GE Industrial Solutions ADSVMA600D User Manual

GE Energy
Industrial Solutions
GEH-6250 Installation Instructions
Voltage Module
For Spectra® RMS Molded-Case Circuit Breakers with microEntelliGuardTM,
®
MicroVersaTrip
PM or MicroVersaTrip® Plus Trip Units
For Catalog Numbers ADSVMA120Y, ADSVMA208Y, ADSVMA240D, ADSVMA277Y, ADSVMA480Y, ADSVMA480D, ADSVMA600D
Circuit Breaker Accessory
Overview
The General Electric Voltage Module is used to provide +24Vdc Control Power to Spectra Case Circuit Breakers with microEntelliGuard MicroVersaTrip Cable System. The Module also provides voltage­sensing signals to Spectra Breakers with microEntelliGuard PM Trip Units on the same UL Listed Circuit Breaker Accessory Distribution Cable System. The Voltage Module is rated 24 watts (+24Vdc @ 1.0 Amp) and has the maximum capacity to power a Distribution Cable System consisting of 20 Spectra Case Circuit Breakers with microEntelliGuard MicroVersaTrip system cable length of 40 feet. The Voltage Module is designed to operate in temperature between 0°C and 70°C.
®
PM/Plus Trip Units via the Distribution
®
®
PM/Plus Trip Units with a maximum
®
RMS Molded-
RMS Molded-Case Circuit
TM
or MicroVersaTrip®
TM
,
®
RMS Molded-
TM
or
Figure 1 shows how the Voltage Module is used in a typical MicroVersaTrip the Voltage Module is used in a typical MicroVersaTrip Plus system. The microEntelliGuard support either configuration.
WARNING: Danger of electrical shock or injury. Turn OFF power ahead of the switchboard before working inside the equipment. Do not remove or install any circuit protective devices, or any other component until the
power is turned OFF.
®
PM system. Figure 2 shows how
TM
Trip Unit can
®
GEH-6250 Installation Instructions
Figure 1. Typical microEntelliGuardTM or MicroVersaTrip® PM Trip Unit System detailing the Voltage Module.
GEH-6250 Installation Instructions
Figure 2. Typical microEntelliGuardTM or MicroVersaTrip® Plus Trip Unit System detailing the Voltage Module.
GEH-6250 Installation Instructions
The Voltage Module contains both a Power Supply Plate and a Voltage Conditioner Assembly as integral components. The module also includes fuse protection for the AC source input terminals (see Figure 3). The Voltage Module is available in seven ratings. Table 1 contains a listing of all GE Voltage Modules. All units are rated 60 Hz.
Figure 3. Interior view of the Voltage Module (left side Power Supply Plate, right side Voltage Conditioner Plate)
Table 1. GE Voltage Modules
Voltage Rating
120Vac 3f4W – Wye ADSVMA120Y Phase to Neutral potential 208Vac 3f4W – Wye ADSVMA208Y Phase to Phase potential 240Vac 3f3W – Delta ADSVMA240D Phase to Phase potential 277Vac 3f4W – Wye ADSVMA277Y Phase to Neutral potential 480Vac 3f4W – Wye ADSVMA480Y Phase to Phase potential 480Vac 3f3W – Delta ADSVMA480D Phase to Phase potential 600Vac 3f3W – Delta ADSVMA600D Phase to Phase potential
System Configuration
Catalog Number
Sensing Connection
EntelliGuard™ TU or a MicroVersaTrip® PM Trip Unit. (Do
®
not connect this voltage signal to a Spectra
Trip Unit. The voltage signal structure is different between the MCCB and ACB/ICCB Trip Unit platforms).
CAUTION: The voltage-sensing signal structure for
®
MicroVersaTrip
PM and EntelliGuard™ TU Trip Units used in Air Circuit/Insulated Case Breakers is different than the voltage-sensing signal structure used on
®
Spectra
RMS Breakers with MicroVersaTrip® PM or
microEntelliGuard™ Trip Units.
Additional 24Vdc output connections are supplied for applications where +24Vdc control power is required independent of the Distribution Cable System (i.e. feeding Air Circuit Breakers and/or Insulated Case
®
Breakers with a MicroVersaTrip
PM/Plus Trip Units).
NOTE: THE VOLTAGE MODULE IS SIZED FOR A MAXIMUM OF 20 BREAKERS. Use of the Voltage Module to provide voltage-sensing signals and/or +24Vdc control power to a main Air Circuit Breaker or a main Insulated Case
®
Breaker with a MicroVersaTrip Trip Unit reduces the total quantity of 20 Spectra Molded-Case Circuit Breakers with microEntelliGuard
®
or MicroVersaTrip
PM/Plus Trip Units by one. The overall
or EntelliGuardTM TU
®
RMS
TM
maximum cabling length of the system remains 40 feet.
