3 shows the Galaxy Vector Controller board. This
board consists of an embedded microcontroller, A/D converters,
timers, memory, and input/output alarm and control circuitry
with connections to the terminal connection boards. There are
two versions of the control board: GCM2 for +24V systems, and
GCM3 for -48V systems. IC27 is the memory IC that contains
the firmware which determines the controller operation, and the
preset voltage and temperature thresholds for plant operation.
Software is updated by replacing IC27. A simpler upgrade
method is to replace the controller board. This avoids directly
handling, and possibly causing damage to the memory IC. There
are no hardware user-configurable items on the GCM boards.
IC27 - Peripheral Support and Memory IC
IC1 - Microcontroller
User Interface
Control Panel
J1J3
IN
+
OUT-
OUT+
Figure 2-3: Galaxy Vector Controller GCM2 or GCM3
Figure 2-4 shows a view of the 848597563 user interface control
panel. This assembly interfaces with the BLJ3 or BTJ2/BTJ3
connection boards via a 26 pin ribbon attached to P2. The
848597563 provides a comprehensive user interface to the
controller. It is used to view plant voltage and load, configure
thresholds and other system parameters, view active alarms and
to initiate system operations. This interface consists of a 4 line x
20 alphanumeric character LCD, a nine key keypad, and three
status LEDs. A standard DB9 connector is available for local
terminal access, or remote access using an optional BSM3
modem board. The modem board also provides isolation to the
local terminal connection. Note: If the BSM3 is not connected
J1 and J3 - Connect to
BLJ3 or BTJ2 Boards
Issue 4 January 2008 Product Description 2 - 3
Galaxy Vector Controller GCM2, GCM3
then the local port is referenced to the battery side of the power
system. Some teminal connections are referenced to true ground.
For these cases, a commercially available external port isolation
device is required. The BSM4 may also be purchased to
internally perform this isolation.
Galaxy Vector Controller
Figure 2-4: 848597563 Control Panel
Four softkeys are located directly to the left of the display. The
labels and functions of these buttons change dynamically as you
make selections and perform system operations. Softkey labels
appear in the display window and are preceded by a "←".
Four navigation keys (up, down, left, and right arrow keys) are
located to the right of the display. These keys are used to
navigate through the controller menus.
The home key, located directly to the left of the four
softkeys, brings you:
• to the main menu from the default screen or any sub-menu
• to the default screen from the main menu
Table 2-B lists the user interface control panel keys and
functions.
Table 2-B: 848597563 Control Panel Keys and Functions
KeyFunction
Softkeys
Left and Right
Arrow Keys
Up and Down
Arrow Keys
Home KeyReturn to top level of menu structure or default screen
Move through the various features and menu structure of
the controller
Move through digits in edit screens
Scroll or select a configuration option or value in an edit
screen
2 - 4 Product Description Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Three alarm status LEDs give a visual indication of system
status. The Major and Minor alarm LEDs indicate when alarms
are present, and then the actual alarm descriptions can be
displayed on the LCD by pressing the Alarms softkey. LED
indications are described in Table 2-C.
Table 2-C: Control Panel LEDs and Functions
LEDIndication
MAJOR (red)
MINOR (amber)
OK (green)
A Major alarm is active. If the MAJOR LED is lit,
MINOR and OK LEDs will not be lit.
A Minor alarm is active. If the MINOR LED is lit,
there are no Major alarms active and the MAJOR
and OK LEDs will not be lit.
No alarms are active. If the OK LED is lit, MAJOR
and MINOR LEDs will not be lit.
The default screen displays system voltage and current, system
mode (FLOAT or BOOST and other system conditions), and any
active alarms. The display will return to the default screen from
any menu whenever there has been no user initiated activity for
three minutes.
All power system attributes are characterized into three main
categories by the Vector Controller:
•Status
• Operations
• Configuration
as shown in Figure 2-5. Under Configuration are all of the
system parameters that can be edited.
Configuration edit screens have values and settings that can be
customized. There are two types of edit screens, numeric and
scroll lists. Numeric edit screens are those on which you modify
numbers by changing the individual digits in the number. An
example is the Float Set Point screen. Scroll list edit screens are
modified by pressing the UP and DOWN buttons to scroll
through a list of possible settings. These lists may include
numeric values or text. Selecting a Shunt Type is an example of
a scroll list edit.
Issue 4 January 2008 Product Description 2 - 5
Main Menu
View Status
Galaxy Vector Controller GCM2, GCM3
Battery Test Results
Batteries
Converters
Rectifier Current
Current
Temperature Probes
TYPE
VOLTAGE
CURRENT
Float Voltage Alrms
HIGH MAJOR
HIGH MINOR
BD MAJOR
LOW MAJOR
Control/
Operations
Configuration
Alarm Thresholds
Enable/Disable
Info
SOFTWARE VER
Float Voltages
Rectifiers
Shunts
Batteries
Contactors
Converters
Boost
Communication
Ports
Calibrate to Meter
Boost Voltage Alrms
BATT TEMP MJ
Start/Stop
Battery Test
Start
Lamp Test
Update Serial Link
Start/Stop Boost
Set Point
Voltage Alarms
Current Limit
No. On Engine
Type
Shunt 1 Rated
Shunt 2 Rated
Type
Batt Test Enable
Batt Temp
Management
Limit Recharge
Contactor 1
Contactor 2
Set Point
Shutdown At
Shutdown Enable
Restart At
HIGH MAJOR
HIGH MINOR
BATTERY TEST
BOOST FEATURE
AUTO BOOST
CONV SHUTDOWN
TEMP COMP
LOW TEMP COMP
RECHARGE LIMIT
High Major
High Minor
BD Major
Low Major
Temp Alarm
Temp Compensation
Limit Enable
Limit At
Boost Enable
Set Point
Boost Voltage Alrms
Auto Boost
Manual Dur
Boost Current Lmt
Local Port
Modem Port
System Voltage
Converter Voltage
Temp Comp Enable
High Temp Comp
Nominal Temp
Low Temp Comp
High Major
High Minor
Auto Boost Enable
Auto Duration
Baud Rate
Handshake
Baud Rate
Handshake
Rings to Answer
Figure 2-5: Galaxy Vector Controller Display Menu Flow
2 - 6 Product Description Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
BLJ3 Terminal
Connection Board
Fuses
Power In/Out
Shunts 1 and 2
Unused
Alarm Outputs
Thermal Inputs
Figure 2-6 shows the BLJ3 Terminal Connection Board. Not all
BLJ3 terminals are used by the Vector Controller. The following
pages describe the required connections.
Contactors
VectorController
Vector Controller Board
BoardNot Shown
(GCM2, GCM3)
System Configuration
DIP Switches
Plant Voltage
Regulation Input
Alarm Inputs
Unused
Bay
Alarm Out
Unused
Unused
To Rectifiers
Unused
To Modem/
Gateway/
Local Terminal
26 Conductor
Ribbon Cable
1
Front Panel
Control/Display
0
1S12345678
S1.1: Front Panel Configuration
- Enabled (shown)
0
- Disabled
1
S1.2: Software Mode
- Standard (shown)
0
- Flexent Default Configuration Parameters
1
1,2
S1.3: Option Card Availability
0
- Modem
1
- Galaxy Gateway Card (Internet)
1. Setting both SW1.2 and SW1.5 to "1" will result in activating the HV alarm cont act.
2. SW1.2 setting will only be read by the software when the GCM is powered up.
3. HV alarm contacts used for 2ACF alarm instead of HV alarm.
SH3+, SH3-, SH4+, SH4-, V2+, V2-, V3+, V3-, V4+, V4-, B1,
B2, M1, M2: These input terminals are not used by the Vector
controller.
Alarm input (IN1 - IN12): Basic office and contactor state
alarm inputs. Individual pin descriptions are shown in Table
2-D.
Table 2-D: BLJ3 Alarm Input Terminals
TerminalName
IN1FAJClosure to Batt Fuse major alarm input
IN2FANNot used
IN3OSNot used
IN4MAINTOpen to Batt Maintenance (open connector)
IN5AMJClosure to Batt Auxiliary major alarm input
IN6AMNNot used
IN7LVD1CNot used
IN8LVD2CNot used
IN9LVD3CNot used
IN10LV D1 O Closure to Batt
IN11LVD 2O Closure to Batt
IN12LV D3 ONot used
Alarm
Asserted
Description
Low voltage disconnect contactor 1 open
status input
Low voltage disconnect contactor 2 open
status input
J1, J2, J3: LVD1, LVD2, and LVD3 contactor configuration
jumpers used to detect the presence of contactors. Table 2-E
shows configuration information.
Table 2-E: LVD Contactor Configuration Jumpers
JumperAcross Pins 1 and 2Across Pins 2 and 3
J1LVD1 presentLVD1 not present
J2LVD2 presentLVD2 not present
J3
2 - 8 Product Description Issue 4 January 2008
LVD3 present
(not available)
LVD3 not present
(default for GCM)
Galaxy Vector Controller GCM2, GCM3
LVD1, LVD2, LVD3: Form C relay contact outputs for LVD
contactor control. These terminals are connected to BJN
contactor drive boards. LVD1 and LVD2 contacts are rated for
2 amps. LVD3 is not available in GCM controller applications.
Table 2-F shows relay state information.
Table 2-F: LVD Drive Terminals
Terminal
ContactorRelayOCR
LV D1K1
Normally open
contact
LV D3K3
Normally closed
contact
Return (common)LV D2K2
Office alarm relay outputs: All alarm output relays are isolated
Form C or transfer type contacts, consisting of normally open
(NO) and normally closed (NC) contacts, with a common return
(RTN) contact. The de-energized state of these relays is the
alarm state. An alarm condition results in a closure of the
normally closed contact to the return contact, and an open
between the normally open and return contacts. Individual relay
pin descriptions are shown in Table 2-G.
* Relay assignment is determined by the settings of S1.2 and S1.5:
HV alarmS1.2-0, S1.5=0
2ACF alarm S1.2=1, S1.5=0
VLV alarmS1.2=0, S1.5=1
Setting both switches to 1 results in activating HV. The S1.2 setting is only read during GCM power up.
Multiple AC Fail /
Very Low Voltage
Normally open
contacts.
Closed to R
when alarm
condition exists.
Normally
closed contacts.
Open to R when
alarm condition
exists.
Return
(common)
Issue 4 January 2008 Product Description 2 - 9
Galaxy Vector Controller GCM2, GCM3
BAT: Connection to the battery discharge bus for controller
power, and fused through F2 (1 1/3A). It is +24V for the GCM2,
and -48V for the GCM3.
ABS: Auxiliary Battery Supply: connection to the battery
discharge bus for user application (four terminals available), and
fused through F1 (2A).
DG: Connection to battery return (discharge ground) bus. DG
(five terminals available) provides the return for BAT (controller
power), and ABS user applications if required.
Battery shunt inputs: The GCM recognizes two of the four
available shunt inputs on the BLJ board. Shunt inputs are 50mv
full scale. The BLJ3 requires 100K 1% resistors in series
with the shunt. See Table 2-H.
Table 2-H: Battery Shunt Inputs
TerminalSignal NameDescription
SH1+Shunt1+
SH1–Shunt1–
SH2+Shunt2+
SH2–Shunt2–
Note: When no shunt is available to connect to Shunt 2 inputs, the Shunt 2
inputs must be jumpered together. When both shunts are used, they must
both be configured as “Load” or “Battery” shunts. They cannot be mixed.
The more positive lead of a battery shunt
during discharge
The more negative lead of a battery shunt
during discharge
The more positive lead of a battery shunt
during discharge (See note)
The more negative lead of a battery shunt
during discharge (See note)
2 - 10 Product Description Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Voltage Sense Inputs: The GCM recognizes one of the four
voltage sense inputs on the BLJ board. Sense inputs are 50mv
full scale. Each of these leads should be fused at the source.
See Table 2-I.
Table 2-I: Plant Voltage Sense Inputs
TerminalSignal NameDescription
V1+Vsense+
V1-Vsense–
Positive remote voltage regulation
sense point for GCM.
Negative remote voltage regulation
sense point for GCM.
J12: This jumper is factory set, and determines the controller
ground (CG) reference. The controller ground reference is set
according to the location of the plant shunts being monitored. If
the shunts are located in the Battery side of the DC bus then J12
should be set to position 1-2. If the shunts are located in the
Discharge Ground (DG) side of the DC bus then J12 should be
set to position 2-3. For +24V and -48V GPS, J12 should be set
to position 1-2.
Table 2-J: J12 Jumper
Jumper+24V System-48V System
J12Across pins 1 and 2
Thermal probe connections: Four thermistor or 210E module
inputs. Each thermistor is connected to the RTH#+ and RTN#,
where # = 1 through 4. A strap is required across RTH#+ and
EN#+ for each thermistor input used. The strap is not required
when using 210E modules. For the indoor system, the thermal
probe and cable are factory installed.
RTH ALM, RTH ALMR: Thermistor alarm input and return
from 210E module. See Section 4 for 210E module connections.
CG: Controller Ground is the GCM reference ground, and
should be connected to the bus on which shunt(s) are mounted.
This pin should be used to reference the 210E ground to the
Vector Controller ground.
Issue 4 January 2008 Product Description 2 - 11
Galaxy Vector Controller GCM2, GCM3
TPT1, TPT2: Thermistor protected test points for access to
system voltage.
LAMP, LAMPR: The LAMP terminal is used to send battery
voltage to the bay lamp. LAMPR is the LAMP return, and is
connected to DG.
P2: 26 pin connector to the user interface control panel
(848597563).
P1, P3: Two 96 pin connectors on which the GCM board
mounts.
J7: A RJ45 connector for the serial rectifier interface.
J4: For the Vector Controller function, these jumpers must be
used to short each C and R pin on the J4 and J11.
P4: RS-232 serial communication port used with the optional
BSM3 modem board or the EBW1 Gateway board (see
Appendix A).
2 - 12 Product Description Issue 4 January 2008
Control Signal Inputs
Galaxy Vector Controller GCM2, GCM3
Table 2-K: BLJ3 Control Signal Inputs
BLJ3 Power
Connections
(+) PWR ControllerBATF2Charge Bus (Rectifier bus)
(-) PWR ControllerDGDischarge Return Bus
LVD power #1See note 1NACharge Bus (Rectifier bus)
LVD power #2See note 1NABattery Bus
Aux. Bat. Source
Note 1: LVD control power, from the power buses for the indoor system, is connected to the
BJNx LVD controller board
Note 2: BLJ3 user available fused (F1) power terminations are labeled ABS. DG terminations are
also provided for user termination on the BLJ3. These terminations are labeled DG.
