GE Logix 764 Operation Manual

Logix 764 Operation Manual
Models: 293/298 Magnum IT
Twin Alternating
Twin Parallel
Single with Remote Regeneration Start
Multi-Single Tank with Lockout
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation Profile Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
How To Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Icons That Appear In This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Location Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Outdoor Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Assembling the Logix 764 Control to the
Magnum Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Magnum General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Magnum Valve Installation Guide (Top Mount) . . . . . . . . . . . . . . . . . . . . . . . . 14
Magnum IT Dimensional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Typical Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Camshaft Cycle Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
764 Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Power Loss Memory Retention . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Flow Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Identifying the Logix Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Display Icons & Cursors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Keypad — Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Programming Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Placing Water Conditioning System Into Operation . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Level l Programming - 764 Control with 298 Valve, 5 Cycle Conditioner . . . . . . . .28
Level l Programming - 764 Control with 293 Valve, 3 Cycle Filter . . . . . . . . . . . . . .29
Placing Water Conditioning System Into Operation (continued) . . . . . . . . . . . . . . . .30
Quick Cycling the Control 293/298A, 293/298P and 293/298L . . . . . . . . .30
In Service Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Programming Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Level I Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Level II Programming – P Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Programming the Lockout Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Salt Setting (298 Conditioner) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Level lll Cycle Programming – C Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Level IV Viewing History - H Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Program Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Manual Regeneration Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Regeneration Modes for Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Connecting the Logix 764 Twin Alternating or Parallel Controls . . . . . . . . 39
Remote Regeneration Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Connecting the Logix 764 Multi Single Tank Control . . . . . . . . . . . . . . . . . . 40
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
764 Controller – Error Codes & 298 ”L” with Check Salt Light . . . . . . . . . 41
System Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Magnum Valve Cartridge Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Magnum Valve Cartridge Removal Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
Performance Injectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Injector Charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Magnum Flow Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Refill Control Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Drain Line Flow Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50
Recommended Backwash Flow Rates for Various Media . . . . . . . . . . . . . .51
764 Logix Magnum Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Replacement Components: Logix Magnum Conditioner/Filters . . . . . . . . . . . . . . . .53
Camshaft and Pilot Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Magnum Valve Cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Injector Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Refill Flow Control Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Magnum IT Flow Sensor Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Installation Adapter Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
Miscellaneous Kits and Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Safety Information
This water conditioner’s control valve conforms to UL/CE Standards. Generic valves were tested and certified for compliance as verified by the agency listing.
Please review the entire Installation and Operation Manual before installing the water conditioning system.
As with all plumbing projects, it is recommended that a trained professional water treatment dealer install the water conditioning system. Please follow all local plumbing codes for installing this water conditioning system.
This system will not make microbiologically unsafe water safe. Water that is unsafe must be treated separately from this conditioner.
This water conditioning system is to be used only for potable water.
Inspect the water conditioning system for carrier shortage or shipping damage before beginning installation.
Use only lead-free solder and flux, as required by federal and state plumbing codes, when installing soldered copper plumbing.
Use caution when installing soldered metal piping near the water conditioning system. Heat can adversely affect the plastic control valve and bypass valve.
All plastic connections should be hand tightened.
1
Teflon
tape may be used on connections that do not use an O-ring seal. Do not use pipe dope type sealants on the valve body. Do not use pliers or pipe wrenches.
Do not use petroleum-based lubricants such as Vaseline, oils or hydrocarbon-based lubricants. Use only 100% silicone lubricants.
Use only the AC adapter supplied with this water conditioning system.
All electrical connections must be completed according to local codes.
The power outlet must be grounded
Install an appropriate grounding strap across the inlet and outlet piping of the water conditioning system to ensure that a proper ground is maintained.
To disconnect power, unplug the AC adapter from its power source.
Observe drain line requirements.
Do not support the weight of the system on the control valve fittings, plumbing, or the bypass.
Do not allow this water conditioning system to freeze. Damage from freezing will void this water conditioning system’s warranty.
Operating ambient temperature: 34° to 120°F (1° to 49°C).
Operating water temperature: 34° to 100°F (1° to 38°C).
Operating water pressure range : 25 to 100 psi (1.72 to 6.89 bar). In Canada the acceptable operating water pressure range is 25 to 100 psi (1.72 to 6.89 bar).
Observe all warnings that appear in this manual.
