IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
Document #52413
8/29/07 Revision:
B
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
1.1: Features and Options...................................................................................................................................12
1.2.1: Current Availability...........................................................................................................................14
1.3: Controls and Indicators........................................................................................... .....................................14
1.8.3: Trim Ring..........................................................................................................................................18
2.6: UL Power-limited Wiring Requirements....................................................................................................45
2.7: Digital Communicator.................................................................................................................................46
3.1: Programming Data Entry ............................................................................................................................50
3.2: User Programming ............................ ..................................................... .....................................................51
3.5: Programming and Passwords ......................................................................................................................52
3.6.2: Point Program........................................................................................ ............................................56
3.6.2.2.3 Edit Module Screen for Monitor Module ............................................................................67
3.6.2.2.4 Edit Module Screen for Control Modules ............................................................................76
3.6.3: Zone Setup ........................................................................................................................................83
3.6.5: System Setup................................ ...................................................... ...............................................88
3.6.5.3.1 Time .....................................................................................................................................90
3.6.5.3.2 Date ......................................................................................................................................91
3.6.5.3.3 Clock Format ........................................................................................................................91
3.6.5.3.4 Daylight Savings Time .........................................................................................................91
3.6.5.5.2 Type ........................................................................................ ..............................................96
3.6.5.5.4 Auto Silence .........................................................................................................................97
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type) .........................................97
3.6.5.5.6 Zone ........................................................................................ ..............................................99
3.6.12: Program Check................................................................................................................................137
3.7.3: Program Check..................................................................................................................................142
3.7.6: Zone Setup.........................................................................................................................................145
4.1: Panel Control Buttons..................................................................................................................................147
4.2: Status Indicators and LEDs.........................................................................................................................148
4.3: Normal Operation........................................................................................................................................149
4.7: Process Monitor Operation..........................................................................................................................153
4.20: Special System Timers..............................................................................................................................157
4.22.1: System Point ....................................... ............................................................................................160
4.22.8: Program Check................................................................................................................................165
4.22.12: Central Station...............................................................................................................................167
4.22.13: Service Terminal ...........................................................................................................................168
6.2: Transferring a Program........................... .....................................................................................................178
7.2: Calculating the AC Branch Circuit .............................................................................................................180
7.3: Calculating the System Current Draw............................................................. ............................................181
7.4.2: Selecting and Locating Batteries.......................................................................................................183
APPENDIX A: Software Zones ............................................................................................................................184
APPENDIX F: HVAC Control ........................................................................................ .....................................198
F.1: Control Module Operation .........................................................................................................................198
G.1: Transmission Format Between DACT and Receiver ................................................................................200
G.2: Ademco Contact ID Typical Printout ........................................................................................................200
8
MS-9050UD P/N: 52413:B 8/29/07
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
•CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and System
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9050UD PN 52413:B 8/29/079
9050udlayo90.cdr
Black
Red
Green
EIA-232 to
personal computer
2 Programmable Relays &
White
(Nonsupervised,
Upload/Download Utility.
personal computer with FACP
Power-limited (Class 2) Circuit)
50 foot maximum within same room.
1 Fixed Trouble Relay
Nonsupervised Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Conta c ts shown below in normal
9 8 7 6
DB9F
5 4 3 2 1
NC NO C
A Fail Safe Trouble
relay switches to the
NO position du r i n g
trouble co nd itions and
conditi on (AC power with no al ar m ,
trouble or supervisory activity).
under loss of all power.
(*)Factory default relay programming
N
G
DTR
X
M
R
C
Supervisory*
Alarm*Trouble
8
D
7
6
T
5
V
RCV XMT DTR GND
PWR
ANN-BUS
C
NC
NO NC C
NONC
NO
NC NO C
NC
CC
NO NC C
NO
J5
J4
Remove this jumper to enable
Supervisory relay wh en
4XTMF module is installed
TB7TB3
JP2
TB6
Cut JP28 to
supervise
4XTMF
JP1
JP28
TB5
J11
SW1
TROUBLE
FIRE ALARM
Basic System Connections
6
BA
AB
5
A
SHIELD
4
A
-
3
B
-
SLC
+
2
1
B
SLC Loop
Manual for detailed
Refer to the SLC Wiring
Supervised Ci rcuit)
for Style 4, 6 and 7.
addressable devices
information on wiring
(Power- Limit ed, Clas s 2
+
B+ A+ B- A-
4XTMF
TB2
LCD DISPLAY
J9
J3
J8
AC POWER
KISSOFF
ALARM
ST
1
DEF
3
ABC
2
1
LED1
LED2
LED3
CLEAR
6
JKL
5
GHI
4
ENTER
DRILL
ESC
MODE
_/.
#
89
QZ_
PRS TUV
7
PH2
DACT Phone
Line Jacks
(nonpower-limited,
supervised)
PH1
J6
RESET
PS2 Keyboard Interface
0
*
B
-
78
A
+
NAC #2
+
Special Application Power
NAC #1
+
+
+
+
-
A
+
NAC2
56
B
+
4
B
-
A
-
23
A
+
NAC1
1
B
+
B+B-B-B+A+ A-A+ A-
-
TB1
Charger Enable/Disable
Switch (shown in charger
enable position)
SW27
+
_
J1
BATTERY
Battery
24 VDC, nonpowe r - l im it e d,
supervised, 18 Amp Hour max.
J2
Notification Appliance Circuits
ELR 4.7K, ½W
2.5 amps m a x. per circuit . Tota l available current 2.5 amps.
Connector
Supervised
NAC #2 Shown Style Z (Class A) (Power-Limit ed, Class 2, Su pervised)
NAC #1 Shown Style Y (Class B) (Power-Limited, Class 2, Supervised)
For specific UL wiring
information, refer to "UL
Power-limited Wiring
Requirements" on page 45
Transformer
CAUTION!