Description
Control Signal
Name
ROReserve Operationclosure to BAT
PBTPower Battery Testclosure to BAT
DescriptionIndoor Input Connection
Power connections from the system to the BLJ3 (factory wired).
Table 2-L: Power Connections BLJ3
Input
Termination
ABS
See note 2
Associated
Fuse
F1NA
Plant Termination
Issue 4 January 2008 Product Description 2 - 13
Galaxy Vector Controller GCM2, GCM3
BTJ2/BTJ3
Termination Board
LVD 1
J23
ALARM
OUT
Fuses
F1
F2
F3
F4
F5
J21
Figure 2-7 shows the BTJ2 (+24V) or BTJ3 (-48V) termination
board used as the terminal and controller interface for Vector
outdoor power systems. S1 is the system configuration DIP
switch.
J5
J6
J7
J2J27
AMJ (BATT FUSE)
J6
P1
LVD2
Vector Controller Board
(GCM2, GCM3)
LVDForcedClosedLED
FAJ
(DIST)
TEMPERATUREPROBES
#1
#2#3#4
RS232
CONNECTION
J13
DISPLAY J14
P3
PWR
S1.1: Front Panel Configuration
0
- Enabled (shown)
1
- Disabled
S1.2: Software Mode
- Standard (shown)
0
- Flexent Default Configuration Parameters
1
S1.3: Option Card Availability
- Modem
0
- Galaxy Gateway Card (Internet)
1
S1.4: Rectifier Class
01- Standard GPS Rectifiers
- NP Rectifiers
1. Setting both SW1.2 and SW1.5 to "1" will result in activating the HV alarm cont act.
2. SW1.2 setting will only be read by the software when the GCM is powered up.
3. HV alarm contacts used for 2ACF alarm instead of HV alarm.
Power connections: Power and sense connections from the
system to the BTJ2/BTJ3 are shown in Table 2-M.
Table 2-M: BTJ2/BTJ3 Power Connections (J21)
Pin
Number
1Shunt 1 (Chg)
2NC
3NC
4Shunt 2 (Chg) Reserved for future use
5NC
6NC
7
8Shunt 1 (Disch)
9DGController power input ground
10Vsense (Grd) Connection to DG bus, remote sense
11Shunt 2 (Disch) Reserved for future use
12
13
14Vsense (Chg) Connection to the charge bus, remote voltage sense
Signal NameDescription
Connection to battery shunt terminal nearest charge
bus (rectifier bus)
Controller
Power
LVD Battery
Bus
LVD Charge
Bus
Controller power input connection to the charge bus
(rectifier bus)
Connection to the battery shunt terminal nearest the
batteries
Battery bus power for LVD circuitry on the BTJ2/
BTJ3
Charge bus power for LVD circuitry on the BTJ2/
BTJ3
J2: RJ45 connector for rectifier communication. Pins 1 and 2 are
the communication pair. Pin 3 is isolated ground. Pin 4 is chassis
ground. All rectifiers are connected to this connector in a daisy
chain fashion.
Issue 4 January 2008 Product Description 2 - 15
Galaxy Vector Controller GCM2, GCM3
J23: LVD1 control.
Table 2-N: BTJ2/BTJ3 LVD1 Control Connections (J23)
Pin
Number
1LV D _N OForm-C output (see Note)
2LVD_CForm-C output (see Note)
3LVD_NCForm-C output (see Note)
4CoilControlled bus voltage to contactor coil
5Maint RTNCurrent limited bus voltage for Maint alarm
6Maint INMaintenance alarm input
7LVD1 RTN
8LVD 1 S t ateLow voltage disconnect signal
Note: These outputs can be used to drive an external contactor board if
Signal NameDescription
Current limited bus voltage for LVD1 state
(LVD open alarm)
J15-17 are jumpered in the 2-3 position.
J4: LVD2 control.
Table 2-O: BTJ2/BTJ3 LVD2 Control Connections (J4)
PBT/OSRT NPlant Battery Test / Rect On Standby RtnJ6-30
Note 1: NO (normally open) contacts are open when an alarm state exists.
NC (normally closed) contacts are open when an alarm state exists.
Note 2: Relay assignment is determined by the setting of S1.2 and S1.5:
HV alarmS1.2-0, S1.5=0
2ACF alarm S1.2=1, S1.5=0
VLV alarmS1.2=0, S1.5=1
Setting both switches to 1 results in activating HV. The S1.2 setting is only read
during GCM power up.
Signal
(Note 1)
NOPower Major Normally openJ6-1
RTNPower Major ReturnJ6-2
NCPower Major Normally closedJ6-3
NOPower Minor Normally openJ6-4
RTNPower Minor ReturnJ6-5
NCPower Minor Normally closedJ6-6
NOBattery on Discharge Normally openJ6-7
RTNBattery on Discharge ReturnJ6-8
NCBattery on Discharge Normally closedJ6-9
NOMajor Fuse Normally openJ6-10
RTNMajor Fuse ReturnJ6-11
NCMajor Fuse Normally closedJ6-12
NOMultiple AC Fail Normally openJ6-14
RTNMultiple AC Fail ReturnJ6-15
NCMultiple AC Fail Normally closedJ6-16
NOSingle AC Fail Normally openJ6-22
RTNSingle AC Fail ReturnJ6-23
NCSingle AC Fail Normally closedJ6-24
Description
Number
Pin
J27: AMJ (Auxiliary major battery fuse) requires a closure
between pins 1 and 2 to activate alarm.
J28: FAJ (Distribution fuse alarm major) requires bus voltage at
pin 1 to activate alarm. Pin 1 connects to J2 pin 1 of the alarm
board, which provides this alarm signal. The input to the alarm
Issue 4 January 2008 Product Description 2 - 17
Galaxy Vector Controller GCM2, GCM3
board is from the load circuit breakers. Pin 3 provides DG
connection to the alarm board. This DG connection provides DG
for alarm board LED operation. Pin 2 is a current limited
(50-ma) battery bus supply for possible future use.
J9-J12: Thermal inputs.
Table 2-Q: BTJ2/BTJ3 Thermal Input Connections
(J9-J12)
Pin
Number
1RTH ALM
2NC
3NC
4RTH +
5RTH RTN
6RTH EN
Description
J13: RS-232 connection.
Table 2-R: BTJ2/BTJ3 RS-232 Connections (J13)
Pin
Number
1TXD
2RTS
3DTR
4RXD
5CTS
6DSR
7DCD
8NC
9MODEM GRN
10MODEM YEL
11DGND 100 ohm terminated
12MODEM PRESENT
13+5 Volts
14DGND
Description
2 - 18 Product Description Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
J14: Local user interface and display connector.
Table 2-S: BTJ2/BTJ3 Display Connections (J14)
Pin
Number
1+5 Volts
2Display connected
3DGND
4Key Mon AE
5Key Mon BE
6Key Mon CE
7Key Mon DE
8Key Mon EE
9KEYPRESS
10DGND
11NC
12NC
13MOSI
14SCLK
15DGND
16LED SELECT
17OUT ENABLE
18DGND
19PMJ LED
20DGND
21CNRL LED
22DGND
23NC
24NC
25Plant Voltage +
26Plant Voltage -
Description
Issue 4 January 2008 Product Description 2 - 19
Galaxy Vector Controller GCM2, GCM3
3Operation
Office Alarm
Contacts
Alarm
Descriptions
The basic Galaxy VC issues PMJ, PMN, MJF, BD, ACF and
HV/2ACF/VLV office alarms off the BLJ3 and BTJ2/BTJ3
boards. Refer to Table 2-G and 2-N, respectively, for a
description of their output terminals. Refer to Table 3-A for a
listing of the various available alarms. Refer to Table 3-B for a
listing of alarm relays and their associated front panel LEDs.
To see active alarms, press the Active Alarm softkey, then use
the ∧ or ∨ keys to page through alarms. See Tables 3-A and 3-B.
The alarms are listed in order of severity. Some abbreviations are
required to fit the LCD screen.
Very Low Voltage Alarms and Battery on Discharge
When rectifier output is insufficient to maintain the load current
at the set voltage (typically because of an ac power failure), the
plant bus voltage drops. When this voltage drops below the
battery voltage, the batteries start providing current to the load.
Any time that the plant voltage is below the threshold selected
for BD, the Battery on Discharge alarm activates. If the plant
voltage continues to drop, a second, lower threshold can be
reached, activating a Very Low Voltage alarm. Default values
for these thresholds are set at the factory. These thresholds can
be changed by the operator in the configuration menu as
described in the Installation and Configuration section of this
manual (Section 4). S1.5 set to “1” will allow the relay dedicated
for HV/ACF/VLV, K8, to be asserted for the VLV condition.
Note that a BD alarm does not necessarily mean that the batteries
are discharging, only that the present voltage is lower than the
set point for this alarm. This alarm may be activated by an
incorrectly set BD threshold or plant voltage set point.
Issue 4 January 2008 Operation 3 - 1
Galaxy Vector Controller GCM2, GCM3
Following the restoration of ac power after a battery discharge of
significant depth, this alarm remains active for some time during
the recharge period, until the batteries have recharged to a level
which allows the plant voltage to rise above the BD threshold.
BD threshold default is set at 25.54V standard (Flexent 25.0V)
in 24V systems and 51.1V in 48V systems with slope thermal
compensation disabled. In systems with slope thermal
compensation, the BD threshold should be 0.5V below the slope
upper temperature voltage for 24V systems, and 1.0V below the
slope upper temperature voltage for 48V systems. The slope
upper temperature equals:
Float Set Point - (number of cells) · E · (F-D)
See Figure 3-1 for system settings E, F, and D
These levels generally avoid nuisance alarms from transient
conditions yet provide alarm indications early in a true BD
event, so that sufficient time is provided for maintenance
personnel to respond before battery reserve is exhausted. VLV
should be activated towards the end of the battery reserve
voltage to indicate a critical service condition.
3 - 2 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Table 3-A: Alarm Identification Standard Assignments
Description
No active alarms presentNormGreenNone
Very low voltageMajorRedNone
Battery on dischargeMajorRedBD
High float voltageMinorYellowNone
Very high voltageMajorRedHV
Voltage sense fuse alarmMajorRedNone
AC failMinorYellowACF
Multiple AC failMajorRedACF
Rectifier failMinorYellowNone
Multiple rectifier failMajorRedNone
Rectifier ID conflictMajorRedNone
Rectifier manual off alarmMinorYellowNone
Rectifier AC phase alarmMinorYellowNone
Converter failMinorYellowNone
Multiple converter failMajorRedNone
Converter ID conflictMinorYellowNone
Converter distribution alarmMajorRedMJF
Converter fan fail minorMinorYellowNone
Converter fan fail majorMajorRedNone
Fuse alarm majorMajorRedMJF
Auxiliary input majorMajorRedNone
Load Share imbalanceMinorYellowNone
Contactor 1 openMajorRedNone
Contactor 1 failedMajorRedNone
Contactor 2 openMajorRedNone
Contactor 2 failedMajorRedNone
High battery temperatureMajorRedNone
Temperature probe failureMinorYellowNone
Maintenance open alarmMajorRedNone
Alarm
Status
BMW
LED
GVM
Relay
Issue 4 January 2008 Operation 3 - 3
Galaxy Vector Controller GCM2, GCM3
Table 3-B: Office Alarm Relay and Front Panel LED Standard Assignments
Asserted ConditionAlarm RelaysFront Panel LEDs
Very high voltage [HV]PMJE, (HV or none)MAJ (red)
High float voltage [HFV]PMNEMIN (yellow)
Battery on discharge [BD]PMJE, BDMAJ (red)
Very low voltage [VLV]PMJE, (VLV or none)MAJ (red)
Single ac fail [ACF]PMNE, ACFMIN (yellow)
Multiple ac fail [MACF]PMJE, (2ACF or none)MAJ (red)
Single rectifier fail [RFA]PMNEMIN (yellow)
Multiple rectifier fail [MRFA]PMJEMAJ (red)
Single converter fail [CFA]PMNEMIN (yellow)
Multiple converter fail [MCFA]PMJEMAJ (red)
Major fuse (Controller, FAJ input) [MJF]PMJE, MJFMAJ (red)
Low voltage battery disconnect [LVBD]PMJEMAJ (red)
Low voltage load disconnect [LVLD]PMJEMAJ (red)
LVD1 fail [LVDA]PMJEMAJ (red)
LVD2 fail [LVDA]PMJEMAJ (red)
Controller fail [CTLR]PMJEMAJ (red)
Slope thermal compensation activeLCD
Defective battery temperature probe [TPA]PMNEMIN (yellow)
Voltage sense fuse alarmPMJEMAJ (red)
Rectifier manual off alarmPMNEMIN (yellow)
Rectifier phase alarmPMNEMIN (yellow)
Rectifier half power alarmPMNEMIN (yellow)
Auxiliary major alarmPMJEMAJ (red)
Battery thermal alarmPMJEMAJ (red)
Controller unpowered
Connector openPMJE, PMNEMAJ (red)
Alarm cut offLCD
Display voltsLCD
Display ampsLCD
PMJE, PMNE, MJF, BD,
ACF, HV
High Float Voltage Minor Alarm and Very High Voltage
Major Alarm and Shutdown
Because of the importance of protecting the batteries and load
from overvoltage conditions, three high voltage thresholds are
provided. Two are controlled by the Vector and one backup
threshold is hard-wired internally in Lineage Power rectifiers.
3 - 4 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
The two lowest thresholds are preset at the factory but can be
adjusted through the Vector control panel or remotely. The third
threshold (ISHVSD) is generated by the controller by adding
1.50V to the very high voltage threshold. This value is then
transmitted to the rectifier and stored. Each rectifier compares its
own output voltage to this threshold value and initiates internal
shutdown if the value is exceeded. “Very High Voltage” and
“High Float Voltage” are set in the Vector in the Configuration
mode. See Section 4, Installation, Configuration and Operation.