Keep the media tank in the upright position. Do not turn upside down or drop. Turning the tank upside down or laying the tank on its side can cause media to enter the valve.
Use only regenerants designed for water conditioning. Do not use ice melting salt, block salt or rock salt .
1. Teflon is a trademark of E. I. duPont de Nemours.
3
Installation Profile Summary
Installation Date: _______________________________
Installation Location: ____________________________
Installer(s): _____________________________________
Phone Number:_________________________________
Valve Number: _________________________________
Application Type: (Softener) (Filter) (Dealkalizer)
Water Source:
(Public Well) (Private Well)
(Surface Supply)
(Other)
Water Test Results:
Hardness: _______________ Iron:_______________
Other: ________________________________________
Misc:
Capacity:________ Flow Rates: ____ min. ______ max.
Tank Size: Diameter _________ Height: ___________
Resin or Media Volume: __________________________
Resin or Media Type: ____________________________
Brine Tank Volume:______________________________
Salt Setting per Regeneration:_____________________
Control Valve Configuration:
Valve Type: ____________________________________
(Hard Water Bypass) (No Hard Water Bypass)
Refill Control:_______________________________ gpm
Injector Control: ____________________________ gpm
Electronic Demand Settings
P1 Time of day ________________
P2 Day of week ________________
P3 Time of regeneration ________________
P4 Number of days between regeneration (99 day
calendar override) ________________
P6 Amount of regenerant used per regeneration or filter backwash time (salt setting) ________________
P7 System capacity ________________
P8 Hardness (not used on Filters) ________________
P9 Units of measure ________________
P10 Clock mode ________________
P11 Service interval ________________
P12 Remote regeneration switch delay ____________
P13 Refill sensor control (conditioner only) _________
0 = Off 1 = Salt detector only 2 = Chlorine generation
P14 Refill rate (conditioner only) ________________
P15 Draw rate (conditioner only) ________________
P16 Reserve type (not used for
alternating mode) ________________
P17 Initial average or fixed reserve
(not used for alternating mode)_______________
P18 Flow sensor select ________________
P19 K-factor or pulse equivalent ________________
Backwash Control: __________________________ gpm
4
How To Use This Manual
This installation manual is designed to guide the installer through the process of installing and starting water conditioning systems featuring the Logix 764 controller.
This manual is a reference and will not include every system installation situation. The person installing this equipment should have:
Training in the 764 series control and the 298 valve.
Knowledge of water conditioning and how to determine proper control settings.
Adequate plumbing skills.
Icons That Appear In This Manual
WARNING:
can result in personal injury or damage to the equipment.
Note:
Helpful hint to simplify procedure.
The Logix 764 control can be installed on several type valves that can have twin alternating, twin parallel or single tank configuration. The section on Logix 764 start­up provides a simple explanation of the valve types that are pre-programmed in the 764 control.
Failure to follow this instruction
R
Tim
egen Tim
e & D
SU
ay
e & D
Salt Am
MO
ay
TU
ount
WE
C apacity
TH
H ardness
Logix 764
FR
SA
DAYS
Figure 1 293/398 Valve Layout
5
LCD Display
Front
Down Button
No-Salt Detector
(Chlorine Generator)
Connection (not used
on Magnum Valves)
Multi Single Tank
Back
Lockout & Remote
Regen/Start
Dry Contact Signal Input
Connection
Extension Cable
Connection
SU MO TU WE TH FR SA
Time & Day
Regen Time & Day
Salt
Capacity
Hardness
Set Button
x2
P H
C
PM MIN
g/L
KG
x100
Lbs/ft³
Up Button
Main Motor & Optical Sensor Connection
Turbine Input
Figure 2 764 Controller Identification
Location Selection
Location of a water conditioning system is important. The following conditions are required:
Manual Regen Button
AC Adapter (low voltage) Input
Figure 3 Remote Start/Multi-Tank Lockout Cable
Figure 4 Twin Sensor Cable
Figure 5 Twin Cable Extension
Level platform or floor.
Room to access equipment for maintenance and adding regenerant (salt) to tank.
Ambient temperatures over 34
o
F (49oC).
120
o
F (1oC) and below
Water pressure below 100 psi (6.89 bar) and above 25 psi (1.7 bar).
In Canada the water pressure must be below 100 psi (6.89 bar).
Constant electrical supply to operate the controller.
Total minimum pipe run to water heater of ten feet (three meters) to prevent backup of hot water into system.