HIGH VOLTAGE
Nonpower-limited,
10MS-9050UD PN 52413:B 8/29/07
Peripheral Devices
ANN-BUS
ANN-80
Text Annunciator
Doc. #52749
SLC Loop
ANN-I/O
LED Driver
Doc. #151416
ANN-RLY
10 Form-C Relay Card
Doc. #53033
4XTMF
Municipal Box Transmitter
Addressable Devices and SLC Wiring
ANN-S/PG
Printer Driver
Doc. #151417
ANN-(R)LED
LED Display
Doc. #53032
Doc. #51309
Battery Connector
CHG-120F Charger
Doc. #50888
RS-232
Local PC
9050UDperi.cdr
CHG-75 Charger
Doc. #51315
MS-9050UD PN 52413:B 8/29/0711
Product DescriptionFeatures and Options
SECTION 1Product Description
The MS-9050UDis a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm
Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent
addressable control panel has an extensive list of powerful features. The combination of Fire-Lite’s
newer series devices and legacy 300 Series devices, along with the MS-9050UD FACP, offer the
latest in fire protection technology. The power supply and all electronics are contained on a single
circuit board housed in a metal cabinet, providing a complete fire control system for most
applications. Available accessories include local and remote upload/download software, remote
annunciators and reverse polarity/city box transmitter.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PK-CD Upload/Download utility via the public switched telephone
network. Any personal computer with Windows
speed of 2400 baud or faster and Upload/Download software kit PK-CD, may serve as a Service
T erminal. This allows download of the entire program or upload of the entire program, history file,
walktest data and current status.
Inventory
When the MS-9050UD shipment is received, check to make certain that all parts have been
included in the shipment. The MS-9050UD shipment should consis t of one of each of the
following:
™
XP or newer, and compatible modem with a
main circu it board with display
chassis with transformer
backbox wit h doo r
plastic bag containing screws, cables, key, etc.
manual
1.1 Features and Options
•Built-in DACT (Digital Alarm Communicator/Transmitter) with remote upload/download
•Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
•50 addressable device capacity (any combination of addressable detectors and addressable
control/relay/monitor modules totalling 50)
•20 software zones
•Two onboard NACs (Notification Appli ance Circ ui ts) which can be configured as Style Y
(Class B) or Style Z (Class A) circuits
•2.5 amps total power for NACs
•2.7 amps total system power (includes battery charger)
•Two programmable relays and one fixed trouble relay
•Built-in Programmer
•Telephone Line Active LEDs
•Communication Confirmation (Kissoff) LED
•Touchtone/Rotary di aling
•EIA-232 PC interface for local upload/download
•80-character LCD display (backlit)
12MS-9050UD PN 52413:B 8/29/07
SpecificationsProduct Description
•Real-time clock/calendar with daylight savings time control
•History file with 500 event capacity
•Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automa tic devi ce type-code veri fication
Point trouble identification
•Waterflow selection per module point
•Alarm verification selection per detector point
•Walktest, silent or audible
•PAS (Positive Alarm Sequence) per addressable detector and Pre-signal per point (NFPA 72
compliant)
•Silence inhibit timer option per NAC
•Autosilence timer option per NAC
•Continuous, March Time, Temporal or California code for main circuit board NACs with
two-stage capability
•Selectable strobe synchronization per NAC
•Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote
annunciator
•Auto-program (learn mode) reduces installation time. Reports two devices set to the same
address
•Password and key-protected nonvolatile memory
•User programmable password
•Fully programmable from local keypad or optional keyboard
•SLC operates up to 10,000 ft. (3,000 m) with twisted, unshield ed fire wire
•Compatible with Fire-Lite’ addressable devices (refer to SLC Wiring Manual)
•Compatible with legacy Fire-Lite 300 Series addressable devices (refer to SLC Wiring
Manual)
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.2 amp
Maximum Battery Charger Capacity: 18 Amp Hour, (FACP cabinet holds maximum of two 18
Amp Hour batteries)
Minimum Battery: 7 Amp Hour
Nonpower-limited, supervised
MS-9050UD PN 52413:B 8/29/0713
2
) with 600 V insulation
Product DescriptionControls and Indicators
SLC Communication Loop - TB2
24 VDC nominal, 27.6 VDC maximum
Maximum length is 10,000 ft. (3,000 m) total twisted, unshielded fire wire
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited circuit
Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB1
Terminal Block provides connections fo r two NACs, Style Y (Class B) or
Style Z (Class A)
Special Application power
Power-limited, supervised circuitry
Maximum voltage drop in wiring: 2.0 VDC
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.5 amps
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC
Refer to Fire-Lite Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays, nonpower-limited, nonsupervised
Refer to Figure 2.5 on page 43 for information on power-limited relay circuit wiring
Annunciator connector: Terminal 1 (Ground), 2 (Power), 3 (A), 4 (B)
Nominal Operating Voltage: 24 VDC
Maximum Current (Terminals 1 & 2): 500 mA
Power-limited, supervised
1.2.1 Current Availability
The Notification Appliance Circuits can provide 2.5 amps maximum per circuit. Total available
current for the FACP is 2.7 amps.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•AC Power (green)
•Fire Alarm (red)
•Supervisory (yellow)
•Trouble (yellow)
•Alarm Silenced signals (yellow)
SYSTEM ALL NORMAL
10:00A 092105
14MS-9050UD PN 52413:B 8/29/07
CircuitsProduct Description
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
•Acknowledge/Step
•Alarm Silenced
•Drill (Manual Evacuate)
•Reset (lamp test)
Service/program keys:
•Keys labeled 1 to 9
•* key
•# key
•0 (recall) key
•1st Event key
•Clear key
•Escape key
•Mode key
•Four cursor keys (up, down, left and right)
•Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory
conditions.
Figure 1.1 Membrane/Display Panel
9050udkypd.cdr
1.4 Circuits
Reference
Manual
SLC Communication Loop
One SLC loop is provided on the FACP main circuit board. The SLC loop, configurable for NFPA
Style 4, 6 or 7, provides communication to addressable detectors, monitor (initiating device) and
control (output device) modules. Refer to the SLC Wiring manual for information on wiring
devices.
Output Circuits
The following output circuits are available on the FACP:
•Charger
24 VDC Battery Charger (up to 18 AH batteries)
•NAC (Notification Appliance Circuits)
Two NACs configurable for Style Y (Class B) or Style Z (Class A), are provided with various
programmable features.