The Vector is equipped to detect a high voltage condition on the
system bus. Such a high voltage condition may typically be
caused by lightning-induced transients on the commercial ac or
a rectifier failure may cause an individual rectifier to go high. To
prevent a high voltage condition from damaging the connected
load, the Vector also sends a signal for the rectifiers to shut down
if the plant voltage goes above a second threshold.
When the system voltage increases above the threshold for
“High Float Voltage,” it issues the High Float Voltage minor
alarm. If the voltage continues to rise and reaches the threshold
for “Very High Voltage,” that alarm is issued as a major alarm
and a shutdown signal is issued simultaneously to the plant
rectifiers. Any rectifier which is producing at least 10% of its
rated capacity and is 10% over the average of all rectifier outputs
in the plant, responds to this shutdown signal by shutting down
with a RFA or ALM condition active and reports back to the
Vector. A restart attempt initiated by the controller occurs 4
seconds after the controller receives the RFA signal from the
rectifier. The rectifier then attempts to restart three times. During
the restart sequence, the rectifier, recognizing that its output
current exceeds the average rectifier current, shuts down and
tries again up to three times.
For plants with the battery thermal lower temperature
compensation disabled, the High Float Voltage threshold is
usually set approximately 0.75V above float for a 48V plant and
0.5V above float for a 24V plant. High Voltage shutdown
threshold is then usually set approximately 2.5V above float for
a 48V plant and 1.0V above float for a 24V plant. In plants with
battery thermal lower temperature compensation enabled, the
High Float Voltage threshold is usually set approximately 0.8V
above the maximum voltage due to low temperature in a 48V
plant and 0.5V in a 24V plant.
Issue 4 January 2008 Operation 3 - 5
Galaxy Vector Controller GCM2, GCM3
Very High Voltage shutdown is usually 0.5V above the High
Float Voltage threshold for 48V plants and 0.25V above the
High Float Voltage threshold in 24V plants. Like the BD and
VLV thresholds, these are set in the Galaxy VC in the
configuration mode as described in the Installation,
Configuration and Operation section of this manual (Section 4).
S1.2 set to “0” will assign the HV/2ACF/VLV alarm contact to
the standard default of HV for the Very High Voltage shutdown
condition.
Voltage Sense Fuse Alarms
A lack of voltage on the Vsense +/- pair to the Vector Controller
as a result of a broken connection or a blown fuse while the
Vector is still powered results in a Voltage Sense Fuse alarm. A
voltage of 16.xx volts is displayed.
Sanity Fail in the Vector microprocessor or loss of power to the
Vector result in operation of the PMJ alarm. This PMJ defaults
to the alarm state if the controller is removed from the BLJ3.
AC Fail and Multiple AC Fail Alarms
If the proper ac input voltage is not available to any system
rectifier which is connected to the serial rectifier bus, an AC Fail
alarm (ACF) activates as a PMN. More than one ACF results in
a Multiple AC Fail alarm, changing this alarm status to a PMJ.
Note: S1.2 set to “1” will allow the HV/2ACF/VLV alarm
contact to be assigned to the Multiple AC Fail condition.
However, this will also cause the Flexent default configuration
values to be used any time the GCM is rebooted at power up.
Rectifier Failure and Multiple Rectifier Failure Alarms
Various rectifier failure modes cause a rectifier failure signal to
be issued to the controller, such as high voltage, temperature
over threshold, fan failure, and rectifier circuit breaker/fuse
open. Additionally, when rectifiers are removed or fail to
communicate with the Vector, a RFA alarm is generated. This
RFA alarm is cleared by updating the serial line in the
Operations and Control menu (see Configuration, Section
4).The RFA signal results in a RFA and Power Minor alarm
being issued by the Vector. More than one RFA at any time
results in a Multiple Rectifier Failure alarm and Power Major.
The Vector does not attempt restarts for RFAs caused by TA
(Thermal Alarm), CB/fuse trip, or Fan Failure.
3 - 6 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Rectifier ID Conflict Alarm
This alarm occurs when rectifier ID numbers are duplicated or
are zero. Refer to the rectifier manuals for setting and viewing
the rectifier ID numbers.
Rectifier Manual Off Alarm
Whenever the rectifier is manually turned to standby, this alarm
occurs. A switch on the front panel for each rectifier allows the
user to manually turn the rectifier on or standby. When the
switch is in standby position, the alarm is active.
Rectifier Phase Alarm
This alarm is for multiphase rectifier. When AC is lost in one or
more phase but not all phases, this alarm occurs.
Converter Failure and Multiple Converter Failure Alarm
Converter failure alarms are generated for various reasons.
These include failure in the converter, the converter is removed,
the converter interface board is removed, or communication is
lost with the converter interface board. The removed CFA is
cleared by updating the serial line in the Operations and Control
menu (see Configuration, Section 4).
Converter ID Alarm
This alarm occurs when converter ID numbers are other than 1
through 8, or are duplicated. Refer to the converter section of the
plant manual for setting and viewing ID numbers.
Converter Distribution Alarm
Any fuse or breaker open at the converter output side (-48v
distribution) causes this alarm.
Converter Fan Fail Minor and Converter Fan Fail Major
The converter carrier 597B has two fans. If one fan in a carrier
fails, the controller reports a Converter Fan Minor alarm. If both
fans fail, the controller reports a Converter Fan Major alarm.
Major and Minor Fuse and Auxiliary Alarms
To create these alarms, the respective alarm inputs must be
connected to Bat or battery voltage or, in the case of J27 on the
BTJ2/BTJ3 board, a connection between two terminals must be
made. This battery voltage typically has a series 1K ohm resistor
between Bat and the alarm input.
Issue 4 January 2008 Operation 3 - 7
Galaxy Vector Controller GCM2, GCM3
The operation of an output distribution fuse or circuit breaker
places battery voltage onto the FAJ input of the BLJ3 or
BTJ2/BTJ3 board, activating the Major Fuse alarm.
Auxiliary Major on the BLJ3 board can be user-assigned for any
supplemental alarm monitoring for which a battery voltage
signal (through 1K ohms) can be obtained, which is asserted by
a signal to the AMJ terminal on the BLJ3 board. Auxiliary Major
on the BTJ2/BTJ3 board is usually reserved for an open battery
fuse alarm or for a major alarm generated by the environmental
controller for the cabinet, and is generated by a closure between
the two pins of J27 of the BTJ2/BTJ3.
Auxiliary Minor is only available on the BLJ3 board and can be
user-assigned for any supplemental alarm monitoring for which
a battery voltage signal (through 1K ohms) can be obtained,
which is asserted by a signal to the AMN terminal on the BLJ3
board.
Load Share Imbalance Alarm
This alarm is generated when the current share function is
enabled and the rectifiers do not share the current equally or
within the current share boundaries. The controller monitors the
current (I
) delivered by each of the rectifiers and determines
rect
the total current delivered by the plant as the sum of all rectifier
currents. The average rectifier current (I
) is calculated by
avg
dividing the total current by the number of active rectifiers in the
plant. If, for any rectifier, actual rectifier current I
from the average rectifier current I
by 10A or more for 5
avg
is different
rect
minutes, then the controller issues a Rectifier Current Imbalance
Alarm. This alarm retires when the difference between the I
A Contactor Open alarm is reported whenever the Vector senses
that a contactor is open. This alarm is processed as a PMJ.
A Contactor Fail alarm is reported whenever the Vector senses
that a contactor that should be open or closed is in the opposite
state (closed or open). This alarm is also processed as a PMJ.
High Battery Temperature Alarms
3 - 8 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Temperature Probe Failure
See Figure 3-1. The Vector reports a High Battery Temperature
Alarm when the temperature rises above the configured set
point. See Section 4, “Installation, Configuration and
Operation,” for information on battery thermal compensation
settings. It reports a Thermal Probe Alarm when thermal
compensation is enabled and a temperature probe is
disconnected or returns a grossly inaccurate reading to the
Thermal Compensation circuit.
Open Maintenance Alarm
Input Number 4 (MAINT) of the BLJ3 terminal connection
board should be connected to battery voltage during normal
operating conditions. This connection may be looped through
one or more circuit packs so that if the connection path is
interrupted, the Open Maintenance Alarm is activated.
System
Features
Load and Battery Contactor Features and Alarms
The Vector has two distinct circuits for controlling the state of
external Load and Battery Disconnect Contactors. Terminals
LVD1 and LVD2 on the BLJ3 board, or J23 and J4 on the
BTJ2/BTJ3 board provide the interface from the controller to
separate contactor driver circuits which must be furnished as
part of the plant circuitry.
Each contactor can be configured as none, load, or battery.
When configured as a battery contactor:
•The contactor is open when the plant voltage is less than the
respective low voltage battery disconnect threshold.
•The contactor is closed when the plant voltage is greater
than the respective low voltage battery reconnect threshold.
At power up, the contactor is closed and there is an 18
second delay before the controller determines the correct
state of the contactor.
When configured as a load contactor:
•The contactor is open when the plant voltage is less than the
respective low voltage load disconnect threshold.
•The contactor is closed when the plant voltage is greater
than the respective low voltage load reconnect threshold.
Issue 4 January 2008 Operation 3 - 9
Galaxy Vector Controller GCM2, GCM3
Additionally, there must be no active ac failure and rectifier
phase alarms, since the load would immediately disconnect
after reconnecting. At power up, there is an 18-second delay
before the load is reconnected to allow the rectifiers to walk
in.
Refer to the Alarm Descriptions section for alarms associated
with these two contactors (Contactor Open and Contactor Fail).
Refer to the associated plant documentation for information on
connecting these Load and Battery Disconnect driver circuits to
the BLJ3 terminal connection board or the BTJ2/BTJ3
connection board.
Thermal Compensation Features and Alarms
The Vector has a flexible Thermal Compensation feature which
provides voltage compensation from that level established by the
Plant Float Set-Point (FSP), dependent on the highest
temperature monitored by thermistors located at the plant
batteries. Thermal Compensation should only be enabled when
the controller is used in a plant containing “sealed” or valve
regulated “maintenance free” batteries. This feature requires the
use of external thermistors at the plant batteries to monitor cell
temperatures. Refer to the Installation section for more details on
wiring and configuring this feature.
Thermal Compensation lowers plant voltage from the FSP for
monitored battery temperatures which are above the ideal
temperature established during configuration as the Battery
Thermal Slope Nominal Temperature. Lowering the plant
voltage helps to keep the batteries at their optimum state of
charge while protecting them from thermal runaway. Thermal
runaway is a complex sealed battery phenomenon where, for a
number of reasons, one or more cells in a string are unable to
dissipate the internal heat generated by their charging current
and experience an increase in internal temperature. By lowering
the float voltage as cell temperature increases, the float current
is lowered to a point where this destructive behavior can be
avoided. If a cell failure is imminent and the cell temperature
continues to rise above the threshold configured for Battery
Thermal Step Temperature, the plant voltage drops in a single
step to a level which helps keep from overcharging and
damaging the remaining cells in the string. Refer to Figure 3-1
for a graphical view of Battery Thermal Compensation and the
relationship of its various set points. Figure 3-2 shows the same
information for the Flexent system.
3 - 10 Operation Issue 4 January 2008
Temperature
Compensation
Voltage Adjustment
(volts per cell)
C(D–A)
•
0
E(F–D)
•
Galaxy Vector Controller GCM2, GCM3
Refer to the Alarm Descriptions section for the Battery Thermal
Alarm and Temperature Probe Failure Alarm.
The Vector can also increase plant voltage above the FSP for
colder environments. Again, this seeks to keep batteries in such
an environment at their optimum charge state. Since this feature
results in an increase in plant voltage, it is activated through a
second enable switch during configuration. Again, refer to
Figure 3-1 or 3-2.
A - Battery Low Temperature Voltage
Increase Threshold (-5 to +20 °C)
B - Low Temperature Voltage
Compensation Disabled
B - Battery Low Temperature Compensation
Voltage Increase (Enable/Disable)
C - Battery Low Temperature Voltage
Increase (1mV to 5mV / Cell / °C)
D - Battery Temperature At Which There
Is No Voltage Compansation (15 to 30 °C)
E - High Battery Temperature Decrease
Voltage Rate (1mV to 5mV / Cell / °C)
F - High Battery Temperature Voltage
Decrease Upper Threshold Limit (30 to 55 °C)
G -High Battery Temperature
Alarm Threshold (30 to 85 °C)
H - High Battery Temperature
Step Down At (45 to 85 °C)
1
2
–0.17
Default Settings
Cell Temperature ( C)
55657545255
1. The Battery High Temperature Alarm occurs when the temperature rises above the High Battery
Temperature Alarm Threshold ( ) set point. It retires when the temperature decreases to 10 °C below
G
this set point set point (45 °C default).
2. Plant voltage decreases 0.17 volts per cell when the temperature increases above the High Temperature
Voltage Step Down At ( ) set point. It is increased 0.17 volts per cell when the temperature decreases to
H
10 °C below this set point, as indicated by the dashed line (65 °C default).
Figure 3-1: Battery Thermal Compensation Set Points (Standard)
Issue 4 January 2008 Operation 3 - 11
Temperature
Compensation
Voltage Adjustment
(volts per cell)
C(D–A)
•
0
E(F–D)
•
Galaxy Vector Controller GCM2, GCM3
A - Battery Low Temperature Voltage
Increase Threshold (-5 to +20 °C)
B - Battery Low Temperature Compensation
Voltage Increase (Enable/Disable)
C - Battery Low Temperature Voltage
Increase (1mV to 5mV / Cell / °C)
D - Battery Temperature At Which There
Is No Voltage Compansation (15 to 30 °C)
B - Low Temperature Voltage
Compensation Disabled
E - High Battery Temperature Decrease
Voltage Rate (1mV to 5mV / Cell / °C)
F - High Battery Temperature Voltage
Decrease Upper Threshold Limit (30 to 55 °C)
G -High Battery Temperature
Alarm Threshold (30 to 85 °C)
H - High Battery Temperature
Step Down At (45 to 85 °C)
1
2
–0.17
Default Settings
Cell Temperature (°C)
1. The Battery High Temperature Alarm occurs when the temperature rises above the High Battery
Temperature Alarm Threshold ( ) set point. It retires when the temperature decreases to 10 °C below
this set point set point (65 °C default).
