modifications reserved 2User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 3
Contents
1 IMPORTANT SAFETY INSTRUCTIONS ....................................................................................................... 4
1.1 Save these instructions.....................................................................................................................................................................4
1.2 Safety warnings and symbols .......................................................................................................................................................4
1.4 Transport / storage.............................................................................................................................................................................5
1.5 Maintenance and servicing.............................................................................................................................................................6
3.3.9 Standard installation procedure ................................................................................................................................................18
3.4 Parallel Operation (only for 8/10 kVA) .....................................................................................................................................20
3.4.1 Installation of a parallel system.................................................................................................................................................20
3.4.2 Installing the parallel connection ..............................................................................................................................................21
4.2.1 Start-up of a 5/6 kVA .......................................................................................................................................................................23
4.2.2 Start-up of a 8/10 kVA.....................................................................................................................................................................24
4.2.3 Start-up of a parallel system (8/10 kVA models)................................................................................................................24
4.3 Use: normal operation........................................................................................................................................ 25
4.3.1 Normal operation conditions.......................................................................................................................................................25
4.4 Use: status and alarm indications................................................................................................................. 27
4.4.1 On bypass .............................................................................................................................................................................................28
4.4.2 On battery.............................................................................................................................................................................................28
4.4.3 Battery low (end of runtime).........................................................................................................................................................28
4.4.4 Bypass out of limits...........................................................................................................................................................................28
4.4.10 Remote Emergency Power Off (REPO) .....................................................................................................................................30
4.4.11 No load shutdown.............................................................................................................................................................................30
4.4.12 Auto Restart .........................................................................................................................................................................................30
5 COMMUNICATION .................................................................................................................................... 32
5.1 DB9 Communication port .............................................................................................................................................................32
6.1 Optional Power Distribution UNIT .............................................................................................................................................33
6.1.1 5/6 kVA PDUs....................................................................................................................................................................................... 34
6.1.2 8/10 kVA PDUs....................................................................................................................................................................................34
7.3 Recycling the UPS at the end of service life.........................................................................................................................35
7.4.1 Internal battery replacement (for 5/6 kVA models)........................................................................................................... 37
7.4.2 Internal battery replacement (for 8/10 kVA models)........................................................................................................38
7.5 Power unit maintenance ............................................................................................................................................................... 39
7.5.1 Power unit replacement (for 5/6 kVA models).....................................................................................................................39
7.5.2 Power unit replacement (for 8/10 kVA models).................................................................................................................. 39
modifications reserved3 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 4
1 IMPORTANT SAFETY INSTRUCTIONS
1.1 SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the UPS.
It also gives all necessary information about the correct use of the UPS. Before attempting to install and start up the
UPS, carefully read this manual. Keep this manual next to the unit for future references.
Full understanding of and compliance with the safety instructions and warnings contained in this
manual are the
ONLY CONDITIONS
to avoid any dangerous situation during installation, operation and maintenance work, and to
preserve the maximum reliability of the UPS system.
GE refuses any responsibility in case of non-observance, unauthorized alterations or improper use of
the delivered UPS.
While every care has been taken to ensure the completeness and accuracy of this manual, GE accepts
no responsibility or liability for any loss or damage resulting from the use of the information contained
in this document.
This document shall not be copied nor reproduced without the permission of GE.
Due to technical improvements, some of the information contained in this manual may be changed
without notice.
The instructions in this manual are for UPS models GT5000 RT, GT6000 RT, GT8000 RT and GT10000 RT. Check your
model number by looking at the top cover of your UPS. Any difference in instructions is clearly indicated in the text
(for instance ‘GT10000 RT’).
1.2 SAFETY WARNINGS AND SYMBOLS
Safety warnings
The text of this manual contains warnings to avoid risk to persons and to avoid damages to the UPS system and the
supplied critical loads. Do not proceed beyond these warnings if you do not fully understand and/or are not able to
meet the mentioned conditions. The non-observance of the warnings reminding hazardous situations could result in
human injury and equipment damage.
Please pay attention to the meaning of the following warnings and symbols.
WARNING!
Refers to procedures or operations which, when not correctly performed, could
cause personal injury or serious damage to the system.
NOTE
Warns the user about important operations or procedures described in this
manual.
Safety Symbols
CAUTION
The product may be in danger: when procedures or operations are not correctly
performed, damage to the product may be the result.
DANGER OF ELECTRICALLY LIVE PARTS
Related to all situations with potentially hazardous voltage.
modifications reserved 4User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 5
1.3 GENERAL
DANGER! RISK OF ELECTRIC SHOCK.
The UPS has an internal battery supply with a nominal voltage of 144Vdc / 288Vdc.
Some of the parts of the UPS are necessarily under a hazardous voltage. Do not
open the unit; there are no user serviceable parts inside.
The appliance outlets and output terminals may be electrically live, even when the
UPS is disconnected from the mains.
CAUTION
There may be damage to the equipment if procedures and practices are not strictly
observed and followed.
1.4 TRANSPORT / STORAGE
NOTE
Check for sufficient floor and elevator loading capacity. Move the UPS and the
battery pack in its original package to the final destination room. Do not stack
other package on top.
WARNING!
Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS from
the pallet! Never try to lift the unit by yourself!
• No liability can be accepted for any transport damage when the equipment is shipped in non-original
packaging.
• Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature must be
within -20 +45 °C (-4°F and 113°F). If the unit is stored for a period exceeding 3 months, optimal battery
lifetime is obtained if the storage temperature does not exceed 30°C (86°F).
• If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Connect the unit to a wall outlet and recharge the batteries for 24 hours:
- if the storage temperature is within -20 and +30°C (-4°F and 86°F): every 6 months,
- if the storage temperature is within -20 and +45°C (-4°F and 113°F): every 3 month.
CAUTION
In case of storage, pay attention to:
modifications reserved 5User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 6
1.5 MAINTENANCE AND SERVICING
• A battery can present a risk of electrical shock and high short circuit current
• Never dispose of batteries in a fire: they may explode
• Do not open or mutilate batteries: their contents may be extremely toxic. If exposed to electrolyte,
wash immediately with plenty of water
• The batteries must be disconnected during maintenance or service work.
• When replacing the batteries, use only the same type and size battery.
• The following precautions should be observed when working on batteries:
- Remove watches, rings or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of
such shock will be reduced if such grounds are removed during installation and maintenance.
• Avoid charging in a sealed container.
NOTE
Do not attempt to service the UPS unless you have had proper training. Refer all
maintenance and servicing, except replacement of the batteries and plug-in cards,
to properly qualified, skilled and competent service personnel.
Qualified, skilled personnel are persons who (because of their training, experience, and position as well as
their knowledge of appropriate standards, regulations, health and safety requirements and working
conditions) are authorized to be responsible for the safety of the equipment, at all times whilst carrying out
their normal duties and are therefore aware of, and can report, possible hazards (observe IEC 60364 and
national wiring regulations and accident prevention rules).
1.6 FCC COMPLIANCE STATEMENT
Note: This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at their own expense.
Modifications not expressly approved by the manufacturer could void the user’s authority to operate the
equipment under FCC rules.
modifications reserved 6User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 7
2 INTRODUCTION
2.1 INTRODUCTION
The GE Digital Energy™GT Series UPS, atruly on-lineuninterruptible power supply, protects your
equipment from all forms of power interference, including complete power failures.
2.2 INTENDED USE
Uninterruptible Power Supplies (UPS) are designed to protect sensitive electronic equipment such as
computers and telecommunications equipment from all forms of power interference.
The technical data as well as information concerning connecting requirements can be found on the rating
label and in this document and shall be strictly observed.
2.3 WARRANTY
GE Digital Energy™ warrants that the standard products will be free of defects in materials and
workmanship for a period of twenty-four (24) months after seller’s shipment date.
