Franklin Fueling Systems TSP-DIS User Manual

TSP-DIS & TSP-EIS
Interstitial BriteSensor® & Standard Sensor
Installation Instructions
Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USA
Tel: +1 608 838 8786 • 800 225 9787 • Fax: +1 608 838 6433 • www.franklinfueling.com
Overview
Conductivity Sensors
1.10
(27.94
mm)
0.62
(15.75
mm)
0.63 (15.75 mm)
2.69
(68.33 mm)
3.22
(81.79 mm)
0.63 (15.75 mm) HEX
TSP-EIS
TSP-DIS
Discriminating Interstitial Sensor (Britesensor
®
)
Electro-optic Interstitial Sensor (Standard Sensor)
Double Wall Fiberglass Tank
Manhole
Cover For
14 Inch (35.56 Cm)
Min. Dia. Manhole
1/2 or 3/4 Inch Conduit
2 Inch (50.8 Mm)
Riser Pipe
TSP-DIS
or
TSP-EIS
Sensor
Eys Seal Fitting
Interstitial
Area (Dry)
TSP-K12 Riser Cap (With Cord Grip ­ Compression Fitting)
Clean Fill Material (Gravel Typical)
Concrete Slab Per NFPA 30
Weatherproof Junction Box
Compression Fitting (Cord Grip)
Annular Space Interstitial Sensor (TSP-EIS or TSP-DIS)
Pull Wire
Doublewall Fiberglass Tank
Sensor Cable
Pull Wire
Riser Pipe
The TSP-EIS is a Standard sensor and the TSP-DIS is an intelligent BriteSensor.® These sensors are used to detect the presence of liquids in the normally dry interstitial (annular) areas of double-wall fuel storage tanks (a Class 1, Division 1, Group D Hazardous Area). Both types of sensors use electro-optical technology (LED & Prism) for liquid-detection.
Figure 1: TSP-DIS and TSP-EIS Dimensions
The TSP-EIS communicates its identication code and current detection status to the ATG console (water present or normal – no liquids detected). An open-circuit is recognized as an alarm-condition at the intrinsically safe (I.S) leak detection circuits of the FFS (Franklin Fueling Systems) ATG (Automatic Tank Gauge).
EYS Seal ttings and Epoxy to ll the tting after
operational testing is completed.
Weatherproof junction box, gasket, and cover, plus a
3/4 to 1/2 inch NPT reducing bushing if 1/2 inch RMC is used – see the ATG Installation Guide for recommended electrical junction boxes.
Wire: THHN, TFFN or THWN, 18 AWG: Red, White, &
Black or Alpha Cable # 58113, 0.131 O.D. – 1,500 feet (457 meters) maximum length. Alpha cable #58113 (INCON P / N 600-0063) must be used when using nonmetallic (PVC) conduit.
Slip joint pliers to seat the no-strip, self-sealing wire
connectors (connectors included with the sensor).
Thread UL approved sealant or pipe dope as required
for installation in UST interstitial areas (Figure 2).
2
The TSP-DIS sensor is enhanced with conductivity sensors and a small microprocessor which allows it to discriminate between water and product. The TSP-DIS also communicates its identication code and current detection status to the ATG console (water present, product present, or normal – no liquids detected).
Both sensors are supplied with no-strip electrical wire connectors, 25 feet of cable, a Model ID tag, and a cord­grip tting for connection to a weatherproof electrical junction box (see diagrams).
Testing the Sensors
Dip the tip of the sensor in a clean cup of water – a standard sensor alarm is generated for a TSP-EIS sensor and a water alarm is generated for the TSP-DIS sensor. When dipped in isopropyl alcohol, the TSP-DIS sensor will produce a product alarm.
Test sensors on a yearly basis, or more frequently — per local code.
Materials Required
Optional – TSP-DB1 Epoxy Seal kit for no-strip electrical
connectors – recommended for sites: within ood zones, high groundwater tables, with poor drainage, or when Junction Boxes are not used.
1/2 or 3/4 inch NPT (National Pipe Thread, tapered),
Rigid Metal Conduit (RMC) or nonmetallic (PVC) conduit if allowed by local codes.
Figure 2: Installation in Double-Walled Fiberglass Tanks
* TSP-KI2 Riser Cap for 2-inch riser pipes, includes a
pre-installed 1/2 inch NPT compression gland (cord grip) tting. Other riser caps are available for different riser pipe sizes – consult your factory rep.
* Riser pipe – 2 inch diameter (OD), threaded at one
end (NPT-14) with all rough edges removed / deburred from the inner edges.