Local drain for discharge as close as possible.
Water line connections with shutoff or bypass valves.
Must meet any local and state codes for site of installation.
Valve is designed for minor plumbing misalignments. Do not support weight of system on the plumbing.
Be sure all soldered pipes are fully cooled before attaching plastic valve to the plumbing.
6
Outdoor Locations
When the water conditioning system is installed outdoors, several items must be considered.
Moisture – The valve and control are rated for NEMA 3 locations. Falling water should not affect performance. The system is not designed to withstand extreme humidity or water spray from below. Examples are: constant heavy mist, near corrosive environment, or upwards spray from sprinkler.
Caution:
used with a listed Class 2 power supply suitable for outdoor use.
Direct Sunlight – The materials used will fade or
Temperature – Extreme hot or cold temperatures will
This unit is for dry location use only unless
discolor over time in direct sunlight. The integrity of the materials will not degrade to cause system failures.
cause damage to the valve or control. Freezing temperatures will freeze the water in the valve. This will cause physical damage to the internal parts as well as the plumbing and conditioning resin. High
temperatures will affect the control. The display may become unreadable but the control should continue to function. When the temperature returns to normal operating limits the display will re-appear. A protective cover should assist with high temperature applications.
Insects – The control and valve have been designed to keep all but the smallest insects out of the critical areas. Any holes in the top plate can be covered with duct tape. The top cover should be installed securely in place.
7
Assembling the Logix 764 Control to the Magnum Valve
The control and the Magnum valve work together as an integral system to ensure synchronization. Follow the steps outlined below to install the control on the Magnum valve.
Slide Camshaft
Slide the camshaft toward the back of the valve by pressing on the release tab and pulling on the back end of the camshaft (Figure 8). The front end of the camshaft will be flush with the mounting plate.
Remove Cam Cover
Remove the cam cover by pressing in on the cover release tabs (Figure 6). Note the cover locking tab and the slot in the top plate. When you reassemble the cover, the locking tab is placed in the slot first and the cover lowered into position.
Locking Tab and Slot
Cover Release Tabs
Figure 6
Release Tabs
Figure 8
Mount Control
Mount the control onto the valve by sliding the mounting tabs over the mounting plate. Note that all models of Magnum controls mount to the valve in the same manner (Figure 9).
Mounting Tabs
Align Camshaft
The camshaft is keyed and should only be engaged or disengaged when in the position illustrated (Figure 7). If the camshaft is not in the proper position, rotate the cam assembly counterclockwise until the camshaft arrow aligns with pillow block arrow.
Camshaft Arrow
Pillow Block Arrow
Figure 7
Mounting Plate
Figure 9
Engage Assembly
The camshaft will not rotate by hand when engaged with the controller. The Logix Magnum controller contains a motor with gears that drive a socket. The camshaft is keyed to only properly engage the socket when the Logix controller is in the treated water (Home) position.
If the camshaft is pulled back and not engaged it can be rotated counterclockwise. Rotate the camshaft to align the arrows (Figure 7). If the Logix Magnum controller is not
8
in the treated water position, cycling the power will cause the socket to rotate to that position.
Engage the control by pressing on the release tab and pushing the camshaft into the control (Figure 10). Do not force the camshaft. If the camshaft does not slide freely into the control, check the alignment of the camshaft to the controller. Ensure it is in the proper position (Figure 7).
The Logix controller moves to the treated water (home) position when first power is applied.
Release Tab and Camshaft
Figure 10
To disassemble the control from the valve, reverse the assembling procedure.
Inlet, Outlet and Drain Connections
The inlet, outlet, and drain connections are designed to accept a GE Water Technologies supplied CPVC or brass adapter (Figure 11). The adapters provide a convenient union for the three connection ports on the valve. In addition, they incorporate a positive O-ring face seal for ease of installation and leak free operation. DO NOT OVERTIGHTEN THE ADAPTERS. As a general guideline, hand tightening the nut onto the valve is adequate. If additional tightening is required, never exceed a quarter turn beyond the hand tight position.
The outlet of the 2-inch Magnum IT has an integrated turbine. The turbine measures the flow of water through the outlet. This information is used by the controller to determine the best time to recycle.