CAUTION!
DO NOT plug household appliances such as electric heaters, toasters or vacuum
cleaners into the UPS. The UPS output is intended to be used only for electronic
loads such as computers and telecommunications equipment.
NOTE
This warranty does not cover failures of the product that result from incorrect
installation, misuse, alterations by persons other than authorized agents,
or abnormal operating conditions.
2.4 DIAGRAM
EMI: Input filter with surge
suppression, radio frequency
and electromagnetic
interference filter.
BF: Back-feed protection.
PFC: AC-DC converter with power
factor correction.
BC: Battery charger.
DCC: DC-DC converter.
INV: Inverter.
BYP: Bypass switch.
MBY: Manual bypass switch.
fig. 2.4
modifications reserved7 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 8
3 INSTALLATION
3.1 PACKAGE CONTENTS
5/6 kVA model shipping box contains:
• 2 front bezels
• 2 top bezels
• 6 support stands parts
• 2 rack mount handles
• 1 screw set – 1 display sticker
• 1 RS232 cable, 2 ferrite beads
• 1 CD ROM (Software tool)
• This Operating Manual
Inspect the UPS for damage after unpacking. If any damage is present please immediately notify the carrier and
place of purchase.
NOTE
The internal battery packs are shipped separately, see section 3.3.3 and 3.3.4
for the installation details
WARNING! In case of recognizable damage:
DO NOT connect any voltage to the unit
DO NOT put the unit into operation
3.2 INSTALLATION RULES
IMPORTANT
8/10 kVA model shipping box contains:
• 3 front bezels
• 3 top bezels
• 6 support stands parts
• 2 internal battery brackets
• 2 rack mount handles
• 1 screw set – 1 display sticker
• 1 paralleling cable
• 1 RS232 cable, 2 ferrite beads
• 1 CD ROM (Software tool)
• This Operating Manual
Before making any connection and switching on the GT Series UPS,
please check the following conditions:
• All electrical connections are to be realized by qualified skilled personnel only.
• To avoid potential health risks, electrical components should not be mechanically damaged or destroyed. Do not
touch electronic components. They may be electrostatic sensitive and are for that reason easily damaged due to
improper handling.
• Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight. It is important that
the unit has adequate ventilation. Maintain air movement around and through the unit. Do not block the air vents.
• The ambient temperature should not exceed 40°C (104°F). Optimal battery lifetime is obtained if the ambient
temperature does not exceed 30°C (86°F).
• Avoid spilling liquids or dropping any foreign object into the UPS.
• The UPS should only be powered from a two phase, four wires AC source equipped with neutral and earth
connection. Your mains supply is 100 - 127 Volts (Line-N) and 60 Hz (if the mains frequency is 50Hz, the output
frequency of the UPS can be changed, see note in section 4.4.4).
• The total power demand of the connected equipment does not exceed the rated output power of the GT Series
UPS (chapter 9 contains the ratings).
• To reduce risk of fire a disconnection switch should be installed for input and output circuit, connect only to
over-current protection branch circuit rated in accordance with the National Electric Code, ANSI/NFPA 70, see
following table:
To reduce risk of fire, connect the UPS only to a circuit provided with fuse values
according to the above.
modifications reserved 8User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 9
3.3 INSTALLATION PROCEDURE
The UPS can be used in a stand alone tower format using the two supporting stands (section 3.3.1), or
can be mounted in a 19 inch rack using the mounting brackets (section 3.3.2). Proceed with the
corresponding section, and then connect internal batteries (section 3.3.3 fro 5/6 kVA models and section
3.3.4 for 8/10 kVA models). All required items are included in the delivery, except rails – available as rail
The UPS output sockets are live as soon as the UPS is connected to the main
power supply, even if the UPS has not been switched on via the front panel.
1. On 5/6 kVA models align terminals on
the backside of the PDU with UPS ones
and slide PDU in the UPS (fig. 3.3.1.a).
2. Assemble the plastic support stand
and place them in the desired position
(2, fig. 3.3.1.b / 3.3.1.c).
3. Place the cabinet upright in to the
plastic support stand and mount
top covers (3, fig. 3.3.1.b / 3.3.1.c).
4. Attach the display sticker (4, fig. 3.3.1.b /
3.3.1.c).
5/6 kVA
fig. 3.3.1.a
5/6 kVA
The GT Series UPS is now ready for further
connection: proceed with internal battery
connection.
modifications reserved 9User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
fig. 3.3.1.b
8/10 kVA
fig. 3.3.1.c
Page 10
3.3.2 Rack mount installation – preparations (all models)
1. On 5/6 kVA models align
terminals on the backside of the
PDU with UPS ones and slide PDU
in the UPS (fig. 3.3.1.a).
2. Install the rack mount handles
that came with the unit using the
provided screws (2, fig.3.3.2.b /
3.3.2.c).
3. Install the UPS into a 19’ rack.
The UPS cabinet must be
supported by an (optional) rack
mount kit, do not mount it by
using the mounting brackets
only.
5/6 kVA
fig. 3.3.2.a
5/6 kVA
fig. 3.3.2.b
8/10 kVA
fig. 3.3.2.c
NOTE
Please consider the weight of the UPS (see section 9) prior to installation to ensure
the rack and floor are capable of supporting the weight. For rack installation we
recommend that the UPS is placed in the lower section of the rack. Fit the unit and
the battery into the rack cabinet with the help of a second person.
fig. 3.3.2.d
The GT SeriesUPS is now ready for further connections. Please proceed internal battery connection.
modifications reserved 10User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 11
3.3.3 Connecting internal battery pack (for 5/6 kVA models)
The internal battery pack is shipped separately from the UPS cabinet. It has to be mounted inside the
unit after UPS installation. Please proceed with the following steps:
1. Unpack the battery pack from
its carton box.
2. Place the battery pack in front
of the battery compartment,
aligning the rear connector to
the front panel (2, fig. 3.3.3.a).
3. Slide the battery pack into the
battery compartment until the
rear connector is plugged with
the UPS internal DC socket.
4. Fix the battery cover by
tightening screws
(4, fig. 3.3.3.b).
5. Mount the front panels by
pushing the plastic part into
the appropriate holes
(5, fig. 3.3.3.c).
6. Proceed with the UPS
preparation.
fig. 3.3.3.a
5/6 kVA
5/6 kVA
fig. 3.3.3.b
5/6 kVA
fig. 3.3.3.c
modifications reserved11 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 12
3.3.4 Connecting internal batteries (for 8/10 kVA models only)
The internal battery packs are shipped separately from the UPS cabinet. They have to be mounted
inside the unit after the UPS installation. Please proceed with the following steps:
1. Unpack the 2 battery packs
from their carton box.
2. Place the battery packs side by
side in the battery
compartment (2, fig. 3.3.4.a).
3. Fix the 2 battery brackets with
the screw set to hold battery
packs into the cabinet
(3, fig.3.3.4.a).
4. Connect the UPS DC
connectors of each battery
pack (4, fig.3.3.4.a).
5. Fix the battery grille in front of
the battery compartment with
3 screws (5, fig.3.3.4.b).
6. Mount the front panels by
pushing the plastic part into
the appropriate position
(6, fig. 3.3.4.c).
7. Proceed with the UPS
preparation.
fig. 3.3.4.a
fig. 3.3.4.b
8/10 kVA
8/10 kVA
8/10 kVA
fig. 3.3.4.c
modifications reserved12 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 13
3.3.5 Connecting additional external batteries (5/6 kVA models)
The additional external battery pack connects to the UPS in the same way whether the UPS is being
used in tower or rack mount format. When used in tower format, the UPS and additional battery packs
can be mounted together in one set of mounting support stands (fig.3.3.5.a). Additional support stands
are shipped with battery cabinet.
