CPS3200U Upstream System – 23” Product Manual CPS3200U
Table of Contents
Table of Contents ...............................................................................................................................................................................................................................2
Table of Figures ..................................................................................................................................................................................................................................3
Table of Tables ....................................................................................................................................................................................................................................4
Customer Service Contacts ..................................................................................................................................................................................................6
On-Line Power Systems Product Manuals and Software .......................................................................................................................................6
System Identification ........................................................................................................................................................................................................... 15
6 Installing the Shelf Level Upstream Product ................................................................................................................................................................... 16
Installing and Powering the CP3200U Converter Shelf ......................................................................................................................................... 16
Ground the Shelf .................................................................................................................................................................................................................... 18
Attach the Load Wiring ....................................................................................................................................................................................................... 18
Set Shelf ID and Attach Alarm Wiring ........................................................................................................................................................................... 20
Installing the Baffle ............................................................................................................................................................................................................... 22
Installing the Fan Shelf ........................................................................................................................................................................................................ 22
Installing the Filter Bracket and Filter ........................................................................................................................................................................... 26
7 Inspect the Network - Check and Mark Wiring Compliance .................................................................................................................................... 28
8 Final Installation........................................................................................................................................................................................................................... 29
Installing the Converters .................................................................................................................................................................................................... 29
Apply DC Power ...................................................................................................................................................................................................................... 30
Recognizing Normal States ............................................................................................................................................................................................... 30
QS982A LED Information Map ......................................................................................................................................................................................... 31
Confirm Operation of Alarm Wiring ............................................................................................................................................................................... 32
Installing the QS941A Ethernet Module ....................................................................................................................................................................... 32
Installing the Office Alarm Connector ........................................................................................................................................................................... 36
9 Reference Information .............................................................................................................................................................................................................. 37
QS982A Converter LED Information Map .................................................................................................................................................................... 37
QS982A LED Information Map (visual) .......................................................................................................................................................................... 38
Alarm Card Information ...................................................................................................................................................................................................... 39
QS930A Fan Shelf .................................................................................................................................................................................................................. 42
Appendix A: Operating Temperature Measurement and Vertical Spacing........................................................................................................... 46
Operating Temperature ...................................................................................................................................................................................................... 46
Baffles and Fan Trays .......................................................................................................................................................................................................... 46
Appendix C: Operation without a Controller - Alarm Wiring ....................................................................................................................................... 49
CPS3200U Shelf Alarm Card State Table ..................................................................................................................................................................... 50
Alarm Card Logical Operation of LEDs and Alarm Relays .................................................................................................................................... 50
Revision History ............................................................................................................................................................................................................................... 51
CC848779826 r09 December 2013 2
CPS3200U Upstream System – 23” Product Manual CPS3200U
Figure 4 Mounting the Converter Shelf .................................................................................................................................................................................. 16
Figure 5 Preparing to Make DC Connections to Converter Shelf ................................................................................................................................ 17
Figure 6 Making DC Connections to Converter Shelf ...................................................................................................................................................... 17
Figure 11 Setting Shelf ID ............................................................................................................................................................................................................ 21
Figure 12 Signal Wiring between Converter Shelves....................................................................................................................................................... 21
Figure 13 Installing a Baffle ........................................................................................................................................................................................................ 22
Figure 14 Mounting the Fan Shelf ............................................................................................................................................................................................ 22
Figure 15 Inserting Fan Trays .................................................................................................................................................................................................... 23
Figure 16 Open the Wiring Region of the Fan Shelf ......................................................................................................................................................... 23
Figure 17 Alarm Wiring for Fan Shelf ..................................................................................................................................................................................... 24
Figure 18 DC Cabling Fan Trays in CPS3200U Systems ................................................................................................................................................. 24
Figure 19 Cover the Wiring Region of the Fan Shelf ........................................................................................................................................................ 25
Figure 20 Fan Tray LEDs .............................................................................................................................................................................................................. 25
Figure 21 Mounting the Filter Bracket.................................................................................................................................................................................... 26
Figure 27 QS982A Faceplate and LEDs ................................................................................................................................................................................. 30
Figure 28 Fan Shelf Right Hand Cover ................................................................................................................................................................................... 32
Figure 29 Fan Shelf Controller Jumper .................................................................................................................................................................................. 32
Figure 30 Preparing a Fan Shelf for a CPS Controller ...................................................................................................................................................... 33
Figure 31 Installing the Controller ........................................................................................................................................................................................... 33
Figure 33 Fan Shelf RS-485 Jacks ............................................................................................................................................................................................ 35
Figure 34 Signal Cables - System ............................................................................................................................................................................................. 35
Figure 36 QS982 LEDs and Test Points .................................................................................................................................................................................. 37
Figure 41 QS930 Fan Shelf Dimensions ................................................................................................................................................................................ 42
Figure 42 QS930 Fan Shelf Connections and Fuses ........................................................................................................................................................ 42
Figure 43 Converter Shelf with Slot Fillers ............................................................................................................................................................................ 46
Figure 44 Alarm Card Office Alarm Pinout and Shelf ID ................................................................................................................................................. 49
Table 4 QS982A LED Information Map ................................................................................................................................................................................... 31
Table 5 QS982A Converter LED Information Map ............................................................................................................................................................. 37
Table 6 QS982A Converter LED Information Map (visual) .............................................................................................................................................. 38
Table 9 Shelf Alarm Card State ................................................................................................................................................................................................. 50
CC848779826 r09 December 2013 4
CPS3200U Upstream System – 23” Product Manual CPS3200U
1 Introduction
Overview
The CPS3200U is the premier upstream dc/dc converter for line powering FTTN networks. The 3200U contains 16 dc/dc
converter/limiter cards in a dense 2 RU shelf. Each card contains a pair of independent -48 Vdc input to ±190 Vdc
output converters with each output safety limited to 100VA. In addition, each output terminal is safety Ground Fault
protected. The cards are fully connectorized and insulator shielded, inrush current protected and completely hot
swappable, making card addition to in-service shelves in the field an easy, one step process. The converter card shelf is
completely front access, with all -48V input and RJ21 output connections made on connectors in front of the midmount shelf brackets. The alarm and communications connections are also on the front of the shelf.
The CPS3200U converter shelf meets the applicable requirements of these North American product standards:
UL60950-21, UL60950-1, Telcordia GR-3108-CORE, GR-1089-CORE, GR-487-CORE (converter shelf), and GR-063-CORE.
Summary
The CPS3200U Upstream System delivers power over telephone lines. The primary application is enabling the delivery of
video bandwidth data rates to residences over twisted pairs by allowing placement of powered electronics at an
acceptable distance from the residence.
48 Vdc Input, ±190 Vdc Output Converter/Limiter System distributes battery backed up power from existing -48V
battery backed up sites like Central Offices and Remote terminals to reliably power electronics near the home. It does
this by converting the -48V to a UL60950-21 safety approved + and – 190V current limited and ground fault protected
source. Each front access shelf provides 32 channels.
Reference Documents
Document Title
CC848836981 Galaxy Pulsar Edge Product Manual
CC848853457 CPS3200U Technical Support Guide
Line Power Product Line Brochure – Specifications and Ordering Guide
CC848779826 r09 December 2013 5
CPS3200U Upstream System – 23” Product Manual CPS3200U
Calling from
Phone Number
+1 877 546 3243
+1 972 244 9288
Or contact your local field support center or your sales representative to discuss your specific needs.
Customer Service Contacts
Customer Service, Customer Training, Technical Support,
Product Repair and Return, and Warranty Service
Services provided include initiating the spare parts procurement process, ordering documents, product warranty
administration, and providing other product and service information.
GE Energy phones are staffed from 7:00 am to 5:00 pm USA Central Time Zone (GMT -6), Monday through Friday, on
normal business days. At other times, this number is still available, but for emergencies only.
•United States, Canada, Puerto Rico, and the US Virgin
Islands
•All other countries
Or
1
USADCC
+ 877 546 3243
On-Line Power Systems Product Manuals and Software
Product manuals, technical support guides, product line brochures, and software are available on-line. Software
includes Easy View and SNMP MIB.
http://www.gecriticalpower.com
1
The USA direct country code for the country where the call is originating
CC848779826 r09 December 2013 6
CPS3200U Upstream System – 23” Product Manual CPS3200U
2 Product Description
Figure 1 Block Diagram -48V Fed CPS3200U Shelf
Basic block diagram of single converter shelf System
Operation
Power comes in as -48V and is distributed in an A and B redundant fashion to each of the converter cards and the
alarm card. There are two +/-190V circuits on each converter card. The circuits both boost the voltage and limit the
current as prescribed by UL60950-21 and GR-1089-CORE.
Warning: Ground faults or short circuits on the output do not permanently disconnect the output. The converter circuit
tests the line every 4 seconds and will re-energize if the wiring fault is cleared.
A serial communication bus links each converter to an alarm card at the end of each shelf.
