, MicroVersaTrip® PM or MicroVersaTrip® Plus Trip Units
For Catalog Number SDCHA11, SDCHA30, SDCHA60
Circuit Breaker Accessory
Overview
The General Electric Distribution Cable Harness is a
modular connector used to carry a variety of electronic
signals between Spectra
Breakers with microEntelliGuard
PM/Plus Trip Units and Distribution Cable Accessories.
The Distribution Cable accessories supported by the
Distribution Cable Harness are as follows:
• Power Supply Plate
• Voltage Conditioner Plate
• Power Supply Assembly
• Voltage Conditioner Assembly
• Distribution Cable Junction Box
• Distribution Cable Extension
• Distribution Cable Terminal Block
• Voltage Module
®
RMS Molded-Case Circuit
TM
or MicroVersaTrip®
The Distribution Cable Harness is also used in GE
Spectra
Distribution Cable Junction Boxes (Cat. Nos. SDCJBB
and SDCJBBC) to other Distribution Cable Junction
Boxes or to connect Distribution Cable Boxes to the
Voltage Module.
Because both ends are receptacles, you cannot use the
Distribution Cable Harness as an extension cable; use
the Distribution Cable Extension (Cat. Nos. SDCEA30
and SDCEA30C) for this application (microEntelliGuard
Trip Units with 20-pin connectors use the SDCEA30C
extension cable).
®
Series Switchboards to either connect
TM
Page 2
GEH-6255 Installation Instructions
Figure 1 shows how the Distribution Cable Harness is used in a typical MicroVersaTrip® PM system. Figure 2 shows
how the Distribution Cable Harness is used in a typical MicroVersaTrip
®
Plus system. The microEntelliGuard
TM
Trip
Unit can be used with either configuration, i.e. Figure 1 or Figure 2. The connection diagram shown in Figure 2
TM
applies to microEntelliGuard
Trip Units with Basic Metering.
Figure 1. Typical MicroVersaTrip® PM Trip Unit System detailing the Distribution Cable Harness.
Page 3
GEH-6255 Installation Instructions
Figure 2. Typical MicroVersaTrip® Plus Trip Unit System detailing the Distribution Cable Harness.
Page 4
GEH-6255 Installation Instructions
The electronic signals supported by the Distribution
Cable Harness vary depending on the type of trip unit
used; a list of supported functions is as follows:
®
Spectra
MicroVersaTrip
RMS Breaker with microEntelliGuardTM or
®
PM Trip Unit
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• Voltage A f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• Voltage B f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• Voltage C f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
®
Spectra
microEntelliGuard
RMS Breaker with MicroVersaTrip® Plus or
TM
(with Basic Metering) Trip Unit
• Control power (+24vdc)
• Control power (-common)
another Distribution Cable Accessory, align the harness
receptacle interlock with the plug hook of the mating
Distribution Cable accessory and insert the receptacle
into the plug until the interlock and hook overlap and
catch (see Figure 4).
To disconnect the Distribution Cable Harness, press
down at the rear of the receptacle interlock until the
interlock clears the hook, and remove the receptacle
(see Figure 5).
Figure 3 shows the connector pinout for the Distribution
Cable Harness for each type of trip unit.
Connections
The Distribution Cable Harness contains a 12-pin
receptacle connector on each end. The connectors are
keyed so they cannot be inserted incorrectly into a
mating 12-pin plug connector.
To connect the end of the Distribution Cable Harness to
Figure 4. Side view of receptacle-plug connection insertion.
Figure 3. End view of Distribution Cable Harness detailing available pinout connections.
Page 5
GEH-6255 Installation Instructions
Figure 5. Side view of receptacle-plug connection removal.
ADDITIONAL INFORMATION
Refer to these other user’s manuals for more details·:
®
GEH-5934 MicroVersaTrip
PM Trip Units in Spectra
Plus and MicroVersaTrip®
®
RMS Molded-
Case Circuit Breakers
®
GEH-700 Spectra
G Breaker w/
microEntelliGuard™ Trip Unit
®
GEH-701 Spectra
G Breaker w/
microEntelliGuard™ Trip Unit
GEH-702 microEntelliGuard™ Trip Unit Users Manual
DEH-41318 Universal Rating Plug
GEH-6250 Voltage Module
GEH-6251 Power Supply Plate
GEH-6252 Voltage Conditioner Plate
GEH-6253 Power Supply Assembly
GEH-6254 Voltage Conditioner Assembly
GEH-703 MET Battery Pack Adapter
GEH-704 MET Advanced Distribution Cable
Junction Box
DEH-006 Distribution Cable Junction Box
GEH-705 MET Distribution Cable Extension (20-pin)
GEH-6256 Distribution Cable Extension (12-pin)
GEH-706 MET Distribution Cable Terminal Blocks
(11 point & 22 point)
GEH-6257 Distribution Cable Terminal Block (11 point)
GEH-6491 POWER LEADER™ Modbus Concentrator
GEH-6502 POWER LEADER™ PMCS 5.0 Network
Architecture Guide
GEH-707 MET Sealable Cover kits
DEH-4568 GTU digital test kit (GTUTK20)
GEH-5551 Shunt Trip and UVR instructions
GEH-5593 Aux switch and bell alarm
GEK-64467 TIM-1 Zone Selective Interlock Module
Page 6
GEH-6255 Installation Instructions
Notes
Page 7
GEH-6255 Installation Instructions
Notes
Page 8
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and
microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they
provide for every possible contingency that may be met in connection with installation,
operation, or maintenance. Should further information be desired or should particular
problems arise that are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to the GE Company.