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe
relay monitors system trouble and the two programmable relays are factory default programmed for
system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5
amps @ 30 VAC (resistive). The programmable relays can be programmed for the following
operations:
•fire alarm
•silenceable alarm
•trouble
•supervisory
•supervisory auto-resettable
•DACT communication failure
•process monitor
•process monitor auto-resettable
•hazard alert
•medical alert
•AC loss
1.5 Digital Alarm Communicator/Transmitter
T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the
following functions:
•Line Seizure: takes control of the phone lines disconnecting any premises phones
•Off/On Hook: performs on and off-hook status to the phone lines
•Dialing the Central Station(s) number: default is Touch-Tone
®
, programmable to rotary
•For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
•Communicate in the following formats:
12 Tone Burst types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
3 Touchtone Types
4+1 Ademco Express
4+2 Ademco Express
Ademco Contact ID
16MS-9050UD PN 52413:B 8/29/07
ComponentsProduct Description
1.6 Components
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and
wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main
circuit board. The circuit board is delivered mounted to a chassis in the MS-9050UD backbox
See Page
(refer to circuit board illustration on page 10).
Cabinet
The MS-9050UD backbox provides space for two batteries (up to 18 Amp
Hour). Ample knockouts are provided for system wiring. Also available is
an optional dress panel, which mounts to the inside of the cabinet (required
by ULC for Canadian installations). The dress panel must be installed to
meet FM requirements.
MS_9050UD.cdr
Reference
Manual
Batteries
The MS-9050UD cabinet provides space for two
batteries (up to 18 Amp Hour). Batteries must be
ordered separately.
Battery Cable P/N 75203
-
+
+
-
9200batt.cdr
1.6.1 Intelligent Addressable
Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling
Line Circuit (refer to the SLC Wiring Manual for detailed information on addressable devices,
device installation, wiring and operation). This allows the control panel to continually process the
information to determine the status (alarm, trouble, maintenance or normal) of each detector . Each
detector responds to an SLC address that is set in the detector head using built-in rotary decimal
switches. Note that a blinking LED on an intelligent detector indicates communication between the
detector and the control panel. Refer to the Fire-Lite Device Compatibility Document for a list of
approved conventional detectors.
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the
control panel and conventional notification and initiating devices. Each module can be set to
respond to an address with built-in rotary switches. A blinking LED on a monitor module indicates
communication between the module and the control panel. These devices can also be used when
installed on older systems. Refer to the SLC Wiring Manual for information on addressable
devices. Refer to the Fire-Lite Device Compatibility Document for a list of approved conventional
notification and initiating devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9050UD
FACP. Refer to the SLC Wiring Manual for device information.
1.6.4 Device Accessories
End-of-Line Resistor Assembly
Refer to the SLC Wiring Manual for device information. The 47 kΩ End-of-Line Resistor
assembly (P/N: R-47K) is used to supervise the MMF-300, MDF-300, MMF-301 and CMF-300
module circuits. The 3.9 kΩ End-of-Line Resistor assembly is used to supervise the MMF-302
module circuit. The End-of-Line resistors are included with each module.
MS-9050UD PN 52413:B 8/29/0717
Product DescriptionOptional Modules
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4-wire smoke
detectors and notification appliances.
N-ELR Mounting Plate
The N-ELR is a single End-of-Line resistor plate which is required for use in Canada. An ELR,
which is supplied with each module and fire alarm control panel, is mounted to the ELR plate.
Resistors mounted to the N-ELR plate can be used for the supervision of a monitor and control
module circuit.
1.7 Optional Modules
The MS-9050UD main circuit board includes option module connectors for the followin g mo dule:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the
module is used to select an option which allows the reverse polarity circuit to open with a system
trouble condition if no alarm condition exists. The module plugs into connectors J8 and J9 which
are located near the top center of the main circuit board. When the 4XTMF module is installed,
Jumper JP28, on the main circuit board, must be cut to allow supervision of the module.
1.8 Accessories
1.8.1 PK-CD Programming Utility
The PK-CD Programming Utility can be used to locally or remotely program an MS-9050UD
directly from most IBM compatible personal computers (PC), running Windows
MS-9050UD program files can also be created and stored on the PC and then downloaded to the
control panel. The PK-CD Kit includes the MS-9050UD Windows-based Programming Utility
software on CD-ROM with on-line help file. A serial cable (P/N: PRT/PK-CABLE), which must
be purchased separately, is required for local connection of the PC to the RS-232 (PC/Printer)
terminals at TB3 of the MS-9050UD main circuit board. Remote programming requires that the
PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for
remote download (refer to "Remote Download" on page 177). Remote interrogation of panel
programming, history logs, detector status, etc., is possible without enabling the remote download
option.
1.8.2 Dress Panel
An optional dress panel (DP-51050) is available for the MS-9050UD (required by ULC for
Canadian installations). The dress panel restricts access to the system wiring while allowing access
to the key panel. The dress panel must be installed to meet FM requirements.
1.8.3 Trim Ring
™ XP (or newer).
An optional Trim Ring (TR-CE) is available for semi-flush mounting of the FACP backbox.
18MS-9050UD PN 52413:B 8/29/07
ANN-BUS DevicesProduct Description
1.9 ANN-BUS Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any
modules or wiring.
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit.
Compatible devices include:
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).
1.9.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the
maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is
necessary to calculate the total worst case current draw for all modules on a single 4-conductor
bus. The total worst case current draw is calculated by adding the individual worst case
currents for each module. The individual worst case values are shown in the following table:
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp. If current
draw exceeds 0.5 amps, refer to "Powering ANN-BUS Devices fr om Auxiliary Power Supply"
on page 22.
MS-9050UD PN 52413:B 8/29/0719
Product DescriptionANN-BUS Devices
After calculating the total worst case current draw, Table 1.1 specifies the maximum distance
the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wi re
gauges, capacitance is the limiting factor. These cases are marked in the chart with an asterisk
(*). Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used.
The formula used to generate this chart is shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case
Current Draw (amps)
0.1001,852 ft.4,688 ft.* 6,000 ft.*6,000 ft.
0.200926 ft.2,344 ft.3,731 ft.5,906 ft.
0.300617 ft.1,563 ft.2,488 ft.3,937 ft.
0.400463 ft.1,172 ft.1,866 ft.2,953 ft.
0.500370 ft.938 ft.1,493 ft.2,362 ft.