The alarm card provides major and minor form C contacts, manages the converters and relays information to a Lineage
Power CPS6000 family controller using Galaxy Protocol over an RS485 bus. Up to 24 shelves can be controlled and
monitored by one CPS6000 family controller. The CPS6000 controller is WEB and SNMP capable.
Configurations
32 circuit, front access +/-190V shelves come in two configurations - airflow from bottom to top and airflow from top to
bottom. A single IP drop can be used to manage up to 24 shelves or 768 circuits.
CC848779826 r09 December 2013 7
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 1 Specifications
Electrical
Parameter
Symbol
Min
Typical
Max2
Unit
Input Voltage
Operating Continuous
Non-operating, No Damage
V
-40 0 -52.8
-60
-40
Vdc
Transient (@ duration =)
1 µs
V
-200
Input Current - (per half shelf
at 97.7W on all circuits)
VIN = 54.4V
I
IN
34.7
Adc
VIN = 52.1V
I
IN
36.2
Adc
VIN = 42.6V
I
IN
44.3
Adc
VIN = 40.0V
I
47.2
Adc
Temperature
Normal Operating Ambient
Temperature at 150 lfm airflow
TA -40 50
°C
Operating Ambient Temperature
at higher (TBD) airflow
TA -40 75
°C
Cold Start Temperature
TA
-40
°C
Storage Temperature
T
stg
-55 85
°C
Power – per C/L Card
Input Power at -42.6 Vdc input
Pin
2403
W
Power Dissipation
Pdiss
21
40*
W
Output Power
Pout
200
W
Output
Voltage – line to line
VO 378
380
382
Vdc
Power – per C/L circuit
PO 95.0
97.7
100
W
Current – per C/L circuit
I
OUT
251
257
262
mA
Isolation
Input to Output Voltage
1500
Vdc
Physical
Height
in (mm)
Width
in (mm)
Depth
in (mm)
Weight
lb (kg)
23-Inch Shelf
3.5 (88.9)
21.4 (543.6)
12 (304)
30 (13.6)
Fan Shelf
3.5 (88.9)
21.4 (543.6)
12 (304)
20 (9.0)
1U Baffle
1.75 (44.4)
21.4 (543.6)
12 (304)
4 (1.8)
Specifications
I
5 Seconds
rise and fall rate of 10V/ms)
10 ms (
10 µs
V
tr
V
tr
V
tr
tr
IN
-65
-75
-100
Vdc
Installation Category
CPS3200U output circuits are suitable for connection to telephone lines that are equipped with primary lightning
protectors consistent with UL 497. The user must provide protection on each copper pair to a level corresponding to a
CommScope 3C*EW Gas tube primary protector or equivalent gas tube protector [For example: 3C3EW provides the
part in a red color]. This protector has a voltage breakdown range of 265-465 Volts and an impulse spark over range of
<265-700 Volts. The 5-Pin protector must be marked as a “special circuit” consistent with the marking protocol in the
users network. Protectors are provided by the telco customer.
Network equipment and components along the powering circuit shall have suitable insulation resistance at 200 Vdc
from each conductor to ground and a total insulation resistance suitable for 400 Vdc from line to line.
2
Max = Absolute Maximum Rating
3
These are maximum situations with each circuit loaded to 100W. No actual or engineered application would load
every circuit to this level. In the absence of detailed information about the network we would recommend using the
typical dissipation value of 21 Watts for most applications with 30W per card for highly loaded networks.
CC848779826 r09 December 2013 8
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 2 Ordering Codes
CODE
COMCODE
DESCRIPTION
Items for new installation or growth of existing installations
QS912A
108996732
Converter Shelf with Alarm Module (provides landings for double-hole lugs)
QS982A
108996641
Converter Card (For first install on single shelf systems the sum of converters cards
Converter slot fillers)
CC109121992
Converter slot filler
QS930A
108996930
Fan Shelf with 2 redundant fan trays
QS941A
108996947
Controller with Display and Ethernet capabilities
CC848756577
Airflow baffle without bracket for air filter
CC109102638
Airflow baffle with bracket for air filter. Includes air filter.
Replacement air filter CC109121984 listed below.
Spares: Items for repair or maintenance of existing installation
CC109121984
Air filter to be used with Airflow baffle CC109102638 (Spare)
QS930B
108997623
Fan tray assembly (Spare)
QS920A
CC109102118
Alarm Module (Spare)
Expansion Items: Provide a 4 ft long wireset to transmit alarm signals past a baffle.
Use when adding a second fan shelf to an existing system.
H5694820G050
CC109122074
Fan Shelf w/2 fan trays, wireset, baffle, filter, controller cover
H5694820G051
CC109132271
Fan Shelf w/2 fan trays, wireset, baffle, controller cover
This is a short list of CPS3200 items that can be purchased. See Line Power Product Line Brochure for detail.
and converter slot fillers should be 16. For example: 14 Converter cards and 2
Note: A baffle must be placed above the topmost converter shelf for use in customer premise locations for UL safety
compliance. Baffles are not required in restricted access locations such as outside plant cabinet, CEV or hut locations.
The baffle can be ordered separately from the above list or in combination with a fan shelf by choosing an item from
this list.
CPS3200U Upstream System – 23” Product Manual CPS3200U
4 Safety
Safety Statements
Please read and follow all safety instructions and warnings before installing, maintaining, or repairing the CPS3200U
System:
• The CPS3200U platform is Underwriters Laboratories (UL) Listed per UL60950-21.
• CPS3200U shelves have high, current limited, voltages on the output connectors with ground fault protection.
• For the product to be safe the chassis must be grounded by a permanent means.
• The return conductor of the -48V shall be terminated in the ground window, (held at frame ground potential).
• Install only in restricted access areas (dedicated equipment rooms, equipment closets, or the like) in accordance
with articles 110-16, 110-17, and 110-18 of the U.S. National Electric Code (NEC), ANSI/NFPA No. 70, and
pursuant to applicable local codes.
• The telecommunication line cable, carrying the +/-190V inside the cabinet between the equipment and the
primary protectors, shall be minimum 26 AWG, and rated minimum 200V. Consideration shall be taken at the
time of installation to verify cable rating.
• Primary protection must be provided on all the telecommunication line cable consistent with UL 497.
• Airflow must be provided at a rate of 175 lfm across the entire cross section of the shelf for operation in
environments up to 65 C, when measured at the inlet of the warmest converter shelf.
• This equipment is to be used in controlled environments (an area where the humidity is maintained at levels that
cannot cause condensation on the equipment, the contaminating dust is controlled, and the steady-state
ambient temperature is within the range specified).
• For multi-shelf systems (up to 3), this equipment has been evaluated for continuous use in central office
environments with ambient temperatures from -40°C to 50°C when used with the QS982A converters. For multishelf systems (up to 2), this equipment has been evaluated for continuous use in outside plant cabinet, CEV, and
hut applications with ambient temperatures from -40°C to +75°C. Proper airflow is required in all cases to ensure
maximum performance.
• This equipment must not be installed over combustible surfaces.
• For installations in the United States, Listed compression connectors are to be used to terminate Listed field-
wired conductors where required. For all installations, the appropriate connector is to be applied only to the
correct size conductor as specified by the connector manufacturer, using only the connector manufacturer's
recommended tooling or tooling approved for that connector.
• If the proper connector for the country of installation is not provided, obtain appropriate connectors and follow
manufacturer’s requirements and all local requirements for proper connections. All national and local rules and
regulations should be followed when making field connections.
• The subject product is not provided with a dc mains disconnect. Provision for mains disconnect such as branch
circuit breakers shall be provided by the end product installation.
• The main output voltage (+/-190V) meets UL60950-21RFT-V requirements. DO NOT CONNECT TO RFT-C
CIRCUITS.
• Insulation on field-wired conductors should be rated no less than 90° Celsius. Wire conductor size should be
sized per electrical codes for 75° Celsius wire, and based on the ampacity of the associated protection device.
Wiring internal to enclosed equipment cabinets should be rated at 105° Celsius (minimum).
• Torque electrical connections to the values specified on labels or in the product documentation.
• Input cables must be dressed to avoid damage to the conductors (caused by routing around sharp edges or
routing in areas where wires could get pinched) and undue stress on the connectors.
• Alarm contacts on the office alarm connector (TB1) are not fused within the distribution panel; therefore, current
limiting protection for these contacts must be provided by external circuits. Maximum ratings for alarm
CC848779826 r09 December 2013 10
CPS3200U Upstream System – 23” Product Manual CPS3200U
connections are 60Vdc and 0.5 amperes. Exceeding these maximum ratings could result in fire or damage to the
unit.
• Fuse and/or circuit breaker loads must not exceed 80% of the fuse and/or circuit breaker current rating.
Distribute loads across the panel.
• The short circuit current capability of the battery input to the panel must not exceed 10,000A.
