Fire-Lite MS-9050UD User Manual

PN: 52413:B ECN 07-494
Addressable Fire Alarm Control Panel
MS-9050UD
IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
Document #52413 8/29/07 Revision:
B
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise follow­ing the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These docu­ments can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Manage­ment Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens­ing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flam­ing fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.). Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com­prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis­sion systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the require­ments of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso­ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room tempera­ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Table of Contents
Table of Content s
SECTION 1: Product Description .........................................................................................................................12
1.1: Features and Options...................................................................................................................................12
1.2: Specifications ..............................................................................................................................................13
1.2.1: Current Availability...........................................................................................................................14
1.3: Controls and Indicators........................................................................................... .....................................14
1.4: Circuits ........................................................................................................................................................15
1.5: Digital Alarm Communicator/Transmitter..................................................................................................16
1.6: Components.................................................................................................................................................17
1.6.1: Intelligent Addressable Detectors: Newer Series..............................................................................17
1.6.2: Intelligent Addressable Modules: Newer Series............................................................. ..................17
1.6.3: 300 Series Intelligent Addressable Devices......................................................................................17
1.6.4: Device Accessories ...........................................................................................................................17
1.7: Optional Modules........................................................................................................................................18
1.8: Accessories..................................................................................................................................................18
1.8.1: PK-CD Programming Utility ............................................................................................................18
1.8.2: Dress Panel........................................................................................................................................18
1.8.3: Trim Ring..........................................................................................................................................18
1.9: ANN-BUS Devices .....................................................................................................................................19
1.9.1: ANN-BUS Wiring.............................................................................................................................19
1.9.1.1 Calculating Wiring Distance for ANN-BUS Modules ............................................................ 19
1.9.1.2 Wiring Configuration ..............................................................................................................21
1.9.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply ................................................22
1.9.2: ANN-BUS Device Addressing..........................................................................................................22
1.9.3: ANN-80 Remote Fire Annunciator...................................................................................................23
1.9.3.1 Specifications ....................................................................................... ...................................23
1.9.3.2 Installation ................................................................................. ..............................................23
1.9.3.3 Mounting .......................................................................................................... .......................23
1.9.3.4 Opening/Closing Annunciator .......................................................................................... ......23
1.9.3.5 Wiring ANN-80 to FACP ................................................................................... ....................24
1.9.4: ANN-S/PG Serial/Parallel Interface Module....................................................................................26
1.9.4.1 Specifications ....................................................................................... ...................................26
1.9.4.2 PRN 6 Printer Installation .......................................................................................................26
1.9.4.2.1 Connecting PRN 6 Printer ....................................................................................................27
1.9.4.2.2 Setting Printer Options .........................................................................................................27
1.9.5: ANN-I/O LED Driver Module..........................................................................................................28
1.9.5.1 ANN-I/O Board Layout ................................................................................ ..........................28
1.9.5.2 Specifications ....................................................................................... ...................................28
1.9.5.3 ANN-I/O Connection to FACP ...............................................................................................29
1.9.5.4 ANN-I/O Module LED Wiring ...............................................................................................30
1.9.6: ANN-LED Annunciator Module.......................................................................................................31
1.9.6.1 ANN-LED Board Layout ........................................................................................................31
1.9.6.2 Specifications ....................................................................................... ...................................31
1.9.6.3 ANN-LED Connection to FACP ............................................................................................32
1.9.7: ANN-RLY Relay Module..................................................................................................................33
1.9.7.1 ANN-RLY Board Layout ........................................................................................................33
1.9.7.2 Specifications ....................................................................................... ...................................33
1.9.7.3 Mounting/Installation .......................................... ..................................................... ............... 33
1.9.7.4 ANN-RLY Connection to FACP ............................................................................................34
1.10: Getting Started...........................................................................................................................................34
1.11: Telephone Requirements and Warnings....................................................................................................35
1.11.1: Telephone Circuitry.........................................................................................................................35
1.11.2: Digital Communicator.....................................................................................................................35
1.11.3: Telephone Company Rights and Warnings .....................................................................................36
1.11.4: For Canadian Applications..............................................................................................................37
SECTION 2: Installation ........................................................................................................................................38
4
MS-9050UD P/N: 52413:B 8/29/07
Table of Contents
2.1: Mounting Backbox............................................... ...................................................... ................................. 38
2.2: Mounting Chassis/Transformer/Main Circuit Board...................................................................................39
2.3: Power...........................................................................................................................................................42
2.3.1: AC Power and Earth Ground Connection.........................................................................................42
2.3.2: Battery Power....................................................................................................................................42
2.4: Relays.............................................................................................................. ............................................43
2.5: Notification Appliance Circuits ..................................................................................................................43
2.5.1: Configuring NACs........................................................................................... .................................44
2.6: UL Power-limited Wiring Requirements....................................................................................................45
2.7: Digital Communicator.................................................................................................................................46
2.8: Optional Modules/Accessories Installation.................................................................................................47
2.8.1: 4XTMF Transmitter Module Installation..........................................................................................47
SECTION 3: Programming ..................................................................................................... ..............................50
3.1: Programming Data Entry ............................................................................................................................50
3.2: User Programming ............................ ..................................................... .....................................................51
3.3: Initial Power-up...................................................................................... .....................................................52
3.4: Programming Screens Description..............................................................................................................52
3.5: Programming and Passwords ......................................................................................................................52
3.6: Master Programming Level............................................................ .............................................................54
3.6.1: Autoprogram......................................... ..................................................... .......................................55
3.6.2: Point Program........................................................................................ ............................................56
3.6.2.1 Detector Programming ............................................................................................................56
3.6.2.1.1 Add Detector ........................................................................................................................56
3.6.2.1.2 Delete Detector ....................................................................................................................57
3.6.2.1.3 Edit Detector ........................................................................................................................57
3.6.2.2 Module Programming .............................................................................................................66
3.6.2.2.1 Add Module .........................................................................................................................66
3.6.2.2.2 Delete Module ......................................................................................................................67
3.6.2.2.3 Edit Module Screen for Monitor Module ............................................................................67
3.6.2.2.4 Edit Module Screen for Control Modules ............................................................................76
3.6.3: Zone Setup ........................................................................................................................................83
3.6.3.1 Enable ......................................................................................................................................83
3.6.3.2 Disable ....................................................................................................................................84
3.6.3.3 Zone 17, 18 and 19 ..................................................................................................................84
3.6.3.4 Zones Installed ........................................................................................................................85
3.6.3.5 Zones Enabled .........................................................................................................................85
3.6.3.6 Zones Disabled ........................................................................................................................85
3.6.3.7 Zone Type ...............................................................................................................................85
3.6.3.8 Zones Available ......................................................................................................................87
3.6.4: Loop Setup...................................... ...................................................... ............................................87
3.6.4.1 Style ........................................................................................................................................87
3.6.4.2 Loop Protocol .........................................................................................................
.................87
3.6.5: System Setup................................ ...................................................... ...............................................88
3.6.5.1 Trouble Reminder ...................................................................................................................89
3.6.5.2 Banner .....................................................................................................................................89
3.6.5.3 Time-Date ...............................................................................................................................90
3.6.5.3.1 Time .....................................................................................................................................90
3.6.5.3.2 Date ......................................................................................................................................91
3.6.5.3.3 Clock Format ........................................................................................................................91
3.6.5.3.4 Daylight Savings Time .........................................................................................................91
3.6.5.4 Timers .....................................................................................................................................92
3.6.5.4.1 PAS (Positive Alarm Sequence) Delay ................................................................................92
3.6.5.4.2 Pre-signal Delay ...................................................................................................................93
3.6.5.4.3 Waterflow Delay ..................................................................................................................93
3.6.5.4.4 AC Loss Delay .....................................................................................................................94
MS-9050UD P/N: 52413:B 8/29/07 5
Table of Contents
3.6.5.5 NAC (Notification Appliance Circuit) ....................................................................................94
3.6.5.5.1 Enabled ....................................................................................................... ..........................95
3.6.5.5.2 Type ........................................................................................ ..............................................96
3.6.5.5.3 Silenceable ...........................................................................................................................96
3.6.5.5.4 Auto Silence .........................................................................................................................97
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type) .........................................97
3.6.5.5.6 Zone ........................................................................................ ..............................................99
3.6.5.5.7 Silence Inhibited ......................................................................................... ..........................99
3.6.5.5.8 Sync Type ..................................... ........................................................................................99
3.6.5.6 Relays .............................................................................................. ........................................100
3.6.5.7 Canadian Option ............................................................................................ ..........................101
3.6.5.8 Waterflow Silenceable ............................................................................................................101
3.6.6: Verify Loop .......................................................................................................................................101
3.6.7: History...............................................................................................................................................102
3.6.7.1 View Events ........................................................................................................ ....................102
3.6.7.2 Erase History ........................................................................................... ................................102
3.6.8: Walktest.............................................................................................................................................103
3.6.9: Option Modules................................................................................................................................104
3.6.9.1 ANN-BUS ........................................................................................................... ....................104
3.6.9.1.1 ANN-BUS Enabled ............................................................................................ ..................104
3.6.9.1.2 Modules Installed .................................................. ...............................................................105
3.6.9.1.3 Auto-Configure .................................................................................................. .................. 115
3.6.9.1.4 ANN-S/PG (Print) Options Screen ......................................................................................115
3.6.9.1.5 ANN-80 Options Screen ......................................................................................................116
3.6.9.2 Onboard DACT ............................................................................................. ..........................117
3.6.9.2.1 Onboard DACT Enable ........................................................................................................117
3.6.9.2.2 Primary Phone ............................................................................................... .......................117
3.6.9.2.3 Secondary Phone ................................................................................................ ..................118
3.6.9.2.4 Service Terminal ........................................................................................ ..........................118
3.6.9.2.5 Central Station ......................................................................................................................121
3.6.9.2.6 Trouble Call Limit (Dialer Runaway Prevention) ...............................................................122
3.6.9.2.7 Manual Dial Mode ...............................................................................................................134
3.6.10: Password Change ............................................................................................................................135
3.6.11: Clear Program..................................................................................................................................136
3.6.12: Program Check................................................................................................................................137
3.7: Maintenance Programming Level ...............................................................................................................139
3.7.1: Disable Point.....................................................................................................................................140
3.7.2: History...............................................................................................................................................141
3.7.3: Program Check..................................................................................................................................142
3.7.4: Walktest.............................................................................................................................................143
3.7.5: System...............................................................................................................................................143
3.7.6: Zone Setup.........................................................................................................................................145
SECTION 4: Operating Instructions ....................................................................................................................147
4.1: Panel Control Buttons..................................................................................................................................147
4.1.1: Acknowledge/Step.............................................................................................................................147
4.1.2: Alarm Silence....................................................................................................................................147
4.1.3: Drill/Hold 2 Sec ................................................................................................................................147
4.1.4: Reset..................................................................................................................................................147
4.2: Status Indicators and LEDs.........................................................................................................................148
4.3: Normal Operation........................................................................................................................................149
4.4: Trouble Operation........................................................................................................................................149
4.5: Alarm Operation..........................................................................................................................................151
4.6: Supervisory Operation.................................................................................................................................152
4.7: Process Monitor Operation..........................................................................................................................153
4.8: Hazard/Tornado Condition Operation .........................................................................................................153
6
MS-9050UD P/N: 52413:B 8/29/07
Table of Contents
4.9: Medical Alert Condition Operation.............................................................................................................153
4.10: NAC Operation .........................................................................................................................................153
4.11: Programmed Zone Operation....................................................................................................................154
4.12: Disable/Enable Operation .........................................................................................................................154
4.13: Waterflow Circuits Operation ...................................................................................................................154
4.14: Detector Functions ....................................................................................................................................154
4.15: Time Functions: Real-Time Clock ............................................................................................................154
4.16: Synchronized NAC Operation ..................................................................................................................155
4.17: Coded Operation .......................................................................................................................................155
4.18: Presignal....................................................................................................................................................155
4.19: Positive Alarm Sequence ..........................................................................................................................156
4.20: Special System Timers..............................................................................................................................157
4.20.1: Silence Inhibit Timer.......................................................................................................................157
4.20.2: Autosilence Timer............................ ..................................................... ..........................................157
4.20.3: Trouble Reminder ....................................................................................................... ....................157
4.20.4: Waterflow Retard Timer..................................................................................................................157
4.20.5: Alarm Verification (None or One Minute)......................................................................................158
4.21: Walktest.....................................................................................................................................................158
4.22: Read Status................................................................................................................................................159
4.22.1: System Point ....................................... ............................................................................................160
4.22.2: Zones.......................................... ...................................................... ...............................................161
4.22.3: Power............................ ...................................................... .............................................................162
4.22.4: Trouble Reminder ....................................................................................................... ....................163
4.22.5: Timers............. ...................................................... ...........................................................................163
4.22.6: NAC ................................................................................................................................................164
4.22.7: Relays.............................. ...................................................... ..........................................................164
4.22.8: Program Check................................................................................................................................165
4.22.9: History......................................................................................................... ....................................165
4.22.10: ANN-BUS.....................................................................................................................................166
4.22.11: Phone Line.....................................................................................................................................167
4.22.12: Central Station...............................................................................................................................167
4.22.13: Service Terminal ...........................................................................................................................168
4.22.14: Print...............................................................................................................................................169
4.22.15: Time-Date......................................................................................................................................171
SECTION 5: Central Station Communications ..................................................................................................172
5.1: Transmittal Priorities.................................... ..................................................... ..........................................175
SECTION 6: Local/Remote Site Upload/Download ............................................................................................177
6.1: Remote Download.................................. ...................................................... ...............................................177
6.2: Transferring a Program........................... .....................................................................................................178
6.3: Security Features.........................................................................................................................................179
SECTION 7: Power Supply Calculations .............................................................................................................180
7.1: Overview..................................... ...................................................... ..........................................................180
7.2: Calculating the AC Branch Circuit .............................................................................................................180
7.3: Calculating the System Current Draw............................................................. ............................................181
7.3.1: Overview............................................... ..................................................... .......................................181
7.3.2: How to Use Table 7.3 on page 182 to Calculate System Current Draw ...........................................181
7.4: Calculating the Battery Size..............................................................................................