Connect the cable provided with the battery between UPS and battery pack – plug it into the UPS
battery socket and the nearest battery connection socket on the battery pack (fig.3.3.5.b). At first start
up the value of the total battery capacity has to be set with the UPS Monitoring software.
5/6 kVA5/6 kVA
fig. 3.3.5.afig. 3.3.5.b
NOTE
If further battery packs are used, they connect via the previous battery pack. Thus,
the cable provided is attached via the nearest socket connection on the existing
battery cabinet (fig. 3.3.5.c).
5/6 kVA
fig. 3.3.5.c
NOTE
When the UPS is connected to the mains, and the battery pack is connected to
the UPS, the batteries start charging. For best results, allow the UPS to recharge
the batteries during a period of approx. 8 hours. It is acceptable to use the UPS
without first charging the battery, but the runtime may be reduced.
modifications reserved 13User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 14
3.3.6 Connecting additional external batteries (8/10 kVA models)
In case of additional external battery packs, batteries are shipped separately from the battery cabinet.
They have to be mounted inside the cabinet after battery installation. Please proceed with the following
steps:
1. Unpack the 2 battery packs from
their carton box.
2. Place the battery packs side by
side in the battery compartment
(2, fig. 3.3.6.a).
3. Fix the 2 battery brackets with
the screw set to hold battery
packs into the cabinet
(3, fig. 3.3.6.a)
4. Connect the DC connectors of
each battery pack (4, fig. 3.3.6.a).
5. Fix the battery grille in front of
the battery compartment with 3
screws (5, fig. 3.3.6.b).
6. Mount the 2 battery front covers.
(6, fig. 3.3.6.b).
8/10 kVA
fig. 3.3.6.a
8/10 kVA
fig. 3.3.6.b
The additional external battery pack connects to the UPS in the same way whether the UPS is being
used in tower or rack mount format. When used in tower format, the UPS and additional battery packs
can be mounted together in one set of mounting support stands (fig.3.3.6.c).
Connect the cables provided with the battery between UPS and battery pack – plug them between UPS
sockets and nearest sockets on the battery pack (fig.3.3.6.d). The connectors and sockets are keyed and
can be plugged only in correct position. At first start up the value of the total battery capacity has to be
set with the UPS Monitoring software.
8/10 kVA
fig. 3.3.6.cfig. 3.3.6.d
8/10 kVA
modifications reserved 14User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 15
NOTE
If further battery packs are used, they connect via the previous battery pack. Thus,
the cable provided is attached via the nearest socket connection on the existing
battery cabinet (fig. 3.3.6.e).
8/10 kVA
fig. 3.3.6.e
NOTE
When the UPS is connected to the mains, and the battery pack is connected to the
UPS, the batteries start charging. For best results, allow the UPS to recharge the
batteries during a period of approx. 8 hours. It is acceptable to use the UPS without
first charging the battery, but the runtime may be reduced.
modifications reserved 15User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 16
3.3.7 Connecting interface devices
The UPS is equipped with two interface ports: a DB9 communication port and an SNMP card slot
(see section 3.3.8). Prepare the included serial communication cable (for DB9 communication port
connection) or the network cable (for SNMP communication connection) as follows:
1. Choose from the 2 provided ferrite beads the smaller
one for serial communication and the bigger one for
SNMP communication.
2. Place the cable part that is close to the UPS connector
inside the ferrite bead. For SNMP communication twist it
once around the ferrite and place the second winding
also inside the ferrite bead (fig 3.3.7.a / 3.3.7.b).
3. Close the ferrite bead such that the cable remains
inside it (fig. 3.3.7.a / 3.3.7.b).
You can now connect the DB9 port to a computer by connecting the previously prepared serial cable
(fig. 3.3.7.c / 3.3.7.d). Additional signals can be read from the serial connector. See section 5.1 for more
information.
Open the SNMP slot by removing the two screws and the cover, then pull in the easy installation SNMP
Card and connect previously prepared network cable (fig. 3.3.7.e / 3.3.7.f). See section 5.2 for more
information.
fig. 3.3.7.a
fig. 3.3.7.b
5/6 kVA
fig. 3.3.7.d fig. 3.3.7.e
8/10 kVA
fig. 3.3.7.f fig. 3.3.7.g
modifications reserved 16User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
5/6 kVA
8/10 kVA
Page 17
3.3.8 Rear panel
Rear Panel 5/6 kVA:
1. Input / output terminals
(see section 3.3.9)
2. External battery connector
3. Output breaker:
2pole, 30A/250Vac
4. Fans
5. SNMP card slot
6. DB9 communication port
Unit with standard Power Distribution Unit:
5/6 kVA
7. Additional ground connector
8. REPO contacts
(see section 4.4.10)
9. Input breaker: 2pole, 30A/250Vac
10. Maintenance Bypass
(Optional Power Distribution Unit)
Rear Panel 8/10 kVA:
1. Input/Output terminals
(see section 3.3.9)
2. Input breaker: 2pole, 60A/250Vac
fig. 3.3.8.a
Unit with Optional PDU (see section 6.6.1)
5/6 kVA
fig. 3.3.8.b
8/10 kVA
3. Maintenance Bypass
(see section 4.3.3)
4. Output breaker: 2pole,
60A/250Vac
5. External battery connectors
6. SNMP card slot
7. DB9 Communication port
8. Fan Module
9. REPO Contacts
(see section 4.4.10)
10. Parallel ports (see section 3.4.2)
fig. 3.3.8.c
modifications reserved 17User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 18
3.3.9 Standard installation procedure
NOTE
Ensure that the UPS is isolated prior to installation; no live input source may be
connected to the UPS during the installation procedure. Open all the input/output
switches/breakers on the power distribution and ensure no one is able to close
them during this installation step.
1. In case of Optional Distribution Unit
please follow instruction at section 6.1,
otherwise proceed with step 2.
2. Remove the terminal cover (fig. 3.3.9.a /
3.3.9.b).
3. Punch out the appropriate holes in the
terminal cover. Secure the input/output
cables using glands, according to
fig. 3.3.9.c.
4. Input. Connect the mains supply wires to
the terminals “L1-L2” (Line) and “N”
(Neutral) and the ground wire to terminal
“
”. Ground connection is essential!
(fig. 3.3.9.d).
5/6 kVA
fig. 3.3.9.a
8/10 kVA
5. Output. Connect the load wires to the
terminals “L1-L2” (Line) and “N” (Neutral)
and the ground wire to terminal “
Ground connection is essential!
(fig. 3.3.9.d).
NOTE
Localize on figure 3.3.9.d proper terminals based on the desired input/output voltage.
For 8/10 kVA models use 6 AWG 75°C (167°F) copper wires, 22 lb-in fixation torque force.
For 5/6 kVA models use 10 AWG 75°C (167°F) copper wires, 20 lb-in fixation torque force.
”.
fig. 3.3.9.b
fig. 3.3.9.c
5/6 kVA8/10 kVA
fig. 3.3.9.d fig. 3.3.9.e
modifications reserved 18User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 19
6. Re-install the terminal
cover (fig. 3.3.9.e).
7. In case of external
batteries, ensure the
battery cable is connected
between the battery
cabinet and the power unit.
(see 3.3.5 / 3.3.6).
8. Connect the utility power to
the UPS.
9. For a quick start proceed
with section 4.2.1.
If parallel-operating units will be
installed, please proceed with
section 3.4. Otherwise, proceed
with section 4.
5/6 kVA
fig. 3.3.9.f
8/10 kVA
NOTE
The UPS output sockets are live as soon as the UPS is connected to the mains,
even if the UPS has not been switched on via the front panel.
For 5/6 kVA models an additional
ground connection is required (main
ground can be removed with the PDU).
Connect the UPS case to the nearest
available ground connection with an
8 AWG (10 mm
(see fig. 3.3.9.h).