• DC branch circuits to this equipment must be protected with either fuses or circuit breakers. Refer to the
equipment ratings to assure rating of equipment will not exceed 80% of the value of the protector chosen.
• For applications in cabinets, huts, vaults, and central offices, the CPS3200U mounting framework must be
connected to the system integrated ground grid.
• Installing fuses or circuit breakers not specified for use in these modules may result in injury to service personnel
or equipment damage. Use only replacement parts listed in this manual and on the equipment drawings.
• The telecom-type (e.g., GMT type) fuses can produce sparks during interruption or clearing of a fault on a high
energy circuit. Use only fuses provided with safety caps for this type of circuit. Installing telecom-type fuses not
equipped with safety caps may result in injury to service personnel.
• The designed capacitance between +/-190V RFT-V conductors is 2.2uF and the measured capacitance between
+/-190V and earth is 4.4uF. DO NOT add capacitance to the system to reach values that exceed safety limits per
the following figure:
CC848779826 r09 December 2013 11
CPS3200U Upstream System – 23” Product Manual CPS3200U
Figure 2 Capacitance Safety Limits
CC848779826 r09 December 2013 12
CPS3200U Upstream System – 23” Product Manual CPS3200U
Indicates the presence of a hazard that will cause death or severe personal injury if
Indicates the presence of a hazard that can cause death or severe personal injury if
Indicates the presence of a hazard that will or can cause minor personal injury or
This symbol identifies the need to refer to the equipment instructions for important
These symbols (or equivalent) are used to identify the presence of hazardous ac mains
This symbol is used to identify the presence of hazardous ac or dc voltages. It may
One of these two symbols (or equivalent) may be used to identify the presence of
precautions.”
One of these two symbols may be used to identify the presence of a hot surface. It
hazardous voltage levels.
This symbol is used to identify the protective safety earth ground for the equipment.
This symbol is used to identify other bonding points within the equipment.
This symbol is used to identify the need for safety glasses and may sometimes be
Warning Statements and Safety Symbols
The symbols may sometimes be accompanied by some type of statement; e.g., “Hazardous voltage/energy inside. Risk
of injury. This unit must be accessed only by qualified personnel.” Signal words as described below may also be used to
indicate the level of hazard.
DANGER
WARNING
CAUTION
the hazard is not avoided.
the hazard is not avoided.
property damage if the hazard is not avoided.
information.
voltage.
also be used to warn of hazardous energy levels.
rectifier and battery voltages. The symbol may sometimes be accompanied by some
type of statement, for example: “Battery voltage present. Risk of injury due to high
current. Avoid contacting conductors with uninsulated metal objects. Follow safety
may also be accompanied by a statement explaining the hazard. A symbol like this
with a lightning bolt through the hand also means that the part is or could be at
accompanied by some type of statement, for example: “Fuses can cause arcing and
sparks. Risk of eye injury. Always wear safety glasses.”
CC848779826 r09 December 2013 13
CPS3200U Upstream System – 23” Product Manual CPS3200U
Precautions
When working on or using this type of equipment, the following precautions should be noted:
• This unit must be installed, serviced, and operated only by skilled and qualified personnel who have the necessary
knowledge and practical experience with electrical equipment and who understand the hazards that can arise
when working on this type of equipment.
• The equipment could be powered by multiple dc inputs. Ensure that the appropriate circuit protection device for
each dc input is disconnected before servicing the equipment. Do not disconnect permanent bonding provisions
unless all dc inputs are disconnected.
• DC inputs may be connected in parallel to power the dc-dc converters. Disconnecting one dc input will not
necessarily remove power from the bus. Make sure all battery power sources are also disconnected and/or follow
safety procedures while working on any equipment that contains hazardous energy/voltage.
• Hazardous energy and voltages are present in the unit and on the interface cables that can shock or cause
serious injury. Follow all safety warnings and practices when servicing this equipment. When equipped with
QS982A modules, hazardous voltages (+/-190Vdc) will be present on the output connectors and associated
interconnection cables.
In addition to proper job training and safety procedures, the following are some basic precautions that should always
be used:
• Use only properly insulated tools.
• Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).
• Wear safety glasses. Fuses can produce sparks. High energy levels on buses and distribution components can
produce severe arcing.
• Do not rely on simple volt meter tests to determine if the +/-190V output circuit is off line. Physically break the
circuit by removing the associated QS982A converter before touching the +/-190V RFT-V circuit. Confirmationtest each circuit for 5 seconds before touching. In some line fault modes, power is cycled on every 4 seconds. The
presence of a fault may make it difficult to determine if the circuit is online. Always physically break the circuit.
• Lock out and tag circuit breakers/fuses when possible to prevent accidental turn on.
• Be aware of potential hazards before servicing equipment.
• Identify exposed hazardous electrical potentials on connectors, wiring, etc. (note the condition of these circuits,
especially wiring).
• Use care when removing or replacing covers; avoid contacting circuits.
CC848779826 r09 December 2013 14
CPS3200U Upstream System – 23” Product Manual CPS3200U
•A Complete Standard Insulated tool set
•Wire cutters and strippers
•Digital meter, +/- 0.02%
•Heat shrink gun
•Screw Drivers (flat-blade and Phillips)
•Torque wrench (0-240 in-lb / 28 Nm)
•ESD wrist strap
•Sockets
5 Pre-Installation
CPS3200U Installation
Purpose
CPS3200U Shelf Installation guide for generic installations. Additional requirements are needed for application specific
installations. Refer to Appendix A for spacing requirements.
Audience
Field application personnel
Precautions
Read Safety section prior to installation.
Observe ESD protection while installing circuit packs
Safety
• Always consider personal safety.
• Make sure the system is properly grounded per the National Electrical Code, local building codes, and any specific
company requirements per standard practice.
• Remove all metal jewelry before beginning the installation.
Installation Tools
System Identification
Identify the product you have received. Make sure to select procedural steps to match the product you have.
CC848779826 r09 December 2013 15
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Before opening the packaging, carefully inspect the outside in the presence of shipping
personnel for signs of damage.
2.
Carefully open the packaging to verify that the contents are complete and undamaged.
3.
If damaged, follow the shipping carrier’s procedure for filing a damage claim.
4.
Save the shipping package until all parts are operating within specifications. If the equipment
must be returned, it should be repacked in the original shipping crate.
Step
Action
1.
Locate the 2 mounting brackets, one on each side of the CPS3200U shelf; align the holes in the shelf-
6 Installing the Shelf Level Upstream Product
Unpacking Shelf Level Upstream Product
Make sure the framework has the space and the airflow to provide an acceptable operating environment for the
CPS3200U shelf. Then unpack the equipment.
Figure 3 QS912A Converter Shelf
(Shown configured with 2 operational circuits and 14 slot fillers for airflow control)
Installing and Powering the CP3200U Converter Shelf
Position the Shelf and mechanically attach it to the frame
mounting bracket with the holes in the mounting frame. Attach the brackets to the frame using two
screws per frame as shown.
Figure 4 Mounting the Converter Shelf
CC848779826 r09 December 2013 16
CPS3200U Upstream System – 23” Product Manual CPS3200U
2.
3.
4.
Open the distribution panel door on the right end of the shelf.
5.
Run 4 DC branch circuits back to the -48V source- Each feed supplies half of the shelf. A&B feeds for side
6.
Using the hardware supplied, attach the return wires for all 4 circuits.
7.
Using the hardware supplied, attach the A and B -48V conductors for side 1 (Slots 1-8).
8.
Using the hardware supplied, attach the A and B -48V conductors for side 2 (Slots 9-16).
9.
Torque each of the ¼ - 20 fasteners to 7 Nm or 65 in-lbs.
10.
Close the distribution door.
11.
Proceed to Grounding the Shelf.
Torque each of the fasteners to 4 Nm or 35 in-lbs.
Make sure the DC connections to be installed are not powered by turning off circuit breakers assigned to
this frame and checking with an Ohm meter.
Figure 5 Preparing to Make DC Connections to Converter Shelf
1 and A&B feeds for side 2.
Size each circuit to support 42 Amp List 2 Drains. Note: Lug landings are ¼ inch studs on 5/8 inch
centers. Use a minimum of 6 AWG conductor for environments up to +65°C (reference NEC Table 310-16
for applications of not more than three conductors in a raceway and correction factors for Ambient
Temperatures Over 30°C). Each installation will vary and the installer should review NEC cabling
requirements as well as local practice to ensure proper cable sizing is achieved for the local conditions.
Lugs for 6AWG conductor are as follows or available equivalent:
T&B 6STR30W
Burndy YAV6C-L2TC14-FX
Figure 6 Making DC Connections to Converter Shelf
CC848779826 r09 December 2013 17
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Run and connect the framework ground lead as shown.
2.
Use 6GA conductor minimum and connect to the safety grounding point
3.
Torque connections to 4 Nm or 35 in-lbs.
Step
Action
1.
The wiring assignment information in the following table provides the appropriate
terminate the J1 and J2 output connectors on the CPS3200U Shelf.
