These instructions do not purport to cover all details or
variations in equipment, nor to provide for every possible
contingency to be met during installation, operation, and
maintenance. Should further information be desired or
should particular problems arise that are not covered
sufficiently for the purchaser's purpose, the matter should
be referred to GE Fuji, Technical Service.
NOTE: The terms "inverter", "controller", and "drive" are
sometimes used interchangably throughout the industry.
We will use the term "Drive" in this document.
AF-300E$™ and X$D™ are trademarks of the General
Electric Company.
®
Energy $aver
Electric Company.
NOTE: Always read the complete instructions prior to
applying power or troubleshooting the equipment and
follow all procedures step by step.
SHOCK HAZARD labels may be located on or inside the
Drive to alert people that dangerous voltage may be
present.
is a registered trademark of the General
WARNING, CAUTION AND NOTES
The following format is used on the equipment or found in
this manual. Read all labels and follow the directions on
them whenever working on the equipment.
WARNING: Denotes operating procedures and practices
that may result in personal injury or loss of life if not
correctly followed.
CAUTION: Denotes operating procedures and practices
that, if not strictly observed, may result in damage to, or
destruction of the equipment.
NOTE: Notes call attention to information that is especially
significant in understanding and operating the equipment.
WARNING, CAUTION AND NOTE PARAGRAPHS
WITHIN THIS INSTRUCTION
The above paragraphs list some general safety reminders
and safety recommendations to be followed when operating or installing this equipment. These safety precautions
will be repeated throughout this instruction book where
applicable.
Drive systems cause mechanical motion. It is the responsibility of the user to insure that any such motion does not
result in an unsafe condition. Factory provided interlocks
and operating limits should not be bypassed or modified.
WARNING - ELECTRICAL SHOCK AND BURN
HAZARD:
When using instruments such as oscilloscopes to work on
live equipment, the oscilloscope’s chassis should be
grounded and a differential amplifier input should be used.
Care should be used in the selection of probes and leads
and in the adjustment of the oscilloscope so that accurate
readings may be made. See instrument manufacturer’s
instruction book for proper operation and adjustments to
the instrument.
WARNING - FIRE AND EXPLOSION HAZARD:
Fires or explosions might result from mounting drives in
hazardous areas such as locations where flammable or
combustible vapors or dusts are present. Drives should be
installed away from hazardous areas, even if used with
motors suitable for use in these locations.
WARNING - STRAIN HAZARD:
WARNING -
Before disassembling, disconnect and lock out power from
the drive. Failure to disconnect power may result in death
or serious injury. A bus charge light provides visual
indication that bus voltage is present; verify the bus voltage
level by measuring the voltage between power terminals
P(+) and N(-) using an analog meter. Do not attempt to
service the drive until the charge indicator has extinguished
and the bus voltage has discharged to zero volts.
WARNING -
Replace all covers before applying power to the drive.
Failure to do so may result in death or serious injury.
CAUTION:
Do not connect power supply voltage that exceeds the
standard specification voltage fluctuation permissible. If
excessive voltage is applied to the drive, damage to the
internal components will result.
CAUTION:
Do not connect power supply to the output terminals (U, V,
W). Connect power supply only to the power terminals (L1,
L2, L3).
Improper lifting practices can cause serious or fatal injury.
Lift only with adequate equipment and trained personnel.
WARNING - ELECTRICAL SHOCK HAZARD:
All motor bases and equipment enclosure housings should
be grounded in accordance with the National Electric Code
or equivalent.
WARNING - MOTOR OVERSPEED HAZARD:
With 400 Hz drive output possible, the drive will allow the
motor to run up to 6 - 7 times its base speed. Never
operate the motor above its top mechanical speed or a
catastrophic failure may occur.
Any applications requiring operation above
120 Hz must be approved by the Company.
CAUTION:
Even though the main AF-300E$ power has been disconnected it may still receive electrical energy from more than
one source. If external power is applied to the control
terminals 30A, B & C and AX1 and AX2 as well as any
option card control input terminal points (if installed in the
drive), and if the independent power source is activated
separately from the AF-300E$'s main input power, failure to
to diconnect this external power source may result in death
or serious injury. This external power must be removed
prior to any work being performed on the drive.
WARNING: this equipment may receive electrical
energy from more than one source. Additional
disconnects are located outside this cabinet. Open all
associated disconnects before servicing equipment.
Refer to equipment diagrams.
1-1
CAUTION:
For RUN and STOP, use the FWD-CM (forward) and REVCM (reverse) terminals. Do not use a contactor (ON/OFF)
installed on the line side of the drive for RUN and STOP.
CAUTION:
Because the ambient temperature greatly affects drive life
and reliability, do not install the drive in any location that
exceeds the allowable temperature. Leave the ventilation
cover attached for temperatures of 40 degrees C or below,
CAUTION:
Do not use a switch on the output side of the drive for ON/
OFF operation.
and remove the cover for temperatures of between 40
(104° F) and 50 (122° F) degrees C (30 Hp and lower).
If the cover needs to be removed, another type of
enclosure may be required for safety purposes.
CAUTION: Do not connect filter capacitors on the output
side of the drive.
CAUTION:
If the Drive’s Fault Alarm is activated, consult the
CAUTION:
Do not operate the drive without the ground wire connected. The motor chassis should be grounded to earth
TROUBLESHOOTING section of this instruction book, and
after correcting the problem, resume operation. Do not
reset the alarm automatically by external sequence, etc.
through a ground lead separate from all other equipment
ground leads to prevent noise coupling.
The grounding connector shall be sized in accordance with
the NEC or Canadian Electrical Code. The connection shall
be made by a UL listed or CSA certified closed-loop
terminal connector sized for the wire gauge involved. The
connector is to be fixed using the crimp tool specified by
CAUTION:
Be sure to remove the desicant dryer packet(s) when
unpacking the drive. (If not removed these packets may
become lodged in the fan or air passages and cause the
drive to overheat.)
the connector manufacturer.
CAUTION:
CAUTION:
Do not perform a megger test between the drive terminals
or on the control circuit terminals.
AC induction motors require that they be sized based on
the applications speed range and associated torque
requirements for the motor-drive system. This is to avoid
excessive motor heating. Observe motor manufacturers
recommendations when operating any ac induction motor
CAUTION:
The AF-300E$ drive develops an adjustable frequency via
pulse width modulation, with the pulse rise time of 0.1
with the drive. Also observe motor manufacturer's
recommended voltage/torque boost at lower operating
frequencies.
microseconds. While this does not present a problem on
200-230Vac applications, it may on 380-460Vac applications. When using the AF-300E$ drives on 380-460Vac,
where the distance between the motor and the drive
exceeds 60 feet, get the motor manufacturer's approval
that his insulation system can withstand the voltage spikes
(up to twice the dc bus voltage 2 x 621Vdc for a 460Vac
power source) of the drive, in conjunction with the long
CAUTION:
The available power source connected to the drive is not to
exceed 500KVA. If the ac power source is greater than
500KVA and the driver's rating (Hp) is less than 10% of the
power source's KVA; ac line reactors will have to be
installed in L1, L2 & L3 power leads of the drive.
motor cable lengths. If the insulation system does not meet
this limit, utilize a filter to increase the Drive's pulse rise time
to 1.0 microseconds.
CAUTION:
The drive must be mounted on a wall that is constructed of
heat resistant material. While the drive is operating, the
temperature of the drive's cooling fins can rise to a
temperature of 90°C (194°F. )
1-2
Section 2: Description, Component Identication and Specifications
The AF-300E$ drive is available in ratings of 0.5 to 30 Hp
200-230 VAC, 1 to 300 Hp (350Hp variable torque) 380-460
VAC. The AF-300E$ drive incorporates multiple control al-
INSPECTION PROCEDURES UPON DELIVERY
Upon receipt of your drive, inspect the equipment for the
gorithms with either the traditional PWM Scalar power control or a selectable torque vector algorithm with a self tuning
1. Check the nameplate to insure that the specifications
drive/motor function that is used in high performance operation. The AF-300E$ Drives are housed in a NEMA 1 type
2. Inspect the unit for any damage that may have occurred
enclosure for either open or panel mounting and all Inverters
are furnished with a detachable wiring lead-in plate to allow
ease of accessing control and power wiring.
Drive operation and Function Code setting is performed from
the “Keypad Panel” that also features a Digital Monitor, LCD
Graphic Display and 8 dual function keys. The 8 dual function keys are used for drive programming and operation as
well as selection of drive local/remote operation.
General data and specification for each drive are listed on
the nameplate attached to the drive. Refer to TABLE 1 for
complete AF-300E$ drive specification listing.
following items:
correspond to those ordered.
during shipment.
If shipping damage is found or the wrong Inverter is
received, contact the distributor from which this
equipment was purchased.
AF-300E$
MODEL NO.
SERIAL NO.
INPUT:
VOLTS
AMPS
FREQ (HZ)
PHASE (S)
INSTRUCTION
BOOK GEI-100211
All models are UL Listed and CSA Approved*
(Nameplate shown larger than actual size.)
Figure 2-1. NAMEPLATE DATA IDENTIFICATION
* CE Mark for three-phase (3ø), 415 VAC, 1 to 30 Hp only.
CONSTANT
TQ OUTPUT:
VOLTS
FREQ RANGE (HZ)
HP
AMPS CONT.
PHASE
ROTATION
MAX 60 SEC. AMPS
GE Fuji Drives America Made in Mexico
TM
VARIABLE
TQ OUTPUT:
2-1
Drive Keypad Functions and Layout
Indication of keypad panel operation
Digital Monitor (4-digit)
LCD Graphic Display
Program Key
Shift Key
Reset Key
Figure 2-2. KEYPAD PANEL COMPONENT IDENTIFICATION
Attachment Screws -The Keypad Panel can be easily
removed from the Drive unit by loosening the two attachment screws. With the optional extension cable, remote
Keypad operation and display is possible.
LCD Graphic Display - LCD Display shows control status or Function Code settings.
PROGRAM (PRG) Key - Operation Mode or Program Mode
selection key.
SHIFT (>>) Key - Changes the digital monitor display in
the Operation Mode. Will also change the LCD graphic
display in Program Mode and Trip Mode.
Unit displayed
}
Up - Down Keys
Run Light
Run Key
Function/Data Key
Stop Key
RUN Key - This key is the RUN command in Keypad operation, run light will be illuminated at this time.
STOP Key - This key is used for stopping operation. If
pressed when the Drive is running by external control, fault
Er6 will be displayed and Drive will coast to a stop.
UP - DOWN Keys - These keys increase or decrease the
frequency (or speed) of the Drive. When unit is in Program
Setting Mode, they change the Function Code or Data Code
values.
LCD Brightness - Function Code 79 permits adjustment
for easy to read brightness of the graphic display.
SET FUND/DATA Key - Displays data setting of selected
Function Codes. Also, stores any changes in software.
RESET Key - After removal of the fault condition, faults
can be reset and will return the Drive to the Operation Mode.
Remote/Local Operation - Remote/Local operation can
be toggled by pressing the RESET and STOP keys simultaneously when the Drive is stopped.
2-2
Unit Display - The unit information is displayed by LEDs
during RUN or STOP condition.
Digital Monitor - Displays Hz, Volts, R/Min, M/Min, or %
as set by the operator using the SHIFT (>>) key or resetting
Function Code 61.
Table 1: AF-300E$ – Standard Specifications
Environmental Conditions
EnclosuresNEMA 1 Standard
Installation LocationSuitable for indoor mounting only, less than 1000 meters (3300 feet) elevation, not in
contact with corrosive gas, oil mist, dust, and out of direct sunlight.
Stored Temperature-20° to +65°C (-4° to + 149°F)
Ambient Temperature-10 to +50
[+104oF] up to 30 Hp; 40 Hp and above not required.)
Humidity20% to 90% relative humidity (non-condensing).
Vibration0.6G or less.
Cooling Method1/2 to 1 Hp – Convection
2 Hp and greater – Forced air
o
C (+14 to +122oF) (remove ventilation covers if temperature is over +40oC
Output
Rated Output Voltage3-Phase, 3-Wire Type, 80-240 VAC or 320-480 VAC
(Can not exceed power supply voltage).
Frequency Range0 - 400 Hertz (0.2 to 60 Hz start frequency; 0.2 to 120 Hz base frequency).
Above 120 Hz, contact Company for approval of application.
Overload Current Rating– 30 Hp and lower
150% for 1 minute duration (inverse time characteristic)
200% for 0.5 seconds
– 40 Hp and greater
150% for 1 minute duration (inverse time characteristic) 180% for 0.5 seconds
Power Supply
Rated Input AC Voltage– 200 to 230 VAC 50/60 Hz, 3 phase (1/2 to 30 Hp)
– 380 to 400 VAC 50 Hz, 3 phase (1 to 300 Hp) CT
– 380 to 480 VAC 60 Hz, 3 phase (1 to 300 Hp) CT
– 460-480 VAC, 60 Hz, 3 phase, 40 Hp and above, variable torque applications only
Voltage - +10%, -15%; Voltage Unbalance - Within 3%; Frequency - +/-5% Units are
dual rated Constant Torque/Variable Torque. Drive looks for a similar Volts/Hz ratio).
Control SystemSinusoidal PWM Control (or with torque-vector control.)
Momentary Voltage DipWhen the input voltage dips below 165 VAC (230V System), 310 VAC (460V system) or
400 VAC (575V System), the Drive can operate for 15 ms with 85% full load applied.
Starting Torque150% (when torque vector control is active.)
Carrier Frequency– 2 to 15 KHz (1/2 to 30 Hp) 230 & 460 VAC
– 2 to 10 KHz (40 to 75 Hp) – 2 to 6 KHz (100 Hp and greater)
2-3
Frequency Setting Resolution– Analog: 1⁄3000 of max. frequency (0.02 Hz/60 Hz; 0.04 Hz/120 Hz)
– Digital: 0.01 Hz (max. frequency up to 99.99 Hz);
0.1 Hz (max frequency of 100 Hz or more)
Accuracy (Stability)– Analog setting: ± 0.2% of max. frequency (@ 25 ± 10°C)
– Digital setting: ± 0.01% of max. frequency (@ -10 to + 50°C)
Torque Boost– Auto: Automatic torque boost control by torque calculated value.