2. Plant voltage decreases 0.17 volts per cell when the temperature increases above the High Temperature
Voltage Step Down At ( ) set point. It is increased 0.17 volts per cell when the temperature decreases to
10 °C below this set point, as indicated by the dashed line (65 °C default).
H
G
65755325–5
Figure 3-2: Battery Thermal Compensation Set Points (Flexent)
Note: Any time that Battery Thermal Compensation is actively
changing the plant voltage above or below that set by the FSP
parameter during configuration, the LCD indicates the mode by
displaying the message “Float - Compensated”. This is not an
alarm condition, only an indication to the user that plant voltage
is different than that set by the FSP parameter.
Rectifier Sequencing
Rectifier Sequencing is a feature which allows the Vector to
bring the plant rectifiers back on line one at a time following an
ac power interruption. This serves to minimize their impact on
3 - 12 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
the ac service, especially useful in avoiding loading down an
emergency generator with an inrush surge.
The Reserve Operation (RO) engine signal (closure, available
only on the BLJ3 board) notifies the Vector that a backup engine
is supplying stable ac power to the rectifiers. A certain number
of rectifiers are then started in sequence. The number of
rectifiers which should be on when the engine is in use is
configurable. Refer to Section 4 for details. The number of ON
rectifiers is usually determined by the capacity of the engine.
When a rectifier reports an ACF to the Vector, it places that
rectifier into standby. As rectifiers report good ac, they are
turned on at 1 second intervals. When the controller senses the
RO signal, it pauses 10 seconds and starts the configured number
of rectifiers at 1 second intervals.
While RO is active, the Vector maintains the configured number
of rectifiers on. When RO retires, the Vector turns the remaining
rectifiers on at 1 second interval.
Shunt Types and Sizes
The Vector provides three separate methods and up to two
separate shunt signals for use in determining the plant current to
display. The access connections to the 2 shunt signals are on the
BLJ3 board SH1+/- and SH2+/- as shown in Figure 2-6, or on
the BTJ2/BTJ3 J21 plug as shown in Table 2-M. These signals
shall be a maximum of 50 mV signals that can represent a range
of 0-9999 amps. Refer to the configuration section of this
manual for additional details.
Float Mode Controls and Thresholds
Float mode is the default mode of operation and is active if the
Boost mode is not active. Plant voltage, while in Float mode, is
determined by the configuration parameter System Float Set
Point (FSP), and may be adjusted by the Battery Thermal
Compensation feature, if it is enabled. There is no individual
adjustment of plant rectifiers in this digital serial bus interface
arrangement. Load share among plant rectifiers is automatic in
all system modes and takes effect within several seconds of a
new rectifier being added to the bus and turned on.
The FSP chosen should correspond to the battery type used and
the battery manufacturer’s recommendations. For example,
Lineage Power KS20472 Round Cell (flooded) battery floats at
2.17 volts per cell (VPC). A 12 cell, 24V plant would therefore
Issue 4 January 2008 Operation 3 - 13
Galaxy Vector Controller GCM2, GCM3
have a FSP of 2.17 x 12 = 26.04V. The Lineage Power KS23619
Enhanced VR (Valve regulated) battery floats at 2.27 VPC, if
Battery Thermal Compensation is enabled or 2.25 VPC if used
without Battery Thermal Compensation. A 12 cell, 24V plant
using this battery would have a desired FSP of 2.27 x 12 =
27.24V with or 2.25 x 12 = 27.00V without Battery Thermal
compensation.
Rectifier Current Limit in Float mode (FCL) is an adjustable
configuration parameter from 30% to 110% of rectifier capacity.
This parameter can be important in limiting the recharge current
available following a deep discharge in a plant using a “sealed”
or valve-regulated battery type to a level which is safe for that
battery and not cause unnecessary internal pressure buildup and
venting. Typically, this maximum safe recharge rate for “sealed”
or valve-regulated battery types in the industry is in the range of
1/10 of the 8 or 10 hour rating. Refer to your specific battery
manufacturer for recommendations regarding the battery type
used. The following typical example shows the use of the FCL
feature to maintain the maximum recharge rate decided upon.
Consider a plant with three strings of 2VR375E Lineage Power
KS23619 Enhanced VR Series batteries, four 100A rectifiers
and a 200 amp typical load. When ac power returns following a
significant discharge, 200 amps are available for recharging
these batteries, a rate of 67A per string (200A / 3 strings).
Recharge should be limited to approximately 40A per string
(1/10 of 375) however, reducing the possibility of venting and
life depreciation of the batteries. Calculate current limit for
limiting recharge to 40A per string as follows:
Check for N + 1 redundancy with this CL value with the
following statement:
Plant Load < [Rect Cap × (# Rect - 1) × CL] / 100
200 < [100 × (4 -1) × 80] / 100
3 - 14 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
200 < [(100 × 3) × 80)] / 100
200 < (300 × 80) / 100
200 < 240
Float mode adjustments are also available for High Float
Voltage Float Threshold which activates the High Float Voltage
(alarm only) minor when exceeded and the High Voltage Float
threshold which activates the High Voltage major alarm and
rectifier shutdown. Battery on Discharge Float Threshold and
Very Low Voltage Threshold are additional Float mode
configuration parameters. Refer to the Alarm Descriptions
section for additional information regarding these alarms.
Battery Recharge
Current limit
Battery Discharge
Tes t
The battery recharge current limit feature enables the Vector
Controller to limit the recharge current flowing into a battery
section during the charge cycle. This feature is available only in
plants that have at least one battery shunt to monitor the battery
current. It can be enabled or disabled using the front panel
display or EasyView® Interface. The recharge current flowing
into the battery section can be limited to any value between 10
and 1000A.
The Vector Controller can monitor up to two shunts connected
to two battery sections, each battery section can contain one or
more battery strings. The controller limits the current flowing
through the shunts thereby limiting the charging current into the
batteries. This feature has no impact on the discharge current
flowing from the battery. The controller maintains the recharge
current within 10% of the set level.
The purpose of the test is to verify the battery capacity connected
to the plant. The reserve time can be predicted after the test and
stored in the memory for future retrieval. By discharging about
20% of the battery capacity, the controller can predict the total
reserve time if 100% battery capacity is discharged at the same
load condition.
This function can be enabled in the configuration process by
enabling the battery test in the appropriate configuration menu.
Refer to Section 4 for detail. If the function is enabled, this test
can be activated by accessing the operations menus and
manually pressing the Battery Test Start softkey. The battery test
Issue 4 January 2008 Operation 3 - 15
Galaxy Vector Controller GCM2, GCM3
can be stopped in the same manner, by pressing the Battery Test
Start softkey again during the test.
Note: The battery type should be configured before starting. The
Vector assumes one type of battery per system. The battery type
may be configured as either valve regulated or flooded.
During the test, rectifiers are set at a lower voltage. The set
voltage is the maximum of {LVD1 threshold +ΔV, the LVD2
threshold +ΔV, or EDV}, where EDV (the end voltage) = 22V
for 24V plant and 44V for 48V plant, ΔV = 0.6V for 24V plant
and 1.2V for 48 plant. The plant mode is returned to float mode
automatically if this set voltage is reached during the test.
The test stops automatically whether it is successful or not. Refer
to the configuration process in Section 4. During the test, the
default screen of the LED indicates a battery test is active. Any
alarm occurring during the test aborts the test, and causes the
system to return to float mode.
The last test results, battery reserve time, and load current are
stored in memory. The user can retrieve them under the
operations menu. Refer to the configuration process in Section 4.
Boost Mode Controls and Thresholds
Boost mode is a feature of the Vector which allows the user to
temporarily raise the system voltage to a higher, predetermined
level for a specified period of time. This feature may be useful in
systems using a flooded battery type where the batteries are
displaying symptoms of an undercharged state such as differing
cell voltages or in the case of the Lineage Power KS20472
Round Cell, lead-sulfate crystals visible on the vertical positive
plate columns. Boost mode may also be used to accelerate the
recharge of discharged strings to their full charge condition.
Plant voltage, while in Boost mode, is determined by the
configuration parameter Plant Boost Set- Point. Refer to “Plant
Boost Mode Settings” in Section 4. Like Float mode, there is no
individual adjustment of plant rectifiers. Load share among plant
rectifiers is automatic.
Boost voltage is determined from the battery manufacturer’s
recommendations, but must also be less than the maximum
voltage rating of all connected loads since Boost Mode raises the
entire system bus voltage. Typical boost levels and durations
used might include 2.25 VPC for 96 hours, 2.27 VPC (volts per
3 - 16 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
cell) for 72 hours, or 2.30 VPC for 48 hours. Do not exceed the
maximum voltage rating of any connected load.
Boost is typically not used with “sealed” or valve regulated
battery types. If it is used, it is generally completed at
significantly lower levels than that of flooded battery design to
avoid the build up of pressure and venting noted under the Float
mode section on Float Current Limit. When Boost mode is
disabled in the configuration menu, the feature cannot be
initiated.
Once enabled, Boost mode is entered by accessing the
operations menu and pressing the Boost softkey. The default
LCD screen shows that the system is in Boost mode of operation.
The present Boost duration is also displayed in hours. This Boost
duration can be edited with 0 and 24 hour minimum and
maximum values (0 = forever). Pressing the Step Boost mode
softkey returns the system to the Float mode. If a High Voltage,
High Float Voltage or RFA alarm occurs while in Boost mode,
the plant returns immediately to Float mode. AC Fail and Phase
Fail alarms does not affect Boost mode.
Boost mode has its own configuration parameters for Rectifier
Boost Current Limit, High Float Voltage Boost Threshold, and
High Voltage Boost Threshold, all of which control these
respective features and alarms whenever Boost mode is active.
Auto Timed Boost
The plant goes into Boost mode automatically if the following
conditions occur:
•Auto Boost is enabled
•Autoboost factor is configured from 1 to 9.
•A battery on discharge alarm occurs with AC Failure
alarms, or rectifier phase alarms occur for at least four
minutes.
When all rectifier phase and AC Failure alarms retire, the plant
automatically goes into boost mode.
The duration of the boost period is BD and AC Failure or Phase
alarm duration multiplied by the autoboost factor. The
maximum boost duration is limited to 24 hours.
Issue 4 January 2008 Operation 3 - 17
Galaxy Vector Controller GCM2, GCM3
If AC Failure alarms and Phase alarms are asserted while the
plant is in autoboost mode, the plant re-enters float mode,
retaining the remaining boost duration. If the Battery on
Discharge (BD) alarm asserts while the AC Failure or phase
alarm is active, the new multiplied time is be added to the boost
duration. When the AC Failure and Phase alarms retire, the plant
re-enters the boost mode for the remaining boost duration.
During autoboost, if the plant has a High Voltage, High Float
Voltage, or RFA alarm, the plant returns to float mode and the
remaining autoboost time is cancelled.
Plant
Battery/Generator
Tes t ( PB T)
Remote Access
and Monitoring
Plant Battery Test is a simple battery test feature available with
the Vector controller. When the controller receives a PBT signal
(either via an external input signal or, for use with the BLJ3
Terminal board only, via setting S1-7 to position 1), all the
rectifier output voltages are reset to 22V/44V so that the
batteries are placed on discharge. The plant voltage will drop to
only 22V/44V minimum, but remain at this voltage until the
PBT signal is released.
Vector does not reset the output voltage to 22V/44V, even if the
PBT signal is asserted, if there are any active major alarms or if
the serial communication alarm is active. If any major alarm
occurs during the test, the plant recovers to float mode and sets
all rectifiers back to the previous float setting.
The Vector controller offers local and remote (modem or
Gateway) access capability to communicate and configure a
limited set of features using personal computers. It is possible to
communicate with the Vector controller by two means:
• By using any ANSI (American National Standards Institute)
character-based terminal including terminal emulators into
either local or modem ports or by using a PC Telnet
communication session via a TCP/IP LAN connection and a
Gateway card. The T1.317 command language is the human
to machine interface used for this communication. Refer to
Appendix-A for modem and Gateway details.
• By using Galaxy EasyView, which combines both a
communications package and a user friendly Microsoft
Windows interface (local or modem ports only).
3 - 18 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
The Vector controller provides one remote access port. It may be
accessed remotely or from a terminal device. The port interfaces
with either the remote access interface card (BSM3) that
provides modem and RS-232 access, or with the Gateway card
(EBW1) for TCP/IP access. See Appendix A.
Once logged into the controller, users type in commands to
access measurements, configuration and control parameters in
the system. The command line interface used for incoming
connections is a version of T1.317 adapted for low end
controllers. Two levels of security, User and Super-user, are
provided to protect incoming access and to prevent any
unauthorized access.
The controller can be configured to dial out on alarm and dial out
when all alarms are cleared using the internal modem. The port
settings, configuration and command language used for remote
access as well as the error messages is described in the
Appendices A and B.
Remote Rectifier
Standby
Dial-out On
Alarm
The rectifiers can be placed in standby after accessing them
through the local port or through a modem. Once the rectifier is
placed in standby, it automatically recovers from this state when
the plant voltage drops below the BD threshold level, when the
active rectifiers cannot supply the plant demand.
This function requires the optional BSM3 modem card. See
Appendix A for description. By default, the controller is
configured not to dial-out at all. It can be configured to dial-out
to a primary phone number or an alternate phone number, used
if the controller fails connect to the primary phone number. The
controller attempts to dial-out when an alarm occurs that it has
not reported yet and when all alarms clear.
Phone numbers may be up to 25 characters long and may contain
any of the following characters: 0123456789,( )#* or space.
Configuring the phone numbers enables the controller to dialout. The phone number must be the number of a modem. After
the controller connects to the remote modem it sends an alarm
report. The alarm report is the same report generated by the
T1.317 “ala” command with addition of the site id at the
beginning of the report.
Issue 4 January 2008 Operation 3 - 19
Galaxy Vector Controller GCM2, GCM3
When attempting to dial-out, the controller first attempts to dial
the primary phone number. It makes up to three attempts, at 1minute intervals, to connect to the primary phone number. If
unsuccessful, the controller makes up to three attempts, at 1minute intervals, to connect to the alternate phone number. If
still unsuccessful, the controller waits for 15 minutes and then
repeats this cycle. The controller attempts the cycle 6 times
before giving up completely. If the controller successfully
contacts either the primary or alternate phone number it sends
the alarm report and then disconnects.