J2, 9-16
J1, 1-8
Ground the Shelf
The next step is to ground the shelf to earth ground. This is an important safety step since each converter relies on this
connection for proper ground fault detection.
(frame ground, or main ground bar) per local practice. Additionally apply
NO-OX ID to all bare metal connections if required by local practice. Lugs
are ¼ inch studs on 5/8 inch centers.
Lugs for 6AWG conductor are as follows or available equivalent:
T&B 6STR30W
Burndy YAV6C-L2TC14-FX
Attach the Load Wiring
Provide a circuit from each converter into the designated network telephone pairs. Follow the steps in the table below
to attach load wiring to the CPS3200U shelf.
connections for each circuit. A cable should be provided with this pinout configuration to
Figure 7 Grounding Converter Shelf
• Wireset Connector: RJ-21 type 50 pin plug:
• 22 AWG solid or stranded AMP 552173-1 or equivalent.
• 24 AWG solid or stranded or 26 AWG solid AMP 229974-1 or equivalent.
• The connector shall be arranged with a right angle housing such that the cable exits to the pin 1 side.
CC848779826 r09 December 2013 18
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 3 Output Connector Pinout
Connector for Circuits 1-8 (Shelf J1)
Connector for Circuits 9-16 (Shelf J2)
Conv Out
Pos
Color
Conv Out
Pos
Color
Conv Out
Pos
Color
Conv Out
Pos
Color
1a-
1
BL / W 1a+
26
W / BL 9a-
1
BL / W 9a+
26
W / BL
1b-
2
O / W 1b+
27
W / O 9b-
2
O / W 9b+
27
W / O
2a-
3
G / W 2a+
28
W / G 10a-
3
G / W 10a+
28
W / G
2b-
4
BR / W 2b+
29
W / BR 10b-
4
BR / W 10b+
29
W / BR
3a-
5
SL / W 3a+
30
W / SL 11a-
5
SL / W 11a+
30
W / SL
3b-
6
BL / R 3b+
31
R / BL 11b-
6
BL / R 11b+
31
R / BL
4a-
7
O / R 4a+
32
R / O 12a-
7
O / R 12a+
32
R / O
4b-
8
G / R 4b+
33
R / G 12b-
8
G / R 12b+
33
R / G
5a-
9
BR / R 5a+
34
R / BR 13a-
9
BR / R 13a+
34
R / BR
5b-
10
SL / R 5b+
35
R / SL 13b-
10
SL / R 13b+
35
R / SL
6a-
11
BL / BK 6a+
36
BK / BL 14a-
11
BL / BK 14a+
36
BK / BL
6b-
12
O / BK 6b+
37
BK / O 14b-
12
O / BK 14b+
37
BK / O
7a-
13
G / BK 7a+
38
BK / G 15a-
13
G / BK 15a+
38
BK / G
7b-
14
BR / BK 7b+
39
BK / BR 15b-
14
BR / BK 15b+
39
BK / BR
8a-
15
SL / BK 8a+
40
BK / SL 16a-
15
SL / BK 16a+
40
BK / SL
8b-
16
BL / Y 8b+
41
Y / BL 16b-
16
BL / Y 16b+
41
Y / BL
spare
17
O / Y spare
42
Y / O spare
17
O / Y spare
42
Y / O
spare
18
G / Y spare
43
Y / G spare
18
G / Y spare
43
Y / G
spare
19
BR / Y spare
44
Y / BR spare
19
BR / Y spare
44
Y / BR
spare
20
SL / Y spare
45
Y / SL spare
20
SL / Y spare
45
Y / SL
spare
21
BL / V spare
46
V / BL spare
21
BL / V spare
46
V / BL
spare
22
O / V spare
47
V / O spare
22
O / V spare
47
V / O
spare
23
G / V spare
48
V / G spare
23
G / V spare
48
V / G
spare
24
BR / V spare
49
V / BR spare
24
BR / V spare
49
V / BR
*FR GRD
25
SL / V *FR GRD
50
V / SL *FR GRD
25
SL / V *FR GRD
50
V / SL
Step
Action
2.
Mark or tag the 25 pair cables on the unterminated end with J1 and J2 to
differentiate the two cables at the splice chamber.
3.
Run the cable down the frame and attach as shown.
4.
Use Screw and Cable tie to secure.
*EMI performance is enhanced when the output cable shield is grounded only at the CPS3200 end of the shield.
Attach output cabling as shown
Figure 8 Output Wiring for Converter Shelves
CC848779826 r09 December 2013 19
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Open the distribution door.
2.
Remove the alarm card.
Note: Door must be level to
Set Shelf ID and Attach Alarm Wiring
For systems where alarming is processed through a central controller using serial communications, each shelf must
have a unique address. Otherwise all alarm cards should be left in their factory default state of address 0, 0. Skip this
step if no QS941 will be present in the system.
Warning: You must properly protect yourself against ESD discharge prior to accessing the alarm card and setting shelf
IDs.
Figure 9 Accessing Alarm Cards
CC848779826 r09 December 2013 20
remove alarm card
Figure 10 Removing Alarm Card
CPS3200U Upstream System – 23” Product Manual CPS3200U
3.
Use a Phillips Head screw driver to set the shelf address rotary switch to indicate a shelf
4.
If local contact closures are also desired continue with Attach Alarm Wiring, otherwise
reinstall alarm card and close door.
5.
Attach signal wiring between the Alarm Cards of adjacent Converter Shelves.
Included Communication Wiresets
Converter Shelf
ID. For most applications the only switch requiring adjustment will be on the far right
labeled ‘Units.’ Start with shelf 1 at the bottom and progress to higher numbers as one
goes up the frame. This figure shows settings for shelf 1 and shelf 6 as examples.
Figure 11 Setting Shelf ID
Doors not shown
Figure 12 Signal Wiring between Converter Shelves
CC848779826 r09 December 2013 21
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Install the baffle using as many fasteners as the frame will accept as shown:
Step
Action
1.
Install the Fan Shelf using as many fasteners as the frame will accept:
Installing the Baffle
Purpose: Redirect air coming into, and objects falling down toward, the FTTN shelf. Follow the steps in the table below to
attach a baffle above the FTTN shelves for all CO or customer premise applications. The baffle has two purposes: 1)
redirect air toward the back isle so that components located below the FTTN shelves will not over heat, and 2) Keep
objects from falling into the FTTN shelf. The baffle can either be fixed at a height above the Fan Shelf to allow for three
CPS3200U Shelves or be removed and reattached every time a CPS3200U shelf is added.
Note: There are two to airflow options provided for different applications: Airflow direction optimized for CO
deployments provided by the FTTN fan shelf is downward. Airflow direction for OSP applications is bottom to top. Baffles
should be oriented to direct cold air from the aisle through the converter shelf and out the back of the rack. A filter is
available and should be utilized in high contaminant areas with proper filter maintenance.
Figure 13 Installing a Baffle
Installing the Fan Shelf
CPS2300U shelves require external forced air. Follow the steps to install a fan shelf below each set of 3 CPS3200U
shelves.
Figure 14 Mounting the Fan Shelf
CC848779826 r09 December 2013 22
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
2.
Insert two fan trays operating the latches as shown:
3.
Remove the clear plastic cover from the wiring area:
Figure 15 Inserting Fan Trays
Figure 16 Open the Wiring Region of the Fan Shelf
CC848779826 r09 December 2013 23
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
3.
Attach signal wiring from the fan shelf to the alarm card in the converter shelf immediately
4.
Attach de-energized DC cabling (typically 14 AWG) as shown here. Use ring lugs or alternate
Included Communication Wireset
Converter Shelf
Fan Shelf
above the fan shelf.
(Door removed
for visibility)
Figure 17 Alarm Wiring for Fan Shelf
per local practice. Fuse externally at 5 Amps. Note: Returns for the A and B feeds are shared
on the -48Vdc RTN. The lowest position on the terminal block is to provide frame ground for
the fan shelf. Power feeds should be derived from a fuse or breaker panel using discrete
cabling which is independent from the converter shelf.
CC848779826 r09 December 2013 24
Figure 18 DC Cabling Fan Trays in CPS3200U Systems
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
5.
Replace the clear plastic (Lexan) cover and apply DC power.
6.
Check LED Display on each fan tray for proper operation.
7.
Resolve Alarm states by first assuring that DC power is being provided to both the A and the B
terminals on the shelf or Bay and then by replacing fan trays until the alarm clears.
Figure 19 Cover the Wiring Region of the Fan Shelf
Figure 20 Fan Tray LEDs
CC848779826 r09 December 2013 25
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Install the Filter Bracket directly below the fan shelf as shown.
2.
Loosen the filter retention screw and rotate retention bracket down.