2
) copper wire
fig. 3.3.9.g
5/6 kVA
fig. 3.3.9.h
modifications reserved19 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 20
3.4 PARALLEL OPERATION (ONLY FOR 8/10 KVA)
The paralleling cable delivered with each UPS allows you to connect up to 3 UPS together in a parallel
system.
3.4.1 Installation of a parallel system
1. All inputs of the UPS must be supplied from the same phase. Be sure that L1 / L2 / N correspond on all
the units of the parallel system. All inputs have to be protected individually by fuses. The values of
these fuses should correspond to the values mentioned in section 3.2.
2. All outputs must be connected together, supplying the load. It is advised to install switches (S 1, 2, 3
fig 3.4.1) in the output wiring, in order to be able to isolate a unit from the remaining system for
service and maintenance purposes.
3. Use insulated copper input and output wiring, rated 90°C (194°F) wire size based on the ampere
capacities given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-2008.
4. The length of all input cables from the input junction (Li, fig. 3.4.1) to the UPS inputs should be equal.
The same applies to the cables from the outputs to the output junction (Lo, fig. 3.4.1). The minimum
length of the input as well as the output cables is 3 meters.
5. The overall system load may not exceed 100% load of a single UPS in the configuration without the
addition of an external maintenance bypass.
NOTE
The units connected in parallel must be the same power rating (i.e. 8 kVA-8 kVA not
8 kVA-10 kVA) and must have the same output voltage setting (i.e. 120V-120V not 120V127V). Before starting up a parallel system be sure that the output terminals on all UPS
are connected in the same way (see section 3.3.9, fig. 3.3.9.d).
fig. 3.4.1
modifications reserved20 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 21
3.4.2 Installing the parallel connection
NOTE
Ensure that the UPS is isolated prior to installation; no live input source may be
connected to the UPS during the installation procedure. Open all the input/output
switches/breakers on the power distribution and ensure no one is able to close
them during this installation step.
1. Localize the parallel port on the rear side
of the unit (fig. 3.4.2.a)
2. Connect the DB 15 parallel cable provided
with the UPS to the parallel port (fig.
3.4.2.b) and tighten it.
3. One cable connects two UPS in parallel.
To connect a third UPS into the parallel
system, repeat the process as above
(fig. 3.4.2.d)
4. For a quick start of the system proceed
with section 4.2.3
5. Each UPS needs a different configuration
of the DIPswitch as identification of unit
in the parallel system (fig. 3.4.2.c).
8/10 kVA
fig. 3.4.2.a
8/10 kVA
fig. 3.4.2.b
8/10 kVA
fig. 3.4.2.c
8/10 kVA
fig. 3.4.2.d
modifications reserved 21User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 22
4 OPERATION
4.1 OPERATING PANEL
fig. 4.1: operating panel
switch / LED main function
‘UPS off’ switchswitches the UPS from normal operation to bypass and from bypass or
1
battery to standby.
‘UPS on’ switch switches on the UPS, starts quick battery test (see section 4.5), mute the
2
buzzer.
LED ‘mains available’ (green) indicates availability of power mains.
3
LED ‘battery’ (yellow)on in case of battery operation: the mains power fails, and the internal
4
batteries supply the required power until either they are depleted or mains
power returns.
LED ‘operation’ (green) on when the output is supplied by the UPS (inverter).
5
LED ‘bypass’ (yellow)on when the UPS operates in bypass mode: the incoming mains power is
6
channeled directly to the load. Blinks if the input voltage is out of bypass
tolerance (see section 4.4.4 for more details).
LED ‘alarm’ (red) on in case of alarm.
7
8
LED bar ‘runtime capacity’
9
LED bars ‘load’
the remaining available battery runtime for the actual load, in % of the
maximum runtime with the actual load. When the alarm LED is on, this bar
may show a combination of LEDs, describing the Alarm cause (see 4.4).
1º LED: 0-20% green
2º LED: 21-40% green
3º LED: 41-60% green
4º LED: 61-80% green
5º LED: 81-100% green
indicates to what extent the output capacity of the UPS is used by the
actual load for each output line (L1 and L2). If e.g. the 25%, 50% and 75%
LED are on for Line 1 and the 25% and 50% LED are on for Line 2, the load
exceeds 50% of the maximum load for Line 1 and 25% for Line 2. If all 5
LEDs are on the unit operates in overload. As this is an abnormal situation
the alarm LED will be on as well.
1º LED: 0-25% green
2º LED: 26-50% green
3º LED: 51-75% green
4º LED: 76-100% green
5º LED: >100% yellow
modifications reserved 22User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 23
4.2 START-UP
4.2.1 Start-up of a 5/6 kVA
1. Ensure that all breakers on the unit are
off.
2. In case external batteries are used
(see section 3.3.5 for battery
connection), switch on the battery
cabinet circuit breaker (fig. 4.2.1.a).
3. In case optional power distribution unit
is used, ensure that the manual bypass
switch is turned to “UPS” position
(fig. 4.2.1.b).
4. Close all switches and breakers
upstream to the UPS.
5. Switch the input circuit breaker placed
on the rear side of the unit to position
“On” (fig. 4.2.1.d). The “Mains available”
LED on the operating panel
(see section 4.1) is lighted on.
6. Wait 45 seconds to allow the output
voltage to stabilize.
7. Press keypad “UPS on” for 1 second.
Within few seconds “operation” LED will
be illuminated and “bypass” LED will be
extinguished.
8. Close the Output circuit breaker placed
on the rear side of the unit
(see fig. 4.2.1.c).
9. The unit is now in operation; equipment
connected to the UPS can now be
switched on.
Load % will be shown on “load” LED bar.
5/6 kVA
fig. 4.2.1.a
5/6 kVA PDU
fig. 4.2.1.b
5/6 kVA
fig. 4.2.1.c
5/6 kVA
fig. 4.2.1.d
modifications reserved 23User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 24
4.2.2 Start-up of a 8/10 kVA
1. Ensure that all breakers on the unit are
off.
2. In case of external batteries are used
(see section 3.3.6 for battery
connection), switch on the battery
cabinet circuit breaker (fig.4.2.2.a).
3. Ensure that Bypass circuit breaker
(see section 3.3.7) is on “UPS” position
(fig.4.2.2.b) or that protection bar is still
mounted.
4. Close all switches and breakers
upstream to the UPS.
5. Switch the input circuit breaker placed
on the rear side of the unit to position
“On” (fig.4.2.1.d). The “Mains available”
LED on the operating panel
(see section 4.1) is lighted on.
6. Wait 45 seconds to allow the output
voltage to stabilize.
7. Press keypad “UPS on” for 1 second.
Within few seconds “operation” LED will
be illuminated and “bypass” LED will be
extinguished.
8. Close the Output circuit breaker placed
on the rear side of the unit (fig. 4.2.2.c).
9. The unit is now in operation; equipment
connected to the UPS can now be
switched on.
Load % will be shown on “load” LED bar.
fig. 4.2.2.a
fig. 4.2.2.b
fig. 4.2.2.c
fig. 4.2.2.d
8/10 kVA
8/10 kVA
8/10 kVA
8/10 kVA
4.2.3 Start-up of a parallel system (8/10 kVA models)
1. Ensure that all breakers on all the units of the system are off.
2. In case external batteries are used, switch on each circuit breaker (fig. 4.2.1.a / 4.2.2.a).
3. Ensure that all manual bypass switches are turned to “UPS” position (fig. 4.2.1.b / 4.2.2.b).
4. Close all switches and breakers upstream to all UPS of the system.
5. Switch to position “on” the output circuit breaker on all UPS in sequence (fig. 4.2.1.c / 4.2.2.c).
6. Switch to position “On” the input circuit breaker on all UPS in sequence (fig. 4.2.1.d / 4.2.2.d).
7. Wait 45 seconds to allow the output voltage to stabilize.
8. Press keypad “I” on each UPS for 1 second. Within few seconds LED ‘operation’ will be illuminated
and LED ‘bypass’ will be extinguished.