..........................183
7.4.1: NFPA Battery Requirements................................................ .............................................................183
7.4.2: Selecting and Locating Batteries.......................................................................................................183
APPENDIX A: Software Zones ............................................................................................................................184
A.1: Correlations ...............................................................................................................................................184
APPENDIX B: Default Programming .................................................................................................................189
APPENDIX C: NFPA Standard-Specific Requirements ...................................................................................190
MS-9050UD P/N: 52413:B 8/29/07 7
Table of Contents
C.1: Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts ...........................................................................................................194
C.2: MBT-1 Municipal Box Trip - Silenceable .................................................................................................195
APPENDIX D: FACP with Keltron .....................................................................................................................196
APPENDIX E: Wire Requirements .................................................................................. ...................................197
APPENDIX F: HVAC Control ........................................................................................ .....................................198
F.1: Control Module Operation .........................................................................................................................198
F.1.1: HVAC SHUTDN .............................................................................................................................198
F.2: Monitor Module Operation ........................................................................................................................198
F.2.1: HVAC RESTART ............................................................................................................................198
F.2.2: HVAC OVRRIDE ............................................................................................................................199
APPENDIX G: Ademco Contact ID Format
Event Code Descriptions ...............................................................................................................200
G.1: Transmission Format Between DACT and Receiver ................................................................................200
G.2: Ademco Contact ID Typical Printout ........................................................................................................200
8
MS-9050UD P/N: 52413:B 8/29/07
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and System
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 SLC Wiring Manual Document #51309
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9050UD PN 52413:B 8/29/07 9
9050udlayo90.cdr
Black
Red
Green
EIA-232 to
personal computer
2 Programmable Relays &
White
(Nonsupervised,
Upload/Download Utility.
personal computer with FACP
Power-limited (Class 2) Circuit)
50 foot maximum within same room.
1 Fixed Trouble Relay
Nonsupervised Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Conta c ts shown below in normal
9 8 7 6
DB9F
5 4 3 2 1
NC NO C
A Fail Safe Trouble
relay switches to the
NO position du r i n g
trouble co nd itions and
conditi on (AC power with no al ar m ,
trouble or supervisory activity).
under loss of all power.
(* )Factory default relay programming
N
G DTR X
M
R
C
Supervisory*
Alarm* Trouble
8
D
7 6
T
5
V
RCV XMT DTR GND
PWR
ANN-BUS
C NC
NO NC C
NONC
NO
NC NO C
NC
CC
NO NC C
NO
J5
J4
Remove this jumper to enable
Supervisory relay wh en
4XTMF module is installed
TB7 TB3
JP2
TB6
Cut JP28 to
supervise
4XTMF
JP1
JP28
TB5
J11
SW1
TROUBLE
FIRE ALARM
Basic System Connections
6
BA
AB
5
A
SHIELD
4
A
-
3
B
-
SLC
+
2 1
B
SLC Loop
Manual for detailed
Refer to the SLC Wiring
Supervised Ci rcuit)
for Style 4, 6 and 7.
addressable devices
information on wiring
(Power- Limit ed, Clas s 2
+
B+ A+ B- A-
4XTMF
TB2
LCD DISPLAY
J9
J3
J8
AC POWER
KISSOFF
ALARM
ST
1
DEF
3
ABC
2 1
LED1
LED2
LED3
CLEAR
6
JKL
5
GHI
4
ENTER
DRILL
ESC
MODE
_/.
#
89
QZ_
PRS TUV
7
PH2
DACT Phone
Line Jacks
(nonpower-limited,
supervised)
PH1
J6
RESET
PS2 Keyboard Interface
0
*
B
-
78
A
+
NAC #2
+
Special Application Power
NAC #1
+
+
+
+
-
A
+
NAC2
56
B
+
4
B
-
A
-
23
A
+
NAC1
1
B
+
B+ B- B-B+A+ A- A+ A-
-
TB1
Charger Enable/Disable
Switch (shown in charger
enable position)
SW27
+
_
J1
BATTERY
Battery
24 VDC, nonpowe r - l im it e d,
supervised, 18 Amp Hour max.
J2
Notification Appliance Circuits
ELR 4.7K, ½W
2.5 amps m a x. per circuit . Tota l available current 2.5 amps. Connector
Supervised
NAC #2 Shown Style Z (Class A) (Power-Limit ed, Class 2, Su pervised)
NAC #1 Shown Style Y (Class B) (Power-Limited, Class 2, Supervised)
For specific UL wiring
information, refer to "UL
Power-limited Wiring
Requirements" on page 45
Transformer
CAUTION!
HIGH VOLTAGE
Nonpower-limited,
10 MS-9050UD PN 52413:B 8/29/07
Peripheral Devices
ANN-BUS
ANN-80
Text Annunciator
Doc. #52749
SLC Loop
ANN-I/O
LED Driver
Doc. #151416
ANN-RLY
10 Form-C Relay Card
Doc. #53033
4XTMF
Municipal Box Transmitter
Addressable Devices and SLC Wiring
ANN-S/PG
Printer Driver
Doc. #151417
ANN-(R)LED
LED Display
Doc. #53032
Doc. #51309
Battery Connector
CHG-120F Charger
Doc. #50888
RS-232
Local PC
9050UDperi.cdr
CHG-75 Charger
Doc. #51315
MS-9050UD PN 52413:B 8/29/07 11
Product Description Features and Options
SECTION 1 Product Description
The MS-9050UDis a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features. The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9050UD FACP, offer the latest in fire protection technology. The power supply and all electronics are contained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applications. Available accessories include local and remote upload/download software, remote annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PK-CD Upload/Download utility via the public switched telephone network. Any personal computer with Windows speed of 2400 baud or faster and Upload/Download software kit PK-CD, may serve as a Service T erminal. This allows download of the entire program or upload of the entire program, history file, walktest data and current status.
Inventory
When the MS-9050UD shipment is received, check to make certain that all parts have been included in the shipment. The MS-9050UD shipment should consis t of one of each of the following:
XP or newer, and compatible modem with a
main circu it board with displaychassis with transformerbackbox wit h doo rplastic bag containing screws, cables, key, etc.manual
1.1 Features and Options
Built-in DACT (Digital Alarm Communicator/Transmitter) with remote upload/download
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
50 addressable device capacity (any combination of addressable detectors and addressable control/relay/monitor modules totalling 50)
20 software zones
Two onboard NACs (Notification Appli ance Circ ui ts) which can be configured as Style Y (Class B) or Style Z (Class A) circuits
2.5 amps total power for NACs
2.7 amps total system power (includes battery charger)
Two programmable relays and one fixed trouble relay
Built-in Programmer
Telephone Line Active LEDs
Communication Confirmation (Kissoff) LED
Touchtone/Rotary di aling
EIA-232 PC interface for local upload/download
80-character LCD display (backlit)
12 MS-9050UD PN 52413:B 8/29/07
Specifications Product Description
Real-time clock/calendar with daylight savings time control
History file with 500 event capacity
Advanced fire technology features:
Automatic drift compensationMaintenance alertDetector sensitivity test capability (NFPA 72 compliant)Automa tic devi ce type-code veri ficationPoint trouble identification
Waterflow selection per module point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) per addressable detector and Pre-signal per point (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
SLC operates up to 10,000 ft. (3,000 m) with twisted, unshield ed fire wire
Compatible with Fire-Lite’ addressable devices (refer to SLC Wiring Manual)
Compatible with legacy Fire-Lite 300 Series addressable devices (refer to SLC Wiring Manual)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
Optional ANN-I/O LED Driver module
Optional ANN-S/PG printer interface module
Optional ANN-80 remote LCD annunciator
Optional ANN-LED Annunciator Module annunciates alarm, trouble and supervisory
Optional ANN-RLED Annunciator Module annunciates alarms only
Optional ANN-RLY Form-C Relay Module
Optional Dress Panels (DP-51050)
1.2 Specifications
Refer to Illustration on page 10 for terminal locations and connections.
AC Power - Transformer Connection
MS-9050UD: 120 VAC, 60 Hz, 3.0 amps Wire size: minimum 14 AWG (2.00 mm Nonpower-limited, supervised
Battery (Lead Acid Only) - J1
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.2 amp Maximum Battery Charger Capacity: 18 Amp Hour, (FACP cabinet holds maximum of two 18 Amp Hour batteries) Minimum Battery: 7 Amp Hour Nonpower-limited, supervised
MS-9050UD PN 52413:B 8/29/07 13
2
) with 600 V insulation
Product Description Controls and Indicators
SLC Communication Loop - TB2
24 VDC nominal, 27.6 VDC maximum Maximum length is 10,000 ft. (3,000 m) total twisted, unshielded fire wire Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB1
Terminal Block provides connections fo r two NACs, Style Y (Class B) or Style Z (Class A) Special Application power Power-limited, supervised circuitry Maximum voltage drop in wiring: 2.0 VDC Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC Refer to Fire-Lite Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays, nonpower-limited, nonsupervised Refer to Figure 2.5 on page 43 for information on power-limited relay circuit wiring
EIA-232 - TB3
EIA-232 PC applications connections: Terminal 5 (Receive), 6 (Transmit), 7 (DTR), 8 (Ground) Power-limited, supervised
ANN-BUS (EIA-485) - TB3
Annunciator connector: Terminal 1 (Ground), 2 (Power), 3 (A), 4 (B) Nominal Operating Voltage: 24 VDC Maximum Current (Terminals 1 & 2): 500 mA Power-limited, supervised
1.2.1 Current Availability
The Notification Appliance Circuits can provide 2.5 amps maximum per circuit. Total available current for the FACP is 2.7 amps.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Alarm Silenced signals (yellow)
SYSTEM ALL NORMAL 10:00A 092105
14 MS-9050UD PN 52413:B 8/29/07
Circuits Product Description
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silenced
Drill (Manual Evacuate)
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
Figure 1.1 Membrane/Display Panel
9050udkypd.cdr
1.4 Circuits
Reference
Manual
SLC Communication Loop
One SLC loop is provided on the FACP main circuit board. The SLC loop, configurable for NFPA Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and control (output device) modules. Refer to the SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
Charger
24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
Two NACs configurable for Style Y (Class B) or Style Z (Class A), are provided with various programmable features.
MS-9050UD PN 52413:B 8/29/07 15
Product Description Digital Alarm Communicator/Transmitter
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following operations:
fire alarm
silenceable alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
•AC loss
1.5 Digital Alarm Communicator/Transmitter
T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Dialing the Central Station(s) number: default is Touch-Tone
®
, programmable to rotary
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats: 12 Tone Burst types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
3 Touchtone Types
4+1 Ademco Express 4+2 Ademco Express Ademco Contact ID
16 MS-9050UD PN 52413:B 8/29/07
Components Product Description
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main circuit board. The circuit board is delivered mounted to a chassis in the MS-9050UD backbox
See Page
(refer to circuit board illustration on page 10).
Cabinet
The MS-9050UD backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel, which mounts to the inside of the cabinet (required by ULC for Canadian installations). The dress panel must be installed to meet FM requirements.
MS_9050UD.cdr
Reference
Manual
Batteries
The MS-9050UD cabinet provides space for two batteries (up to 18 Amp Hour). Batteries must be ordered separately.
Battery Cable P/N 75203
-
+
+
-
9200batt.cdr
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on addressable devices, device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector . Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel. Refer to the Fire-Lite Device Compatibility Document for a list of approved conventional detectors.
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. A blinking LED on a monitor module indicates communication between the module and the control panel. These devices can also be used when installed on older systems. Refer to the SLC Wiring Manual for information on addressable
devices. Refer to the Fire-Lite Device Compatibility Document for a list of approved conventional notification and initiating devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9050UD FACP. Refer to the SLC Wiring Manual for device information.
1.6.4 Device Accessories
End-of-Line Resistor Assembly
Refer to the SLC Wiring Manual for device information. The 47 kΩ End-of-Line Resistor assembly (P/N: R-47K) is used to supervise the MMF-300, MDF-300, MMF-301 and CMF-300 module circuits. The 3.9 kΩ End-of-Line Resistor assembly is used to supervise the MMF-302 module circuit. The End-of-Line resistors are included with each module.
MS-9050UD PN 52413:B 8/29/07 17
Product Description Optional Modules
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-wire smoke detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the ELR plate. Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control module circuit.
1.7 Optional Modules
The MS-9050UD main circuit board includes option module connectors for the followin g mo dule:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J8 and J9 which are located near the top center of the main circuit board. When the 4XTMF module is installed, Jumper JP28, on the main circuit board, must be cut to allow supervision of the module.
