Flowserve ESP3 User Manual

Automax Valve Automation Systems
3-Position Control/Dribble Control
Installation, Operation and Maintenance Instructions
Flowserve Corporation 765 South 100 East Phone: 801 373 3028 Flow Control Division Provo, Utah 84606 Facsimile: 801 489 2228 Automation Business Unit www.flowserve.com Email: actuators@flowserve.com
SR Limit Switch Method
ESP3 Electronic Servo Positioner
Automax electric actuators with servo control are factory adjusted for 90 degree operation and shipped in the full clockwise (CW) position as viewed from the motor side.
WARNING (SEE NOTE 6 ON PAGE 4)
DO NOT CONNECT SHORT CIRCUIT TO MOTOR LEADS WHILE MOTOR IS CONNECTED TO ESP3 - SERIOUS DAMAGE WILL RESULT AND WARRANTY VOIDED.
Specifications
Power 110-125V, 50/60 Hz Requirement* 5W @ 115 VAC Temperature** -40°F (-40°C) to 160°F (70°C) Approvals UL recognized
CSA certified
Range Of 30° to 180° rotational span Adjustability
* Options availability for 240 VAC or 12/24 VDC applications. ** Options available for high humidity/outdoor use.
Servo Control Input Options
1. Connect input signal to TB1 terminals marked +IN and
-IN (4-20mA configuration is supplied as standard).
Type of Input
RESISTIVE VOLTAGE CURRENT
© 2001, Flowserve Corporation, Provo, Utah
Signal Board Adjustment
4 to 20 mAdc Input Jumper JP1 to the left 1 to 5 mAdc Input Jumper JP1 to the right 10 to 50 mAdc Requires special board.
Consult factory. 0 to 5 Vdc Input Jumper Removed 2 to 10 Vdc Input Jumper Removed 1 to 10 Vdc Input Jumper Removed
1.5 to 135 Ohm Requires special board.
Consult factory.
1.5 to 1000 Ohm Input Jumper Removed
(see notes on p.2) (250 Ohm Shunt)
Direct or Reverse Acting
Make sure valve and actuator rotate in the same direction and are in the same position, i.e. valve full CW, actuator full CW.
1. Standard units are direct acting: Low input (e.g. 4 mA) = CW
High input (e.g. 20 mA) = CCW
2. To make reverse acting, place jumpers JP2 and JP3 to ‘R’
positions on ESP3 and proceed with Valve Alignment and Servo Calibration. For reverse action with ESP3 Transmitter, see notes on page 2.
Valve Alignment and Servo Calibration
Note:
Standard units are calibrated for 0 to 90 degree operation.
Units may be recalibrated for 180 degree operation.
1. Connect 115Vac/60hz power to terminals marked L1, N, and
GND. Power should be fused with an in-line 5 amp slow­blow fuse. ESP3 may be run on 50hz, but actuator may be affected. See specific actuator I.O.M.
2. Safety overtravel switches disconnect the motor if the
actuator overtravels approximately 5 degrees past the full CW or CCW position. On valves with mechanical stops, the safety overtravel switches need to be set so that the motor will not disconnect prior to hitting a mechanical valve stop. See notes 3 and 6 under “Trouble Shooting” on page 4 before adjustment.
3. Minimum Position Adjustment:
For Direct Acting: Apply minimum input signal to
ESP3 terminals +IN and -IN and adjust zero ‘Z’ potentiometer until actuator stops at full CW position and CW LED turns off. Turn the ‘Z’ adjustment CW to move actuator CW.
For Reverse Acting: Apply minimum input signal to
ESP3 terminals +IN and -IN and adjust zero ‘Z’ potentiometer until actuator stops at full CCW position and CCW LED turns off. Turn the ‘Z’ potentiometer CCW to move actuator CW.
4. The voltage at test point ‘A’ referenced to test point ‘G’
should be approximately 0.75 Vdc. If not, see note #4 under “Trouble Shooting”.
5. Maximum Position Adjustment:
For Direct Acting: Apply maximum input signal to
ESP3 and adjust span ‘S’ potentiometer until actuator stops at full CCW position and CCW LED turns off.