Figure 11
No Hardwater Bypass Feature
The Magnum control valve may be configured for “Hard Water Bypass” or “No Hard Water Bypass”. With Hard Water Bypass, unsoftened or unfiltered water is allowed to bypass the Magnum control valve during regeneration or backwash. With No Hard Water Bypass, a valve cartridge ensures that no unsoftened or unfiltered water bypasses the valve during regeneration or backwash.
It is easy to observe which option is installed in the valve. Note that the Hard Water Bypass End Cap has much longer standoffs than the No Hard Water Bypass cartridge. The No Hard Water Bypass assembly looks identical to the other three valve cartridges on the valve and has a label identifying the cartridge assembly (Figure
12).
No Hard Water Bypass No Unfiltered Water Bypass
Normal Standoffs
Extended Standoffs
With Hard Water Bypass End Cap
Figure 12
9
Hydraulic Output Signal
T
Magnum Tank Adapter
An optional hydraulic output signal is available on the valve. An optional cam lobe on pilot valve #6 is used on the camshaft assembly to initiate the hydraulic output signal during regeneration or backwash (Figure 13). The hydraulic line pressure signal is available through the 1/4-inch connection on the back of the valve marked “AUX”. See Figure 14. Remove the tube cap installed for shipping.
Optional cam lobes available are:
P/N 1000554 Provides a hydraulic signal from the
beginning of BACKWASH through the start of REFILL.
P/N 1000553 Provides a hydraulic signal from the
beginning of BACKWASH through the end of REFILL.
P/N 1041064 Breakaway cam. Can be programmed to
send a hydraulic signal at any time during the REGENERATION or BACKWASH cycle. Note: The camshaft must be turning for the signal to change states, i.e. switch from OFF to ON, or from ON to OFF.
The tank adapter on the control valve is designed to be compatible with a 4 inch-8UN (8 threads per inch) tank opening. In addition, the adapter is designed to accept a full 1-1/2-inch (3.81-cm) riser pipe with outside diameter of
1.90 to 1.91 inches (48.26 to 48.51 mm) (Figure 15). The
riser pipe is sealed by an O-ring on the inside of the tank adapter (Figure 15). It is recommended that the riser pipe extend beyond the top of the tank by 1/4 inch ± 3/8 inch (6 mm ± 9 mm).
O-ring
Tank O-ring
op of Tank
.375" (9.52 mm)
Top of Riser
Riser O-ring
O-ring
0.25"
(6.4 mm)
±.375"
(9.5 mm)
Figure 13
Optional Cam
Lobe Position #6
“Hydraulic Output
Signal
Auxiliary Hydraulic Output Port “AUX”
Figure 15
Optional Switch Assembly
A single optional feedback switch kit is available to provide an electrical signal during the entire regeneration or backwash cycle (Figure 16). The switch may be wired in the “Normally Open” or “Normally Closed” position and is rated for 0.1 amp at 125 volts AC. An optional 5.0 amp switch at 1/10 HP 125/250 volts AC is available upon request.
Common
Normally Open
Figure 14
Normally Closed
Pilot Drain Port
Figure 16
Optional multi-switch kits are available to provide
10
additional electrical or switch closure signals during the regeneration or backwash cycles. Coupled with the optional breakaway cams, signals can be sent to external system equipment at virtually any time while the control/ camshaft motor is running. Consult the instruction sheet covering the multi-switch option for additional application and programming information. The instruction sheet is sent with the switch kit.
11
Magnum General Specifications
Operating and Environmental
Dynamic Pressure .................................................................................................................................................25 to 100 psig (172 to 688 kPa)
100 psig (688kPa) maximum in Canada
o
Operating Water Temperature Range.......................................................................................................................... 34 to 100
Ambient Temperature Range............................................................................................................................................ 34 to 120
F (1 to 36oC)
o
F (1 to 50oC)
Cap Bolt Torque ............................................................................................................................................... 35 to 40 inch lbs. (3.95 to 4.51 N
m
Connections
Inlet and Outlet ...................................................................................................................... ........................ ......................... .......... 2-inch Magnum IT
Tank....................................................................................................................................................................................................................... 4-inch 8UN
Brine...................................................................................................................................................................................................................3/4-inch NPT
Pilot Drain and Auxiliary Hydraulic Out .............................................................................................................................1/4-inch tube fitting
Riser Pipe Fitting............................................................................................................................................................................ 1-1/2 inch (3.81-cm)
Drain ...................................................................................................................................................................................................1-1/2 inch (3.81-cm)
Physical
Dimensions ...................................................................................................................................................26-11/16" L, 16-1/4" W, 10-11/16" H
Approximate Weight (Valve and Control) ................................................................................................................................23.3 lbs. (10.6 kg.)