Whether or not the controller successfully connects with the
primary or alternate phone number, it makes a new attempt to
dial-out when a new alarm occurs or all active alarms clear.
The alarm report includes the site ID followed by all active
alarms in the system or the message NO ALARMS if no alarms
are active in the system.
3 - 20 Operation Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
4Installation and Configuration
This section covers the installation and configuration procedures
specific to the Galaxy Vector controller, including its
application in the Flexent system. This controller is typically
factory wired and assembled in a GPS series battery plant
equipped with serialized bus communication rectifiers. Follow
the installation instructions of the appropriate plant, rectifier,
converter and battery products to complete all external wiring
related to those components of the system.
WiringRefer to Figure 2-6 or Figure 2-7 for a summary of all
input/output connections associated with the Vector. Insure that
the factory connection (ribbon cable) between the BLJ3 or
BTJ2/BTJ3 terminal connection board and BMW in the Control
Panel assembly is present and secure. The digital serial bus
connection must be established from BLJ3 or BTJ2/BTJ3 board
port to the rectifiers.
Internal cabinet monitoring is factory wired to the appropriate
alarm input terminations. They are also available for connection
in the field.
PMJ, PMN, BD, HV/2ACF/VLV, ACF, and MJF alarm output
connections are provided on the BLJ3 or BTJ2/BTJ3 boards, as
described in Section 2 of this manual. Refer to Figure 2-6 and
Figure 2-7 for details.
If either or both of the available Low Voltage Disconnect (LVD)
circuits, LVD1 or LVD2 is equipped, the wiring from the BLJ3
or BTJ2/BTJ3 board LVD1 and LVD2 terminals to the
associated driver circuit and associated wiring from this driver
circuit to the Low Voltage Battery Disconnect or Low Voltage
Issue 4 January 2008 Installation and Configuration 4 - 1
Galaxy Vector Controller GCM2, GCM3
Load Disconnect must be completed. The installation of this
circuitry is covered in the appropriate plant product manual.
These connections are typically factory wired.
If the plant batteries are the sealed or maintenance free valveregulated type, Battery Thermal Compensation may be used.
This feature requires 10K ohm thermistor devices. The Vector
controller can monitor up to four temperatures. If more than four
devices are needed, a 210E thermistor multiplexer may be used.
The 210E is then wired into the BLJ3 or BTJ2/BTJ3 temperature
ports as shown in Figure 2-6 or 2-7. The installation of this
equipment is covered in its respective product manual. These
connections may be factory or field wired.
Thermistor input and alarm connections for the 210E thermistor
multiplexer unit are shown in Figure 4-1 (BLJ3 board), and
Figures 4-2a and 4-2b (BTJ2/BTJ3 board).
The Vector performs rectifier sequencing based on the state of
the ACF alarms from the rectifiers and Rectifier RO (Reserve
Operation) engine signal terminated at the BLJ3 RO terminal. If
this feature is to be used, complete this wiring as described in
Section 3.
4 - 2 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
210E
µP FailMaj
LED Test
Ω Out
Open/Shorted
Probe
BLJ3 with GCM2/3
J1
1
2
BK
G
Temperature Port
RTH ALM
RTH ALMR
Temperature Alarm
Ground
3
Min
4
5
6
O
R
BR
848302048 Cable Set
J4
4
6
RTHn+
RTNn
ENn
Probe Signal +
Probe Signal –
Probe Present
n = 1 to 4
These two connections are only required
if it is desirable to have the 210E Power
Minor Alarm (PMN) give a Temperature
Probe Alarm (TPA) for thermistor number 1.
Figure 4-1: 210E Thermistor Multiplexer Connections to BLJ3
Issue 4 January 2008 Installation and Configuration 4 - 3
Galaxy Vector Controller GCM2, GCM3
210E
µP FailMaj
LED Test
Ω Out
Open/Shorted
Probe
J1J9 (J11)
1
2
3
4
5
6
BK
O
BR
G
R
Y
J4
BK
O
BR
G
R
Y
Min
1
2
3
4
5
6
BTJ2/3 Temperature Port
J9, J10, J11, J12
Temperature Alarm
1
2
Lamp Test
3
Probe Signal +
4
Probe Signal –
5
Probe Present
6
J10 (J12)
Temperature Alarm
1
2
Lamp Test
3
Probe Signal +
4
Probe Signal –
5
Probe Present
6
Ground
Ground
847157674 Cable Set
Figure 4-2a: 210E Thermistor Multiplexer Connections with 847157674 Cable Set to BTJ2/BTJ3
4 - 4 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
210E
µP FailMaj
LED Test
Ω Out
Open/Shorted
Probe
J1J9-J12
1
2
3
4
5
6
J4
BK
4
Min
6
G
BK
G
BR
O
R
Y
848669412 Cable Set
BTJ2/3 Temperature Port
with GCM2/3 (OPS)
J9, J10, J11, J12
Temperature Alarm
1
Ground
2
3
Probe Signal +
4
Probe Signal –
5
Probe Present
6
Figure 4-2b: 210E Thermistor Multiplexer Connections with 8478669412 Cable Set to BTJ2/BTJ3
Front Panel
Operation
Default Front Panel Menu
The Galaxy Vector Controller with its LCD display presents a
default front panel screen. The System Bus Voltage and Load
Current are displayed on the screen. Plant voltage is displayed
while in this mode. Regardless of the active display mode, if no
key is pressed for approximately 3 minutes, the Vector returns to
its default menu. The present operating state of the system is also
displayed on the default menu.
View Active
Alarms Mode
If alarms are active in the system, the last two rows of the screen
will provide additional softkey information. The third row will
provide a softkey that allows a user to deactivate all audible
alarms. This is performed by using the “ACO” feature. The
fourth row on the display will provide immediate access to the
system alarms. This mode is entered by pressing the View
Active Alarms softkey. While in this mode, alarms are listed in
order of severity. All major alarms will be listed first, followed
by minor alarms. If four or more alarms are present, use the up
Issue 4 January 2008 Installation and Configuration 4 - 5
Galaxy Vector Controller GCM2, GCM3
or down arrows to scroll through the alarms. When no alarms are
present, the default screen will display No Active Alarms. To
exit View Active Alarms mode, press “Done” the Home key. If
no key is pressed for 3 minutes, the Vector returns to the default
screen automatically.
ConfigurationAll rectifiers must be numbered uniquely. Valid numbers for
rectifiers are 1 through 24. Refer to the appropriate sections of
the plant manuals for setting ID numbers. NP rectifier
numbering is managed through configuration in the shelf. For
additional information, consult the appropriate NP
documentation.
SW1 and Softkey Display Navigation in Configuration Mode
SW1-1 of the BLJ3 or BTJ2/BTJ3 board is a hardware enable
switch for Configuration mode of the Vector display. If
Configuration is not enabled, the user is only permitted to access
and view the configuration parameters, but may not change any
of them. To allow configuration changes, move SW1-1 to
position 0. Once configuration has been completed, it is a good
practice to disable (position 1) SW1-1 to prohibit someone from
mistakenly changing these parameters.
Configuration mode is entered by pressing the Home key to
display the menu selections. Press the appropriate softkey to
enter the Configuration mode. The first parameter of the
configuration menu will be displayed. Refer to Table 4-A for a
description of the parameters of the configuration menu. Note
that two columns of default values are shown, for standard and
Flexent applications. The defaults are determined by SW1-2.
SW1-2 = 0 is standard, SW1-2 = 1 is Flexent. SW1-2 is
recognized only upon power-up of the GCM.
In addition, the other remaining switches on SW1 (see Figures
2-6 and 2-7) are used to configure the installed option card, the
installed rectifier class, and alarm setting for alarm contacts
HV/2ACF/VLV. If no option card is installed, set S1-3 to the
factory default of “0”. This will allow local terminal access. The
GPS rectifier class includes all 596 and 595 series of serial
controlled rectifiers. NP rectifiers include NP2500, NP1500,
NP1200, and NP1300 with installed NPC1 GP serial
communication option cards. The alarm select switch, S1-5, can
be changed and recognized while the GCM is powered.
Similarly, S1-7 can be recognized while the GCM is powered
and setting this switch to “1” will manually force a PBT session
4 - 6 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
(BLJ3 board only). S1-8 is used only with the BTJ2/BTJ3
termination board to force the LVD1 contactor to a closed
position.
Once in configuration mode, use the ∧ and ∨ keys to select the
heading that contains the item you want to edit See Figure 4-x
for assistance. Press the appropriate softkey on the left to access
the item to be edited. Then use the appropriate arrow keys to
change the default values of the parameters being edited.
Generally the ∧ and ∨ arrows are used to scroll through a
selection of items or used to change a digit in a numerical value.
The < and > arrows are used to move left and right in a
configuration field. Items displayed in brackets identify the
user’s place in the menu structure. For instance, [config 1/3]
means screen 1 of 3 in the Configuration menu.
Once a change is made, two actions are available. The first is to
press the softkey designated “Save.” The new value for the
parameter is saved and will be used from then on. The second
choice is to press the softkey designated “Quit.” The new
parameter is not saved. The previous value is restored as the
system value. Pressing the Menu hardkey has the same effect as
“Quit.” Both of these choices remove the user from the
parameters edit screen.
If an attempt is made to set a parameter higher than allowable,
the maximum value will be displayed. Likewise, an attempt to
set a parameter lower than allowed results in display of the
minimum value.
To save changes made to a parameter value and return to the
configure menu, press the Save softkey. To return to the
configure menu without saving any changes to a parameter,
press the Quit softkey. To exit configuration mode and return to
the default screen, press MENU twice. If no key is pressed for
approximately three minutes, the display will return to the
default front panel screen.
Refer to Table 4-A as each of the Configuration Parameters is
explained in the following sections. Each section also explains
how to access the data available from these features.
Issue 4 January 2008 Installation and Configuration 4 - 7
Galaxy Vector Controller GCM2, GCM3
Table 4-A: Configuration Parameters
Main Menu
Heading
Float Voltage
Rectifiers
Shunts
Parameter
Description
System float
voltage set point
High float voltage
major alarm
High float voltage
minor alarm
Battery discharge
major alarm
Very low voltage
major alarm
Rectifier output
float current limit
Number of
rectifiers on line
System shunt typeBattery, load, noneBatteryBattery
Shunt 1 current
rating
Shunt 2 current
rating
(24V, 48V Systems)
Range
22-28V, 44-56V27.24V, 54.48V27.24V, 54.48V
25-30V, 50-60V28.24V, 57V28.5V, 57.0V
25-30V, 50-60V27.74V, 56V27.74, 56.0V
23-27.5V, 46-55V25.54V, 51.1V25.0V, 51.1V
20-25.5V, 40-51V23.00V, 46.00V23.0V, 46.0V
30-110%100%110%
1-2424, 124
0-9999A800A1000A
0-9999A0A0A
Default (24V, 48V Systems)
StandardFlexent
4 - 8 Installation and Configuration Issue 4 January 2008
Issue 4 January 2008 Installation and Configuration 4 - 9
Galaxy Vector Controller GCM2, GCM3
Table 4-A: Configuration Parameters (Continued)
Main Menu
Heading
Contactors
Converters
Boost
Parameter
Description
Contactor 1 typeBattery/Load/NoneNoneBattery
Disconnect voltage,
contactor 1
Reconnect voltage,
contactor 1
Contactor 2 typeBattery/Load/NoneNoneN/A, None
Disconnect voltage,
contactor 2
Reconnect voltage,
contactor 2
Converter set point
voltage
Converter
shutdown voltage
(disconnect
threshold)
Converter
shutdown voltage
enable (low voltage
disconnect)
Converter restart
voltage (reconnect
threshold)
Boost feature
enable
Boost set point
system voltage
High boost voltage
major alarm
threshold
High boost voltage
minor alarm
threshold
Auto boost feature
enable
Auto boost duration
(_ × BD duration)
Manual boost
duration
Boost current limit
(rectifier limit
during boost)
(24V, 48V Systems)
Range
20-26V, 40-52V21V, 43.2V21.25, 43.2V
20-26V, 40-52V22.2V, 44.4V25.00, 44.4V
20-26V, 40-52V21V, 43.2VN/A, 43.2V
20-26V, 40-52V22.2V, 44.4VN/A, 44.4V
46-57V50VN/A
20-26V21VN/A
Enable/DisableDisableN/A
20-26V22.2VN/A
Enable/DisableDisableDisable
24-30V, 48-60V27.24V, 55.2VN/A, 55.2V
26-30V, 52-60V28.24V, 57VN/A, 57.0V
25-30V, 50-60V27.74V, 56.2VN/A, 56.2V
Enable/DisableDisableDisable
1 to 91N/A, 1
1-250 hours8N/A, 8
30%-110%100%N/A, 100%
Default (24V, 48V Systems)
StandardFlexent
4 - 10 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Table 4-A: Configuration Parameters (Continued)
Main Menu
Heading
Communication
ports
Calibrate to meter
Parameter
Description
Local port baud rate
setting
Local port flow
control setting
Modem port baud
rate setting
Modem port flow
control setting
Number of rings
before modem
answers
Calibrate system
voltage to a new
value
Calibrate converter
voltage to a new
value
Range
(24V, 48V Systems)
Auto/1200 to 19,200AutoAuto
None/SW/HWNoneNone
Auto/1200 to 19,20024002400
None/SW/HWNoneNone
1 to 911
22-28V, 44-56VSystem voltageN/A
46-57VConverter voltageN/A
Default (24V, 48V Systems)
StandardFlexent
Battery Discharge
Test Results
After initiating a Battery Discharge Test through the Operations
menu, the user obtains the data or results from a battery
discharge test through the View Status menus. Selecting
Battteries > Battery Test Result displays the result of the last
battery test. The Vector stores the result of the last completed
test. This is the recorded data (not manually changeable) for the
battery test result. Refer to the battery discharge test operation
for detail test procedure and results.
Pressing the Battery Test Result softkey displays an indication
of the last battery test performed. The display indicates either
that the test was completed or not completed. In addition, the last
completed battery test results are saved and can be accessed by
pressing the “< View Completed” softkey. This allows the user
to observe the reserve time and load current during the test. If for
some reason the test was completed and results were
unsatisfactory, the message “Check Battery” is displayed. If the
last test was interrupted, the message “Not Available” is
displayed. If a test was stopped before completion, the phrase
“Previous Test Was Interrupted” will also appear when the
Battery Test softkey is pressed.
