GE Industrial Solutions EntelliGuard G Flat front Terminations Envelope User Manual

1
Accessories
WARNING: Before installing any accessories, turn the
AVERTISSEMENT: Avant d’installer tout accessoire,
DEH
Flat front Terminations Envelope 1 & 2
Flat Front Terminal assemblies are supplied with the Entelliguard breaker when needed
Fig A. Flat front Termination assembly
Catalogue No:
Catalog # Description GBB1TBF3 Envelope 1-3pole 800 - 2000A GBB1TBF4 Envelope 1-4pole 800 - 2000A GBB2TBF3 Envelope 2-3pole 800A - 3000A GBB2TBF4 Envelope 2-4pole 800A - 3000A
GBB1STBF3 Envelope 1-3pole Type S up to 1200A GBB1STBF4 Envelope 1-3pole Type S up to 1200A
- 41405 Installation Instructions
EntelliGuard ® G Circuit Breaker
Flat Front Terminations for Fixed Breaker
Flat Front Terminations Assembly Procedure:
1. Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background.
2. Assemble the Flat Front to the rear terminals with M12 Hardware as shown in Fig A., Tighten the hardware to torque 50N-m (36.9 ft-lbs)
3. Assemble the Heat Sink with M8 Hardware to Flat Front as shown in Fig A. Tighten to torque 12­14N-m (8.9-10.3 ft-lbs)
4. Similarly populate the Flat Front and Heat sink on all other terminals as shown in fig B & C.
5. The bus bars to be supported within 200mm distance and tightened to 50N-m (36.9ft-lbs) torque.
breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation, et décharger les resorts d’armement
2
These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in con
nection
GE
Fig C. 4 Pole Breaker assembly
Fig B. 3 Pole Breaker assembly
Fig D. F1 3 Pole Breaker assembly Type S up to 1200A Fig E. F1 4 Pole Breaker assembly Type S up to 1200A
with installation, operation, or maintenance. Should further information be desired, or should particular problem s arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE.
41 Woodford Ave, Plainville, CT 06062 www.geelectrical.com
© 2009 General Electric Company
DEH- 41405 R02 (30/08/2010)