GE Conversion Kits are designed for upgrading existing
GE low-voltage power circuit breakers, rather than
replacing the entire breaker. The Conversion Kits include
ProTrip™ Trip Units, the latest technological advance in
GE trip systems.
ProTrip Conversion Kits are designed and tested to
conform to ANSI Standard C37.59, allowing the retrofitter
to properly install the kit and acceptance test the breaker.
This publication covers installation of ProTrip Conversion
Kits on GE types AK-15, AK-25, and AKU-25 low-voltage
power circuit breakers. Each Conversion Kit contains all
the components needed to convert from an existing GE
trip system.
ProTrip™ Conversion Kits
For GE Types AK-15, AK-25, and AKU25
Low-Voltage Power Circuit Breakers
TABLE OF CONTENTS
SECTION 1. GENERAL INFORMATION............................................................................................................4
SECTION 2. BEFORE INSTALLATION..............................................................................................................4
SECTION 3. FRONT-FRAME CONVERSION
Separation of the Front and Back Frames..............................................................................................5
Removal of the Existing Trip Device.......................................................................................................6
Remounting the X and Y Relays.............................................................................................................7
Installing the Flux Shifter.........................................................................................................................8
Installing the Trip Unit Bracket and Trip Unit........................................................................................10
SECTION 4. BACK-FRAME CONVERSION
Current Sensor Installation ...................................................................................................................13
Nuisance Tripping on Ground Fault-Equipped Breakers.........................................................17
2
LIST OF FIGURES
1. Arc chute retainer and arc chutes. ...................................................................................................................5
2. Screw to be removed from connecting links. ................................................................................................... 5
3. Breaker bottom bracket connected to the escutcheon and the back frame.................................................... 6
4. Type EC-2A trip device, with adjacent device removed...................................................................................6
5. Front view of the front frame, showing relocation of the X and Y relays..........................................................7
6. Right side view of the front frame, showing relocation of the Y relay..............................................................8
7. Y relay installed on the arc chute retainer........................................................................................................8
8. Unassembled flux shifter and mounting hardware...........................................................................................8
9. New flux shifter installed on the right side of the breaker mechanism (shown in the
10. Mounting and adjusting the flux shifter shown from the right side of the mechanism. ....................................9
11. Flux shifter as isntalled on the breaker............................................................................................................ 9
12. Trip unit, mounting plate, support bracket, and harness................................................................................10
13. Trip unit support bracket mounted to the breaker frame on a manually operated stationary
15. Bottom view of the trip unit support bracket installed on an electrically operated breaker,
showing the X relay and insulator.................................................................................................................. 11
16. Trip unit attached to the mounting plate.........................................................................................................11
17. Trip unit and mounting plate attached to the breaker. ...................................................................................12
18. Flux shifter wiring harness in place................................................................................................................ 12
19. Components for the current sensor assembly for one pole...........................................................................13
20. Current sensor assembly, right-side view......................................................................................................13
21. CT terminal board bracket and insulator installed..........................................................................................13
23. Right-side view of the back frame, showing installation of the flux shifter actuator bushing.........................14
24. Modification of the lower stud shields............................................................................................................ 15
25. Primary disconnect modification for AK-15 breakers..................................................................................... 15
27. Cabling diagram for PtoTrip™ trip units with ground fault on four-wire loads...............................................19
3
SECTION 1. GENERAL INFORMATION
GE Conversion Kit installation is straightforward, but
does require careful workmanship and attention to these
instructions. Familiarity with the breaker is highly
desirable. Then general approach is to first remove the
existing trip devices from the breaker, then install the
ProTrip components. Following this procedure, the
converted breaker is performance tested before it is
returned to service.
The majority of trip unit kit installations do not require any
customized assembly work. However, some installations
may involve unusual mounting conditions or accessory
combinations that require minor modifications and/or
relocation of components. In most instances, this
supplementary work can be done on site.
In preparation for the conversion, the installer should
verify that the appropriate current sensors and trip unit
have been furnished. Whenever a ProTrip kit is installed
on a breaker with a four-wire system, an associated
neutral sensor (CT) is required for separate mounting in
the equipment. Ensure that retrofitted breakers are
applied within their short-circuit ratings.
Note that all ProTrip trip units supplied with conversion
kits are equipped with long-time, short-time,
instantaneous, and defeatable ground fault (LSIGX) trip
functions. The installer should be aware of how these
functions will affect his application before installing the
conversion kit.