– Manual: 0.0 to 20.0 code setting (includes the energy savings pattern,
Function Code for variable torque load.)
Acceleration/Deceleration0.2 to 3600 seconds (independent acceleration/deceleration)
Characteristics4 selectable linear and non-linear "S" curve characteristic.
Internal Functions:The quality of the sound produced by the motor can be changed to
Operating Sound Selectionreduce irritating noise.
Frequency Meter AdjustmentScale calibration of externally connected analog meter (6.5-10.5 VDC) or pulse frequency
6 to 100 times output frequency.
Data ProtectionData lock is possible to ensure that the data codes are not changed.
Pattern OperationSeven independent stages (frequency up to 400 Hz, duration up to 6,000 seconds each.
Configuration:
Single cycle
Repeat cycling
Single cycle with continuous 7th speed
Momentary PowerFive selections available. (Refer to Power Supply Specification.)
Loss Ride Thru
High/Low LimiterOutput frequency upper and lower range limit 0 to 400 Hz; 1 Hz step settings.
BiasMagnitude of the zero offset can be set from 0 to 100% of maximum
frequency (1 Hz steps.)
GainOutput frequency gain corresponding to the reference signal can be set
from 0 to 200% (0.1% steps.)
Programmable Jump FrequencyThree selectable frequencies can be set to avoid a mechanical resonant point. Width is
adjustable from 0 to 30 Hz (1 Hz steps.)
Slip Compensation ControlMaintains motor at constant speed with load fluctuations.
Adjustable from -9.9 Hz to +5.0 Hz.
Torque Limit ControlOutput torque can be controlled within a range of 20% to 180% (1% steps.)
Momentary or MaintainedSelection between the maintained contact operation/stop command (2-wire operation) or
Contact Operationthe momentary contact (3-wire operation).
Terminal Function ChangeMulti-Use terminals changed via Function Code settings.
X1 to X5 inputs; Y1 to Y5 outputs.
Line to Drive Transition LogicMotor transfer function from the AC line to Drive operation.
Sensorless Vector Control– Improves torque characteristics throughout speed range.
– Improves speed regulation.
2-4
Operation
Frequency Reference Signal– Speed potentiometer/0 to +10 VDC
– 4 to 20 mA
– 0 to ±10 VDC (Standard on 40 Hp and greater) (Option on 1/2 to 30 Hp)
Input Signal (contact type)Forward, reverse, self-holding selection (when operation is 3-wire), multi-step
speed setting (7-step), multiple accel/decel time settings (4 settings),
coast-to-stop, external alarm, and reset.
External Output SignalsOne Dry Form "C" alarm output contact rated 250 VAC, 0.3 amp.one auxiliary run
contact rated 250 VAC, 0.3 amp (available only on 40 Hp and above ratings.)
5 – Open collector outputs each rated 24 VDC, 50mA from external power.
– Drive Run– Time-up signal during pattern mode
– Frequency equivalence signal– Undervoltage detection
– Overload early warning– Keypad operation
– Auto restart mode– Torque limiting mode
– Cycle completion pattern mode– Auto reset mode
– Momentary power failure– Overcurrent
– Drive overheating– Overvoltage
– External faults– Link error
– CPU malfunction– Communication error
– Motor overload– Ground fault
(electronic thermal)
Frequency Meter Output SignalPulse frequency (6 to 100) times output frequency.
Analog - 0 to +10 VDC (adjustment range of 6.5 to 10.3 VDC)
KeypadDigital Display - 4 digit LED
Graphic Display - LCD, with brightness control
Drive OperationOutput frequency, output current, output voltage, motor speed, line speed (m/min),
machine speed (r/min), torque limit (driving), torque limit (braking), and motor torque.
Set frequency is displayed when not in Run or Program Mode.
Drive SettingFunction Code and setting data displayed (see Operation Panel paragraph).
2-5
Drive Fault– OC1 - Acceleration overcurrent
– OC2 - Deceleration overcurrent
– OC3 - Constant speed overcurrent
– EF - Ground fault
– LU (LV) - Undervoltage
– OU1 - Overvoltage at accel
– OU2 - Overvoltage at decel
– OU3 - Overvoltage at constant speed
– FUS - DC Bus fuse failed
– OH1 - Drive overheat (Fins)
– OH2 - External alarm
– OH3 - Drive internal temperature
– Er1 - EE Prom malfunction
– Er2 - Communication error
– Er3 - CPU malfunction
– Er4 - Link error
– Er5 - Option malfunction
– Er6 - Drive error at start-up
– Er7 - Missing motor connection
Drive Input/Output Display– Forward– Reverse
– Hld– Bx
– X1 thru X5– Y1 thru Y5
– Incoming reference voltages can be shown on LCD graphic display.
Charge Lamp (LED)Lights when DC Link capacitor voltage is present.
2-6
AF-300E$ Model Numbering System Diagram
Description
␣␣␣␣␣␣
GE Product Code
AF-300 Drive Family
Series Revision
1 = 1st Product Revision
2 = 2nd Product Revision
Input Voltage
2 = 230V 50/60 Hz
4 = 460V 50/60 Hz
Input Phases
1 = 1 Phase
3 = 3 Phase
6KE$NNN (X/N)NN X N X N
Horsepower
F50 = 1/2 Hp
010 = 10 Hp
100 = 100 Hp
Factory Installed Options
N = None
X = Keypad
B = to be determined
Enclosure Type
1 = NEMA 1
2 = NEMA 12
4 = NEMA 4
Product Revision
A = 1st Revision
B = 2nd Revision
Minor Product Revision
1 = 1st Minor Revision
2 = 2nd Minor Revision
2-7
Table 2:AF-300E$ Drive Dimensions
ConstantConstant VariableVariable
TorqueTorqueTorqueTorqueAF-300E$CatalogList PriceH x W x DWeight
Hp RatingRated OutputHp RatingRated OutputModel No.No.GO-5E$inches(lbs.)
150% 1 min.*Amps115% 1 min.*Amps
230 VAC, 3 phase, 50/60 Hz Input, NEMA 1 Enclosure
0.53.0N/AN/A6KE$223F50X1A1D5501810. 10.24 x 4.33 x 4.535.3
15.0N/AN/A6KE$223001X1A1D5502860. 10.24 x 4.33 x 5.125.3
28.0N/AN/A6KE$223002X1A1D5503920. 10.24 x 5.91 x 5.718.4
311.0N/AN/A6KE$223003X1A1D5504990. 10.24 x 5.91 x 5.718.4
517.0N/AN/A6KE$223005X1A1D55051,220. 10.24 x 5.91 x 5.718.4
7.525.01029.06KE$223007X1A1D55061,520. 10.24 x 8.66 x 7.6813
1033.01542.06KE$223010X1A1D55071,850. 10.24 x 8.66 x 7.6813
1546.02055.06KE$223015X1A1D55082,475. 15.75 x 9.84 x 7.6825
2059.02568.06KE$223020X1A1D55093,120. 15.75 x 9.84 x 7.6825
2574.03080.06KE$223025X1A1D55103,705. 15.75 x 9.84 x 7.6827
3087.0N/AN/A6KE$223030X1A1D55114,300. 15.75 x 9.84 x 7.6827
460 VAC, 3 phase, 50/60 Hz Input, NEMA 1 Enclosure
12.5N/AN/A6KE$243001X1A1D55121,100. 10.24 x 5.91 x 5.718.4
23.7N/AN/A6KE$243002X1A1D55131,180. 10.24 x 5.91 x 5.718.4
35.5N/AN/A6KE$243003X1A1D55141,270. 10.24 x 5.91 x 5.718.4
59.0N/AN/A6KE$243005X1A1D55151,560. 10.24 x 5.91 x 5.718.4
7.513.01016.56KE$243007X1A1D55161,950. 10.24 x 8.66 x 7.6814
1018.01523.06KE$243010X1A1D55172,375. 10.24 x 8.66 x 7.6814
1524.02030.06KE$243015X1A1D55183,175. 15.75 x 9.84 x 7.6825
2030.02537.06KE$243020X1A1D55194,000. 15.75 x 9.84 x 7.6825
2539.03044.06KE$243025X1A1D55204,750. 15.75 x 9.84 x 7.6827
3045.0N/AN/A6KE$243030X1A1D55215,510. 15.75 x 9.84 x 7.6827
3045.04052.06KE$243035X1A1D55226,350.33.5 x 13.4 x 9.6589
4060.05066.06KE$243040X1A1D55237,050.33.5 x 13.4 x 9.6589
5075.06077.06KE$243050X1A1D55248,560.33.5 x 14.8 x 9.65100
6091.07596.06KE$243060X1A1D55259,955.39.4 x 14.8 x 9.65111
75112.0100124.06KE$243075X1A1D552611,965.39.4 x 14.8 x 9.65122
100**150.0125156.06KE$243100X1A1D552714,915. 43.3 x 14.8 x 10.63144
125**176.0150180.06KE$243125X1A1D552817,540. 47.3 x 20.9 x 12.4221
150**210.0200253.06KE$243150X1A1D552919,830. 57.1 x 20.9 x 14.2287
200**304.0250304.06KE$243200X1A1D553124,070. 57.1 x 20.9 x 14.2298
250**377.0300377.06KE$243250X1A1D553228,135. 57.1 x 26.8 x 14.2430
300**415.0350415.06KE$243300X1A1D553330,425. 57.1 x 26.8 x 14.2430
* Verify the full load rated current of the motor to which the drive will be applied.
4-001
** A DC Link Inductor is shipped as a separate item (Ratings equal to and greater than 100 Hp)
and is to be connected to Drive Power Terminals P1 and P+. The DC Link Inductor is open core
design. If single unit construction is required refer to the Panel Section of the manual.
Note: In variable torque applications, Function Code 86 (Motor Hp Capability) needs to be changed to
Set Drive Hp vs. Load Hp. 40 Hp and above is 460-480 VAC input, variable torque applications only.
2-8
Table 3:CE Labeled AF-300E$ and Fuji Electric G9 Products
GE Fuji has expanded its product
offering again, with a new line of CE
labeled AF-300E$ drives. The drives
are available in 415 VAC (380 VAC to
460 VAC UL, CSA only) ratings.
Drives from 1 - 30 Hp also carry the
UL and CSA approvals in addition to
the CE Mark. Drives rated at 40 Hp
and above carry the CE label
exclusively. The units have the same
variable torque and constant torque
ratings as the existing line of AF300E$ drives. In addition to the new
CE labeled drives, GE Fuji offers a
complete compatible line of RFI
filters.
The mounting wall for the drive must be constructed of
heat resistant material because during operation, the
temperature of the Inverter's cooling fins rises to approxi-
mately 90 degrees C (194° F).
NOTE: When installing two or more drives in close
proximity, allow sufficient space as shown in Figure 3-1 and
install them in a horizontal row. If they must be installed in
a vertical column, at least 19.7 inches (50cm) internal
space must be provided between each one or a ventilation
baffle should be provided to prevent the ambient temperature from rising.
—Mounting screws or bolts should be of appropriate size
—See the appropriate view in Figure 3-2 for the location
—After removing the knockouts in the wiring lead in
for weight of drive.
of mounting holes.
plate, install the rubber bushings supplied to prevent
cable damage and to minimize dust entry.
4.8” (12CM) or more
(9 amps) x = 8.84 amps derated
Motor derate may also be required, contact motor
manufacturer.
— Vibration should be less than 0.6G.
Installation Mounting Clearance
CAUTION:
Because the ambient temperature greatly
affects drive life and reliability, do not install the drive in any
location that exceeds the allowable temperatures.
—Install at a sufficient distance from other equipment,
walls, or wiring ducts as shown in Figure 3-1 (these
clearances are required to allow the heat generated by
the drive to escape).
—Install the drive perpendicular to the ground and with
the lettering right side up. (If the drive is installed
upside-down or horizontally, heat build-up will occur.)
100 - 1.8
( )
100
output current.