1.8 Accessories
1.8.1 PK-CD Programming Utility
The PK-CD Programming Utility can be used to locally or remotely program an MS-9050UD directly from most IBM compatible personal computers (PC), running Windows MS-9050UD program files can also be created and stored on the PC and then downloaded to the
control panel. The PK-CD Kit includes the MS-9050UD Windows-based Programming Utility software on CD-ROM with on-line help file. A serial cable (P/N: PRT/PK-CABLE), which must be purchased separately, is required for local connection of the PC to the RS-232 (PC/Printer) terminals at TB3 of the MS-9050UD main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "Remote Download" on page 177). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.
1.8.2 Dress Panel
An optional dress panel (DP-51050) is available for the MS-9050UD (required by ULC for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. The dress panel must be installed to meet FM requirements.
1.8.3 Trim Ring
XP (or newer).
An optional Trim Ring (TR-CE) is available for semi-flush mounting of the FACP backbox.
18 MS-9050UD PN 52413:B 8/29/07
ANN-BUS Devices Product Description
1.9 ANN-BUS Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit. Compatible devices include:
ANN-80 LCD Annunciator
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
ANN-RLED Annunciator Module (red alarm LEDs only)
ANN-RLY Relay Module
1.9.1 ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B).
1.9.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the following table:
Model Number Worst Case Current Draw
ANN-80 LCD Annunciator 0.040 amps ANN-S/PG Serial/Parallel Printer Interface Module 0.040 amps ANN-I/O LED Driver Module 0.200 amps ANN-RLY Relay Module 0.075 amps ANN-(R)LED Annunciator Module 0.068 amps
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp. If current draw exceeds 0.5 amps, refer to "Powering ANN-BUS Devices fr om Auxiliary Power Supply" on page 22.
MS-9050UD PN 52413:B 8/29/07 19
Product Description ANN-BUS Devices
After calculating the total worst case current draw, Table 1.1 specifies the maximum distance the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wi re gauges, capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case
Current Draw (amps)
0.100 1,852 ft. 4,688 ft. * 6,000 ft. *6,000 ft.
0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft.
0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft.
0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft.
0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft.
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Table 1.1 Wiring Distances
Note: The following formulas were used to generate the wire distance chart:
6.0 Volts
Maximum Resistance (Ohms) = Total Worst Case Current Draw (amps)
Maximum Wire Length (feet) = Maximum Resistance (Ohms) *500
(6,000 feet maximum) Rpu
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire Gauge Ohms per 1,000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum 24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:
Wire Gauge Maximum Wire Length
18 312 feet 16 497 feet 14 787 feet 12 1,250 feet
20 MS-9050UD PN 52413:B 8/29/07
ANN-BUS Devices Product Description
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
3 ANN-80 Remote Fire Annunciators
1 ANN-S/PG Serial/Parallel Printer Interface Module
1 ANN-I/O LED Driver Module
The total worst case current is calculated as follows:
ANN-80 Current Draw = 3 X 0.040 amps = 0.120 amps ANN-S/PG Current Draw = 1 X.0.040 amps = 0.040 amps ANN-I/O Current Draw = 1 X.0.200 amps = 0.200 amps Total Worst Case Current Draw = 0.360 amps
Using this value and referring to the Wiring Distance Table 1.1 on page 20, it can be found that the available options are:
463 feet maximum using 22 Gauge wire1,172 feet maximu m using 18 Gauge wire1,866 feet maximu m using 16 Gauge wire2,953 feet maximu m using 14 Gauge wire
1.9.1.2 Wiring Configuration
Figure 1.2 illustrates the wiring between the FACP and ANN-BUS devices.
ANN-BUS and power wiring are supervised and power-limited
ANN-BUS Device
MS-9050UD
Figure 1.2 FACP wiring to ANN-BUS Device
MS-9050UD PN 52413:B 8/29/07 21
Product Description ANN-BUS Devices
1.9.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 1.3 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANN­BUS power requirements.
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
ANN-BUS and power wiring are supervised and power-limited
-24 VDC
+24 VDC
ANN-BUS
ANN-80
MS-9050UD
FCPS-24FS6/8
Figure 1.3 Powering ANN-BUS Devices from FCPS-24FS6/8
1.9.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the F ACP. A 5-position DIP switch on each device is used to set this address. The address set for these devices must also be programmed at the FACP for the specific device (refer to the programming section titled "ANN-BUS" on page 104).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device addresses do not need to be sequential and can be set to any number between 01 and 08. Note that 00 is not a valid address. The following table shows the DIP switch setting for each address.
Address Switch 5 Switch 4 Switch 3 Switch 2 Switch 1
not valid OFF OFF OFF OFF OFF 01 OFF OFF OFF OFF ON 02 OFF OFF OFF ON OFF 03 OFF OFF OFF ON ON 04 OFF OFF ON OFF OFF 05 OFF OFF ON OFF ON 06 OFF OFF ON ON OFF 07 OFF OFF ON ON ON 08 OFF ON OFF OFF OFF
Note: Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
22 MS-9050UD PN 52413:B 8/29/07
ANN-BUS Devices Product Description
1.9.3 ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator which mimics the FACP display. It also provides system status indicators for AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and FACP is accomplished over a two wire serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, filtered, power supply.
1.9.3.1 Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal /Standby (no activity): 37.0 mATrouble: 39.0 mAAlarm: 40.0 mAAC Fail ( not backlit): 15.0 mA
For use indoors in a dry location
1.9.3.2 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the annunciator.
1.9.3.3 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box. Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and mount the annunciator in or on the wall depending on the type of installation desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator to the electrical box/wall. The cover cannot be reattached or removed after the annunciator has been mounted.
1.9.3.4 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. T o close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Annunciator cover with LCD display
Annunciator backplate
Press in latch and pull annunciator cover open
Key switch shown in ON position
MS-9050UD PN 52413:B 8/29/07 23
Product Description ANN-BUS Devices
1.9.3.5 Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator . Make certain all power has been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring chan nel and then to ANN-80 terminal block TB1
wiring channel
wires
TB1
2. Remove appropriate amount of wire insulation
3. Connect the wiring from the F ACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B). Make certain to connect A to A and B to B
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals 3 & 4. Make certain to connect A to A and B to B
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+). Make certain to observe proper polarity
6. If appropriate, connect the power wiring going to the next device to terminals 1 (-) & 2 (+). Make certain to observe proper polarity
7. After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any excess wire pushed back through hole into electrical box
24 MS-9050UD PN 52413:B 8/29/07
ANN-BUS Devices Product Description
ANN-BUS and power wiring are supervised and power-limited
ANN-80
FACP
Figure 1.4 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the MS-9050UD.
MS-9050UD (TB3) ANN-80 (TB1)
Terminal 1 GND (-) Terminal 1 (-) Terminal 2 PWR (+) Terminal 2 (+) Terminal 3 A (ANN-BUS) Terminal 3 (A) Terminal 4 B (ANN-B US) Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator must added to the system via FACP programming. Refer to the programming section titled "ANN­BUS" on page 104 in this manual for detailed programming information. Select the LCD option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the F ACP, the ANN-80 will indicate a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address corresponding to the address set on the ANN-80 at the FACP.
MS-9050UD PN 52413:B 8/29/07 25
Product Description ANN-BUS Devices
1.9.4 ANN-S/PG Serial/Parallel Interface Module
The ANN-S/PG Serial/Parallel Interface module allows the connection of a serial or parallel printer to the FACP for a real-time log of system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mounting. Proceed with the installation as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 1.5
ANN-BUS and power wiring are supervised and power-limited
ANN-S/PG Module
MS-9050UD
Parallel
Cable
Connectors for
connection to
printer
Serial
Figure 1.5 ANN-S/PG Connection to FACP
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address) to the module
4. Select the address and configuration options for the ANN-S/PG module as described in the Programming section of this manual (refer to "ANN-BUS" on page 104) Note that the Auto-configure feature allows the programmer to quickly bring all installed ANN-BUS modules online (refer to "Auto-Configure" on page 115)
5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 1.5). Only one printer can be connected.
1.9.4.1 Specifications
Operating Voltage: 24 VDC
Current (Alarm and Standby): 45 mA
o
Ambient Temperature: 32
F to 120oF (0oC to 49oC)
Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
Mounting: Surface
Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
For indoor use in a dry location only
1.9.4.2 PRN 6 Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN prints the status changes within the control panel and time-stamps the printout with the time of day and date that the event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This section contains information on connecting a printer to the control panel and setting the printer options.
26 MS-9050UD PN 52413:B 8/29/07
ANN-BUS Devices Product Description
1.9.4.2.1 Connecting PRN 6 Printer
Remote printers require a primary AC power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Since a secondary power source is not provided as a standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used. The building emergency power supply may be used, as long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25 cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB­9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the same time.
1.9.4.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN 6 printer for instructions on using the printer menu controls. Set the printer options (under the menu area) as shown in the following table:
TABLE 1-3:PRN Setup Options
Option Setting Option Setting
Font HS Draft CPI 10CPI LPI 6 LPI Skip 0.5 ESC Character ESC Emulate Epson FX-850 Bidirectional Copy ON I/O CG-TAB Graphic Buffer 40K Country E-US ASCII Serial Auto CR OFF Baud 9600 or 2400 Color Option Not Installed Format 7 Bit, Even, 1 Stop Formien Protocol XON/XOFF Lines 6LPI=60 Character Set Standard Standard Exec 10.5 SI.Zero On
Auto LF On PAPER BIN 1 12/72” BIN 2 12/72” SINGLE 12/72” PUSH TRA 12/72” PULL TRA 12/72” PAP ROLL 12/72”
MS-9050UD PN 52413:B 8/29/07 27
Product Description ANN-BUS Devices
1.9.5 ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic enclosure for mounting inside the annunciator or accessory box. The following sections describe hardware installation. Refer to the section titled "ANN-BUS" on page 104 for programming information.
1.9.5.1 ANN-I/O Board Layout
Figure 1.1 illustrates the ANN-I/O board showing locations of screw terminals for connection to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN­BUS ID number.
Terminals not used (future)
ANN-BUS Connector
Figure 1.1 ANN-I/O Board Layout
1.9.5.2 Specifications
Max. ANN-BUS Voltage: 28 VDC
Max. Current:
Alarm: 200 mAStandby: 35 mAEach LED: 10 mA
Operating Temperature: 32
For indoor use in a dry location only
o
F to 120oF (0oC to 49oC)
ANN-BUS (ID#) Address DIP switch
ann-IObrd.cdr
28 MS-9050UD PN 52413:B 8/29/07
ANN-BUS Devices Product Description
1.9.5.3 ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 1.2. After the ANN-I/O is connected to the panel, it must be added to the system via FACP programming. Refer to the section titled "Modules Installed" on page 105.
ANN-I/O Module
MS-9050UD
Figure 1.2 ANN-I/O Connection to FACP
ANN-BUS and power wiring are supervised and power-limited
ann-IOtoFACP.cdr
MS-9050UD PN 52413:B 8/29/07 29
Product Description ANN-BUS Devices
1.9.5.4 ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10 LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized so that there is approximately 10 mA of current for each LED. No series resistors are required. LED outputs can be mapped to output circuits. Refer to the programming section titled "Modules Installed" on page 105 of this manual.
The LEDs are wired as illustrated in Figure 1.3. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
Figure 1.3 ANN-I/O Board Layout
30 MS-9050UD PN 52413:B 8/29/07
annI-Oleds.cdr
ANN-BUS Devices Product Description
1.9.6 ANN-LED Annunciator Module
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general system faults and input zones/points when used with a compatible F ACP. The ANN-LED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. The ANN-RLED provides alarm (red) indication for up to 30 input zones or addressable points. Multiple ANN-(R)LED modules may be used for full sy stem coverage.
1.9.6.1 ANN-LED Board Layout
Figure 1.4 illustrates the ANN-LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#) Address DIP switch
ANN-BUS Connector
Figure 1.4 ANN-LED Board Layout
1.9.6.2 Specifications
Max. ANN-BUS Voltage: 24 VDC
Max. Current:
Alarm: 68 mAStandby: 28 mA
Operating Temperature: 32
For indoor use in a dry location only
o
F to 120o F (0o C to 49o C)
MS-9050UD PN 52413:B 8/29/07 31
Product Description ANN-BUS Devices
1.9.6.3 ANN-LED Connection to FACP
Figure 1.5 illustrates the ANN-LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-LED
-24 VDC
+24 VDC
MS-9050UD
ANN-BUS and power wiring are supervised and power-limited
ANN-BUS
Figure 1.5 ANN-LED Connection to FACP
32 MS-9050UD PN 52413:B 8/29/07
ANN-BUS Devices Product Description
1.9.7 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.
1.9.7.1 ANN-RLY Board Layout
Figure 1.6 illustrates the ANN-RLY board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#) Address DIP switch
Figure 1.6 ANN-RLY Board Layout
1.9.7.2 Specifications
Operating Voltage: 24 VDC
Max. Current:
Alarm: 75 mAStandby: 15 mA
Operating Temperature: 32
For indoor use in a dry location only
1.9.7.3 Mounting/Installation
o
F to 120o F (0o C to 49o C)
ANN-BUS Connector
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis. Refer to the documentation (P/N: 53033) supplied with the ANN-RLY.
MS-9050UD PN 52413:B 8/29/07 33
Product Description Getting Started
1.9.7.4 ANN-RLY Connection to FACP
Figure 1.7 illustrates the ANN-RLY board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
1.10 Getting Started
The following is a brief summary of the minimal steps involved in bringing an MS-9050UD on-line:
Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page 38)
Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
Enter Autoprogramming (refer to "Autoprogram" on page 55)
Resolve Programming Conflicts
Go to Point Program to Enter Specific Data (refer to "Point Program" on page 56). Use the right and left arrow keys to navigate between devices.