9. The parallel system is now in operation and the connected equipment can now be switched on.
The load will be shared between the UPS as shown on the LED bar ‘load’.
modifications reserved 24User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 25
4.3 USE: NORMAL OPERATION
4.3.1 Normal operation conditions
1. The mains supply is present and within the tolerance (see chapter 9), and
2. The UPS is on, and
3. The load does not exceed the capacity of the UPS, and
4. The operating temperature is below alarm level.
4.3.2 Switching off
1. Be sure that the load has been shut
down in a controlled way.
2. Press keypad “O” (fig. 4.3.2.a) for 1
second to switch the unit to bypass.
3. Press one more time the keypad “O”
for 1 second to switch off the unit
(fig. 4.3.2.a).
If electrical isolation is required (e.g. for maintenance purposes) proceed with steps 4-7 below:
4. Turn the Output circuit breaker to position
“off” (fig. 4.3.2.b / 4.3.2.c).
5. Turn the Input circuit breaker to position “off”
(fig. 4.3.2.d / 4.3.2.e).
6. In case of external batteries are connected,
switch off the battery cabinet circuit breaker
and disconnect battery cabling at the rear
side of the UPS.
7. Open all switches and breakers upstream to
the UPS.
8. Remove internal and external battery
connections (see section 7.4.1 / 7.4.2) and
disconnect additional battery packs.
All LED should be out on the front panel; the UPS is
shut down.
fig. 4.3.2.a
fig. 4.3.2.b
fig. 4.3.2.c
5/6 kVA
8/10 kVA
5/6 kVA
fig. 4.3.2.d
modifications reserved 25User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
fig. 4.3.2.e
8/10 kVA
Page 26
4.3.3 Maintenance Bypass
It’s possible to bypass the unit for maintenance purpose (with Optional Distribution Unit for 5/6 kVA
models, standard for 8/10 kVA models, section 3.3.8). In case of necessity, please proceed with the
following steps:
1. Switch the unit on bypass, for 5/6 kVA
models by pressing keypad “UPS Off” on
the front panel (see section 4.1) for 1
second and for 8/10 kVA models by
removing the bypass protection cover
(fig. 4.3.3.b).
2. Switch the Maintenance Bypass Switch to
“Bypass” position (fig. 4.3.3 a / 4.3.3.b). For
8/10 kVA models remove the bypass lock
plate before switching to “Bypass”.
3. Switch the unit off, by pressing keypad
“UPS Off” on the front panel
(see section 4.1) for 1 second.
4. Open the Output circuit breaker
(see section 3.3.8).
5. Open the Input circuit breaker
(see section 3.3.8).
fig. 4.3.3.a
5/6 kVA
8/10 kVA
6. The unit is now operating in “External
Bypass mode” and maintenance can be
done.
Once the maintenance is executed, recover normal conditions with the following steps:
1. Close the Input circuit breaker
(see section 4.2.1 / 4.2.2).
2. Wait 45 seconds to allow the output
voltage to stabilize.
3. Press keypad “UPS on” for 1 second
(see section 4.1). Within few seconds
“operation” LED will be illuminated and
“bypass” LED will be extinguished.
4. Switch the unit to bypass, by pressing
keypad “UPS Off” on the front panel
(see section 4.1) for 1 second.
NOTE
After the UPS is shutdown or in “External Bypass” condition, the residual DC voltage in
the unit will be eliminated within 5 minutes.
fig. 4.3.3.b
fig. 4.3.3.c
5/6 kVA
8/10 kVA
5. Close the Output circuit breaker
(see section 4.2.1 / 4.2.2).
6. Switch the Maintenance Bypass Switch to
“UPS” position (fig. 4.3.3.c / 4.3.3.d). For
8/10 kVA models screw the bypass lock
plate (fig. 4.3.3.d).
7. Press keypad “UPS On” (see section 4.1) for
1 second.
Now the UPS protects the load again.
modifications reserved 26User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
!! high priority alarms situations in which the actual output voltage of the UPS is no longer guaranteed;
immediate action should be taken
Situation
o Stand-by (4.4.9)
Indicators on front panel (fig 4.1)
1 - 5
o Normal operation (4.3.1)
1 - 5 0 - 4
! Overload warning (4.4.5)
!! Battery not connected (4.5)
- - - -
1 - 5
!! Replace battery (4.4.6)
1& 3 0 - 4
! Bypass out of limits (4.4.4)
- - - -
1 - 5 0 - 4
o On bypass (4.4.1)
1 - 5 0 - 4
o On battery (4.4.2)
1 - 5 0 - 4
!! Battery low (4.4.3)
!! Fault on bypass
1
- - - -
- - - -
!! Fault stand-by
- - - -
Operating modes and corresponding indications, see 4.3.1 - 4.3.2 and 4.4.1 – 4.4.9.
- - - - : intermittent
⎯⎯: continuous
0 – 5 : number of LEDs that can be on, depending on runtime capacity / load bar
mute buzzer : press push button ‘I’ briefly
5
0 - 4
0 - 4
0 - 5
- - - -
1 / 0.5 sec
- - - -
1 / 60 sec
- - - -
1/120 sec
- - - -
1 / 5 sec
- - - -
modifications reserved 27User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 28
4.4.1 On bypass
The UPS is equipped with an automatic bypass switch. This switch automatically transfers the load to the
main power supply if the UPS is unable to deliver the demanded output power due to overload or over
temperature. If all 5 load LED are illuminated, bypass operation is caused by an overload. If only first
runtime LED is illuminated, bypass operation is caused by over temperature (see 4.4.8 tab .1).
The UPS will switch back to normal operation when the overload has been removed. When temperature
drops below alarm level unit can be switched back to normal operation. If a power failure occurs during
bypass operation, the UPS will switch to battery if possible, otherwise output power is lost.
4.4.2 On battery
In normal operation conditions, if a main power supply failure occurs, the UPS uses the energy stored in
the batteries to supply the load. The runtime capacity LED bar will show the remaining time (see 4.1). For
further information about runtime refer to chapter 9, Battery runtime. The UPS will shutdown:
• After the batteries have been discharged (automatic restart if enabled), or
• If keypad ‘UPS off’ is pressed (restart via front panel required), or
• If a ‘UPS shutdown’ command is given by the computer (via UPS monitoring software). Restart
depends on the setting of “auto-restart” function (see 4.4.12).
4.4.3 Battery low (end of runtime)
If during battery operation the buzzer starts beeping every 5 seconds and the first LED of the battery
runtime bar starts blinking the batteries are nearly discharged: the remaining runtime is less than 2
minutes (default setting, adjustable via the UPS monitoring software). Controlled shutdown of any
computer equipment is absolutely necessary when this alarm is raised.
If the UPS operates at 100% load, the shutdown procedure should be completed within 2 minutes after the
‘battery low’ alarm started. If only part of the output capacity of the UPS is used this period can be longer,
with aged batteries this period can be shorter. When the batteries are fully discharged, the UPS is no
longer able to supply the connected equipment and eventually output power is lost.
4.4.4 Bypass out of limits
The mains voltage or mains frequency is outside bypass tolerance but inside UPS input tolerance (see
chapter 9). Bypass operation is inhibited: if for whatever reason the UPS is not able to deliver the required
output, output power is lost. If the input frequency is often out of tolerance – during which bypass
operation is inhibited and an alarm is generated – it may be useful to disable bypass function (via UPS
monitoring software) after which the unit operates as a UPS without automatic bypass switch.