2.0” (5 CM)
or more
4.8” (12CM) or more
Figure 3-1. DRIVE MOUNTING CLEARANCE
2.0” (5 CM)
or more
3-1
Dimensions 0.5 Hp 230 VAC
Dimensions in inches (mm)
0.24 (6)
4.33 (110)
3.78 (96)
0.28 (7)0.28 (7)
9.69 (246)
.28 (7)
10.24 (260)
4.53 (115)
0.87 (22)
0.24 (6)
2.52 (64)
0.24 (6)
2.52 (64)
1.26 (32)
0.87 (22)
BUSHING SUPPLIED
3-2
Dimensions 1 Hp 230 VAC
Dimensions in inches (mm)
0.24 (6)
4.33 (110)
3.78 (96)
0.28 (7)0.28 (7)
9.69 (246)
.28 (7)
512 (130)
1.46 (37)
0.24 (6)
10.24 (260)
3.11 (79)
0.24 (6)
3.11 (79)
1.26 (32)
0.87 (22)
BUSHING SUPPLIED
3-3
Dimensions 2, 3, 5 Hp 230 VAC and 1, 2, 3, 5 Hp 460 VAC
Dimensions in inches (mm)
0.24 (6)
5.91 (150)
5.35 (136)
0.28 (7)0.28 (7)
9.69 (246)
.28 (7)
5.71 (145)
2.05 (52)
0.24 (6)
10.24 (260)
3.7 (94)
1.26 (32)
0.24 (6)
3.7 (94)
1.26 (32)
0.87 (22)
BUSHING SUPPLIED
3-4
Dimensions 7.5 , 10 Hp 230 and 460 VAC
Dimensions in inches (mm)
0.47 (12)
2.26 (57.5)
1.81 (46)
8.66 (220)
7.72 (196)
2.07 (52.5)
0.39 (10)
0.47 (12)
0.47 (12)
9.37 (238)
0.39 (10)
0.87 (22)
7.68 (195)
3.82 (97)
0.39 (10)
10.24 (260)
6.18 (157)
6.18 (157)
BUSHING SUPPLIED
3-5
Dimensions 15, 20, 25, 30 Hp 230 and 460 VAC
Dimensions in inches (mm)
0.47 (12)
9.84 (250)
8.90 (226)
2-0.39 (10)
0.47 (12)
14.88 (378)
0.39 (10)
0.47 (12)
15.75 (400)
7.68 (195)
3.78 (96)
0.39 (10)
1.34 (34)
2.48 (63)
5.93 (150.5)
2.17 (55)
2.42 (61.5)
.0.39 (10)
6.02 (153)
BUSHING SUPPLIED
1.65 (42)
3-6
Dimensions 35 , 40 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
4-ø 1.9 (48)
wire inlet
Knock out hole
13.4 (340)
9.5 (240)
2.6
(65)
3.8
(97)
AF-300E$
2.8
(70)
2.3
(58)
0.5 (12)
0.4 (10)
2-ø 0.4 (10)
32.7 (830)
33.5 (850)
9.7 (245)
0.1 (2.3)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
3540650850
408501100509001050
BACK PANEL
THROUGH PANEL MOUNTING
12.8 (326)
9.5 (240)
1.6 (41)
1.0 (25)
4-MB (0.3)4.1 (105)
0.4 (9)
32.7 (830)
32.0 (812)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
3540195255
4025533050270315
BACK PANEL
3-7
Dimensions 50 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
4-ø 1.9 (48)
wire inlet
Knock out hole
2.6
(65)
14.8 (375)
10.8 (275)
AF-300E$
3.8
(97)
2.8
(70)
2.3
(58)
0.5 (12)
0.4 (10)
2-ø 0.4 (10)
32.7 (830)
33.5 (850)
9.7 (245)
0.1 (2.3)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
509001200609501150
BACK PANEL
THROUGH PANEL MOUNTING
14.2 (361)
10.8 (275)
1.6 (41)
1.0 (25)
4-MB (0.3)4.1 (105)
0.4 (9)
32.7 (830)
32.0 (812)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
5027036060285345
BACK PANEL
3-8
Dimensions 60, 75 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
4-ø 1.9 (48)
wire inlet
Knock out hole
14.8 (375)
10.8 (275)
2.6
(65)
AF-300E$
(100)
3.8
0.4 (10)
2.8
(70)
2-ø 0.4 (10)
0.5 (12)
38.61 (980)
3.7
(93)
9.7 (245)
0.1 (2.3)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
60100013007510501250
751150155010013001500
39.4 (1000)
BACK PANEL
THROUGH PANEL MOUNTING
14.2 (361)
10.8 (275)
0.4 (9)
1.6 (41)
4-M8 (0.3)
38.6 (980)
37.9 (962)
0.4 (10)
4.1 (105)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
6030039075315375
75345415100390450
BACK PANEL
3-9
Dimensions 100 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
4 ø 1.9 (48)
wire inlet
Knock out hole
14.8 (375)
10.8 (275)
3.2
(80)
3.6
(92)
AF-300E$
3.6
(92)
2.5
(62)
0.5 (12)
0.4 (10)
2-ø 0.4 (10)
42.5 (1080)
43.3 (1100)
3-ø 2.5 (64)
wire inlet
Knock out hole
106 (270)
0.1 (2.3)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
1001500160012517001850
BACK PANEL
THROUGH PANEL MOUNTING
14.2 (361)
10.8 (275)
1.7 (43)
0.4 (9)
4-M8 (0.3)
42.5 (1080)
41.8 (1062)
4.1 (105)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
100450480125510555
NOTE: Drive includes a separately mounted DC Link Reactor.
BACK PANEL
NOTE: Drive includes a separately mounted DC Link Reactor. See Page 4-10 for details
3-10
Dimensions 125 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
4 ø 1.9 (48)
wire inlet
Knock out hole
5.9
(150)
20.9 (530)
16.9 (430)
5.5
(139)
AF-300E$
3.7
(94)
2.4
(62)
2-ø 0.6 (15)
0.7 (18)
0.4 (10)
3-ø 2.5 (64)s
45 (1170)
47.2 (1200)
12.4 (315)
0.1 (3.2)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
1251750200015018002000
BACK PANEL
THROUGH PANEL MOUNTING
20 (510)
16.9 (430))
1.9 (48)
1.0 (25)
0.5 (12.5)
45.1 (1145)
4-M12 0.5
46.1 (1170)
4.9 (125)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
125525600150540600
NOTE: Drive includes a separately mounted DC Link Reactor
BACK PANEL
NOTE: Drive includes a separately mounted DC Link Reactor. See Page 4-10 for details
3-11
Dimensions 150 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
ø 1.9 (48)
wire inlet
Knock out hole
3.2
(80)
20.9 (530)
16.9 (430)
AF-300E$
5.4
(136)
3.6
(92)
2.7
(68)
2-ø 0.6 (15)
0.7 (18)
0.6 (15)
3-ø 2.5 (64)s
55.9 (1420)
57.1 (1450)
14.2 (360)
0.1 (3.2)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
1502050235020020502300
BACK PANEL
THROUGH PANEL MOUNTING
20 (510)
16.9 (430)
3.2 (81)
0.8 (20)
0.5 (12.5)
54.9 (1395)
4-M12 0.5
55.9 (1420)
5.5 (140)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
150615705200615690
NOTE: Drive includes a separately mounted DC Link Reactor.
BACK PANEL
NOTE: Drive includes a separately mounted DC Link Reactor. See Page 4-10 for details
3-12
Dimensions 200 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
4 ø 1.9 (48)
wire inlet
Knock out hole
3.7
(95)
20.9 (530)
16.9 (430)
AF-300E$
6.4
(162)
5.4
(138)
3.4
(86)
2-ø 0.6 (15)
0.7 (18)
0.6 (15)
3-ø 2.5 (90)
55.9 (1420)
57.1 (1450)
14.2 (360)
0.1 (3.2)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
2002850325025028003150
BACK PANEL
THROUGH PANEL MOUNTING
20 (510)
16.9 (430)
2.8 (71)
0.6 (15)
0.5 (12.5)
54.9 (1395)
4-M12 0.5
55.9 (1420)
5.5 (140)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
200855975250840945
NOTE: Drive includes a separately mounted DC Link Reactor
BACK PANEL
NOTE: Drive includes a separately mounted DC Link Reactor. See Page 4-10 for details
3-13
Dimensions 250, 300 Hp 460 VAC
Dimensions in inches (mm)
BACK PANEL MOUNTING
BRACKET AREA
(BRACKET
SUPPLIED BY
OTHERS, MUST
BE CAPABLE OF
SUPPORTING
500 LBS. MIN.)
4 ø 1.9 (48)
wire inlet
Knock out hole
4-ø 3.5 (90)
wire inlet
Knock out hole
1.6 (41)
2.4
(60)
4.3
(110)
26.8 (680)
22.8 (580)
6.7
(170)
24 (610)
AF-300E$
4.9
(125)
5.3
(134)
2-ø 0.6 (15)
0.7 (18)
43.
3.9
56.3 (1430)
57.1 (1450)
4-ø 0.6 (15)
3
(110)
1.6
(100)
14.2 (360)
4.5 (115)
AF-300E$ Back-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
2503500400030034503800
3003850445035039004300
BRACKET REQUIRED FOR MOUNTING
(75)
(40)
THROUGH PANEL MOUNTING
26 (660)
22.8 (580)
2-M12 0.56
0.4 (10)
4.5 (115)
AF-300E$ Thru-Panel Mounting: Interior Watts Loss
Hp (CT) 0 setting 10 setting Hp (VT) 0 setting 10 setting
2501050120030010351140
3001155133535011701290
56.3 (1430)
55.7 (1415)
BRACKET AREA
(BRACKET
SUPPLIED BY
OTHERS, MUST
BE CAPABLE OF
SUPPORTING
500 LBS. MIN.)
NOTE: Drive includes a separately mounted DC Link Reactor
BRACKET REQUIRED FOR MOUNTING
BACK PANEL
NOTE: Drive includes a separately mounted DC Link Reactor. See Page 4-10 for details
3-14
Keypad Mounting Hole (Panel Cutting)
Dimensions in inches (mm)
3-15
Notes:
3-16
Section 4: Wiring Procedures
WIRING PROCEDURES
REMOVE TERMINAL BLOCK COVER
Remove the terminal block cover as follows
(see Figure 4-1):
1.Remove the screw(s) located at the bottom of the
cover.
2.Press upward on bottom of cover and lift off.
3.See Figure 4-2 for the location of the Main Circuit
Terminal Block and the Control Circuit Terminal Block.
WARNING:
Some printed circuit boards and drive components may
contain hazardous voltage levels. If LED light CRG 1 on the
Base Driver Board is illuminated, hazardous voltages are
present in the drive circuit boards. Remove and lock out
power before you disconnect or reconnect wires, and
before you remove or replace fuses and circuit boards. Do
not attempt to service the drive until the LED indicator has
extinguished and the bus voltage has discharged to zero
CONTROL CIRCUIT WIRING
drive is wired at shipment for operation and frequency
setting through the keypad panel (frequency is set at 60 Hz.)
– See Figure 4-3 & 4-4 for wiring connections.
– See TABLE 4 for description of all terminals.
Make wire connections as shown in Figure 4-4 through 4-6
for desired mode of external operation through control
circuit terminals.
– See TABLE 4 for description of all terminals.
CAUTION:
The control circuit terminal wiring should be kept as far away
as possible from the main power wiring to prevent operational error due to noise interference. Never install both
types of wiring in the same duct or conduit. (A separation
distance of 4 inches [10 centimeters] or more is recommended.) If the control circuit wiring must cross the main
power wiring, it should cross at a right angle.
CAUTION:
volts.
Use shielded or twisted wire for the control circuit wiring
(wiring should be as short as possible, i.e. 65 feet or less [20
meters].) Connect outer covering of the shielded wires to the
drive ground terminal and leave the other end open, but
taped.
Figure 4-1. REMOVING THE FRONT COVER
CAUTION:
Install a supressor in parallel with any relays or solemoid
type coils that may be close to the drive to prevent noise
from causing drive misoperation.
DC RELAY
Figure 4-2.
AC CONTACTOR
4-1
MAIN CIRCUIT WIRING
CAUTION:
Be sure that the power supply is never connected to the U,
3.Connect the 3-phase motor wires to the U, V, and W
V, W terminals or the N, P, DB terminals.
1.Connect the ground terminal as shown in the appropriate view of Figure 4-3 or 4-4. (Do not operate without
the unit being grounded.)
The ground wire must be as large and short as
possible (see TABLE 5 for application wiring list.)
2.Connect the power supply wires to the L1, L2, and L3
terminals of the Main Circuit Terminal Block as shown
NOTE: Motor will rotate counterclockwise when viewed
from the load side when connected normally. If the motor
rotates in reverse direction, interchange any two of the U,
V, or W terminal connections.
in the appropriate view of Figure 4-3 or 4-4. (See
TABLE 5 for description of all terminals and TABLE 4
for recommended wire sizes.)
Control Circuit Terminal
Block
terminals of the Main Circuit Terminal Block as shown
in the appropriate view of Figure 4-3 or 4-4. (See
TABLE 5 for description of all terminals and TABLE 4
for recommended wire sizes.)
* In variable torque applications, Function Code 86 (Motor Hp Capacity) needs to be changed to Set Drive Hp vs. Load Hp.
40 Hp and above is 460-480 VAC input, VT applications only.
1 Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
2 Based on GE Fuji DB resistor designs. Other ratings require careful review.
3 Device ratings such as system coordination, short-circuit rating and type must be carefully reviewed by the user.
Note: Wire size from NEC table 310-16. Copper wire rated 60 Deg. C for 100 amps or less, 75 Deg. C for over 100 amps in 30 Deg. C
ambient and 1.25 times Drive rated amps. These are minimum wire sizes; consult and conform to local and national codes.
CAUTION: The grounding connector shall be sized in accordance with the NEC or Canadian Electrical Code. The connection shall be made
by a UL listed or CSA certified closed-loop terminal connector sized for the wire gauge involved. The connector is to be fixed using the
crimp tool specified by the connector manufacturer.
Recommend GE Spectra RMS MAG-BREAK Circuit Breakers.
CAUTION: Quick-acting bussman JKS or equivalent J-class AC line fuses are required on 30 Hp or lower Drives. Check local electrical code
for 40 Hp and higher.
AW
QTYTERMINAL #FUSESBREAKER
AC-LINE DEVICE
AC-LINE DEVICE
2
2
4-3
Control Terminal Board 1⁄2 - 30 Hp
CAUTION
Remove Jumper from between terminals THR and
CM when thermal interlocks are used.
NOTE
Wiring connections for operation with kaypad
reference control.
CM-FWD and CM-THR terminals are jumpered
together at the factory.
Power Terminal Board
FUSES:
Reference UL power circuit
protection requirements.
Refer to Table 4 on page 4-4.
UL Listed non-time delay fuses
should be used.
✱
* Refer to Dynamic Braking Table on Page 4-16.
NOTE: P1 - P+ terminals are jumpered together at the factory.
Figure 4-4. 1⁄2 - 30 Hp TERMINAL BOARDS
4-4
Control Terminal Board 40 - 300 Hp
CAUTION
Remove Jumper from between terminals THR and CM
when thermal interlocks are used.
CAUTION
Remove jumper from between terminals FWD and CM.
NOTE
Wiring connections for operation with kaypad reference
control.
CM-FWD and CM-THR terminals are jumpered
together at the factory.
Power Terminal Boards
40-75 Hp
100 – 300 Hp
NOTE: A DC Link Reactor is also shipped for connection between terminals P1 - P+, 100 Hp and greater.
