GE Industrial Solutions EntelliGuard G Auxiliary Switch User Manual

Introduction Auxiliary Switch:
Auxiliary contacts indicate the position of the Circuit Breaker main contacts. These contacts operate simultaneously with the breakers main contacts. Default breaker configuration consists of 3 normally open (NO) and 3 normally closed (NC) contacts. The STD Auxiliary switch (GAUX3R) can be replaced with any of the following configurations to increase the number of available contacts.
Power rated contacts 8 NO & 8 NC
(GAUX6R)
Power rated contacts 3 NO & 3 NC plus
Low Signal rated contacts 2 NO & 2 NC (GAUX5R)
Power rated contacts 4 NO & 4 NC plus
Low Signal rated contacts 4 NO & 4 NC (GAUX8R)
See Wiring Diagram on last page for Power Rated and Low Signal Connections
DEH-41415 Installation Instructions
EntelliGuard ® G Circuit Breaker Accessories
Auxiliary Switch
WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
AVERTISSEMENT: Avant d’installer tout accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement

Table 1. Auxiliary switch ratings

AC Ratings

AC
220/240V 10A 110/120V 15A
DC Ratings*
5A (6 contacts in
series)
10A (3 contacts in
series)
DC
240V
125V
24V 15A
* DC ratings are not UL listed
Note: The following Aux options are not available when a Side Mounted Disconnect or Coil Signaling Contacts are installed in the breaker
Power rated contacts 4 NO & 4 NC plus
Low Signal rated contacts 4 NO & 4 NC (GAUX8R)
Power rated contacts 8 NO & 8 NC (GAUX6R)
1
Use the following procedure to install the Auxiliary Switch accessory into the circuit
breaker.
1. Verify that the rating on the Auxiliary Switch identification plate matches the voltage rating required for the application, as listed in Table 1.

2. Side mounted Breakers are limited to maximum 5 NO & 5 NC contacts.

3. Verify Secondary Disconnect Block B is present.
4. Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background. If installing in a draw-out type breaker remove breaker from adaptor (cassette) before continuing.
5. Loosen the 6 screws on front cover (fascia) using a posidrive screw driver as shown in Fig 1.B Rotate the charging handle down and slide the front cover over the handle to remove the front cover as shown in Fig. 1.C.
Figure 2. Unplug the existing connectors.
7.
Remove the e-ring from the Auxiliary switch
link to the mechanism as shown in Fig. 3.
Figure 3. E-ring removal
8. Remove the existing M5 nut & M6 screw from the assembly as shown in Fig. 4.
Figure 1. (A) Front Cover (B) Screw Removal (C) Handle Rotation
6. Unplug the existing Auxiliary switch connector plugs from the secondary disconnect as shown in Fig. 2.
Figure 4. Remove the Screw & nut
9. Remove the existing Auxiliary switch assembly from the housing as shown in Fig. 5.
2
Loading...
+ 2 hidden pages