ANN-RLY
+24 VDC
-24 VDC
FACP
ANN-BUS and power wiring are supervised and power-limited
ANN-BUS
Figure 1.7 ANN-RLY Connection to FACP
34 MS-9050UD PN 52413:B 8/29/07
Telephone Requirements and Warnings Product Description
1.11 Telephone Requirements and Warnings
1.11.1Telephone Circuitry
AC Ringer Equivalence Number (REN) = 03B DC Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
1.11.2Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-9050UD FCC Registration Number: US:1W6AL03B9050UD AC Ringer Equivalence: 0.3B DC Ringer Equivalence: 0.0B
Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to "Digital Communicator" on page 46 for an illustration of the proper installation of this equipment.
Important! The DACT must not
MS-9050UD PN 52413:B 8/29/07 35
be used to dial a phone number that is call-forwarded.
Product Description Telephone Requirements and Warnings
1.11.3Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same tele-
phone line. The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACT A. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
36 MS-9050UD PN 52413:B 8/29/07
Telephone Requirements and Warnings Product Description
1.11.4For Canadian Applications
The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements docu­ment(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility des­ignated by the supplier. Any repairs or alterations made by the user to this equipment, or equip­ment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspections authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termi­nation of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emis­sions from digital apparatus set out in the Radio Interference Regulations of the Canadian Depart­ment of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
24 Viceroy Road Concord, Ontario L4K2L9 Phone: (905) 660-7210 FAX: (905) 660-7204
IC Certificate Number: Ringer Equivalence Number (REN): 0.4B Load Number: 2
MS-9050UD PN 52413:B 8/29/07 37
Installation Mounting Backbox
SECTION 2 Installation
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left . Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Mounting Backbox
The circuit board contains static-sensitive components. Always ground yourself with a pr oper wrist strap before handling any boards so that static charges are removed from the body. Use static
!
suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a safe location until it can be reinstalled in the backbox.
See Page
backbox stud mounting hole
mounting stud
mounting slot
Ground Stud
Mark and pred rill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.3 on page 40
Inst all center top fastener in the wall with the screw head protrudingPlace backbox over the top screw, level and secureMark and dri ll the left and ri ght upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
Inst all remaining fasteners and tighten
mounting tab holes
mounting stud
backbox stud mounting hole
mounting slot
FACP Main Circuit Board on Chassis
mounting tabs
9050udbdUnmn.cdr
backbox stud mounting hole
Backbox
backbox stud mounting hole
Figure 2.1 Chassis Removal
38 MS-9050UD PN 52413:B 8/29/07
Mounting Chassis/Transformer/Main Circuit Board Installation
2.2 Mounting Chassis/Transformer/Main Circuit Board
One transformer is supplied standard with the control panel. Install the transformer and chassis in the location indicated in the following illustration.
6. When the location is dry and free of construction dust, install the chassis/transformer/circuit board assembly.
7. Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the backbox, then position the two mounting hole tabs over the studs with nu ts located in the upper portion of the backbox.
8. Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by pressing the chassis down.
9. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top, and to ensure proper grounding, use a 3/8” nut driver or socket.
10. If the main circuit board is not already attached to the chassis, install it by positioning the ten mounting holes over the studs on the chassis and secure with the supplied screws.
11. Ensure the transformer plug is connected to Connector J2 on the FACP main circuit board
12. Complete the installatio n as det a iled in the following sections.
mounting tab holes
FACP Main Circuit Board on Chassis
mounting stud
mounting slot
Ground Stud
mounting stud
Transformer is mounted to the back of the chassis in the lower left corner.
mounting slot
Backbox
Figure 2.2 Main Circuit Board/Chassis Installation
mounting tabs
9050udbdmn.cdr
MS-9050UD PN 52413:B 8/29/07 39
Installation Mounting Chassis/Transformer/Main Circuit Board
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to
Hinge Slot for optional Dress Panel
avoid covering venting holes on top of box.
Mounting slots for optional Trim Ring
Semi-Flush mounting hole
Hinge Slot for optional Dress Panel
9050udencl.cdr
Figure 2.3 FACP Cabinet Mounting
40 MS-9050UD PN 52413:B 8/29/07
Mounting Chassis/Transformer/Main Circuit Board Installation
9050udcab.cdr
Figure 2.4 FACP Cabinet Dimensions
.
MS-9050UD PN 52413:B 8/29/07 41
Installation Power
2.3 Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
2.3.1 AC Power and Earth Ground Connection
Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for the MS-9050UD. Overcurrent protection for this circuit must comply with Art icle 760 of the National Electrical Code (NEC) and/or local codes. Use 14 AWG (2.00 mm rating. Make certain that the AC mains circuit breaker is off between the mains and the control panel. Connect wiring from the AC mains to the Transformer on the FACP, being careful to observe proper connections.
Connect the AC ground wire to the Ground Stud located in the left side of the backbox. Refer to Figure 2.2 on page 39 and the illustration below for location of the stud. This connection is vital for maintaining the control panel’s immunity to unwanted transients generated by lightning and electrostatic discharge. Apply AC power to the panel only after the system is completely installed and visually checked. Note that AC power must be applied to the panel before installing the battery
interconnect cable (refer to the following section).
2
) or larger wire with 600 volt insulation
before wiring any connections
See Page
-
+
+
-
Interconnect Cable
2.3.2 Battery Power
Before connecting the batteries to the FACP, make certain that the interconnect cable between the batteries is not Do not connect the interconnect cable until the system is
connected.
completely installed. Observe polarity when connecting the batteries. Connect the battery cable to J1 on the main circuit board. Refer "Power Supply Calculations" on page 180, for calculation of the correct battery rating.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
AC Connection to
Transformer leads:
HOT
NEUTRAL
Battery Connection to J1 on FACP
Ground Stud
9050udpowr.cdr
42 MS-9050UD PN 52413:B 8/29/07
Relays Installation
2.4 Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited. Refer to UL Power-limited wiring requirements.
Note that the programmable relay labeled as Relay 1 is factory default programmed as Alarm and programmable Relay 3 is factory default programmed as Supervisory. The relay labeled Relay 2 is fixed as a Trouble relay and cannot be changed. It is a fail-safe relay which will transfer on any trouble or total power failure.
9050udreyp.cdr
Relay contacts shown with power applied to panel and no active troubles, alarms or supervisories
Figure 2.5 Relay Terminals
2.5 Notification Appliance Circuits
The control panel provides two NACs (Notification Appliance Circuits) Style Y (Class B) or Style
See Page
Reference
Manual
Z (Class A). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 2.5 amps (refer to "Calculating the System Current Draw" on page 181). Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited. Refer to the Fire-Lite Device Compatibility Document for a listing of compatible notification appliances. The NACs, which are located on the main circuit board, may be expanded via the Fire­Lite FCPS Series field charger/power supplies.
The following sections describe the configuration and wiring of Style Y and Style Z Notification Appliance Circuits on the FACP main circuit board.
MS-9050UD PN 52413:B 8/29/07 43
Installation Notification Appliance Circuits
2.5.1 Configuring NACs
The Notification Appliance Circuits are configured for Style Y (Class B) or Style Z (Class A) by properly wiring the NAC devices to TB1 on the main circuit board as illustrated below.
Style Y (Class B) Notification Appliance Circuits, supervised and power-limited -
4.7 kΩ, ½ watt P/N:71252 UL listed
Polarized Bells
Polarized Strobes
Notification Appliance Circuit polarity shown in alarm state
NAC 1 NAC 2
Style Z (Class A) Notification Appliance Circuits, supervised and power-limited
Polarized Bells
Polarized Strobes
Polarized HornsPolarized Horns
terminal number
Figure 2.6 NAC Wiring
Dummy Load all unused circuits with a 4.7 kΩ, ½ watt resistor across the B+ & B- terminals or wire jumpers between A+ & B+ and A- & B-.
9050udnac.cdr
44 MS-9050UD PN 52413:B 8/29/07
UL Power-limited Wiring Requirements Installation
2.6 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower­limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the FACP is shown below.
maintain minimum 0.25” between power-limited and nonpower-limited
Power-limited Circuits (Class 2)
circuits wiring
Nonpower-limited Circuits (Class 1)
Power-limited Circuits (Class 2)
Transformer Wires (nonpower-limited, supervised)
AC Power
Hot
Neutral
Ground
Ground Stud
4XTMF
To Batteries (nonpower-limited, Class 1 supervised)
Nonpower-limited, (Class 1) supervised Telephone Circuit
9050udulpwr.cdr
Figure 2.7 Typical UL Power-limited Wiring Requirements
MS-9050UD PN 52413:B 8/29/07 45
Installation Digital Communicator
2.7 Digital Communicator
T wo independent telephone lines can be connected to the control panel. Telephone line control/ command is made possible via double line seizure as well as usage of an RJ31X style interconnec­tion. Note that it is critical that the panel's digital communicator be located as the first device on
the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded per r equire­ments of UL 864 9th Edition.
Customer Premises Equipment and Wiring
Network
Service
Provider’s
Facilities
Telephone
Line
Network
Demarcation
Point
RJ31X
Jack
Telephone
Unused
RJ-11 Jack
MS-9050UD
Fax Machine
Answering
System
Telephone
Figure 2.8 DACT Installation
Computer
Telephone
Unused
RJ-11 Jack
9050ACTAdact.cdr
The control panel's digital communicator is built into the main circuit board. Connection and wir­ing of two phone lines is required as shown below.
Figure 2.9 Wiring Phone Jacks
46 MS-9050UD PN 52413:B 8/29/07
9050udjack.cdr
Optional Modules/Accessories Installation Installation
2.8 Optional Modules/Accessories Installation
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
2.8.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFP A 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building
MS-9050UD PN 52413:B 8/29/07 47
Installation Optional Modules/Accessories Installation
Before installing the module, place the disconnect switch to the right (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the MS-9050UD. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
Note: 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal. For an application using reverse polarity of a supervisory signal, refer to "FACP with Keltron" on page 196.
+ - + - + ­1 2 3 4 5 6 7
TBL Jumper
}Remote Alarm (power-limited)* }Remote Trouble (power-limited)*
No connection
}Municipal Box (nonpower-limited)*
Polarities are shown for module activation
Connect to FACP J8 & J9
* Wiring from these terminals can exit the protected premises. Dummy load terminals 6 and 7 (4.7kΩ, ¼ watt resistor) if Municipal Box is not connected.
Disconnect LED
4xtmfl.cdr
Disconnect Switch shown in disconnect position
Figure 2.10 4XTMF Transmitter Module
48 MS-9050UD PN 52413:B 8/29/07
Optional Modules/Accessories Installation Installation
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (Primary and Secondary) from the FACP before installing 4XTMF
2. Cut jumper JP28 on the main circuit board to allow the control panel to supervise the 4XTMF module
3. Remove two screws securing main circuit board to mounting plate and install two standoffs for securing 4XTMF module to main circuit board. Refer to Figure 2.11 for standoff locations on main circuit board
4. Carefully plug the connectors on the 4XTMF module into connectors J8 and J9 on the MS­9050UD main circuit board, being careful not to bend any pins
5. Secure 4XTMF module to standoffs with supplied screws removed in step 3.
6. Reapply power to the FACP
7. For proper 4XTMF operation, the main circuit board output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3
8. When the installation has been completed, enable the 4XTMF module by sliding the disconnect switch to the left
9. Test system for proper operation
4XTMF
Standoff
J8 & J9 Connectors
Standoff
Jumper JP28
MS-9050UD
Figure 2.11 4XTMF Connectors to MS-9050UD Connectors
Jumper JP2
9050ud4xtm.cdr
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTMF module. Relay 3 at TB3 must be programmed as a supervisory relay. Removing the jumper from JP2 will allow the 4XTMF to generate a trouble if the supervisory contact opens Leaving the jumper on JP2 will prevent generation of a trouble if the supervisory contact opens
MS-9050UD PN 52413:B 8/29/07 49
Programming Programming Data Entry
SECTION 3 Programming
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PAR TIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Stan­dard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be lim­ited to specific values or not used at all as indicated below:
Program feature
or option
Trouble Call Limit N
Remote Download Y
Permitted in
UL 864? (Y/N)
Possible settings
Refer to "Trouble Call Limit (Dialer Runaway Preven­tion)" on page 122.
Trouble Call Limit = 0 (factory def ault): unlimited calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble to from 1 to 99 within a 24 hour period
Refer to "Remote Download" on page 177. Remote Download - Proprietary No Remote Download - Proprietary Yes
Settings permitted in
UL 864
Tr ouble Call Limit = 0 for unlimited Central Station trouble calls
Remote Download Proprietary Yes for Proprietary Installations Only
3.1 Programming Data Entry
Programming can be accomplished using the MS-9050UD keypad or by connecting an optional standard computer keyboard. The keyboard can be connected to the PS-2 connector J6 on the control panel main circuit board.
The information presented in this section refers to programming the MS-9050UD via the onboard keypad. If an optional computer keyboard is connected to the MS-9050UD main circuit board, the following table describes the keyboard keys which correspond to the onboard keypad keys.
