GE Industrial Solutions AF-300C User Manual

Urinves
GEK-85716A
TM Trademark of General Electric Company, U.S.A. These
lnsfwcfions
operation mainfenance. Should lurfherinformafion bo desired or should parficularprobloms arise which are not covered sullicienffy for the purchasers purposes, fhe
mafter should be
do
nol
to
coverall
referred to General
details
or
E!eclric Comwnv
vafialions
in equipment lo provide for
every possible
confingency
lo be
mef
in
connecficn with insfallafion
GE Drive Systems
SUPPLEMENT
FOR INSTRUCTION MANUAL GEK-85716A
These
instructions
during
installation, operation, and maintenance. Should further information be desired or should particularproblems arise that are not
covered sufJ?ciently for the purchaser’s purpose,
do not purport to cover all details or variations in equipment, nor to provide for evey possible contingency to be met
tlze
matter should be referred to GE Drive Systems, Salem, Virginia U.S.A.
This supplement contains additional information needed when installing and operating the
AF3OOC
series of inverters. Refer to the information of this supplement in addition to that contained in
GEK-
85716A for the figures, tables, and paragraphs listed in this supplement.
Figure
4-15.
Basic Connection Diagram
Figure S-12. Control Block Diagram
The 3-phase AC circuit breaker shown in these figures is incorrectly illustrated as three breakers. It is actually a single,
3-pole
breaker.
#1
Table 5: Function Code Data Table 6: Function Code Descriptions
Function Code lb, Electronic Thermal Overload Protection, that is built in to the AF-300C series of inverters is factory set as Operational. If the user changes this to Non-Operational, conventional overload protection for the motor and wiring must then be provided by the user. Typical wiring for an overload relay is shown in figure 8-12 of GEK-85716A.
All inverter installations
must
meet the applicable na-
tional (NEC, CEC) and local electrical codes. It is the
system engineer’s responsibility to be certain that the
inverter installation complies with all applicable electrical codes. (If a system engineer is not involved, it is the user’s responsibility.)
(10/14/94)
Page 1 of 1
AF-300C
Inverter
40 to 300 HP
380/400-460
GEK-85716A
Issue Date: August 1994
VAC,
-
50/60
Hz
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible contingency to be met during installation, operation, and maintenance. Should further information be desired or should particular problems arise that not covered chaser’s purpose, the matter
This document contains proprietary information of General Electric Company, U.S.A. and Is furnished to its customers solely to assist that customer in the instaliatlon, testing, and/or maintenance of the equipment described. This document shall not be reproduced in whole or in part nor shall tents be disclosed to any third party without the written approval of GE Drive Systems, 1501 Roanoke Boulevard, Salem, Virginia 24153, U.S.A.
should
be referred to GE Drive Systems, Salem, Virginia, U.S.A.
sufficiently
for the pur-
tts
con-
Copyright 1994 by General Electric Company, U.S.A.
All rights reserved.
Printed in the United States of America.
TABLE OF CONTENTS
Paae
1.
2. DESCRIPTION, COMPONENT IDENTIFICATION,
SAFETY PRECAUTIONS
AND SPECIFICATIONS ........................................................................
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Description................................................................................
Inspection Items Upon Delivery ............................................................
Movement and Storage ..........................................................................
l-l
2-I
2-1 2-l
2-l
lnverter Components and Cooling ........................................................ 2-2
TABLE 1: AFSOOC lnverter Standard Specifications
AF300C AFSOOC
3. INSTALLATION GUIDELINES .............................................................. 3-l
lnverter Catalog Numbers
......................................................
lnverter Options (inc. Line Reactors)
Installation Environment ........................................................................
Open Installation Mounting Clearance Enclosed Mounting Installation Guidelines
..................................................
..........................................
AFSOOC Dimensions ..............................................................................
4. WIRING PROCEDURES
......................................................................
Main Circuit Wiring ..................................................................................
Auxiliary Control Power Supply Connections
......................................
..........................
....................................
2-5
2-8
2-9
3-l
3-l
3-2
3-4
4-1
4-l
4-2
AC Line Reactor Connection ................................................................ 4-2
DC Reactor Connections ...................................................................... 4-2
Braking Unit and Braking Resistor Connections Ground Terminal Connections
..............................................................
................................
4-3
4-8
Control Circuit Wiring ............................................................................ 4-6
TABLE 2: Terminal Identification/Function TABLE 3: Application of Wiring and Equipment
..........................................
..................................
4-l 0
4-l 3
5.
6.
INVERTER
Before Applying AC Power Inspection
OPERATION ......................................................................
..................................................
Keypad Panel Identification/Function ..................................................
TABLE 4: Keypad and Display Operation
............................................
Display Examples Chart ........................................................................ 5-4
Monitoring Control Signals and lnverter Output
..................................
Setting Function Codes.......................................................................... 5-6
Function of Reset Key After Changing Function Code Data
..............
Fault Indication And Retrieval ................................................................ 5-6
Data Protection
......................................................................................
Trial Keypad Operation (Optional) ........................................................ 5-9
Control Circuit Connection and Operation Actual Operation TABLE 5: Function Code Data
FUNCTION CODE DESCRIPTIONS ....................................................
.................................................................................... 5-l 5
..............................................................
.......................................... 5-l 1
TABLE 6: Function Code Descriptions ................................................
5-1
5-l 5-l 5-2
5-5 5-6 5-9
5-l 7
6-1
6-l
AF-300C
hverters
GEK-85716
TABLE OF CONTENTS
Section
7.
8.
9.
10.
Title
MAINTENANCE AND INSPECTION
Megger Test ............................................................................................
Periodic Parts Replacement Inspection Items
Measurement Points and Meters ..........................................................
TROUBLESHOOTING ..........................................................................
TABLE 7: Fault Description and Operation TABLE 8: Fault Condition Display and Corrective Action..
WARRANTY PARTS AND SERVICE ....................................................
Warranty Coverage ................................................................................
Out-Of-Warranty Procedures ..................................................................
Motors ......................................................................................................
In-Warranty Failure Checklist ..................................................................
PARTS REPLACEMENT ......................................................................
TABLE 9: AF3OOC
......................................................................................
lnverter Renewal Parts ..........................................
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..*..*......
..................................................................
..........................................
..................
Paae
7-1
7-1 7-1
7-I
7-3
8-l 8-I
83
9-1
9-1
9-1 9-l
9-1
1 o-1
1 O-l
NOTES:
ii
LIST OF FIGURES
Fiuure #
Figure 2-1. Figure 2-2.
Figure 2-3. Figure 2-4. Figure 2-5. Figure 2-6. Figure 3-1. Figure 3-2. Figure 3-3. Figure 4-1. Figure 4-2. Figure 4-3. Figure 4-4. Figure 4-5. Figure 4-6. Figure 4-7. Figure 4-8. Figure 4-9. Figure 4-10. Figure 4-l Figure 4-12. Figure 4-l 3. Figure 4-l 4. Figure Figure 4-l 6. Figure 4-l 7. Figure 4-l 8.
Figure 4-l 9.
Figure 4-20.
Figure 4-21.
Figure 4-22.
Figure 4-23.
Figure 4-24.
Figure 4-25.
4-l
1.
5.
Title
NAMEPLATE DATA IDENTIFICATION
TYPICAL INVERTER COMPONENTS ..........................................................
INVERTER COOLING METHODS ................................................................
KEYPAD PANEL COMPONENT IDENTIFICATION
104X220FA003,004 104X220FA005,006
INVERTER MOUNTING CLEARANCE ..........................................................
INVERTER ENCLOSURE MOUNTING ARRANGEMENTS ........................
INVERTER EXTERNAL DIMENSIONS TERMINAL
AC POWER CONNECTION ..........................................................................
AUXILIARY CONTROL POWER SUPPLY CONNECTIONS DC REACTOR CONNECTION
OUTPUT WIRING CONNECTIONS ..............................................................
BRAKING RESISTOR AND BRAKING UNIT CONNECTIONS
GROUND CONNECTIONS ............................................................................
CONTROL WIRE ROUTING ..........................................................................
FREQUENCY
FAULT RESET CONNECTION ......................................................................
EQUIVALENT CONTROL CIRCUIT FAULT OPEN COLLECTOR CONNECTION
SURGE SUPPRESSOR CONNECTION ......................................................
BASIC CONNECTION DIAGRAM OPERATION FROM KEYPAD REMOTE OPERATION WITH MOMENTARY CONTACTS REMOTE OPERATION WITH MOMENTARY CONTACTS
AND REVERSING CAPABILITY
REMOTE OPERATION WITH MAINTAINED CONTACTS
REMOTE OPERATION WITH MAINTAINED CONTACTS AND REVERSING CAPABILITY
REMOTE OPERATION WITH MAINTAINED CONTACTS
AND JOG FUNCTION ....................................................................................
REMOTE OPERATION WITH MAINTAINED CONTACTS
AND JOG FUNCTION WITH REVERSING CAPABILITY REMOTE OPERATION WITH MOMENTARY CONTACTS
AND AUTO/MANUAL OPERATION ..............................................................
REMOTE OPERATION WITH MOMENTARY CONTACTS AND REVERSING CAPABILITY AND AUTO/MANUAL OPERATION
REMOTE OPERATION WITH MAINTAINED CONTACTS
AND AUTO/MANUAL OPERATION ..............................................................
BLOCKS
RELAY
LINE REACTOR OUTLINE AND SCHEMATIC.. LINE REACTOR OUTLINE AND SCHEMATIC
......................................................................................
......................................................................
SEl-TING/MONITORING
CONTACTS ..........................................................................
........................................................................
.......................................................... 2-l
......................................
........ 2-l 1
.......... 2-12
.......................................................... 3-3
........................ 4-2
.................... 44
TERMINAL CONNECTIONS
.............................................................. 4-8
............................................................
................................................................ 4-l 5
.......................... 4-l 6
.................................................................... 4-l 6
..........................
....................................................................
............................ 4-l 9
........
........ 4-20
Pacle
2-2
2-3
2-4
3-l 3-2
4-I 4-2
4-2 4-3
4-6 4-6 4-7
4-8
4-8 4-8 4-9
4-l 5
4-l 7
4-17
4-l 8
4-20
4-21
. . . III
LIST OF FIGURES
Fiaure
#
Figure 4-26.
Figure
5-l.
Figure 5-2. Figure 5-3. Figure 5-4.
Figure 5-5.
Figure 5-6. Figure 5-7. Figure 5-6.
Figure 5-9. Figure 5-l 0. Figure 5-l 1. Figure 5-l 2. Figure 5-13. Figure
5-l
4.
Title
REMOTE OPERATION WITH MAINTAINED CONTACTS
AND REVERSING CAPABILITY AND AUTO/MANUAL OPERATION ..........
KEYPAD PANEL COMPONENT IDENTIFICATION ...................................... 5-2
DISPLAY LED INDICATOR IDENTIFICATION ..............................................
FUNCTION CODE
FAULT INDICATIONS .................................................................................... 5-7
ELECTRIC MOTOR ROTATION ....................................................................
FACTORY CONNECTIONS .......................................................................... 5-I 1
EXAMPLE OF COMMONLY USED SIGNALS ..............................................
KEYPAD PANEL
KEYPAD PANEL “RUN” OPERATION EXAMPLE .......................................... 5-l 2
REMOTE OPERATION CONNECTIONS ...................................................... 5-I 3
REMOTE OPERATION EXAMPLE ................................................................ 5-14
MULTI-STEP FREQUENCY OPERATION CONNECTIONS ........................ 5-14
MULTI-STEP FREQUENCY ‘RUN” OPERATION EXAMPLE ........................ 5-15
MULTI-STEP ACCELERATION AND DECELERATION
OPERATION CONNECTIONS ...................................................................... 5-l 6
“06”
AND ‘07’ DATA ........................................................ 5-5
OPERATION CONNECTIONS .......................................... 5-12
Page
4-21
5-4
5-I
5-I I
0
Figure 5-15.
Figure
6-l.
Figure 7-1. Figure 7-2. Figure
6-I.
Figure 6-2. Figure 6-3. Figure 6-4. Figure 6-5. Figure 6-6. Figure 6-7. Figure 6-6. Figure 8-9. Figure 8-10.
MULTI-STEP ACCELERATION AND DECELERATION ‘RUN’
OPERATION EXAMPLE..................................................................................
AF900C
MAIN CIRCUIT MEGGER TEST CONNECTIONS ........................................ 7-l
MEASUREMENT LOCATIONS AND DEVICES EXAMPLE .......................... 7-3
MOTOR RUNS BUT SPEED DOES NOT CHANGE
TROUBLESHOOTING CHART ...................................................................... 8-5
MOTOR ROTATION IS NOT SMOOTH TROUBLESHOOTING CHART ...... 8-6
MOTOR OVERHEATS TROUBLESHOOTING CHART ................................ 8-6
INVERTER
CPU ABNORMAL TROUBLESHOOTING CHART ........................................ 8-7
EXTERNAL FAILURE TROUBLESHOOTING CHART .................................. 8-8
OVERCURRENT TROUBLESHOOTING CHART.......................................... 8-9
OVERVOLTAGE TROUBLESHOOTING CHART .......................................... 8-I 0
UNDERVOLTAGE TROUBLESHOOTING CHART ...................................... 8-10
OVERLOAD TROUBLESHOOTING CHART ................................................
FUNCTION
OVERHEATS TROUBLESHOOTING CHART ............................ 8-7
CODE
MAP.................................................................. 6-I 3
5-I
8-11
6
iv
LIST OF FIGURES
Fiaure #
Figure
Figure
Figure S-13. Figure
Figure 8-15.
Figure 8-16. Figure Figure 6-18.
Table
TABLE 1:
8-l 1.
8-I 2.
8-I
4.
8-l
7.
#
Title
MOTOR STALLS DURING ACCELERATION
TROUBLESHOOTING CHART
CONTROL BLOCK DIAGRAM ......................................................................
INTERCONNECTION DIAGRAM - 40 HP INVERTERS
INTERCONNECTION DIAGRAM - 50 AND 60 HP INVERTERS ................
INTERCONNECTION DIAGRAM - 75 HP INVERTERS ..............................
INTERCONNECTION DIAGRAM - 100 AND 125 HP INVERTERS ............
INTERCONNECTION DIAGRAM - 150 HP INVERTERS ............................ 8-22
INTERCONNECTION DIAGRAM - 175 TO 300 HP INVERTERS ................
......................................................................
..............................
Pacre
8-11
8-12
8-14
8-16
8-I
S-20
8-24
LIST OF TABLES
m
AFSOOC
INVERTER STANDARD SPECIFICATIONS .................................. 2-5
Pacae
8
TABLE 2: TABLE 3: TABLE 4:
TABLE 5: TABLE 6: TABLE 7:
TABLE 8:
TABLE 9:
TERMINAL IDENTIFICATION/FUNCTION .................................................... 4-10
APPLICATION OF WIRING AND EQUIPMENT
KEYPAD AND
FUNCTION CODE DATA .............................................................................. 5-17
FUNCTION CODE DESCRIPTIONS ............................................................ 6-l
FAULT DESCRIPTION AND OPERATION .................................................... 8-l
FAULT CONDITION DISPLAY AND CORRECTIVE ACTION
AF-3OOC INVERTER
DISPLAYOPERATION ..........................................................
RENEWAL PARTS ......................................................
............................................ 4-13
5-2
...................... 8-3
1 O-l
V
AMOOC lnverters
,.
GEK-85716
NOTES:
vi
Af-300C lnverfers
1
m
SAFETY PRECAUTIONS
GEK-85718
WARNING, CAUTION AND NOTE LABELS PLACED ON THE EQUIPMENT
The following format is used on the safety and informative labels placed on the equipment. Read all labels and follow the directions on them whenever working on the equipment.
WARNING:
practices that may result in personal injury or loss of life if not correctly followed.
Denotes operating procedures and
WARNING labels will be red in color with black or white lettering.
CAUTION:
practices that, if not strictly observed, may result in damage to, or destruction of the equipment.
Denotes operating procedures and
CAUTION labels will be amber in color with black letterina.
NOTE:
especially significant in understanding and operating the equipment.
Notes call attention to information that is
WARNING - ELECTRICAL SHOCK AND
BURN HAZARD:
as oscilloscopes to work on live equipment, the
oscilloscope’s chassis should be grounded and a
differential amplifier input should be used. Care should be used in the selection of probes and
leads and in the adjustment of the oscilloscope so
that accurate readings may be made. See instrument
manufacturers instruction book for proper operatlon
and adjustments to the instrument.
WARNING - STRAIN HAZARD: improper
lift
trig
Lift only with adequate equipment and trained personnel.
WARNING
HAZARD:
mounting inverters in hazardous areas such as locations where flammable or combustible vapors or dusts are present. lnverters should be Installed away from motors suitable for use in these locations.
NOTE labels will be white in color with black
letterincr.
WARNING, CAUTION AND NOTE
PARAGRAPHS WITHIN THIS INSTRUCTION
The following paragraphs list some general safety reminders and safety recommendations to be followed when operating or installing this equipment. These safety precautions will be repeated throughout this instruction book where applicable.
WARNING -MECHANICAL MOTION
HAZARD:
motion. it is the responsibility of the user to insure that any such motion does not result in an unsafe condition. Factory provided Interlocks and operating limits should not be bypassed or modified.
inverter systems cause mechanical
WARNING- ELECTRICAL SHOCK
HAZARD:
enclosure houslngs should be grounded in accordance with the National other required standards.
WARNING- MOTOR OVERSPEED
HAZARD:
inverter for operation up to 400 Hz maximum output
frequency, the inverter is capable of running the
motor at up to 8 - 7 times its base speed. Never
operate the motor above its top mechanical speed or a catastrophic failure may occur. the inverter for a top frequency above the safe
mechanical speed for the motor. Consult factory
for any application exceeding 120 Hz.
WARNING - PERSONAL INJURY HAZARD:
Carry the inverter only by the body, not by the terminals or top cover. Equipment movement
should only be performed by trained personnel.
When using instruments such
practices can cause serious or fatal injury.
-
FIRE AND EXPLOSION
Fires or explosions might result from
hazardous
All
motor bases and equipment
Because it is possible to configure the
areas, even if used with
Electric
Never
Code or
configure
1-l
AF-300C
lnverters
GEK-85716
WARNING - BURN AND SHOCK HAZARD:
Shut off the AC power supply before making the output connections. Voltage may be present be­tween the output terminals even though the verter Is stopped. Make sure that the “CHARGE LED indicator has gone out before making any output connections.
in-
WARNING - BURN AND SHOCK HAZARD:
Do not conduct any inspections until after discon­necting the power supply and after the “CHARGE” LED indicator on the inverter has gone out.
CAUTION: Do not connect power
output terminals
onlv to the power terminal; (Ll , L2,
CAUTION: Do not connect power
brakina resistor connection terminals short-circuit between P-N or P-DB terminals, and do not connect anv resistance with a resistance value less than the standard application brakina resistor.
CAUTION:
control circuit terminals (except 30A, B, Cl.
WARNING -MECHANICAL MOTION HAZARD:
Function Code 01 displays zero. If Function Code 13 or 15 contains a non-zero number, the motor will run when a RUN comand Is glven even If the frequency reference is zero.
When the frequency reference is zero,
CAUTION:
dotward) and REV-CM (reverse) terminals. Do not
use a contactor (for ON/OFFoperation) on the line side of the inverter for RUN and STOP.
CAUTION:
WARNING -MECHANICAL MOTION
HAZARD:
with the ‘Local/Remote” switch in the “Local” posi­tion, pressing the FWD or REV key will cause the motor to rotate. Any RUN permissives that may be wired to the FWD or REV terminals are ignored.
When running from the Keypad Panel
WARNING - PERSONAL INJURY HAZARD:
To prevent personal caused by equipment malfunction, only adequately trained persons should modify any programmable inverter.
Injury
or equipment damage
side of the inverter for ON/OFF operation.
CAUTION: The AC
KVA ratina should be Horsepower ratina of the invetter, but not areater than 500 greater than 500
reactor (optional; must be pruchased seperatelv) on
the line side of the inverter. A Line Reactor is also
required if an SCR Tvpe controller and/or Power Factor Correction Capacitors are used on the same power lines.
supplv
to the
(U,
V,
Do not connect power
For RUN and STOP, use the FWD-CM
Do not use a contactor on the output
KVA.
If an AC
KVA
Connect power supply
w)
L3).
SUPDIV
to the
(P, DB).
Supplv
is to be used, install a line
Power Transformer
treater
than 1.5 times the
SUPPIV
Power Transformer
Never
SUDPIV
to the
WARNING - FIRE HAZARD: Use
namic braking resistors that are provided by GE
Drive Systems. These are special resistors that have a thermal fuse built in that opens if the resistor gets too hot. This fuse should only open
If the DB transistor In the lnverter or DB unit fails short circuited. The resistor will need to be re­placed if this happens.