Figure 4-5. 40 - 300 Hp TERMINAL BOARDS
4-5
1⁄2 to 30 Hp AF-300E$ Drive Rating
Circuit
Breaker
380/460 VAC
3PH AC
50/60 Hz
L1
L2
L3
Main
Input
Power
U
V
W
Motor
Ground
+
CURRENT
_
Pulse Counter
Speed Pot
1-5K Ohm
REF
4 TO
20 mA
Frequency Meter 10V
(Movable coil type 10V)
_
_
0000
Start
Stop
2W
3
1
+
+
FWD
OFF
REV
FWD
OFF
REV
C1
13
2
+
12
11*
E(G)
P1
P+
DB
N-
Braking Section **
1/2 to 10 HP
P+
DB
12
Braking Resistor
FMA
FMP
FWD
REV
HLD
CM*
X1
X2
X3
X4
FAULT
30A
30B
30C
Y1
Y2
Y3
R-C
Breaking Section
15 to 30 HP
P+
P+
N-DB
N-
Thermal Switch
Power
On
Power
Off
P
P
DB
Customer
supplied
power for
}
contactor
coil
X5
BX
RST
CM*
THR
Y4
Y5
E(G)
CME*
Ground
12
Breaking
Unit
Any additional normally
closed protective interlocks
should be added in series.
12
Breaking
Resistor
*Terminal 11 should not be connected to either CM and/or CME.
** Refer to the Dynamic Braking Table on Page 4-13.
Figure 4-6. 1⁄2 - 30 Hp BASIC CONNECTION DIAGRAM
4-6
40 to 300 Hp AF-300E$ Drive Rating
Curcuit
Breaker
380/460 VAC
460V
3PH AC
50/60 Hz
CURRENT
+
REF
4 TO
_
20 mA
Pulse Counter
VS
Speed Pot
1-5K Ohm
2W
+
FWD
OFF
REV
FWD
OFF
REV
VOLTAGE
REF
0 TO
± VDC
Frequency Meter 10V
(Movable coil type 10V)
_
+
_
0000
Start
Stop
3
2
1
L1
L2
L3
C1
V1
13
+
12
11*
E(G)
FMA
FMP
FWD
REV
HLD
CM*
X1
X2
X3
X4
Main
Power
Input
R0T0
Control
Power
Input
AX
FAULT
U
V
W
P1
P+
N-
30A
30B
30C
Y1
Y2
Y3
***
Braking Unit
Run Relay
Dry Contact
Output
R-C
P+
N
Braking Section **
2
1
Power
On
Motor
Ground
P
DB
2
1
Braking Resistor
Power
Off
Customer
supplied
power for
}
contactor
coil
X5
BX
Y4
Y5
RST
CM*
THR
E(G)
CME*
Any additional normally
closed protective interlocks
should be added in series.
*Terminal 11 should not be connected to either CM and/or CME.
** Refer to the Dynamic Braking Table on Page 4-13
*** DC Link Reactor furnished and mounted external on 100 Hp and higher.
4-7
Table 5:Terminal Identification/Function
TerminalTerminal
LabelNameFunction
POWER TERMINAL BOARD
L1, L2,ac Supply LineConnection for commercial power (200-230 VAC or 380-460 VAC);
L3Input Terminals3-phase; 50⁄60 Hz.
U, V, WDrive OutputConnection for 3-phase induction motor.
Terminals
P+, DBExternal BrakingConnection for external braking resistor.
Resistor Terminals(Only on 10 Hp or less.)
N-, P+External BrakingConnection for external braking resistor via external braking unit.
Unit Terminals(Only required on 15 Hp)
P+, P1DC ReactorConnection for a dc link reactor on unit rated 100 Hp and greater.
These terminals are jumpered on units rated 75 Hp and less.
E (G)Ground TerminalConnection for ground. Note: Be sure to ground the chassis to
prevent electrical shock & to reduce radio noise.
RO, TOControl PowerConnection point for single-phase, 460 ac power for backing up the
Auxiliary Inputcontrol circuit power when input starter is used (40 Hp and greater.)
U1, U2Auxiliary TransformerFactory connection set at U1 for 400 - 460 VAC input.
TapsReconnect to U2 for 380 VAC input. (40 Hp and greater)
CONTROL TERMINAL BOARD
Frequency SettingCommon terminal for terminals 12, 13, C1 & V1, and FMA (Do not
11Common Terminalconnect to CM terminal or electrical noise immunity may be lost.)
12Frequency SettingWhen 0 to +10 VDC (0 to 5V) is input, the maximum frequency is
Voltage Inputreached at +10 VDC (5V) and is proportional to output frequency
down to 0 VDC. Input impedance is 22K ohm. Must be isolated source.
13Frequency SettingRegulated +10 VDC power supply for frequency setting potentiometer,
Voltage Output Term.10mA or less (13 to terminal 11.)
C1Frequency SettingWhen the input signal is +4 to +20mA dc, the maximum frequency is
Current Inputreached at 20mA and is proportional down to a minimum frequency
setting at 4mA. Input impedance is 250 ohm. Must be isolated source.
V1Voltage InputReaches maximum output frequency at +/- 10 VDC (the output
Auxiliary Terminalfreq. is proportional down to 0 VDC.) Input impedance is 22K ohms.
Must be isolated source.
CMControl CircuitCommon terminal for control input commands, and FMP pulse
Common Terminaloutput signal. (Do not connect to terminal 11.)
FWDForward Command
Input TerminalForward command via FWD-CM (closed). Reverse command via
REV-CM (closed). When FWD-CM is closed and REV-CM is closed
Reverse Commandat the same time, the drive will decelerate to stop.
REVInput Terminal
BXMotor Coast-To-StopMotor will coast-to-stop with BX-CM (closed). (For use when
Input Terminalapplying mechanical brake with drive in operation.) Note: If
BX-CM is opened with FWD or REV closed, the drive will start
operating.
Control Terminal Board Cont'd
HLD3-wire Operation -When 3-wire operation is selected and HLD-CM is closed, the pulse
Stop Commandsignal input from FWD, REV terminals is held internally.
(Operation From
Momentary Contacts)
RSTReset Signal InputAfter removal of fault condition, Faults are reset when a momentary
contact closure is made between the RST-CM terminals for more than
0.1 seconds.
NOTE:
will not RESET.
THRExternal thermal tripWith THR-CM (open), OH2 trip will occur and the motor will
commandcoast-to-stop.
NOTE:
thermostat, the THR-CM terminals must be closed or the drive
will not operate. OH2 is a latched fault.
FMAFrequency MeterProvides an output of 0 to +10 VDC (+10Vdc at max. frequency.)
Connection PointsAvailable for connection of a voltmeter (with internal resistance of
Analog10K ohms.) See Function Code 46 for monitoring selection. Meter
connects between terminal FMA & 11. Two (2) voltmeters, each having
an internal resistance of 10KΩ can be connected in parallel.
If there is an input to the FWD and/or REV terminals, the unit
With no external thermal relay or external braking resistor
FMPFrequency MeterPulse frequency output equal to drive output frequency multiplied
Connection Pointsby the set value of Function Code 43. Meter connects between FMP
Pulseand CM.
AX1Run Relay DryContact is closed when the drive is running. (Contact rating
AX2Contact Outputresistive load: 250 VAC, 0.3 Amps.) (Only applicable to 40 Hp and greater)
30AFault Relay OutputDuring normal operation, the relay is not energized and contact is made
30BTerminalsbetween 30B and 30C. When a fault is detected, the relay is energized
30Cand contact is made between 30A and 30C. (Contact rating resistive
When using the circuit shown in Figure 4-8, it is necessary
to connect terminals "RO" and "TO" to the line side of the
MC Contactor.
CAUTION: Do not neglect to make these connections.
If not made, continuous cycling of the MC Contactor may
occur that will stress (or fail) the charge resistor and DC
link capacitors.
CAUTION: The RO and TO terminal control power cannot
be separate or isolated from the main AC power.
AF-300E$
MAIN POWER
INPUT
A DC Reactor is required on all AF-300 drives rated 100 Hp
and above. This reactor is included in the purchase of the
drive and shipped with the drive. This reactor must be
installed or the warranty will be voided.
1.Remove the jumper between the "P+" and "P1"
terminals (if required.)
2.Connect DC Reactor between these terminals as
shown in Figure 4-4 (see Table 4 for wire sizing.)
*
*
* 40 - 300 Hp typical fuse 10 amp
(similar to Gould A60Q10-2)
Figure 4-8. AUXILIARY CONTROL POWER SUPPLY CONNECTION
DETACH THE FACTORY INSTALLED JUMPER (IF REQUIRED)
Figure 4-9. DC LINK REACTOR CONNECTION
(100 Hp AND GREATER)
4-10
Remote Operation
Y1
30B
30A
30C CME Y2 Y4
E
Y2
Y5 C1
12 13 CM
11
FMA FMP
JOG
01=1 (REMOTE)
33JOG ACCEL TIME SETTING
34JOG DECEL TIME SETTING
20JOG SPEED (FREQUENCY) SETTING
X1
FWD
#2
RUN
X2
REV CM
STOP
X3 X4
#1
THR
X5
RST
BX
HLD
NOTE:
CONTACT BETWEEN FWD AND
CM MUST BE OPEN DURING
POWER-UP OR "Er6" TRIP
WILL OCCUR.
Figure 4-10A. REMOTE OPERATION WITH MAINTAINED contacts and JOG FUNCTION (NON-REVERSING)
Y1
30B
30A
30C CME Y2 Y4
Y2
Y5 C1
12 13 CM
11
FMA FMP
#2
X1
FWD
X3 X4
X2
REV CM
#1
THR
X5
RST
BX
HLD
E
JOG
OFF
F
01=1 (REMOTE)
33JOG ACCEL TIME SETTING
34JOG DECEL TIME SETTING
20JOG SPEED (FREQUENCY) SETTING
Figure 4-10B. REMOTE OPERATION WITH MAINTAINED contacts and JOG FUNCTION with reversing capability
JOG REV
R
NOTE:
CONTACT BETWEEN FWD AND
CM MUST BE OPEN DURING
POWER-UP OR "Er6" TRIP
WILL OCCUR.
#1 CAUTION:
REMOVE JUMPER FROM BETWEEN
TERMINALS THR AND CM WHEN
THERMAL INTERLOCKS ARE USED.
Note: Duty Factor is the % of calculated total cycle time NOT to exceed the listed brake time for the total cycle.
Total Cycle Time = ( Brake time Duty Factor)* 100
4-13
Main Circuit Wiring for CE Mark
Connect the power supply of overvoltage category 2 to the main power input terminals L1, L2 and L3 via a
circuit breaker and/or a leakage current breaker. There is no need to match the phase when connecting.
If the power supply is overvoltage category 3, place the devices to limit overvoltage below 2.5 kV as shown.
LI
L2
L3
Isolation Transformer Inverter
Varistor
Surge Absorber
LI
L2
L3
Inverter
Figure 4-13. MAIN CIRCUIT WIRING FOR CE MARK
4-14
Section 5: Drive Operation
Drive Operation
Pre-operation Inspection
After mounting and wiring has been completed, check the
drive for the following items before applying AC power:
—Check for wiring errors (especially main circuit wiring).
—Verify that there are no wiring chips, screws, etc.
remaining in the drive.
—Check that all screw and terminal connections are tight.
—Verify that no exposed wire ends are touching other
terminals.
Keypad Panel Identification
See TABLE 6 for Display and Keypad Operation description
when in the Operation Mode, Program Mode or Trip
Mode.
Function Code and Data Code Description/Selection
When AC power is applied to the drive, the operation panel
display will be as shown in Figure 5-1 and will be flashing on
and off. If the RUN key is pressed at this point, operation
will be at 60 Hertz according to the Function Code set at
the factory. (Use the STOP key to halt operation.)
--A Flashing display indicates the set frequency when a
run command is not present.
Table 6: Keypad and Display Operation Programming
Keypad Panel
NOTE:
"Inv Running" on LCD display indicates Function Code
cannot be changed until drive is stopped.
--A Solid display indicates the actual output frequency
when the drive is running.
If a test run is desired, press the DOWN key to change the
flashing display of 60.00 Hz frequency setting to 5.00 Hz.
Within 4 seconds, press the FUNC/DATA key to set the new
setting into software. Conduct the test run and check for
smooth rotation and correct direction of the motor.
Mode Selection
The Drive has three (3) modes:
(1) Operation Mode:Full operation of Drive.
(2) Program Mode:Drive Function Code settings.
(3) Trip Mode:Drive system faults.
The following is an example of the key functions in the
Programming Method:
(1) Push PRG:set Program Mode
(2) Push UP/DOWN:to move cursor to select a
Function Code
(3) Push FUNC/DATA:displays data setting of selected
Function Code
(4) Push UP/DOWN:changes setting. >> can shift
decimal point
(5) Push FUNC/DATA:to write the data into drive
memory and return to the
Program Mode
(6) Push PRG:return to last display
Figure 5-1. KEYPAD PANEL DISPLAY WHEN AC POWER IS APPLIED
(7) Push PRG:return to Drive Operation Mode
5-1
Program Mode Example of Changing a Function Code
LCD Graphic Display
at Power Up.
STOP
PRG → DATA SET
>> → LED SEL
→
Press PRG Key to
Display Function Codes
00FREQ COMND
01OPR METHOD
02MAX Hz
03BASE Hz-1
→
→
Press DOWN Key to scroll
to Function Code 05,
which is highlighted.
02MAX Hz
03BASE Hz-1
04Rated V-1
05ACC TIME 1
→
Press FUNC/DATA Key to
indicate setting and range of
setting.
05ACC TIME 1
→
Press UP Key to Increase
Accel Time. >> Key Can
Shift Decimal Point.
05ACC TIME 1
6.00S
10.00S
Store F/D KEY
→
→
Setting Blinks until FUNC/DATA
Key is pressed setting it in
Software and returning to the next
screen.
06DEC TIME 1
07TRQ BOOST 1
08ELCTRN OL
09OL LEVEL
→
Press PRG Key to Return to
Operation Mode.
STOP
PRG → DATA SET
>> → LED SEL
6.00S
0.013600
˜
5-2
Program Mode Example of Checking Function Codes (Also Allows Changing Settings)
LCD Graphic Display
at Power Up
STOP
PRG → DATA SET
>> → LED SEL
→
Press FUNC/DATA Key
➪DATA CHECK
I/O CHECK
TRIP IND CK
TRIP FACTOR
→
Press FUNC/DATA Key to
Display Function Code
settings.
000
010
0260 Hz
*0360 Hz
→
*Would indicate a
change from
Factory Setting.
→
Press FUNC/DATA Key to
indicate setting and range
of setting.