22 Gauge18 Gauge16 Gauge14 Gauge
Table 1.1 Wiring Distances
Note: The following formulas were used to generate the wire distance chart:
6.0 Volts
Maximum Resistance (Ohms)=Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)=Maximum Resistance (Ohms)*500
(6,000 feet maximum)Rpu
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire GaugeOhms per 1,000 feet (Rpu)
2216.2
186.4
164.02
142.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring
limitations:
Wire GaugeMaximum Wire Length
18312 feet
16497 feet
14787 feet
121,250 feet
20MS-9050UD PN 52413:B 8/29/07
ANN-BUS DevicesProduct Description
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
The total worst case current is calculated as follows:
ANN-80 Current Draw= 3 X 0.040 amps= 0.120 amps
ANN-S/PG Current Draw= 1 X.0.040 amps= 0.040 amps
ANN-I/O Current Draw= 1 X.0.200 amps= 0.200 amps
Total Worst Case Current Draw= 0.360 amps
Using this value and referring to the Wiring Distance Table 1.1 on page 20, it can be found that
the available options are:
463 feet maximum using 22 Gauge wire
1,172 feet maximu m using 18 Gauge wire
1,866 feet maximu m using 16 Gauge wire
2,953 feet maximu m using 14 Gauge wire
1.9.1.2 Wiring Configuration
Figure 1.2 illustrates the wiring between the FACP and ANN-BUS devices.
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS Device
MS-9050UD
Figure 1.2 FACP wiring to ANN-BUS Device
MS-9050UD PN 52413:B 8/29/0721
Product DescriptionANN-BUS Devices
1.9.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 1.3 illustrates the powering of ANN-BUS devices from an auxiliary power supply such
as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANNBUS power requirements.
ANN-BUS and power wiring are
supervised and power-limited
-24 VDC
+24 VDC
ANN-BUS
ANN-80
MS-9050UD
FCPS-24FS6/8
Figure 1.3 Powering ANN-BUS Devices from FCPS-24FS6/8
1.9.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
F ACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 104).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
AddressSwitch 5Switch 4Switch 3Switch 2Switch 1
not validOFFOFFOFFOFFOFF
01OFFOFFOFFOFFON
02OFFOFFOFFONOFF
03OFFOFFOFFONON
04OFFOFFONOFFOFF
05OFFOFFONOFFON
06OFFOFFONONOFF
07OFFOFFONONON
08OFFONOFFOFFOFF
Note: Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
22MS-9050UD PN 52413:B 8/29/07
ANN-BUS DevicesProduct Description
1.9.3 ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator which
mimics the FACP display. It also provides system status indicators for AC Power, Alarm, Trouble,
Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and FACP is
accomplished over a two wire serial interface employing the ANN-BUS communication format.
The devices are powered, via two additional wires, from either the host FACP or remote UL-listed,
filtered, power supply.
1.9.3.1 Specifications
•Operating Voltage Range: 18 VDC to 28 VDC
•Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal /Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail ( not backlit): 15.0 mA
•For use indoors in a dry location
1.9.3.2 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the
annunciator.
1.9.3.3 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical
box. Select and remove the appropriate knockout(s), pull the necessary wires through the
knockouts and mount the annunciator in or on the wall depending on the type of installation
desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the
annunciator to the electrical box/wall. The cover cannot be reattached or removed after the
annunciator has been mounted.
1.9.3.4 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the
terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. T o close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Annunciator cover with LCD display
Annunciator backplate
Press in latch and pull
annunciator cover open
Key switch shown in ON position
MS-9050UD PN 52413:B 8/29/0723
Product DescriptionANN-BUS Devices
1.9.3.5 Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator . Make certain all power has
been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring chan nel and then to ANN-80 terminal
block TB1
wiring channel
wires
TB1
2. Remove appropriate amount of wire insulation
3. Connect the wiring from the F ACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1
terminals 3 & 4. Make certain to connect A to A and B to B
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2
(+). Make certain to observe proper polarity
6. If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity
7. After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical
box
24MS-9050UD PN 52413:B 8/29/07
ANN-BUS DevicesProduct Description
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
FACP
Figure 1.4 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the MS-9050UD.
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must added to the system via FACP programming. Refer to the programming section titled "ANNBUS" on page 104 in this manual for detailed programming information. Select the LCD option
for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the F ACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address
corresponding to the address set on the ANN-80 at the FACP.
MS-9050UD PN 52413:B 8/29/0725
Product DescriptionANN-BUS Devices
1.9.4 ANN-S/PG Serial/Parallel Interface Module
The ANN-S/PG Serial/Parallel Interface module allows the connection of a serial or parallel printer
to the FACP for a real-time log of system events, detector status reports and event history. The
module is provided with a plastic enclosure for surface mounting. Proceed with the installation as
described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 1.5
ANN-BUS and power wiring are
supervised and power-limited
ANN-S/PG Module
MS-9050UD
Parallel
Cable
Connectors for
connection to
printer
Serial
Figure 1.5 ANN-S/PG Connection to FACP
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number
(address) to the module
4. Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to "ANN-BUS" on page 104)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to "Auto-Configure" on page 115)
5. Connect a printer to the ANN-S/PG Parallel or Serial connectors (refer to Figure 1.5). Only
one printer can be connected.
1.9.4.1 Specifications
•Operating Voltage: 24 VDC
•Current (Alarm and Standby): 45 mA
o
•Ambient Temperature: 32
F to 120oF (0oC to 49oC)
•Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
•Mounting: Surface
•Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
•For indoor use in a dry location only
1.9.4.2 PRN 6 Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the
event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This
section contains information on connecting a printer to the control panel and setting the printer
options.
26MS-9050UD PN 52413:B 8/29/07
ANN-BUS DevicesProduct Description
1.9.4.2.1 Connecting PRN 6 Printer
Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.
The building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25
cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the
other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a
Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the
same time.
1.9.4.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN 6 printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
Auto LFOn
PAPER
BIN 112/72”
BIN 212/72”
SINGLE12/72”
PUSH TRA12/72”
PULL TRA12/72”
PAP ROLL12/72”
MS-9050UD PN 52413:B 8/29/0727
Product DescriptionANN-BUS Devices
1.9.5 ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The module is provided with a plastic enclosure for mounting inside the annunciator or
accessory box. The following sections describe hardware installation. Refer to the section titled
"ANN-BUS" on page 104 for programming information.