Issue 4 January 2008 Installation and Configuration 4 - 11
Galaxy Vector Controller GCM2, GCM3
When a test has been completed, the battery reserve time is
displayed in the form of hours and tenths of hours (hh.h).
Load current is displayed in the form of Amps without decimal
point (dddd). The load current is the current observed during the
test.
Battery Discharge
Test Enable
Two settings are available, Enable or Disable. Selecting Enable
allows the battery discharge test to be performed and selecting
Disable prevents the battery discharge test from being
performed. Press the < Save softkey to save one of the two
settings. When the test is enabled, the battery test softkey will be
enabled. Otherwise, the battery test softkey is disabled.
Shunt Type/Size The Vector provides three separate methods and up to two
separate shunt signals for use in determining the system current
to display. The access connections to the two shunt signals are
on the BLJ3 board SH1+/- and SH2+/- as shown in Figure 2-6,
or on the BTJ2/BTJ3 board J21 plug as shown in Table 2-M. The
shunts are rated for 50 mV and can be in the in the range of 09999 amps.
The method used by the Vector to determine the display load
value is determined by the configuration of the Shunt Type. The
three choices for this parameter are “None”, “Load”, and
“Battery”.
None: Select “None” if no shunt is used or connected to the
BLJ3 or BTJ2/BTJ3 board. Selecting “None” results in
displaying the system load current as the sum of the individual
rectifier loads. This may not be the true “load” current in systems
with battery backup since it includes the portion of the rectifier
loads which is floating or recharging the batteries, and will show
a 0 amp load when the rectifiers are off and the batteries are
carrying the system load. Typically, this shunt type would be
used only in batteryless systems, where this is an accurate
depiction of system load.
Load: Selecting “Load” as the shunt type assumes that one or
both of the shunt signals received through the BLJ3 or
BTJ2/BTJ3 board is monitoring load current. When the shunts
are configured for “Load,” the displayed system load is the sum
of all active shunts. Battery float or charge current can be
determined by subtracting this load current from the sum of the
4 - 12 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
individual rectifier loads. The use of two separate shunt signals
allows loads to two distribution bays to be monitored separately.
If the current is displayed as “Err,” the system may contain a
battery shunt or may be improperly wired.
Battery: Placing one or both shunts in the charge/discharge path
of the system batteries and configuring the shunts as Battery
shunts results in a current display that is the calculated difference
of the sum of the individual rectifier currents and the sum of the
battery charge currents obtained from the shunt measurements.
This is the typical configuration used with most distributed
architecture systems and is accurate regardless of whether
system batteries are charging or discharging.
Shunt Size The shunts are assumed to have a voltage rating of 50mV. The
full scale load ratings are user configurable. Each shunt can be
configured from 1 to 9999 amps. A value of 0000 disables that
shunt reading.
System Float
Mode Settings
The following parameters are settings which are active anytime
the plant is in Float mode.
System Float Voltage Set-Point: This is the output voltage that
all system rectifiers will be set to while in Float mode. If Battery
Thermal Compensation is enabled and active, the actual system
voltage will be adjusted from Float Set Point based on the
highest battery temperature monitored by the Vector.
Rectifier Float Current Limit: Rectifier current limit can be
adjusted from 30 to 110% of rectifier capacity. This is the
current limit while the system is in Float mode.
High Float Voltage Major Alarm Threshold: System voltage
monitored above this threshold results in a High Voltage major
alarm and possible rectifier shutdown while in Float mode.
High Float Voltage Float Minor Alarm Threshold: System
voltage monitored above this threshold results in a High Float
Voltage minor alarm (no rectifier shutdown) while in Float
mode.
Battery on Discharge Float Major Alarm Threshold: System
voltage monitored below this threshold results in a Battery
Discharge major alarm while in Float or Boost mode.
Issue 4 January 2008 Installation and Configuration 4 - 13
Galaxy Vector Controller GCM2, GCM3
Very Low Voltage
Threshold
Battery Recharge
Current Limit
Settings
Battery Thermal
Compensation
Settings
Very Low Voltage Major Alarm Threshold: In any system
mode, system voltage monitored below this threshold results in
a Very Low Voltage major alarm.
Battery Recharge Current Limit: The maximum current
flowing into a monitored battery string during a recharge period
is adjustable to any value between 10A and 1000A. At least one
battery string must be present to have this function.
Battery Recharge Current Limit Enable: To activate the
battery recharge current limit feature, the function must be
enabled in the appropriate configuration menu. The user must
select “enabled;” the default setting is “disabled.”
Refer to Figure 3-1 (Standard) or Figure 3-2 (Flexent) for a
graphical representation of the various Battery Thermal
Compensation settings.
High Battery Temperature Alarm Threshold (G): A
monitored battery temperature above this threshold results in a
Battery Temperature major alarm. This threshold can be set from
30°C to 85°C. The default temperature is 45°C.
High Battery Temperature Step Down Temperature (H): A
monitored battery temperature above this threshold results in a
“step” decrease in plant voltage to a level corresponding to 0.17
volts per cell (VPC) below the Plant Float Voltage Set-Point
(FSP). This threshold can be set from 45°C to 85°C. The default
temperature is 65°C.
Battery Temperature Slope Upper Temperature (F): This is
the upper temperature where Battery Temperature
Compensation will have reduced system voltage to a level
corresponding to F*(F-D)*cells-per-string below the FSP.
System voltage will be reduced proportionally at any
temperature between this point and the No Voltage
Compensation Temperature (D).
Battery No Voltage Compensation Temperature (Nominal
Temperature) (D): This is the zero compensation temperature
point. Temperatures monitored between this point and the High
Battery Temperature Voltage Decrease Upper Threshold (F)
will result in a proportional decrease of plant voltage to a level
corresponding to F*(F-D)*cells-per-string below the limit. If the
4 - 14 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Low Battery Temperature Compensation is enabled,
temperatures monitored between this point and the Battery Low
Temperature Voltage Increase Threshold (A) will result in a
proportional increase of plant voltage to a level corresponding to
C*(D-A)*cells-per-string above the limit.
Battery Low Temperature Voltage Increase Threshold (A):
This is the lower temperature where, if Battery Low
Temperature Compensation is enabled, the temperature
compensating feature will have increased system voltage to a
level corresponding to C*(D-A)*cells-per-string above the FSP.
System voltage will be increased proportionally at any
temperature between this point and the Nominal Battery
Temperature (D) Slope.
Battery High Temperature Voltage Decrease Rate (Slope)
Per Cell (E): This is the slope rate for the voltage decrease per
cell when the battery temperature is above the Nominal Battery
Temperature (D) Slope.
Low Voltage
Disconnect
Contactor 1 and 2
Settings
Battery Low Temperature Voltage Increase Rate (Slope) Per
Cell (C): This is the slope rate for the voltage increase per cell
when the battery temperature is below the temperature at which
there is no voltage compensation (Nominal Temperature, D).
Battery Low Temperature Voltage Compensation Increase
Enable: This feature must be enabled in the appropriate
configuration menu in order to compensate at the lower
temperatures. This feature increases plant voltage rather than
decreasing it based on temperature. The capability to enable this
feature separately from high temperature compensation is
provided so that equipment loads sensitive to high voltages can
be protected.
Battery Temperature Compensation Enable: Battery
Temperature Compensation (slope thermal compensation) must
be configured to “enabled” in order for the feature to be active.
Contactor 1 and 2 Low Voltage Disconnect Threshold: The
low voltage at which a signal will be sent to the respective
contactor driver circuit, causing it to open, disconnecting either
the load or the batteries, depending on the contactor’s location in
the circuit.
Issue 4 January 2008 Installation and Configuration 4 - 15
Galaxy Vector Controller GCM2, GCM3
Contactor 1 and 2 Reconnect Voltage Threshold: This is the
voltage at which a signal will be sent to the respective contactor
driver circuit, to force the contactor to reconnect or close. This
can be used to reconnect either loads or batteries, depending on
the contactor’s configuration within the system.
Contactor 1 and 2 Type: The contactor type defines how the
contactor is used in the system. The type can be set to one of
these three choices:
Noneno contactor available
Loadcontactor used for connecting a load
Batterycontactor used to connect/disconnect
battery strings
Plant Boost Mode
Settings
The following configuration parameters are settings which are
active anytime the plant is in Boost mode.
System Boost Set-Point: This is the voltage that all system
rectifiers will be set to when the Boost mode is entered.
Rectifier Boost Current Limit: This is the current limit of the
rectifiers while in Boost mode. This current limit is adjustable
from 30% to 110% of rectifier capacity.
High Voltage Boost Threshold: System voltage monitored
above this threshold results in a High Voltage major alarm. The
controller attempts to shutdown the offending rectifiers.
High Float Voltage Boost Threshold: A voltage monitored
above this threshold results in a High Boost Voltage alarm. No
rectifier shutdown attempts are made.
Boost Auto Enable: This function enables and disables the auto
boost feature. The parameter must be configured to “enabled”
for this feature to be available.
Boost Enable: This function enables and disables the manual
timed Boost feature. The parameter must be configured to
“enabled” for this feature to be available.
Boost Auto Mode Factor: This factor sets the duration of the
boost. A value from 1 to 9 sets the factor that determines how
long the plant is in boost mode after a discharge. The time is
4 - 16 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
determined by multiplying the BD duration by this factor. The
Boost Enable parameter must be enabled for this feature to be
available.
Converter
Settings
The following configuration parameters are settings which
affect the operation of any converters that may be connected to
the system and communication on the serial bus.
Converter Voltage Set-Point: This is the output voltage that all
converters will be set to by Vector.
Converter Low Voltage Disconnect Enable: This feature
allows the converter LVD to be operational. Select “Enabled” in
the configuration menu to enact the function.
Converter Low Voltage Disconnect Threshold: This is the
value at which the converters are placed into standby.
Converter Low Voltage Reconnect Threshold: This is the
value at which the converters are retired from standby and their
outputs returned to the set-point.
Converter Front Panel Voltage Calibration: The voltage
displayed on the front panel is the uncalibrated converter output
voltage as seen by the controller. If necessary, this voltage can
be calibrated to match a meter. Adjust the displayed voltage until
it matches the voltage displayed on a calibrated voltmeter that is
measuring the voltage across the converter’s output.
Voltage
Calibration
Controller’s displayed system voltage may be adjusted or
calibrated to a known, calibrated meter.
Caution:
This calibration affects all controller functions using plant
voltage and/or current values. These functions include the
float and boost set points. Generally, this feature is not
necessary.
Front Panel Voltage Calibration: The displayed value of
voltage can be adjusted by going through the configuration
menu. Under “Calibrate to meter,” the “System Voltage” softkey
can be used to adjust the system of the system voltage. Adjust the
Issue 4 January 2008 Installation and Configuration 4 - 17
Galaxy Vector Controller GCM2, GCM3
displayed voltage until it matches the voltage displayed on a
calibrated voltmeter measuring the plant or converter output
voltage.
Reserve
Operation Engine
Serial Bus
Updating and
Clearing
Number of Rectifiers On With Backup Engine (Reserve
Operation Engine): When a backup engine is running to supply
ac power to the rectifiers, a certain number of rectifiers in the
system are allowed to be turned on. This number should be based
on the engine capacity. The number can be selected between 1
and 24. The default number is 24 (maximum rectifiers on).
The user can perform several operations under the
Control/Operations softkey in the Main Menu. These operations
include Start Battery Test, Star Lamp Test, Updating the Serial
Link, and Starting Boost. Brief descriptions of these items
follow:
The Vector remembers any rectifier or converter connected to
the system’s digital serial bus. A Rectifier Fail Alarm (RFA) will
be active if any one of these components is removed from the
system or if communication is lost between the component and
the controller. If the controller is indicating Rectifier or
Converter Fail Alarm (RFA) and no alarm is indicated by the
LEDs of the rectifiers or converters, it may be necessary to clear
the Galaxy VC rectifier memory. Operating the Update Serial
Link (USL) resets the Vector rectifier memory and tells the
controller to recognize all devices on the bus. The alarm may be
cleared.
Note: A few moments after executing Update Link the
controller alarms should clear and each rectifier should display
no alarms. If alarms continue to be displayed, see Section 5,
Troubleshooting. USL will not restart the rectifiers or converters
at any time.
Software Release
Information
A report of the present software release active in the control
board microprocessor may be obtained via the
View Status -> Software Version menu path.
4 - 18 Installation and Configuration Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
5Troubleshooting
Replacing Circuit
Packs
Table 5-A: Replacement Circuit Packs and Temperature Modules
Table 5-A lists the circuit packs available as replacements in the
Vector Controller.
DesignationDescription
210EThermal Probe Multiplexer107789513
BLJ3Connection Board848262622
BMW2VC Control Panel108358102
BSM3Modem Board108415647
BSM4Local Port Isolation Board848501037
BTJ2+24V Outdoor Connection Board108629528
BTJ3-48V Outdoor Connection Board108963562
EBW1Gateway Network Card108340100
GCM224V Vector Control Board108890088
GCM348V Vector Control Board108890096
--LCD Display Module848518577
--Keypad848569430
Ordering
Number
Checking the
highest battery
temperature
If temperature probes are connected to the controller and thermal
compensation is enabled, the highest battery temperature can be
calculated based on the plant voltage. Temperatures between the
battery thermal lower temperature and the battery thermal
nominal temperature can be calculated if the raising of system
voltage is also enabled.
Calculate the temperature as follows:
voltage difference =
(system set point – system voltage reading)
cells per string
where cells per string is the number of 2-volt cells per string.
Issue 4 January 2008 Troubleshooting 5 - 1
Galaxy Vector Controller GCM2, GCM3
If voltage difference ≥ 0.17, the highest battery temperature is at
least as high as the battery thermal step temperature hysteresis
value, which is the battery thermal step temperature – 10 degrees
C.
If voltage difference = 0.1, the highest battery temperature is
between the battery thermal upper temperature and the battery
thermal step hysteresis value.
If voltage difference > 0 and voltage difference < 0.10,
temperature = thermal nominal temp + voltage difference ×
(thermal upper temp – thermal nominal temp)
Note: This will be a temperature in the range of the battery
thermal nominal temperature setting and the battery thermal
upper temperature setting.