05ACC TIME 1
6.00S
0.013600
˜
→
Press UP Key to Increase
Accel Time. >> Key Can
Shift Decimal Point.
05ACC TIME 1
6.00S
10.00S
Store F/D KEY
→
→
Setting Blinks until FUNC/DATA
Key is pressed setting it in
Software and returning to the
next screen.
Press DOWN Key to scroll
to Function Code 05,
which will be highlighted.
0260 Hz
0360 Hz
04OV
056.00S
066.00S
070.0
081
0914.5A
Continue through Function
Codes or Press PRG Key to
Return to Operation Mode.
STOP
PRG → DATA SET
>> → LED SEL
→
5-3
Program Mode Checking Input/Output Signals
LCD Graphic Display at Power Up
STOP
PRG → DATA SET
>> → LED SEL
→
Press FUNC/DATA Key
to Display Program
Mode
➪DATA CHECK
→
I/O CHECK
TRIP IND CK
TRIP FACTOR
→
Press DOWN Key to I/O
Check
→
DATA CHECK
➪I/O CHECK
TRIP IND CK
TRIP FACTOR
→
→
→
FMA=0.0 V
FMP=0.0 V
FMP=0 Hz
→
Press >> Key to Display Operating Time
and Version Numbers.
TIME=Oh
UNIT=S00000
KEYPAD =K00000
→
Press RESET key
to return to I/O
check display.
→
Press PRG Key to return
to Operation Mode.
→
STOP
PRG → DATA SET
>> → LED SEL
Press FUNC/DATA Key to
Display Input Terminal Points.
FWD
REV
HLD
BX
Press >> Key to Display Output
Y1
Y2
Y3
Y4
Press >> Key to Display
Reference Inputs.
12=0.0 V
V1=0.0 V
C1 =4.0 ma
THR
RST
X1
X2
→
terminal points.
Y5
→
X3
X4
X5
: ON
: OFF
→
Press >> Key to Display Output signals.
5-4
Keypad fault indication
LCD Graphic Display at Power Up
→
STOP
PRG → DATA SET
>> → LED SEL
→→
PressFUNC/DATA key to
display Program Mode.
➪DATA CHECK
Press DOWN key to move
cursor toTRIP IND CK.
➪TRIP IND CK
→
I/O CHECK
TRIP IND CK
TRIP FACTOR
→
DATA CHECK
I/O CHECK
TRIP FACTOR
→
Press DOWN key to move
cursor toTRIP FACTOR.
➪TRIP FACTOR
→
DATA CHECK
I/O CHECK
TRIP IND CK
→
FWD
REV
HLD
BX
Press >> key to display output
terminal status.
Y1
Y2
Y3
Y4
Press >> key to display
current and last 3 faults.
THR
RST
X1
X2
→
→
Y5
→
→
0=LV
-1=0H2
-2=0C1
-3=LV
X3
X4
X5
: ON
: OFF
→
Press FUNC/DATA key
The following displays would only be accessible after a fault and
→
before main power is removed.
OC3
LCD graphic display of the trip status.
Fout =.
Fref=.
Iout=.
Vout =
Hz
Hz
A
V
→
Press FUNC/DATA key
→
OC3
LCD graphic display
of the trip factors.
SHOCK LOAD
EXCESS LOAD
TRQ BOOST
▼ SHORT CIRCT
→
→
Press >> key to display
circumstances of trip.
TIME =
TRQ =
TEMP=
→
→
h
%
°C
(*See next page for
Conditions at Fault)
Press >> key to display any
additional trip factors.
▲ GROUND FAULT
→
→
Press >> key to return
to trip status display.
→
Press RESET key to
return to Operation Mode.
STOP
PRG → DATA SET
>> → LED SEL
→
Press >> key to display
input terminal status.
Press RESET key
→
to return to Operation Mode.
5-5
Circumstances of Trip
Press >> key to
TIME =
TRQ =
TEMP=
Conditions at Fault
→
1
F W D
h
%
°C
Exploded view of Circumstances of Trip Display (from previous page.)
1
The above drawing shows the spacing of the display.
23
4
Blank – Normal Operation
Forward Direction
R E V
2
I L
3
U V
V L
4
Reverse Direction
Normal Condition
Current Limit Reached
Normal Condition
Undervoltage Condition
Voltage Limit Reached
Normal Condition
T L
Torque Limit Reached
5-6
Display at a Fault
L U
*
LCD Graphic Display
LED Display on Digital Monitor
UNDER VOLTAGE
F/D → FACTOR
>> → ITEM SEL
RESET
→
Press FUNC/DATA Key to Indicate
Operating Conditions to be reviewed.
→
LOW SUP V
PWR FAILURE
→
Press RESET Key to Reset Fault
and Return to Program Mode.
STOP
PRG → DATA SET
>> → LED SEL
→
→
Press >> Key to Display
Status of the Trip.
Fout =.
Fref=.
Iout=.
Vout =
→
Press >> Key to Display
Conditions of the Trip.
TIME =
TRQ =
TEMP=
Press >> Key to Display
Input Terminal.
→
IL UV
→
→
Hz
Hz
A
V
h
%
°C
→
Press >> Key to
Return to Program Mode.
→
→
Press >> Key to Display last 3
Faults and Current Fault.
→
0=LV
-1=0H2
-2=0C1
-3=LV
*
FWD
REV
HLD
BX
→
Press >> Key to
Display Output
Terminal.
→
Y1
Y2
Y3
Y4
THR
RST
X1
X2
Y5
X3
X4
X5
: ON
: OFF
<
It is possible that a 1 may appear in this column
when a fault occurs. This indicates that multiple
faults occurred at the same time. Press UP key
to acces the second or third fault.
5-7
Accessing Fault History
STOP
PRG → DATA SET
>> → LED SEL
→
Press FUNC/DATA Key to Display
Program Mode.
➪DATA CHECK
I/O CHECK
TRIP IND CK
TRIP FACTOR
→
Press DOWN Key to scroll
to Trip Indication Check.
DATA CHECK
I/O CHECK
➪TRIP IND CK
TRIP FACTOR
→
Press FUNC/DATA Key to
Display the last 3 Faults
and Current Fault.
0=LV
-1=0H2
-2=0C1
-3=LV
→
Press PRG Key to return
to Program Mode.
STOP
PRG → DATA SET
>> → LED SEL
5-8
Notes
5-9
Table 7:Function Code Settings
Function Code Numbers Followed by Function Descriptions
* Function can be changed while the Drive is operating.
Basic Functions
00Frequency Command
01Operation Method
02Maximum Frequency
03Base Frequency 1
04Rated Output Voltage 1
05* Acceleration Time 1
06* Deceleration Time 1
07* Torque Boost 1
08* Electronic Thermal Overload
Relay (Select)
09* OL Level
10Restart After Instantaneous
Power Failure
11* High Limiter
Basic Functions (cont'd)
23* Multistep Frequency
Setting 4
24* Multistep Frequency
Setting 5
25* Multistep Frequency
Setting 6
26* Multistep Frequency
Setting 7
27* Electronic Thermal Overload
Relay (For Braking Resistor)
28* Slip Compensation Control
29Torque Vector Control
30Number of Motor Poles
31* Function Block
(32–41)
Input Terminal Functions
Analog Monitor Output
43* FMP Terminal Pulse Rate
Multiplier
44* FMP Terminal Voltage Adjust
45* FM Terminal Output Voltage
Adjust
46* FM Terminal Function
Output Terminal Functions
47Y1 – Y5 Terminal Function
48* FAR Function Signal
(Hysteresis)
49* FDT Function Signal
(Level)
50* FDT Function Signal
(Hysteresis)
51* OL Function Signal (Level)
52* Function Block
(53–59)
12* Low Limiter
13* Bias Frequency
14* Frequency Setting Signal
Gain
15* Torque Limiter (Driving)
16* Torque Limiter (Braking)
17* DC Brake Starting Frequency
18* DC Brake Level
19* DC Braking Time
20* Multistep Frequency
Setting 1
21* Multistep Frequency
Setting 2
22* Multistep Frequency
Setting 3
32X1 – X5 Terminal Function Select
Acc/Dec Times
33* Acceleration Time 2
34* Deceleration Time 2
35* Acceleration Time 3
36* Deceleration Time 3
37* Acceleration Time 4
38* Deceleration Time 4
Motor #2
39Base Frequency 2
40Rated Output Voltage 2
41* Torque Boost 2
42* Function Block
(43–51)
Frequency Control
53Jump Frequency 1
(Frequency Rejection)
54Jump Frequency 2
(Frequency Rejection)
55Jump Frequency 3
(Frequency Rejection)
56Jump Frequency Hysteresis
57Starting Frequency
(Frequency)
58Starting Frequency
(Holding Time)
59* Frequency Setting Signal Filter
60* Function Block
(61–79)
5-10
LED & LCD Monitor
Special Functions (cont'd)
61* LED Monitor (Function)
62* LED Monitor
(Display at Stop Mode)
63* Coefficient for Line Speed
64* LCD Digital Monitor Selection
Pattern Operation
65Pattern Operation (mode select)
66* (Stage 1)
67* (Stage 2)
68* (Stage 3)
69* (Stage 4)
70* (Stage 5)
71* (Stage 6)
72* (Stage 7)
Motor Characteristics
86Motor 1 (Capacity)
87Motor 1 (Rated Current)
88Motor 1 (No Load Current)
89Motor 2 (Rated Current)
90Motor 1 Impedance
(Tuning)
91* Motor 1 Impedance
(% R1 Setting)
92* Motor 1 Impedance
(% X Setting)
Special Functions
93Dedicated Function for
Manufacturer
94Dedicated Function for
Manufacturer
73Accel/Decel Pattern
Special Functions
74N/A
75Energy Savings
76Reverse Phase Sequence Lock
77Data Initializing (Data Reset)
78* Language
79* LCD Display (Brightness)
80* Function Block
(81–94)
81* Motor Sound
82Auto Restart (Restart Time)
83Fall Rate
95Data Protection
84* Auto Reset (Times)
85* Auto Reset (Reset Interval)
5-11
Notes
5-12
LCD
Section 6: Function Code Descriptions
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
GRAPHICFACTORY
BASIC FUNCTIONS
NOTE: * = Function can be changed while the Drive is operating.
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTION SETTING
00FREQ COMNDFREQUENCY COMMAND 0
Frequency reference can be supplied by
three different methods: Keypad
(digital), 0 to +10 VDC, 4 to 20 mA.
01OPR METHOD
0:
1:
2:
0:
1:
2:
Keypad operation (Digital setting with
/\ or \/ keys).
0 to +10 VDC analog signal (terminal 12),
or a speed potentiometer connected to
terminal 11, 12 and 13.
Sum of 0 to +10 VDC (terminal 12) and 4 to
20 mA (terminal C1).
NOTE : Drives 40HP & greater can use a 0
to + 10 VDC analog signal input (terminal V1) which is summed with the
0 to +10 VDC input.
OPERATION METHOD 0
RUN, STOP, and RESET commands can be
supplied by two different methods: Keypad
(local) or terminal strip (remote).
toggled by pressing RESET and STOP
keys simultaneously when the
drive is in the STOP condition.
NOTE: Contact between FWD or REV and CM must
be open during power-up or "Er6" trip
will occur.
6-1
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
02MAX HzMAXIMUM HERTZ60
Maximum output frequency is adjustable from
50 Hz to 400 Hz in 1 Hz steps.
V
Maximum frequency
WARNING: Review motor capabilities for operation above motors's base frequency.
03BASE Hz-1
04RATED V-1
* 05ACC TIME 1
BASE FREQUENCY #160
Base frequency for motor #1 is adjustable
from 30 Hz to 400 Hz in 1 Hz steps.
(30 to 120 Hz, 40 Hp & above, var. torque loads.)
WARNING: Review motor capabilities for operation above motors's base frequency.
RATED VOLTAGE #1230
Maximum output voltage for motor #1 is(460)
adjustable from 80 to 240 VAC (230V
Drives), or 320 to 480 VAC (460V
Drives)
NOTE: On 30 Hp and lower when set at zero (0),
the maximum output voltage will follow the
AC line input. Function Code 29 setting
will affect this Function Code.
ACCELERATION TIME #16.0
Acceleration time #1 is adjustable from (30HP and less)
0.01 to 3600 seconds. Note that this20.0
setting defines the time to accelerate from (40HP and greater)
zero to maximum frequency (Function Code 02).
Smaller frequency steps will result in shorter
acceleration times because the rate is
constant.
Example: ACC TIME 1 = 10 seconds
MAX Hz = 60
The acceleration rate is 6 Hz/sec, therefore a
step from 8 to 42 Hz would take (42-8)/6 =
5.6 seconds.
* 06DEC TIME 1
DECELERATION TIME #16.0
Deceleration time #1 is adjustable from (30HP and less)
0.01 to 3600 seconds. Rules are the same20.0
as for Function Code 05 except that a (40HP and greater)
setting of zero (0) causes the motor to coast
down until it reaches the new set point.
(Available up to 30 HP only)
6-2
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 07TRQ BOOST1TORQUE BOOST #12.0
Torque boost for motor #1 can be set to
optimize the V/Hz characteristics of the
drive according to the type of load the
motor will see. The factory setting of
zero (0) causes the drive to automatically select the boost level according to
its torque calculations
0.0:
0.1 - 0.9
1.0 - 1.9:
2.0 - 20:
Automatic
Variable torque loads (Fans)
Proportional torque loads (Machine tool spindle)
Constant torque loads (Conveyor)
NOTE : Function Code 29 setting will affect this
Function Code.
Volts
Hz
1.0 - 1.9
0.1 - 0.9
2.0
Base Frequency
20.0
2.1
0
CAUTION: When using Automatic (0.0 setting) be sure Function Codes
87 & 88 are set for the connected motor. With the motor connected,
not rotating, and with load disconnected, if possible, activate Function
Code 90 (Tuning) to reset Function Code 91 & 92.
* 08ELCTRN OL
ELECTRONIC OVERLOAD1
The Drive's Electronic Overload can be selected to
help protect the motor from thermal overload due to
various operating conditions. Selection should be
based on operating conditions, type of load, motor
thermal characteristics and the applicable NEC and
local electrical code requirements.