1.9.5.1 ANN-I/O Board Layout
Figure 1.1 illustrates the ANN-I/O board showing locations of screw terminals for connection
to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANNBUS ID number.
Terminals not used (future)
ANN-BUS Connector
Figure 1.1 ANN-I/O Board Layout
1.9.5.2 Specifications
•Max. ANN-BUS Voltage: 28 VDC
•Max. Current:
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
•Operating Temperature: 32
•For indoor use in a dry location only
o
F to 120oF (0oC to 49oC)
ANN-BUS (ID#)
Address DIP
switch
ann-IObrd.cdr
28MS-9050UD PN 52413:B 8/29/07
ANN-BUS DevicesProduct Description
1.9.5.3 ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 1.2. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming.
Refer to the section titled "Modules Installed" on page 105.
ANN-I/O Module
MS-9050UD
Figure 1.2 ANN-I/O Connection to FACP
ANN-BUS and power wiring are
supervised and power-limited
ann-IOtoFACP.cdr
MS-9050UD PN 52413:B 8/29/0729
Product DescriptionANN-BUS Devices
1.9.5.4 ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized
so that there is approximately 10 mA of current for each LED. No series resistors are required.
LED outputs can be mapped to output circuits. Refer to the programming section titled
"Modules Installed" on page 105 of this manual.
The LEDs are wired as illustrated in Figure 1.3. Note that the illustration depicts only
connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
Figure 1.3 ANN-I/O Board Layout
30MS-9050UD PN 52413:B 8/29/07
annI-Oleds.cdr
ANN-BUS DevicesProduct Description
1.9.6 ANN-LED Annunciator Module
The ANN-LED and ANN-RLED annunciator modules provide LED annunciation of general
system faults and input zones/points when used with a compatible F ACP. The ANN-LED module
provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones
or addressable points. The ANN-RLED provides alarm (red) indication for up to 30 input zones or
addressable points. Multiple ANN-(R)LED modules may be used for full sy stem coverage.
1.9.6.1 ANN-LED Board Layout
Figure 1.4 illustrates the ANN-LED board showing locations of screw terminals for connection
to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 1.4 ANN-LED Board Layout
1.9.6.2 Specifications
•Max. ANN-BUS Voltage: 24 VDC
•Max. Current:
Alarm: 68 mA
Standby: 28 mA
•Operating Temperature: 32
•For indoor use in a dry location only
o
F to 120o F (0o C to 49o C)
MS-9050UD PN 52413:B 8/29/0731
Product DescriptionANN-BUS Devices
1.9.6.3 ANN-LED Connection to FACP
Figure 1.5 illustrates the ANN-LED board showing locations of screw terminals for connection
to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-LED
-24 VDC
+24 VDC
MS-9050UD
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS
Figure 1.5 ANN-LED Connection to FACP
32MS-9050UD PN 52413:B 8/29/07
ANN-BUS DevicesProduct Description
1.9.7 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
1.9.7.1 ANN-RLY Board Layout
Figure 1.6 illustrates the ANN-RLY board showing locations of screw terminals for connection
to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
Figure 1.6 ANN-RLY Board Layout
1.9.7.2 Specifications
•Operating Voltage: 24 VDC
•Max. Current:
Alarm: 75 mA
Standby: 15 mA
•Operating Temperature: 32
•For indoor use in a dry location only
1.9.7.3 Mounting/Installation
o
F to 120o F (0o C to 49o C)
ANN-BUS Connector
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis.
Refer to the documentation (P/N: 53033) supplied with the ANN-RLY.
MS-9050UD PN 52413:B 8/29/0733
Product DescriptionGetting Started
1.9.7.4 ANN-RLY Connection to FACP
Figure 1.7 illustrates the ANN-RLY board showing locations of screw terminals for connection
to the FACP and the DIP switches for selecting the ANN-BUS ID number.
1.10 Getting Started
The following is a brief summary of the minimal steps involved in bringing an
MS-9050UD on-line:
•Install Backbox and Main Circuit Board (refer to "Mounting Backbox" on page 38)
•Address and Install Intelligent Devices (refer to the SLC Wiring Manual)
•Enter Autoprogramming (refer to "Autoprogram" on page 55)
•Resolve Programming Conflicts
•Go to Point Program to Enter Specific Data (refer to "Point Program" on page 56). Use the
right and left arrow keys to navigate between devices.
ANN-RLY
+24 VDC
-24 VDC
FACP
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS
Figure 1.7 ANN-RLY Connection to FACP
34MS-9050UD PN 52413:B 8/29/07
Telephone Requirements and WarningsProduct Description
1.11 Telephone Requirements and Warnings
1.11.1Telephone Circuitry
AC Ringer Equivalence Number (REN) = 03B
DC Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone
line. Excessive RENs on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line as determined by the total RENs,
contact the telephone company to determine the maximum REN for the calling area.
1.11.2Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of
two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty
information, please contact:
Manufacturer:Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Product Model Number: MS-9050UD
FCC Registration Number: US:1W6AL03B9050UD
AC Ringer Equivalence: 0.3B
DC Ringer Equivalence: 0.0B
Note: This equipment complies with Part 68 of the FCC rules and the requirements
adopted by the ACTA. On the inside of the FACP door is a label that contains,
among other information, a product identifier in the format US:AAAEQ##TXXXX.
If requested, this number must be provided to the telephone company.
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency
situation. It must be able to do this even if other equipment (telephone, answering system,
computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment
must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of
all other equipment attached to the same telephone line. If there are any questions concerning these
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack
and alarm dialing equipment. Refer to "Digital Communicator" on page 46 for an illustration of
the proper installation of this equipment.
Important! The DACT must not
MS-9050UD PN 52413:B 8/29/0735
be used to dial a phone number that is call-forwarded.
Product DescriptionTelephone Requirements and Warnings
1.11.3Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or
make changes in its facilities, services, equipment or procedures which may affect the operation of
this control panel. However, the telephone company is required to give advance notice of such
changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right
to temporarily discontinue service. Advance notification will be provided except in cases when
advance notice is not practical. In such cases, notification will be provided as soon as possible.
The opportunity will be given to correct any problems and to file a complaint with the FCC if you
believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY
LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same tele-
phone line.
The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACT A. This equipment
is designed to be connected to the telephone network or premises wiring using a compliant RJ31X
male modular plug and compatible modular jack that is also compliant.