For Reverse Acting: Apply maximum input signal to
ESP3 and adjust span ‘S’ potentiometer until actuator stops at full CCW position and CCW LED turns off.
6. Due to Zero-Span interaction, repeat steps 3 and 5 until
actuator positions repeat at both ends of travel (usually 2 to 3 times).
Page 1 of 4
Automax Valve Automation Systems
3-Position Control/Dribble Control
Installation, Operation and Maintenance Instructions
Flowserve Corporation 765 South 100 East Phone: 801 373 3028 Flow Control Division Provo, Utah 84606 Facsimile: 801 489 2228 Automation Business Unit www.flowserve.com Email: actuators@flowserve.com
SR Limit Switch Method
Resistive Inputs (optional)
3 wire: Clockwise rotation of input potentiometer increases signal
(increase resistance). Connect potentiometer’s clockwise lead to terminal marked IS. Connect counter-clockwise lead to terminal marked -IN. Connect potentiometer’s wiper lead to terminal marked +IN. Remove JP1 input select jumper.
Note:
If clockwise rotation of potentiometer does not rotate actuator
in an increasing signal direction, reverse potentiometer leg leads.
RESISTIVE INPUT CONFIGURATIONS
Heater & Thermostat (optional)
1. 115 Vac heater and thermostat are connected to TB1 terminals L1 and N on the ESP3 servo board (see Wiring Diagram on page 3).
ESP3 Transmitter (optional)
Note:
If the ESP3 Transmitter is used, the servo calibration (p.1) must be completed with the 4-20mA transmitter installed Servo calibration should be performed before transmitter calibration.
1. Connect 4-20mAdc output leads to transmitter
terminals marked ‘+’ and ‘-’.
2. Place transmitter JP1 jumpers to positions 1-3 and 2-4
for 90 degree operation,or positions 1-2 and 3-4 for actuators calibrated for 180 degree operation.
3. Drive actuator to the full CCW position and adjust ‘S’
span adjustment for 20mA output.
4. Drive actuator to the CW position and adjust ‘Z’ zero
adjustment for 4mA output.
5. Repeat steps 3 and 4 until the desired output is achieved
in both positions.
6. Standard ESP3 transmitters are direct acting. A low
output signal indicates CW position and high output signal indicates CCW position. For reverse acting see below.
7. The transmitter is self powered and optically isolated
from the AC motor drive circuits.
Important Notes About Reverse Acting ESP3 with Transmitter
Note:
Reverse acting transmitter means a 4mA output for full
CCW, and a 20mA output for full CW position.
1. The BLUE and GREEN feedback potentiometer wires have been reversed on TB1 (see chart below).
2. The feedback potentiometer voltages as measured from test points ‘A’ to ‘G’ on the ESP3 card are as follows:
CCW ~ 0 .75 Vdc CW ~ 4.70 Vdc
3. JP2 and JP3 (Direct / Reverse acting jumpers) are to be on
‘D’ Direct (left two posts).
4. The RED and BLACK motor drive leads on TB2 have been reversed (see chart below).
5. The drive LED’s will now indicate the opposite of the actual drive travel.
Wire Transmitter Transmitter
BLUE (Feedback Pot.) P1 P3 GREEN (Feedback Pot.) P3 P1 RED (Motor Drive) CW CCW
BLACK (Motor Drive) CCW CW
Reverse Standard Position Position
Performance Data (Centura/ESP3)
CE2ATA CE4ATA CE7ATA CE1ATA LINEARITY +/-1% +/-1% +/-1% +/-1% RESOLUTION 2.0° 1.8° 1.8° 1.5° DEADBAND +/-0.8% +/-0.7% +/-0.5% +/-0.3% HYSTERESIS +/-1.0% +/-0.8% +/-0.5% +/-0.5%
ACTUATOR ANGLE FEEDBACK VOLTAGE
(DEGREES) OF POTENTIOMETER
-5° PAST CW ~0.53 VOLTS 0° CW POS. ~0.75 VOLTS
90° CCW POS. ~4.70 VOLTS
(TPA TO TPG)
© 2001, Flowserve Corporation, Provo, Utah
ESP3 FEEDBACK POTENTIOMETER
Page 2 of 4
Loading...
+ 2 hidden pages