Figure 22 Filter Retention Bracket
Retention Bracket
Installing the Filter Bracket and Filter
CPS3200U system has optional filters to provide a degree of protection from airborne particulate matter. Follow the
steps to install a filter bracket adjacent to the fan shelf. The example shown is for a separate filter bracket for bottom to
top airflow solutions. Top to bottom airflow applications require the filter to be above the system.
Figure 21 Mounting the Filter Bracket
CC848779826 r09 December 2013 26
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
3.
Slide the filter in to the filter bracket.
Figure 23 Install Filter
4.
Rotate retention bracket back into place and tighten screw.
Figure 24 Secure Filter Retention Bracket
Filter
Retention Bracket
CC848779826 r09 December 2013 27
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Is accessibility to the circuit throughout the network consistent with A2 requirements?
2.
Is the 5-pin protector marked as a special circuit?
3.
Does the 5-pin protector protect each pair to a level corresponding to a CommScope
lower voltage breakdown rating will be problematic.
Step
Action
1.
Recognize that the Remote Feed Telecommunication Voltage limited (RFT-V) circuit is
voltage limited to +190V and -190V from ground.
2.
Is the total capacitance to ground on each line of the circuit less than 10μF?
5.6 μF of capacitance.
3.
Is the total capacitance line to line of the circuit less than 40μF?
37.2 μF of capacitance from tip to ring.
4.
Is the remote equipment also a RFT-V voltage limited circuit? Both ends of the circuit
connected together.
5.
Is the voltage rating of the Network Wiring sufficient to support 190V to ground?
6.
Is the chassis of the system bonded to ground? Verify by both observation and
Many network providers use a value of 10 ohms.
7.
Test each circuit by powering an open circuit at the remote end of the wire with a QS982
If the FLT light does not blink yellow, there is no hard short between tip and ring.
7 Inspect the Network - Check and Mark Wiring
Compliance
The CPS3200U +/-190V system is classified as an A2 circuit tested according to GR-1089-CORE Issue 3. As such, each
location in the network where the output is available to be touched must be protected and marked as an A2 voltage.
3C*EW Gas tube primary protector? This protector has a voltage breakdown range of
265-465 Volts and an impulse spark over range of <265-700 Volts. Protectors with a
To meet UL60950-21 specific procedural steps must be taken at the time of installation. This section goes through those
steps. These steps should be performed before power is distributed in the network. Normally the final step is performed
by closing the circuit using a 5-pin protector after DC power is applied to the system.
The QS982A introduces 4.4μF. The remote electronics and line must introduce less than
The QS982A introduces 2.2μF. The remote electronics and line must introduce less than
must be designed to the same standard. This must be verified before the equipment is
measurement before powering the system. Measurement from the exterior of the
CPS3200U shelf to the cabinet ground bus should indicate continuity as determined via a
meter providing an audible beep or the standard method of continuity verification used in
the network.
output. If red lights do not flash, there is no leakage path to ground at operating voltage.
CC848779826 r09 December 2013 28
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Warning: You must properly protect yourself against ESD discharge prior to installing the
QS982A Controller.
2.
Use the ESD jack on the left of each converter shelf to provide grounding before removing
3.
Remove the QS982A converter from its shipping container.
4.
Align the plastic converter housing on the right and insulated circuit board on the left.
5.
Guide the converter into the first available slot by positioning the plastic converter
6.
Slide the converter into the shelf until it is fully seated in the connector on the rear of the
CPS3200U shelf.
7.
Push the display faceplate into the shelf until the latch on the top of the converter
housing catches.
8.
Repeat this process as needed for your application.
9.
Insert empty slot fillers into all unused slots to control airflow in multi-shelf systems
ESD Jack
8 Final Installation
Installing the Converters
QS982A Converters mount in the CPS3200U shelf. Note that Converter Card numbering starts from the left and should
be correlated to the marking on the panel located on the other end of the load cable that plugs into J1 and J2. This may
be a cross connect panel or the 5-pin protector block near the building entrance.
the QS982A converters from their anti-static wrap:
Figure 25 Shelf Level ESD Jack
housing in the notch on the top right edge of the opening.
Figure 26 Installing Converters
CC848779826 r09 December 2013 29
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Observe the LEDs.
2.
Use the state table below to determine the state of the system and required corrective actions
if needed.
Apply DC Power
Apply DC power by turning on input fuses or circuit breakers. Power the fan shelf and the converter shelf
simultaneously. The system will operate from voltages between -40 and -60 volts with normal status at feed voltages
between -52 Volts and -54.5 Volts.
Fault LEDs will flash red until communications is established between the alarm card and each converter. The alarm
card will flash its fault LED until connection is confirmed to the QS941, if present. If no QS941 is present the alarm cards
will flash their red LED until they are set to address 0, 0 as described in the Set Shelf ID and Attach Alarm Wiring
section.
Complete UL 60950-21 step 7 under Inspect the Network to test each circuit after DC power is applied.
Recognizing Normal States
Once power is provided to the CPS3200U system the LEDs on the converters will illuminate. Understanding what the
LEDs mean allows one to recognize normal states and diagnose abnormal states.
Figure 27 QS982A Faceplate and LEDs
(Note: Test points work best if each voltage is measured with respect to ground)
CC848779826 r09 December 2013 30
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 4 QS982A LED Information Map
LED Display
Conditions
(on b circuit)
Action Required
All OK
None
Circuit Placed in Standby
None depending on desired
Loss of comm.
Check seating on Alarm card
Ground fault
Check 5 pin protectors and
Overcurrent or under
Check output lines for shorts to
OV or internal failure
Replace unit
Thermal Alarm
Solve Thermal problem
card not powered or input
Check source voltage
Lamps test requested from
Observe Lamp Test
QS982A LED Information Map
Examples in the table are shown for conditions on the b circuit of the QS982A card. The same reasoning applies when
the "a" circuit LEDs are illuminated.
state of circuit b. Standby state
can be set using the QS941
controller or web browser.
and converter card
voltage
fuse failure
faults to ground
each other
CC848779826 r09 December 2013 31
controller
CPS3200U Upstream System – 23” Product Manual CPS3200U
Figure 28 Fan Shelf Right Hand Cover
Figure 29 Fan Shelf Controller Jumper
Confirm Operation of Alarm Wiring
After the converters are recognized to be in a normal state, one should confirm the proper operation of the alarm
contact closures. If alarm wiring is correct:
1. The loss of A or B input power should result in the assertion of a Power Minor.
2. The loss of both A and B input power, which will result in a loss of service, should result in a Power Major and a
Power Minor.
3. If a controller is installed in the system then it will demonstrate an alarm state by turning the display red. Using
the buttons on the keypad the specific alarm can be retrieved by pressing the Back Arrow,. When the system
returns to normal function the display will be green.
Installing the QS941A Ethernet Module
To connect CPS2300U shelves to an IP Drop, follow these steps to install QS941A Ethernet module.
Step Action
1. Remove the cover from the right hand end of the fan shelf that will house the controller.
2. Move the controller jumper on the selected fan shelf into the leftmost position.
Warning: Controller may be damaged if this step is not
completed.
3. Replace the cover over the right hand end of the shelf.
CC848779826 r09 December 2013 32
CPS3200U Upstream System – 23” Product Manual CPS3200U
Figure 30 Preparing a Fan Shelf for a CPS Controller
Figure 31 Installing the Controller
Step Action
4. Remove the faceplate on the left end of the fan shelf:
5. Install the controller into the fan shelf:
CC848779826 r09 December 2013 33
CPS3200U Upstream System – 23” Product Manual CPS3200U
Figure 32 Controller Wiring
Step Action
6. Attach signal wiring to the controller at connector P6. The Ethernet connection to the local
network is made through the P6 RJ45 connector. Of the two RJ45s on the left side of the
controller, P6 is the one more toward the front labeled: P6 10/100 Base-T. Plug the local
network cable into P6. As shown here:
7. To check the network connection, use the controller display to determine what IP address has
been assigned to the QS941 controller. Press the square key,
of the keypad to display the menu.
■, on the upper right hand corner
8. Press the down arrow key, ▼, 2 times to scroll down to the “Status” item on the menu.
9.
Press the right arrow,
10. Press the down arrow key, ▼, 8 times to scroll down to the “Network Settings” item and select
by pressing the right arrow key.
11. Press the right arrow, ▼, to advance to the “Network Settings” menu.
12.
13. Read and record the network address for Port 1.
Press the right arrow,
When an IP address is listed connection to the server is confirmed.
, to advance to the “Status” menu.
, to select Port 1. The P6 connector is Port 1.
CC848779826 r09 December 2013 34
CPS3200U Upstream System – 23” Product Manual CPS3200U
14.