36MS-9050UD PN 52413:B 8/29/07
Telephone Requirements and WarningsProduct Description
1.11.4For Canadian Applications
The following is excerpted from CP-01 Issue 5:
NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety
requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the
facilities of the local telecommunications company. The equipment must also be installed using an
acceptable method of connection. The customer should be aware that compliance with the above
conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to
disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power
utility, telephone lines and internal metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate
electric inspections authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication
of the maximum number of terminals allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only to the requirement
that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”
IC Certificate Number:
Ringer Equivalence Number (REN): 0.4B
Load Number: 2
MS-9050UD PN 52413:B 8/29/0737
InstallationMounting Backbox
SECTION 2Installation
The cabinet may be either semi-flush or surface mounted. The cabinet mounts using two key slots
and two 0.250” (6.35 mm) diameter holes located in the backbox. The key slots are located at the
top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the
cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left .
Determine the number of conductors required for the devices to be installed. Sufficient knockouts
are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors
into the box. All wiring should be in accordance with the National and/or Local codes for fire
alarm systems.
2.1 Mounting Backbox
The circuit board contains static-sensitive components. Always ground yourself with a pr oper wrist
strap before handling any boards so that static charges are removed from the body. Use static
!
suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main
circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top
flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis
assembly in a safe location until it can be reinstalled in the backbox.
See Page
backbox stud
mounting hole
mounting stud
mounting slot
Ground Stud
Mark and pred rill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.3 on page 40
Inst all center top fastener in the wall with the screw head protruding
Place backbox over the top screw, level and secure
Mark and dri ll the left and ri ght upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
One transformer is supplied standard with the control panel. Install the transformer and chassis in
the location indicated in the following illustration.
6. When the location is dry and free of construction dust, install the chassis/transformer/circuit
board assembly.
7. Mount the chassis to the backbox by aligning the two mounting tabs with the slots in the
backbox, then position the two mounting hole tabs over the studs with nu ts located in the
upper portion of the backbox.
8. Slide the tabs located on the bottom of the chassis into the mounting slots in the backbox by
pressing the chassis down.
9. Secure the chassis to the backbox by tightening the two mounting nuts (#10-32) at the top,
and to ensure proper grounding, use a 3/8” nut driver or socket.
10. If the main circuit board is not already attached to the chassis, install it by positioning the ten
mounting holes over the studs on the chassis and secure with the supplied screws.
11. Ensure the transformer plug is connected to Connector J2 on the FACP main circuit board
12. Complete the installatio n as det a iled in the following sections.
mounting tab holes
FACP Main Circuit Board on Chassis
mounting stud
mounting slot
Ground Stud
mounting stud
Transformer is mounted to the back of the
chassis in the lower left corner.
mounting slot
Backbox
Figure 2.2 Main Circuit Board/Chassis Installation
WARNING: Several different sources of power can be connected to this panel. Disconnect all
sources of power before servicing. The panel and associated equipment may be damaged by
removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
2.3.1 AC Power and Earth Ground Connection
Primary power required for the FACP is 120 VAC, 60 Hz, 3.0 amps for the MS-9050UD.
Overcurrent protection for this circuit must comply with Art icle 760 of the National Electrical
Code (NEC) and/or local codes. Use 14 AWG (2.00 mm
rating. Make certain that the AC mains circuit breaker is off
between the mains and the control panel. Connect wiring from the AC mains to the Transformer on
the FACP, being careful to observe proper connections.
Connect the AC ground wire to the Ground Stud located in the left side of the backbox. Refer to
Figure 2.2 on page 39 and the illustration below for location of the stud. This connection is vital for
maintaining the control panel’s immunity to unwanted transients generated by lightning and
electrostatic discharge. Apply AC power to the panel only after the system is completely installed
and visually checked. Note that AC power must be applied to the panel before installing the battery
interconnect cable (refer to the following section).
2
) or larger wire with 600 volt insulation
before wiring any connections
See Page
-
+
+
-
Interconnect
Cable
2.3.2 Battery Power
Before connecting the batteries to the FACP, make certain that
the interconnect cable between the batteries is not
Do not connect the interconnect cable until the system is
connected.
completely installed. Observe polarity when connecting the
batteries. Connect the battery cable to J1 on the main circuit board. Refer "Power Supply
Calculations" on page 180, for calculation of the correct battery rating.
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
water for 15 minutes and seek immediate medical attention.
AC Connection to
Transformer leads:
HOT
NEUTRAL
Battery Connection
to J1 on FACP
Ground Stud
9050udpowr.cdr
42MS-9050UD PN 52413:B 8/29/07
RelaysInstallation
2.4 Relays
The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble
relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited. Refer to UL Power-limited wiring
requirements.
Note that the programmable relay labeled as
Relay 1 is factory default programmed as
Alarm and programmable Relay 3 is factory
default programmed as Supervisory.
The relay labeled Relay 2 is fixed as a
Trouble relay and cannot be changed. It is a
fail-safe relay which will transfer on any
trouble or total power failure.
9050udreyp.cdr
Relay contacts shown with power applied to panel and
no active troubles, alarms or supervisories
Figure 2.5 Relay Terminals
2.5 Notification Appliance Circuits
The control panel provides two NACs (Notification Appliance Circuits) Style Y (Class B) or Style
See Page
Reference
Manual
Z (Class A). Each circuit is capable of 2.5 amps of current. Total current in alarm for all external
devices cannot exceed 2.5 amps (refer to "Calculating the System Current Draw" on page 181).
Use UL listed 24 VDC notification appliances only. Circuits are supervised and power-limited.
Refer to the Fire-Lite Device Compatibility Document for a listing of compatible notification
appliances. The NACs, which are located on the main circuit board, may be expanded via the FireLite FCPS Series field charger/power supplies.
The following sections describe the configuration and wiring of Style Y and Style Z Notification
Appliance Circuits on the FACP main circuit board.
MS-9050UD PN 52413:B 8/29/0743
InstallationNotification Appliance Circuits
2.5.1 Configuring NACs
The Notification Appliance Circuits are configured for Style Y (Class B) or Style Z (Class A) by
properly wiring the NAC devices to TB1 on the main circuit board as illustrated below.