CAUTION: When removinn or
handle them bv the connector onlv and not bv the wire itself. Be careful not to mix wires when recon-
nectina them.
CAUTION:
that exceeds the standard specification fluctuation permissible. lf excessive voltaae is applied to the invetter, damaae to the internal components will result.
Do not connect power
replacina
only’dy-
SUPPIV
voltage
wires,
voltaae
l-2
CAUTION:
output side of the invetter.
CAUTION:
ground wire connected.
CAUTION:
consult the TROUBLESHOOTING section of this
instruction book, and after correctina the problem, resume operation. Do not reset the fault alarm
automaticallv bv external seauence, etc.
CAUTION:
the inverter terminals or on the control circuit terminals.
Do not connect filter capacitors on the
Do not operate the inverter without the
If the inverter’s fault alarm is activated,
Do not perform a meaaer test between
AF-300C lnverfers
GEK-85718
CAUTION: Motor Thermal Overload protection
must be provided, either bv motor thermoswitch, external motor overload relav, or inverter electronic thermal overload.
CAUTION: Because the ambient temperature
oreatlv affects inverter life and reliabilitv, do not install
the inverter in anv location that exceeds the allowable temperature. Leave the ventilation cover attached for temperatures of 40 deqrees C or below, and remove the cover for temperatures between 40 and 56 dearees
C. If the cover needs to be removed, another of enclosure The inverter should not be operated when the ambient temperature is above 50 dearees C.
CAUTION:
densor
inverter will overheat and be damaoed due to har­monics.
CAUTION:
be kept as far awav as possible from the main power wirinq to prevent operational error due to noise inter­ference. Never install both tvoes of wirino in the same duct or conduit. (A separation distance of 10 centi­meters 14 inches1 or more is recommended.) If the control circuit wiring must cross the main power wir- inn, it should cross at a rioht anale (see Fiaure
may
be required for
Do not connect a phase advance con-
in the output wires. The
The control circuit terminal wirinn should
safetv
condenser
tvpe
purposes.
and
4-81.
CAUTION: Use shielded or twisted wire for the
control circuit wirina lwirina should be as short as
possible, i.e. 20 meters
outer coverino of the shielded wires to the inverter around terminal and leave the other end uncon-
nected, but taped.)
CAUTION:
relavs or solenoid tvpe coils, etc. that mav be close to
the inverter or used with the inverter.
NOTE: Always read the complete instructions prior to
applyingpoweror troubleshooting the equipmentand follow al/procedures step by step.
NOTE: The motor chassis should be grounded to earth ground through a separate ground lead from all other equipment ground leads to prevent noise coupling.
NOTE: Readandheedall WARNING, CAUTION, and
NOTE labels posted on the equipment.
Install a suppressor in parallel with any
165
feet1 or less). (Connect
NOTES;
1-3
AF-JOOC /wetters
GEK-85718
/VOTES:
l-4
AF-300C
2.
DESCRIPTION, COMPONENT
Inverters
GEK-85716
IDENTIFICATION, AND SPECIFICATIONS,
GENERAL DESCRIPTION
The
AF-300CTM
versions (380-460 VAC @ 50Hz; 400-460 VAC @ 60 Hz). All of the inverters use two Processing Units’
to provide high performance in all applications.
General data and specifications for each individual inverter are listed on the nameplate attached to the inverter (see Figure 2-1 for nameplate example). See
TABLE 1 for a complete listing of all
specifications. lnverter operation and Function Code setting can be
performedfromthe“Keypad Panef’thatalsofeatures
an LED Data Monitor Display. Eleven Touch Keys and the LOCAL/REMOTE switch arefurnished on the Keypad Panel for operation and Function Code adjustment. Operation Monitoring, Function Code
Setting, Fault Monitoring, Data Protection, Reset, and
Mode Changeover can all be performed from the
Touch Panel. Operation Commands and Frequency
Setting Commands can also be entered from the Keypad Panel. (See Figure 2-4 for Keypad Panel component identification and function.)
TM - Trademark of General Electric Company, U.S.A.
inverter is available in 40 to 300 HP
18bit
“Central
(CPUs)
for multifunction processing
AFSOOC
inverter
INSPECTION ITEMS UPON DELIVERY
Upon receipt of the inverter, inspect equipment for the following items:
1. Check the nameplate to insure that the inverter specifications correspond to those ordered.
2. Inspect the unit for any damage that may have occurred during shipment.
-- lf
there are any problems or questions regarding the above, contact the distributor that the inverter was purchased from.
MOVEMENT AND STORAGE
WARNING - PERSONAL INJURY HAZARD:
Carry the inverter only by the body, not by the terminals or top cover. Equipment movement should only be performed by trained personnel.
For temporary storage after delivery, the following guidelines should be followed:
1.
Ambienttemperature range in the storage area should be between -25 to
2. Leave inverter in its packing carton to avoid exposure to dust and potential damage.
3.
Avoid placing the inverter directly on a concrete floor or in a location exposed to direct sunlight.
(Store on a stand or shelf.)
+65
degrees C.
Figure 2-1.
NAMEPLATE DATA IDENTIFICATION
2-l
AF-300C lnverfers
GEK-85716
4. Avoid storage in humid environments or in atmospheres that contain corrosive gases such
as sulferized gas, ammonia gas, or chlorine
gas.
NOTE:
lfrhe inverref is stored or insralledin a locarion
where construction work is still being done, keep the
inverfer prorecred from exposure until
it is to be placed in service.
to
water and dust
This pedastal should mount to the bottom of the inverter.
NOTE: inverrers
for ‘cooling inside
the
enclosure” is required,
repositioned (see Figure 2-3).
The mounting adapter, positioned at either the top or
bottom of the enclosure, must be located in accordance with the installation/cooling method.
With the “cooled outside the enclosure” method, the
INVERTER COMPONENTS AND COOLING
Refer to Figure 2-2 for identification and location of inverter components. There are two types of cooling methods depending on the installation method, “cooled inside control enclosure’ and Vooled outside control enclosure’ (see Figure 2-3).
cooling fan is mounted externally and approximately 60% of the total heat generated by the inverter is discharged outside the unit.
NOTE:
When the cooling fan is insralled ourside the control enclosure, it must be periodically cleaned (especially in dus& environments).
lnverters rated 200,250, and 300 HP can be mounted “Cooled Inside Control Enclosure”. However, a mounting pedastal will need to be constructed that can support the weight of the inverter.
Mounting Adaptor
are shipped
rhe
wirh
the adapter mounted
enclosure’. If *cooling outside
the
adapter must be
Control Cooling Fan Charge
Contactor
-
Keypad
-
Panel
AC Line .
Fuses (3)
Mounting Adaptor
Figure 2-2.
TYPICAL
INVERTER
COMPONENTS
Main Control Card
(Base Driver is integral
on this Card)
Control Circuit Terminal Board
Ground Fault Detection Card
-
Main Circuit
Terminal Board
2-2
lnverter Cooled Inside
The Control Enclosure
lnverter Cooled Outside
The Control Enclosure
w
t t
----
Q
:-
cl
I
-
COOLING AIR
II
b!
t t
COOLING AIR
y
MOUNTING AND
UFilNG
ADAPTER
Figure 2-3.
INVERTER
COOLING METHODS
MOUNTING AND LIFTING ADAPTER
AF-300C
Invetters
GEK-85716
FUNCTION
ED Selection Indicator
FAST
LOCAL
Figure
LED Indicator
three sections as follows:
Function Display - Displays in two digits the
selected Function Code number.
Data Display -
data, Function Code setting data, and the fault codes.
-The LED Indicator is made up of
Displays in four digits the operation
2-4. KEYPAD PANEL COMPONENT IDENTIFICATION
DATA
Unit Indicators
Unit Indicator - The LED on the left of each unit
symbol corresponds to the contents of the data display.
NOTE:
except W, W, and
All letters are displayed in upper case
UP.
Touch Kevs - There are eleven Touch Keys and the LOCAL/REMOTE switch that perform the following
functions: (See Section 5 for a description of each individual key.)
I
Function
Operation Monitoring Monitor the operation status of the inverter. Function Code Setting:
Fault Monitoring
Set Data Protection
Reset
I
Operation Mode Selection
I
Operation Commands
Frequency Setting Commands
Basic Function Codes Auxiliary Function Codes Set data required for control.
Calibration Function Codes Adjust output signals to match with instruments
Set data required for operation.
externally installed. Display and retrieval of the Fault Code and the
operating conditions at the time of the fault. Protect set data against accidental modification. Data reset at Function Code setting, reset to returr
to operation monitoring mode after completing the
setting, fault reset, and Error Displav Reset.
Switch for changing between “Local” and “Remote’
modes of operation.
I
Forward, Reverse, and Stop commands can entered in the “Local” mode.
Increase and decrease reference frequency com­mands can be entered in the “Local’ mode.
Description
be
2-4
AF-300C
lnwetiers
GEK-85718
TABLE 1: AF-300C
inverter HP (400460 VAC)
Standard Applicable
Motors460V (KW)
OUTPUT:
Rated Capacity-460V (KVA}
Rated Output Current46OV (Amps)I60
Rated Output Voltage (*2)
Rated Output Frequency (*3)
Overload Current Rating
POWER SUPPLY:
Rated input AC Voltage
Allowable Fluctuations
(*l)
INVERTER
50 60 75 100 125
30
37 45 55 75 90
46
57 69 65 75
3-Pk
%se,
I
50 - 120 Hertz Base Frequency
150% for 1 minute duration (inverse time characteristic)
3-Phase, 3-Wire Type, 400-460 VAC @ 60 Hertz, 380-460 VAC @ 50 Hertz
Voltage:
I
STANDARD SPECIFICATIONS
SPECIFIC
114 134
91 112 150 176
3-Wire Type, 400-460 VAC
+lO%,
-15%; Voltage Unbalance: Within 3%; Frequency: +/-5%
4TION
150 175 200 250 300
110 132 166 200 220
160 193 232 287 316
210 253 304 377 415
Control System
Output Frequency Range
CONTROL:
Frequency/Temperature Fluctuation (Stability)
Frequency Setting Resolution
Voltage/Frequency Characteristics w/F)
Torque Boost
Acceleration/Deceleration Chacteristics
Control Torque
(*3)
(*3)
Sinusoidal Wave PWM With Flux Control
I
0.5 - 120 Hz (0.5 to 5.0 Hz start frequency; 50 to 120 Hz base frequency)
I
Analog Setting - Maximum frequency
Digital Setting - Maximum frequency +/-0.01% (at
Analog Setting - 0.1% (0,05Hz/50Hz) of maximum frequency
Digital Setting - 0.1 Hz (0.01 Hz/50Hz)
Voltage - 320-460
Base Frequency - 50 to 120 Hz voltage and frequency.)
21 selectable patterns plus energy conservation mode.
0.2 to 3600 seconds, four Accel/Decel time settings available. Three patterns available (Linear,
Standard: Regenerative Brake, (DC Link Pump-Up) DC injection Brake,
Optional: Dynamic Brake, 100% (5% Duty Cycle).
VAC (Adjustable independently for both
Starting Frequency of O-60 Hz at O-l 0 Seconds Time
+/-O-2%
‘s’
Curve, Logarithmic Curve)
(at
25oC, +/-1OoC)
-1OoC
to
O-10%
Voltage for
+5OoC)
(*I) Indicates rated capacity when rated output voltage is 440 VAC.
(9)
It is not possible for output voltage to exceed power supply voltage.
(*3) Consult distributor for operation above 120
Hertz.
2-5
AF-300C
lnverters GEK-85716
TABLE 1: AF-300C
ITEM
inverter HP (400-46OV)
CONTROL: (continued),
Torque Limit Control
Automatic Acceleration and
Deceration Operation
Slip Compensation Control Multi-Step Frequency Setting
Up-Down Control
Momentary Power Failure Restart inverter Bypass Logic Bias Frequency Setting (*4)
INVERTER
40 50 60 75 100 125 150 175 200 250 300
Output current can be limited within a range of approximately 30% to 150% (1% step).
Can be used to avoid DC Link overvoltage trips caused by motor
regeneration during deceleration. Maintains motor at constant speed with load fluctuations. Seven adjustable frequency presets can be selected via three external
contacts. External momentary contacts can be used to control frequency increase
decrease. After momentary power failure, automatic restart is possible. Allows switching the motor between the inverter and the power line. Magnitude of the bias added to the frequency reference signal can be set
from 0 to 100% (1% step).
STANDARD SPECIFICATIONS (continued)
SPECIFICATION
ant
Frequency Jump
Reversing Operation By Frequency Setting Signal Characteristics
Upper and Lower Limiters of Output Frequency
PFiOTECTiON/DETECTiON:
OPERATION:
Frequency Reference Signals
input Signals
Output Signals
Up to three resonant frequencies can be skipped. Width adjustable from
0 - 5 Hertz (IHz
Makes bipolar frequency reference input possible. (Reverse motor rotation by changing frequency reference voltage polarity, rather than by using REV-CM contact.)
Output frequency can be limited to a specified range (overiding frequency reference).
Stall Prevention, Overcurrent, Overvoltage, Undervoltage, instantaneous Power Failure, lnverter Overload, Motor Overload (electronic thermal action), External Failure (external thermal action), CPU Abnormal, Output Short Circuit, Ground Fault (for inverter protection only), and Input Surge.
Frequency Reference (Voltage Input): 0 to Current input: 4 to 20 Ma DC.
Forward Command, Reverse Command, Self-Holding Selection, Current Input Selection, Multi-Frequency Setting, Up-Down Control, Accel/Decel Selection, Free-Run Command, lnverter Bypass Command, Output Switch Interlock Selection, External Alarm input, Alarm Reset Input, and Ground
Protection
Contact Outputs:
Open Collector outputs:
Input.
step).
+/-lo
VDC (0 to +/-5VDC).
Power-Side (or Motor-Side) electromagnetic contact0
command, Fault Relay Output..
See Section 6, Function Code 45.
Tim<
(*4) Bias does not affect operation when frequency command comes from the Keypad Panel.
2-6
AF-300C
lnverfers
GEK-85718
TABLE 1: AF-300C
ITEM
lnverter HP (400-460 VAC)
INDICATION:
Frequency Meter Output
Touch Panel LED Operation:
ISetting:
Al-
LED Indication (charge light)
ENVIRONMENT:
Installation Location
INVERTER
40 50 60 75 100 125 150 175 200 250 300
Analog - 0 to Output Frequency, Set Frequency, Synchronous Speed, Output Current,
Output Voltage, Load Revolution Speed, and Presence of Input and Output Signals.
Indication of Function Code and Set Data (Refer to Function Code List).
OCI -
Deceleration, OC3 - Overcurrent During Constant Speed, OV LV - Undervoltage, Motor Overload, OH2 - External Failure, Err0 - CPU Abnormal or Failure, and Failure History (three previous failure indications).
Lights up when DC Link capacitors are charged (DC Link voltage is present),
Indoors, altitude of 3281 ft (1000 meters) or less, free of direct sunlight, corrosive gas, and dust. Motor wiring should be less than 66 feet, otherwise wire separation of 4 inches may be required.
STANDARD
+lO
VDC, Pulse Frequency - (6 to 100) x Output Frequency.
Overcurrent During Acceleration, OC2 - Overcurrent During
SPECfFlCATlONS
SPECIFICATION
OLl -
lnvener Overload, OH1 - lnverter Overheat,
(continued)
-
Overvoltage,
Ol2 -
Ambient Temperature
Humidity
Vibration Temperature During Transportation
APPROXIMATE WEIGHTS
Pounds Kilograms
-10 to
+5ooc
20 to 90% Relative Humidity (free of condensation).
0.5G or less.
-25 to
+6Y
C
66
77
95 95 221 221 221 276 331 419 419
30 35 43 43
100 100 100 125 150 190 190
2-7
AF-300C lnverters GEK-85718
TABLE 1: AF-300C INVERTER STANDARD SPECIFICATIONS (continued)
ITEM
lnverter HP (400460 VAC)
Efficiencv and Loss:
Loss
(w)
Efficiencv (%I Constant Torque Load:
Base Speed Full Load
0.75 Base Speed Full Load
0.5 Base Speed Full Load
0.25 Base Speed Full Load
Efficiencv (%I Pump or Fan:
0.8 Base Speed 64% Load
0.6 Base Speed 36% Load
0.4 Base Speed 16% Load
I
1280
1520 1800I2050
95.9 96.0
94.7 94.9
+
74.2 175.0 76.5
SPECIFICATION
96.3 96.6
87.9
95.8
95.4
95.3
94.4
94.9
74.8 77.7
95.3 95.5
79.4 79.6 78.4 79.3
95.8
79.9
AFSOOC Catalog Numbers
HP Rating
40 50 60 75
100 6VAF3431 OOC-- -(I)
(1) The two character
No dash or characters - inverter is not UL listed or CSA approved.
Al - lnverter is UL listed only. A2 - lnvener is UL listed and CSA approved.
positions
(41
)
VAC,
3=Phase, 50160
HP
Cataloq
6VAF34304OC­6VAF34305OC­6VAF34306OC­6VAF343075C--
No.
-(l)
-(l)
-(l)
-(l)
following a dash in the catalog number designate the following:
2-8
Rating
125 150
200 250
300 6VAF3433OOG-
Hertz)
Cataloq No.
6VAF343125C-­6VAF34315OC-­6VAF3432OOC­6VAF34325OC,
-(l)
-(l)
-(l)
-(l)
-(l)
AMOOC
lnverters
GEK-85718
INVERTER OPTIONS
Various options are available for the These options can be ordered from the supplier of the inverter per the GE Catalog Number shown on the chart within this paragraph. The General Electric Company ‘6v” catalog numbers are coded as shown in the following Examples:
Example: (Non-HP Related
6VKAAA3AANN*
6V - GE Drives Products Operation K - Option Kit
AAA -
Applicable Series (1,2, or 3 characters) 3 - AF-300 Family of invetters
AA -
Option Abreviation
NN - Option Size/Length (if applicable)
*A
=
alphabetical character, N = Numerical char.
AFSOOC
Items)
Inverter.
NOTE: Option charts are divided into horsepower
relatedandnon-horsepowerrelateditems. Checkthe
horsepower of the inverter before ordering options to be sure the correct option is ordered.
Example: (HP Related
6VKA3NAANN*
6V - GE Drives Products Operation
K - Option Kit
AAA -
Applicable Series 3 - AF-300 Family of inverters N - Voltage
AA - Option Abreviation
NN - Horsepower Rating (2 or 3 characters)
Items1
AF-300C HORSEPOWER RELATED OPTIONS - Braking Units and Braking Resistors
(See Section 4 for recommended wiring.)
Horsepower Braklng Unit
6VKC34BU
Quantity Req. Braklng Resistor
6VKC34BR
Quantity Req. Capacity Resistance (Ohms)
NOTE:If the braking unit or resistor overheats, the thermal switch opens which turns off the braking unit
transistors and trips the inverter on an “OH2’ fault (provided thermal interlocks are wired correctly).
recommended braking unit and resistor combinations willprovide up to
duty cycle (maximum continuous ON time of braking unit is 60 seconds). *Total value, not for one resistor.
---
---
(KW)
40 50 60 75
050 050
1 1 1 1 1 1
040
050 060 075
1
1
3.6 4.8 6.0 7.2 9.6* 12.0* 14.4* 18.0* 19.2* 24.0” 28.8*
15 12
075 075 150 150
1 1
10
7.5 6.0* 5.0* 3.75* 3.33* 3.0* 2.5* 1.88”
100 125
050 060 2 2
150 175
150 175 150 150 150 1 1
075 060 050 060
2
100% braking torque with a maximum 5%
3 4
200 250 300
2 2 2
075
4 4
These
2-9
AF-300C NON-HORSEPOWER
GE
Description
RS-422/485 Card
BCD Card Amps Signal Card Output Signal Card 6VKC3AC Pulse Tach Feedback Card
Catalog #
6VKC3RS 6VKC3BC 6VKC3AS
6VKC3TF
R&ATED
Description GE Catalan
Relay Unit 6VKC3RY Keypad Cable - 2M 6VKC3CBO2 Speed Potentiometer
RFI
OPTIONS
6VKC3SP
Reactor 6VKABC3RF
#
CAUTION:
the Inverter, but not greater than 10 times the HP ratinq of the lnverter or 500 KVA (whichever is oreater). If an AC Power Supplv Transformer qreater than this is to be used, install a Line Reactor (must be purchased
seperatelv] on the line side of the Inverter. A Line Reactor
factor correction capacitors are used on the same
The AC Power Suoplv Transformer KVA rating should be oreater than 1.5 times the HP ratino of
is
also required if an SCRtvpe controller and/or power
power
lines.
AC LINE REACTORS FOR
AF-300C INVERTERS (See Caution)
200 460 250 460 300 460
*
For input voltages other than 460, Contact General Electric Company, Drives Products Operation.