The motor thermal characteristics and the diagram
shown in Function Code 09 should be reviewed, and
their characteristics coordinated, to determine what
is the protection level available with the drive/motor
combination, and what additional protection will be
required. (Refer to Function Code 09.)
0:
1:
Inactive (Internal thermal overload device)
Active (Review motor thermal characteristics)
2:Special factory setting (Consult Company)
6-3
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
Forced air cooled mo
* 08(cont'd)NOTE: If the carrier frequency is set higher
than 10 KHz and an internal overheating
condition occurs, the drive will automatically reduce the carrier frequency to
10 KHz in order to avoid an overheating
fault (available up to 30 Hp only).
* 09OL LEVEL
OVERLOAD LEVELRATED
The overload level for the electronicCURRENT
overload protection algorithm (see Function
Code 08) can be adjusted from the factory
default setting of rated drive nameplate amps.
For example, if a 20 Hp/30A motor were
applied to a 30 Hp/45A drive, you would
change Function Code 09 from 45 to 30 amps to
protect the motor. The setting range is
approximately 20 to 135% of rated drive current.
Minutes
10
7
5
3
2
1
0
20 40 60 80 110 120 140 160 180 200
% of Drive Current Rating
60 Hz or more
10Hz
20 Hz
10RESTART
RESTART 0
The AF-300E$ family of Drives are
designed to tolerate an AC line voltage dip
to 165V (230 VAC), 310V (230 VAC),
400V (575 VAC) 70% for 15 msec at 85% of full load
without any disturbance in output power delivered
to the load. However, in the event of a more
serious power dip or outage, the drive may
act in one of five ways depending on the
setting of this Function Code.
6-4
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
10(cont'd)0 :Restart inactive - Drive will trip and
alarm when low voltage point is detected.
1:
Restart inactive - Drive will trip but
will not alarm until voltage recovers.
2:
Restart active - Normal smooth recovery
method: drive will continuously decrease
speed until voltage recovers, then accelerate
normally back to
3:
Restart active - Drive stops (motor coasts)
set point.
when low voltage detected, then restarts from
set frequency when power returns.
4:
Restart active - Drive stops (motor coasts)
when low voltage detected, then restarts at
starting frequency when power returns.
* 11H LIMITERHIGH FREQUENCY LIMITER 70
The high frequency limiter sets a clamp
on the maximum drive output frequency
regardless of the frequency
reference setting. Adjustable from 0 to 400 Hz.
* 12L LIMITER
LOW FREQUENCY LIMITER 0
The low frequency limiter sets a clamp
on the minimum drive output frequency
regardless of the frequency
reference setpoint. Adjustable from 0 to 400 Hz.
100%
Output
Frequency
Low Limiter
High Limiter
Starting
Frequency
Frequency Setting Hz
NOTE: If L Limiter is set higher than H
Limiter, the H Limiter setting takes
priority. If set frequency is higher
than H Limiter, the H Limiter takes effect.
6-5
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 13FREQ BIASFREQUENCY BIAS 0
Frequency bias is an offset which is
added to the frequency set point when an
analog reference is selected. This will
allow for improved resolution when adjustment over the entire speed range is not
required. Adjustable from 0 to 400 Hz.
100%
Output
Frequency
Bias
Frequency Setting 100%
WARNING: Bias is operational only when
frequency setting method is analog (Function
Code 00 = 1 or 2). When the drive does
not have a run command, the reference or
output flashes on the display (see Function
Code 62). When bias is operational and the
speed reference is zero, the display flashes
bias frequency. When a RUN command is given,
the motor runs at the bias setting.
6-6
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 14FREQ GAINFREQUENCY GAIN100.0
Frequency gain is a multiplier on the
frequency set point when an analog reference is selected (100% equals unity gain).
Adjustable from 0 to 200%.
100%
70%
Output
Frequency
* 15DRV TORQUE
Set Signal 100%
(Gain 70% Example)
NOTE: Frequency gain is operative only when
DRIVING TORQUE999
This limit puts a hard clamp on the amount
of torque which the drive will provide
in the driving direction (i.e. delivering
power). It is set as a percentage of rated
torque and is adjustable from 20 to 180%.
Setting this Function Code to 999 will remove
the limit. This Function Code can be used to
avoid the breakdown torque region of the
motor (see related Function Code 86 concerning
motor capacity.)
200%
100%
Output
Frequency
(Gain 200% Example)
frequency setting method is analog
(Function Code 00 = 1 or 2).
CAUTION: If this Function Code is set too low when compared to the actual load
requirement, the motor may not accelerate.
6-7
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 16BRK TORQUEBRAKING TORQUE999
This limit puts a hard clamp on the amount
of torque which the drive will provide
in the braking direction (i.e. absorbing
power). It is set as a percentage of rated
torque and is adjustable from 20 to 180%.
Setting this Function Code to 999 will
remove the limit.
A setting of zero (0) will activate automatic deceleration control. This feature
will decelerate according to programmed rate
unless the absorption capability of the Inverter is exceeded. Normally this would result
in a dc link overvoltage fault (OU2) but automatic deceleration control will stop deceleration long enough to avoid tripping. This
feature should not be used if smooth decel
torque is a requirement. Instead set torque
limit according to dynamic braking capability
and deceleration time proportionate to load
inertia to avoid overvoltage faults.
CAUTION: Setting this Function Code too low when compared to actual load
requirement could cause the motor to decelerate slower than the decel time setting.
If motor decel exceeds three (3) times the decel time setting, Torque Limiter
(Braking) will be ignored.
* 17DC BRK Hz
* 18DC BRK LVL
DC INJECTION BRAKE STARTING Hz0.0
DC injection braking can provide an effective
means of stopping the motor, especially after
the motor has already reached a low speed
This setting determines the frequency at which
dc braking takes affect during a deceleration.
Adjustable from 0 to 60 Hz. (See related
Function Codes 18 and 19).
DC INJECTION BRAKE LEVEL (STRENGTH)0.0%
The dc injection braking level is adjustable
from 0 to 100%. Note that the actual braking
strength is dependent on the motor characteristics. (See related Function Codes 17 and 19.)
6-8
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 19DC BRK tDC INJECTION BRAKING TIME "ON"0.0S
The dc injection brake time is adjustable
from 0.1 to 30.0 seconds using this setting.
A setting of zero (0) causes dc braking to be
inactive.
Output
Frequency
Brake Start
Frequency
Brake
Output
Voltage
Time
Brake
Voltage
CAUTION: Use care when applying dc braking as motor
currents & temperatures can build up to very high levels in
a short period of time possibly resulting in motor damage.
MULTI STEP FREQUENCIES
Seven (7) digitally preset speeds can be programmed into Function Codes 20 through 26.
These can be used as part of a pattern operation (see Function Code 65) or individually selectable
through switching of control terminals X1, X2, and X3 (see Function Code 32.)
* 20MULTI Hz-1
* 21MULTI Hz-2
* 22MULTI Hz-3
* 23MULTI Hz-4
* 24MULTI Hz-5
* 25MULTI Hz-6
MULTI STEP FREQUENCY #10.0
MULTI STEP FREQUENCY #20.0
MULTI STEP FREQUENCY #30.0
MULTI STEP FREQUENCY #40.0
MULTI STEP FREQUENCY #50.0
MULTI STEP FREQUENCY #60.0
* 26MULTI Hz-7
MULTI STEP FREQUENCY #70.0
(Relationship between the terminals and multi-step frequency 1 to 7)
CM are all OFF, frequency reference is
set by keypad (/\ \/ keys) or by the
analog inputs per Function Code 00 setting.
–A setting in Function Code 20 through 26
above the maximum frequency in Function
Code 02 is NOT possible.
–When Function Code 65 equals 1, 2, or 3,
pattern operation is active.
DYNAMIC BRAKING RESISTOR OVERLOAD 0
The drive has a pre-programmed electronic (15 Hp and UP)
thermal overload protection function for the 1
dynamic braking resistors for Drives rated (UP TO 10 Hp)
10 Hp and below. Drives rated 15 Hp and
above, or for non-standard braking resistor
packages, use a thermal overload sensing
device.
0:
Inactive (15 Hp and greater or non-standard
DB resistors)
1:
Active (for internal braking resistor, up to
10 Hp.
6-10
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 28SLIP COMPSLIP COMPENSATION0.0
Slip compensation provides a means of
improving speed accuracy without employing
speed feedback (i.e. open-loop method). It
does this by adjusting output frequency as a
function of load and can be expected to improve speed fluctuations to within 1/3 of
normal slip. Adjustable from -9.9 Hz to +5 Hz.
NOTE:Function Code 29 setting will affect this
Function Code.
Example: A 4 pole motor is nameplated at a full load
speed of 1740 RPM for 60 Hz operation.
Therefore,
w
= 60 Hz x 120 (Constant) = 1800 RPM
sync
4 Poles
29TRQ VECTOR
Slip = 1800 - 1740 = 0.0333
1800
Slip Freq = 0.0333 x 60 Hz = +2.0 Hz setting
at Function Code 28.
Note that slip compensation can also be less
than zero. A negative setting has the effect
of reducing speed fluctuations in the presence
of overhauling loads. A negative setting might
also be used when trying to get two motors with
a common shaft to load share better.
TORQUE VECTOR CONTROL0
Sensorless torque vector control is a recently
developed control strategy which provides much of
the performance of AC flux vector drives without the
cost of an expensive motor mounted encoder. The
algorithm uses knowledge of motor parameters (see
Function Codes 90 through 92) to adjust voltage and
current in a way which optimizes motor torque under
all operating conditions.
0:
1:
Inactive
Active (SINGLE MOTOR APPLICATIONS ONLY)
NOTE: If this Function Code is set (i.e. active) it
will affect the following function codes as follows:
-Function Code 04 (Rated Voltage)
If “0” (Free) is set, the following will apply:
230 VAC Drives, 230 VAC maximum output
6-11
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
29 (cont'd)460 VAC Drives, 460 VAC maximum output
voltage to motor #1.
If a value other than “0” is set then value will apply.
-Function Code 07 (Torque Boost)
Automatic torque boost will always apply even if
a value other than “0.0” is set.
-Function Code 28 (Slip Compensation)
If “0.0” (no slip compensation) is set, the slip
compensation for a 4-pole GE Energy $aver®
motor will be used.
If a value other than “0.0” is set then that value
will apply.
Torque vector control will not work correctly if more
than one motor is to be driven from one drive or if
the motor does not have either 2, 4, or 6 poles. If
either of these situations apply, torque vector control
should be made inactive. If the motor cables exceed
164 feet (50m) in length, or if filters or reactors are
connected between the drive and the motor, the autotune feature (see Function Code 90) may not be able
to measure the motor parameters accurately enough
to provide the specified performance. However, torque
vector control may still be used if performance is
adequate for the application.
For your convenience we have pre-installed the
parameters for the 4-pole GE Energy $aver® motor
with horsepower rating corresponding to the drive
rating. If you are using any other motor you should set
Function Code 04 (Rated Voltage #1) and Function
Code 28 (Slip Compensation) per the motor's nameplate and use Function Code 90 (Motor Tuning) so the
drive can learn the motor's equivalent circuit parameters (Function Code 91 and 92.)
WARNING: An incorrect setting in Function Code 87 (Motor Full Load Current),
Function Code 88 (Motor No Load Current), Function Code 91 (% Motor Resistance),
and Function Code 92 (% Motor Impedance) will cause an error in the torque
calculation. This could result in motor hunting or abnormal vibration. If a STOP
command is applied, the motor could decel at a slow rate and if that rate exceeds
three (3) times the decel time setting, Torque Limiting (Braking) setting, Function
Code 16, will be ignored.
6-12
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
30MTR POLESMOTOR POLES 4
The number of motor poles is set only for
the display of synchronous RPM. It has NO
effect on drive operation. Adjustable from
2 to 14 (even numbers only).
Example: When a 4 pole motor is operated at 60
Hz, the synchronous RPM display should read
60 x 120/4 = 1800 RPM.
Recall, synchronous speed (in RPM) =
# poles
Hz x 120(Constant)
* 31 32-41FUNCTION CODE BLOCK DISPLAY0
This setting determines whether or not
Function Codes 32 through 41 will be displayed
and available for adjustment.
0:
1:
Function Codes 32 through 41 NOT displayed.
Function Codes 32 through 41 displayed.
INPUT TERMINAL FUNCTIONS
32X1-X5 TERMX1 THROUGH X5 TERMINAL FUNCTIONS0000
This Function Code determines the functions
of the X1 through X5 contact inputs on the
terminal block. It is adjustable from 0000
to 2223. Each of the four digits has a
separate meaning as defined below.
X1 and X2 - function selected by 1st digit:
0 - - 1 - - 2 - - -
Multistep speed selection (four steps)
UP/DOWN control 1 (start from 0 Hz)
UP/DOWN control 2 (start from previous
setting).
- 0 - -
- 1 - -
- 2 - -
X3 - function selected by 2nd digit:
Multistep speed selection (8 steps using
X1, X2, and X3).
Switching operation from line to drive
(50 Hz)
Switching operation from line to drive
(60 Hz)
6-13
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
32 (cont'd)
X4 - function selected by 3rd digit:
- - 0 -
- - 1 -
- - 2 -
ACC/DEC time selection (two steps)
Selects 4 to 20 mA as an input for
frequency reference at terminal (C1) (will ignore
speed pot, V1 inputs and keypad)
DC brake command (can be used to maintain
stopped motor rotor position - see diagram and
notes)
Output
Frequency
DC Brake
Frequency
DC Brake
FWD-CM
X4-CM
NOTES:– Strength of the dc brake is set by
Function Code 18.
Operation command takes precedence
(RUN, FWD, REV) (While X4 to CM is
ON, if FWD to CM is ON: dc brake reset.
– As dc current continues to flow to the
motor during the X4 to CM - ON period,
be careful of motor temperature rise. (When
long periods of dc braking are required
measure the motor's temperature continuously).
– DC brake time (Function Code 19) is ignored.
CAUTION: Motor may overheat if the dc brake is left ON for too long.