Check the other end of the fan shelf to make sure the serial bus reaches all of the shelves in the
to Shelf above, if present
to Shelf below, if present
Step Action
system. RS-485 signals are Daisy Chained from all the elements in the system. The signal from
equipment located in the frame above the controller typically comes through the RJ45 jack on
the left. The jack shown here on the right will typically accept information from equipment
mounted below the fan shelf containing the controller:
Figure 33 Fan Shelf RS-485 Jacks
CC848779826 r09 December 2013 35
Figure 34 Signal Cables - System
CPS3200U Upstream System – 23” Product Manual CPS3200U
Figure 35 Office Alarm Cable Pinout
CC848773671
10ft alarm cable - for QS941 controllers
848748558
25ft alarm cable - for QS941 controllers
CC848764448
50ft alarm cable - for QS941 controllers
848748566
150ft alarm cable - for QS941 controllers
Installing the Office Alarm Connector
Step Action
1. Plug appropriate length alarm cable into the socket on the side of the controller labeled J1.
Alarm cable options listed below.
2. Dress Cable out to alarm block and use the pinout below to appropriately route the alarms.
3. Available alarm cables are as follows:
CC848779826 r09 December 2013 36
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 5 QS982A Converter LED Information Map
Action Required
OK LED
Fault LED
Conditions
Notes
None
Green
Off
All OK
Verify circuit
Off
Yellow
Standby
Standby can be set using the QS941
web browser.
Check seating on
converter card
Green
Blink Red On ½ second,
Loss of comm.
Check 5 pin
to ground
Red Blink
Red Blink
Ground fault
Check output lines for
shorts to each other
Green
Yellow Blink
Overcurrent or under
voltage
Replace unit
Red Blink
Off
OV or internal failure
Solve Thermal
problem
Off
Red Blink
Thermal Alarm
Latch off after 3 retry cycles
Check source voltage
Off
Off
card not powered or
input fuse failure
Observe Lamp Test
Bi-Color: 4.5 seconds
1 second off
Bi-Color: 4.5 seconds
1 second off
Lamps test requested
9 Reference Information
Overview
This section contains additional information (connector pin designations, etc.) that may be required for making,
customizing, or troubleshooting system connections.
QS982A Converter LED Information Map
configuration
Alarm card and
protectors and faults
Figure 36 QS982 LEDs and Test Points
on, 4.5 seconds on and
Off ¼ second
on, 4.5 seconds on and
controller display or remotely using a
from controller
CC848779826 r09 December 2013 37
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 6 QS982A Converter LED Information Map (visual)
LED Display
Conditions
(on b circuit)
Action Required
All OK
None
Circuit Placed in Standby
None depending on desired state of circuit b. Standby
Loss of comm.
Check seating on Alarm card and converter card
Ground fault
Check 5 pin protectors and faults to ground
Overcurrent or under
Check output lines for shorts to each other
OV or internal failure
Replace unit
Thermal Alarm
Solve Thermal problem
card not powered or input
Check source voltage
Lamps test requested from
Observe Lamp Test
QS982A LED Information Map (visual)
Examples in the table are shown for conditions on the b circuit of the QS982A card. The same reasoning applies when
the “a” circuit LEDs are illuminated.
state can be set using the QS941 controller or web
browser.
voltage
fuse failure
controller
CC848779826 r09 December 2013 38
CPS3200U Upstream System – 23” Product Manual CPS3200U
Alarm Card Information
The alarm card faceplate looks one of these depending on whether you have a front access system (on the left) or a
rear access system (on the right):
Figure 37 Alarm Card Faceplate
Figure 38 Shelf ID Rotary Switches
CC848779826 r09 December 2013 39
CPS3200U Upstream System – 23” Product Manual CPS3200U
QS912A Converter Shelf
Figure 39 QS912A Dimensions
CC848779826 r09 December 2013 40
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 7 Output Connector Pinout
Connector for Circuits 1-8 (Shelf J1)
Connector for Circuits 9-16 (Shelf J2)
Conv Out
Pos
Color
Conv Out
Pos
Color
Conv Out
Pos
Color
Conv Out
Pos
Color
1a-
1
BL / W 1a+
26
W / BL 9a-
1
BL / W 9a+
26
W / BL
1b-
2
O / W 1b+
27
W / O 9b-
2
O / W 9b+
27
W / O
2a-
3
G / W 2a+
28
W / G 10a-
3
G / W 10a+
28
W / G
2b-
4
BR / W 2b+
29
W / BR 10b-
4
BR / W 10b+
29
W / BR
3a-
5
SL / W 3a+
30
W / SL 11a-
5
SL / W 11a+
30
W / SL
3b-
6
BL / R 3b+
31
R / BL 11b-
6
BL / R 11b+
31
R / BL
4a-
7
O / R 4a+
32
R / O 12a-
7
O / R 12a+
32
R / O
4b-
8
G / R 4b+
33
R / G 12b-
8
G / R 12b+
33
R / G
5a-
9
BR / R 5a+
34
R / BR 13a-
9
BR / R 13a+
34
R / BR
5b-
10
SL / R 5b+
35
R / SL 13b-
10
SL / R 13b+
35
R / SL
6a-
11
BL / BK 6a+
36
BK / BL 14a-
11
BL / BK 14a+
36
BK / BL
6b-
12
O / BK 6b+
37
BK / O 14b-
12
O / BK 14b+
37
BK / O
7a-
13
G / BK 7a+
38
BK / G 15a-
13
G / BK 15a+
38
BK / G
7b-
14
BR / BK 7b+
39
BK / BR 15b-
14
BR / BK 15b+
39
BK / BR
8a-
15
SL / BK 8a+
40
BK / SL 16a-
15
SL / BK 16a+
40
BK / SL
8b-
16
BL / Y 8b+
41
Y / BL 16b-
16
BL / Y 16b+
41
Y / BL
spare
17
O / Y spare
42
Y / O spare
17
O / Y spare
42
Y / O
spare
18
G / Y spare
43
Y / G spare
18
G / Y spare
43
Y / G
spare
19
BR / Y spare
44
Y / BR spare
19
BR / Y spare
44
Y / BR
spare
20
SL / Y spare
45
Y / SL spare
20
SL / Y spare
45
Y / SL
spare
21
BL / V spare
46
V / BL spare
21
BL / V spare
46
V / BL
spare
22
O / V spare
47
V / O spare
22
O / V spare
47
V / O
spare
23
G / V spare
48
V / G spare
23
G / V spare
48
V / G
spare
24
BR / V spare
49
V / BR spare
24
BR / V spare
49
V / BR
*FR GRD
25
SL / V *FR GRD
50
V / SL *FR GRD
25
SL / V *FR GRD
50
V / SL
Figure 40 Output Connectors
Wireset Connector: RJ-21 type 50 pin plug:
• 22 AWG solid or stranded AMP 552173-1 or equivalent.
• 24 AWG solid or stranded or 26 AWG solid AMP 229974-1 or equivalent.
• The connector shall be arranged with a right angle housing such that the cable exits to the pin 1 side.
*EMI performance is enhanced when the output cable shield is grounded only at the CPS3200 end of the shield.
CC848779826 r09 December 2013 41
CPS3200U Upstream System – 23” Product Manual CPS3200U
QS930A Fan Shelf
Figure 41 QS930 Fan Shelf Dimensions
Figure 42 QS930 Fan Shelf Connections and Fuses
Note: Returns for A and B feeds are shared on the -48Vdc RTN terminal.
The lowest position on the terminal block is frame ground.
CC848779826 r09 December 2013 42
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Remove the Filter from the Filter Bracket.
2.
Wash the filter in soap and water.
3.
Dry the filter completely.
4.
Replace the Filter in the Filter Bracket.
5.
Repeat from Step 1 for each Filter in the system.
10 Maintenance
Filter Cleaning
Clean Filters on the schedule specified by the telco customer site specific instructions or practices.
See the Installing the Filter Bracket and Filter section for Filter removal and replacement detail.
CC848779826 r09 December 2013 43
CPS3200U Upstream System – 23” Product Manual CPS3200U
Product Type
New Product
Repaired Product*
Central Office Power
Equipment**
* The Warranty Period for a repaired Product or part thereof is six (6) months or, the remainder of
the unexpired term of the new Product Warranty Period, whichever is longer.
11 Product Warranty
A. Seller warrants to Customer only, that:
1 As of the date title to Products passes, Seller will have the right to sell, transfer, and assign such Products
and the title conveyed by Seller shall be good;
2 During the warranty period stated in Sub-Article B below, Seller’s Manufactured Products (products
manufactured by Seller), which have been paid for by Customer, will conform to industry standards and
Seller’s specifications and shall be free from material defects;
3 With respect to Vendor items (items not manufactured by Seller), Seller warrants that such Vendor items,
which have been paid for by Customer, will be free from material defects for a period of sixty (60) days
commencing from the date of shipment from Seller’s facility.