**
Amps shown are at 460 VAC input voltage.
***AC Line Reactors may also be required for inverters rated
700
provided with the inverter.
NOTE:
peak (non-saturating) current rating of the reactor is greater
than 2.8 times the input current rating of the inverter.
232 295 FA005*** 287 370 316 400
UP and above even though a DC Link reacfor is
If reactors are supplied by others, be sure that the
FAOOG*** FAOOG***
2-10
75 50 50
AF-300C
lnveriters
GEK-85718
104X22OFAOO3
104X220FA004
123456
NOTE: AU DIMENSIONS ARE IN INCHES.
104X22OFAOOl. 002.
I--“‘-7
104X225FAOO4
LZl
GO3
1
f
4 5
6
S/16
HOLES
1
2 3
:
:
:
IN. MTG.
(WY.
:
4)
+.,, I_
Reactor
104X22OFAOO3 104X22OFAOO4
*
Toierece of
**
If
4AWG
is required, use #4 solid or two
Figure 2-5.
i-l-
0.125 inches
6
I
H dlA.
(1 EACH TERM.)
Dlmensions (inches) A B C* D
3.125 5.563 0.875
3.625 7.250 0.625
#IO
stranded
104X220FA003,004
LINE REACTOR OUTLINE AND SCHEMATIC
HOLE
I.c’A’-I
k.56
Terminal Weight Board
1.750 16-6
1.50
(#4
stranded will not fit in connector).
AWG** 37
----
6
S/16
MTG. SLOTS
(pounds)
67
I
X
5/6
LONG
{QlY.
4)
2-11
AWOOC lnwerfers
NOTES:
All dimensions in inches (not drawn to scale). Dimension tolerance of +/-0.09 unless otherwise indicated. Reactor may be slightly different than shown.
GEK-85716
TYPICAL TERMINAL CONNECTION
(QUANTllYl 6)
1O4X2!tOFAOO5. 006
T-
I-
(OUTLINE)
1
:
i
:
6
S/18
IN.
HOLES
:
:
MTG.
(STY.
4)
Reactor
104X22OFAOO5 1 104X220FA006 1
Figure 2-6.
Dlmensions (inches) A
I
5.00 1 8.875 1 1.00
5.50 1 12.50 1
IB
104X22OFAOO5,006
iC(max)lD
.875 1
Weight
1
G
(min)
IE
IF
1
1
.I25 1
7.250
1.00
LINE REACTOR OUTLINE AND SCHEMATIC
1
8.50
2-12
IO.406 1 IO.531 1
1.00
1.250
H
I
W9
I
AF-300C lnverters GEK-85718
3. INSTALLATION GUIDELINES
INSTALLATION ENVIRONMENT
Install the inverter in a location that meets the follow­ing requirements:
-- The ambient temperature is between -lCPC and
+5OoC (+14oF
--
The relative humidity is between 20% and 90%. Avoid any location subject to dew condensa­tion, freezing, or where the inverterwould come
in contact with water.
-- Do not install in any location subject to direct sunlight, dust, corrosive gas, inflammable gas, water vapor, or oil mist.
-
The inverter should be installed at an elevation below 1000 meters (3281 feet) and vibration should be less than
--
Motor wiring should be less than 66 feet. Oth­erwise, wire seperation of 4 inches may be required.
to
OSG.
+122+).
OPEN INSTALLATION MOUNTING CLEARANCE
NOTE: When installing two or more in close proximity, allow sufficient shown in Figure 3-1 and install them in a hori-
zontal row.
row, atleast 79.7inches
provided between each one to prevent the
ambient temperature from rising.
--
See the appropriate view in Figure 33 for the location of mounting holes.
-- Install the rubber bushings supplied with the inverter into the cable openings in the wiring lead-in plate to prevent cable damage and to minimize dust entry.
If they must be installed in a vertical
(SOcm)
4.8 inches
(120
mm)
inverfers
space as
spacemust be
CAUTION:
affects inverter life and reliabilitv, do not install the invetter in any location that exceeds the allowable temperatures.
--
Install the inverter perpendicular to the ground and with the lettering right side up. (If the inverter is installed up-side-down or horizon­tally, heat build-up will occur.)
--
Install at a sufficient distance from other equip­ment, walls, or wiring ducts as shown in Figure
3-l (these clearances are required to allow for proper cooling air circulation).
CAUTION:
ture of the coolina fins of the inverter rise to ap- proximatelv 90 decrees C (194 dearees R. For this reason, the mountinq wall must be of heat resistant material.
Because the ambient temperature
Durinq operation, the tempera-
oreatlv
4.8 inches
(120
mm)
4.8 inches (120 mm)
‘lgure
3-1. INVERTER MOUNTING CLEARANCE
(Open Installation)
4.8 inches (120 mm)
3-1
ENCLOSED MOUNTING INSTALLATION
GUIDELINES
--
When mounting inverter(s) inside of an enclosure, the temperature inside of the enclosure should not exceed 50%
--
Do not install the inverter in a small sealed enclo­sure or mount other heat-generating components near the inverter within the enclosure.
--
Cooling fans are to be installed in such a way that the cooling air passes through the ing components.
(122oF).
heat-generat-
NOTE:
verter or Cooling Fan mayprevent the air tempera­ture within the enclosure from being reduced to the specified value, even though the cooling fan is of the proper capacity.
--
When installing more than one inverter within the same enclosure, arrange them horizontally as shown in Figure 3-2. If the invetters must be arranged vertically, provide a partition board be­tween the inverters to negate the heat generated by the lower unit from affecting the upper one (see Figure 3-2).
Improper installation positions of the In-
AIR OUT
-
Horizontal Arrangement
m
COOLING
FANS
M0$’
If
Vertical Arrangement
AIR OUT~
I
II
e
AIR OUT
PARTITION
/
BOARD
Figure
3-2.
INVERTER
AIR IN
13
ENCLOSURE MOUNTING ARRANGEMENTS
3-2
View
‘A”
View
“B”
--IL-=a
(ON. 2)
‘U
BOLT
(ON. 4)
\
PANEL DRILLING
+
1
+
Hl
UFUNG
HOLE5
-w+
*
w2
*y-1w’-ii
_i
-
-AL
n
d= (ON. 2)
-0
Dl
A
0
-k
~LirnNG
HOLES
-I--
PANEL DRILLING
r-w3 7
rwi-l
h
fh5
+
7
II
H2
HI
w-
Wl
r
1
10
t---2--l
View
“c”
DIMENSIONS ARE IN INCHES
AND
[UILUYETERS]
Hl
PANEL
ORiLUNC
1
4.53
[115]
EXTERNAL DIMENSIONS
4
Figure
6.26
[2351
13.6
[36D]
-t
3-3.
INVERTER
h3
3
H2
3-3
AF-300C Dimensions (Refer to Figure 3-3)
lnverter
Catalog
HP Number 40
50
60
75
100
125
150
200
250
300
6VAF34304OC
6VAF34305OC
6VAF34306OC
6VAF343075C
6VAF2431OOC
6VAF343125C
6VAF343150C
6VAF3432OOC
6VAF34325OC
6VAF3433OOC
View
A,B
A,B
A,B
A,B
A,B
A,B
A,B
C
C
C
Dimension in Inches and (mm)
H
35.25 84.45 33.45 33.75 11.26
(=I
39.20 88.45 37.40 37.75
(996) (sn) (950) (959) (356) (13) (25) (9)
43.90 43.15 42.15 42.44 (1115) (1096) (1071) (1078) (424) (13) (25) (9)
48.90 43.15 42.15 42.44 (1115) (1096) (1071) (1078) (424) (13) (25) (9)
51.20 50.0 48.60 49.0 20.25 (1300) (1270) (1234) (1245) (514) (18) (36) (13)
51.20 50.0 48.60 49.0 20.25 (1300) (1270) (1234) (1245) (514) (18) (36) (13)
51.20 50.0 48.60 49.0 20.25 (1300) (1270) (1234) (1245) (514) (18) (36) (13)
64.60 63.60 63.20 (1641) (1615) (1605) ---
64.60 63.60 63.20 (1641) (1615) (1605) ---
64.60 63.60 63.20 (1641) (1615) (1605) ---
Hl
H2 H3 H4 hl h2 h3
.50 1.0
(875)
RW
(857) (286) (13) (25)
---
---
---
14.02
16.70 .50 1.0 -35
16.70 -50 1.0 .35
32.40
(823) ___
32.40
(823)
32.40
(823) ___
50
.70 1.4 .50
.70 1.4 .50
.70 1.4 .50
e-w es_ ___
___
- mm_
-
1.0
w-m
___
- -
___
___
mm_
___
35 (9)
35
-
lnverter
Catalog
HP Number
40
50
60
75
100
125
150
200
250
300
6VAF343040C
6VAF343050C
6VAF343060C
6VAF343075C
6VAF2431OOC
8VAF343125C
6VAF34315OC
6VAF3432OOC
6VAF343250C
6VAF3433OOC
View
A,6
A,B
A,B
A,B
A,B
A,B
A,B
C
C
C
Dimension in Inches and (mm)
W
13.4
W") (240)
14.8 10.80 14.70 14.40 2.55 (375) (275) (373) (366) (65) (250) (145) (10)
14.8 10.80 14.70 14.40 (375) (275) (373) (366) (65)
14.8 10.80 14.70 14.40 (375) (275) (373) (368) (65) (250) (145) (10)
20.90 (530) (430) (527) (520) (80) (320) (180) (15)
20.90
(530) (430)
20.90 (530) (430) (527) (520) (79)
26.80 22.80 26.00 24.00 3.10 14.40 9.25 (680) (580) (660) (610) (79)
33.50 29.50 32.70 30.70 3.10
(850) VW
33.50 29.50 32.70 30.70 3.10 (850)
Wl
W2 W3 W4 D
9.45
16.90
16.90
16.90
0'50)
13.30
(338)
20.75 20.50 3.14 12.60 7.10
20.75 20.50
(527) (520)
20.75 20.50
(830)
(830) (780)
13.00 2.55 9.85
W)
(65)
2.55 9.85 5.70
2.55 9.85 5.70
3.11
t-1
3.11
(780)
(79)
WI
Dl
d
5.70
(250) (145) (10)
9.85
(250) (145) (10)
12.60 7.10 (320) (180)
12.60 7.10 (320) (180)
(366) (235) ---
14.40 (366) (235) ---
14.40 (366) (235) ---
5.70
9.25
9.25
40
40
.40
40
-60
-60 (15) .60 (15)
---
---
---
3-4
AF-300C lnverters GEK-85718
4.
WIRING PROCEDURES
Wiring should be implemented in accordance with the following procedures. If these procedures dis-
agree with local electrical codes, the local codes
should be followed instead. After completing wiring,
check that all wires have been properly connected.
CAUTION:
Incorrect wiring mav cause damaae to
the inverter and/or result in improper operation. The Main Circuit Terminal Block is located at the
bottom portion of the inverter. The Control Circuit
Terminal Block is located near the middle of the
inverter. (See Figure 4-l) NOTE: P7-P and
CM-T/-I/?
terminals are jumpered
together at the factory. A DC Reactor is also shipped
for connection between terminals
Pl-P
on 100 HP
inverters and above.
MAIN CIRCUIT WIRING CAUTION:
connected to the U, V, W terminals nor the N,
Be sure that the power supplv is never
PI,
and
P terminals. Never connect N to Pl nor N to P.
Power Supplv Connections
1.
Connect a circuit breaker between the three-phase power supply and main circuit terminals Li ,
l2,
L3
(see Figure 4-2).
-
An AC Line Reactor may be required for some
applications. (See
“AC
Line Reactor Connec-
tion” paragraph in this section.)
2.
If a starter or contactor is used between the circuit breaker and the main circuit terminals to shut off power to the inverter if an inverter fault occurs,
then wire control power as shown in Figure 43.
NOTE: See TABLE 2 for description of all terminals
and TABLE 3 for application wiring list.
NOTE: An MC Contactof (see figure 4-3) should be used when either:
(7) A dynamic braking option is installed. (2) Thepower supply lines can experience an ovef-
voltage condition. if the current rating of the MC Contactor coil is too large for the Fault Relay Contacts, be sure to use a pilot relay as shown in Figure
472.
RF-30K
TBS
RX1
RX2
JBA~JEIB~~EC~RIN~ LV ImTl
Q
JmsG
=
‘3-E FRR OL FMI
II 1 12 1 13
LI I
SW2 s-41
I
I
CONTROL CIRCUIT
FM2 VI CI XI X2 X3 CM RTI RT2 RUT
(FWOIRNI BX I CH JTHRIRSTI FU 1
MRIN CIRCUI;
L2 1 L3
INPUT
Figure 4-1.
u I
TERMINAL BLOCKS
TERtlINRL
I
TERMINRL BLOCKS
v I w
OUTPUT
1-1
4-1
BLOCKS
IL
CONTROL CARD
TB6 TB4
\-G/lZj
v
m}
0
RF-3 00c
MRIN
POWER
INPUT
Ll
2
RC LINE
REACTOR
1
i
>
P
CUSTOMER SUPPLIED
3
PHASE
RC POWER
(IF REQU
CIRCUIT
BRERKER
IRED)
Figure 4-2. AC POWER CONNECTION
AUXILIARY CONTROL POWER SUPPLY CONNECTION
When using the circuit shown in Figure 4-3, it is necessary to connect terminals
“RO”
and ‘To” to the
hot side of the MC Contactor.
CAUTION:
Do not neolect to make the RO and TO
connections. If not made, continuous cyclinq of the MC Contactor mav occur under certain conditions that will stress (or fail) the charoe resistor and DC link capacitors.
AC LINE REACTOR CONNECTION
An AC Line Reactor is required on AF-300C inverters
if the KVA rating of the supply transformer is greater
than
lOtimes
the horsepower rating of the inverter or 500 KVA (whichever is greater). This reactor is con­sidered optional and must be purchased separately when required for specific applications (see “Op­tions’ paragraph in Section 2).
(CUSTOMER
SUPPLIED)
Figure 4-3. AUXILIARY CONTROL POWER SUPPLY CONNECTION
DETACH THE FACTORY INSTALLED SHORT-CIRCUIT
CONRlCTOR
(IF PRESENT)
\,_ _. _ _ (
I
.
N Pl
T
P
DC
RERCTOR
Figure 4-4. DC REACTOR CONNECTION
DC REACTOR CONNECTION
A DC Reactor is required on all
AF300C
inverters rated 100 HP and above. This reactor is included in the purchase of the inverter and shipped with the inverter. This
reactor must be installed or the war-
ranty will be voided.
1. Remove the jumper between the
‘P”
and
‘PI”
terminals (installed at factory).
2. Connect DC Reactor between these terminals as
shown in Figure 4-4 (see TABLE 3 for wire sizing).
4-2
Motor Connectlons (See Fiaure
WARNING-BURNANDSHOCKHAZARD:
Shut off the power supply before making the out­put connections. If the power supply is on, a
voltage may be present between the output termi-
nals even though the lnverter Is stopped.
4-31
BRAKING UNIT AND BRAKING RESISTOR CONNECTIONS
NOTE:
tion with braking unit. The number of braking units and braking resistors varies per the horsepower of the inverter and the braking requirements of the the appli­cation (see Figure 4-6 for wiring).
1.
Connect the 3-phase motor wires to the U, V, and W terminals of the Main Circuit Terminal Block as shown in
Figure4-5
view A).
(SeeTABLE
2for de-
CAUTION:
tween the inverter and the brakina unit.
scription of all terminals and TABLE 3 for wire sizing.)
NOTE: Motor
will
rotate counterclockwise
when
viewed from the load side when connected normally. If the motor rotates in reverse direction, interchange any two of the U, V, or W terminal connections.
1. Remove the jumper between the THR and CM terminals of the inverter (installed at the factory).
2. Connect the thermal contacts in series (to THR and CM) so that both the braking unit and braking
resistor will be OFF should overheating occur.
-- Connect braking unit so that thermal contacts
2. If contactors are connected as shown in Figure
4-5
(View B), connect an interlock to prevent clos-
ing both contactors (MC-1 and MC-2) at the same
time. A contactor on the output for any other
purpose must operate such that the contactor
closes before the inverter is started and opens
after the inverter stops.
3. When two brakino units are used, set Switch SW1 on the printed circuit board of the braking unit in
the 1-2 position (set in 2-3 position at factory).
Braking Resistor must be used in combina-
Alwavs match terminals ‘P’ and ‘N’ be-
can be made for terminals 1 and 2 (of braking unit) to terminals THF? and CM (of the inverter) respectively.
CAUTION:
output
heat and be
Do not connect anv capacitors in the
wires. The capacitors and inverter will over-
damaoed
due to harmonics.
ff-300c
OUTPUT
u v w
HOTOR
w
View A
RF-300C
IN=‘UT
Ll
1 L2 1
0
0 0
P’ P’ P’
CUSTOMER SUPPLIED
3 PHRSE AC POWER
L3
NOTE :
CROSS INTERLOCKING BOTH STRRTERS
‘ON’ FIT
THE
Ll
1 v 1 w
RC
LIN
REFICTCR
K-1
CIRCUIT -- -- -­BREAKER
SRME
AF-300C
OUTPUT
.
..__ ._.. .
(MC-I RN! ME-2,
View B
REO
TIM.
1’
J\!,. _
,*’ :
I
IR D TO
.__._
-- -- --
PREVENI
FROM
_-__
0
MC-2
Figure 4-5. OUTPUT WIRING CONNECTIONS
4-3
AF-300C
lnverfers
1 Braking Unit
1 Braking Resistor
View
GEK-85716
‘A”
NOTE:
Be sure to remove the jumper from between terminals
THR
and
CM
or the Braking Unit will not operate.
1 Braking Unit
2 Braking Resistors
View
“B”
NOTE: Be sure to remove
the jumper from between terminals THR and
CM
or
the Braking Unit will not
operate.
Figure 4-6.
BFlAKlNG RESISTOR AND BRAKING UNIT CONNECTIONS (Part
4-4
1
of 2)
1 Braking Units
3 Braking Resistors
Vlew
%a
AF300C
hverters
GEK-85718
NOTE:
Be sure to remove the jumper from between terminals THR and CM or the Braking Unit will not
operate.
2 Braking Units
4 Braking Resistors
View “D
I
I
--j
01
02
$1
32
I2
I=
--
i
Ii
1
I
1 I
NOTE: Be sure to remove the jumper from between terminals THR and
CM
or
the Braking Unit will not
operate.
Figure 4-6.
BRAKING RESISTOR AND BRAKING UNIT CONNECTIONS (Part 2 of 2)
4-5
Figure 4-7.
GROUND CONNECTIONS
GROUND TERMINAL CONNECTIONS CONTROL CIRCUIT WIRING
It is necessary to provide grounding in order to pro-
tect against an electral shock due to leakage and to
reduce the effects of electrical ‘noise”. (See Figure 4-
7.1
Preferably, each inverter or other piece of equipment should be grounded individually. If this is not pos­sible, the alternative method is common grounding where the ground wire from each piece of equipment is connected at the ground point.
NOTE: The ground wire should be as large a gauge
as possible and the length should be kept as short as possible.
Avoid grounding method where the ground wire is used in common with other equipment i.e., do not daisv chain around
connections.
Perform all control wiring in accordance with the
following applicable subparagraphs (and referenced
Figures) and the applicable circuit as shown in Fig­ures 4-15 to 4-26 (located at the end of this Section). Refer to TABLE 2for terminal descriptions and TABLE
3 for wire sizing.
CAUTION:
Hiah reliabilitv contacts for lowvoltaqe
and current sianals must be used on the control circuit terminals (FWD, REV, BX, THR, X2. X3, RTI , RT2,
the voltage is approximatelv
AUT).
When the contact is open,
+24 VDC;
contact is closed, the current is approximatelv 3 mA
DC (see Fioure 4-12 for circuit).
CAUTION:
The control circuit terminal wirina should be kept as far awav as possible from the main power wirinn to prevent operational error due to noise inter-
ference. Never install both tvpes of wirinq in the same
INVERTER CONTROL
CIRCUIT WIRING
duct or conduit. (A separation distance of 10 centi-
I
meters [4 inches1 or more is recommended.) If the control circuit wirina must cross the main power wir- inn, it should cross at a riaht annle and be seperated
#$$, plq
/=lIN
CIRCUIT WIRING
bv at least 1 inch(see Fiqure 4-8).
FIST.
PU, IL, Xl
when the
t
CROSS AT RIGHT ANGLE AND KEEP AT LEAST 1 INCH
SEPERATION
Figure 4-8.
CONTROL WIRE ROUTING
*
x
KEEP NOT LESS
THffl 4’(l@cm)
L
CAUTION:
trol circuit wirina; wirinn should be as short as
I
sible, i.e. 20 meters
to the invetter around terminal and leave the other end open and electricallv insulated.