NOTE
The unit can be used as frequency converter: the input frequency range is
40-70 Hz; the output frequency is selectable 50/60 Hz, via UPS monitoring
software. If the unit is used in this configuration, the bypass function is no
longer available.
4.4.5 Overload
The demanded power exceeds the nominal capacity of the UPS. The “overload warning” alarm occurs
when the load exceeds 150% the UPS will immediately switch to bypass, assuming that the conditions for
a transfer to bypass are fulfilled.
If an overload condition between 110-150% persists, the UPS will also switch to bypass operation. In both
conditions the “overload” alarm (see 4.4.8 tab. 1) is generated. During an overload the UPS may
automatically switch off within a few minutes (load dependent) and output power is lost:
• if a transfer to bypass is inhibited (see section 4.4.4), or
• if the bypass function has been disabled (see section 4.4.4), or
• if the UPS operates on battery (see section 4.4.2).
To avoid these problems, be absolutely certain that the power demand of the protected equipment is
within the limits of the UPS.
modifications reserved 28User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 29
4.4.6 Replace battery
Either the batteries are almost chemically worn out or the battery wiring, including the battery fuse, is
faulty. If the batteries are aged, they must be replaced as soon as possible to ensure full protection for
your equipment (see section 7.4.1 & 7.4.2). Perhaps the 'replace battery' alarm occurs after a test, which
was started immediately after installation or after a power failure. In this case the alarm may be incorrect,
as the batteries have been (partly) discharged during transport or storage or during the power failure. For
this reason we advise to execute battery test only after 5 hours on line operation with no mains failures. This allows the UPS to recharge the batteries.
4.4.7 Alarm priority
‘General alarm’ comprises a group of alarms; the buzzer behavior indicates the priority of the generated
alarm.
ON: Battery not connected (see section 4.5)
1 / 0.5 sec.: Overload (see section 4.4.5)
1 / 4 sec.: General Alarm
1 / 60 sec.: Battery test failed (see section 4.5)
1 / 120 sec.: On bypass (see section 4.4.1)
4.4.8 Fault mode
The UPS may be in “fault mode” if the following failure occurred:
Fault Situation
Indicators on Battery Charge Bar
!! Charger Over-voltage
!! Output Short Circuit
!! Negative Power
!! Overload
!! Over-temperature
= continuous- - - - = intermittent!! = high priority
LED 1LED 2LED 3LED 4LED 5Buzzer
- - - -
1 / 4 sec
- - - -
1 / 4 sec
- - - -
1 / 0.5 sec
- - - -
1 / 4 sec
In “fault mode”, the UPS is “forced” on bypass or stand-by. After having solved the cause of the fault
condition you have to press the ‘UPS off’ button for 0.5 seconds to switch the UPS to normal mode or
restart the unit.
4.4.9 Stand-by
In stand-by mode the UPS is turned off (output power is lost) and the batteries are being recharged.
To put the unit in this condition press for 1 second the ‘UPS off’ switch, the unit switches to bypass.
Press one more time ‘UPS off’ switch for 1 second. The unit is now in stand-by mode. Most changes of
UPS settings are only possible in bypass or stand-by mode.
modifications reserved 29User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 30
4.4.10 Remote Emergency Power Off (REPO)
REPO may be created using either normally open or normally closed switch. The unit is shipped with a
jumper connected between pin 3 and 4 (fig.4.4.10.a), corresponding to no REPO functionality.
In case of connection with a normally open contact, this jumper must be removed and a normally open
switch cabling has to be connected between pin 1-2 (fig. 4.4.10).
In case of connection with a normally closed contact, the jumper must be shifted between pin 1 and 2,
and the normally close switch has to be connected between pin 3 and 4 (fig. 4.4.10).
5/6 kVA8/10 kVA
fig.4.4.10
When REPO is activated the UPS will transfer to stand-by mode (see 4.4.9) and output power is lost. It’s not
possible to restart the unit while the REPO is activated, thus, depending on the used switch, the
connection must be restored by closing or opening the contact. Press “UPS off” button 2 times within 4
seconds to be able to restart the unit.
4.4.11 No load shutdown
If no load shutdown is enabled, the load is less than 5% and in case of utility failure the UPS will switch
off avoiding deep discharge of the batteries and output power is lost. “No load shutdown” is disabled as
default. It’s possible to enable it via UPS Monitoring Software.
4.4.12 Auto Restart
Default enabled “Auto restart” may be disabled via UPS monitoring software. Auto Restart acts after the
UPS has been shut down during a mains failure:
- if the function is set “enabled”, the UPS will automatically restart when the mains returns
- if the function is set “disabled”, a manual restart is required, either as explained in section 4.2.1 / 4.2.2
or via the UPS monitoring software.
modifications reserved 30User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 31
4.5 BATTERY MANAGEMENT
Maximum battery life and reliability are obtained by the following features:
• Battery connection test
At start-up the unit performs an automatic test to check that the battery cabling and fuses are
properly connected.
If the test detects a battery disconnection, the corresponding alarm will be generated (see section 4.4.7).
• Quick battery test
A quick battery test may be launched to check whether batteries are healthy. To start the test,
press ‘UPS on’ button (see section 4.1) for 0.5 seconds when the unit is in “normal operation”
conditions (see section 4.3.1).
In case of failure the corresponding alarm will be generated (see section 4.4.6 / 4.4.7)
• Deep battery test
A deep battery test will update the runtime calculation and may be started via the UPS monitoring
software. The test will start only if the battery charge level is higher than 90% and the load must be
at least 20% of the nominal rating. The runtime calculation will be updated only if the test can run
uninterrupted till complete battery discharge.
NOTE
When executing a deep battery test the available runtime in case of mains
failure may be shorter than normal. Don’t execute this test if reduced battery
runtime is not acceptable.
NOTE
It’s possible to reset the battery test, by pressing the ‘UPS off’ switch (see 4.1)
for 1 sec. The UPS will switch to bypass mode.
modifications reserved 31User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 32
5 COMMUNICATION
5.1 DB9 COMMUNICATION PORT
The RS232 port is a plug-in interface port, which enables advanced communication between the UPS
and the computer via serial cable (fig. 5.1) and UPS monitoring software. The interface port is already
operative in stand-by mode (see section 4.4.9).
To change settings of the unit, we strongly recommend to be sure that the unit is in stand-by mode.
Some settings can only be changed if the UPS operates in bypass or stand-by mode.
For more information regarding possible settings, please refer to the “Help” manual of the UPS
monitoring software.
NOTE
The change of some settings can cause the unit to switch from bypass to
standby and output power is lost.
8/10 kVA
5/6 kVA
fig. 5.1
5.2 SNMP INTERFACE CARD (OPTION)
This card allows the data interface to be connected directly to an Ethernet network. The card is fitted into
the SNMP Card slot (8, fig. 3.3.5.a). For more information, please refer to the user manual that comes with
the interface card.
modifications reserved 32User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 33
6 OPTIONS
6.1 OPTIONAL POWER DISTRIBUTION UNIT
A different power distribution unit, equipped with Maintenance Bypass switch, can be installed on the
rear side of the unit.
To replace the Power Distribution Unit (on 5/6 kVA models) or to place the Optional Power Distribution
Unit (on 8/10 kVA models) proceed as follows:
1. Ensure the unit is completely shutdown, with
all breakers opened (see section 4.3.2).
2. Disconnect internal batteries (see section
7.4.1 and 7.4.2) and external batteries by
removing cabling from UPS DC connector.
3. On 5/6 kVA models remove all power
connection cables from the Standard PDU
(see section 3.3.9).
4. On 5/6 kVA models loosen the three mounting
screws (fig. 6.1.a) of the Standard PDU until it
can be removed from the UPS cabinet.
On 8/10 kVA models loosen the four mounting
screws (fig. 6.1.b) of the PDU cover and
remove it.