Style Y (Class B) Notification Appliance
Circuits, supervised and power-limited -
4.7 kΩ, ½ watt P/N:71252 UL listed
Polarized Bells
Polarized Strobes
Notification Appliance Circuit
polarity shown in alarm state
NAC 1NAC 2
Style Z (Class A) Notification Appliance
Circuits, supervised and power-limited
Polarized Bells
Polarized Strobes
Polarized HornsPolarized Horns
terminal number
Figure 2.6 NAC Wiring
Dummy Load all unused circuits
with a 4.7 kΩ, ½ watt resistor
across the B+ & B- terminals or
wire jumpers between A+ & B+
and A- & B-.
9050udnac.cdr
44MS-9050UD PN 52413:B 8/29/07
UL Power-limited Wiring RequirementsInstallation
2.6 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpowerlimited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through
different knockouts and/or conduits. A typical wiring diagram for the FACP is shown below.
maintain minimum 0.25”
between power-limited
and nonpower-limited
Power-limited Circuits (Class 2)
circuits wiring
Nonpower-limited Circuits (Class 1)
Power-limited Circuits (Class 2)
Transformer Wires
(nonpower-limited,
supervised)
AC Power
Hot
Neutral
Ground
Ground Stud
4XTMF
To Batteries
(nonpower-limited,
Class 1
supervised)
Figure 2.7 Typical UL Power-limited Wiring Requirements
MS-9050UD PN 52413:B 8/29/0745
InstallationDigital Communicator
2.7 Digital Communicator
T wo independent telephone lines can be connected to the control panel. Telephone line control/
command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is critical that the panel's digital communicator be located as the first device on
the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded per r equirements of UL 864 9th Edition.
Customer Premises Equipment and Wiring
Network
Service
Provider’s
Facilities
Telephone
Line
Network
Demarcation
Point
RJ31X
Jack
Telephone
Unused
RJ-11 Jack
MS-9050UD
Fax Machine
Answering
System
Telephone
Figure 2.8 DACT Installation
Computer
Telephone
Unused
RJ-11 Jack
9050ACTAdact.cdr
The control panel's digital communicator is built into the main circuit board. Connection and wiring of two phone lines is required as shown below.
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any
modules or wiring.
2.8.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFP A 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having compatible
ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the right (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the MS-9050UD. In addition, the System Trouble LED will turn on
to indicate the Disconnect condition.
Note: 4XTMF Module is not directly suitable for transmitting reverse polarity
supervisory signal. For an application using reverse polarity of a supervisory
signal, refer to "FACP with Keltron" on page 196.
* Wiring from these
terminals can exit the
protected premises.
Dummy load terminals
6 and 7 (4.7kΩ, ¼ watt
resistor) if Municipal
Box is not connected.
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (Primary and Secondary) from the FACP before installing 4XTMF
2. Cut jumper JP28 on the main circuit board to allow the control panel to supervise the
4XTMF module
3. Remove two screws securing main circuit board to mounting plate and install two standoffs
for securing 4XTMF module to main circuit board. Refer to Figure 2.11 for standoff
locations on main circuit board
4. Carefully plug the connectors on the 4XTMF module into connectors J8 and J9 on the MS9050UD main circuit board, being careful not to bend any pins
5. Secure 4XTMF module to standoffs with supplied screws removed in step 3.
6. Reapply power to the FACP
7. For proper 4XTMF operation, the main circuit board output relays must be programmed for
the factory default settings: Alarm Relay 1, Trouble Relay 2 and Supervisory Relay 3
8. When the installation has been completed, enable the 4XTMF module by sliding the
disconnect switch to the left
9. Test system for proper operation
4XTMF
Standoff
J8 & J9 Connectors
Standoff
Jumper JP28
MS-9050UD
Figure 2.11 4XTMF Connectors to MS-9050UD Connectors
Jumper JP2
9050ud4xtm.cdr
NOTE: Jumper JP2 on the FACP main circuit board can be used to configure the FACP supervisory relay
for operation with the 4XTMF module. Relay 3 at TB3 must be programmed as a supervisory relay.
Removing the jumper from JP2 will allow the 4XTMF to generate a trouble if the supervisory contact
opens
Leaving the jumper on JP2 will prevent generation of a trouble if the supervisory contact opens
MS-9050UD PN 52413:B 8/29/0749
ProgrammingProgramming Data Entry
SECTION 3Programming
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PAR TIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature
or option
Trouble Call LimitN
Remote DownloadY
Permitted in
UL 864? (Y/N)
Possible settings
Refer to "Trouble Call Limit (Dialer Runaway Prevention)" on page 122.
Trouble Call Limit = 0 (factory def ault): unlimited
calling to Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique
trouble to from 1 to 99 within a 24 hour period
Refer to "Remote Download" on page 177.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Settings permitted in
UL 864
Tr ouble Call Limit = 0
for unlimited Central
Station
trouble calls
Remote Download
Proprietary Yes for
Proprietary
Installations Only
3.1 Programming Data Entry
Programming can be accomplished using the MS-9050UD keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J6 on the
control panel main circuit board.
The information presented in this section refers to programming the MS-9050UD via the onboard
keypad. If an optional computer keyboard is connected to the MS-9050UD main circuit board, the
following table describes the keyboard keys which correspond to the onboard keypad keys.
Keypad KeysComputer Keyboard Keys
1st EventHome
CLRDelete
ESCEsc
RECALLInsert
**
##
A - ZA - Z
0 - 90 - 9
(on QZ key)
——
//
••
Space bar
ENTEREnter
ACK/STEPF1
SILENCEF2
DRILLF3
RESETF4
50MS-9050UD PN 52413:B 8/29/07
User ProgrammingProgramming
3.2 User Programming
The MS-9050UD is completely field programmable and requires no special software skills. While
!!!
programming the MS-9050UD, the fire protection capabilities of the control panel are
Site-specific programming may be accomplished in three ways:
•Autoprogramming Feature - This is a convenient method for quickly bringing the FACP
addressable SLC devices on-line without the necessity of programming each device
individually. Refer to "Autoprogram" on page 55 for a detailed description of
Autoprogramming
•Manual programming or editing, using the FACP keypad or a PC keyboard
•Off-line Programming and Editing Feature - allows creation and editing of site-specific
custom programs using a Windows-based computer. For programs requiring a large amount
of data entry, this method may be preferred. A PK-CD programming kit can be ordered for
this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
SYSTEM ALL NORMAL
10:00A 092105
enabled.
