GE Industrial Solutions DB-75, DBL-75, DB-100, DBL-100 User Manual

DEH–40032A Installation Instructions
g
INTRODUCTION
GE Conversion Kits are designed for upgrading
®
existing Westinghouse circuit breakers, rather than replacing the entire breaker. The Conversion Kits include ProTrip™ Trip Units, the latest advance in GE trip systems.
ProTrip Conversion Kits are designed and tested to conform to ANSI Standard C37.59, allowing the retrofitter to properly install the kit and acceptance test the breaker.
This publication covers installation of ProTrip™ Conversion Kits on Westinghouse Type DB-75, DBL-75, DB-100, and DBL-100 power circuit breakers. Each Conversion Kit contains all the components needed to convert from an existing Westinghouse electromechanical trip system.
low-voltage power
low-voltage
ProTrip™ Conversion Kits
For Westinghouse
®
Type DB-75, DBL­75, DB-100, DBL-100 Low-Voltage Power Circuit Breakers
TABLE OF CONTENTS
INTRODUCTION.........................................................................................................................................................1
SECTION 1. GENERAL INFORMATION............................................................................................................4
SECTION 2. BEFORE INSTALLATION
..............................................................................................................4
SECTION 3. BACK FRAME BREAKER CONVERSION
Removing the Electromechanical Trip Devices......................................................................................5
Installing the Phase Sensors (CTs) ........................................................................................................6
SECTION 4. FRONT FRAME BREAKER CONVERSION
Installing the Trip Paddle ........................................................................................................................7
Installing the Trip Unit Mounting Bracket................................................................................................7
Adjusting the Flux Shifter........................................................................................................................8
Connecting the Trip Unit Wiring Harness ...............................................................................................9
Installing the Trip Unit ...........................................................................................................................10
Configuring the Trip Unit.......................................................................................................................10
SECTION 5. FOUR-WIRE GROUND FAULT OPTION................................................................................11
SECTION 6. TESTING AND TROUBLE-SHOOTING
Testing ..................................................................................................................................................12
Trouble-Shooting...................................................................................................................................12
Nuisance Tripping on Ground Fault-Equipped Breakers.........................................................12
2
LIST OF FIGURES
1. Removing a trip device.....................................................................................................................................5
2. Electromechanical trip devices removed from the breaker..............................................................................5
3. Preparing the load terminals............................................................................................................................6
4. CTs installed on the breaker............................................................................................................................6
5. Trip paddle installed on the trip bar..................................................................................................................7
6. Trip unit mounting bracket................................................................................................................................ 7
7. Installing the support bracket...........................................................................................................................7
8. Trip unit mounting bracket installed on the breaker frame. ............................................................................. 8
9. Adjusting the flux shifter...................................................................................................................................8
10. Wiring harness installation on the CTs. ...........................................................................................................9
11. Trip unit attached to its mounting plate..........................................................................................................10
12. Harness connector attached to the trip unit...................................................................................................10
13. Mounting the trip unit on the breaker. ............................................................................................................ 10
14. Neutral sensor outline for a DB-75 or DB-100 breaker..................................................................................11
15. Cabling diagram for ProTrip™ trip units with ground fault on four-wire loads...............................................14
3
SECTION 1. GENERAL INFORMATION
SECTION 2. BEFORE INSTALLATION
GE Conversion Kit installation is straightforward, but does require careful workmanship and attention to these instructions. Familiarity with the breaker is highly desirable. Then general approach is to first remove the existing trip devices from the breaker, then install the ProTrip components. Following this procedure, the converted breaker is performance tested before it is returned to service.
The majority of trip unit kit installations do not require any customized assembly work. However, some installations may involve unusual mounting conditions or accessory combinations that require minor modifications and/or relocation of components. In most instances, this supplementary work can be done on site.
In preparation for the conversion, the installer should verify that the appropriate current sensors and trip unit have been furnished. Whenever a ProTrip kit is installed on a breaker with a four-wire system, an associated neutral sensor (CT) is required for separate mounting in the equipment. Ensure that retrofitted breakers are applied within their short-circuit ratings.
Note that all ProTrip trip units supplied with conversion kits are equipped with long-time, short-time, instantaneous, and defeatable ground fault (LSIGX) trip functions. The installer should be aware of how these functions will affect his application before installing the conversion kit.
As a service-related consideration, the installation of a ProTrip kit provides an excellent opportunity to perform normal maintenance on the breaker, particularly when the front and back frames are separated. Such procedures are described in the installation and maintenance manuals supplied with the breaker and equipment.
Before starting any work, turn off and lock out all power sources leading to the breaker, both primary and secondary. Remove the breaker to a clean, well-lighted work area.
WARNING: Low-voltage power circuit breakers use high-speed, stored-energy spring operating mechanisms. The breakers and their enclosures contain interlocks and safety features intended to provide safe, proper operating sequences. For maximum personnel protection during installation, operation, and maintenance of these breakers, the following procedures must be followed. Failure to follow these procedures may result in personal injury or property damage.
• Only qualified persons, as defined in the National Electrical Code, who are familiar with the installation and maintenance of low-voltage power circuit breakers and switchgear assemblies, should perform any work on these breakers.
• Completely read and understand all instructions before attempting any breaker installation, operation, maintenance, or modification.
• Turn off and lock out the power source feeding the breaker before attempting any installation, maintenance, or modification. Follow all lock-out and tag-out rules of the National Electrical Code and all other applicable codes.
• Do not work on a closed breaker or a breaker with the closing springs charged. Trip an OPEN breaker and be sure the stored-energy springs are discharged, thus removing the possibility that the breaker may trip OPEN or the closing springs discharge and cause injury.
• Trip the breaker OPEN, then remove the breaker to a well-lighted work area before beginning work.
• Do not perform any maintenance that includes breaker charging, closing, tripping, or any other function that could cause significant movement of a draw-out breaker while it is on the draw-out extension rails.
• Do not leave the breaker in an intermediate position in the switchgear compartment. Always leave it in the CONNECTED, TEST, or DISCONNECTED position. Failure to do so could lead to improper positioning of the breaker and flashback.
4
SECTION 3. BACK FRAME BREAKER CONVERSION
The back frame conversion of a Westinghouse DB-75 or DB-100 breaker consists of the following steps:
1. Remove the breaker to a clean, well-lighted work bench and place it on its left side, so that both the bottom and back are easily accessible.
2. Remove the existing electromechanical trip devices.
3. Install the new phase sensors (CTs).
Removing the Electromechanical Trip Devices
1. Remove and discard the four bolts holding each trip device to a pole of the breaker, as shown in Figure 1.
2. Remove and discard the three electromechanical trip devices, shown in Figure 2.
CAUTION: Do not remove the trip paddles from the common trip bar. They are used to balance the trip action and could cause nuisance tripping if removed.
Figure 1. Removing a trip device.
Figure 2. Electromechanical trip devices removed from
the breaker.
5
Loading...
+ 11 hidden pages