6-14
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
32 (cont'd)
ACCEL/DECEL TIMES
X5 - function selected by 4th digit:
- - - 0
- - - 1
- - - 2
- - - 3Restart Function
ACC/DEC time selection (four steps
using X4 and X5)
Select motor #2 Function Codes
Function Code 03 to Function Code 39
Function Code 04 to Function Code 40
Function Code 07 to Function Code 41
Function Code 87 to Function Code 89
(This would
applications where a second motor
can be connected to the drive with
mechanical switchgear.)
Selects data protection mode (only
Function Code 95 can be changed)
X5 to CM contacts open - Protected (Change prevented)
X5 to CM contacts closed - Not Protected (Changeable)
NOTE: In order to bypass GE Safety software
(Er6), select "3" and install a wire jumper between
Terminal X5 and CM.
ONLY be useful for
* 33ACC TIME 2ACCELERATION TIME #210.0
Adjustable from 0.01 to 3600 seconds. (30Hp and less)
(40 Hp and
greater)
* 34DEC TIME 2
greater)
* 35ACC TIME 315.0 (30Hp and less)
* 36DEC TIME 315.0 (30Hp and less)
* 37ACC TIME 43.0 (30Hp and less)
* 38DEC TIME 43.0 (30Hp and less)
DECELERATION TIME #210.0
Adjustable from 0.01 to 3600 seconds. (30Hp and less)
(40 Hp and
NOTE: 100 Seconds for 40 Hp and greater.
Acceleration/Deceleration times 2 through 4
are identical in behavior to Function Codes
05 and 06 respectively. They can be activated
via the X4 and X5 terminals as explained for
Function Code 32 and the following chart.
Adjustable from 0.01 to 3600 seconds.
100 (40 Hp and greater)
100 (40 Hp and greater)
100 30 Hp and greater)
100 (40 Hp and greater)
100
100
6-15
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
MOTOR #2
NOTE: Motor #2 is a second motor NOT multi-motor.
39BASE Hz-2
40RATED V-2
* 41TRQ BOOST2
BASE FREQUENCY #2 60
Base frequency for motor #2 is adjustable
from 30 Hz to 400 Hz in 1 Hz steps. Motor
#2 Function Codes become active when Function
Code 32 equals - - 1 and X5 – CM contacts are
closed.
(30 Hz to 120 Hz, 40 Hp & above, var. torque loads.)
WARNING: Review motor capabilities for operation above base frequency.
RATED VOLTAGE #2230
Maximum output voltage for motor #2 is(460)
adjustable from 80 to 240 V (230 V Drives)
or 320 to 480 V (460 V Drives). Motor #2
Function Codes become active when Function
Code 32 equals - - - 1 and X5 – CM contacts
are closed.
NOTE: When set at zero (0), the maximum
output voltage will follow the input
AC line voltage. (30 Hp & lower only)
TORQUE BOOST #22.0
Torque boost for motor #2 can be set to
optimize the V/Hz characteristics of the
drive according to the type of load the
motor will see. Motor #2 Function Codes
become active when Function Code 32 equals
FUNCTION CODE BLOCK DISPLAY 0
This setting determines whether or not
Function Code 43 through 51 will be
displayed and available for adjustment.
Function Code 43 through 51 NOT displayed.
Function Code 43 through 51 displayed.
6-16
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
ANALOG MONITOR OUTPUT
* 43FMP PULSESFMP FREQUENCY PULSE OUTPUT24
The FMP terminal provides a pulse whose
output is proportional to drive output
frequency. The number of pulses per
second is given as output Hz multiplied by
the setting in Function Code 43 with a
maximum output of 6,000 pulses per second.
Function Code 43 is adjustable from 6 to
100. The output frequency is accurate to
within ±1 %. Ex: 60Hz, setting 24 – 60x24 = 1440 pulses.
* 44FMP V-ADJ
* 45FMA V-ADJ
FMP VOLTAGE ADJUST100
The average voltage of the FMP terminal
pulsed output can be adjusted from approximately 5 to 12 VDC by changing Function Code
44 from 50 to 120, respectively. The voltage
will be accurate to ±5%. The peak voltage
of the pulses will be approximately 15.6 VDC
regardless of this setting, only the average
output voltage is changed. Ex: V
= 12V x 100 setting = 10V
avg.
120
CAUTION: The minimum load impedance which should be
placed between the FMP and CM terminals is 5,000 ohms.
FMA VOLTAGE ADJUST100
The FMA terminal provides a 0 to +10 VDC
analog output which can indicate output
frequency, current, torque, or power (see
Function Code 46). This Function Code can
be used to adjust the voltage output by a
factor of 0.65 to 2.00 (note that the maximum available output is 10.3 VDC).
Adjustable from 65 to 200% for 10.3VDC output.
FMA
Adjustment
Range
11
6-17
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 46FMA FUNCFMA OUTPUT INDICATION0
This Function Code selects the quantity
to be displayed via the analog output
between the FMA and II terminals.
0:
1:
2:
3:
Output frequency (0 to 100% full scale)
Output current (0 to 200% full scale)
Output torque (0 to 200% full scale)
Output power (0 to 200% full scale)
CAUTION: The load impedance placed between
the FMA and 11 terminals should be a minimum
of 10,000 OHMS.
OUTPUT TERMINALS
47Y1-Y5 TERMY1-Y5 OPEN COLLECTOR OUTPUT TERMINALS01234
This Function Code determines the functions
of the Y1-Y5 open collector outputs on the
terminal block. It is adjustable from 00000
to FFFFF. Each of the five digits can be set
to one of the following selections to configure
its corresponding output.
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
A:
B:NOT USED.
C:
D:
Drive running (RUN), see Function Code 57.
Frequency at reference (FAR), see Function
Code 48.
Frequency level detection (FDT), see Function Codes 49 and 50.
Overload early warning (OL), see Function
Code 51.
Undervoltage detection (LU).
Keypad operation mode.
Torque limiting, see Function Codes 15 and 16.
Drive stopped (STOP).
Auto-restarting, see Function Code 10.
Auto-resetting.
Initializing restart timer, picks up when power returns.
Time-up signal (TP) for pattern operation,
picks up when changing to a new stage.
Cycle completion signal (TO) for pattern
operation, picks up at completion of stage 7,
see Function Code 65.
NOTE: Auto Restart, setting of A, requires two (2)
wire maintained contacts (see Pg. 4-14).
Auto Reset requires three (3) wire start/stop.
Auto restart and auto reset cannot be activated
at the same time.
6-18
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
47 (cont'd)EStage number indication for Pattern Operation,
requires Y3, Y4, and Y5 outputs, set Function
Code 47 equal - - EEE.
Stage
F
Alarm indication in alarm trip mode,
Y3
Y4
1
Off
Off
Off
On
On
On
On
Off
On
On
Off
Off
On
On
2
3
4
5
6
7
On
Off
On
Off
On
Off
On
Y5
requires Y2, Y3, Y4, and Y5 outputs, set
Function Code 47 equal - FFFF.
Terminal
Cause of trip
0OffOffOffOff
1OC1OffOffOffOn
2OC2OffOffOnOff
3OC3 and EFOffOffOnOn
4OU1, OU2, OU3OffOnOffOff
* 48FAR HYSTRFREQUENCY AT REFERENCE HYSTERESIS (WIDTH)2.5
The signal is on when the output frequency
equals the frequency reference’s set point.
This is an open collector output and can be
used in conjuction with a relay unit to allow
connection to system control circuitry.
Adjustable from 0.0 to 10 Hz in 0.1 Hz steps.
Far
Hyster
Far
Hyster
* 49FDT LEVEL
t
Far
Signal
FREQUENCY DETECTION THRESHOLD60
The signal is on when the output frequency
exceeds the detection level setting. This
is an open collector output and can be used
in conjuction with a relay unit to allow
connection to system control circuitry.
Adjustable from 0 to 400 Hz.
6-20
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 50FDT HYSTRFREQUENCY DETECTION HYSTERESIS1.0
The setting is the offset that FDT will
have from the FDT level. Adjustable from
0.0 to 30 Hz.
* 51OL WARNING
* 52 53-59
Output
Frequency
Hz
FDT
Signal
0
FDT Hyster
OVERLOAD EARLY WARNING RATED
This open collector output is active whenCURRENT
the output current exceeds the OL setting.
This output can be used in conjunction with
a relay unit to allow connection to system
control circuitry. Adjustable from approximately 20 to 135% of drive rated current.
NOTE: This is a timed function similar to
Function Code 08 and 09 (ELCTRN OL).
FUNCTION CODE BLOCK DISPLAY0
This setting determines whether or not
Function Codes 53 through 59 will be displayed
and available for adjustment.
FDT Level
t
0:
1:
Function Codes 53 through 59 NOT displayed.
Function Codes 53 through 59 displayed.
6-21
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
FREQUENCY CONTROL
These Function Codes are used to avoid the
natural mechanical vibration of the load.
The three jump frequencies can be set
independently and are adjustable from 0 to
400 Hz.
53JUMP Hz-1
54JUMP Hz-2
55JUMP Hz-3
FREQUENCY JUMP SETTING0
FREQUENCY JUMP SETTING0
FREQUENCY JUMP SETTING0
Output
Frequency
Hysteresis
Hysteresis
Jump
Frequency 2
Hysteresis
Jump
Frequency1
Setting Frequency
Jump
Frequency 3
t
56JUMP HYSTR
FREQUENCY JUMP HYSTERESIS3
This setting determines the hysteresis
(jump width) of the jump frequency setting.
Adjustable from 0 to 30 Hz.
Example: Function Code 53 set at 20 Hz, Function
Code 56 set at 4 Hz. Output frequency will reach
18 Hz, jump to 22 Hz and continue ramping if input
reference is set above 20 Hz. On a decel, output
frequency will reach 22 Hz and jump to 18 then
continue to decel.
6-22
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
57START HzSTART FREQUENCY0.5
Starting frequency set range is adjustable
from .2 to 60 Hz (used to optimize available
starting torque.)
Output
Frequency
Start Freq.
0.2 to 60 Hz
Holding time
0 - 10 sec.
58HOLDING t
* 59FILTER
* 60 61-79
START FREQUENCY HOLD TIME0.0
A starting frequency and holding time can
be set that is suitable for the starting
torque characteristics of the load. Function
Codes 57 and 58 are only effective from a
START command. Adjustable from 0.0 to 10.0
seconds. This function will also operate when
Pattern Operation has been selected using
Function Code 65, and includes the timer's time.
REFERENCE SIGNAL FILTER0.05
This Function Code is used to set the time
constant for the input filter in order to
eliminate the effects of noise present in
the analog signals (voltage and current
references). If the time constant set point
is too long, the response to changes in analog
commands will become inadequate for the
required performance level. Adjustable from
0.01 to 5.00 seconds.
FUNCTION CODE BLOCK DISPLAY 0
This setting determines whether or not
Function Codes 61 through 79 will be
displayed and available for adjustment.
0:
1:
Function Codes 61 through 79 NOT displayed.
Function Codes 61 through 79 displayed.
6-23
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
LED & LCD MONITOR
* 61LED MNTR 1LED MONITOR SELECTION #10
Setting from 0 to 8 for a total of nine (9)
selectable indicating modes. See table below:
displays changes to indication below if speed is changed
Setting Motor Speed
(w/o slip)
This setting determines the LED display
in the STOP Mode of operation.
0:
1:
* 63SPEED COEF
Setting value
Output value
MOTOR POLE SPEED CONVERSION COEFFICIENT0.01
The LED display for machine speed and line speed
can be changed by setting this Function Code.
Output Hz indication multiplied by this value
will be shown on the LED display. Adjustable
from 0 to 200.
Unit
r/min
6-24
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 64LCD MNTRLCD GRAPHIC DISPLAY SELECTION0
LCD GRAPHIC DISPLAY is selectable from the
the following:
0:
RUN or STOP
RUN STOP
Prg ➮ DATA SET Prg ➮ DATA SET
>> ➮ LED SET >> ➮ LED SET
1:
Bar graph (set frequency and output frequency)
Stop
Hz
100%
Hz
100%
F
ref /F out
2:
Bar graph (output frequency and output current)
Stop
Hz
100%
A
200%
F
out /I out
3:
Bar graph (output frequency and motor torque)
Stop
Hz
100%
%
200%
F
out /Trq
6-25
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
PATTERN OPERATION
65PATTERNPATTERN OPERATION0
A pattern operation can be set for seven
(7) individually set speeds (Function Codes
20 through 26) to run up to 6,000 seconds
each, forward or reverse direction (Function
Codes 66 through 72) with the following choice
of cycles:
0:
1:
2:
3:
* 66STAGE 1
* 67STAGE 2Each of the pattern operation’s seven (7)
* 68STAGE 3stages can be set based on the following
* 69STAGE 4codes that includes direction of rotation,
* 70STAGE 5selection of acceleration/deceleration
* 71STAGE 6times (Function Codes 5, 6, 33 through 38),
* 72STAGE 7and a maximum duration running time of 6,000
Inactive
Single cycle
Continuous cycle (repeating)
Single cycle with continuous seventh speed
15:00 -Run time is 15 seconds to
include accel rate.
F2 -Foward direction, ACC2/DEC2
timing set in Function Codes
33 and 34.
NOTES: –If a stage’s timer is set at 0.00,
it will be skipped.
– /\ or \/ keys select the direction of
rotation, rate of acceleration and deceleration, and length of pattern stage run
time. The SHIFT >> key selects the digit of
the run time to be set using the /\ or \/ keys.
6-26
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
65Pattern Operation (cont’d)
NOTES : – When Function Code 65 is set
to 1, 2 or 3, pattern operation is made
possible by setting the multi-step
frequency combination of stages 1 through 7
(Function Codes 66 through 72).
– When in the pattern operation,
frequency changeover via the X1, X2 and X3
terminals is not required.
– Pattern operation switches to set
frequencies 1 through 7 in ascending numerical
order only.
Stage 4
Time
Stage5
Stage 5
Stage 1
Time
Stage1
Stage 2
Time
Stage2
Stage 3
Time
Stage 3
Time
Stage 4
– To set motor’s direction of
rotation and acceleration/deceleration time,
utilize Function Codes 66 through 72.
