GE Industrial Solutions AEG47, AEG47S User Manual

g
p
g
quip
y
g
g
p
DEH212 Installation Instructions R02
Spectra Series™ Power Panelboards
Equipment Grounds Catalog Numbers AEG47 and AEG47S
These kits are provided for installing equipment grounds on Spectra Series panelboards. Figure 1 illustrates the installation of a bonded ground, catalog number AEG47. Figure 2 illustrates the installation of an isolated ground, catalog number AEG47S.
WARNING: Danger of electrical shock or injury.
OFF
Turn switchboard before workin
ment or removing any component.
e Equipment is to be installed and maintained b properly trained and qualified personnel only.
1. Mounting holes are not provided on the equipment for ground assembly. Position the ground assembly as required on the box back. Use the mounting holes as a template to locate and drill four 0.173-inch diameter holes for the #10-32 self tapping screws provided.
2. Secure the ground assembly with the #10-32 mounting screws tightened to 32 in-lb.
3. Apply the AEG47 or AEG47S identification and torque label next to the ground assembly.
ower ahead of the panelboard or
inside the
#10-32 Mounting
Screws
Cable Entry
This Direction
Figure 1. Bonded equipment ground, catalog number AEG47.
#10-32 Mounting
Screws
Minimum Clearance
Maintain the minimum electrical clearances listed in Table 1 between uninsulated live parts and grounded dead metal through air or over a surface.
Voltage
Difference
0–250
251–600 1
Table 1. Minimum clearances.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contin information be desired or should purposes, the matter should be referred to the GE Company.
ency that may be met in connection with installation, operation, or maintenance. Should further
Minimum
Clearance, in.
1
/2
articular problems arise that are not covered sufficiently for the purchaser’s
GE Industrial Systems
General Electric Company 41 Woodford Ave., Plainville, CT 06062
DEH212 R02 0401 © 2001 General Electric Company
Cable Entry
This Direction
Figure 2. Isolated equipment ground, catalog number AEG47S.