Keypad Keys Computer Keyboard Keys
1st Event Home CLR Delete ESC Esc RECALL Insert ** ## A - Z A - Z 0 - 9 0 - 9
(on QZ key)
—— //
••
Space bar
   
ENTER Enter ACK/STEP F1 SILENCE F2 DRILL F3 RESET F4
50 MS-9050UD PN 52413:B 8/29/07
User Programming Programming
3.2 User Programming
The MS-9050UD is completely field programmable and requires no special software skills. While
!!!
programming the MS-9050UD, the fire protection capabilities of the control panel are
Site-specific programming may be accomplished in three ways:
Autoprogramming Feature - This is a convenient method for quickly bringing the FACP addressable SLC devices on-line without the necessity of programming each device individually. Refer to "Autoprogram" on page 55 for a detailed description of Autoprogramming
Manual programming or editing, using the FACP keypad or a PC keyboard
Off-line Programming and Editing Feature - allows creation and editing of site-specific custom programs using a Windows-based computer. For programs requiring a large amount of data entry, this method may be preferred. A PK-CD programming kit can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms, troubles or supervisories, as illustrated below:
SYSTEM ALL NORMAL 10:00A 092105
enabled.
See Page
Read Status and Manual Dial mode can be entered while the panel is in any Manual Dial mode, however, cannot be entered while the panel is communicating with the Central Station. If an alarm or supervisory event exists at the panel, the event must be cleared before entering Programming mode. T o access any of the programming or read status features, the Enter or Mode key must be pressed, which will cause the LCD to display the following:
mode of operation.
1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODE 4=REMOTE DOWNLOAD
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status Mode which allows the user to view the programmed features and status of the control panel The Read Status feature is not password protected. Refer to "Read Status" on page 159 for a detailed description of this feature.
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized person. After pressing 2, a screen will prompt for a password. After entering the correct password, the user may select from a list of programming options.
Pressing 3 will select the Manual Dial Mode which allows the user to enter a troubleshoot mode of operation.
Pressing 4 will select Remote Download which allows the user to enable the remote programming option. Refer to "Remote Download" on page 177.
Exit Programming, Read Status and Manual Dial Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the display reads System All Normal. Note that the data which is entered during Programming mode
is not
saved until the programmer exits this mode by repeatedly pr essing the ‘ESC’ key. If the Reset
key is pressed or power is lost before exiting Programming mode, all data just entered will be lost.
MS-9050UD PN 52413:B 8/29/07 51
Programming Initial Power-up
User Programming Levels
There are two user programming levels:
User Master Program Level 1 is used for programming panel specific data relating to device types, zoning, messages, control panel functions, etc.
User Maintenance Program Level 2 is used by a qualified operator to access features such as Disable/Enable, View and Clear History, Walktest and System Time Change.
3.3 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If the addressable devices have not yet been programmed into the F ACP, their LEDs will not flash and the following trouble message will be displayed.
TROUBL IN SYSTEM NO DEVICES INSTALLED
09:03A 092105
3.4 Programming Screens Description
Three options are available when the Enter key is pressed: Read Status, Programming and Manual Dial Mode. The Read Status and Programming options have multiple functions or features which may be chosen. To view all of the choices, it is necessary that the programmer scroll through a number of additional subscreens. These selections are displayed on multiple screens to make them
See Page
more readable for the programmer. Refer to "Master Programming Level" on page 54, for additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed in the upper right corner of the screen being viewed. The programmer can then press the keypad Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen. The same process, as detailed in the previous paragraphs, is follo w ed to view all option choices.
3.5 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as indicated in the following examples. From either of the screens, access to specific system and device features or programming may be obtained. All user programming entries are stored in
See Page
nonvolatile memory. The factory set passwords can be changed by the user as described in "Password Change" on page 135. If an invalid password is entered, the blinking cursor will return to the first password character position. To exit Programming, Read Status or Manual Dial mode at any time, press the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC key in order to store the program data entered during this mode. If the Reset key is pressed or power is lost before exiting Programming mode, the data just entered will not be saved.
52 MS-9050UD PN 52413:B 8/29/07
Programming and Passwords Programming
To access user Programming mode, press the Enter or Mode key. The LCD will display the following:
1=READ STATUS MODE 2=PROGRAMMING MODE 3=MANUAL DIAL MODE 4=REMOTE DOWNLOAD
To enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMING ENTER PASSWORD *****
Entering the Master
If the Maintenance
level password (default 00000) will cause the following screen to appear:
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
level password (default 11111) is entered, the following screen will appear:
PROGRAMMING 1=POINT PROGRAM 2=HISTORY 3=PROGRAM CHECK
Note that in the two preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad down arrow key.
MS-9050UD PN 52413:B 8/29/07 53
Programming Master Programming Level
3.6 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and the system Trouble LED flashes until Programming mode is exited. The following display will appear:
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as illustrated below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP
Programming Screen #2
PROGRAMMING 1=HISTORY 2=WALKTEST 3=OPTION MODULES
Programming Screen #3
PROGRAMMING 1=PASSWORD CHANGE 2=CLEAR PROGRAM 3=PROGRAM CHECK
Programming Screen #4
54 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
3.6.1 Autoprogram
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which prompts the control panel to poll all devices installed on the SLC loop. The primary purpose of autoprogramming is to allow the installer a fast and easy way to bring the system on-line as quickly as possible. The first time the system is powered-up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only add default values for newly installed devices.
When Autoprogram is selected, the control panel will begin autoprogramming the system by communicating with each addressable device installed on the SLC loop. While autoprogramming, the panel will display the following:
AUTOPROGRAM AUTOPROGRAMMING! PLEASE WAIT
Autoprogram Progress Screen
When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop similar to the following display:
# OF DET LOOP1 022 # OF MON LOOP1 015 # OF CON LOOP1 010
Autoprogram Result Screen #1
In the preceding example, the display indicates that the SLC Loop has 22 addressable detectors, 15 monitor modules and 10 control modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
MS-9050UD PN 52413:B 8/29/07 55
Programming Master Programming Level
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #1
3.6.2 Point Program
The Point Program option allows the programmer to add a new addressable device to an SLC loop, delete an existing device from a loop or change the programming for an existing device. Pressing 2, while viewing Programming Screen #1, will select the Point Program option and display the following screen:
POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE
Point Program Screen
3.6.2.1 Detector Programming
Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete or change the programming of an addressable detector. The following screen will be displayed by the control panel:
DETECTOR 1=ADD 2=DELETE 3=EDIT
Detector Screen
3.6.2.1.1 Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector address to programming:
ADD DETECTOR ENTER DETECTOR# ***
Add Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE(ION)
Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the newly added detector.
56 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
DETECTOR 1=ADD 2=DELETE 3=EDIT
Detector Screen
When the type has been selected, the following screen will be displayed:
ADD DETECTOR DETECTOR# 005 IS ADDED
The programmer can continue adding detectors by pressing the ESC key which will return the display to the Add Detector Screen.
3.6.2.1.2 Delete Detector
Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the programmer to delete a specific detector:
DELETE DETECTOR ENTER DETECTOR# ***
Delete Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 005. When the last digit is keyed-in, the following screen will be displayed:
DELETE DETECTOR DETECTOR# 005 IS DELETED
The programmer can continue deleting detectors by pressing the ESC key which will return the display to the Delete Detector Screen.
3.6.2.1.3 Edit Detector
The programmer can change a detectors existing or factory default programming by pressing 3 in the Detector Screen. The following screen will be displayed:
EDIT DETECTOR ENTER POINT ADDRESS ***
Edit Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as 017.
MS-9050UD PN 52413:B 8/29/07 57
Programming Master Programming Level
When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device that is selected address, will be displayed.
If no
detectors have been installed on the loop, the following will be displayed:
installed with a lower address, closest to the
NO DETECTOR INSTALLED
Edit Detector Screen #1
If the selected address has been added to programming, device summary screens will be displayed. These screens allow the programmer to view all device settings at a single glance. Pressing the left or right arrow keys will allow the programmer to rapidly view the devices at the previous or next address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not physically installed on the SLC or has a communication fault but the address is programmed in the system, the following screen will be displayed:
TROUBL SMOKE(PHOTO) <ADJ><NOUN> ZNNN * 1D017
Edit Detector Screen #1
If the selected address has been added to programming and a detector (such as a photoelectric detector) with the selected address is physically installed on the SLC and is communicating with the control panel, the following will be displayed:
NORMAL SMOKE (PHOTO) <ADJ><NOUN> ZNNN V 1D017
Edit Detector Screen #1
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to view the Edit Detector screens.
In the preceding example:
Normal - indicates that the detector with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - rep resents the adjective and noun, which have been programmed,
describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the detector is assigned to
(NNN = the three digit zone number from 000 - 019)
V or * - indicates whether or not alarm verification is enabled (V = alarm verification
enabled and * = alarm verification disabled)
1D017 - represents the Loop, Device type and Device address (1 = SLC Loop, D=Detector
and 017 = Detector Address 017)
58 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
The following examples show the editing of a photoelectric smoke detector with address 017, located on the SLC loop:
EDIT DETECTOR 1D017 1=ENABLED YES 2=TYPE SMOKE(PHOTO) 3=VERIFICATION OFF
Edit Detector Screen #2
EDIT DETECTOR 1D017 1=WALKTEST NO 2=PAS NO 3=PRE-SIGNAL NO
Edit Detector Screen #3
EDIT DETECTOR 1D017 1=ZONE ASSIGNMENT 00 ** ** ** **
EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION
Edit Detector Screen #2
Edit Detector Screen #4
EDIT DETECTOR 1D017 1=NOUN/ADJECTIVE 2=DESCRIPTION ********************
Edit Detector Screen #5
Enable/Disable Detector
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the detector will not be polled by the control panel, preventing the detector from reporting alarms and troubles to the panel. The control panel will display the device type and address which has been disabled and will turn on the Trouble LED.
MS-9050UD PN 52413:B 8/29/07 59
Programming Master Programming Level
EDIT DETECTOR 1=ENABLED 2=TYPE 3=VERIFICATION
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector Screen #2. This will cause the control panel to display the following Detector Type Screen:
DETECTOR TYPE 1=SMOKE(PHOTO) 2=USER-DEFINED-1 3=SMOKE (ION)
Edit Detector Screen #2
Detector Type Screen #1
Pressing the down arrow key will display additional detector types as indicated in the following table.
Detector Type Action When Activated
Smoke Photo Fire Alarm User-Defined-1 same as previous (Smoke Photo) Smoke Ion Fire Alarm User-Defined-2 same as previous (Smoke Ion) Heat Detect Fire Alarm User-Defined-3 same as previous (Heat Detect) Smoke DuctP Fire Alarm User-Defined-4 same as previous (Smoke DuctP) Photo w/Heat Fire Alarm User-Defined-5 same as previous (Photo w/Heat) Duct Superv Supervisory, latching User-Defined-6 same as previous (Duct Superv) Photo Superv Supervisory, latching User-Defined-7 same as previous (Photo Super) future not used
While viewing any Detector Type screen, select the type of detector being programmed by pressing the corresponding keyboard number key. The display will return to Edit Detector Screen #2 and indicate the selection next to the Type option.
See Page
EDIT DETECTOR 1=WALKTEST 2=PAS 3=PRE-SIGNAL
Edit Detector Screen #3
60 MS-9050UD PN 52413:B 8/29/07
Note: If a detector is selected to be a SUPERV DUCTP type, it will function like a supervisory point not a fire alarm point. The supervisory LED and supervisory relay will activate, not the fire alarm LED or alarm relay, if the detector senses smoke.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector Screen #2 so that the display reads Verification On. Each time the 3 key is pressed, the display will toggle between Verification On and Verification Off. For a detailed description, refer to "Alarm Verification (None or One Minute)" on page 158.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable a device for the Walktest feature, press 1 while viewing the Edit Detector Screen #3 until the display reads
Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 158.
Master Programming Level Programming
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel acti vation (including alarm relay and communicator) for a period of 15 seconds plus a programmable time of up to 3 minutes. Zone 17, however, will activate immediately and may be used to connect a signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose). To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until
See Page
the display reads PAS Yes. Each press of the 2 key will cause the display to toggle between PAS Yes and PAS N o. Refer to "Positive Alarm Sequence" on page 156.
For example, if a detector with address 005 is to be configured for PAS operation:
Select PAS Yes when editing the detector set to address 005 Program the desired zone or zones to be activated by this detector, in this example Z001Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
Program an output, such as a control module, for P AS activation by assigning zone Z17 to
it. This control module may be connected to a signaling device used to indicate a PAS condition (do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone PAS 17 and set the PAS delay timer to some
value
With the preceding program settings, when the detector with address 005 is activated, zone Z17 will cause its associated control module to activate immediately, sounding the connected PAS signaling device. Following the PAS delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
EDIT DETECTOR 1=WALKTEST 2=PAS 3=PRE-SIGNAL
Edit Detector Screen #3
See Page
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a preprogrammed time delay of up to three minutes while allowing for visual verification by a person. Note that the alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone 18 will activate. This zone can be programmed to a control module which may be used to activate a sounder or indicator which the installer designates as a Presignal indication (do not use a Notification Appliance Circuit for this purpose). To enable the Pre-signal feature, press 3 while viewing Edit Detector Screen #3 until the display reads Pre-signal Yes. Each press of the 3 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to "Presignal" on page 155.