CAUTION:
Use shielded twisted wire for the con-
POS-
(65
feet) or less. Connect
shield
Install a suppressor in parallel with any
relavs or solenoidtvpe coils, etc. that mav be close to
the inverter.
4-6
ov
(I chi I
f3x
IREVI FWDI
FREQUENCY
REFERENCE
13 I 12 I 11 I ( ( I AUT I
OUTPUT
FREQUENCY
SIGNAL
ANALOG PULSE
SPEED POT
Figure 4-9.
FREQ. SETTING/MONITORING EQUIVALENT CIRCUIT
Frequencv SettindMonitoring
Equivalent Circuit
Frequency Setting Power Terminal (13) can beset for either positive or negative voltage polarity via jumper SW1 on the Main Control Card. (See Figure 4-9 for equivalent circuit.)
-- Factory setting of polarity is positive (SW1 in l-2 position).
-- Also see Function Code 47.
E
2
FREQUENCY
2 ’
METER
Although output frequency is digitally displayed on the keypad, when an external display is required,
connect a frequency meter to monitoring terminals FM1 and FM2. Either analog or digital meters can be connected, but Switch SW2 must be set in accor­dance with the type meter used. Set SW2 as follows:
-- 1-2
Position for Analog Output (factory setting)
-- 2-3 Position for Digital Output
-- Also see Function Codes 40 and 50
NOTE: These
signed for meter connection
output
terminals (F/W,
only.
FM2) are de-
Ifa
special applica­tion (for control, etc.) is required, confact the distribu­tor that supplied the inverter.
4-7
AMOOC lnverters
GEK-85716
Alarm Reset Switch Connection
If an external RESET is required, connect a momen-
tary pushbutton to the RST terminal as shown in
Figure 4-10.
NOTE:
parallel operation to be performed with the RESETkey
on the Keypad Panel. Carelessness when setting Function Codes and/or retrieving faults
inputting a RESET signal.
Equivalent Control Circuit
The equivalent circuit as shown in Figure 4-11 is pres-
ent in the control circuits (FWD, REV, BX, THR, RST, PU, IL, must be highly reliable contacts for low voltage sig­nals. 24 VDC is present when the switch is open; 3
mA DC is present when the switch is closed. The
maximum leakage current that can be tolerated and still maintain an OFF state is 80 uA. The maximum
voltage drop that can be tolerated and still maintain
an ON state is one volt.
The application of this terminal allows a
may result
Xi,
X2, X3, RTI , RT2,
AUT).
The contacts used
in
CAUTION:
supply connections are correct. Damaue will occur if
Figure
,
Verifv
that the
4-l
0. FAULT RESET CONNECTION
! 1
.
polar&
;‘customer
of the power
RESET
SWITCH
supplied.
1p
1 t_______.__ 0
Flgure
Fault Relay Contact Rating
The Fault Relay contacts are rated at 250 VAC, 300
milliamps inductive @ cos 9 2 0.3. When a large MC Contactor is used, use a pilot relay with the appropri­ate contact rating and coil rating. (See Figure 4-12.)
Open Collector Output Terminal Connection
It is recommended to use the optional relay output
unit when using these output signals, however it is
possible to use a customer furnished power supply
and relays. The open collector outputs are “sink circuits. If customer supplied relays are to be con­trolled, an external DC power supply (27 VDC max.) is
required. A diode must also be installed (reverse
biased) for relay coil suppression (see Figure 4-13).
4-I
1.
EQUIVALENT CONTROL CIRCIUT
-
4-8
I
Figure 4-12.
UP TO
Figure 4-13.
27VDC
(CUSTOMER
SUPPLIED)
A A
FAULT RELAY CONTACTS
+-J-d
THAN
50ma.
A
OPEN COLLECTOR CONNECTION
Surge Suppressor Connection
When a magnetic coil actuated device such as a starter, control relay, solenoid valve, etc., opens and closes, the current will sharply fluctuate resulting in a voltage spike (or noise). In some instances this voltage spike can cause misoperation of the electri­cal circuits of the inverter and other peripheral equip-
ment. A surge suppressor should be connected across all magnetic coils connected to the inverter, as well as across all magnetic coils with supply wiring
running parallel with inverter wiring. Wiring should be kept as short as possible (8 inches
mum). See Figure 4-14 for
connection
[20
cm] maxi-
methods and
thefollowing chart for recommended RC Filter capac-
ity.
Surge Suppressor (RC Filter) Application
AF-300C
/metiers
GEK-85716
I
Magnet 1 c
Eauipment
Magnetic Contactor (DC)
Main Circuit (AC) Auxiliary Relay (DC) Auxiliary Relay (AC) Solenoid Brake (DC)
Braking Clutch
*Diode to be used only when the current of the operating coil is no more #an 1 Amp.
cant
actor
0.2 microfarad,
0.2 microfarad,
0.1
0.2 microfarad,
0.2 microfarad, 500 VDC Capacitor; 500 Ohm Resistor or diode*.
0.2 microfarad, 500 VDCCapacitor; 500 Ohm Resistor.
Figure 4-14.
RC Filter or Diode
500
VDC Capacitor; 500 OhmResistor or diode*.
500
VDC Capacitor; 500 OhmResistor.
microfarad,
DC
500
VDC Capacitor; 500 Ohm
500
VDC Capacitor; 500 OhmResistor.
Resistor or diode*.
SURGE SUPPRESSOR CONNECTION
I
4-9
AF-300C
lnvetfers
TABLE 2: TERMINAL IDENTIFICATION/FUNCTION
GEK-85716
Terminal
Label
MAIN CIRCUIT:
Ll, a
L3
u, v,w
P, N
P,
Pl
E (G)
CONTROL POWER:
RO, TO
Terminal Name
AC Supply Line
Input Terminals lnverter Output
Terminals
Brake Unit Terminals
DC Reactor Connection Terminals
Ground Terminal Connection for ground.
Control Power Auxiliary Input
Function
Connection for commercial power (400460 VAC @ 60 Hz) or
(380-460
Connection for 3-phase induction motor.
Connection for brake unit (optional). (Brake resistor must be connected through brake unit.)
To be connected when power factor improving DC Reactor
(optional on 75 HP and below) is used. (Provided and required on 100 HP and above.)
Connection for single-phase AC power for backing up the control circuit power when input starter is used (460 VAC).
VAC @ 50 Hz).
FREQ. SET MONITOR
11
12
13
Cl
Vi
FM1 FM2
Frequency Setting Common
Frequency Setting
Voltage Input
Frequency Setting
Voltage Output Term. Frequency Setting
Current Input Voltage Input
Auxiliary Terminal Frequency Meter
Connection Points
Common terminal for frequency setting signals (terminals 12, 13,
When 0 to + IO VDC is input, the maximum frequency is
reached at +I 0 VDC. The output frequency is proportional down to 0 VDC. Input impedance is 22K ohm. (Speed Pot Wiper)
+ 10 VDC power supply for Speed Pot (1 (Speed Pot Power)
When 4 to 20mA DC is input, the maximum frequency is reached at
20mA. The output frequency is proportional down to 4mA. Reaches maximum output frequency at
freq. is proportional down to 0 VDC). Input impedance is 22K ohms.
Provides an output of 0 to +10 VDC
Available for connection of a voltmeter (with internal resistance of
1 OK ohms). FM1
SW2 must be changed to 2-3 position. (See Figure 4-9 and
Function Codes 40 and 50.)
Vl,
and Cl). (Speed Pot Common)
(+lO
= Pos., FM2 = Neg. To output a digital signal,
OmA
maximum).
+/-I
0 VDC (the output
VDC at max. frequency).
4-10
AF-300C lnwerters
GEK-85718
TABLE 2: TERMINAL IDENTIFICATION/FUNCTION
Terminal Label
CONTACT INPUT:
CM
AUT
FWD REV
BX
Xl x2
x3
Terminal Name
Contact Input Corn. Current Input Select
Forward Command Input Terminal Reverse Command Input Terminal
Motor Coast-To-Stop Input Terminal
Multi-Step Frequency
Setting Terminals Increase/Decrease
Frequency Control
Momentary START/ STOP Contact Selection
Function
Common terminal of contact input signals. When the frequency setting signal is provided with voltage or
current, this changes over the input signal to be used. AUT-CM On = Selects current input (4 to 20 mA). AUT-CM Off = Selects voltage input and frequency setting input,
Forward command via FWD-CM (closed). Reverse command via REV-CM (closed). When FWD-CM is closed and REV-CM is closed at the same time, the inverter will decelerate and stop (only when Function Code 41 is set inactive).
Motor will coast-to-stop with BX-CM (closed). No alarm signal will be output. If BX-CM is opened while FWD or REV closed , the inverter will start to operate because a RUN command is present.
Eight differenct frequency settings can be made with the
combinations of ON and OFF of each terminal. By changing Function Code 42 to YES, the Xl and X2 terminals are
changed from multi-step speed commands to increase and decrease commands. The increase and decrease commands simulate a motorized speed pot.
By changing Functtion Code 41 to YES, the X3 terminal is changed from a multi-step speed command to a momentary pushbutton common input for momentary START/STOP commands. With X3­CM closed, FWD and REV signals input by a pulse signal (pulse width of 50 msec or greater) can be self-sealed.
(continued)
RTl
RT2
THR
RST
Multi-Step Accel/
Decel Time Command
Input Terminals
External Thermal External Braking
Resistor Thermostat Terminal
Reset Signal Input Terminal
Rela]
RTI-CM (closed),
second, third, and fourth types of acceleration/deceleration time selections.
by normal first acceleration/deceleration time.
With THR-CM open, OH2 trip will occur and motor will coast-to-stop. NOTE: With no external thermal relay or external braking resistor
thermostat, the THR-CM terminals must be jumpered or the inverter
will
not operate.
Faults are reset when a momentary contact is made between the RST-CM terminals for more than 0.1 seconds. NOTE: If there is an input to the
not RESET.
RT2-CM
NOTE: When there is no input to
4-11
(closed), RTI-RT2-CM (closed) are the
RT1, RT2,
FWD
or REV terminals, the unit
operation is
will
Af-300C
lnverters
GEK-85718
TABLE 2: TERMINAL
Terminal
Label Name
CONTACT INPUT: (continued)
PU
IL
OPEN COL­LECTOR OUTPUT*:
CME RUN
FAR
FDT
OL
LV
Terminal
Commercial To lnverter When PU-CM is closed, reference increases and preparation for
Output Starter When providing an output starter, its auxiliary contact (normally
Interlock closed) must be between IL-CM (closed). When the starter picks-
Open Collector Comm. Common terminal for output of open collectors.
lnverter
Set Frequency When the set frequency is reached (inverter is up-to-speed), Detection Signal FAR-CME will be ON. See Function Code 36.
Optional Detection of FDT-CME will be on when the output frequency is larger than the set Frequency Level
lnverter Overload Early Warning Signal
Undervoltage Stop
In Operation
IDENTlFtCATION/FUNCTION
inverter operation is made. When set to OFF after a fixed time, inverter will operate. (Used for open transfer Line-lnverter-Line; also used with terminal
up, the auxiliary contact must open (IL-CM open) permitting inverter operation. IL-CM On - interrupts inverter operation; IL-CM Off continues inverter operation. Used with terminal ‘Pu” for transfer.
Transistor turns ON between RUN-CME at start frequency and above. Transistor turns OFF when inverter is stopped, during coast stop, and DC braking.
detection frequency; FDT-CME will be OFF when output frequency is less than set frequency. See Functtion Code 35.
OL-CME will be on when the output current is larger than the set value; OL-CME will be OFF when output current is less than set
current. See Function Code 32.
LV-CME will be on when an undervoltage condition exists. LV-CME will be off when output will occur for a set time after power-up.
“IL’
for transfer.)
the
DC link voltage is above the trip threshold.
(continued)
-
No
CONTACT OUTPUT:
Ax1
30A
308
3oc
*Open collector outputs are
must
be provided via an external power supply when using them to control external relays (see Figure 4-13.)
The Relay Option
Run Relay Dry Contact Contact is closed when the inverter is running. (Contact rating: output
Fault Relay Dry Contact Output
‘Sink”
GVKC3RY
has this power supply built in.
circuits
250 VAC, 0.3 Amps inductive @ cos theta 2 0.3)
During normal operation, the relay is not energized and contact is
made between 308 and 30C. When a fault is detected, the relay is energized and contact is made between 30A and 30C.
rating: 250 VAC, 0.3 Amps inductive @ cos theta 2 0.3)
wi?h +27 VDC,
4-12
50mA maximum ratings.
Power for these circuits
(Contact
TABLE 2: TERMINAL IDENTIFICATION/FUNCTION (continued)
Terminal Terminal Label
PROTEC-
TION
Name
I
Function
I
AF-3OOC Invertem
GEK-85718
GFl
GF2
Ground Fault Input terminals exclusively used for internal ground fault detection Protection Input unit.
TABLE 3: WIRING AND EQUIPMENT SIZING (Power Wire, AWG*)
lnverter HP
40 40
An
50
1 2
Qty.**
1 1
--
Input
Power Power Reactor Diameter
2
--
me -- __
50 1 -- 2
50
60 60
&)
75 75
75
100 100 100
125
125
125
150 150
150
200 2 200 2
20(-j
250 2 250 3 250 3
300 3 300 3
3oc)
__
1 1 --
__ __ -­1
1 -­__ -_ --
1 1 -­1 -- --
1
1 --
2
2 2
-- -- --
l/O
2/o
2/o
4/o
-- --
l/O
--
2 -- --
3/o
--
2
3
__ --
4/o
--
-- --
2/o
-­__ __
Output DC
__ __ 2
-- --
-- -­2
--
l/O
--
3/o
--
4/o
--
--
__
--
--
--
--
--
--
4/o
--
--
l/O
--
110
--
3/o
-- --
2/o
__
2/o
--
VO
--
--
4/o
--
3/o
--
--
4/o
Stud
0.236
0.236
0.315
0.315
0.315
0.315
0.315
0.315
0.393
0.393
0.393
0.393
0.393
0.393
0.393
0.393
0.433
0.512
0.512
0.512
0.512
0.512
0.512
0.512
0.512
0.512
GE
Amp Amp
Terminal Terminal Crimp
104X161AA- Number
057 320383 69062 057 320383
056 321600 69062 056 321600 69062
060 321868 056 321600 69062
023 36923 060 321868
023 36923 69120 025 36927 69120 068 321878
068 321878 69120 068 321878 060 321868
060 321868 060 321868
024 36925 026 36929 69120
026 36929 028 36934
028 38934 024 36925 026 36929
024 36925 024 36925 028 36934
Tool #
69062
69120
69120
69120
69120 69120
69120
69120 69120 69120
69120 69120
69120
69120 69120
69120
69120
69120
*Wire
size from NEC Table 310-76. Copper
wire
rated
ambientand 1.25 times inverterratedamps. These
codes.
**Quantity of wires in parallel per terminal.
6oOC
for 100 amps and less, 75% for over 100 amps in
are
minimum wire sizes; consult and conform to localand national
4-13
30%
AF-300C /metiers
GEK-85716
-I
2
rz&. 7TiR
IWlJl
L3
1
Cl
Vl
13
&l?c
_
TO,
RF-300C
U
V
W
P
;EJ ._______-_-_---_________
+ _ - -_ -- _ -- -
& _- - - _. .-. -
,
t-- _ - _ - ­)-.,L;-
.-------------.---.------.-,~
(1) CAUTION: Do not connect externally supplied power to terminals 1 or 2 on the Braking
Unit or the Braking Resistor.
Doing so will cause damage to occur.
,..-........- -_,.
.-. '
;
I *
. . . ..-..---_._.-
F
lr f
1. +-*A-
:
:
$
:: *I
I 1 \i
I’
E(G)
PEV
CM
FM1
FM2
6
RUT
KI
K2
RTI
RT2
Pu
IL
i
EIX
Rsr
CM
TH?
N
FUN
Rl
81
Cl
A2 B2
c2 A3
B3 C3
ii B4
C4 I35 85
c5
Figure 4-t 5.
BASIC CONNECTION DIAGRAM
4-14
AF-300C
hverkrs
GEK-85718
IMPORTANT: The following CAUTIONS apply to Figures 4-l 6 through 4-26.
Other NOTES that apply to a specific Figure are shown on that Figure.
I
*l -
CAUTION:
nals THR and CM and connect Normallv Closed thermal interlock contacts in series between THR
and CM.
*2 -
CAUTION:
START/STOP commands from remote are ionored.
If it is desired to use thermal interlocks, remove the jumper from between termi-
If the “LOCAL/REMOTE’ switch on the Kevpad Panel is in the ‘LOCAL’ position,
I
NOTE:
LOCAL/REMOTE switch should be in the ‘LOCAL’ position (*2).
RF-300C
DYNAMICDYNAMIC
BRAKEBRAKE THERMALTHERMAL SWITCHESSWITCHES
Figure 4-18.
Figure 4-18.
OPERATION FROM KEYPAD
OPERATION FROM KEYPAD
4-l 5
NOTE:
“0’
(Yes).
LOCAL/REMOTE switch should be in the ‘REMOTE’ position (“2). Set Function Code 41 to
NOTE:
‘0”
(Yes).
BRAKE THERMAL SWITCHES
Figure 4-17.
SPEED POT
LK n
,
l/2
WRTT
REMOTE OPERATION WITH MOMENTARY CONTACTS
LOCAL/REMOTE switch should be in the ‘REMOTE” position (*2). Set Function Code 41 to
Figure 4-18.
SWITCHES
REMOTE OPERATION WITH MOMENTARY CONTACTS AND REVERSING CAPABILITY
4-16
AF-300C
Inwetters GEKm8571
6
NOTE:
‘--*
(No).
LOCAL/REMOTE switch should be in the “REMOTE’ position (*2). Set Function Code 41 to
SWITCHES
Figure 4-19.
REMOTE OPERATION WITH MAINTAINED CONTACTS
NOTE:
‘-’
(No).
RF-3
LOCAL/REMOTE switch should be in the “REMOTE” position
00C
SPEED POT
1K n
,
l/2 WRTT
(*2).
Set Function Code 41 to
BRAKE THERMAL SWITCHES
Figure
4-20. REMOTE OPERATION WITH MAINTAINED CONTACTS AND REVERSING CAPABILITY
4-17
AF-300C
RF-380C
lnverters
GEK-85716
3EIA
FIX
1
flX2
CME FRR OL FM1 FM2
30B 30C
RUN LV FDT II 12
I
SPEED POT
1K I-l, 112
I
Vl
Cl XI X2 X3 CM
13 FWD REV BX CM THR RST PU IL
I
I I
/I
/
1
RTl
RT2 RUT
I
f
­1
-
WATT
*1
T
f
DYNAMIC BRAKE THERMAL SWITCHES
TLml&
NOTE: LOCAl&EMOTE switch should be in the “REMOTE’ position (*2). Set Function Code 41 to
‘--”
(No).
NOTE: JOG Decel follows the same slope as RUN Decel, except when JOG is commanded during operation above the JOG frequency setting. Check the following Function Codes:
Function Code 23 = JOG Speed (Frequency) Setting. Function Code 2A = JOG Accel Time Setting. Function Code 26 = JOG Decel Time Setting.
Figure 4-21. REMOTE OPERATION WITH MAINTAINED CONTACTS AND JOG FUNCTION
4-18
AF-300C
SPEED POT
1K i-L, l/2
WATT
AWOOC fnverters
GEK-85718
NOTE:
LOCAL/REMOTE switch should be in the “REMOTE’ position (*2). Set Function Code 41 to
‘--’ (No).
NOTE:
JOG Decel follows the same slope as RUN Decel, except when JOG is commanded during
operation above the JOG frequency setting. Check the following Function Codes:
Function Code 23 = JOG Speed (Frequency) Setting. Function Code 2A = JOG Accel Time Setting. Function Code 26 = JOG Decel Time Setting.
Figure 4-22. REMOTE OPERATION WITH MAINTAINED CONTACTS AND JOG FUNCTION
WITH REVERSING CAPABILITY
4-I
9
AF-300C lnverters
GEK-85716
NOTE:
‘0’
(Yes).
Figure
LOCAL/REMOTE switch should be in the ‘REMOTE” position (*2). Set Function Code 41 to
SPEED POT
lKfi.l/2
WATT
OPEN:
MANUAL SPEED
BRAKE THERMAL SWITCHES
CLOSED:
AUTO SPEED
REFERENCE
4-23. REMOTE OPERATION WITH MOMENTARY CONTACTS AND AUTO/MANUAL OPERATION
NOTE:
‘0’ (Yes).
LOCAL/REMOTE switch should be in the “REMOTE” position (*2). Set Function Code 41 to
AUTO SPEED
REFERENCE
Figure
SPEED POT
IK IT, I/2 WRTT
4-24. REMOTE OPERATION WITH MOMENTARY CONTACTS AND
BFtAKE
THERMAL SWITCHES
REVERSING CAPABILITY AND AUTO/MANUAL OPERATION
4-20
AF300C
lnvetiers
GEK-85716
NOTE: LOCAL/REMOTE switch should be in the “REMOTE” position (*2). Set Function Code 41 to
‘-’
(No).