A communications connection is provided for applications where data is transmitted to an external intelligent device (See Table 2). The distribution cable system is used to interconnect the voltage signal on
®
the Voltage Conditioner Plate and the Spectra
RMS
Molded-Case Circuit Breakers.
CAUTION: The microEntelliGuard™ trip unit system uses modbus communications and should never be connected to a Commnet bus
An additional voltage output connection is available for applications where a voltage signal is needed on an Air Circuit Breaker or Insulated Case Circuit Breaker with an
Supplemental 24Vdc input terminals are provided for systems that have access to an external +24Vdc power supply. If this supplemental input is connected, the Voltage Module will continue to pass the control power to breakers and accessories connected to the Distribution Cable System if the primary AC power is lost or drops below the minimum requirement. This backup input must meet ANSI C37.90.1 for oscillatory and fast transient surges or damage to the Voltage Module may result (the Voltage Module provides this protection for the primary AC input). By plugging the Voltage Module into the Distribution Cable System, you create system wide signals that are available to
®
all Spectra microEntelliGuard
RMS Molded-Case Circuit Breakers with
TM
or MicroVersaTrip® PM/Plus Trip Units connected to the system; a list of available signals appears in Table 2.
GEH-6250 Installation Instructions
Table 2. Signals available on the Distribution Cable System by connection of the Voltage Module.
Spectra® RMS Breaker with MicroVersaTrip PM Trip Unit
control power (+24vdc)
control power (common) system communications (comm. +) system communications (comm. -)
voltage 1 (defined as potential between Af & N or between Af & Cf)
voltage 2 (defined as potential between Bf & N or between Cf & Bf)
voltage 3 (defined as potential between Cf & N or between Bf & Af)
®
Spectra Breaker with MicroVersaTrip Plus Trip Unit
control power (+24vdc) control power (common)
®
RMS
Spectra Breaker with
®
microEntelliGuard Trip Unit
control power (+24vdc)
control power (common) system communications (comm. +) system communications (comm. -)
voltage 1 (defined as potential between Af & N or between Af & Cf)
voltage 2 (defined as potential between Bf & N or between Cf & Bf)
voltage 3 (defined as potential between Cf & N or between Bf & Af)
®
RMS
TM
The Voltage Module contains eight connection points. Refer to Figures 5A and 5B or 6A and 6B for connection details and location information. The following is a detailed list of the Voltage Module connection points:
• “To Distribution Cable” (2x) – 12-pin plug connectors that mate with the 12-pin
receptacle of a Distribution Cable Harness (catalog number SDCHA11, SDCHA30 or SDCHA60). If the
®
Voltage Module is factory installed in a Spectra Series Switchboard these connections are factory wired to Distribution Cable Junction Boxes (catalog number SDCJBB).
• “Input” – Three-screw terminal block on the Power Supply
assembly. Use the one-terminal “GND” screw for connection of the ground. If the Voltage Module is
®
factory installed in a Spectra
Series Switchboard, this connection is wired to the switchboard equipment ground (the other two-terminal screws are pre-wired to the load side of the Power Supply Plate fuse block).
• “Communications” – Two-screw terminal block for Modbus
communications link or for Commnet link to the GE POWER LEADER™ Network.
• “Supplemental Input 24Vdc” – Two-screw terminal block for connection to an
external +24Vdc power supply.
• “Output to ACB/ICCB” – Three-screw terminal block for an additional voltage
®
sensing signal output to MicroVersaTrip
EntelliGuard
TU Trip Units in Air Circuit Breakers
PM or
and/or Insulated Case Breakers.
• “Output to 24Vdc” – Two-screw terminal block for an additional control
®
power output to MicroVersaTrip
or EntelliGuard™ TU Trip Units in Air Circuit Breakers and/or Insulated Case Breakers.
• Three-phase rear pressure connector – Provides an AC source connection for control power
and voltage sensing signals. If the Voltage Module is
®
factory installed in a Spectra
Series Switchboard, these connections mate with the vertical bus bars in the switchboard. For catalog number ADSVMA120Y and ADSVMA277Y, an additional AC neutral connection must be made at one of the potential transformers. This connection is factory wired if the
®
Voltage Module is factory installed in a Spectra Series Switchboard.
Dimensions, Weights and Wiring Diagrams
A Voltage Module dimensioned drawing is provided in Figure 4 to assist in mounting the accessory. The maximum unit weight is 38 pounds.
Figure 4. Dimensioned drawing of the Voltage Module (dimensions shown in inches).
Loading...
+ 11 hidden pages