5. Remove PDU from UPS.
The unit is now ready for new PDU assembly.
5/6 kVA
fig. 6.1.a
8/10 kVA
fig. 6.1.b
6. On 5/6 kVA models align terminals on the
backside of the PDU with UPS ones and slide
PDU in the UPS (fig. 6.1.c). On 8/10 kVA
connect terminals on the backside of the PDU
with connections in the PDU tray on the
backside of the UPS and slide PDU in to the
UPS (fig. 6.1.d).
7. On 5/6 kVA models fix the PDU to the UPS
with the three mounting screws (fig. 6.1.c). On
8/10 kVA models fix the PDU to the UPS with
the four mounting screws (fig. 6.1.d).
8. Connect Input / Output terminals and follow
standard installation procedure
(see section 3.3.9).
The unit is now ready to be turned on again.
Proceed with section 4.2.1.
5/6 kVA
fig. 6.1.c
8/10 kVA
fig. 6.1.d
modifications reserved33 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 34
6.1.1 5/6 kVA PDUs
Model Outlets (NEMA) Inlets (NEMA)
GT PDU A 01* 1 1
GT PDU A 02 1 1
GT PDU A 03 2 2 1 1 1
GT PDU A 04 1 1 2 1
GT PDU A 05 2 2 2 1
GT PDU A 06 2 2 1
GT PDU A 07 2 2 1 1 1
GT PDU A 08 2 2 2 1
GT PDU A 09 4 1
*: No 3 pole 6 ms maximum transfer time manual bypass
GT PDU B 01 4 4 2
GT PDU B 02 2 2 4
GT PDU B 03 2 2 4
GT PDU B 04 2 2 2 2
GT PDU B 05 2 2 1 1 2
GT PDU B 06 2 2 4
6.2 EXTENDED RUNTIME
Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In this
case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of
the available runtime (via UPS monitoring software). Depending of the charge condition of the new
batteries the new runtime calculations may temporarily be unreliable.
Additional batteries increase the recharging time for the unit; all other operational information is the same
as for standard models. The following table shows runtimes with up to 3 Battery Packs. 1 Battery Pack is
the normal configuration.
10% 75 min 156 min 235 min 313 min
25% 31 min 75 min 115 min 155 min
GT5000 RT
GT6000 RT
GT8000 RT
GT10000 RT
50% 14 min 34 min 58 min 82 min
75% 8 min 22 min 35 min 50 min
100% 5 min 14 min 25 min 36 min
10% 75 min 156 min 235 min 313 min
25% 31 min 75 min 115 min 155 min
50% 14 min 34 min 58 min 82 min
75% 8 min 22 min 35 min 50 min
100% 5 min 14 min 25 min 36 min
10% 107 min 251 min 333 min 494 min
25% 40 min 100 min 160 min 225 min
50% 16 min 39 min 66 min 92 min
75% 10 min 24 min 41 min 58 min
100% 6 min 17 min 28 min 41 min
10% 107 min 251 min 333 min 494 min
25% 40 min 100 min 160 min 225 min
50% 16 min 39 min 66 min 92 min
75% 10 min 24 min 41 min 58 min
100% 6 min 17 min 28 min 41 min
modifications reserved 34User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 35
7 MAINTENANCE
7.1 SAFETY
7.2 GENERAL
The GE Digital Energy GT Series UPS is virtually maintenance free: take care of proper environmental
conditions and keep air inlets/outlets free of dust. Please read 3.2.
DANGER
When the UPS operates, all parts of the electronics are directly connected to the
utility and high voltages are present on all internal parts, including the battery.
Even after disconnection from the utility, all parts inside the UPS, including the
battery, conduct dangerous voltages (except the COM port outlet). For your
safety, only authorized service personnel may remove the cabinet cover.
Refer to section 4.3.2 for further details.
NOTE
Apart from battery replacement, refer maintenance and service work to
qualified and skilled personnel only. Refer to section 1.2 for further details.
7.3 RECYCLING THE UPS AT THE END OF SERVICE LIFE
NOTE
This product has been designed to respect the environment, using materials and
components respecting eco-design rules. It does not contain CFCs (Carbon
Fluorine Chloride) of HCFCs (Halogen Carbon Fluorine Chloride).
The batteries contain lead, which is a harmful substance for the environment.
Proper disposal or recycling of the batteries is required. Refer to your local codes
for disposal requirements.
GE Digital Energy™, in compliance with environment protection recommends
that the UPS equipment, at the end of its service life, must be recycled
conforming to the local applicable regulations.
modifications reserved 35User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 36
7.4 BATTERIES
The service life of the battery is from 3 to 5 years, depending on the operating temperature and on the
number of discharge cycles.
As a healthy battery is critical to the performance of the UPS, an automatic quick battery test is performed
regularly to ensure failsafe operation (see section 4.5). When the condition of the battery is critical, a
'replace battery' alarm will be activated (see 4.4 and 4.4.6). Replace the batteries as soon as possible.
General guidelines:
•When replacing the batteries, use all of them of only the
same type and size.
•Never short the battery terminals. Shorting may cause the
battery to burn. When working with batteries remove
watches, rings or other metal objects and only use
insulated tools.
• Avoid charging in a sealed container.
• Proper disposal of batteries is required: refer to your local
codes for disposal requirements.
• Never dispose batteries in fire: they may explode.
• Never disassemble or reassemble batteries; their contents
(electrolyte) may be extremely toxic. If exposed to
electrolyte, wash immediately with plenty of water, if eye
contact occurs flush with water and contact a physician.
Don’t throw batteries away,
treat them as harmful
waste
modifications reserved 36User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 37
7.4.1 Internal battery replacement (for 5/6 kVA models)
In case of battery failure, please proceed with the following steps to replace that:
NOTE
During battery replacement the UPS will not be able to support the load if a mains
failure occurs! It is recommended to switch off the load (see section 4.3.2) before
battery manipulation.
1. Remove the UPS front cover
from the cabinet by gently
pulling it out.
2. Remove the battery grille by
loosening the two mounting
screws (fig. 7.4.1.a).
3. Grab hold of the battery pack
and slide it out (fig. 7.4.1.b).
Be careful during this
operation and consider the
weight of the battery.
5/6 kVA
4. Unpack the new battery pack
from its carton box.
5. Place the battery pack in
front of the battery
compartment, aligning the
rear connector to the front
panel (see section 3.3.3).
6. Slide the battery pack into
the battery compartment
until the rear connector is
plugged with the UPS
internal DC socket.
7. Fix the battery grille by
tightening screws.
8. Mount the two front covers.
NOTE
To avoid battery malfunction, in case of additional batteries connected, all battery packs
have to be replaced! It’s not possible to replace only 1 pack. Avoid connection between
new and old battery packs.
fig. 7.4.1.a
5/6 kVA
fig. 7.4.1.b
modifications reserved 37User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 38
7.4.2 Internal battery replacement (for 8/10 kVA models)
In case of battery failure, please proceed with the following steps to replace that:
NOTE
During battery replacement the UPS will not be able to support the load if a mains
failure occurs! It is recommended to switch off the load (see section 4.3.2) before
battery manipulation.
1. Remove the 2 lower UPS
front cover from the cabinet
by gently pulling them out.
2. Remove the battery grille by
loosening the three
mounting screws (fig. 7.4.2.a).
3. Disconnect DC cabling from
battery pack connectors
(fig. 7.4.2.b).
4. Grab hold of the battery
packs and slide them out
(fig. 7.4.2.b). Be careful during
this operation and consider
the weight of the battery.
5. Unpack the 2 new battery
packs from their carton
boxes.
fig. 7.4.2.a
8/10 kVA
8/10 kVA
6. Place the battery packs side
by side in the battery
compartment.
7. Fix the 2 battery brackets
with the screw set to hold
battery packs into the
cabinet (see section 3.3.4).