RUT0
SPEED
REFERENCE
OPEN: MANUAL SPEED
CLOSED:
AUTO SPEED
REFERENCE
SPEED POT
1K n,1-‘2
WRTT
BRAKE THERMAL SWITCHES
Figure 4-25. REMOTE OPERATION WITH MAINTAINED CONTACTS AND AUTO/MANUAL OPERATION
NOTE: LOCAYREMOTE switch should be in the “REMOTE position (*2). Set Function Code 41 to
‘-’
(No).
AUTO’
SPEED
OPEN:
MANUAL SPEED
REFERENCE
CLOSED: AUTO SPEED
REFERENCE
SPEED POT
lKn,l/2
WRTT
BRAKE
THERMAL
SWITCHES
Figure 4-26. REMOTE OPERATION WITH MAINTAINED CONTACTS AND
REVERSING CAPABILITY AND AUTO/MANUAL OPERATION
4-21
AF-3OOC inverters
GEK-85718
NOTES:
4-22
5.
INVERTER
AF-300C
OPERATION
lnverfers
GEK-85718
BEFORE APPLYING AC POWER INSPECTION
After mounting and wiring has been completed, check the inverterfor the following items before applying AC power:
--
Check for wiring errors (especially main circuit wiring).
-- Verify that there are no wiring chips, screws, etc. remaining in the inverter.
--
Check that all screw and terminal connections are tight.
--
Verify that no exposed wire ends are touching other terminals.
Before a test run is performed,
understand the operation of the Keypad Panel as described in the following charts and paragraphs.
Refer to Trial Operation ’ paragraph near the end of this Section for recommended procedures.
besure to review and
CAUTION:
the inverter termirlals or control circuit terminals. For meqqer testina method, refer to Section 7, Mainte-
nance and Inspection.
KEYPAD PANEL IDENTIFICATION/ FUNCTION
The Keypad Panel is installed on the front panel of the inverter and is used for data display and Function Code setting and modifications. The inverter is oper­ated with the Function Codes set by this Keypad Panel and by external operation/control commands.
Also, FORWARD/STOP and REVERSE/STOP can be input and the reference frequency can be set from the Keypad Panel. A Mode Change Switch is also pro­vided to switch operation between LOCAL (Keypad Panel) and REMOTE (control circuit terminals). See the following chart for a description of all Keypad Panel functions and TABLE 4 for Keypad Panel op­eration procedures. Refer to Figure tion of the components of the Keypad Panel.
¬
conduct_menoer testsbetween
5-I
for identifica-
KEYPAD PANEL FUNCTIONS CHART
Function
Operation Monitoring Monitor the operation states of the inverter. Function Code Setting: Basic Function Codes Set data required for operation.
Auxiliary Function Codes Set data required for control. Calibration Adjust output signals to match with instruments
Function Codes externally installed.
Fault Monitoring
Set Data Protection Reset Data reset at Function Code setting, reset to return
Operation Mode Selection Switch for changing between “Local and ‘Remote’
Operation Commands Forward, Reverse, and Stop commands can be
Frequency Setting Commands Increase and decrease reference frequency com-
Display and retrieval of a fault and the operating conditions at the time of the fault.
Protect set data against accidental modification.
to operation monitoring mode after completing the setting, fault reset and error display reset.
modes of operation.
entered in the “Local mode.
mands can be entered in the “Local’ mode.
Description
5-I
FUNCTION
DATA
Figure 5-1.
KEYPAD PANEL COMPONENT iDENTiFiCATiON
TABLE 4: KEYPAD AND DISPLAY OPERATION
LED indicator
three sections as follows:
Function Code Display-Displays
the selected Function Code number. LED Selection Indicator under each digit lights when that digit is selected to be changed.
Data Display - Display in four digits the operation
data, Function Code setting data, and the fault codes.
Unit Indicator
symbol corresponds to the contents of the data display.
NOTE: All letters are displayed in upper case
except W, W, and
-The LED indicator is made up of
in two digits
-The LED on the left of each unit
T.
Touch
Kevs - There are eleven Touch Keys and
one switch that perform as follows:
SHIFT
Key - Selects the Function Selecting Mode
and the Parameter Setting Mode.
-- The order of selecting each digit is fixed as 2nd Function digit - 1st Function digit - Data digits in sequence, except the order is 2nd Function Digit - 1 st Function digit for Function Codes 00-05, Fl
2).
--
When the data on the Data Display is blinking,
-F3,
and F5-F7 (see Figure
5-
you cannot change the selection by pressing the SHIFT Key. Press the RESET key to
recover original data and stop the blinking or press the
data and stop the blinking. The
SET
key to store the newly changed
SHIFT
key
can then be used to make the selection.
5-2
AF-300C
Inverters
GEK-85716
TABLE 4: KEYPAD AND DISPLAY OPERATION
UP and DOWN ARROW Keys - Used to modify
values
- The
- The
--
FAST Key - Used in conjunction with the DOWN ARROW
Code data change.
--
--
-- Pressing
SET Key - Used when setting parameters to enter
set data into memory.
-
-
RESET Key - Used in the Parameter Setting Mode
and Fault Monitoring Mode as follows:
Parameter Settlng Mode
-- Reset of Set Data -
-- Reset of Set Error Display -
-
of each mode selected
UP ARROW
DOWN ARROW
The increase and decrease of values can be set anywhere between the upper and lower limits (see TABLE 5, Function Code Data).
Pressing the pressing FAST key) will obtain low speed.
While pressing the press
FAST
and twice to obtain high speed changes. the UP or DOWN ARROW key to clear the
moderate and high speed changes.
SET or RESET
FAST
Protection’ Function (see “Set Data Protection” paragraph in this Section).
When new data is being set, the Data Display will blink; pressing SET key will enter the new data into the memory and the blinking will stop.
Data that has been set in the memory is not
erased when power supply is turned off.
SET
so that you can return to the original data.
when ‘Err” is displayed due to incorrect setting
and the set data will be cleared so that you can return to the previous data setting.
Return to Operation Monitoring Mode - After
setting parameters, press to Operation Monitoring Function Code that had been selected and displayed before setting parameters.
key allows selection/setting of ‘Set Data
key and the displayed data will be cleared
key increases values.
keys to increase speed of Function
UP
or
DOWN ARROW key
UP
key once to obtain moderate speed
Press
by SHIFT key.
key
decreased values.
or
DOWN
key
RESET
RESET
ARROW key,
while
key prior to
Press
RESET key
key to return
UP
and
(without
Release
pressing
(continued)
Fault
Monitoring Mode
-- Fault Reset - Press RESET key after solving problem and the fault will be cleared so that you can return to the mode selected before the fault occurred. (Faults command is present.)
LOCALREMOTE Switch - Used for operation mode
selection.
-- Do not change while running.
not change if operated while running; the mode changes only after stopping.
--
Local Mode accepts input from the upper and lower rows of keys of the keypad panel.
-- Remote Mode accepts input from the FWD, REV, BX, and frequency setting terminals (lower row keys on the keypad are not accepted except STOP key; see “STOP
INC
SPEED Key - Increases reference frequency
when in the “Local mode.
--
When power is off or afault occurs, the reference frequency is stored.
DEC SPEED Key - Decreases reference frequency
when in the “Local’ mode.
-
When the INCSPEED and DEC SPEED keysare pressed at the same time, the DEC SPEED key is given priority.
-
When power is off or a fault occurs, the reference
frequency is stored.
FWD Key - Forward operation command when in
the
“Local”
mode.
--
FWD Command is not accepted when operating by a
REV
first.}
REV Key - Reverse operation command when in
the “Local” mode.
--
REVCommand is not accepted when operating
by a FWD
first.)
STOP
or “Remote” mode and “Serial Link” mode.
-- When pressed while running in “Locat’ mode,
-- When pressed while running in “Remote’ or
Key - Stop command when in either ‘Local”
MID/REV LED goes off, inverter output frequency
decreases, and motor stops. ‘Serial Link” mode, inverter output is turned off
and motor coasts to a stop (OH2 Fault Trip).
cannot be reset while
The mode will
Key”).
operation command. (Press
operation command. (Press
a RUN
STOP
STOP
5-3
AMOOC
lnvetfers
GEK-85716
Function/l)ata
indicators
fumon
selection
indicator
Figure
OATA
5-2. DISPLAY LED INDICATOR IDENTIFICATION
DISPLAY EXAMPLES CHART
Fault (When the 4th digit indicates the first fault in overcurrent during deceleration)
Setting
frequency exceeds that of the upper limit frequency)
Setting
during operation has been set)
*The display for Synchronous Code 3d) be set in advance. (Also, for Machine Speed [Function Code
must be entered in advance.)
Error (When the setting of the lower limit of
Error (When a Function Code that cannot be set
Speed
(Function Code 02) requires that the Number of Electric Motor Poles (Function
5-4
F 0
051,
the machine speed conversion factor
1.0 c 2
E r r 1
E r r 2
MONITORING CONTROL SIGNALS
AND INVERTER OUTPUT
1
When monitoring functions other than faults, perform the following procedures. (See Figures 5-2 and 5-3.)
OPERATION PROCEDURE
Function Codes 00 through OA provide “Read
Only”
access to inverter control signals and output informa-
tion. These can be very useful in troubleshooting
problems quickly. Function Codes 06 and 07 will be covered first be-
cause they take an additional step, due to the Func­tion Code extension, to get to the signal status infor­mation,
Function 1
Descrbtion
00
01
02
OS
04 05
05
07
06
09 OA Calculated Torque
Output Frequency Reference Frequency Synchronous Speed Output Current Output Voltage Machine Speed Input Signal Status Output Signal Status Motoring Torque Lim. Braking Torque Limit
1
Ind. Unit
HZ Hz
RPM A V
RPM
1. Press
RESET
key and confirm that the Function Selection LED under the second digit of the Func­tion
Code
Display is lit and that thevalue of it is
“0”.
2. Press the SHIFT key once to move the Function Selection LED to the first digit of the Function Code Display.
-
The Function Selection LED under the first digit
Figure
will now be lit and the value of this first digit will
be changed in the next step.
3. Press the UP ARROW or DOWN ARROW key to set the first digit of the Function Code to ‘6’.
9. Press the SHIFT key once to turn off the Function Selection LED and permit data retrieval.
--
4. Press the SHIFT key once to turn off the Function Selection LED and permit data retrieval.
-- The 4th digit of the Data Display will indicate the
Function Code Extension
(A, b, C, d,
or
E)
of
-- Function Code datawill be displayed in the3rd,
Function Code “06”.
-- Function Code datawill be displayed in the3rd,
-- Display symbols are ‘Signal Received = [0],
2nd, and 1 st digits of the Data Display and data
units are shown by the Unit Indicator.
-- Display symbols are “Signal Received = [0],
No Signal Received = [-I’.
5.
Press the UP contents of
6.
Press the
ARROW
b,
C, d, and E (of Function Code 06).
SHIFT
key
key
onceto
to
display (in order) the
light the Function Se-
lection LED under the second digit of the Function Code Display.
7.
Press the
SHIFT
key a second time to move the
All other signals from Function Codes 00 through OA are obtained using the Codes 06 and 07, except that the Function Code extension does not exist.
NOTE: After
have been completed, it is recommended to return
the display to Function Code “00’ (Output Frequency)
unless your particular application deems otherwise.
Function Selection LED to the first digit of the Function Code Display.
-- The Function Selection LED under thefirst digit
will now be lit and the value of this first digit will
be changed in the next step.
6-3. FUNCTION CODE 06 AND 07 DATA
The4th
Function Code Extension
Code
2nd, and 1
digit of the Data Display will indicate the
(A
or
b)
of Function
‘07”.
st
digits of the Data Display and data
units are shown by the Unit Indicator. No Signal Received =
I-1’.
same
procedure as Function
any operations with the Keypad Panel
6.
Pressthe
UP ARROW key oncetosetthefirstdigit
of the Function Code to ‘7”.
5-5
AF-300C lnverfefs
GEK-85718
SETTING FUNCTION CODES
To change Function Codes settings, perform the fol-
lowing procedures. (See Figure NOTE: For convenience, always change the second
digit of a Function Code first since changing the second digit always returns the first digit to a value of zero.
NOTE:If the inverter is running and a Function Code
is changed that is not permitted to be changed while running, an
‘Err2”
fault
will
be displayed. Press
SET key to clear this fault and continue.
NOTE: ff Function Code data is “protected’ (Function
Code
99),
it cannot be changed until Function Code
99 is changed to Wnprotected’. See ‘Data Protection’ paragraph in this section.
OPERATION PROCEDURE
1. Press RESET key and confirm that the Function Selection LED under the second digit of the Func­tion Display is lit and that the value of it is ‘0”.
2. Press the
UP
ARROW or DOWN ARROW key to set the second digit of the Function Display to the second digit of the Function Code to be changed.
5-2)
RE-
8.
If additional Function Codes changes are desired, press SHIFT key and repeat steps 2 thru 7 of this procedure.
NOTE:
After any operations with the Keypad Panel have been completed, it is recommended to return the display to Function Code
‘00’
(Output Frequency)
unless your particular application deems otherwise.
FUNCTION OF RESET KEY AFTER
CHANGING FUNCTION CODE DATA
Pressing RESET after finishing Function Code changes will always return the display to one of the Operation Monitoring Function Codes (Function Codes that begin with zero). The particular one that it is returned to can be changed by selecting the desired Function Code and leaving it there for approximately two or three minutes without pressing any of the keys on the keypad.
NOTE: The “Power-Up
Function Code as the ‘Return Via Code.
Defaul?
will be the same
ReseP
Function
3. Press the SHIFT key once to move the Function Selection LED to the first digit of the Function Display.
--
The Function Selection LED under the first digit will now be lit and the value of this first digit will be changed in the next step.
4.
Press the
UP
ARROW or DOWN ARROW key to set the first digit of the Function Display to the first digit of the Function Code to be changed.
5.
Press the
SHIFT
key once to turn off the Function Selection LED and permit Function Code data changes.
6. Press the UP ARROW or DOWN ARROW key to change data of the Function Code selected to the desired new value.
-
To make large changes, use FAST key to-
gether with
UP
or DOWN ARROW keys. Press UP or DOWN ARROW key first (data will change in tenths of units), then press FAST key once to change data in single units, or press FAST key
twice to change data in tens of units.
-- Data Display data will blink durning change procedure and when desired value is reached.
7. Press the SET key to set the new Function Code value into memory.
--
Data Display will cease to blink after the data has been set into memory.
FAULT INDICATION AND RETRIEVAL
When a fault occurs, the mode is automatically switched to the Fault Monitoring mode. The fault Function
Code will be displayed in the Function Display, the number (in order) and type of fault will be shown in the
Data Display (blinking), and the Function Selection LED for the first digit of the Function Code will be lit.
The fault indication function is composed of the fol-
lowing three parts:
1.
Indication of present fault.
2.
Indication of operating conditions at the time that
the fault took place.
3. Indication of previous faults.
If the fault is a multiple fault, indication can be re-
trieved in the order of occurence (up to seven faults)
by Function Code
In addition, the operating conditions at the time of the first fault can be indicated by Function Codes through
F4
(only for present fault; after RESET, this
information is lost). Also, the first fault for the past three fault trips can be
indicated by F5 through NOTE: First fault means the first detected fault when
mu/tip/e faults occur at the same time.
FO,
1-7.
Fi
F7.
5-6
AF-300C
lnverfers
GEK-85718
NOTE:If control power is
display, fault output signal
turned
will
not be he/d.
off during fault
Perform either of the following procedures to obtain fault information. (See Figures 5-2 and 5-4.)
WHEN FAULT OCCURS AND IS STILL PRESENT
1.
Press
SHIFT
key once to turn off the Function Se­lection LED under the first digit of the Function display and advance control to the Fault Retrieval mode.
--
The fault number
(1)
will be shown in the fourth digit of the Data Display and the fault type will be shown in the third, second, and first digits of
the Data Display.
2. Press the UP ARROW key once to display the second fault in the Data Display.
--
The fault number (2) will be shown in the fourth digit of the Data Display and the fault type will be shown in the third, second, and first digits of
the
Data Display.
3. Press the UP ARROW key again to display the
third fault in the Data Display,
--
The fault number (3) will be shown in the fourth
digit of the Data Display and the fault type will be shown in the third, second, and first digits of
the Data Display.
4. Repeat step 3 until no fault is shown in the Data Display (Example:
“3. - - - ”
indicates that no third
fault exists.)
NOTE: If you plan on investigating the fault, history
and operation data is required. Also record the date, time, and any information about the machine opera­tion prior to the fault
Function Code
FO
Fi
F2 F3
F4
FS
F8 F7
Indication Data (by digit)
4th
1 -
7
in
order
of occurence.
3rd 2nd
0 0
0
0 H 0 H 0
0 L 2
E r E r r
6 6 0. 0
1
1-4 in
order
0
of indication
1st
c
c 2
c 0
1
3
U
L u
1
2
L
r
1
0 d
0.
0. F
0 0
0
E
::
L
u
L
u u
Name of Fault
Overcurrent At Acceleration Overcurrent At Deceleration Overcurrent At Fixed Speed Overvoltage Undervoltage lnverter Oveheat External Alarm lnverter Overload Motor Overload CPU Error
Memorv Error
Output
Frequency Setting Frequency Output Current
Normal Operation Reverse Operation Current Restriction Voltage Restriction Undervoltage Restriction
1st Prev. Fault (Pres. Fault - 1) 2nd Prev. Fault (Pres. Fault - 2) 3rd Prev. Fault (Pres. Fault - 3)
Figure
54. FAULT INDICATIONS
5-7
5. History and Operation Data Not Rewired:
The confirmation of the fault has been completed at this point. If the operation data and fault history are not required, press RESET key after fault cause has been corrected and do not perform the
remaining steps of this procedure.
--
This will clear the fault and the control will auto-
matically return fault and be ready for operation. Please note that thesecond, third, etc. faults have stored in the memory. It is recommended that they be recorded for possible future reference.
Hlstory and Operation Data Rewired:
Press
SHIFT
for the first digit of the Function Code Display is lit
to retrieve operation data at the time of the fault.
6.
Press the information in the Data Display: (See Figure 5-4.)
a.
quency will be displayed.
b.
C.
d.
tion State will be displayed.
e.
Selection LED under the firstdigit of the Func­tion Display and advance control the the Op-
State Number (1) will be shown in the fourth State will be shown in the third, second, and
first digits of the Data Display.)
f.
the Data Display.
State will be displayed as in
h.
State will be displayed as in
UP ARROW
Press once to select Fi
Press a second time to select F2 and the Sat
Frequency will be displayed.
Press a third time to select F3 and the Output
Current will be displayed.
Press a fourth time to select F4 and the Opera-
Press SHIFT key once to turn off Function
eration State Retrieval Mode. (The Operation
digit of the Data Display and the Operation
Press the
Operation State Number (2) in the fourth digit
of the Data Display and the Operation State will
be shown in the third, second, and first digits of
Press the
Operation State Number (3) and the Operation
Press the UP ARROW key again to display the
Operaton State Number (4) and the Operation
tothe
mode it was in prior to the
not
been
key until the Function Selection LED
key to display the following
and the Output Fre-
UP ARROW
UP ARROW
key once to display the
key again to display the
(9
above.
(9
above.
7.8.Fault Hktory Data Not Required: If the fault history is not required, press
after fault cause has been corrected and do not perform the remaining steps of this procedure.
--
This will clear the fault and the control will auto­matically return to the mode it was in prior to the fault and be ready for operation.
Fault History Data Required:
Press
SHIFT
for the first digit of the Function Code Dispfay is lit to retrieve fault history data.
Press the UP information in the Data Display:
a.
Press once to select F5 and the last fault (first of a multiple fault occurence) to occur will be displayed.
b.
Press a second time to select F6 and the fault one time previous to the last fault will be dis­played.
C.
Press a third time to select F7 and the fault two times previous
NOTE: When RESETkeyispfessed, a ‘moving
the fault history will occur. The inverter can not be reset when a
9.
Press
RESET
rected. Data retrieval for fault monitoring is com­plete at this point.
--
This will clear the fault and the control will auto­matically return to the mode it was in prior to the fault and be ready for operation.
OBTAINING FAULT HISTORY WHEN FAULT IS NOT PRESENT
1.
Press
SHIFT
under the second digit of the Function Code dis­play lights.
-- This selects the second digit.
2.
Press the UP ARROW key or DOWN ARROW key
to set
‘F’.
3.
Press the Function Code Display.