B. The Warranty Period listed below is applicable to Seller’s Manufactured Products furnished pursuant to this
Agreement, commencing from date of shipment from Seller’s facility, unless otherwise agreed to in writing:
Warranty Period
24 Months 6 Months
C. If, under normal and proper use during the applicable Warranty Period, a defect or nonconformity is identified in
a Product and Customer notifies Seller in writing of such defect or nonconformity promptly after Customer
discovers such defect or nonconformity, and follows Seller's instructions regarding return of defective or
nonconforming Products, Seller shall, at its option attempt first to repair or replace such Product without charge
at its facility or, if not feasible, provide a refund or credit based on the original purchase price and installation
charges if installed by Seller. Where Seller has elected to repair a Seller’s Manufactured Product (other than
Cable and Wire Products) which has been installed by Seller and Seller ascertains that the Product is not readily
returnable for repair, Seller will repair the Product at Customer’s site.
With respect to Cable and Wire Products manufactured by Seller which Seller elects to repair but which are not
readily returnable for repair, whether or not installed by Seller, Seller at its option, may repair the cable and Wire
Products at Customer’s site.
D. If Seller has elected to repair or replace a defective Product, Customer shall have the option of removing and
reinstalling or having Seller remove and reinstall the defective or nonconforming Product. The cost of the
removal and the reinstallation shall be borne by Customer. With respect to Cable and Wire Products, Customer
has the further responsibility, at its expense, to make the Cable and Wire Products accessible for repair or
replacement and to restore the site. Products returned for repair or replacement will be accepted by Seller only
in accordance with its instructions and procedures for such returns. The transportation expense associated with
returning such Product to Seller shall be borne by Customer. Seller shall pay the cost of transportation of the
repaired or replacing Product to the destination designated by Customer.
E. Except for batteries, the defective or nonconforming Products or parts which are replaced shall become Seller's
property. Customer shall be solely responsible for the disposition of any batteries.
F. If Seller determines that a Product for which warranty service is claimed is not defective or nonconforming,
Customer shall pay Seller all costs of handling, inspecting, testing, and transportation and, if applicable, traveling
and related expenses.
CC848779826 r09 December 2013 44
CPS3200U Upstream System – 23” Product Manual CPS3200U
G. Seller makes no warranty with respect to defective conditions or nonconformities resulting from actions of
anyone other than Seller or its subcontractors, caused by any of the following: modifications, misuse, neglect,
accident, or abuse; improper wiring, repairing, splicing, alteration, installation, storage, or maintenance; use in a
manner not in accordance with Seller’s or Vendor’s specifications or operating instructions, or failure of
Customer to apply previously applicable Seller modifications and corrections. In addition, Seller makes no
warranty with respect to Products which have had their serial numbers or month and year of manufacture
removed, altered, or experimental products or prototypes or with respect to expendable items, including,
without limitation, fuses, light bulbs, motor brushes, and the like. Seller’s warranty does not extend to any system
into which the Product is incorporated. This warranty applies to Customer only and may not be assigned or
extended by Customer to any of its customers or other users of the Product.
THE FOREGOING WARRANTIES ARE EXCLUSIVE AND ARE IN LIEU OF ALL OTHER EXPRESS AND IMPLIED WARRANTIES,
INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
CUSTOMER’S SOLE AND EXCLUSIVE REMEDY SHALL BE SELLER’S OBLIGATION TO REPAIR, REPLACE, CREDIT, OR
REFUND AS SET FORTH ABOVE IN THIS WARRANTY.
CC848779826 r09 December 2013 45
CPS3200U Upstream System – 23” Product Manual CPS3200U
Appendix A: Operating Temperature
Measurement and Vertical Spacing
Overview
The CPS3200U has been designed for mounting in relay racks or in equipment cabinets. It is designed for use with user
provided vertical airflow cooling of at least 175 linear feet per minute over the entire flow cross-section of the shelf.
Equipment may be placed on top of the CPS3200U provided airflow is not impeded or sufficient spacing is provided. A
1U Baffle is required above the highest converter shelf; this baffle provides sufficient vertical spacing. Direct the airflow
into a 3 inch minimum space. If the spacing is less than 3 inch spacing application specific testing is required.
Operating Temperature
The CPS3200U is rated to work to 65 C in stacks of two shelves in outdoor cabinets without baffles. Note: in outdoor
cabinets where the air entering the second shelf may be heated above 65C inlet temperature, additional airflow beyond
the 175 linear feet per minute is required. These cases require an engineered solution.
In Central Office environments when baffles are required for safety reasons, a three shelf system is rated to operate in
55C environments.
Baffles and Fan Trays
For Central Office applications, baffles are used between every set of three Converter shelves. Fan Shelves are required
for every set of three Converter shelves. No more than 6 shelves may be located in a particular frame. Slot covers must
be used on all empty slots when more than one shelf is being cooled by a particular airflow device.
Always mount converter shelves above the fan tray that cools them.
When mounting fan trays with converter shelves, leave no space between the top of a fan tray and the converter shelf
above it. The QS930A Fan Shelf draws air down through whatever equipment is located directly above it. If a gap is left
above a fan tray, air will be drawn into the fan tray from the aisles rather than from the converter shelf above the fan
tray. This will result in service effecting problems due to insufficient cooling air flowing through the active converters.
The QS931A Fan Shelf forces air up through whatever equipment is located directly above it. If a gap is left above a fan
tray, air will escape into the aisles rather than flowing into the converter shelf above the fan tray. This will result in
service effecting problems due to insufficient cooling air flowing through the active converters.
When mounting converter shelves always mount a converter shelf immediately above a fan shelf, or above a converter
shelf stacked on a fan shelf. Any gaps between converter shelves, or absence of slot covers, can cause service effecting
problems.
Note: All unpopulated converter slots must be filled with slot fillers. For example the figure below shows a shelf with
operational converters in the first two slots and slot fillers in the remaining 14 slots:
Figure 43 Converter Shelf with Slot Fillers
CC848779826 r09 December 2013 46
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 8 Alarm Reference
QS941
Alarm Card
Converter Card
Alarm Display
What it means
LED
Relay
Alarm
State
Relay
OK
State
Alarm
State
Corrective Action
Circuit Fail
Short + to -
Yellow
Min
Yellow
Min
Green
Flashing
Make sure each
send and return path.
Circuit Fail
Short to Ground
Yellow
Min
Yellow
Min
Flashing
Flashing
Make sure each
send and return path.
Communication
1 Card Removed
Yellow
Min
Yellow
Min
Green
Off
Check to see that all
functioning cards.
Communication
2 Cards
Red
Maj
Check to see that all
functioning cards.
Communication
Communication
Red
Maj
Flashing
Green
Off
Check communication
Communication
Fail
Alarm Card
Removed
Red
Maj
Green
Flashing
Red
Replace Alarm card.
None
Standby
Green
Green
Yellow
Remove unit from
Ethernet interface
Circuit Fail
Open Fuse
Yellow
Min
Yellow
Min
Green
Flashing
Replace unit. Note:
card.
Circuit Fail
Under Voltage
Yellow
Min
Yellow
Min Flashing
Replace unit. Note:
card.
Fan Fail
1 Fan Tray Failed
Yellow
Min
Yellow
Min
Green
Off
Replace fan tray.
Fan Fail
1 of 6 fans Failed
on one Fan Tray
Yellow
Min
Yellow
Min
Green
Off
Replace fan tray.
Fan Fail
2 Fan Trays
Failed
Red
Maj
Red
Maj
Green
Off
Replace fan trays.
Input Power
A1-8 Power Fail
Yellow
Min
A Red
Min
Green
Off
Reconnect DC input
Appendix B: Alarm Reference Table
This Alarm Table shows how FTTN Alarms are categorized by the QS941 Controller. Details of non-FTTN Alarms can be
found in the Plant Level product manuals. Many alarms are best processed at the converter shelf alarm card and
converter card level.
Fail
Fail
Fail
Removed
Cable Removed
State
State
Red
LED
State
LED
Red
LED
Yellow
Red
converter has an
independent isolated
converter has an
independent isolated
cards are seated.
Replace non-
cards are seated.
Replace non-
path from alarm cards
to QS941 controller. If
no controller is
present, set alarm
card rotary switch to
position 0 for contact
closures only
communication.
CC848779826 r09 December 2013 47
Yellow
Yellow
standby if desired
using QS941 or
Restoring service to
one line will interrupt
service to the other
line served by that
Restoring service to
one line will interrupt
service to the other
line served by that
power flowing to the
A1-8 input terminal.
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 8 Alarm Reference
QS941
Alarm Card
Converter Card
Alarm Display
What it means
LED
Relay
Alarm
State
Relay
OK
State
Alarm
State
Corrective Action
Input Power
B1-8 Power Fail
Yellow
Min
B Red
Min
Green
Off
Reconnect DC input
B1-8 input terminal
Input Power
A9-16 Power Fail
Yellow
Min
A Red
Min
Green
Off
Reconnect DC input
A9-16 input terminal
Input Power
B9-16 Power Fail
Yellow
Min
B Red
Min
Green
Off
Reconnect DC input
B9-16 input terminal.
