Fisher IM Suppplement: Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor Manuals & Guides

Instruction Manual Supplement
D103263X102
FIELDVUE Instruments
October 2018
Using FIELDVUE™ Instruments with the Smart
®
HART
Fisher™ FIELDVUE instruments can be used in conjunction with a HART interface module, such as the Smart HART Loop Interface and Monitor (HIM) from Moore Industries, to provide additional diagnostic coverage to non-HART hosts. Installed transparently across the 4‐20 mA instrument loop, the HIM receives the HART digital process data and converts the digital information into up to three scalable, isolated analog (4‐20 mA) process signals and two relay outputs that are readily accepted by an existing control system, such as a DCS or PLC. For additional information on the HIM, refer to Smart HART Loop Interface and Monitor documentation www.miinet.com.
The relay outputs are configurable within the HIM and can be used to indicate instrument status and detailed alert information. For example, when a DVC6200 SIS digital valve controller in a Safety Instrumented System (SIS) application instructs the safety valve to move during the partial stroke test, the HART interface module receives the digital signal representing valve position. The HIM reads this signal, and, depending on the Fail Safe mode, energizes a relay at a configured trip point (such as 90%). The relay output is sent to the control system verifying the desired position has been achieved.
When the digital valve controller instructs the valve to return to the open position, the HIM energizes a second relay when the valve is fully open. This allows the control system to verify and report that the valve is fully reopened and the test is complete. Depending on how the HIM is wired to the control system, the relay outputs may be normally open (NO) or normally closed (NC) contacts. In this example, the relay outputs are configurable in the HIM, and do not reflect the status byte configuration in the FIELDVUE instrument.
Loop Interface and Monitor (HIM)
or the Moore Industries web site at
Figure 1. Moore Industries HART Loop Monitor
www.Fisher.com
FIELDVUE Instruments
October 2018
Instruction Manual Supplement
D103263X102
Additionally, the discrete relay output could also be used for various other alerts generated by the DVC6200 SIS, such as “Diagnostics in Progress, “Valve Stuck Alert” etc.
The HIM operates from an external 24 volts DC ± 10% voltage source and connects to the 4‐20 mA control signal lines.
The HIM requests information from the FIELDVUE instrument. The FIELDVUE instrument responds by sending the appropriate data. Figure 2 shows a typical installation of a FIELDVUE instrument with the HIM. The HIM is not recommended for FIELDVUE instrument applications involving split ranging.
Figure 2. FIELDVUE DVC6200 SIS Digital Valve Controller Installed with a Moore Industries HART Loop Monitor
X0079
FIELDVUE DVC6200 SIS
Digital Valve Controller
HART Digital Communication
Smart HART Loop
Interface and Monitor
4‐20 mA Valve Control Signal
with Superimposed HART Digital Signal
Valve 90% Open
Relay #1
Relay #2
Valve Full Open
Valve Travel
Output Pressure
4-20 mA
4-20 mA
Control System
Installation Considerations
The HIM design allows two different DIN‐rail mounting options:
D 32mm (EN50035) G rail
D 35mm (EN50022) top hat rail
The HIM dimensions are shown in figure 3.
2
Instruction Manual Supplement
D103263X102
Figure 3. HIM HART Loop Monitor Dimensions
65 mm
(2.56 in)
100 mm (3.94 in)
FIELDVUE Instruments
October 2018
130 mm
(5.1 in)
118 mm
(4.7 in)
Figure 4 shows the proper installation of a FIELDVUE digital valve controller with the HIM. The schematic depicts a Fisher HF340 HART filter in the loop when the digital valve controller is operating with a 4‐20 mA control signal. If the digital valve controller is operating from a 24 volt DC source, a Fisher LC340 line conditioner is substituted for the HART filter. The necessity of a HART filter for 4‐20 mA operation depends upon the control system; the HIM does not add a requirement for a filter. Refer to the appropriate FIELDVUE instrument quick start guide or instruction manual for detailed installation instructions. For instructions on installing the HART filter, refer to instruction manual
D102796X012
. For instructions on installing the LC340 line conditioner, refer to instruction manual D102797X012.
See Related Fisher Documents on page 13.