If voltage difference ≤ -0.10, the highest battery temperature is
at or lower than the battery thermal lower temperature setting.
Inaccurate Plant
Voltage Readings
If voltage difference < 0 and voltage difference > -0.10,
temperature = thermal lower temp – voltage difference ×
(thermal nominal temp – thermal lower temp)
Note: this will be a temperature in the range of the battery
thermal lower temperature setting and the battery thermal
nominal temperature setting.
If the default menu of the LCD indicates that the system is in
“compensation mode,” this indicates that the plant voltage has
been altered to raise or lower based on the highest battery
temperature. Temporarily disabling the Battery Thermal
Compensation feature through the configuration menu returns
the system voltage to the set point.
The system voltage may differ slightly from an external meter
reading. This difference could be attributed to the calibration or
accuracy of the external voltmeter. A meter adjustment may be
attempted by using the “Calibrate to meter” function in the
Configuration menu. See to the plant voltage configuration
section.
5 - 2 Troubleshooting Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Temperature
Probe Alarm is
present
Unexplained
Rectifier Failure
Alarm and
Multiple Rectifier
Failure Alarm
The Temperature Probe Fail alarm indicates that either there is
something wrong with the temperature connections, or that there
is a problem with one of the external temperature processing
units. An additional possibility is that the alarm is indicating that
the thermal compensation feature is enabled, and that no
temperature probes are present. If there are no temperature
probes connected to the Vector, then disable the Battery Thermal
Compensation Enable setting.
A rectifier that is removed from the plant will generate a
Rectifier Fail Minor alarm. If more than one rectifier is missing,
a Multiple Rectifier Fail Major alarm is generated. To clear these
alarm conditions, go to the Operation Menu and assert the
Update Serial Link (USL) command.
Note: A few minutes after executing Update Serial Link function
to clear alarms, the controller RFA alarm should clear and no
rectifier should display any alarms. If alarms continue to be
displayed, continue investigating the system for possible
rectifier problems.
Unexplained
Converter Failure
Alarm and
Multiple
Converter Failure
Alarm
Rectifier Id
conflict alarm is
asserted
Converter Id
(Cid)
A converter that is removed from the plant will generate a
Converter Fail Minor alarm. If more than one converter is
missing, a Multiple Converter Fail Major alarm is generated. To
clear these alarm conditions, go to the Operation Menu and
assert the Update Serial Link (USL) command.
Note: A few minutes after executing Update Serial Link function
to clear alarms, the controller CFA alarm should clear and no
rectifier should display any alarms. If alarms continue to be
displayed, continue investigating the system for possible
converter problems.
This alarm indicates that a rectifier Id has not been set or is
duplicated in the system. Verify all rectifiers are numbered
uniquely between 1 and 24. Refer to numbering procedure in
rectifier manual.
This alarm indicates that a converter Id has not been set or is
duplicated in the system. Verify all converters are numbered
uniquely between 1 and 8. Refer to numbering procedure in bay
manual.
Issue 4 January 2008 Troubleshooting 5 - 3
Galaxy Vector Controller GCM2, GCM3
6Product Warranty
A. Seller warrants to Customer only, that:
1.As of the date title to Products passes, Seller will have the right to
sell, transfer, and assign such Products and the title conveyed by
Seller shall be good;
2.During the warranty period stated in Sub-Article B below, Seller’s
Manufactured Products (products manufactured by Seller), which
have been paid for by Customer, will conform to industry standards
and Seller’s specifications and shall be free from material defects;
3.With respect to Vendor items (items not manufactured by Seller),
Seller warrants that such Vendor items, which have been paid for by
Customer, will be free from material defects for a period of sixty
(60) days commencing from the date of shipment from Seller’s
facility.
B. The Warranty Period listed below is applicable to Seller’s Manufactured
Products furnished pursuant to this Agreement, commencing from date
of shipment from Seller’s facility, unless otherwise agreed to in writing:
Warranty Period
Product TypeNew ProductRepaired Product*
Central Office
Power Equipment
*The Warranty Period for a repaired Product or part thereof is six (6) months
or, the remainder of the unexpired term of the new Product Warranty Period,
whichever is longer.
C. If, under normal and proper use during the applicable Warranty Period,
a defect or nonconformity is identified in a Product and Customer
notifies Seller in writing of such defect or nonconformity promptly after
Customer discovers such defect or nonconformity, and follows Seller's
instructions regarding return of defective or nonconforming Products,
Seller shall, at its option attempt first to repair or replace such Product
without charge at its facility or, if not feasible, provide a refund or credit
based on the original purchase price and installation charges if installed
by Seller. Where Seller has elected to repair a Seller’s Manufactured
Product (other than Cable and Wire Products) which has been installed
by Seller and Seller ascertains that the Product is not readily returnable
for repair, Seller will repair the Product at Customer’s site.
24 Months6 Months
Issue 4 January 2008 Product Warranty 6 - 1
Galaxy Vector Controller GCM2, GCM3
With respect to Cable and Wire Products manufactured by Seller which
Seller elects to repair but which are not readily returnable for repair,
whether or not installed by Seller, Seller at its option, may repair the
cable and Wire Products at Customer’s site.
D. If Seller has elected to repair or replace a defective Product, Customer
shall have the option of removing and reinstalling or having Seller
remove and reinstall the defective or nonconforming Product. The cost
of the removal and the reinstallation shall be borne by Customer. With
respect to Cable and Wire Products, Customer has the further
responsibility, at its expense, to make the Cable and Wire Products
accessible for repair or replacement and to restore the site. Products
returned for repair or replacement will be accepted by Seller only in
accordance with its instructions and procedures for such returns. The
transportation expense associated with returning such Product to Seller
shall be borne by Customer. Seller shall pay the cost of transportation of
the repaired or replacing Product to the destination designated by
Customer.
E. Except for batteries, the defective or nonconforming Products or parts
which are replaced shall become Seller's property. Customer shall be
solely responsible for the disposition of any batteries.
F.If Seller determines that a Product for which warranty service is claimed
is not defective or nonconforming, Customer shall pay Seller all costs of
handling, inspecting, testing, and transportation and, if applicable,
traveling and related expenses.
G. Seller makes no warranty with respect to defective conditions or
nonconformities resulting from actions of anyone other than Seller or its
subcontractors, caused by any of the following: modifications, misuse,
neglect, accident, or abuse; improper wiring, repairing, splicing,
alteration, installation, storage, or maintenance; use in a manner not in
accordance with Seller’s or Vendor’s specifications or operating
instructions, or failure of Customer to apply previously applicable Seller
modifications and corrections. In addition, Seller makes no warranty
with respect to Products which have had their serial numbers or month
and year of manufacture removed, altered, or experimental products or
prototypes or with respect to expendable items, including, without
limitation, fuses, light bulbs, motor brushes, and the like. Seller’s
warranty does not extend to any system into which the Product is
incorporated. This warranty applies to Customer only and may not be
assigned or extended by Customer to any of its customers or other users
of the Product.
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND ARE IN
LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES,
INCLUDING BUT NOT LIMITED TO WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
CUSTOMER’S SOLE AND EXCLUSIVE REMEDY SHALL BE
SELLER’S OBLIGATION TO REPAIR, REPLACE, CREDIT, OR
REFUND AS SET FORTH ABOVE IN THIS WARRANTY.
6 - 2 Product Warranty Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
Appendix
A
Modem
Port SettingsThis section describes the communication port settings for the
Modular Phone Jack
Pin 3 - Tip
Pin 4 - Ring
Communications
BSM3 internal modem, external modem, and RS-232 terminal.
Figure A-1 shows the BSM3 modem board. In addition, set
SW1-3 to “0” for the MODEM option.
To Phone
Line
To Controller
(14 Conductor Cable)
TipRing
6
4
RS-232 Local Port
DS102
DS101
DS100
Yellow
Green
Green
Yellow and Green - Modem Board Not Initialized
(Terminal)
Status LEDs
Carrier Detect (Phone Line Connection)
Modem Board Fail
Modem Board Ok
Figure A-1: BSM3 Modem Board
Issue 4 January 2008 Communications Appendix A - 1
Galaxy Vector Controller GCM2, GCM3
The controller communicates with the BSM3 internal modem
and an external modem at the same communication settings.
These settings are as follows:
baud rate:2400
data bits:8
stop bits:1
parity:none
The controller communicates over the RS-232 terminal interface
using the following settings:
baud rate:9600 default, auto baud from 1200 to
19200
data bits:8
stop bits:1
parity:none
Logging inThis section describes how to log into the system. The first step
to logging in is to get to an "ENTER PASSWORD: " prompt.
From a modem, dial into the controller and wait for the modem
to connect. After the modem connects you will be presented with
the log-in prompt. If you don't see the log-in prompt after the
modem connects, you may have to press the ENTER key in
order to see the prompt.
From a terminal connected to the RS-232 port, simply press
ENTER until you are presented with the log-in prompt. The
number of ENTER keys required will depend on the baud rate
you are trying to connect at. The controller will adjust its baud
rate automatically until it recognizes the carriage return
character (ASCII 13) sent by pressing ENTER.
At the "ENTER PASSWORD" prompt type the user or superuser password. The default password for each level of security is
listed below.
lineagedefault user password
super-user default super-user password
In general, the user and super-user may view any measurement,
configuration, or control parameter. The super-user can also set
configuration and control parameters as well as change system
passwords.
Appendix A - 2 Communications Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
After receiving the correct password, the controller will respond
with one of the following command line prompts:
* user command line prompt
** super-user command line prompt
When these prompts appear the controller is ready to accept
commands. If the port is idle for 15 minutes then the session will
terminated.
Issue 4 January 2008 Communications Appendix A - 3
Galaxy Gateway
IntroductionThis section describes the Galaxy Gateway installation and
Galaxy Vector Controller GCM2, GCM3
cabling procedures required in a Galaxy Power System (GPS)
equipped with a Vector controller. Computer and Galaxy
Gateway configuration is also addressed. GPS configurations
consist of cabinets equipped with either a metal front door or a
plastic front door. Figures A-2a and A-2b show the Galaxy
Gateway installation for each configuration.
Figure A-2b: GPS with Plastic Door (DA) and Vector Controller
PreparationThe following Network Configuration Parameters must be
obtained from your Network Administrator before starting:
•IP address
•Subnet mask
•Host name
•Gateway IP address
Note: Host and Gateway are optional.
PrecautionsNote: Before starting, make sure proper ESD precautions are
observed. The ESD grounding termination point is located on
the door latch bracket of the GPS cabinet.
• Wear grounded antistatic wrist straps when handling all
circuit packs. The wrist strap must be in contact with the skin
and is not to be worn over clothing.
Issue 4 January 2008 Communications Appendix A - 5
Galaxy Vector Controller GCM2, GCM3
• Always consider personal safety. Be aware of the presence of
battery potential in the vicinity of the controller.
• Use only insulated tools.
Verify that no controller related alarms are active on the LCD
display panel. If controller alarm is active, consult the “Galaxy
Vector Controller ACP-BIC2, BIC3” or the “Galaxy Vector
Controller GCM2, GCM3” product manual for troubleshooting
help.
Tools/Equipment
Required
Unpacking the
Galaxy Gateway
Before installing and configuring the Galaxy Gateway, the
following tools/equipment are required:
• PC with terminal emulation program (example:
HyperTerminal)
• 9 pin male serial interface cable (DB-9 male) to connect to
Galaxy Gateway
• Network interface cable (CAT 5 UTP)
The 108876400 Galaxy Gateway Kit has been inspected, tested
and carefully packed. Examine the shipping carton and all
components for any sign of shipping damage.
1. Check for external damage to the shipping cartons.
2. Remove all parts from shipping cartons.
3. Check the following table and verify that all components
are present.
Appendix A - 6 Communications Issue 4 January 2008
Galaxy Gateway circuit pack
Black insulator (not used)
Millennium Controller interface cable (not used)
Nylon mounting posts (HMSP-TM-10)
Cable tie
Metal standoff (9740-SS-0632)
Screw, PPHM 6-32 x 5/16"
Black insulator
Vector Controller interface cable
Metal standoff (AL-5171-16)
Screw, PPHM M3 x 6mm
Nut, hex 6-32
Mounting bracket
If damage is found and/or components are missing, file a claim
with the carrier if applicable, and notify Lineage Power
Customer Service (See Section 1).
The physical interface for the Vector controller to the Galaxy
Gateway is through P4 connector on the BLJ terminal
connection board, close DIP switch S1.3 (set to 1) to allow
communication between Gateway and the Vector Controller.
Gateway
Installation for
Vector Controller
Use the following procedure and Figures A-2a and A-2b to
install a new or replacement Galaxy Gateway on a GPS metal or
plastic (DA) door.
1. Install 848649943 bracket to metal door and secure with
two 901351239 hex nuts (6-32) per Figure A-2a or install to
plastic door and secure with three 901377366 screws per
Figure A-2b.
2. Place 848589859 black insulator under the Galaxy Gateway
and position over the mounting standoffs so that J1 (RJ-45
network interface connector) and J2 (DB-9 serial port
connector) are facing down. The component side of the
circuit pack should be facing outward.
3. Install two 408456465 nylon mounting posts to the lower
mounting standoffs (torque to 3 in·lbs).
Issue 4 January 2008 Communications Appendix A - 7
Galaxy Vector Controller GCM2, GCM3
4. Install two 407882141 metal standoffs to the upper
mounting standoffs (torque to 10 in·lbs).
5. Wrap insulator around the Gateway board and snap onto
nylon posts. Using two 845143866 screws, secure top of
insulator to metal standoffs (torque to 10 in·lbs).
Galaxy
Gateway Cable
Connections
Gateway to Controller
The Galaxy Gateway receives power and communications from
the controller. Use the following procedure and Figure A-3 to
connect the Galaxy Gateway to the Vector controller.
1. Locate 848575841 controller interface cable provided in the
kit.
2. Identify the end with a black, 14 position connector.
Connect this end to P4 on the BLJ3 terminal connector
board.
3. The red and black leads should be connected to posts
marked ABS and DG of the BLJ3. The ABS connection is
protected by a 2 ampere fuse F1 (top fuse) on the BLJ3
terminal board. F3 holds a spare 2 amp fuse if needed. The
maximum current required by the Gateway is 600mA.
