Features:
• 3U High
• Up to 9,000W in a 19” Rack
• Single & Three Phase Input Models
• Fits 3 Hot-Plug / N+1 Redundant Rectifiers
• Individual Input feeds with O-ring Diodes
• Current Sharing and Remote Sensing
• World-wide safety approvals
• Optional 1U Controller Available
ACE3000T
3 Bay / 9 Kilowatt Power Shelf
FEATURES BENEFITS
Single wire current sharing Provide system stress balancing and increases reliability
Constant power characteristic Better suited for battery charging applications
No Minimum Load Eliminates need for pre-load resistors. Reduces cost of ownership.
Optional 1U High Controller Addresses telecom application requirements for redundant operation
SPECIFICATIONS 9,000 Watt Power Shelf for CAR3000T Rectifier Modules
Rack Model Number ACE303TN-1A ACE303T-1A ACE333TN-1A ACE333T-1A
Rectifier Module Part Number
Voltage Range
Output Current
Input Voltage Single Phase 180-264 VAC / 47-63 Hz Three Phase 180-264 VAC / 47-63 Hz
Maximum Input Current (per module) 19A @ Full Load and 180 VAC Operation (per module) 11A per phase @ Full Load and 180 VAC Operation (per module)
Maximum Output Power 9,000 Total Output Power (6,000 Watts Redundant Output Power)
AC Input Feeds Individual Input Feeds for each rectifier for 4mm2 cable
Input Protection Each CAR rectifier module is equipped with it's own internal fuse
Efficiency 90% typical at 230VAC
Regulation (Line & Load) +/- 0.5% of V1
Ripple & Noise 1% of V1 (pk-pk) - using 10µF tantalum cap. and 0.1µF ceramic cap.
Load Sharing Single wire. +/- 5% of nominal current
DC Bus Rectifiers connected in parallel. Floating bus with common "+". Maximum current is 250A
Status Indicators DC Good and Temperature OK (Green), AC Good (Amber)
Alarm Signals Over Temperature, Over/Under Voltage, No Power, Module not present
Battery Interface RJ45 signal connector per rectifier. RS232 for programming via laptop (with Controller).
Temperature Range 0 to 50°C at rated output power. Derates linearly to 60°C at 2.2% per °C
Shock & Vibration Per MIL STD-810F, NEBS Compliant to GR 63 Core
EMI / EMC Meets EN61000-3-2, -3 CISPR22 and FCC Part 15 Class A, Bellcore GR-1089-Core
Safety Approvals UL: 478, 1012, 1950; CSA 22.2 No. 650; IEC: 380, 435, 950; VDE: 0804, 0806; & CE Mark (LVD)
Dimensions Chassis Measures 16.00”/406.4mm (depth) x 17.165”/436.0mm (width) x 5.12”/132.1mm (height)
CAR3010L1TN-1A CAR3010K1TN-1A CAR3010L1T-1A CAR3010K1T-1A CAR3030L1TN-1A CAR3030K1TN-1A CAR3030L1T-1A CAR3030K1T-1A
-40 ~ -58 VDC -20 ~ +29 VDC +40 ~ -58 VDC +20 ~ +29 VDC -40 ~ -58 VDC -20 ~ +29 VDC +40 ~ -58 VDC +20 ~ +29 VDC
164.5A @ -54Vout 333A @ -27Vout 164.5A @ +54Vout 333A @ +27Vout 164.5A @ -54Vout 333A @ -27Vout 164.5A @ +54Vout 333A @ +27Vout
KEY MARKETS & APPLICATIONS
• Central Office • Cellular Base Stations
• Telecom Access Nodes • Wireless
• Satellite Hubs • RF Amplifiers
• Broadband Switchers • PCS Installations
• XDSL Access Networks • Factory Automation
rev 100506
Lineage Power Lineage Power Lineage Power (China)
3000 Skyline Dr. 2841 Dow Avenue 1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Mesquite, TX 75149 Tustin, CA 92780 USA Shanghai, 201401 China
Phone: (972) 284-2000 Phone: (714) 544-6665 Phone: 021 6710 8910
www.lineagepower.com/oem

Outline Drawing
5.18
(131.6)
RTN V1
16.00
(406.4)
17.165
(436)
17.165
(436)
V1
V1 RETURN
5.18
(131.6)
Series
3=3kW x 3 Bays
9kW Total
Power
Blank=Non-Compliant
Y0=5 of 6 Compliant
Z0=6 of 6 Compliant
RoHS Compliance
Re v.
0 = 1Ø
3 = 3Ø
Input Phase
3 = 3 Slots
Output V
Blank = Front End
T = Rectifier
Type
Blank = Positive
N = Negative
Polarity
Blank = Bus Bar
H = Positronic
(front-end only)
Backplane Connector
ACE 3 x 3 x x x xx - 1A
RTN V 1
L1 L2
L3
-
+
L1 L2
L3
RTN
V1
FRONT END POWER SHELVES (POSITIVE POLARITY)
FRONT END POWER SHELVES (NEGATIVE POLARITY )
16.00
(406.4)
16.00
(406.4)
17.165
(436)
5.18
(131.6)
5.18
(131.6)
ACE3000T
3 Bay / 9 Kilowatt Power Shelf
J4 / J5 / J6 are RJ45 Receptacle
AMP Part Number 55162-1
J4 FUNCTION
1 IOUT 1
2 IOUT 1 (RS)
3 VPROG 1
4 VPROG 1 (RS)
5 I-SHARE 1
6 ALARM 1
7 GROUND 1 (RS)
8 ON/OFF 1
J5 FUNCTION
1 IOUT 2
2 IOUT 2 (RS)
3 VPROG 2
4 VPROG 2 (RS)
5 I-SHARE 2
6 ALARM 2
7 GROUND 2 (RS)
8 ON/OFF 2
J6 FUNCTION
1 IOUT 3
2 IOUT 3 (RS)
3 VPROG 3
4 VPROG 3 (RS)
5 I-SHARE 3
6 ALARM 3
7 GROUND 3 (RS)
8 ON/OFF 3
3-Phase Input Shelves
Use 3-Position Terminal
Blocks (Consult Factory
for Outline Drawing)
PART NUMBER DEFINITION GUIDE
rev 100506
Lineage Power Lineage Power Lineage Power (China)
3000 Skyline Dr. 2841 Dow Avenue 1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Mesquite, TX 75149 Tustin, CA 92780 USA Shanghai, 201401 China
Phone: (972) 284-2000 Phone: (714) 544-6665 Phone: 021 6710 8910
Example Part Numbers:
Backplane
Part # Type Phase Polarity Connector
ACE303T Rectifier Single Positive Bus Bar
ACE333T Rectifier Three Positive Bus Bar
ACE303TN Rectifier Single Negative Bus Bar
ACE333TN Rectifier Three Negative Bus Bar
www.lineagepower.com/oem