In addition to performing the designed function, the filter or line conditioner also provides a convenient method for connecting field wiring between the control system, the signal converter, and the FIELDVUE instrument. If no filter or conditioner is required, the HF341 communication tap is available. This device provides the connection convenience but without filter action (straight‐through). When a DLC3010 digital level controller is used with the HIM, a HART filter or line conditioner is not required (see figure 5). However, the HF341 communication tap may be used for connection convenience.
3
FIELDVUE Instruments
October 2018
Instruction Manual Supplement
D103263X102
Figure 4. Example HIM Smart HART Loop Interface and Monitor Installation with a FIELDVUE Digital Valve Controller
HAZARDOUS AREA NON‐HAZARDOUS AREA
FISHER HF340 HART FILTER OR LC340 LINE CONDITIONER
+
-
FIELDVUE DIGITAL
VALVE CONTROLLER
INTRINSIC SAFETY BARRIER IF REQUIRED BY APPLICATION
+
-
4-20 mA
+ HART
HART LOOP INTERFACE AND MONITOR (HIM)
COMMFLD
SYS
-
ANALOG OUTPUT
+
+INB
+OUT
INB
OUT
99.999 PERC
+
ANALOG OUTPUT TO FIELDVUE INSTRUMENT
-
CONTROLLER ANALOG INPUT CHANNEL
CONTROLLER DISCRETE INPUT CHANNEL
CONTROL ROOM
NOTE: REFER TO SMART HART LOOP INTERFACE AND MONITOR USERS' MANUAL
224‐778‐00
WIRING INFORMATION.
AVAILABLE FROM MOORE INDUSTRIES FOR MORE DETAILED
DISCRETE
OUTPUT
24 VDC POWER
Figure 5. Example HIM Smart HART Loop Interface and Monitor Installation with a FIELDVUE Digital Level Controller
HAZARDOUS AREA NON‐HAZARDOUS AREA
ANALOG INPUT CHANNEL FOR PRIMARY VARIABLE (PV) FROM FIELDVUE INSTRUMENT)
+
-
+
FIELDVUE DIGITAL LEVEL CONTROLLER
SENSE RESISTOR
-
INTRINSIC SAFETY BARRIER IF REQUIRED BY APPLICATION
4-20 mA
+ HART
IN
-
+
OUTPUT
IN
+
ANALOG
(230 TO 600 OHMS)
CONTROLLER ANALOG INPUT CHANNEL
CONTROLLER DISCRETE INPUT CHANNEL
8.6
HART LOOP INTERFACE
IN
CONTROL ROOM
AND MONITOR (HIM)
NOTE: REFER TO SMART HART LOOP INTERFACE AND MONITOR USERS' MANUAL
224‐778‐00
WIRING INFORMATION.
IN ORDER TO MEET THE HART LOOP IMPEDANCE REQUIREMENT, THERE MUST BE BETWEEN 230 AND 600 OHMS IN SERIES WITH THE VOLTAGE SOURCE.
AVAILABLE FROM MOORE INDUSTRIES FOR MORE DETAILED
4
DISCRETE
OUTPUT
24 VDC POWER
Instruction Manual Supplement
D103263X102
FIELDVUE Instruments
October 2018
HIM Configuration
The HIM Operating Parameters can be configured using HIM PC Configuration Software. The software is composed of the following sections as shown in figure 6.
1. HIM Status and Information Section The left side of the screen includes seven boxes that display the different
settings of the attached HIM.
Program Status—Displays the activity of the connected HIM. It indicates if the unit is Idle, Uploading, Downloading, Monitoring or Searching.
HIM Device Info—Displays the individual characteristics of the attached HIM, such as its identity, hardware and software revisions, and the last date that the device was configured.
HIM Tag—A phrase used to identify the HIM.
HIM Device Status—Displays functioning of the HIM. OK is displayed if it is operating normally, otherwise an error
message is displayed.
HIM Displayed Data—This shows what appears on the display at the front of the HIM. This information is programmed on the Display page.
Progress—This bar stays in motion any time the HIM is monitoring, uploading or downloading.
Communication Status—Monitors the PC software's ability to communicate with the HIM.
Figure 6. The HART Menu Sets the HART Communications Parameters Using the HIM PC Configuration Software
5
Loading...
+ 9 hidden pages