GE Industrial Solutions Distribution Cable Harness User Manual

Page 1
GE Energy
Industrial Solutions
GEH-6255 Installation Instructions
Distribution Cable Harness
For Spectra® RMS Molded-Case Circuit Breakers
TM
with microEntelliGuard
, MicroVersaTrip® PM or MicroVersaTrip® Plus Trip Units
For Catalog Number SDCHA11, SDCHA30, SDCHA60
Circuit Breaker Accessory
Overview
The General Electric Distribution Cable Harness is a modular connector used to carry a variety of electronic signals between Spectra Breakers with microEntelliGuard PM/Plus Trip Units and Distribution Cable Accessories. The Distribution Cable accessories supported by the Distribution Cable Harness are as follows:
• Power Supply Plate
• Voltage Conditioner Plate
• Power Supply Assembly
• Voltage Conditioner Assembly
• Distribution Cable Junction Box
• Distribution Cable Extension
• Distribution Cable Terminal Block
• Voltage Module
®
RMS Molded-Case Circuit
TM
or MicroVersaTrip®
The Distribution Cable Harness is also used in GE Spectra Distribution Cable Junction Boxes (Cat. Nos. SDCJBB and SDCJBBC) to other Distribution Cable Junction Boxes or to connect Distribution Cable Boxes to the Voltage Module.
Because both ends are receptacles, you cannot use the Distribution Cable Harness as an extension cable; use the Distribution Cable Extension (Cat. Nos. SDCEA30 and SDCEA30C) for this application (microEntelliGuard Trip Units with 20-pin connectors use the SDCEA30C extension cable).
®
Series Switchboards to either connect
TM
Page 2
GEH-6255 Installation Instructions
Figure 1 shows how the Distribution Cable Harness is used in a typical MicroVersaTrip® PM system. Figure 2 shows how the Distribution Cable Harness is used in a typical MicroVersaTrip
®
Plus system. The microEntelliGuard
TM
Trip
Unit can be used with either configuration, i.e. Figure 1 or Figure 2. The connection diagram shown in Figure 2
TM
applies to microEntelliGuard
Trip Units with Basic Metering.
Figure 1. Typical MicroVersaTrip® PM Trip Unit System detailing the Distribution Cable Harness.
Page 3
GEH-6255 Installation Instructions
Figure 2. Typical MicroVersaTrip® Plus Trip Unit System detailing the Distribution Cable Harness.
Page 4
GEH-6255 Installation Instructions
The electronic signals supported by the Distribution Cable Harness vary depending on the type of trip unit used; a list of supported functions is as follows:
®
Spectra MicroVersaTrip
RMS Breaker with microEntelliGuardTM or
®
PM Trip Unit
• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• Voltage A f (must be from Voltage Module or Voltage Conditioner Plate or Voltage Conditioner Assembly)
• Voltage B f (must be from Voltage Module or Voltage Conditioner Plate or Voltage Conditioner Assembly)
• Voltage C f (must be from Voltage Module or Voltage Conditioner Plate or Voltage Conditioner Assembly)
®
Spectra microEntelliGuard
RMS Breaker with MicroVersaTrip® Plus or
TM
(with Basic Metering) Trip Unit
• Control power (+24vdc)
• Control power (-common)
another Distribution Cable Accessory, align the harness receptacle interlock with the plug hook of the mating Distribution Cable accessory and insert the receptacle into the plug until the interlock and hook overlap and catch (see Figure 4).
To disconnect the Distribution Cable Harness, press down at the rear of the receptacle interlock until the interlock clears the hook, and remove the receptacle (see Figure 5).
Figure 3 shows the connector pinout for the Distribution Cable Harness for each type of trip unit.
Connections
The Distribution Cable Harness contains a 12-pin receptacle connector on each end. The connectors are keyed so they cannot be inserted incorrectly into a mating 12-pin plug connector.
To connect the end of the Distribution Cable Harness to
Figure 4. Side view of receptacle-plug connection insertion.
Figure 3. End view of Distribution Cable Harness detailing available pinout connections.
Page 5
GEH-6255 Installation Instructions
Figure 5. Side view of receptacle-plug connection removal.
ADDITIONAL INFORMATION
Refer to these other user’s manuals for more details·:
®
GEH-5934 MicroVersaTrip
PM Trip Units in Spectra
Plus and MicroVersaTrip®
®
RMS Molded-
Case Circuit Breakers
®
GEH-700 Spectra
G Breaker w/
microEntelliGuard™ Trip Unit
®
GEH-701 Spectra
G Breaker w/
microEntelliGuard™ Trip Unit GEH-702 microEntelliGuard™ Trip Unit Users Manual DEH-41318 Universal Rating Plug GEH-6250 Voltage Module GEH-6251 Power Supply Plate GEH-6252 Voltage Conditioner Plate GEH-6253 Power Supply Assembly GEH-6254 Voltage Conditioner Assembly GEH-703 MET Battery Pack Adapter GEH-704 MET Advanced Distribution Cable
Junction Box DEH-006 Distribution Cable Junction Box GEH-705 MET Distribution Cable Extension (20-pin) GEH-6256 Distribution Cable Extension (12-pin) GEH-706 MET Distribution Cable Terminal Blocks
(11 point & 22 point) GEH-6257 Distribution Cable Terminal Block (11 point) GEH-6491 POWER LEADER™ Modbus Concentrator GEH-6502 POWER LEADER™ PMCS 5.0 Network
Architecture Guide GEH-707 MET Sealable Cover kits DEH-4568 GTU digital test kit (GTUTK20) GEH-5551 Shunt Trip and UVR instructions GEH-5593 Aux switch and bell alarm GEK-64467 TIM-1 Zone Selective Interlock Module
Page 6
GEH-6255 Installation Instructions
Notes
Page 7
GEH-6255 Installation Instructions
Notes
Page 8
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.
GE Energy
41 Woodford Avenue, Plainville, CT 06062 www.geelectrical.com © 2011 General Electric Company