--
The Function Selection LED under the first digit will light.
key until the Function Selection LED
ARROW
RUN
key after fault cause has been cor-
key until the Function Selection LED
SHIFT
key to display the following
tothe
last fault will be displayed.
command is present.
key to select the first digit of the
RESET
up”
key
of
NOTE:If you plan on investigating the fault, history
and operation data is required. Also record the date, time, and any information about the machine opefa-
tion prior to the fault.
5-8
NOTE:
FO
inverter is not presently faulted.
There are no fault inputs for Function Codes
to F4 and the Data Display will show I- - -* when the
AF-300C inverters GEK-85718
4.5.Press the UP or DOWN ARROW keys to set the desired number (F5, F6, F7). (See Figure
-- Each fault history will be shown on the Data
Display when selected.
Press RESET key to return to Operation Monitor-
ing mode (no ‘move up’ of fault history will occur).
5-4.)
DATA PROTECTION
Function Code data can be protected against acci­dental changes by the setting of Function Code 99.
When data is ‘Protected’, it cannot be changed until
Function Code 99 is changed to’Unprotected’. There are two different methods of setting the data protec-
tion. Perform either of the following procedures that
best suits your particular application. OPERATION PROCEDURE
To Set Protection:
Press FAST key first and then SET key (while FAST key is still depressed) to set Function Code
99 to ‘Protected’.
-- Function Code Display will display
neither of the Function Selection LEDs lit.
-
Data Display will show (0) in the first digit posi-
tion to indicate ‘Protected*. (This will be dis-
played for approximately 5 seconds after keys
are released.)
-- Data Display will then return to its previous
mode.
-- All Function Code data currently set will be pro­tected.
To
Release
Press FAST key first and then RESET key (while FAST key is still depressed) to set Function Code 99 to “Unprotected’.
-- Function Code Display will display ‘99” with
-
-
Data Display will then return to its previous
-
All Function Code data currently set will no
Protection:
neither of the Function Selection LEDs lit.
Data Display will show (-) in the first digit posi- tion to indicate ‘Unprotected”. played for approximately 5 seconds after keys are released.)
mode.
longer be protected.
#l
“99”
with
(This will be dis-
OPERATION PROCEDURE
1.
Press SHIFT key until Function Selection Led under the second digit of Function Code Display is lit.
-- This selects the second digit.
2.
Press UP or DOWN ARROW keys until played in the second digit position.
-
-
3.
Press SHIFT key to advance to DataSetting Mode.
-
4.
Press UP ARROW key to set to “Protected” status.
-- (0) will be displayed in the first digit position of
Press DOWN ARROW key to set to “Unprotected status.
-- (-) will be displayed in the first digit position of
5.
Press SET key to store selection into memory.
6.
Press RESET key to return to Operation Monitor­ing Mode.
TRIAL KEYPAD OPERATION (Optional)
Before trial operaton of the inverter, ensure that all inspections outlined in the “Before Applying AC Power Inspections’ paragraph have been performed.
WARNING - MECHANICAL MOTION HAZARD:
wlth the “Local/Remote” switch In tion, presslng the FWD or REV key motor to rotate. Any RUN permissives that may be wired to the FWD or REV termlnals are Ignored.
If a test run Is desired, run the inverter at a low fre­quency of around 5 Hertz. Conduct thetrial operation per the following procedure:
1. Disconnect all couplings and belts that connect the electric motors and machinery so as to allow
independent operation of the electric motors.
--
#2
‘9’
is dis-
First digit of Function Code Display will auto-
matically be set to
Current status of “Protected’ (0) or ‘Unpro-
tected” (-) will be be displayed in the first digit position of the Data Display.
Both Function Selection LEDs will go out.
Data Display.
Y9*
also.
or
Data Display.
When
If the electric motors are connected directly to the machinery, verify that any mechanical motion will not pose a safety hazard.
running
from the Keypad Panel
the”Local” posl-
will
cause the
5-9
2. Set all operating switches to OFF and set Remote’ switch to
3. Apply AC power.
--
Control circuits and sequence circuits will be activated and charge LED will light.
--
Data Display portion of blink
‘LoAd”
internal data.
_-
‘LoAd” ceases to blink while CPU is checking
that Function Code set data matches the speci­fication.
--
Touchpad Panel will display last operation mode
of invetter prior to removal of AC power.
4. Use “Increase Speed” or ‘Decrease Speed’ keys to set desired reequency. (A low frequency of
about 5 Hz is recommended for the first run.)
5. Give a Forward or Reverse command and check for the following: (See Figure 5-5.)
--
Correct direction of rotation.
__
Smooth rotation of motor.
-_
Any abnormal vibration or noise in the motor.
--
Smooth speed increase and speed reduction.
“LocaIn
position.
Touchpad
while the CPU is checking the
‘Local/
Panel will
6. Check for any abnormal heating, fumes, etc. while motor is rotating.
7. Perform the following using the Keypad Panel: __
-
__
8. Reconnect any equipment disconnected in step of this procedure.
9. Perform steps 5 thru 7 with the load connected. NOTE: If any Function Code settings need to be
changed, refer to ‘Setting Function Codes’ paragraph
in this Section.
Raise the reference frequency gradually and
verify that it reaches top frequency for the
particular application (typically 60 Hz, default setting from factory).
Check AC motor current (should be approxi-
mately 3040% of rated current with no load). Lower the reference frequency and stop the
motor.
1
OUTPUT
p-p-p-j
Figure 5-5. ELECTRIC MOTOR ROTATION
5-10
AF-300C
Inverters
GEK-85718
CONTROL CIRCUIT CONNECTION AND OPERATION
Basic connectlons
from the Keypad Panel are shown in Figure 5-6 (this is a factory installed jumper).
A wiring example of commonly used signals
are optional for either Keypad Panel Operation or External Operation (through control circuit terminals) is shown in Figure 5-7.
Connection description is as follows:
- 3OA,
308, 30C - Fault Relay Output used for
alarm circuits, etc.
- FMI,
FM2 - Used for external analog meter
when frequency indication is needed.
--
THR - Connected to
Connects to a normally closed contact. When inverter STOP is desired through external alarm, open this contact. The inverter will trip on
‘OH2’ and the motor will coast stop.
--
RST
-Connects to a normally open momentary
contact for resetting a fault externally.
that are required for operation
that
CM
terminal at factory.
-- BX - Connects to a normally open contact. When motor coast stop is desired during nor­mal operation, close this contact
and remove
the RUN command (FWD or REV).
Termlnal Connectlons required for operatlon from Keypad Panel
are shown in Figure 5-8.
Operation is as follows:
--
Rotation Direction - Press for forward rotation or
FWD on the Keypad
REV
on the Keypad for
reverse rotation.
-- Frequency Setting - The frequency reference can come into the inverter in one of the follow­ing ways when the
in the
‘LOCAL’
LOCAL/REMOTE
position.:
switch is
1. Set the motor speed by pressing the IN­CREASE SPEED or DECREASE SPEED kevs on the Keypad Panel to increase or de­crease the inverter output frequency.
2. Multi-Step Speed Settings can be selected by terminals
Xi,
X2, and X3. (Program­mable preset frequencies in the Function Codes can be selected.)
-- See Figure 5-9 for RUN Operation example.
3ORj31BjIICIRUN]
z
F
RXl/RX2lCflElFRRI
l
l CAUTION: lf it is desired to use thermal interlocks, remove the
jumper from between terminals THR and CM, and connect nor-
mally closed thermal interlock contacts in series between THR and CM.
OL
lFtIl]Ftl2 Vl
Lv
1~13~111 I12 I13 IFUU~REV~
1 Cl 1 Xl 1
X2]
X3 1 en
BX I en
Figure 5-6. FACTORY CONNECTIONS
: If it is desired to use thermal interlocks, remove the
between terminals THR and CM, and connect nor-
thermal interlock contacts in series between THR
INlERWL CIFXUIT
IRTlIRt21AUT
ITHR~RST~ pu I IL
r
r
Figure
5-7. EXAMPLE OF COMMONLY USED SIGNALS
5-l 1
AF-300C lnverters
GEK-85718
F
Forward
AXljRX2ICtlEIFAR[
3ml3~~13mcl~u~I
*l
CAUTION: If it is desired to use thermal interlocks, remove the
jumper from between terminals THR and CM, and connect nor-
mally closed thermal interlock contacts in series between and CM.
OL
IFllllFH2l VI 1
LV
IFDT~ 11 I12 I13 IFUD~REV~ Rx I
Cl 1 Xl 1 X2 1 X3 1 Cn
THR
Figure 5-8. KEYPAD PANEL OPERATION CONNECTIONS
IRTlIRT2(RUt
cn
ITHR~RST] PU 1
I I
IL
Reverse
*FWD-CM and RRI-CM terminals arre both ignored.
WARNING - MECHANICAL MOTION HAZARD:
When running from the Keypad Panel with the “Local/Remote’ switch in the ‘Local” position,
pressing the FWD or REV key will cause the motor to rotate. Any RUN permissives that may be wired
to the FWD or REV terminals are ignored.
Figure 5-9. KEYPAD PANEL ‘RUN’ OPERATION EXAMPLE
5-12
AF300C
lnverfers
GEK-85718
Terminal Connections
required
for Remote
Operation are shown in Figure 5-l 0. Connection description/operation is as follows:
-- Rotation Direction -Make contact between FWD-CM for forward rotation or between REV-
CM for reverse rotation.
-- Frequency Setting - The frequency reference
can come into the inverter in one of the follow- ing ways when the LOCAL/REMOTE switch is in the ‘REMOTE’ position:
1. Speed Pot - 1 K ohm,
connected to terminals
2. Voltage - 0 to
Vl
and 11 (11 is common).
+I0
3. Current - 4 to terminals Cl and 11 (11 is common).
l/2
watt potentiometer
11,12,
and 13.
VDC signal to terminals
2OmA
DC current signal to
(Ter-
minal AUT must be connected to CM.)
4.
Speed Pot Plus Voltage - 1 K ohm,
l/2
watt potentiometer connected to terminals 11, 12, and 13 is added to 0 to +I 0 VDC signal connected to terminals Vl and 11.
5. Voltage Plus Voltage - 0 to +I 0 VDC signal connected to terminals Vl and 11 is added to 0 to + 10 VDC signal connected to terminals 12 and 11 (11 is common).
6. Multi-Step Frequency Settings - Selected by terminals Xi, X2, and X3.
(Program-
mable preset frequencies in the Function Codes can be selected.)
7. UP/DOWN Control (Simulated Motorized Potentiometer) - Selected by terminals Xl and X2.
-- See Figure 5-l 1 for Remote RUN Operation ex­e--,-
al I ipia.
‘1
CAUTION: If it is desired to use thermal interlocks, removethe
jumper from between terminals THR and CM, and connect nor-
mally closed thermal interlock contacts in series between THR
and CM.
Figure 5-10. REMOTE OPERATION CONNECTIONS
5-l 3
Forward
Reverse
,
I I
I
ON
: I
I
I
I
ON
ON ON
Figure
5-I 1. REMOTE OPERATION EXAMPLE
*l
CAUTION: lf it is desired to use thermal interlocks, remove the jumper from between terminals THA and CM, and connect nor­mally closed thermal interlock contacts in series between THR and CM.
Flgure 5-12. MULTI-STEP FREQUENCY OPERATION CONNECTIONS
5-14
ACTUAL OPERATION
Terminal connections and Function Code selections for Multi-Step Frequency Operation and MultiStep Acceleration and Deceleration Operation are as described in the following subparagraphs.
MultI-Step Acceleration and Deceleration Opera-
tion terminal connections (RTI, shown in Figure 5-14. Fourdifferent acceleration and deceleration times can be externally selected.
1. The multi-step acceleration and deceleration
Multi-Step Frequency Operation terminal connec­tions (Xl, X2, X3 terminals) that are required are shown in Figure 5-12. Multi-step Frequency Opera­tion can be used to select one of eight different speed settings (one manual setting and seven preset set­tings).
1. The multi-step frequency Function Code
set-
tings are:
[23]
1241
[25] [26]
[271
PI
[29]
for multi-step frequency 1. for multi-step frequency 2. for multi-step frequency 3. for multi-step frequency 4. for multi-step frequency 5. for multi-step frequency 6. for multi-step frequency 7.
3. See Figure 5-15 for RUN Operation example.
2. See Figure 5-13 for RUN Operation example.
RT2,
terminals) are
Function Code settings are:
[16]
for acceleration time 1.
[2A] for acceleration time 2. [2C]
for acceleration time 3.
[2E] for acceleration time 4. [17] [2b] [2d] [2F]
for deceleration time
I.
for deceleration time 2. for deceleration time 3. for deceleration time 4.
Forward
Xl
-CM
x2
-CM
Fw!?CM
~%.l
_ ri-
i .
i ;
-. .
SPEED 1 (FUNCTION CODE
SPEED 2 (FUNCTION CODE 241
r
ON
SPEED r-SPEED 3 -
:
ON
*
ob
CFUtKTION SFEED 4 (FUNCTION 5
! .
I
I
i
I
23)
CODE
lFUNCT.I 251
-
MRNUFL
-SPEED 6 (FUNCTION CODE
M
I
ON
CODE
-~-ON
263
CODE
SPEED
SPEED 7 (FUNCTION
I *
ON
27)
ON
28)
CODE 29)
Figure 5-13. MULTI-STEP FREQUENCY ‘RUN’ OPERATION EXAMPLE
5-15
*l CAUTION: lf
jumper from between terminals THR and CM, and connect nor-
mally closed thermal interlock contacts in series between THR
and CM.
it is desired to use thermal interlocks, remove the
Figure 5-14.
Forward
FWII
-CM
MULTI-STEP ACCELERATION AND DECELERATION OPERATION CONNECTIONS
CN
,
I I
;
ON
I
:
ON
*
:
: !
: ’ :
I I
,
4
ON
1
I
I I
I I
I
ON
Figure 5-15.
MULTI-STEP ACCELERATION AND DECELERATION “RUN’ OPERATION EXAMPLE
5-I
6
TABLE 5: FUNCTION CODE DATA
Mode
OPERATION MONITOR
BASIC
PARAMETER
Funct. Code Name
00
01
02(“)
03 04 Output Voltage
0.5(“)
06 07 Output Signal Status
08 Motoring Torque Limit 09 Braking Torque Limit OA
10 11
12 13 14 15
16(‘3) 17r.3, lp)
19
1A
lb
Output Frequency Reference Frequency
Synchronous Speed
Output Current
Machine Speed
Input Signal Status
Calculated Torque
Maximum Frequency Base Frequency Rated Output Voltage Frequency Bias High Limiter Low Limiter
Acceleration Time 1
Deceleration Time 1
Frequency Gain Torque Boost Auto Energy Saving Op.
Elec. Thermal Overload
Setting and Indication Data Factory
Range
Indicates During Operation Hz
u II II ,I II II II II II II
II II II I, II II II
I, ,I II II
II I, II II II
50.0 - 400.0 (*5) 50 - 400 (*5) 320 - 460 O-400 O-400 O-400
0.2 3600
0.2 3600 O-200 O-20 Yes - (0), No - (-) 0 (not used) 50 -105
II II
II ”
&&t
HZ RPM
Amps 1 Amp ---­Volts 2v
RPM
____
-*--
----
----
____
HZ HZ
V
HZ HZ
HZ
set set
%
Increment Setting
0.1 Hz ----
0.1 1 RPM ----
1 RPM ----
mm-* ____
11.m
____
----
0.1 Hz 1 Hz
1v
1 Hz 1 Hz 1 Hz
0.1
0.1
0.1% 1
mm-
1%
Hz
set
set
----
____
____
-___ mamm
----
-w-s
60.0 Hz 60 Hz 460 V
OHz
60 Hz 1 Hz
2O.Osec
20.0
105.0 %
3
No (-1
105%
s
set
AUXILIARY
PARAMETER
20 21 22
23p2) 24e’ 25(‘2)
26r2) 27r2)
28r2) 29m
2A
2b 2c 2d 2E
2F 30
DC Brake Starting Freq.
DC Brake Voltage DC Braking Time Multi-Step Freq. Setting 1 Multi-Step Freq. Setting 2
Multi-Step Freq. Setting 3 Multi-Step Freq. Setting 4 Multi-Step Freq. Setting 5
Multi-Step Freq. Setting 6 Multi-Step Freq. Setting 7 Acceleration Time 2 Deceleration Time 2 Acceleration Time 3 Deceleration Time 3 Acceleration Time 4 Deceleration Time 4 Accel / Decel Pattern
0.0, 0.5 - 60.0
0.0 - 10.0
0.0 - 10.0
0.5 - 400.0
0.5 - 400.0
0.5 - 400.0
0.5 - 400.0
0.5 - 400.0
0.5 - 400.0
0.5 - 400.0
0.2 - 3600
0.2 - 3600
0.2 - 3600
0.2 - 3600
0.2 - 3600
0.2 - 3600 0,
1,2.
5-17
Hz %
Hz Hz Hz Hz Hz
Hz Hz
set
set set
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
___
Hz
% set
Hz Hz Hz Hz Hz Hz Hz
set set set set set set
0.0 Hz
10.0%
0.5
set
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz 100
set
100
set
100
set
100
set
100
set
100
set
0
TABLE 5: FUNCTION CODE DATA (continued)
Mode Funct.
Code
31 32
33(‘2)
AUXILIARY PARAMETER (continued)
34(-j 35(“)
36(‘2)
37 38 39 3A
38
3c
3d(*2) 3~(*21
40 41
42
43(‘4)
44 45 46 47
Name
Tone Control Selection Overload Early Warning
Motoring Torque Limit Braking Torque Limit Freq. Detection Threshold
Freq. At Reference
Start Frequency Start Freq. Holding Time
Jump Frequency 1 Jump Frequency 2 Jump Frequency 3 Jump Frequency Range Number of Motor Poles Coefficient Mach Spd. Pulse Freq. Meter Coeff ic.
FWD/REV Command Hold
(3 wire control) Up / Down Control
Restart After Power Failure Under Vottage Alarm Open Coil. Output Select Slip Compensation Control
Voltage Signal Polarity Op.
Yes (0), No
Setting and Indication Data
Ranqe
1) 2,3,4. 50-105 0,20 -
180
0,20-180
l-400
0.5 - 5.0
0.5 - 5.0
0.0 - 10.0
0.0,0.5 -
0.0,0.5 - 400.0
0.0, 0.5 - 400.0
0.0 - 5.0 2,
0.1 - 10.0 6-100 Yes (0), No
Yes (0), No Yes (0), No Yes (0), No
0,
0.0 - 2.5
4,6,
8, 10, 12
1,2.
400.0
(-)
(-) (-) (-)
(-)
yniJ
___
% %
%
HZ HZ HZ
set
HZ HZ HZ HZ
___ _I
___ H.?
___
Increment
--a
1% 1% 1% 1 Hz
0.1 Hz
0.1 Hz
0.1
set
0.1
Hz
0.1 Hz
0.1 Hz
0.1 Hz 2
0.1 1
--w
Factory
Settinq
1
105% 150%
100%
30 Hz
2.5
Hz
0.5
Hz
0.0
set
0.0 Hz
0.0 Hz
0.0 Hz
2.0 Hz 4
1.0 30 Yes (0)
No (-I No C-1
Yes (0) 0
0.0 Hz
No f-1
ADJUSTMENT
PARAMETER
PROTECTION
*I
Because the data display is four digits, if the indication exceeds four digits it will be shown as automatically. (Example: 12000 RPM
*2
These parameter values can be changed during inverter operation; other parameters can only be changed when the
inverter is stopped.
*3 If the setting of Acceleration/Deceleration time exceeds 100 seconds, the minimum setting unit resolution will become
1 second.
*4
Momentary power failures only (duration may vary with horsepower and load).
*5
Consult distributor for operation above 120 Hz.
50 Freq. Meter Calibration 70.0 - 105.0 % 0.1% 100.0%
99
Set Data Protection Yes (0), No (-)
would
be displayed as 1200 RPM.)
5-18
___
__-
1110
of the actual
No t-1
AF-300C lnverfefs
TABLE 5: FUNCTION CODE DATA (continued)
GEK-85718
Mode
FAILURE INDICATION
Funct. Name
Code
FO
Fl
F2 F3 F4
F5 F6 F7
Fautt Message
Output Frequency at Fault Setting Frequency at Fault Output Current at Fault Operating Mode at Fault Fault Memory 1 Fault Memory 2 Fault Memory 3
Settina and Indication Data
Indication Failure Condit. Hz
NOTES:
yniJ
HZ
A
Increment
0.1 Hz
0.1 Hz
1A
Factorv
Setting
---
5-l g
NOTES:
AMOOC
hefters
GEK-85716
5-20
6.
FUNCTION CODE DESCRIPTIONS
TABLE 6: FUNCTION CODE DESCRIPTIONS
OPERATION MONITOR FUNCTIONS
Functions 00 n OA
The operation monitor will indicate any of the data selections shown in the chart on the right.
-
For monitoring functions 02 (synchronous speed)
and 05 (load turning speed), it is necessary to set auxiliary parameters 3d and 3E.