8. Connect the DC connectors
of each battery pack.
9. Fix the battery grille in front
of the battery compartment
with 3 screws.
10. Mount the two front covers
NOTE
To avoid battery malfunction, in case of additional batteries connected, all battery packs
have to be replaced! It’s not possible to replace only 1 pack. Avoid connection between
new and old battery packs.
fig. 7.4.2.b
modifications reserved38 User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 39
7.5 POWER UNIT MAINTENANCE
For maintenance purposes the power unit can be replaced while output is transferred to manual bypass
(for 5/6 kVA models only with PDUs including manual bypass switch). See following sections for detailed
description on replacement procedure.
WARNING
The UPS has to be switched to manual bypass before power unit replacement
otherwise output power is lost.
7.5.1 Power unit replacement (for 5/6 kVA models)
NOTE
UPS replacement is only possible with PDUs including manual bypass switch.
1. Switch the UPS to manual bypass;
see section 4.3.3 for further details.
2. Loosen the 3 mounting screws of the optional
PDU (fig. 7.5.1.a) and slide it out from the power
module.
3. Loosen the 2 terminal cover fixation screws, on
the back side of the optional PDU slide the
cover over the terminals and fix the screws
again (fig. 7.5.1.b)
4. Power module can now be replaced. If internal
batteries are not at end of life they can be
placed in the new power module
(see section 3.3.3)
5. Slide optional PDU into new power module and
fix the three mounting screws (fig. 7.5.1.a).
6. Switch the UPS back to normal operation;
see section 4.3.3 for further details.
7.5.2 Power unit replacement (for 8/10 kVA models)
1. Switch the UPS to manual bypass; see
section 4.3.3 for further details.
2. Remove the 3 front covers (2, fig. 7.5.2.a).
3. Loosen the 3 mounting screws of the
internal battery cover and remove it
(3, fig. 7.5.2.a).
4. Loosen the 5 mounting screws of the power
module cover and remove it (4, fig. 7.5.2.a).
5. Slide the power module out of the box
(5, fig. 7.5.2.a).
6. Power module can now be replaced.
7. Slide in the new power module until the rear
connector of the power module is plugged
in the socket on the UPS (6, fig. 7.5.2.b).
8. Reposition the power module cover and fix it
with the 5 screws. In the same way mount
the internal battery cover (7 & 8, fig. 7.5.2.b).
9. Place again the 3 front covers (9, fig. 7.5.2.b).
10. Switch the UPS back to normal operation;
see section 4.3.3 for further details.
fig. 7.5.1.a
fig. 7.5.1.b
fig. 7.5.2.a
fig. 7.5.2.b
5/6 kVA
8/10 kVA
8/10 kVA
modifications reserved 39User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 40
8 TROUBLESHOOTING
Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see fig. 3.3.5.a/b) and be sure that the
UPS is not overloaded.
The following chart is a simple troubleshooting checklist. If the suggested solution does not succeed, or if
the information is insufficient to solve the problem, please contact your dealer or consult
www.GEDigitalEnergy.com
PROBLEM POSSIBLE CAUSE SOLUTION
No display
No alarm
(UPS switched off)
Mains switched off Switch on mains supply
No mains voltage present Carry out mains inspection,
consult qualified electrician
Mains indicator not illuminating,
acoustic alarm intermittent
Mains indicator not illuminating,
mains voltage present, acoustic
alarm intermittent
Alarm LED illuminated,
continuous acoustic alarm
Delivered runtime less than
specified
Last load bar LED is lit, acoustic
alarm intermittent
Input fuse blown or circuit
Replace fuse or reset breaker
breaker tripped
No mains voltage present Read section 4.4.2 – UPS on
battery
Input fuse blown or circuit
Replace fuse or reset breaker
breaker tripped
UPS failure
UPS over-temperature
Overload at UPS output
Battery extension fuse switch is
Contact UPS dealer or go to
www.GEDigitalEnergy.com
Allow UPS to cool down
Reduce UPS load
Switch to ‘On’ position
in ‘Open’ position
Batteries are not fully charged Charge batteries for 8 hours and
reconfirm runtime
Batteries are defective Contact UPS dealer
Charger is defective Contact UPS dealer
Overload at UPS output Reduce UPS load
No communication between
UPS and PC
Incorrect communication cable Check whether correct cable is
used
PC interface defective or being
accessed by another service
Check if no other software is
accessing the interface
Interference on the data cable Rearrange cables
modifications reserved 40User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)
Page 41
9 SPECIFICATIONS
Model : GT5000 GT6000 GT8000 GT10000
Ratings
Power ratings depending on input voltage : VA / W VA / W VA / W VA / W
AC input voltage : Nominal: 120 / 208 V
AC input voltage range : 100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
Input current waveform : sine wave
Input current (A) at nominal input voltage : 20 20 40 40
Input power factor : > 0.97
Input frequency range : 40 - 70 Hz
Input phase (L1 to L2) : 120° / 180° / 240° ±10°
Inrush current : 40 40 40 40
Output converter
AC output voltage : 100 / 110 / 115 / 120 / 127 V (selectable)
AC output voltage tolerance : L-N ± 3%; L1-L2 ± 5% L-N ± 2%; L1-L2 ± 5%
Output frequency : 50 / 60 Hz, auto selection
Output frequency range : nominal ± 5% with mains synchronizing
Output waveform : sine wave
Harmonic distortion : < 3% with linear load, < 5% with non-linear full load
Power factor at nominal input voltage : 0.87 0.8 0.86 0.92
Crest factor (peak to RMS current) : ≤ 3 : 1
Capacity appliance outlets : with 55A Terminal Block
Bypass
AC input voltage range : ± 15% of selected output voltage
Frequency tracking rate : 1Hz/s
Frequency tracking range : ± 5% of selected frequency
Typical transfer time, msec : 0
Overload capability: fully protected against overload and short circuits
Overload behavior during battery operation : 130% during 10 seconds 130% during 1 minute
: 200% during 2 seconds 200% during 5 seconds
Overload behavior during bypass operation : depends on rating of thermal circuit breaker overload protection
125% of TCB value for 200 seconds 110% for 300 seconds
200% of TCB value for 10 seconds 130% for 30 seconds
300% of TCB value for 4 seconds 200% for 5 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc) : 144 144 288 288
Number / Ah batteries
(in battery kit and battery ext. pack) : 12pcs / 8Ah 12pcs / 8Ah 24pcs / 8Ah 24pcs / 8Ah
Type : REW45-12 FR
Service life : up to 5 years (depending on use)
Recharge current : 1 A
Battery recharge time
(batt. discharged at 100% load) : 6 hours for 90% capacity 3 hours for 90% capacity
Runtime in minutes
at typical load (75%) : 8 8 9 9
25% : 31 31 40 40
50% : 14 14 16 16
75% : 8 8 9 9
100% : 5 5 5 5
General
Weight UPS kg : 30.3 Kg (67 lbs) 49.3 Kg (109 lbs)
Dimensions UPS (h
xwxd) : 176x430x592 mm (6.9x16.9x22.55 in) 267x430x660 mm (10.5x16.9x26 in)
Weight battery pack kg : 43 Kg (94.7 lbs) 91 Kg (200.4 lbs)
Dimensions battery pack : 87x430x592 mm (3.47x16.9x2255 in) 173x430x660 mm (6.8x16.9x26 in)
Enclosure / protection : steel-plastic / IP20
Environment
Safety : UL1778
Electromagnetic compatibility : EMI: FCC CFR47 Part 15, class A, ESD: IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4, level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A (level 3) & B (level 1)
Ambient temperature : 0 to +40ºC
Audible noise at 1 meter : < 55 dB(A), load and temperature dependent
Max. relative humidity : 90% (non-condensing)
Color : Black - RAL 9005