GE Industrial Solutions EntelliGuard G Drawout Secondary Disconnect User Manual

Introduction

Drawout Secondary Disconnect:

Drawout breakers are always supplied with one secondary disconnect (auxiliary connection block) suitable for 39 connection points (terminal A). When the number of factory installed accessories exceeds the available number of connection
nd
points needed, a 2 automatically added (terminal B) to the Breaker. For cases where the accessories are mounted in the field, or needed for the cassette an additional auxiliary connection block can be added to provide 39 more additional connections.
Figure 1. SD Breaker End
Figure 2. SD Cassette End
connection block is
DEH-41401 Installation Instructions
EntelliGuard ® G Circuit Breaker Accessories
Drawout Secondary Disconnect
WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
AVERTISSEMENT: Avant d’installer tout accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement
Catalog Number:
Catalog No Description GSDWTR Aux, Disconnect Drawout 39
terminal
Use the following procedure to install the Drawout Secondary Disconnect accessory into the circuit breaker.

Installation of Breaker side Secondary disconnect:

1. Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background. If installing in a draw-out type breaker remove breaker from adaptor (cassette) before continuing.
2. The breaker should be safely isolated and fully removed from the cassette.
3. Place the secondary disconnect block on the mounting bracket and assemble the two mounting screws as shown in fig 3 & 4
.
1
1. Remove the screw shown in the fig 6.
Figure 3. Screws assembly
Figure 4. Screws assembly
4. Push the secondary disconnect block toward the back of the mounting plate of the breaker and ensure it is inline with the first block as shown in fig 5.
Figure 6. Removing the screw
2. Assemble the label as shown in the fig 7.
Figure 7. Label assembly
3. Assemble the new SD block as shown in fig 8 &
9.
Figure 5. SD assembly

Installation of Cassette side Secondary disconnect:

Figure 8.
2
Loading...
+ 2 hidden pages