NOTE:
the indication exceeds four digits it as
12000 RPM would be displayed as 1200 RPM.)
--The input signal status and output signal status can be monitored via the keypad by going to Function Code 06 or 07, then using the UP/ DOWN ARROW keys to change the fourth digit.
The chart on the right shows what signals are shown in the first, second, and third digits.A
indicates that the signal is present; a
the signal is not present.
Because the data display is four digits, if
will
be shown
7110
of the actual automatically. (Example:
“-’
means
“0’
Function
00 01 02 03 04 05 05 07
05
09 OA
F Unction
Uo?
AF-300C Invertem GEK-85716
Description
Output Frequency Reference Frequency
Synchronous Speed Output Current Output Voltage Machine Speed Input Signal Status Output Signal Status Motoring Torque Lim. Braking Torque Limit Calculated Torque
Ind. Unit
HZ HZ RPM A V RPM
BASIC PARAMETER
SElTlNG
Functions 10 - 19
Voltage/Frequency Setting Characteristics
Function 10 Maximum Frequency
(fmax) Function 11 Base Frequency (fbase)
Function 12 Rated Output Voltage
(Vrated)
These parameters will be set with fbase, Vrated, and fmax adjusted to the rating of the electric motor. Consult distributor for operation above 120 HZ.
fbase:
Vrated: 320
fmax:
Function 13 Frequency Bias When the frequency setting signal is at
50 to 400 Hz
to 460 VAC
50-400
Hz/freq.
set signal 100% time
(fbias)
O%,
bias can be added so that the inverter will run at a specified frequency even with zero reference ap­plied. (Used to add an offset to the low end of the reference signal.}
fbias: 0
to
fmax
0%
Frsauency smng slwar
MO%
6-l
AF-300C lnverters
GEK-85718
Adjustment of Upper/Lower Limits
Function Function
14 High Output Freq. Limiter 15 Low Output Freq. Limiter
(IHL)
(fLL)
The upper and lower limiters can be set so that the
inverter output frequency will stay within these limits.
This
will prevent motor overspeed and under-
speed.
NOTE:
If the High Limit is set lower than the Low Limit, the Low Limit will be ignored and an error in­dication (Errl) will be displayed.
fHL: 0 to fmax fLL: 0 to fmax
outoul
frwurney
:::, pq
0%
Fm~uemcy srt!lng ugnil
look
AccjDec time setting
Function 16 Acceleration Time Function 17
Deceleration Time
(lVo.
I)
(t,,=,) (t,,,)
The acceleration and deceleration times define the
amount of time it takes between 0 Hz and fmax.
t
ACC, : 0.2
t
DEC, :0.2
r
Function
to 3600 seconds to 3600 seconds
18 Frequency Gain (Gain)
I
The frequency gain adjustment can be used to scale the analog voltage reference at the top end.
Gain: 0 to 200%
When the freauencv setting
sicrnal
is applied with a
current input, this function cannot be used.
1
Function 19 Torque Boost
I
21 patterns can be selected (torq. boost = 0 to 20).
-- Patterns (0) and (1) are used for low torque loads
(available for fans and blowers, thus improving characteristics such as vibration, noise, and effi­ciency.
-- Pattern (2) is characteristic of V proportional to
the square of f up to fSase/3.
-- Pattern (3) is characteristic of constant V/f up to
ff3ase.
-- Patterns (4) through (20) are to increase V/f in a
low frequency range between 0 to
fSase/3
to make up the torque at low speed operation and to give torque boost characteristics.
Torque Boost: 0 to 20
Settmg swul
0u10ut
lfeauenw
fwx
outw wttagr
0
I
1
Time
ACC. mlt
0
Output
Ihe. tlma
E
frraurncy
6-2
Function 1 A Automatic Energy Saving Oper.
When automatic energy saving operation is se­lected, voltage is reduced as shown. The voltage is decreased as the load current decreases. 0
= Active
-
= Inactive
Outout
voltage
AF-300C
hvertefs GEK-85716
Function 1 bElectronic Thermal Overload
I Electronic thermal setting should be made with the following equation: Electronic Thermal Overload =
Rated electric motor current x 100%
Rated inverter current
--When using a 4 pole, 3 phase motor, the motor
can be protected from overload without an exter­nal thermal relay.
-- The electronic thermal calculation compensates
for a decrease in motor cooling at low speed .
--When using one inverter with more than one
motor, an external thermal overload relay should be used for each motor.
-- lfthe ElectronicThermal Function is not used, set
at 0%.
CAUTION:
lav
meets the reauirements of
The electronic thermal overload
4-Dole
standard
re-
motors onlv. When anv of the followina conditions exist, use conventional overload relavs instead of
the electronic overload built into the inverter.
-- Motors other than 4-oole tvpe.
-
Special motors (anv non-standard motor).
-
For a orouc oneration where two or more motors
are run usinn a sinole inverter.
-- Aoplication has frequent startinn/stocoinq,
-- Operation is at 10 Hz or less.
* 105%
30%
Threshold Where Timing Begins Based
On Output Frequency And Current,
And Electronic Thermal Overload Setting
Time
Before
Trip
(Min.)
6-3
Output Current
(%)
Inverse Time Characteristic with
Electronic Thermal Overload = 105%
AUXILIARY FUNCTION CODES
Functions 20 - 47
DC Brake
Function Function 21 Function
Brake Start Freq.: 0.0, 0.5 to 60 hz. Brake Voltage: Brake Time: Brake Duty Cycle:
The DC brake is applied when aSTOP command is
given and the inverter output frequency is at or below the DC brake start frequency.
-- If the motor/load inertia is so large that the rota­tion is not stopped aftertheset DC brake time (10 seconds maximum), the motor/load will coast
until stopped.
-- When DC brake is not used, set the Brake Start
Frequency to
20 DC Brake Start Frequency (f,-,J
DC Brake Voltage (VocJ
22 DC Brake Time
(t&
otolo%
0 to IO seconds 5% maximum
“0’.
Ouwut houency
(turnmg screw)
:::lzYL
Mu/f;-Step Frequency Setting Selections 1 - 7
Function Function Function Function Function Function Function
23 Multi-Step frequency1(MSSl) 24 Multi-Step
frequency 25 Multi-Step frequency 26 Multi-Step 27 Multi-Step
frequency
frequency 26 Multi-Step frequency 29 Multi-Step frequency
2 (MSS2) 3 (MSS3) 4 (MSS4) 5 (MSS5) 6 (MSSG) 7 (MSS7)
External contact signals allow a selection of seven speeds.
Each step speed can be set between 0.5 and 400 HZ. The rate of change of the output frequency be-
tween each step is adjustable by the accel/decel time setting. NOTE: Multi-step frequency opefaticm overrides
other frequency reference signals.
Relationship Between Terminals and
I
Fun. Code
x2-w
X3-M
Multi-Step Frequencies 1 to 7
Depel LoC/R
off
off Cfl
liiii
Cff
On On Off Off On Or Off Off On On On Or
Speed
4
iii+,
6-4
AcclDec Time Settings Numbers 2 - 4.
Function Function Function 2E Function 2b Function 2d Function 2F
2A Acceleration Time
2C Acceleration Time
Acceleration Time Deceleration Time Deceleration Time Deceleration Time
(fAcc2) (fAcc3) (tAccd)
(t,,,) (t,& (t,,&
Function Code External Contact
Signal
IT1
-CM
FtT2-CM
#1
Acc/Dec Acc/Dec Acc/Dec Acc/Dec
otl cm
#2 #3 #4
On
off
9ff On
On On
-- The time between 0 to fmax and from fmax to 0 can be set anywhere between 0.2 to 3600 sec-
onds.
-- Accel and Decel time can be selected from four
different acceleration and deceleration groups
using the RTI and
RT2
terminals.
-- Even during acceleration and deceleration, Ac-
ccl /Decel time can be changed using the exter-
nal contact signals
1
Function 30
Accel/Decel
FITI
and RT2.
Pattern
ACC/DEC Pattern Setting
Linear ACC/DEC Curve ACC/DEC Curve ACC/DEC
NOTE:
Linear pattern will override Pattern B if
‘A’ ‘B’
0 1 2
fmax is greater than 60 Hz.
NOTE: This function cannot be used in the event
Multi-Step Frequency selection is made.
Settmg swat
Acceleratron
I
AvaAaBle
Curve A -
for
telectmg
‘S’
cUN’3
I
..,
time
two
,,
,
~,
I
Oecelerat~on time
kmds of patlerns:
Cunre
B - For Use On
Fans And Blowers
ltvu
A
Time
Trma
an0 B
:
lime
Function 31 Tone Control Selection
I
There are four different tone control selections that set the chopping frequency of the inverter output transistors. This can be used to reduce audible resonant frequencies from the motor.
IFunction 32 Overload Early Warning Signal
1
An early warning signal is given if the inverter output current exceeds the overload alarm level for a certain period of time.
This is an open collector output. If the optional relay unit is used, this signal can be used as a dry contact output.
If
‘0’ is
set, this function is inactive.
Operating Time
6-S
AF-300C hverters GEK-85718
Torque Limiter (Motoring and Braking)
Function Function 34
33 Motoring Torque Limit (T,J
Braking Torque Limit (T,J
-- Torque is calculated from the output voltage and current of the inverter.
-- This function can improve impact load restora­tion characteristics during ACC/DEC and con­stant
speed
operations and improve instantane-
ous restart ability.
Reoeneration Avoidance Control
Set braking torque limit to
O%,
and power regenera­tion to the inverter will be limited to obtain decelera­tion characteristics close to coasting.
Automatic ACC/DEC Even if the acceleration and deceleration time is re­duced to less than the time fixed by load inertia, automatic acceleration and deceleration can be maintained by maintaining the torque limit level.
NOTE:
optional brake unit and brake resistor will
To obtain more torque on deceleration,
be
re-
quired.
Torque Limit Setting Range (Motoring and Braking)
-- Set to
“0”
to render inactive.
-- Adjustable from 20 to 180%.
(Motoring)
Slip = 0
Torque
1
­W
df
(Braking)
-
Slip
NOTE:
The
data setting for
Function Code 34 is
100% (assuming that a braking resistor is con­nected). If no braking resistor is connected, setting should be changed to 15% or less. If left at
lOO%,
an overvoltage trip will occur during deceleration if the decel time setting is too shortforthe motor/load inertia.
Function
This signal
35 Frequency Detection Threshold
(FDT)
is active (On) when the outputfre-
quency exceeds the detection level.
This is an open collector output. If the optional relay unit is used, this signal can be
used as a dry contact output.
Outout
signal
(f-01-WE)
OUIOUI treauency
I
0
Time
6-6
1
Function
36 Frequency At Reference (FAR)
I
This signal is active (On) when the output fre-
quency reaches the reference frequency.
This is an open collector output.
If the optional relay unit is used, this signal can be used as a contact output. FAR: 0.5 to 5.0 Hertz
Starting Actions
Function 37 Function
-
Starting frequency set range is 0.5 to 5 Hz.
Starting Frequency
36 Start Frequency Hold Time
(F,)
v,,,,)
-- Starting frequency holding time setting range is
0.0 to 10 sec.
A starting frequency and holding time can be set that is suitable for the starting torque characteris- tics of the load.
(Setting is ignored during decelera-
tion and reverse operation.)
Frequency Jump
Outpul
freouency
OS- snz
0
!
Time
These functions are used to avoid the natural mechanical vibration of the load. Three jump frequencies can be set. Jumpfrequen-
ties
are not active during acceleration and decel-
eration or if the multi-step speed settings are used.
The jump frequency range is adjustable between 0
to 5 Hz. (When the jump frequency is not used, set it to ‘0.0’.
Jump 1, Jump 2, &Jump 3:
0.0,0.5 to 400 Hz
Number of Electric Motor Poles Speed Conversion Coefficient.
Function 3d Function 3E
Number of Motor Poles
Machine Speed Conversion
Coefficient.
These Function Codes are set to monitor the syn­chronous speed of the motor and the machine speed.
fUAx
Oulout
trBauulcv
/
Function
3d
3E
Jum wdlh sat&o
Settins Ranae
2, 4, 6, 8, IO,
0.1
:&5.0H~
100%
- 10.0
c
.tumo twawncy
WlOJl
12
Machine Speed = (Motor Synchronous Speed) X (Machine Speed Conversion Coefficient).
6-7
Frequency Monitor
Function Function 50
40 Pulse Freq. Meter Coefficient
Analog Freq. Meter Calibration
The inverter output frequency can be monitored from terminals FM1 (+) and FM2
SW2on the Main Control Card in the
(-).
Set Jumper
I-2
position for an analog meter or in the 2-3 position for a pulse type meter.
Function 41
FWDIREV Command Hold (3-wire)
This function enables control by a one-shot (50ms minimum) RUN/STOP command (FWD and REV command), External self-sealing circuits can be omitted. When this function is selected, multi-step speed settings from 1 to 3 can be used, but those from 4 to 7 cannot.
NOTE:
After
commend
hold, no other commands
will be received uniess a STOP command is given.
Active: Inactive:
Function
‘0’
(3-wire control, momentary contacts)
1-11
(2-wire control, maintained contacts)
42 Up-Down Control Selection
Pulse Period =
-----------------­o Analog output
Output
voltage
‘b-l
l/nf
1ov
ov
(sec.)
0
output
frequency
n coefficient 6 to 100 f =
lnvetter Output
100%
lmaxlmum Irequency)
Pulse Signal Width
be 60 msec. or longer
Freq.
Calibration Range:
70x-
105%
17v- 1o.m
m&it
The frequency can be increased and decreased using terminals Xl -CM and X2-CM. This function simulates a motor driven potentiometer.
In addition, if power is shut down, set value is stored. When operation is started again, inverter will come up to the stored frequency.
NOTE:
sealing selection, and
The functions of multi-step
up-down
frequency,
control use the
self-
same terminals. Thus, there are four possible combinations of operation. A// three functionsca nor be used simulraneouslv.
Act.
IAct. 1
Up-down control
1
Comm-hold sel.
NOTES: When this control function is selected, multistep
speed setting 4 (Function Code 26) can be used, but the other six settings cannot.
Multi-Step Speed Setting, and Up-Down Control cannot be usedsimultaneously because the same terminals are used for these func­tions.
If the Up-Down function is selected, external
quency
setting signals (voltage and
gored. If Up-Down buttons are pressed at
down will take precedence.
FWDIRN
Command Hold,
current)
the
same time,
fre-
are
in-
6-8
Function 43
I
This function specifies whether the inverter is to be
restarted automatically when power is recovered after a momentary power failure.
If automatic restart is selected, the inverter is re­started after power recovery under the following conditions:
1
Function44IUndervoltage Alarm
When
undervoltage level, inverter will cease to give an
output.
to indicate alarm and transmit an alarm signal
indicate that it has reached the undervoltage level without self-holding (can select either one).
main circuit
Auto-Restart For Momentary
Power Failure
DC
voltage decreases to the
Atthattime, it will self-hold the failure signal
I
I
a
1. The power failure duration is within the allow­able time.
2. A RUN command is present when the power is restored.
3. Must be in “Remote” Mode.
Setting
0 __
Alarm
Setting Operation Self-Hold Alarm
0
-
Auto-Restart Active
stop Stop No
Yes
Status YES NO
Ind
Y0S
Yes No Trans.
Transmit
Sig,
Function 45
The
RUN, FAR, FDT,
to output faults and operation monitoring signals.
The output mode can be selected with this func-
Open Collector Output Selection
OL, and LV terminals are used
Output Signal Selection
lk%i * I ’
Symbol
tion. Three modes, 0, 1, and 2, can be selected. If
mode 1 or 2 is selected, signals are output in a bit pattern (see following charts).
This function is used for external indication of
Operating Mode and/or Fault Condition. NOTE: individual fault signal will output only one
fault,
even if more than one fault occufs simultane-
ous/y.
Combination of Individual Fault Output When Setting Is
Individual No
Fault
Terminal
RUN (MSB) Off FAR FDT
(LSB)
Fault
Off
Off
oc ou
Overcurrent Over
Voltaae
Off Off On
Off On
Off
iLver,oad
1
nals
“1’
LU
Under Voltaae
Off On On
LV
OLl
lnverter Overload
On Off Off
I
1
Early Warning Early Warning
Undervoltage Undervoltage
Alarm Alarm
OL2 OH1
Elec.
Overload Overheat On
Off On On
!
Motor lnverter
On
Off
!
vi&al
Fault Sig-
I
*
OH2
External Alarm .
On On On
6-9
Function
45 Open Collector Output Selection (continued)
Operation Monitor Output When Setting
Individual Fault
ou
LU OLI
OL2 Electric Motor Overload
OH1
OH2 External Alarm
Operation Monitor Output When Setting
lnverter Running
A
Overvoltage
Undervoltage lnverter Overload
lnverter Overheat
Is ‘2” (When inverter is tripped)
Terminal Symbol
LV
ILSBl
t
OL1 FDT1 FAR 1 RUN
Off
On off On off On Off On
Off
On
Is
“2”
(While inverter is not tripped)
Hoff /off
On On Off Off On On Off
E
Hoff
off off off off
On Off On Off On Off On Off Off On Off On
off off off off
lMSBl
Off Off
Off
Off 3 Off 4 Off off off
~off
Off 9
Decimal
Eaulv.
0
1
2
5 6 7 6
I
P P
P
P P P P
NOTE:
Function
Used for compensation of speed errors caused by load fluctuation. A slip frequency corresponding to
the load current can be added; compensation range is 0.0 to 2.5 Hz.
P A A
A
P P
)
indicates that monitor signal is present (True), A indicates that monitor signal is absent (False).
46 Slip Frequency Compensation
P
P P
A P Off Off Off Off On
P P
A On Off On On Off P
Off On On On Off On On On On Off
On Off Off Off On
13
14
15
16 17
6-10
Function 47 Operation By Signal Polarity
This function enables the direction of motor rota­tion to be changed according to the polarity
(+, -)
of the frequency setting voltage.
To operate the inverter with an external frequency
setter, turn on the switch between terminals FWD
and CM. Apply a positive voltage (+ 10 VDC) to terminal Vl to turn the motor in the forward direc­tion, or apply a negative voltage to the terminal to turn it in the reverse dirction.
If the switch between terminals REV and CM is on,
a positive voltage applied to terminal
Vi
turns the motor in the reverse direction and a negative volt­age to the terminal turns it in the forward direction.
This means that the motor rotation direction can be
changed simply by changing the polarity of the setting voltage.
‘0’
(zero):
Active
‘-’ (dash): Inactive
CAUTION:
made, the analoa sianal is iunored. When this hap­pens, the rotation direction will be set accordina to terminals FWD and REV.
AF-300C
lnverters
. ’
GEK-85716
S&itch
ON
(RN-CM)
If a Multi-Step Freauencv selection is
DATA PROTECTION
Function 99 Data Protection
I
Function Code settings can be protected so that
they cannot be changed or lost accidentally. Pro­tected data cannot be changed without first
cancelling the data protection function. The Data Protection function can be operated in the follow­ing two ways:
1. Select Function Code 99 using the SHIFT and
UP ARROW or DOWN ARROW keys. Use the SHIFT key to set the unit to Data Setting Mode. If
thedata
protected, displays
is protected,
“--’
is displayed. Pressing the UP key
“O’,
then pressing the SET Key stores
‘0’
is displayed.
If it is not
this value in memory and disables a data change.
Pressingthe DOWN key displays”--“, then press­ing the SET Key stores this value in memory and enables a data change.
2. While holding down the FAST key, press the SET key to protect the data or the RESET key to release data protection. The display shows
‘0’
when the data cannot be changed (protected) or
‘--”
when the data can be changed (not pro-
tected). The current display is held for five seconds after
the keys are released and then returns to the previous display.
NOTE:
In the Fault Monitoring Mode
or
while the data display is blinking, the Data Protection function cannot be selected.
6-I 1
Af-300C lnverters
GEK-85716
FAULT INDICATION AND DETECTION
fault
lndicafion
1
Functions FO - F7
The fault indication function is composed of the following three pans:
1. Indication of the present fault.
2. Indication of operating conditions at the time that the fault took place.
3. Indication of previous faults.
When a fault occurs, the mode will automatically be switched to the Fault Display Mode.
-- If the fault is a complex one (two or more simulta-
neous faults), use the UP or DOWN ARROW keys
to change the 4th data digit and the faults will be
displayed in the
-- Inaddition, the operating conditions at thetimeof the
present fault only
tions Fl
-- Also, the first fault for the previous three fault trips
can be indicated by
NOTE:
when multiple faults occur at the same time.
through F4.
First fault means the first detected fault
1st
2nd, and 3rd digits.
can be indicated by Func-
F5
through F7.