As a service-related consideration, the installation of a
ProTrip kit provides an excellent opportunity to perform
normal maintenance on the breaker, particularly when
the front and back frames are separated. Such
procedures are described in the installation and
maintenance manuals supplied with the breaker and
equipment.
SECTION 2. BEFORE INSTALLATION
Before starting any work, turn off and lock out all power
sources leading to the breaker, both primary and
secondary. Remove the breaker to a clean, well-lighted
work area.
WARNING: Low-voltage power circuit breakers use
high-speed, stored-energy spring operating
mechanisms. The breakers and their enclosures
contain interlocks and safety features intended to
provide safe, proper operating sequences. For
maximum personnel protection during installation,
operation, and maintenance of these breakers, the
following procedures must be followed. Failure to follow
these procedures may result in personal injury or
property damage.
• Only qualified persons, as defined in the National
Electrical Code, who are familiar with the installation
and maintenance of low-voltage power circuit
breakers and switchgear assemblies, should
perform any work on these breakers.
• Completely read and understand all instructions
before attempting any breaker installation,
operation, maintenance, or modification.
• Turn off and lock out the power source feeding the
breaker before attempting any installation,
maintenance, or modification. Follow all lock-out
and tag-out rules of the National Electrical Code and
all other applicable codes.
• Do not work on a closed breaker or a breaker with
the closing springs charged. Trip an OPEN breaker
and be sure the stored-energy springs are
discharged, thus removing the possibility that the
breaker may trip OPEN or the closing springs
discharge and cause injury.
• Trip the breaker OPEN, then remove the breaker to
a well-lighted work area before beginning work.
• Do not perform any maintenance that includes
breaker charging, closing, tripping, or any other
function that could cause significant movement of a
draw-out breaker while it is on the draw-out
extension rails.
• Do not leave the breaker in an intermediate position
in the switchgear compartment. Always leave it in
the CONNECTED, TEST, or DISCONNECTED
position. Failure to do so could lead to improper
positioning of the breaker and flashback.
4
SECTION 3. FRONT-FRAME
CONVERSION
Front-frame conversion consists of the following steps:
1. Separation of the front and back breaker frames.
2. Removal of the existing trip devices.
3. On electrically operated breakers with EC trip
devices, relocating and remounting the X and Y
relays.
3. Installation of the flux shifter and trip paddle.
4. Installation of the trip unit mounting bracket.
5. Installation of the trip unit wire harness.
Separation of the Front and Back Frames
Use the following procedure to separate the front and
back frames of the breaker.
1. Remove the breaker from its enclosure and place it
on a suitable work surface.
2. Verify that closing springs are discharged and that
the breaker is OPEN.
3. Loosen the two captive nuts and lift off the arc chute
retainer, shown in Figure 1.
4. Lift the three arc chutes straight up and out of the
breaker.
5. Remove the long screw and nut through the two
connecting links on each side of the breaker, as
shown in Figure 2.
6. Carefully place the breaker on its back surface,
resting on the primary disconnects.
Figure 1. Arc chute retainer and arc chutes.
Figure 2. Screw to be removed from connecting links.
5
7. Remove the two mounting screws and lock washers
attaching the bottom bracket to the escutcheon, as
shown in Figure 3.
8. Loosen the recessed Allen screw in the side of the
charging handle base and lift off the handle.
9. Remove the snap ring and flat washer on the
charging handle mounting shaft.
10. Remove the four Philips-head screws and lock
washers on the front of the escutcheon and lift off the
escutcheon.
11. Lift the bottom bracket from its back frame
attachment.
12. Remove the nuts and washers securing the front
frame to the two long studs from the back frame.
13. Remove the nuts and washers on the studs connecting the front frame bracket to the back frame
(one on each side).
14. Lift the front frame off the back frame.
Removal of the Existing Trip Device
Figure 4 shows an existing Type EC-2A trip device with
the adjacent trip device already removed, to illustrate this
procedure.
1. Remove the existing overcurrent trip devices and trip
paddles.
2. On draw-out breakers, remove the primary disconnects from the bottom (load) copper studs.
3. Remove the three bottom (load) copper stud
assemblies. On Power Sensor-equipped breakers,
these will have been removed with the trip devices.
4. On breakers equipped with Type EC trip devices,
remove and discard the mounting brackets on the
lower front of the back frame.
Figure 3. Breaker bottom bracket connected to the
escutcheon and the back frame.
Figure 4. Type EC-2A trip device, with adjacent device
removed.
6
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.