Verify that the current required by all equipment connected
to these ABS connections does not exceed the capacity of
the fuse. Connect the black 4-position connector of the
cable to the P1 power connector on the Galaxy Gateway.
Power will be applied to the Galaxy Gateway when this
cable is plugged into P1. The DB-9 male (9 pin) connector
will not be connected until after the Gateway is configured.
4. After the connection to P1, wait approximately 45 seconds.
The Yellow status LED should blink, indicating that the
Gateway is ready to be configured.
Appendix A - 8 Communications Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
ABS
DG
BLJ
Power
P1
J2
P4
EBW1
RS-232
J1
Network
Connection
Figure A-3: Gateway Connection to BLJ3 Terminal Board.
10Base-T Network
The Galaxy Gateway has an IEEE 802.3 compliant 10Base-T
network interface. Since the cable length required to connect the
Galaxy Gateway to the network is variable, this cable must be
supplied by the user. Connect the network interface cable from
the IEEE 802.3 compatible network to J1 (RJ-45) connector on
the Galaxy Gateway as shown in Figure A-3.
1. Connect one end of the network interface cable to J1 (RJ-45
Network Interface Connector), usually located at the bottom
right on the Galaxy Gateway. (Other configurations are
possible with the hardware shown in Figure A-3.)
2. Connect the other end to an IEEE 802.3 compatible
network.
Issue 4 January 2008 Communications Appendix A - 9
Galaxy Vector Controller GCM2, GCM3
Configuring
Network
Communications
The Galaxy Gateway uses Transmission Control Protocol/
Internet Protocol (TCP/IP) to communicate with the host
computer on a local area network. TCP/IP is a widely used
protocol that provides communication across networks of
diverse computers and devices. This protocol forms the basis for
the Internet. Each device or host on a
TCP/IP network has its own IP address. The IP address is a 32bit number, usually written in dot notation (e.g., 127.9.235.48).
Another 32-bit number, called subnet mask (or address mask,
netmask, e.g., 255.255.0.0) is used to identify the network
portion and subnet portion of the IP address.
1. Connect a PC to the local port (9-pin female connector) of
the Galaxy Gateway.
2. Using the built-in configuration utility, enter network
configuration information. This information may have to be
provided by the network administrator. The following
equipment is required:
• PC with terminal emulation program
Logging In to the
Galaxy Gateway
• Serial interface cable (DB-9 Male) for connection to the
Galaxy Gateway
To configure the Galaxy Gateway for your network, the
following information is required for the Galaxy Gateway
and your network:
• IP address
• Subnet mask
In addition, the following optional information may be
entered:
• Host name
• Default Gateway IP address
To login to the Galaxy Gateway, follow these steps:
1. Start-up the PC terminal program (Windows Terminal,
Procomm, etc.) using the following communication
parameters:
Appendix A - 10 Communications Issue 4 January 2008
Typing HELP at the “$” will show all available network
administration commands and command line formats.
Issue 4 January 2008 Communications Appendix A - 11
Galaxy Vector Controller GCM2, GCM3
*note: 1) commands are not case sensitive
2) for the commands that follow, ddd is a number from 0
- 255
• To set the IP Address, type:
CHA NET1,IP=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,IP
• To set the Subnet mask, type:
CHA NET1,SUB=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,SUB
• Optional:
To set the Default Gateway Address, type:
CHA NET1,GTWY=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,GTWY
• Optional:
To set the Host Name, type:
CHA NET1,HOST=host name
Verify by typing:
STA NET1,HOST
Logging Out of
the Galaxy
Gateway
To terminate the configuration session, enter the “bye”
command. The Galaxy Gateway will notify the user if
configuration is not complete. This message will have the
following format:
NOTICE:
Default gateway may be required for network
access.
Host Name may be required for network access.
Logging off...
Messages referencing the Gateway and Host Name are
acceptable, since these parameters are optional.
Note: If the IP address or Subnet mask messages appear, for
example:
IP Address is required for network access.
Subnet mask is required for network access.
Appendix A - 12 Communications Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
then the configuration procedure must be repeated.
Post Installation
Procedures
Once configuration has been completed
1. Disconnect the serial cable from the Galaxy Gateway (J2
connector).
2. Connect the 9-pin male end of the auxiliary port cable
assembly to the J2 connector on the Galaxy Gateway.
3. Press SW1 (uP reset) on the Galaxy Gateway.
4. After approximately one minute, observe the LEDs on the
Galaxy Gateway.
• Yellow STATUS LED: OFF
• Green STATUS LED: ON
• Link LED: ON
• XMIT/RCV: May be blinking
The Galaxy Gateway should be communicating over the
network.
5. Secure the cable to the lance on the mounting bracket using
the cable tie provided.
Issue 4 January 2008 Communications Appendix A - 13
Galaxy Vector Controller GCM2, GCM3
Appendix
T1.317 Objects and Attributes
B
The command language is based on the T1.317 standard. The T1.317 standard has been
adapted to the needs of a low-end controller. This section describes the commands, objects
and attributes used to access measurements, configuration, and control parameters in the
controller.
Objects and Attributes
The T1.317 standard organizes system parameters called attributes into groups called
objects. The tables below lists the objects supported for remote access.
An object-attribute pair uniquely identifies a measurement, configuration, or control
parameter. For example, the object-attribute pair "dc1,vdc" identifies the plant voltage
while the object-attribute pair "dc1,adc" identifies the plant load current. In each of these
examples "dc1" identifies the plant object and "vdc" and "adc" identify DC voltage and DC
current respectively. The table below summarizes the object-attribute pairs in the system
along with the commands that can be used with the pair and the valid range that the attribute
may have. Commands are defined in detail in the following section.
Issue 4 January 2008 T1.317 Objects and Attributes Appendix B - 1
Galaxy Vector Controller GCM2, GCM3
Table B-1: Power System
Related Commands
OBJ,ATTRDESCRIPTIONSTACHAOPETYPERANGE OF VALUES
ps1,desPower system description√text"Tyco Vector Controller"
ps1,sidSite ID√√textUp to 15 characters:""
ps1,swvSoftware version√textVector software version
ps1,uslUpdate serial link
& clear alarms√√number 1
Table B-2: DC Plant
Related Commands
OBJ,ATTRDESCRIPTIONSTACHAOPETYPERANGE OF VALUES
dc1,sttPlant state√√text"FLOAT", "BOOST"
dc1,vdcPlant voltage√number dd.dd V
dc1,adcPlant load current√number dddd A
dc1,shtPlant shunt type√√text"NONE","LOAD","BATTERY"
dc1,sha1Plant shunt 1 size√√Number 0-9999:800 0 means none
dc1,sha2Plant shunt 2 size√√Number 0-9999 0 means none
dc1,trdPlant Total Rectifier Drain√number dddd A
Table B-3: Alarm Thresholds
Related Commands
OBJ,ATTRDESCRIPTIONSTACHAOPETYPERANGE OF VALUES
hva1,fthVery High Float Voltage Major √√number 25-30:28.24V or 50-60:57V
hva1,bthVery High Boost Voltage Major√√number 26-30:28.24V or 52-60:57V
hfv1,fthHigh Float Voltage Minor√√number 25-30:27.74V or 50-60:56V
hfv1,bthHigh Boost Voltage Minor√√number 25-30:27.74V or 50-60:56.20V
bda1,thrBattery on Discharge√√number 23-27.50:25.54V or 46-55:51.10V
vla1,thrVery Low Voltage√√number 20-25.5:23V or 40-51:46V
bta1,thrBattery Thermal Alarm√√number 30:85:55°C
Table B-4: Rectifier Management
Related Commands
OBJ,ATTRDESCRIPTIONSTACHAOPETYPERANGE OF VALUES
gm1,fspRectifier float set-point√√number 22-28.5:27.24V or 44-56:54.48V
gm1,bspRectifier boost set-point√√number 24-30:27.24V or 48-60:55.20V
gm1,fclRectifier float current limit√√number 30-110:100%
gm1,bclRectifier boost current limit√√number 30-110:100%
gm1,roneRectifiers on while on engine √√number 1-24
Appendix B - 2 T1.317 Objects and Attributes Issue 4 January 2008
enable√√number 0:disable 1:enable
br1,cltBattery recharge current limit √√number 10-1000 A
br1,btcBattery test class√√text"FLOODED","VALVE-REG"
br1,bteBattery test enable√√number 0:disable 1:enable
br1,btrBattery test results√mixedresult, reserve, load
code: ok, aborted, failed, not run,
interrupted
reserve: dd.d (hours)
load: dddd (amps)
br1,btsBattery test state√√number 0:inactive 1:active
Table B-7: Battery Sections
Related Commands
OBJ,ATTRDESCRIPTIONSTACHAOPETYPERANGE OF VALUES
b01,adcBattery section 1 current√dddd A
b02,adcBattery section 2 current√dddd A
Table B-8: Controller Battery Temperature Channels
Related Commands
OBJ,ATTRDESCRIPTIONSTACHAOPETYPERANGE OF VALUES
ct1,valController battery temp chan 1√dd °C
ct2,valController battery temp chan 2√dd °C
ct3,valController battery temp chan 3√dd °C
ct4,valController battery temp chan 4√dd °C
Issue 4 January 2008 T1.317 Objects and Attributes Appendix B - 3
Galaxy Vector Controller GCM2, GCM3
Table B-9: Converter Plant
Related Commands
OBJ,ATTRDESCRIPTIONSTACHAOPETYPERANGE OF VALUES
cp1,vdcConverter output voltage√number dd.d V
cp1,adcConverter load current√number dd.d A
cp1,vspConverter float set-point√√number 46-57:50V
cp1,dthConverter disconnect
threshold√√number 20-26:21.00V
cp1,rthConverter reconnect threshold√√number 22-26:22.20V
cp1,lvdConverter low voltage
Issue 4 January 2008 T1.317 Objects and Attributes Appendix B - 5
Galaxy Vector Controller GCM2, GCM3
Commands
This section describes each of the remote access commands supported by this controller.
ala Report Active Alarms
Syntax ala
Description:
This command reports all the active alarm conditions in the plant. One alarm message is
listed per line in the report. The table below lists the alarm messages.
Table B-15: Alarm Messages
MAJ,Multiple Rectifier
MAJ,Multiple AC Fail
MAJ,Rectifier ID Conflict
MAJ,Very Low Voltage
MAJ,Battery On Discharge
MAJ,High Voltage
MAJ,Sense Fuse
MAJ,Multiple Converter Fail
MAJ,Converter Distribution Fuse
MAJ,Converter Fan Major
MAJ,Fuse Major
MAJ,Auxiliary Major
MAJ,Contactor 1 Open
MAJ,Contactor 1 Failed
MAJ,Contactor 2 Open
MAJ,Contactor 2 Failed
MAJ,Battery High Temp
MAJ,Open Connection
MIN,Rectifier Fail
MIN,AC Fail
MIN,Phase Fail
MIN,Manual Off
MIN,High Float Voltage
MIN,Converter Fail
MIN,Converter ID Conflict
MIN,Converter Fan Minor
MIN,Load Share Imbalance
MIN,Thermal Probe Failure
If no alarms are active "NO ACTIVE ALARMS" is reported.
bye Log-off
Syntax bye
Description:
This command is used to terminate remote access session. If the user is connected via a
modem, the controller will command the modem to hang-up the line.
Appendix B - 6 T1.317 Objects and Attributes Issue 4 January 2008
Galaxy Vector Controller GCM2, GCM3
cha Change Value
Syntax cha obj,attr=value
where: obj,attr is an object-attribute pair. For example, ps1,sid.
Description:
This command is used to change system configuration parameters. A couple of examples
are listed below to illustrate how this command works.
cha ps1,sid="My Plant" - change the site id to My Plant
cha p1,phn="123456789"- change the primary phone number to 123456789
You must be logged in as a super-user to use this command.
login Login
Syntax login "password"
where: password is either the user or super-user password
Description:
This command is used to log-in as a user or super-user. For example, if you are currently
logged into the controller as a user but would like to change the site id you must first use
this command to log-in as a super-user.
ope Operate a Control
Syntax ope obj,attr=value
where: obj,attr is an object-attribute pair. For example, dc1,pbt.
Description:
This command is used to operate a system control parameter. A couple examples are listed
below to illustrate how this command works.
ope dc1,pbt=1start a plant battery test
ope dc1,stt="boost"place plant into boost mode
You must be logged in as a super-user to use this command.
pas Change Passwords
Syntax pas t,"password", "password"
where:t is u to change the user password or s to change the super-user password
password is the new password
Description:
This command changes either the user or super-user password. You must be logged in as a
super-user to use this command. The password is sent twice in order to avoid mistakes. The
password must have at least 6 characters but no more than 15 characters.
Issue 4 January 2008 T1.317 Objects and Attributes Appendix B - 7
Galaxy Vector Controller GCM2, GCM3
sta Report Status
Syntax sta obj,att
where: obj,attr is an object-attribute pair. For example, ps1,sid.
Description:
This command reports the value of the measurement, configuration, or control parameters
in the system. A couple of examples are listed below to illustrate how this command works.
sta dc1,vdc- report plant voltage
sta dc1,adc- report plant load current
The command line would respond as follows for first command listed above.
* sta dc1,vdc
:DC1
VDC=-52.48
.
* _
The “*” in the example above is the user command line prompt. The line “:DC1” indicates
that the information that follows is for the plant object. The line starting with “VDC”
identifies the DC voltage. The “.” line is the end-of-command identifier.
Error Messages
While logging into the vector controller or while entering commands you may encounter
one or more of the following error messages:
Table B-16: Error Messages
Error MessageDescription
!-112,SYNTAX ERRORUnrecognizable command was entered.
!-220,SECURITYSuper-user command was entered by a mere user.
!-221,EXCESSIVE LOGIN ATTEMPTSToo many attempts were made to login with an unrecognized password.
!-223,INVALID PASSWORDNew password contains an illegal character.
!-224,NEW PASSWORD MISMATCHFirst and second copy of new passwords don't match
!-304,INVALID PARAMETERAn attempt was made to change a parameter to an illegal value.
!-319,INVALID ATTRIBUTEAn invalid object id was specified in the command or, a command referred to
an attribute that doesn't support it.
!-320,INVALID OBJECTAn invalid object id was specified in the command
Appendix B - 8 T1.317 Objects and Attributes Issue 4 January 2008
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.