Input Power
A1-8 & B1-8
Red
Maj
A Red
Maj
Green
Off
Reconnect DC input
terminal
Input Power
A9-16 & B9-16
Red
Maj
A Red
Maj
Green
Off
Reconnect DC input
B9-16 input terminal.
Load Drop
Load Drop
Yellow
Min
A, B &
Green
Off
Check the integrity of
feature.
Load Share
As set of circuits
be expected
Yellow
Min
A, B &
Green
Off
Check the integrity of
Line Test
OK, Fail or
A, B &
Green
Off
Estimated line
measurement.
Loss Of
Yellow
Min
A, B &
Green
Off
The loss of n additional
in the configuration.
Mul Circuit Fail
Mul Circuit Fail
Power Fail
Power Fail
State
State
LED
B Red
B Red
OK
Green
State
LED
LED
power flowing to the
power flowing to the
power flowing to the
power flowing to the
A1-8 input terminal
and Reconnect DC
input power flowing to
the B1-8 input
power flowing to the
A9-16 input terminal.
Reconnect DC input
power flowing to the
the circuits going to
the load. Or Adjust
load drop threshold to
0 to disable this
Redundancy
assigned to one
remote
destination are
not sharing
current as would
Aborted
OK
Green
OK
Green
OK
Green
the circuits going to
the load. Or Adjust
load share threshold
to disable this feature.
resistance has
increased since last
circuits will cause
customers to lose
service. Check
redundancy threshold
CC848779826 r09 December 2013 48
CPS3200U Upstream System – 23” Product Manual CPS3200U
Step
Action
1.
Attach the required alarm leads to the office alarm screw terminals (TB1 on the alarm card) as
2.
Set Shelf ID to address 0, 0 - Figure 44.
3.
Reinstall Alarm card and close distribution door.
Office Alarm Cables
Shelf ID Switches
Appendix C: Operation without a Controller Alarm Wiring
Each CPS3200U Shelf Provides Alarm contact closures for Power Major and Power Minor for operation without a
controller. Wire these relays into the alarm network in deployments where a controller is not utilized. If a controller is
installed then an alarm cable can be attached to the QS941A controller during final installation in section 8 under
“Installing the QS941A Ethernet Module”.
designated.
Figure 44 Alarm Card Office Alarm Pinout and Shelf ID
Figure 45 Alarm Card Office Alarm Cables
CC848779826 r09 December 2013 49
CPS3200U Upstream System – 23” Product Manual CPS3200U
Table 9 Shelf Alarm Card State
-48 V INPUT BUS
Vin LEDs
STATUS LEDs
ALARM RELAYs
A
1-8
B
1-8
A
9-16
B
9-16
A LED
B LED
OK LED
ALM LED
PMN
PMJ
OK
OK
OK
OK
GRN
GRN
GRN
OFF
E
E
LOW
OK
OK
OK
RED
GRN
OFF
YEL
D
E
OK
LOW
OK
OK
GRN
RED
OFF
YEL
D
E
OK
OK
LOW
OK
RED
GRN
OFF
YEL
D
E
OK
OK
OK
LOW
GRN
RED
OFF
YEL
D
E
LOW
LOW
OK
OK
RED
RED
OFF
RED
E D LOW
OK
LOW
OK
RED
GRN
OFF
RED
E
D
LOW
OK
OK
LOW
RED
RED
OFF
RED
E
D
OK
LOW
LOW
OK
RED
RED
OFF
RED
E
D
OK
LOW
OK
LOW
GRN
RED
OFF
RED
E
D
OK
OK
LOW
LOW
RED
RED
OFF
RED
E
D
LOW
LOW
LOW
OK
RED
RED
OFF
RED
E
D
LOW
LOW
OK
LOW
RED
RED
OFF
RED
E D LOW
OK
LOW
LOW
RED
RED
OFF
RED
E
D
OK
LOW
LOW
LOW
RED
RED
OFF
RED
E
D
LOW
LOW
LOW
LOW
OFF
OFF
OFF
OFF
D
D
CPS3200U Shelf Alarm Card State Table
This section shows Alarm and LED response for the Alarm Card LEDs and Relays.
The CPS3200U shelf contains a pair of A bus feeds and a pair of B bus feeds. The use of dual A and B feeds is to not
exceed the 48 AMPS L2 input current per feed. The A bus feeds are designated A
(left side) and 9-16 (right side) respectively. The B bus feeds are also designated in an identical fashion. The alarm card
monitors the -48v on each of these four feeds, and asserts alarms and indicators as follows:
and A
1-8
, and power shelf slots 1-8
9-16
Alarm Relay: E – Energized relay in non-alarm state; D – De-energized relay in alarm state
Alarm Card Logical Operation of LEDs and Alarm Relays
The Alarm Card contains a pair of form C relays to provide shelf PMN and PMJ isolated closures. The relays are
energized, from both the A & B input bus, in their non-alarmed state, such that these relays will revert to the alarm state
if both A and B input fail. The relay circuit interfaces to a pair of parallel buses connected to each of the 16
Converter/Limiter Cards. Each Converter has an open collector output on the bus, and pulls the bus low to chassis
ground when it is asserting an alarm. The PMN/PMJ circuit on the Alarm card recognizes the bus state change and
denergizes the relay. The alarm card separately monitors both the PNM and PMJ bus. When the PMN bus is active
(pulled low), the Alarm card asserts a PMN relay and lights the ALM LED Yellow. When the PMJ bus is active (pulled low),
the Alarm card asserts a PMJ relay and lights the ALM LED Red. While an active PMJ is present the Alarm Card ignores
the state of the PMN bus (and does not assert a PNM relay/LED action). This IS necessary since the same LED is used for
both Minor (Yellow) and Major (Red) visual indication.
The Alarm Card also monitors the -48V dc inputs and asserts PNM/PMJ for conditions as described in the earlier section
dealing with input voltage monitoring.
The Alarm Card also monitors the two fan tray alarms. When either of the two fan tray alarms is active, the Alarm Card
asserts a PMN relay and Yellow ALM LED. When both of the fan tray alarms are active, the Alarm Card shall assert a PMJ
relay and Red ALM LED.
2
The Alarm Card shall also monitor its internal I
constitute a PMN condition.
C to RS-485 conversion processor. A failure of this processor shall
CC848779826 r09 December 2013 50
CPS3200U Upstream System – 23” Product Manual CPS3200U
Revision History
Issue Comments
9 2013 December Corrected typos, restored Specification of Output Voltage, added weights for fan shelf and baffle,
updated figures showing converter shelf output side, updated figures showing baffle and filter holder installation,
and added section for Maintenance – Filter Cleaning.
8 2013 July Rebranding, minor reformatting, and minor updates.
7 2008 January Rebranding.
6 2007 December Clarifications: Page 5, added ‘converter shelf’ after GR487. Page 9, Dissipation clarifications. Page
10, Listed specific protector. Page 13, The return conductor of the -48V shall be terminated in the ground window,
(held at frame ground potential). Page 13, The telecommunication line cable, carrying the +/-190V between the
equipment and the primary protectors, shall be minimum 26 AWG, and rated minimum 200V. Page 13, Airflow must
be provided at a rate of 175 lfm across the entire cross section of the shelf for operation in environments up to 65 C,
when measured at the inlet of the warmest converter shelf. Page 13, For multi-shelf systems (up to 3), this equipment
has been evaluated for continuous use in ambient temperature from -40°C to 50°C when used with the QS982A
converters. Page 28, added: Otherwise all alarm cards should be left in their factory default state of address 0,0. Skip
this step if no QS941 will be present in the system. Page 28, added text and changed picture to show angle required
to remove alarm card. Page 38, Measurement from the exterior of the CPS3200U shelf to the cabinet or building
ground bus should indicate a resistance of less than 10 Ohms. Page 56, cleaned up some of the tense grammatical
errors.
Changes: Pages 7 and 9: L1 and 2 currents. Page 13, changed J1 to TB1. Page 49, Step 12 “J6” changed to “P6.”
Page 65, changed outdoor applications to 2 shelf system configurations between fan shelves. The operating
temperature section now reads:
The CPS3200U is rated to work to 65 C in stacks of two shelves in outdoor cabinets without baffles. Note: in outdoor
cabinets where the air entering the second shelf may be heated above 65C inlet temperature, additional airflow
beyond the 175 linear feet per minute is required. These cases require an engineered solution.
In Central Office environments when baffles are required for safety reasons, a three shelf system is rated to operate
in 55C environments.
5 2007 March References to multi-shelf configurations removed. Network inspection added.
4 2006 September Added transitional statements to improve flow. Added note on grounding practice for best EMI
performance to output connector pin out description. Added Ethernet present confirmation procedure.
3 2006 June Removed -190V items including rear access converter shelf. Clarified sections to support
downward airflow as standard configuration for fan tray. Corrected drawings.
2 Reformatted sections. Corrected shelf depth in reference information.
1 Draft with focus on installing Bulk fed shelves. Pictures added.
CC848779826 r09 December 2013 51
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.