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
Select Pre-signal Yes when editing the detector set to address 005 Program the desired zone or zones to be activated by this detector, in this example Z001Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
Program an output, such as a control module, for Pre-signal activation by assigning zone
Z18 to it. This control module may be connected to a signaling device used to indicate a Pre-signal condition (do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone Pre-signal 18 and set the Pre-signal delay
timer to some value
MS-9050UD PN 52413:B 8/29/07 61
Programming Master Programming Level
With the preceding program settings, when the detector with address 005 is activated, zone Z18 will cause its associated control module to activate immediately, sounding the connected signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone Z001 will cause its associated control module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
Zone Assignment
EDIT DETECTOR 1=ZONE ASSIGNMENT 00 ** ** ** **
Edit Detector Screen #4
See Page
EDIT DETECTOR 1=NOUN/ADJECTIVE 2=DESCRIPTION *****************
Edit Detector Screen #5
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while viewing Edit Detector Screen #4 displays the following screen:
ZONE ASSIGNMENT Z00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zone Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Detector Screen #4. Note that the left and right arrow keys can be used to navigate through the zones and the CLEAR key can be used to quickly clear a zone.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will cause the following screen to be displayed:
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
62 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
********************** 1=NORTH 2=SOUTH 3=EAST
********************** 1=WEST 2=FRONT 3=CENTER
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the detector currently being programmed. When an adjective has been selected, it will appear at the top of the display as indicated by the asterisks.
********************** 1=3RD 2=4TH 3=5TH
Adjective Screen #1
Adjective Screen #5
********************** 1=FLOOR1 2=FLOOR2 3=FLOOR3
Adjective Screen #2
********************** 1=REAR 2=UPPER 3=LOWER
Adjective Screen #3
********************* 1=MAIN 2=FIRST 3=2ND
Adjective Screen #6
********************** 1=FLOOR4 2=FLOOR5 3=ROOM
Adjective Screen #7
Adjective Screen #4
MS-9050UD PN 52413:B 8/29/07 63
Programming Master Programming Level
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM
********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the detector currently being programmed. When a noun has been selected, it will appear at the top of the display as indicated by the asterisks.
********************** 1=KITCHEN 2=LOBBY 3=OFFICE
Noun Screen #1
Noun Screen #5
********************** 1=PATIENT 2=RESTROOM 3=ROOM
Noun Screen #2
********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR
Noun Screen #3
********************** 1=GARAGE 2=HALLWAY 3=HVAC RM
Noun Screen #6
********************** 1=STAIRWAY 2=STOREROOM 3=WING
Noun Screen #7
********************** 1=ZONE
Noun Screen #4
64 MS-9050UD PN 52413:B 8/29/07
Noun Screen #8
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
EDIT DETECTOR 1=NOUN/ADJECTIVE 2=DESCRIPTION
Edit Detector Screen #5
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns which have been programmed into the control panel by the user utilizing the PK-CD programming kit. These descriptors are selected as described in the previous sections.
Description
The Description selection allows the programmer to enter additional information about the detector currently being programmed. This information will be displayed as part of the device label on the display. Pressing 2 while viewing Edit Detector Screen #5 will cause the following screen to be displayed:
DESCRIPTION 1D002 1=NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Detector Screen #5, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Description, Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire field is replaced with the field entered for the previous device programmed
, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by-letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one (9 will change to 0). If the last character is a letter, it changes to a 0.
The above increment function may be repeated with each press of the zero key
MS-9050UD PN 52413:B 8/29/07 65
Programming Master Programming Level
POINT PROGRAM SELECT TYPE 1=DETECTOR 2=MODULE
Point Program Screen #2
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 19. Z00 (default zone) is the general alarm zone. Z01 through Z19 may be selected to link software zones
3.6.2.2 Module Programming
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or change the programming of an addressable module. The following screen will be displayed by the control panel:
MODULES 1=ADD 2=DELETE 3=EDIT
Modules Screen
3.6.2.2.1 Add Module
Pressing 1 while viewing the Modules Screen will display the following screen which allows the programmer to add a new module address to programming:
ADD MODULE ENTER MODULE# ***
Add Module Screen #1
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 006.
When the last digit is keyed-in, the following screen will be displayed:
ADD MODULE 1=CONTROL 2=MONITOR
Add Module Screen #2
66 MS-9050UD PN 52413:B 8/29/07
MODULES 1=ADD 2=DELETE 3=EDIT
Modules Screen
Master Programming Level Programming
Pressing 1 for Control Module or 2 for Monitor Module will cause the following screen to be displayed:
ADD MODULE MODULE# 006 IS ADDED
Add Module Screen #3
The programmer can continue adding modules by pressing the ESC or left arrow key which will return the display to the Add Module Screen #1.
3.6.2.2.2 Delete Module
Pressing 2 in the Modules Screen will display the Delete Module Screen which allows the programmer to delete a specific module:
DELETE MODULE ENTER MODULE# ***
Delete Module Screen
A flashing cursor will appear in the position of the first asterisk to the left. Using the panel keypad, key in the module address such as 006. When the last digit is keyed in, the following confirmation that the module has been deleted will be displayed:
DELETE MODULE MODULE# 006 IS DELETED
3.6.2.2.3 Edit Module Screen for Monitor Module
The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed:
EDIT MODULE ENTER MODULE ADDRESS ***
Edit Module Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 012.
MS-9050UD PN 52413:B 8/29/07 67
Programming Master Programming Level
When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device that is selected address, will be displayed. If no modules are installed on the loop, the following screen will be displayed:
installed with a lower address, closest to the
NO MODULE INSTALLED
Edit Module Screen
If the selected address has been added to programming but a module (such as a monitor module) with the selected address is not physically installed on the SLC or has a communication fault, the following screen will be displayed:
TROUBL MONITOR <ADJ><NOUN> ZNNN * 1M012
If the selected address has been added to programming and a module (such as a monitor module) with the selected address is physically installed on the SLC and is communicating with the control panel, the following screen will be displayed:
NORMAL MONITOR <ADJ><NOUN> ZNNN W 1M012
To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Monitor screens. In the preceding example:
Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - rep resents the adjective and noun, which have been programmed,
describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the two digit zone number from 000 - 019)
1M012 - rep resents the Loop , Device type and Device address (1 = SLC Loop 1,
M=Module and 012 = Module Address 012)
W or * - indicates whether or not the device is programmed for Walktest (W =
programmed for walktest, * = not programmed for walktest).
68 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
If the selected address corresponds to a control module, a screen displaying information about
See Page
the control module with the selected address will be displayed as shown in "Edit Module Screen for Control Modules" on page 76.
If the selected address corresponds to a monitor the module with the selected address will be displayed as illustrated in the following:
module, a screen displaying information about
NORMAL MONITOR <ADJ><NOUN> ZNNN 1M012
EDIT MONITOR 1M012 1=ENABLED YES 2=TYPE MONITOR
Edit Monitor Screen #2
EDIT MONITOR 1M012 1=PRE-SIGNAL NO
Edit Monitor Screen #3
EDIT MONITOR 1M012 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** **
Edit Monitor Screen #4
EDIT MONITOR 1M012 1=ADJECTIVE/NOUN 2=DESCRIPTION ********************
Edit Monitor Screen #5
MS-9050UD PN 52413:B 8/29/07 69
Programming Master Programming Level
Enable/Disable Module
To Enable or Disable the monitor module, press the 1 key while viewing th e Edit Modu le Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from reporting alarms and troubles to the panel. The control panel will indicate a system trouble condition if any devices are disabled.
EDIT MONITOR 1=ENABLED 2=TYPE MONITOR
Edit Monitor Screen #2
Type Monitor
Using the PK-CD Upload/Download utility program, unique user-defined monitor types can be created and loaded into the FACP for later use. The FACP response to the activation of a user­defined type is the same as most previous standard types in the list, thus allowing a variety of user-defined types and responses. To select the type of monitor module being programmed, press the 2 key while viewing the Edit Monitor Screen #2. This will cause the control panel to display the first Monitor Type Screen as illustrated below
MONITOR TYPE 1=PULL-STATION 2=USER-DEFINED-1 3=WATERFLOW
Monitor T ype Screen #1
T o view additional Monitor T ype Screens, press the down arrow key. While viewing one of the Monitor Type screens, select the type of monitor module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which will show the new type selection. The following table lists all of the Monitor Types available for programming and their respective functions.
70 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
Monitor module type selection will affect the function of the point as follows:
Table 3.1 Monitor Types
Monitor Type Action When Activated
Pull-Station Fire Alarm User-Defined-1 Fire Alarm Waterflow Fire Alarm Delayed (uses waterflow delay) User-Defined-2 Fire Alarm Delayed (uses waterflow delay) Monitor Fire Alarm User-Defined-3 Fire Alarm Future Use Future Use Future Use Future Use
Smoke-Conventional User-Defined-5 Heat-Conventional User-Defined-6
Medic-Alert Supervisory, latching User-Defined-7 Supervisory, latching Hazard-Alert Supervisory, latching User-Defined-8 Supervisory, latching Tornado-Alert Supervisory, latching User-Defined-9 Supervisory, latching Future Use Future Use Future Use Future Use Tamper Supervisory, nonlatching (tracking) User-Defined-11 Supervisory, nonlatching (tracking) Supervisory Supervisory, latching User-Defined-12 Supervisory, latching Supervisory-AR Supervisory, nonlatching (tracking) User-Defined-13 Supervisory, nonlatching (tracking) HVAC OVRRIDE Switch Supervisory, nonlatching (tracking) Power-Monitor AC Fault User-Defined-14 AC Fault Trouble-Monitor Trouble User-Defined-15 Trouble Proc-Mon Piezo User-Defined-16 Piezo Procmon-AR Piezo, nonlatching (tracking) User-Defined-17 Piezo, nonlatching (tracking) Future Use Future Use Future Use Future Use Ack-Switch Acts like panel Acknowledge Key Sil-Switch Acts like panel Alarm Silence Key Reset-Switch Acts like panel Reset Key Drill-Switch Acts like panel Drill Key PAS-Bypass PAS Disable HVAC RESTART Switch Drill-Switch AR
4, 5
5
5
5
Fire Alarm Fire Alarm Fire Alarm Fire Alarm
Acts like panel Drill Key, nonlatching (tracking)
3
Notes:
1. For the SUPERVISORY-AR and PROCMON-AR selections, AR refers to AutoResettable.
2. For HVAC RESTART AND HVAC OVRRIDE descriptions, refer to "HVAC Control" on page 198.
3. Drill Switch Auto-Resettable turns on the NACs and any control module mapped to the Drill Switch zone.
4. Conventional 2-wire smoke detectors may be powered using an external power supply with an SLC Control Relay Module programmed for Resettable Power operation. A Control
Relay Module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control module is disabled.
5. Use only these Monitor Type IDs for the Zone Modules (MMF-302). The Zone Modules will not function correctly if any other Type ID is used.
MS-9050UD PN 52413:B 8/29/07 71
Programming Master Programming Level
Pre-signal
EDIT MONITOR 1=PRE-SIGNAL
Edit Monitor Screen #3
See Page
EDIT MONITOR 1=WALKTEST 2=ZONE ASSIGNMENT 00 ** ** ** **
Edit Monitor Screen #4
T o enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre- signal Yes and Pre-signal No. Refer to "Presignal" on page 155 for additional information.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable devices, which are connected to a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 158 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2 while viewing Edit Monitor Screen #4 displays the following screen:
MON ZONE ASSIGN
Z00 Z** Z** Z** Z**
Zone Assignment Screen
EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION *****************
Edit Monitor Screen #5
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5 will cause the following screen to be displayed:
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
72 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
********************** 1=NORTH 2=SOUTH 3=EAST
********************** 1=WEST 2=FRONT 3=CENTER
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the monitor module currently being programmed.
********************** 1=3RD 2=4TH 3=5TH
Adjective Screen #1
Adjective Screen #5
********************** 1=FLOOR 1 2=FLOOR 2 3=FLOOR 3
Adjective Screen #2
Adjective Screen #6
********************** 1=REAR 2=UPPER 3=LOWER
Adjective Screen #3
********************** 1=MAIN 2=FIRST 3=2ND
Adjective Screen #4
********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM
Adjective Screen #7
MS-9050UD PN 52413:B 8/29/07 73
Programming Master Programming Level
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM
********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the monitor module currently being programmed.
********************** 1=KITCHEN 2=LOBBY 3=OFFICE
Noun Screen #1
Noun Screen #5
********************** 1=PATIENT 2=RESTROOM 3=ROOM
Noun Screen #2
Noun Screen #6
********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR
Noun Screen #3
********************** 1=GARAGE 2=HALLWAY 3=HVAC RM
Noun Screen #4
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD.
********************** 1=STAIRWAY 2=STOREROOM 3=WING
Noun Screen #7
********************** 1=ZONE
Noun Screen #8
74 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
EDIT MONITOR 1=NOUN/ADJECTIVE 2=DESCRIPTION *****************
Edit Monitor Screen #5
Description
The Description selection allows the programmer to enter additional information about the monitor module currently being programmed. This information will be displayed as part of the device label on the LCD display. Pressing 2 while viewing Edit Monitor Screen #5 will cause the following screen to be displayed:
DESCRIPTION 1M012 1=NOUN/ADJECTIVE
********************
Noun/Adjective Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the LCD display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 2, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Monitor Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire Adjective field is replaced with the field entered for the previous device programmed
, and the cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by-letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one (9 will change to 0). If the last character is a letter, it changes to a 0.