Electrical*
Voltage - Logix 764 Series Control..................................................................................................... 12 VAC wall mount transformer only
Power Consumption...............................................................................................................................................................................................4 watts
)
*See section on Electronic Controls for alternative electrical configurations.
12
General Installation Information
Please review the following items thoroughly to ensure an efficient and safe installation of the water treatment system. The typical installation line drawings for the Magnum valves are shown in Figure 19.
WARNING:
Filter media may need to be properly conditioned before the filter is placed into full operation. Consult the original equipment
manufacturer for proper procedure.
Operating Conditions -
A minimum dynamic operating water pressure of 25 psig (172 kPa) is required for the Magnum control valve to operate properly.
(688 kPa). In Canada, water pressure is not to exceed 100 psig (688 kPa). Water temperature is not to exceed 100 conditions.
Space Requirements - Allow adequate space for the water treatment system and associated piping. A minimum of 4 1/2 inches (11.5 cm) front and rear clearance is required for cartridge assembly and removal.
Plumbing - Always follow good plumbing practices and conform to local codes. Check existing pipes for lime and/ or iron buildup. Replace piping if heavy buildup exists and initiate the proper treatment to prevent additional occurrences. Locate the equipment close to a drain that is capable of handling the maximum drain flow rate during backwash.
Flexible Connectors - Some tanks expand and contract over the acceptable range of operating water pressures of the Magnum control valve. The use of flexible connectors is recommended on polywound or fiberglass tank installations of 24-inch (60.96-cm) diameter and larger. Follow the tank manufacturers instructions for more information.
Inlet and Outlet Piping - Inlet and outlet plumbing should be adequately supported to avoid excessive loads on the valve. Install a manual bypass system to provide for occasions when the water conditioner must be bypassed for servicing.
Drain LIne Piping - To prevent mineral loss during backwash, and to ensure proper operation of the control valve, A DRAIN LINE FLOW CONTROL must be plumbed into the drain line prior to placing the valve in the service mode. Flow controls from 5 to 40 gpm (18.92 to 151.4 Lpm) are available from GE Water Technologies and can be easily installed in the drain line. Flow controls greater than 40 gpm (151.4 Lpm) must be plumbed externally. Selection of the proper drain line flow control depends on the tank size and media used for the installation.
Water pressure is not to exceed 100 psig
o
F (36oC). Do not subject the valve to freezing
The following general drain line piping guidelines should be observed:
1-1/2 inch (3.81 cm) or larger piping
Should not exceed 20 feet (6.1 m)
Should not be elevated higher than f ive feet above the
control valve
No shut-off valves should be installed in drain line
Minimal number of elbows and fittings should be
installed in drain line
Piping must be self-supporting
Flow control should be installed as close to the
Magnum Series control valve as possible if an external flow control is used.
DAYS
SUMO TU WE TH FR SA
Time & Day
Salt Amount
Regen Time & Day
Capacity
Hardness
Drain Line Flow Control Disk
Figure 17
Brining System - The Magnum control valve utilizes timed water refill to add water to the salt tank. A refill tube with check ball is required in the brine tank that does not restrict the refill or brine draw flow rate capabilities of the valve. Although not required, a separate brine valve (safety float) system is recommended for use with Magnum installations. Select a “High-Flow” brine valve that does not restrict the refill or brine draw flow rate capabilities of the valve. The “Performance Injectors and Magnum Flow Controls” section of this manual contains flow rate information for various size injectors and refill controllers.
Pilot Drain - During regeneration, a small amount of water (200 ml or 1 cup) is discharged from the 1/4-inch (6.3-mm) tube fitting on the back of the valve marked DRAIN (Figure 18). To prevent this water from being discharged to the floor, plumb this connection to a non­pressurized drain or to the brine tank. Do not plug or
apply back pressure to the pilot drain at any time.
Crimping the pilot drain line or installing the line to go up, which causes backpressure, prevents the diaphragm cartridges from shifting properly through the cycles of regeneration or backwash.