– If each subsequent frequency is
higher or lower than the present frequency, the
acceleration or deceleration time will be automatically selected based on the Stage setting
(Function Codes 66 through 72).
Time
Stage6
Stage 6
Time
Stage7
Stage 7
6-27
LCDGRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
Example 1: when Function Code is 67 (stage 2) 5.00 F1.
f
f
Stage 2
Stage 1
t
Example 2: when Function Code is 67 (stage 2) is set at 5.00R1.
f
Forward
Stage 1
Stage 1
Stage 2
t
t
Reverse
Stage 2
05
Function Code 05 setting
Acceleration Time
Function Code 06 setting
Deceleration Time
06
The timer’s setting includes the time required for the
motor to accelerate or decelerate to the set frequency.
Therefore, if the time set on the timer is less than
the time required for the acceleration/deceleration
conditions, it will proceed to the next process, before
the original set frequency is reached.
Output
Frquency
Stage 1
Stage 2
Stage 2
Timer
Required acceleration
time due to load
6-28
t
LCDGRAPHICFACTORY
Pattern Operation Method #1: Keypad Panel
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
The key functions are changed as follows:
RUN key: Start operation
STOP key: Temporary stop of drive
operation (pause)
RESET key: Resets pattern to original
starting point.
The next RUN input will start operation from
pattern stage 1.
Output
Frequency
Stage 1
Stage 2
NOTE: The RESET key only functions when the drive is stopped or paused.
Stage 4
Stage 3
Stage 5
Output
Frequency
Stage 6
Stage 7
Stage 1
t
During this span
time is not
counted
Remaining
operation time
for Time 1
Stage 2
Output
Frequency
RUN
Stage 1
Stage 2
STOP
RESET
6-29
RUN
RUN
STOPRUN
Stage 3
Stage 2
Stage 1
LCD
PATTERN OPERATION METHOD #2: CONTROL TERMINAL BOARD
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
GRAPHICFACTORY
“REMOTE”
The terminal functions are changed as follows:
FWD-CM = ON :Start operation
FWD-CM = OFF :Stops timer operation (Pause)
RESET key :Timer reset
NOTE: The RESET key only functions when the drive
is stopped or paused.
Example #1:
Output
Frequency
Stage 4
FWD-CD
Stage 1
Example #2:
Output
Frequency
Stage 2
Stage 3
Stage 1
Stage 5
Stage 6
Stage 7
t
Stage 3
Stage 2
Stage 2
Stage 1
FWD-CM
t
6-30
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
73ACC PTNACCELERATION/DECELERATION PATTERN0
Selection can be made from the following
types:
0:
1:
2:
Linear acceleration/deceleration (Fig. a)
S curve acceleration/deceleration (Fig. b)
Non-linear for variable torque load (Fig. c)
Output
Frequency
Accel
Fig. A
Linear
Frequency
Decel
Output
t
Accel
Fig. B
S Curve
Frequency
Decel
Output
Accel
t
Fig. C
Non-Linear
Decel
SPECIAL FUNCTIONS
74N/ANOT USED0
75ENERGY SAV
0:
1:
ENERGY SAVINGS0
Automatically saves energy by weakening
the V/Hz pattern during light load operation.
Inactive
Active-Volt/Hz ratio is decreased automatically at light loads. Not active
during acceleration or deceleration.
t
76REV-PH LOC
0:
1:
77DATA INIT
0:
1:
* 78LANGUAGELANGUAGE SELECTION1
0:
1:
2:
3:
REVERSE DIRECTION LOCK OUT0
Prevents the drive from operating in
a reverse direction.
Inactive
Active-Will not allow the motor to run in
reverse direction even in pattern mode.
DATA INITIALIZATION0
Allows resetting Function Codes to factory
settings.
Manual setting value (customized drive
settings).
Return to factory default setting values.
Allows selection of the language in which
the LCD Graphic Display will be shown.
Japanese
English
Spanish
French
This setting determines whether or not
Function Codes 81 through 94 will be
displayed and available for adjustment.
Function Codes 81 through 94 NOT displayed.
Function Codes 81 through 94 displayed.
Allows the selection of the carrier frequency that determines the quality of the
sound produced by the motor.
Low carrier (0) to High carrier (10)
Time from frequency output reaching zero to (30HP and less)
frequency output restarting.0.5S
See Function Code 10 (Restart) (40HP and greater)
0.0 TO 5.0
83FALL RATERATE OF FALL10.00
0:
1 TO 100
* 84AUTO-RESET
0 TO 7
Time in seconds
This Function Code sets the deceleration rate
for the motor during lead-in when Function
Code 10 (RESTART) is active and a momentary
power failure occurs.
Deceleration occurs for the set decel time.
Deceleration occurs for the value set in
Hz per second.
AUTOMATIC RESET TIMES0
Selects the number of times the drive
will attempt to reset after a fault condition.
Reset after overcurrent, overvoltage, low
voltage, overheating and overload faults.
WARNING: Personal safety must be considered when activating
this function.
6-32
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 85RESET INTRESET INTERVAL5
Time interval between reset attempts as set
in Function Code 84.
2 TO 20
Time in seconds.
MOTOR CHARACTERISTICS
86MOTOR CAPMOTOR Hp CAPACITY1
This Function Code is used to select the
motor Hp capacity in relation to the
drive Hp capacity.
0:
1:
2:
3:
87MOTOR 1-Ir 0.00 TO
2000AMPS
88MOTOR 1-Io 0.00 TOMOTOR #1 NO LOAD CURRENT (Magnitizing
2000
One frame up in Hp capacity (variable torque
application).
Standard capacity (constant torque application).
One frame down in Hp capacity.
Two frames down in Hp capacity.
MOTOR #1 NAMEPLATE FULL LOAD CURRENTRATED
current).
89MOTOR 2-Ir 0.00 TO
2000AMPS
90TUNINGMOTOR TUNING 0
CAUTION: When using motor tuning, be sure the correct values are set in Function Code 03, 04 and 87.
0:
1:
WARNING: Ensure the motor is connected, free to rotate and at a standstill. Upon setting
Function Code 90 equal to 1, the drive will pulse the motor three (3) times in order to calculate
the settings in Function Codes 91 and 92.
MOTOR #2 NAMEPLATE FULL LOAD CURRENTRATED
This Function Code is used to tune the
primary resistance and inductance of the
motor.
Inactive
Active
6-33
LCD
GRAPHICFACTORY
FUNCTIONDISPLAYSETTINGDESCRIPTIONSETTING
* 91%R1 SETMOTOR #1 CALCULATED % PER UNIT RESISTANCE%
0.00 TOPercent of motor resistance.
50.00 %:
%R1 =
R1 + Cable R x 100
V/ (
R1 is motor resistance;
Cable R is resistance of cable between drive
and motor; V is rated motor voltage.
√ 3 x I)
* 92%X SET
0.00 TOPercent of motor impedance.
50.00 %:
MOTOR #1 CALCULATED % PER UNIT IMPEDANCE%
%X =
X1 + X2 x XM/ (X2 + XM) + Cable X x 100
V/ (
X1, X2, XM are motor values;
Cable X is inductance of cable between drive
and motor; V is rated motor voltage.
SPECIAL FUNCTIONS
93DD FUNC 1DO NOT USE
94DD FUNC 2DO NOT USE
95DATA PRTC
DATA PROTECTION0
Once the Function Codes have been set, the
data protection can be activated and prevent
any further changes.
√ 3 x I)
0:
1:
Not protected (changeable)
Protected (change prevented)
Press >> and UP Key together to change Function
Code 95 to 1.
Press >> and DOWN Key together to change Function
Code 95 to 0.
Press FUNC DATA to store change in software.
6-34
Section 7: Maintenance and Inspection
So that the AF-300E$ drive may give long periods of
trouble-free operation and to prevent potential problems
from occuring, the following items should be periodically
inspected.
CAUTION: Do not conduct any inspections until after
disconnecting the power supply and after the “CRG” light
on the drive has gone out.
MEGGER TEST
1.Disconnect all drive terminals and never apply test
voltage to the drive when conducting an external circuit
megger test.
2.Perform the test only on the main circuit as shown in
Figure 7-1 when conducting a megger test on the drive
itself.
—Do not conduct a megger test on the control
circuits.
—Short L1, L2, L3, U, V, W, P, N, DB, and P, then
megger to ground.
3.Use a high resistance range type tester to conduct a
continuity test on the control circuits and not a megger
or a buzzer.
PERIODIC PARTS REPLACEMENT
The life of the drive will vary according to the installation
environment and the amount of running time. However, if
continuous operation is within the allowable limits, the life of
the dc Link capacitor is approximately five years and the life
of the cooling fan is approximately three years. It is recommended that these parts be replaced before failure occurs.
INSPECTION ITEMS
Refer to the Inspection Items Chart in this section for
inspection points and corrective action.
POWER
MEGGER
MEGGER TEST OUTLINE
•
•
•
•
P(+) DB
P1
L1
IF SINGLE PHASE
}
L2
L3
•
+
+
–
•
–
GROUND
Figure 7-1. MAIN CIRCUIT MEGGER TEST CONNECTIONS
E (G)
W
U
V
•
•
•
Motor
IM
7-1
INSPECTION ITEMS CHART
ItemInspection CriteriaCorrective Action
Power SourceWithin permissible limits (170 - 253 VAC)Adjust the power supply voltage
Voltagefor 230 VAC drives; or (323 - 506) for
460 VAC drives; or (480-575) for
575 VAC drives.
AmbientWithin permissible limits (-10o to +50o C)Investigate cause and make corrections
Temperature(+14o to +122oF)until environment is within permissible limits.
AmbientWithin permissible limits (20 - 90% RH)Investigate cause and make corrections
HumidityNo dew condensation or freezinguntil environment is within permissible limits.
VibrationWithin permissible limit (0.6G or less)Investigate cause and make adjustments
until within permissible limits.
NoiseAbnormal Audio Noise from coolingContact the supplier where the Drive
fan, etc.was purchased.
OdorSmell or burningContact the supplier where the Drive
was purchased.
DustDust accumulation on cooling fins,Clean and blow out with compressed air.
cooling fan, or on the control board.
Screws/Check for any looseningRetighten as needed.
Connectors
MEASUREMENT POINTS AND METERS
Since the Drive's input/output voltage and current
contain high frequencies, selection of the wrong measuring device can lead to gross miscalculations. When
using a CT (current-detection transformer) to measure
the current, the amount of error will be large if the
frequency is low. Because of this, always use a CT with
as large a capacity as possible. See the following chart
and Figure 7-2 for recommended measurement devices.
RECOMMENDED MEASUREMENT DEVICE CHART
ItemSimple MeasurementPrecision Measurement
Input VoltageTesterMoving-Iron type voltmeter
Input CurrentClamp MeterMoving-Iron type ammeter
Input Power—Electrodynamometer type wattmeter
Output VoltageTesterRectifier type voltmeter
Output CurrentClamp MeterMoving-Iron type ammeter
Output Power—Electrodynamometer type wattmeter
7-2
Figure 7-2. MEASUREMENT LOCATIONS AND DEVICES EXAMPLE
7-3
Notes:
7-4
Section 8: Troubleshooting
TABLE 11: Fault Condition Description and Operation
The following GE AF-300E$ drive protection functions have been incorporated in the basic drive software and will be
indicated in the LED display as well as listed in the fault table display.
Protective
Function
OvercurrentProtects the Drive when the output current reaches the
momentary overcurrent protection level.
The protection is effective for Drive output terminals- U, V, W.
Ground FaultGrounded output. The protecction is effective for Drive output
Over voltageProtects the Drive when the DC bus voltage reaches the
Under voltageProtects the Drive when the DC bus voltage reaches the
Over heatProtects the Drive against overheating caused by
DB (Dyn Brk)Protects the dynamic brake resistor from over-heatingd b HX
Electronic
thermal
overload
Inside fuseDetects the DC bus failed fuse, 15 Hp and above.F U SX
terminals - U, V, W.
momentary overvoltage protection level by a braking operation.
(Drive cannot protect against an input line overvoltage.)
momentary low voltage protection level. Output alarm relay
(30a, b & c) is dependent on function.
overload operation, cooling fan failure, abnormal high ambient
temperatures, etc.
Protects the Drive with electronic overload.
Protects the motor with electronic overload sense
Range of setting: 20 to 135% of Drive rated current.
Function Explanation
LED
Display
O C 1
O C 2
O C 3
EFGrnd FaultX
O U 1
O U 2
O U 3
L UFunction
O H 1
O H 3
O L U
O L
Remarks
At accel
At decel
At oper
At accel
At decel
At oper
10: 0 or 1
10: 2,3,4
Fin temp.
Internal
temp.
Alarm RY
(30A, B & C)
X
X
X
- no
X
X
ExternalStops Drive by an external alarm signal.O H 2X
Memory errorDetects memory EE-PROM malfunction.E r 1X
Keypad
communication
CPU errorDetection of a CPU malfunction.E r 3X
Option
communication
Option errorDetects Drive option failure.E r 5X
Operating
Proc. Error
Tuning errorDetects missing connection to the motor @ auto-tune.E r 7X
Prevent
stall
Detects a continuous communication error between
control PCB and keypad panel.
Detects a continuous communication error between
control PCB and option PCB.
Detects Drive operating procedure error during Drive startup.
FWD or REV connected to terminal CM at time of main power
being applied to Drive. Stop keypad in remote operation.
Prevents OC-trip by ceasing frequency output at high current when
torque limit is disabled and drive is accelerating, or when high impact
loads are applied to the motor. Second, by decreasing frequency
level when torque limit is activated and its value is being exceeded
during steady state operation and load acceleration.
E r 2X
E r 4X
E r 6X
8-1
FAULT CONDITION DISPLAY AND CORRECTIVE ACTION
CAUTION:
Electrostatic Discharge: The AF-300E$ has components
and board assemblies that are sensitive to electrostatic
charges. These parts can be damaged if electrostatic
CAUTION:
Do not conduct any inspection until after disconnecting the
power supply and after the "CHG" light on the drive has gone
out.
discharge procedures are not implemented during
disassembly, handling of electronic components, reassembly and equipment checkout.