The above increment function may be repeated with each press of the zero key
MS-9050UD PN 52413:B 8/29/07 75
MODULES 1=ADD 2=DELETE 3=EDIT
Modules Screen
Programming Master Programming Level
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 19. Z00 (default zone) is the general alarm zone. Z01 through Z19 may be selected to link software zones
3.6.2.2.4 Edit Module Screen for Control Modules
The programmer can change a module’s existing or factory default programming by pressing 3 in the Modules Screen. The following screen will be displayed:
EDIT MODULE ENTER MODULE ADDRESS ***
Edit Module Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit module address, such as 002. When the last digit is
keyed-in, if the selected address corresponds to a control module, a screen displaying information about the control module with the selected address will be displayed as illustrated in the following:
NORMAL CONTROL <ADJ><NOUN> ZNNN SW 1M002
Edit Control Screen #1
In the preceding example:
Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - rep resents the adjective and noun, which have been programmed,
describing the location of the displayed device
Control - indicates that the selected module is a control moduleS or * - represents Silenceable (S) or Nonsilenceable (*)W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled)
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 019)
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module
and 002 = Module Address 02)
76 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
To change the programming for the displayed module, press the keyboard down arrow key to view the following Edit Control screens:
EDIT CONTROL 1=ENABLED YES 2=TYPE CONTROL 3=SILENCEABLE YES
Edit Control Screen #2
EDIT CONTROL 1=WALKTEST YES 2=ZONE ASSIGNMENT 00 ** ** ** **
Edit Control Screen #3
EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION ********************
Edit Control Screen #4
Enable/Disable Module
T o Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the module from activating its output devices. The control panel will indicate a system trouble condition and the Disable LED will turn on if any devices are disabled.
MS-9050UD PN 52413:B 8/29/07 77
Programming Master Programming Level
Type
T o select the type of control module being programmed, press the 2 key while viewing the Edit Control Screen #2. This will cause the control panel to display the following Control Type Screens:
EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE
Edit Control Screen #2
CONTROL TYPE 1=BLANK 2=BELL-CIRCUIT 3=HORN-CIRCUIT
Control Type Screen #1
While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding keypad number key. The display will return to the Edit Control Screen #2 and indicate the new type selection.
Notes:
1. A control r elay module set to the Resettable Power type will follow the main circuit boar d 24 VDC resettable power unless the control r elay module is disabled.
The following table contains control module type codes and their functions which are displayed in the Control Type screens:
Control Type Special Function
Blank NAC Type - Supervised Bell Circuit NAC Type - Supervised Horn Circuit NAC Type - Supervised Sounders NAC Type - Supervised Relay Ignore Open Circuit Strobe Circuit NAC Type - Supervised Control NAC Type - Supervised Resettable Power Relay Type - Ignore Open Circuit HVAC SHUTDN Relay Type - Ignore Open Circuit
Note: For HVAC SHUTDN descriptio n, refer to "Control Module Operation" on page 198.
78 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
EDIT CONTROL 1=ENABLED 2=TYPE 3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL 1=WALKTEST 2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to the control module can be silenced, either by pressing the Alarm Silence key or by enabling Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the Silenceable feature causing the display to read Silenceable Yes. Repeated presses of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable No.
Note that nonsilenceable outputs will not
be activated for Fire Drill.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting the control panel after each device activation. To enable devices, which are connected to a control module, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 158 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable control module. Pressing 2 while viewing Edit Control Screen #3 displays the following screen:
EDIT CONTROL 1=NOUN/ADJECTIVE 2=DESCRIPTION
Edit Control Screen #4
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this device. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the Edit Control Screen #3.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the control module currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause the following screen to be displ a yed:
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
MS-9050UD PN 52413:B 8/29/07 79
Programming Master Programming Level
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
********************** 1=NORTH 2=SOUTH 3=EAST
********************** 1=WEST 2=FRONT 3=CENTER
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective screens. Press the number corresponding to the adjective that is to be used as a descriptor for the location of the control module currently being programmed.
********************** 1=3RD 2=4TH 3=5TH
Adjective Screen #1
Adjective Screen #5
********************** 1=FLOOR 1 2=FLOOR 2 3=FLOOR 3
Adjective Screen #2
Adjective Screen #6
********************** 1=REAR 2=UPPER 3=LOWER
Adjective Screen #3
********************** 1=MAIN 2=FIRST 3=2ND
Adjective Screen #4
********************** 1=FLOOR 4 2=FLOOR 5 3=ROOM
Adjective Screen #7
80 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
1=STANDARD ADJECTIVE 2=STANDARD NOUN 3=CUSTOM ADJECTIVE 4=CUSTOM NOUN
Noun/Adjective Screen
********************** 1=BASEMENT 2=BOILER RM 3=CLASSROOM
********************** 1=CLOSET 2=CORRIDOR 3=ELECTRIC RM
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens. Press the number corresponding to the noun that is to be used as a descriptor for the location of the control module currently being programmed.
********************** 1=KITCHEN 2=LOBBY 3=OFFICE
Noun Screen #1
Noun Screen #5
********************** 1=PATIENT 2=RESTROOM 3=ROOM
Noun Screen #2
Noun Screen #6
********************** 1=ELEVATOR 2=ENTRANCE 3=FLOOR
Noun Screen #3
********************** 1=GARAGE 2=HALLWAY 3=HVAC RM
Noun Screen #4
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns which have been programmed into the control panel using the PK-CD programming kit.
********************** 1=STAIRWAY 2=STOREROOM 3=WING
Noun Screen #7
********************** 1=ZONE
Noun Screen #8
MS-9050UD PN 52413:B 8/29/07 81
Programming Master Programming Level
Description
The Description selection allows the programmer to enter additional information about the control module currently being programmed. This information will be displayed as part of the device label on the display. Pressing 2 while viewing Edit Control Screen #4 will cause the following screen to be displayed:
EDIT CONTROL 1=ADJECTIVE/NOUN 2=DESCRIPTION
Edit Control Screen #4
DESCRIPTION 1M002 1=NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter additional descriptive information about the device being programmed. This information will appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times until a blank appears in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Edit Control Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as follows:
If the zero key is pressed, a 0 is placed in the first letter position
If the zero key is then pressed a second time with no intervening key actions, the entire Adjective field is replaced with the field entered for the previous device programmed cursor moves to the last character of the field (Recall function). The Recalled Adjective or Noun field may now be changed letter-by-letter
If the zero key is pressed again with no other intervening key actions and the last character in the field is a number 0-9, the number is incremented by one (9 will change to 0). If the last character is a letter, it changes to a 0.
The above increment function may be repeated with each press of the zero key
, and the
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the display ROOM_304. The cursor automatically jumps from the first to the last letter of the Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 19. Z00 (default zone) is the general alarm zone. Z01 through Z19 may be selected to link software zones
82 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
3.6.3 Zone Setup
Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated below:
PROGRAMMING 1=AUTOPROGRAM 2=POINT PROGRAM 3=ZONE SETUP
Programming Screen #2
ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 17 18 19
Zone Setup Screen #1
ZONE SETUP 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED
Zone Setup Screen #2
ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=FUTURE USE
Zone Setup Screen #3
ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 17 18 19
Zone Setup Screen #1
3.6.3.1 Enable
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:
ZONE TO ENABLE Z
Enable Screen
This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the second digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z. Another zone can then be enabled.
MS-9050UD PN 52413:B 8/29/07 83
Programming Master Programming Level
ZONE SETUP 1=ENABLE 2=DISABLE 3=ZONE 17 18 19
Zone Setup Screen #1
3.6.3.2 Disable
Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:
ZONE TO DISABLE Z
Disable Screen
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the second digit is entered, the zone will be disabled and the cursor will return to the original position next to the Z. Another zone can then be disabled.
3.6.3.3 Zone 17, 18 and 19
Pressing 3 for Zone 17, 18 and 19, while viewing Zone Setup Screen #1, will display the following screen:
SPEC PURPOSE ZONE 1=PAS 17 OFF 2=PRE-SIGNAL 18 OFF 3=TWO STAGE 19 OFF
Zone 17, 18 and 19 Screen
Zones 17, 18 and 19 can be programmed for normal zone operation or for special purpose applications. In the above illustration, the three zones are shown Off, which means they can be programmed to function in the same manner as all other zones, by assigning them to input and output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 17 On. Each press of the 1 key will cause the display to toggle between PAS 17 On and PAS 17 Off. When Zone 17 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 17 to activate. By assigning Zone 17 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a PAS condition in the control panel. Do not assign Zone 17 to a Notification Appliance Circuit when using this zone to
indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software checks .
Pressing 2 will cause the display to change to Pre-signal 18 On. Each press of the 2 key will cause the display to toggle between Pre-signal 18 On and Pre-signal 18 Off. When Zone 18 is programmed On, a Pre-signal activation of any device will cause Zone 18 to activate. By assigning Zone 18 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 18 to a Notification Appliance Circuit when using this zone
to indicate a Pre-signal condition. Attempting to do so will generate an error message and will be prevented by software checks.
Pressing 3 will cause the display to change to Two Stage 19 On. Each press of the 3 key will cause the display to toggle between Two Stage 19 On and Two Stage 19 Off. Refer to "Two Stage Operation" on page 98 for a description of this feature.
84 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
ZONE SETUP 1=ZONES INSTALLED 2=ZONES ENABLED 3=ZONES DISABLED
Zone Setup Screen #2
3.6.3.4 Zones Installed
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to the following:
ZONES INSTALLED 00 01 02 03 04 05
Zones Installed Screen
This display will show all of the zones that have been programmed into the control panel.
3.6.3.5 Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
ZONES ENABLED 00 01 02 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19
ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=FUTURE
Zone Setup Screen #3
Zones Enabled Screen
This display will show all of the zones that are enabled in the control panel.
3.6.3.6 Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar to the following:
ZONES DISABLED 03
Zones Disabled Screen
This display will show all of the zones that are disabled in the control panel.
3.6.3.7 Zone Type
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a screen similar to the following:
ZONE TYPE PROG 1=Z00 MONITOR 2=Z01 MONITOR 3=Z02 MONITOR
Zones Installed Screen
MS-9050UD PN 52413:B 8/29/07 85
Programming Master Programming Level
The Zones Installed screen will show the system zones (default and user programmed) and their associated types. Note that an up and/or down arrow will appear in the upper right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow keys to view zones Z00 through Z19.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each Zones Installed Screen. Available zone types will be displayed in the resultant screens. For example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following screens will be displayed:
ZONE TYPE PROG 1=MONITOR 2=SMOKE PHOTO 3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG 1=HEAT 2=PULL STATION 3=DUCT
Zone Type Program Screen #2
ZONE TYPE PROG 1=MEDICAL 2=HAZARD 3=TAMPER
ZONE TYPE PROG 1=SUPERVISORY 2=PROC. MON 3=SMOKE ION
Zone Type Program Screen #4
ZONE TYPE PROG 1=NONE
Zone Type Program Screen #5
Zone Type Program Screen #3
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow silenceable same zone can feature.
To program a waterflow circuit as nonsilenceable
Note: Zone Types are only relevant for Central Station reporting. Changing a zone type will only
change how it is reported to the Central Station.
86 MS-9050UD PN 52413:B 8/29/07
zone type to the selected zone. Any signaling devices programmed to the
be silenced by pressing the Alarm Silence key or by using the auto-silence
, refer to "System Setup" on page 88.
Master Programming Level Programming
ZONE SETUP 1=ZONE TYPES 2=ZONES AVAILABLE 3=FUTURE
Zone Setup Screen #3
3.6.3.8 Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
ZONES AVAILABLE 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19
The display will show all of the zones that are still available for programming.
PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP
Programming Screen #2
3.6.4 Loop Setup
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 wiring and to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the following screen to be displayed:
LOOP SETUP 1=STYLE 4 2=PROTOCOL CLIP
Loop Setup Screen
3.6.4.1 Style
T o program the SLC Style for the loop, press 1 for Style, while viewing Loop Setup Screen. In the preceding example, the control panel is programmed for Style 4 SLC wiring as indicated by the 4 to the right of Style in the display. To change the style, press 1 to toggle the display to read
Style 6. Each press of the 1 key will cause the display to toggle between Style 4 and Style 6. Note that, when programming the Loop Style, the programmer can only select between Style 4 and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop Setup for Style 6. S tyle 7 wiring is the same as Style 6 with the added requir ement that each device on the loop must have a pair of isolator modules, one on each side. The factory default setting is Style 4.
Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for Style 6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired, the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear the SLC trouble.
3.6.4.2 Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. The only mode available is CLIP (Classic Loop Interface Protocol) which is used for the older legacy addressable devices such as the M300 Series modules and detectors as well as the newer devices. Pressing 2 while viewing the Loop Setup Screen will have no effect on programming.
Device Addressing
It is important to note that the MS-9050UD addressable device capacity is 50 detectors and control/monitor modules. Addressable devices must not Programming will not allow addresses higher than 50.
Important: Detectors and Modules cannot have the same address. For example, if a detector is installed at address 04, you cannot also have a module at address 04.
Note that It is permissible to mix old and new devices on the same loop.
MS-9050UD PN 52413:B 8/29/07 87
be set to addresses higher than 50.
Programming Master Programming Level
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
Tr ouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or trouble still exists on the FACP after the control panel has been silenced. The control panel piezo sounder will pulse once every 15 seconds during an alarm and every two minutes during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The piezo will continue to sound at these rates until the alarm or trouble condition is cleared.
Trouble Resound is independent of Trouble Reminder. If a silenced trouble condition is not cleared by midnight, the panel will reactivate the trouble sounder.
Banner: This option allows the user to change the top two lines of the LCD display from the factory default readout to a user defined readout when the control panel is in Normal condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12 hr), date and daylight savings time feature into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time delay, Pre-Signal time delay and Waterflow time delay.
NACs: This feature allows the programmer to configure the control panel Notification Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable, autosilence, coding, silence inhibit, zone assignment and enable/disable.
Relays: This option allows programming of two onboard relays for activation by various control panel events, such as alarm, trouble, supervisory, etc.