13
Auxiliary Hydraulic
Output Port - Plugged
Electrical
1. Electrical requirements for the installation depends on the configuration of the control.
2. The standard North American Series Logix electronic control is supplied with a 12 volt AC adapter. Optional AC adapters must be ordered separately for all international 12 VAC configurations.
Pilot Drain Port
Figure 18
Magnum Valve Installation Guide (Top Mount)
Before the installation of the internal distribution system and loading of the media into the tank, the Magnum valve must be temporarily installed onto the tank. This will ensure that correct alignment of the inlet and outlet piping once the internals are installed and the media is loaded onto the tank.
1. Install tank O-ring into the tank adapter section at the bottom of the Magnum valve. Be sure to lightly
lubricate the O-ring with the 100% silicone lubricant provided with the valve.
2. Screw the Magnum valve onto the empty tank until O-ring touches the top of the tank.
3. Turn (tighten) the Magnum valve an additional 60° to 90° (max).
4. Align valve with plumbing connections to minimize unnecessary stress.
Caution:
The Logix Control and supplied AC adapter are for dry location use only, unless used with a Listed Class 2 power supply suitable for outdoor use.
Lubricants
It is very important that 100% silicone lubricant is the only lubricant used for installing the Magnum control valve. Any other lubricant may cause material degradation and potential failure of the valve components.
NOTE: Some silicone based lubricants contain petroleum-based ingredients. If there is a question about the lubrication that you are using contact the lubricant manufacturer to be sure the product is 100% silicone.
Caution:
Plumbing cannot be used for electrical grounding when metal inlet and outlet piping is connected to a non-metal valve.
Connect the inlet and outlet piping together using a grounding strap or clamp to establish continuity.
5. For reference, place a mark on the tank beneath the front center of the Magnum valve.
6. Remove the Magnum valve in preparation for installation of the internals and media loading.
7. Prior to loading media, make sure the tank alignment is correct using the mark on the front of the tank.
8. Cut riser 1/4-inch above the top of the tank, plus or minus 3/8 inch. Place riser inside the tank.
9. Load media following your supplier’s recommendations.
10. Follow piping recommendations to provide support and flexibility. Layout piping to accommodate for FRP tanks and piping dimensional changes and potential water hammering. Flexible connectors may be needed.
11. Proper pipe alignment is needed.
Flex connectors are recommended when installing valves on FRP tanks that are 24 inches or larger in diameter.
14
Magnum IT Dimensional Specifications
2-Inch Inlet and Outlet, 1 1/2-Inch Drain
1-11/16 (4.3 cm)
9-3/4
(24.8 cm)
4-7/16
(11.3 cm)
7
(17.8 cm)
16-1/4
(41.3 cm)
4-1/2
(11.4 cm)
13-1/2
(34.2 cm)
9
(22.9 cm)
4-1/2
(11.4 cm)
6-1/2
(16.5 cm)
2-15/16 (7.5 cm)
7-1/2
(19 cm)
11-3/4
(29.9 cm)
13-15/16
(35.5 cm)
1-1/16
(2.7 cm)
15-7/16
(39.2 cm)
26-11/16 (67.8 cm)
4-7/16
(11.3 cm)
15
Typical Installation Drawings
Twin Tank
Multiple Tank
Figure 19
16
Camshaft Cycle Positions
764 Control Operation
The front end of the camshaft has an indicator cup. The cup has slots in the outer edge and cycle numbers on the inside face.
Remove the cover and look over the top of the 764 control to view the cycle numbers. The number in the opening, (Figure 20) indicates the current cycle position of the control valve. The corresponding slot for the number is positioned at the optical sensor, which is rotated approximately 90 degrees out of phase.
Cycle Indicators:
0 = Treated Water 1 = Backwash Cycle 2 = Regenerant Draw Cycle 3 = Slow Rinse Cycle 5 = Fast Rinse Cycle 8 = Regenerant Refill Cycle
Number of Current Cycle
Power Loss Memory Retention
The 764 control features battery-free Time of Day and Day of Week retention during loss of power. A super capacitor is designed to keep time for 8 to 24 hours depending on the installation. If the super capacitor is exhausted the Logix control will display four dashes (- - :- -) immediately upon power up. The Time of Day and Day of Week must be reset.
All other programmed parameters are stored in the static memory and are retained.
Figure 20 View with Cover and Logix Control Removed
17
Loading...
+ 44 hidden pages