I
A more detailed explanation on obtaining fault
information can be found in Section 5 of this Instruction Book. If the fault will be investigated, obtain as much fault information as possible before resetting the inverter to resume operation. Also record the date, time, and any information about
the machine operation prior to the fault. This will
help in determining the cause more quickly.
Function Code
FO
___-
----
Fl
F2 F3
F4
F5 F6 F7
Indication Data (by digit)
4th
1
- 7 in
order 0
of
occurence.
E r r E r r
1
1-4inorder
of indication
3rd 2nd 1st
0 c 2
0
0 0 H 0 L 0 L
6 0.
6 0.
0 0.
c
c
0
L U H
F
::
L u L u u
1
3
U 1
2
1
2
0 d
0
0
0 0
E
Name of Fault
Overcurrent At Acceleration Overcurrent At Deceleration Overcurrent At Fixed Speed Overvoltage Undervoltage lnverter Overheat External Alarm lnverter Overload Motor Overload
CPU Error Memory Error
Output Frequency Setting Frequency Output Current
Normal Operation Reverse Operation Current Restriction
Voltage Restriction
Undervoltage Restriction
1st Prev. Fault (Pres. Fault - 1) 2nd Prev. Fault (Pres. Fault - 2) 3rd Prev. Fault (Pres. Fault - 3)
6-12
AF-300C /metiers GEK-85716
Figure
6-l.
AF300C FUNCTION CODE MAP
6-13
AF300C
lnwerters
GEK-85718
NOTES:
6-I
4
AF-300C
7.
MAINTENANCE AND INSPECTION
lnwerters
GEK-85716
So that the AF-300C inverter may give extended pe-
riods of trouble-free operation and to prevent poten-
tial problems from occuring, the following items should
CAUTION:
7-1 and meqqer them all at one time. each terminal individuallv.
be periodically inspected.
3. Use a multi-meter set on a high resistance range
WARNING - BURN AND SHOCK HAZARD:
Do not conduct any Inspectlons until after discon-
to conduct a continuity test on the control circuits and not a megger or a buzzer.
necting the power supply and after the “CHARGE” light on the inverter has gone out.
CAUTION: When removina or
replacing
wires,
handle them bv the connector onlv and not bv the
wire itself. Be careful not to mix wires when recon-
necting them.
PERIODIC PARTS REPLACEMENT
The life of the inverter will vary according to the
installation environment and the amount of running
time. However, if continuous operation is within the
allowable limits, the life of the DC Link capacitor is ap­proximately five years and the life of the cooling fan is
MEGGER TEST
NOTE: Perform t//is test only if absolute/y necessary.
1.
Disconnect all inverter terminals and never apply test voltage to the inverter when conducting an external circuit megger test.
2.
Perform the test only on the main circuit as shown
approximately three years. It is recommended that
these parts be replaced before failure occurs.
INSPECTION ITEMS
Refer to the Inspection Items Chart in this section
for inspection points and corrective action.
in Figure 7-l when conducting a megger test on the inverter itself.
--
Do not conduct a megger test on the control circuits.
Short all terminals as shown in Fiaure
Do not meqqer
TB5
8
E(G)
+
I
5OOV
MEGGER
Figure 7-1.
CONTROL CIRCUIT
TERMINAL BOARD
y,*piifyq
(8
MAIN CIRCUIT TERMINAL BOARD
N
Pl
Ll
L2 L3 u v w
I
P
MAIN CIRCUIT MEGGER TEST CONNECTIONS
7-1
INSPECTION ITEMS CHART
Item Reason of InsDection Corrective Action
Power Source
Voltage
Ambient Temperature
Ambient
Humidity
Vibration
Noise
Odor
Dust
Screws/ Connectors*
*Check internal screws/connectors only during periodic inspections or when cover is removed.
Wiihin permissible limits (323 - 506 VAC) Adjust the power supply voltage
for 380/400-460 VAC @ 50/60 Hz.
Within permissible limits
(+140
to
+122+)
Wiihin permissible limits (20 - 90% RH) Investigate cause and make corrections No dew condensation or freezing until environment is within permissible limits
Within permissible limit
Abnormal Audio Noise from cooling fan, etc.
Smell or burning
Dust accumulation on cooling fins, Clean and blow out with compressed air.
cooling fan, or on the control board. (Follow appropriate safety precautions.) Check for any loosening Retighten as needed.
(-100
to +500 C) Investigate cause and make corrections
until environment is within permissible limits
(0.6G
or less) Investigate cause and make adjustments
until within permissible limits. Contact the supplier where the inverter
was purchased. Contact the supplier where the inverter
was purchased.
Dailv
Inspections
For daily inspections, it is not necessary to remove
the inverter cover. Check the inverter from the out-
side for any abnormal items per the above chart.
--
If anything is found, take corrective action as soon as possible.
--
If the inverter is to be kept in operation before cor-
rections can be made, record details of the prob­lem for future reference.
7-2
Periodic Inspections
Periodic inspection intervals will vary per the inverter application (bi-monthly, semi-annualy, annually, etc.). Pick an interval that best suits the particular applica-
tion, but do not ignore the inspections entirely.
For periodic inspections, remove the inverter cover and check the inverter for any abnormal items as per the daily inspections, plus the following:
-- Check all internal screws/connections.
-- Check the DC Link capacitor for any leakage or swelling.
-- Check relay contacts for roughness.
--
Check all wires and conductors for any deforma-
tion or heat damage/deterioration.
-- Check resistor insulation for cracks.
--
Verify output voltage of each phase.
AF-300C hefters
GEK-85718
input Side (Power Side)
Amperemeter AR, S, T
Movable Core
Type
Symbol of Instrument
Item Measurement of Output Freq.
Output Side (Electric Motor Side)
Input Side Measuring Inst. (Power Side)
Voltmeter VR, S, T
Rectifier Type or Movable Core
Tvoe
Terminals FM1 and FM2
Wattmeter WR, T
Electrodyna-
mometer Type
INVERTER
Output Side Measuring lnst (Electric Motor Side)
I I
Wattmeter wu, w
Electro-
dynamo­meter Tvoe
Name of Instrument
Kind of lnetrument
Symbol of Instrument
DC Voltmeter
V
Movable Coil Type
Figure 7-2. MEASUREMENT LOCATIONS AND DEVICES EXAMPLE
MEASUREMENT POINTS AND METERS
Since the inverter input/output voltage and current
contains high frequencies, selection of the wrong measuring device can lead to gross miscalculations.
RECOMMENDED MEASUREMENT DEVICE CHART
Item Simde Measurement Precision Measurement
Input Voltaoe Tester Moving-Iron type voltmeter Input Current Clamp Meter Moving-Iron type ammeter Input Power -­Output Voltane Output Current Clamp Meter Moving-Iron type ammeter Output Power --
Tester Rectifier type voltmeter
When using a CT (current-detection transformer) to
measure the current, the amount of error will be large if the frequency is low. Because of this, always use a CT with as large a capacity as possible. See the fol­lowing chart and Figure 7-2 for recommended meas­urement devices.
Electrodynamometer type wattmeter
Electrodynamometer type wattmeter
7-3
AF-300C
lnverfers
GEK-85715
NOTES:
7-4
AF-300C lnverters
GEK-85718
8. TROUBLESHOOTING
TheTABLES and Figures within this Section arefurnished to aid in troubleshooting the more common problems
that may be encountered with the problem still is present, it may be necessary to contact the distributor that the inverter was purchased from. parts ordering procedures (In Warranty and Out of Warranty), refer to Section 9; for replacement parts listing, refer to Section as possible be recorded from the inverter before resetting and continuing operation. See Sections 5 and 6 of this Instruction Book for additional Fault information
IO.
For more expediant troubleshooting of Faults, it is recommended that as much information
AFSOOC
Inverter.
If after performing all suggested procedures and the
For
m J&Y
CL
LU
OCl
oc2
oc3
ou
OLl
OH1
OL2
Functlon
Current Limit
Undervoltage Trip
Overcurrent Trip
Overvoltage Detection
lnverter Overload
lnverter Overheat
Motor Overload
(Electronic Thermal
Overload)
TABLE
7:
FAULT DESCRIPTION AND OPERATION
Description
Provides restriction of the output current when the inverter reaches the current limit level.
--
Operation will be kept on for 15 msec at full load in case of power failure. (At light load, operating time may be slightly longer.)
--
When the DC Link goes below the under-voltage level, the inverter will stop output
When the output current of the inverter reaches the overcurrent protection level, the inverter will stop output and hold the fault trip (motor coasts to stop).
OCI : Overcurrent during acceleration.
OC2:
OC3: Overcurrent during constant speed. Ground faults are detected by the ground fault detection unit (standard equipment).
NOTE:
For prevention of personnel injury, efc, a leak-proof relay, should be
connected separately.
When the DC Link voltage reaches the overvoltage protection level,
the inverter will stop output and hold the fault trip (motor coasts to stop). When overload operation exceeds the overload limit (inverse time
characteristic) of the invetter, the inverter will stop output and hold the fault
trip (motor coasts to stop).
If the temperature of the inverter unit is too high, the inverter will stop output and hold the fault trip (motor coasts to stop).
When only one motor is driven, overload can be detected without an external thermal device. Since reduction in the cooling effect at low speed is taken into account, protection over a wide operation range can be provided. When overload operation exceeds the electronic thermal overload setting (inverse time characteristic) the inverter will stop output and hold the
fault trip (motor coasts to stop).
The ground fault defecfion
and
hold the fault trip (motor coasts to stop).
Overcurrent during deceleration.
unit is
to
protect
the
inverfer on/y.
.
CAUTION:
thermal
relav
When drivina more than one motor, provide protection with a
in line with each motor.
8-1
AF-300C
TABLE 7: FAULT DESCRIPTION AND OPERATION (continued)
Dis­plav
lnverters
Function
GEK-85718
Description
OH2 External Fault
Err0 CPU Err9
Err1
Err2
Errd
Abnormal
Setting Error Setting Error
NV-RAM Error
Stall Prevention
When the overtemp detection device of the brake unit and brake resistor
(optional) or the user’s external thermal relay is activated, the inverter will
stop output and hold the fault trip (motor coasts to stop). If the inverter CPU operation is abnormal, the inverter will stop output and
hold the fault trip (motor coasts to stop). When low limit frequency setting exceeds that of the high limit frequency. When a Function Code that cannot be set while inverter is running has been
attempted to be set. Stored setting data is abnormal. This error message cannot be reset.
Replace the Main Control Card.
NOTE:
reinserting any socketted integrated circuit chips on the Main Conttrol Card
(tota/ of three).
Automatically extends acceleration time to restrict overcurrent during rapid acceleration (to prevent overcurrent trip). Automatically extends deceleration time to restrict overcurrent and over­voltage during rapid deceleration (to prevent overcurrent and overvoltage trip).
It
may be possible
to c/ear this condition by removing and
input Surge
The inverter can be protected from 5KV standard impact wave voltage which will invade from the main circuit power.
8-2
AF-300C
TABLE 8: FAULT CONDITION DISPLAY AND
CORRECTIVE ACTION
lnverters
GEK-85718
Displa]
OCl
oc2
oc3
Check For: Corrective Action
AC supply voltage not within permissible limits . . . . . . . . . . . . Check inverter specs and adjust AC supply voltage.
Output line short-circuited
Proper torque boost Proper acceleration time Loose Connections
Other than above .,.,,.................................,..,....,,..,..,..,... Check transistors
AC supply voltage not within permissible limits . . . . . . . . . . . . Check inverter specs and adjust AC supply voltage.
Output
line short-circuited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Proper deceleration time ,..........,,...............................~...
Loose Connections .,...
Other than above
AC supply voltage not within Output line short-circuited
Sudden change in load
Loose Connections
Other than
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
above . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
,,..,.,,.,,..,..,,..,.,......................... Lengthen the acceleration time.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
permissible limits . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
.,..,...,..,..,..,.,............................,. Eliminate sudden load changes.
. . . . . . . . . . . . . . . . .
,..................................... .Check on operation of external output contactor
,......................
Check output line insulation.
Megger test the motor.
Adjust as needed (reduce torque boost).
Check on operation of external output contactor
If used.
Check Main Circuit wiring connections
Increase inverter capacity (use larger HP inverter).
Check
output
line insulation. Megger test the motor. Lengthen the deceleration time. Check on operation of external output contactor If used. Check Main Circuit wiring connections Connect DB braking unit resistor (optional) or check operation of if already present. (Check
thermal interlock connections to DB unit.)
Increase inverter capacity (use larger HP inverter). Check inverter specs and adjust AC supply voltage.
Check
output
line insulation. Megger test the motor.
if used. Check Main Circuit wiring connections Check for electrical noise. Check on operation of external output contactor If used. Increase inverter capacity (use larger HP inverter).
polarll
of
ou
NOTE: Motor will coast-to-stop when fault condition is displayed. After obtaining Fault information and correcting the cause of the problem, reset by pressing the RESET key on the Keypad Panel, or momentarily close contact between the
RST-CM control circuit terminals after the motor has stopped.
NOTE: if a fault cannot be reset, check to be sure that a RUN command is not present. NOTE:
AC supply voltage not within permissible limits . . . . . . . . . . . .
Proper deceleration time ..,.............................................
Dynamic Braking not functioning properly ..,.................
‘Lu”
may be displayed when the AC supply is switched OFF and does not indicate any abnormality.
8-3
Check inverter specs and adjust AC supply Lengthen the deceleration time. Connect DB braking unit resistor (optional) or check operation of if already present. Check polarity of thermal interlock connections to DB unit. Check Function Code 34; increase setting necessary.
voltage.
value if
AMOOC lnverfers
GEK-85718
TABLE 8: FAULT CONDITION DISPLAY AND
CORRECTIVE ACTION (continued)
Dimlay
OH1
OH2
LU
Ol2
Err1
Check For:
lnverter ambient temperature not within permissible
limits .,..*..............................................*..............................
Cooling fan(s) Loadisover permissibte limits
Proper wiring External thermal overload relay activated
(Continuity check between external
DB braking unit terminal 1-2) lnverter ambient temperature not within permissible
limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC supply voltage not within permissible limits.............. Check inverter specs and adjust AC supply voltage.
Circuit breaker is open
Open AC supply phase .................................................... Correct input wiring and check AC supply fuses.
Other than above ............................................................ Check customer power supply capac.ky.
Electronic thermal overload set incorrectly .................... Check Function Code 1 b.
Load is over permissible limits ........................................
Correct Function Code selection
(Low limit frequency has been set higher
than high limit frequency)
not operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
between THR-CM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . .
..-...... I
....................................................
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Corrective Action
Correct to proper temperature range. Replace cooling fan(s).
Reduce load. Increase inverter capacity (use larger HP inverter).
Rewire as needed.
. . . . .
Check relay. Reduce load.
Correct to proper temperature range. Correct ambient temp./lower braking duty cycle.
Close circuit breaker.
Reduce load.
Check Function Codes14and
15.
Err0
Err9
Err2
Errd
NOTE: Motor
cause of the problem, reset by pressing the RESETkey on RST-CM control circuit
NOTE: If a fault cannot b8 reset, check to b8 NOTE:
Electrical noise source close to inverter
A Function Code that cannot be set while running has been attempted to be set
Normal stored data settings (Stored setting data has been determined to be abnormal.)
will
coast-to-stop when faulf condition is displayed. After
terminals
“Lu”
may be displayed when the AC supply is switched OFF and does not indicate any abnormality.
(after the motor has stopped}.
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . Replace Main Control card.
sure that
a RUN command is notpresent.
Take noise prevention measures. Check to make sure noise is not coming into terminals “11” or “CM”.
Attempt to change only those Function Codes in TABLE 5 marked with “*2” while inverter is running.
NOTE:
condition by removing and reinserting any
SoCketted integrated circuit chips
Control Card (total of three).
the
Keypad Panel or momentarily close contact between the
obfaing
It
may be possible to clear this
on
the Main
far.& information and
correcting the
8-4
Motor Runs But Speed Does Not Change
NO
I
Is Upper/Lower Limiter
Activated?
(Function Codes
14
andll5)
AF-300C lnverters GEK-85716
Correct Wiring Error.
Analog Frequency NO
Setting Device Failure.
I,
What position is the
LOCAL/REMOTE switch
on the Keypad in?
NO
I
Is 11,
Vi
Wiring Correct?
Do Voltage And
Current Inputs To
Vi, 12, or
-T-
Are Acceleration/
Deceleration Times
NO
12,13,
Cl,
YES
Cl
Change?
YES
I
Too Long?
LOCAL
REMOTE
Are Xl, X2, X3
terms. connectea
to CM?
NO
Are All Frequency
Settings Different?
YES NO
I
YES
Use INC SPEED and
DEC SPEED Keys On
I
Keypad To Change
Speed
.
Are Function
,-
Codes 41 and 42
set correctly?
Correct Function
Code Settings.
-
Change Frequency
Settings.
Use
Xi,
X2, X3 terms.
to select frequency.
Adjust Acceleration/
Deceleration Time
To Match Load.
NO
lnverter Problem.
Figure 8-1. “MOTOR RUNS BUT SPEED DOES NOT CHANGE“ TROUBLESHOOTING CHART
8-5
AF-300C hvetters
GEK-85718
Motor Rotation Is Not Smooth
During Acceleration/Deceleration?
NO
Input Voltage Fluctuation? Correct Power Line Problem.
NO
Large Load Fluctuation?
NO
Noise Interference In Analog Input? Test With Analog Frequency Setting Device.
lnverter Problem
Figure 8-2. “MOTOR ROTATION IS NOT SMOOTH” TROUBLESHOOTING CHART
YES
YES
YES
Lengthen Acceleration/Deceleration
Time Setting.
Increase Motor And lnverter Capacity.
Attach A Flywheel.
Motor Overheats
Do Motor And V/F Pattern Match?
YES
Is There Continuous Low Speed Operation?
Is The Load Too Heavy?
Check lnverter Output Voltage Balance.
I
NO
I
If Not Good, Indicates lnverter Problem.
I
Figure 8-3. “MOTOR OVERHEATS” TROUBLESHOOTING CHART
NO
YES
YES
YES
I
Use Special lnverter Motor. Lower The Torque
Reduce Load. Increase lnverter Capacity
Correct V/F Pattern Setting
(Function Codes 10, 11, and 12).
Boost (Function Code 19).
(Use Larger HP Inverter).
If Good, Indicates Motor Problem.
8-6
AF-300C Imetiers GEK-85716
INVERTER
OVERHEAT
I
I
Is the inverter cooling
fan working?
YES
Is the inverter’s air
passage plugged?
NO
I
Is ambient temperature
within specified value?
NO
Figure 8-4.
NO
YES
YES
(OHl)
Check Power to
cooling fan.
Remove obstacles.
Check Speed Pot
wiring.
YES
-
Potential noise
interference.
“INVERTER
OVERHEATS” TROUBLESHOOTING CHART
Correct Power
No
Supply Problem.
Replace Cooling Fan.
Check that proper
noise prevention
measures have
I
-
been taken.
twisted wire for
control inputs. (Do not
connect terminals 11 or
NO
YES
CPU ABBNORMAL
Display abnormal
or out
YES
Turn power OFF, then
Sack ON (after CHARGE
lamp goes out).
Has data been dis-
played on indicator?
NO
Check that insertion of
CPU into IC socket is
correct.
Figure
YES
The inverter is normal;
allow continuous
operation. measures have
YES
Potential noise
interference.
8-5. “CPU ABNORMAL” TROUBLESHOOTING CHART
Check that proper
noise prevention
been taken.
YES
Use shielded and
twisted wire for
control inputs. (Do not
connect terminals 11 or
CM to earth ground.)
NO
I
YES
Possible inverter failure - Contact
lnverter Supplier
I
8-7
AF-300C
lnwenters
GEK-85718
EXTERNAL FAILURE (OH2)
Is the connection
between THR and CM
correct and intact?
NO
I
Is the alarm function of
the external equipment
working properly?
IYES
Is ambient temperature
for the external
equipment within the
specified value?
INO
Correct the ambient
condition to make it within the specified
value.
YES
YES
control inputs. (Do not
connect terminals 11 or
CM to earth ground.)
Are external thermal
sensors working
thermal sensors.
The inverter will trip on Remove RUN com-
OH2 if powered-up with
a RUN command RESET on the keypad
present. This is a to clear the trip.
safetv feature.
Use shielded and
twisted wire for
r
YES
mand and press
YES
RUN command from remote conflicts with
STOP command from
Reduce the load of the
external equipment or
decrease the duty
cycle, or use
larger HP
fnverter/Motor.
I
was present (FWD or
Was STOP pressed on
the keypad when the
inverter was running
with the LOCAL/RE-
Potential noise intetfer-
ence at THR or CM
terminals .
NO
I
Possible invetter
failure - Contact
fnverter Supplier
Figure 8-8. “EXTERNAL FAILURE” TROUBLESHOOTING CHART
8-8
NO
YES
Check that proper
noise prevention
measures have
been taken.
YES
I
I
Loading...