Canadian Option: This option allows the automatic programming of ionization smoke detector sensitivity thresholds to Canadian specifications.
W aterflow Silenceable: This option provides the ability to silence any output circuit activated by a monitor module programmed as a waterflow type.
PROGRAMMING 1=LOOP SETUP 2=SYSTEM SETUP 3=VERIFY LOOP
Programming Screen #2
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following screens to be displayed:
SYSTEM SETUP 1=TROUBLE REM OFF 2=BANNER 3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
SYSTEM SETUP 1=CANADIAN OPT. OFF 2=WATERFLOW SIL. NO
System Setup Screen #3
88 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
BANNER 1=FACTORY 2=USER DEFINED
Banner Screen
See Page
3.6.5.1 Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 88, for a detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will cause the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1 key will cause the display to toggle between Trouble Rem On and Trouble Rem Off.
3.6.5.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be displayed:
BANNER 1=FACTORY 2=USER DEFINED
Banner Screen
Pressing 1 while viewing the Banner Screen will select the factory default banner setting and display the following screen:
FACTORY BANNER
Factory Banner Screen
Pressing the Enter key will store this selection in nonvolatile memory and return the display to the Banner Screen.
Pressing 2 while viewing the Banner Screen will cause the following screens to be displayed:
USER DEFINED BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
USER BANNER - LINE 2 PRESS ENTER IF OK ************
User Defined Banner Screen #2
MS-9050UD PN 52413:B 8/29/07 89
Programming Master Programming Level
SYSTEM SETUP 1=TROUBLE REM 2=BANNER 3=TIME-DATE
System Setup Screen #1
These screens allow the programmer to enter a two line custom banner. A flashing cursor will appear in the bottom left corner of each display. A maximum of 20 characters (including spaces) can be entered into each screen for a total of two lines with 40 characters. After entering up to 20 characters in the first screen, press Enter to view the second screen. Enter up to 20 characters in the second screen in the same manner or just press Enter if a second banner line is not being entered. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ) key four times to place a blank in the desired position. When all characters have been entered, press the Enter key to store the information. The display will return to the Banner Screen.
3.6.5.3 Time-Date
The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen #1. The following screen will be displayed:
TIME AND DATE 1=TIME 10:00 AM 2=DATE 09-07-2009 3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE 1=DAYLIGHT SAVINGS
Time-Date Screen #2
3.6.5.3.1 Time
T o change the time, press 1 while viewing the Time-Date Screen. The following screen will be displayed:
ENTER TIME
10:00 AM 1=AM 2=PM
Time Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current time. To change the time, enter the two-d igi t hours followed by the two-dig it minutes. The cursor will move one position to the right each time a digit is entered. After the last minutes digit is entered, the cursor will again move one position to the right. At this point enter 1 for AM or 2 for PM. The display will then return to the Time-Date Screen which will show the new time entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and begin again.
90 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
3.6.5.3.2 Date
T o change the date, press 2 while viewing the Time-Date Screen. The following screen will be displayed:
ENTER DATE
MONTH DAY YEAR 09-07-2005
Date Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current date. To change the date, enter the two-digit month fol lowed by the two-digit day and then the two-digit year (01 for 2001, 02 for 2002, etc.). The cursor will move one position to the right each time a digit is entered. After the last year digit is entered, the display will return to the Time-Date Screen which will show the new date entry. If an error is made while entering a digit, press the CLR key to delete the entire entry and begin again.
3.6.5.3.3 Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time. Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display .
Note: If the clock is changed to 24 hour (military) format, the date will change to the European standard of Day-Month-Year (for display purposes only).
TIME AND DATE 1=DAYLIGHT SAVINGS
Time & Date Screen #2
3.6.5.3.4 Daylight Savings Time
Pressing 1 while viewing Ti me-Date Screen #2 will cause the following screens to be displayed:
DAYLIGHT SAVINGS 1=ENABLED YES 2=START MONTH MAR 3=START WEEK WEEK-1
Daylight Savings Screen #1
DAYLIGHT SAVINGS 1=END MONTH NOV 2=END WEEK LAST-W
Daylight Savings Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected. Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows
the programmer to select the month that daylight savings time will begin. In this sub-screen, pressing 1 will select March, 2 will select April and 3 will select May.
MS-9050UD PN 52413:B 8/29/07 91
Programming Master Programming Level
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will begin. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third week, while in the second sub-screen, pressing 1 will select the fourth week and 2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows the programmer to select the month that daylight savings time will end. In this sub-screen, pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow the programmer to select the week of the month that daylight savings time will end. In the first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will select the last week of the selected month.
3.6.5.4 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while viewing System Setup Screen #2. The following screen will be displayed:
TIMERS 1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
TIMERS 1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
Timer Screen #1
Timer Screen #1
TIMERS 1=AC LOSS DELAY 000
Timer Screen #2
3.6.5.4.1 PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180 seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The following display will appear:
PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
92 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
3.6.5.4.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen #1. The following screen will be displayed:
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
TIMER 1=PAS DELAY 000 2=PRE SIGNAL 000 3=WATERFLOW 000
Timer Screen #1
Note that detectors can be programmed for either PAS or Pre-signal operation, not both. Refer to "Edit Detector" on page 57 for programming details.
3.6.5.4.3 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any built-in delays of the waterflow device. The factory default setting for Waterflow delay is 000 for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow delay, press 3 while viewing Timer Screen #1. The following screen will be displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Scr een
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the time delay will be stored in the control panel memory and the display will return to the Delay Screen which will indicate the new delay time.
MS-9050UD PN 52413:B 8/29/07 93
Programming Master Programming Level
TIMER 1=AC LOSS DELAY
Timer Screen #2
3.6.5.4.4 AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length of the desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY 1=NO DELAY 2=ENTER DELAY
AC Loss Delay Screen #1
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
AC LOSS DELAY
RANGE 00-23
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
AC Loss Delay Screen #2
A flashing cursor will appear in the lower left corner of the display. The factory default setting is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note: Upon the loss of AC power at the control panel, relays programmed for ‘AC Loss’ will transfer immediately, regardless of the AC Loss Delay setting. If no troubles exist at the panel other than AC Loss, the System Trouble relay will delay its activation for the duration of the AC Loss Delay setting.
3.6.5.5 NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configure by pressing 2 while viewing System Setup Screen #2. The following screens will be displayed:
NACS 1=NAC 1 2=NAC 2
NAC Selection Screen
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1 or 2 for NAC 2.
94 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
The following screens will be displayed for each selection:
NAC # 1=ENABLED YES 2=TYPE BELL 3=SILENCEABLE YES
NAC Screen #1
NAC # 1=AUTO SILENCE 00 2=CODING TEMPORAL
NAC Screen #2
NAC # 1=ZONE 00 00 00 00 00 2=SIL INHIBITED NO
NAC Screen #3
NAC # 1=SYNC TYPE S
NAC Screen #4
3.6.5.5.1 Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
MS-9050UD PN 52413:B 8/29/07 95
Programming Master Programming Level
3.6.5.5.2 Type
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1. The following screen will be displayed. Press the down arrow key to view additional screens:
NAC # 1=ENABLED 2=TYPE 3=SILENCEABLE
NAC Screen #1
NAC TYPE 1=BELL 2=HORN 3=STROBE
Type Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate screen. When the selection is made, the display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
NAC Type Code Special Function
Bell None Horn None Strobe None Synced Strobe Synchronized to manufacturer Strobe Sil Sync Same as Synced Strobe but Silence turns off audible & visual devices Door Holder
Reset Power Non-Reset Power
Table Footnote
NAC normally active NAC normally active NAC normally active
1. Important: User should be aware that selecting Door Holder, Reset Power
or Non-Reset Power types for an NAC will immediately activate (turn on) the NAC circuit and any devices connected to it.
1
1 1
3.6.5.5.3 Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This will prevent the selected main circuit board NAC from being silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the synchronization feature is selected, only the audible devices will be turned off if the Silence key is pressed or if the Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate.
96 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
3.6.5.5.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notification appliances after a programmed length of time. To enable this feature and program the time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following screens will be displayed:
NAC # 1=AUTO SILENCE 2=CODING TEMPORAL
NAC Screen #2
AUTO SILENCE 1=NO 2=5 MINUTES 3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE 1=15 MINUTES 2=20 MINUTES 3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE 1=30 MINUTES
Auto Silence Screen #3
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To enable the Auto Silence feature, press the number corresponding to the time delay which will elapse before Auto Silence activates. This information will be stored in memory and the display will return to NAC Screen #2.
Note: All silenceable contro l modules will be controlled by the Autosilence timer for NAC 1.
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type)
The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when activated. Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear:
CODING 1=STEADY 2=MARCH TIME 3=CALIFORNIA
Coding Screen #1
CODING 1=TEMPORAL 2=TWO STAGE 3 MIN 3=TWO STAGE 5 MIN
Coding Screen #2
MS-9050UD PN 52413:B 8/29/07 97
Programming Master Programming Level
The programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding selections are:
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second off
Two Stage 3 Minutes or 5 Minutes - Refer to “Two Stage Operation” on page 98. for a description of this feature
Selection of one of the above options will cause the control panel to store the information in memory and return the display to NAC Screen #2, which will display the new coding choice.
3.6.5.5.5.1 Two Stage Operation
Two Stage operation consists of the following:
1st stage output - 20 ppm (pulse-per-minute) coding
2nd stage output - Temporal coding as described above
If Two Stage operation is programmed as the Coding option, the following sequence of events will occur during an alarm.
1. The on-board NACs which are programmed to General Alarm Zone 0 will activate with a
1st stage output upon activation of any alarm point
2. If the activated alarm point is directly mapped to a zone which is programmed to an on-
board NAC, that NAC will go directly to 2nd stage coding output. All other NACs not directly mapped to the activated alarm point’s zone but assigned to Zone 0 will activate with a 1st stage output
3. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not
been
pressed, all NACs presently in 1st stage activation will go to 2nd stage activation
4. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation
will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already in 2nd stage activation
5. If another alarm point is activated and the countdown timer is counting, the alarm point
will have no effect on the NACs unless the alarm point’s zones are directly mapped to one of the NACs, in which case it will follow the procedure outlined in step 2
6. If another alarm point is activated and the countdown timer has stopped counting due to
the Acknowledge switch being pressed, the countdown timer will restart and the NACs will respond as outlined in step 2. NACs already in 2nd stage activation will not be affected
7. Any control modules assigned to special Zone 19 will be activated either by direct
mapping of an input device programmed to Zone 19 or if an NAC enters 2nd stage operation
8. Control modules that are programmed to the same zone as the activated input device will
not be delayed for activation
98 MS-9050UD PN 52413:B 8/29/07
Master Programming Level Programming
3.6.5.5.6 Zone
A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1 while viewing NAC Screen #3 displays the following screen:
ZONE ASSIGNMENT
NAC # 1=ZONE 00 00 00 00 00 2=SIL INHIBITED NO
NAC Screen #3
Z00 Z** Z** Z** Z**
Zone Screen
Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned to this NAC. The cursor moves to the next Z** designation. Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zone Z00. When all desired changes have been made, press the Enter key to store the zone assignments. The display will return to the NAC Screen #3 which will show the zone assignments just entered.
Note: Zones do not apply to NACs programmed as Door Holder, Reset Power or Non-Reset Power.
3.6.5.5.7 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit board NAC for a period of one minute. Resetting the FACP will also be prevented for one minute while the NAC programmed for silence inhibit is activated. Pressing 2 while viewing NAC Screen #3 will cause the display to change from the factory default of Silence Inhibit No to Silence Inhibit Yes. Each press of the 2 key will cause the display to toggle between the two options.
3.6.5.5.8 Sync Type
If synchronized strobes were selected as the Type of device installed, the type of synchronization must be selected in this option. Pressing 1 while viewing NAC Screen #4 will cause the following screen to be displayed:
NAC # 1=SYNC TYPE
NAC Screen #4
NAC SYNC TYPE 1=SYSTEM SENSOR 2=WHEELOCK 3=GENTEX
Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select Wheelock and 3 will select Gentex.
3.6.5.5.8.1 Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the manufacturer’s documentation supplied with the Strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following is a list of the strobes that have been tested with this FACP and the maximum number that can be connected to each NAC. Make sure that the NAC maximum current is not exceeded:
System Sensor: 40 StrobesWheelock: 25 StrobesGentex: 23 Strobes
MS-9050UD PN 52413:B 8/29/07 99
Programming Master Programming Level
SYSTEM SETUP 1=TIMERS 2=NAC 3=RELAYS
System Setup Screen #2
3.6.5.6 Relays
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two main circuit board Form-C relays from the following screen:
RELAYS 1=RELAY 1 2=RELAY 2 3=RELAY 3
Relays Selection Screen
T o program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming. The following screen will appear for each relay to be programmed:
RELAY # 1=TYPE ALARM
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be displayed:
RELAY 1=ALARM 2=SUPERVISORY 3=SUPERVISORY AR
Relay Screen #1
RELAY 1=TROUBLE 2=COMM FAIL 3=PROCESS MON
Relay Screen #2
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice. Press the Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
Relay Type Screen
RELAY 1=PROCESS MON AR 2=AC LOSS 3=HAZARD
Relay Screen #3
RELAY 1=MEDICAL 2=SILENCEABLE ALARM
Relay Screen #4
Notes:
1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the Supervisory and/or Process Monitor type code, when activated, will automatically reset when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and reset when the alarm is cleared and/or when the Alarm Silence button is pressed.
100 MS-9050UD PN 52413:B 8/29/07
Loading...