See Page
Read Status and Manual Dial mode can be entered while the panel is in any
Manual Dial mode, however, cannot be entered while the panel is communicating with the Central
Station. If an alarm or supervisory event exists at the panel, the event must be cleared before
entering Programming mode. T o access any of the programming or read status features, the Enter
or Mode key must be pressed, which will cause the LCD to display the following:
mode of operation.
1=READ STATUS MODE
2=PROGRAMMING MODE
3=MANUAL DIAL MODE
4=REMOTE DOWNLOAD
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read
Status Mode which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to "Read Status" on page 159 for a
detailed description of this feature.
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized
person. After pressing 2, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.
Pressing 3 will select the Manual Dial Mode which allows the user to enter a troubleshoot mode of
operation.
Pressing 4 will select Remote Download which allows the user to enable the remote programming
option. Refer to "Remote Download" on page 177.
Exit Programming, Read Status and Manual Dial Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the
display reads System All Normal. Note that the data which is entered during Programming mode
is not
saved until the programmer exits this mode by repeatedly pr essing the ‘ESC’ key. If the Reset
key is pressed or power is lost before exiting Programming mode, all data just entered will be lost.
MS-9050UD PN 52413:B 8/29/0751
ProgrammingInitial Power-up
User Programming Levels
There are two user programming levels:
•User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
•User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.3 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of addressable devices to the SLC, apply power to the control panel. If
the addressable devices have not yet been programmed into the F ACP, their LEDs will not flash and
the following trouble message will be displayed.
TROUBL IN SYSTEM
NO DEVICES INSTALLED
09:03A 092105
3.4 Programming Screens Description
Three options are available when the Enter key is pressed: Read Status, Programming and Manual
Dial Mode. The Read Status and Programming options have multiple functions or features which
may be chosen. To view all of the choices, it is necessary that the programmer scroll through a
number of additional subscreens. These selections are displayed on multiple screens to make them
See Page
more readable for the programmer. Refer to "Master Programming Level" on page 54, for
additional information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the
programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed
in the upper right corner of the screen being viewed. The programmer can then press the keypad
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the
programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is follo w ed to view all option choices.
3.5 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in
See Page
nonvolatile memory. The factory set passwords can be changed by the user as described in
"Password Change" on page 135. If an invalid password is entered, the blinking cursor will return
to the first password character position. To exit Programming, Read Status or Manual Dial mode
at any time, press the ESC (Escape) key repeatedly. Note that Programming mode must be exited
using the ESC key in order to store the program data entered during this mode. If the Reset key is
pressed or power is lost before exiting Programming mode, the data just entered will not be saved.
52MS-9050UD PN 52413:B 8/29/07
Programming and PasswordsProgramming
To access user Programming mode, press the Enter or Mode key. The LCD will display the
following:
1=READ STATUS MODE
2=PROGRAMMING MODE
3=MANUAL DIAL MODE
4=REMOTE DOWNLOAD
To enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
*****
Entering the Master
If the Maintenance
level password (default 00000) will cause the following screen to appear:
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
MS-9050UD PN 52413:B 8/29/0753
ProgrammingMaster Programming Level
3.6 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble LED flashes until Programming mode is exited. The following display will
appear:
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as
illustrated below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
54MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
3.6.1 Autoprogram
Pressing 1 while viewing Programming Screen #1, will select the Autoprogram option, which
prompts the control panel to poll all devices installed on the SLC loop. The primary purpose of
autoprogramming is to allow the installer a fast and easy way to bring the system on-line as quickly
as possible. The first time the system is powered-up, it should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only add default
values for newly installed devices.
When Autoprogram is selected, the control panel will begin autoprogramming the system by
communicating with each addressable device installed on the SLC loop. While autoprogramming,
the panel will display the following:
AUTOPROGRAM
AUTOPROGRAMMING!
PLEASE WAIT
Autoprogram Progress Screen
When Autoprogramming is completed, the control panel will display the type and quantity of each
device installed on the SLC loop similar to the following display:
# OF DET LOOP1 022
# OF MON LOOP1 015
# OF CON LOOP1 010
Autoprogram Result Screen #1
In the preceding example, the display indicates that the SLC Loop has 22 addressable detectors, 15
monitor modules and 10 control modules installed.
Pressing the ESC key will return the display to Programming Screen #1.
MS-9050UD PN 52413:B 8/29/0755
ProgrammingMaster Programming Level
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
3.6.2 Point Program
The Point Program option allows the programmer to add a new addressable device to an SLC loop,
delete an existing device from a loop or change the programming for an existing device. Pressing
2, while viewing Programming Screen #1, will select the Point Program option and display the
following screen:
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen
3.6.2.1 Detector Programming
Pressing 1, while viewing the Point Program Screen, will allow the programmer to add, delete
or change the programming of an addressable detector. The following screen will be displayed
by the control panel:
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
3.6.2.1.1 Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows
the programmer to add a new detector address to programming:
ADD DETECTOR
ENTER DETECTOR#
***
Add Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer
keys in the three digit detector address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
Press the down arrow key to view additional choices. Press the number corresponding to the
desired selection to program that type to the newly added detector.
56MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
When the type has been selected, the following screen will be displayed:
ADD DETECTOR
DETECTOR# 005
IS ADDED
The programmer can continue adding detectors by pressing the ESC key which will return the
display to the Add Detector Screen.
3.6.2.1.2 Delete Detector
Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the
programmer to delete a specific detector:
DELETE DETECTOR
ENTER DETECTOR#
***
Delete Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer
keys in the three digit detector address, such as 005. When the last digit is keyed-in, the
following screen will be displayed:
DELETE DETECTOR
DETECTOR# 005
IS DELETED
The programmer can continue deleting detectors by pressing the ESC key which will return the
display to the Delete Detector Screen.
3.6.2.1.3 Edit Detector
The programmer can change a detectors existing or factory default programming by pressing 3
in the Detector Screen. The following screen will be displayed:
EDIT DETECTOR
ENTER POINT ADDRESS
***
Edit Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer
keys in the three digit detector address, such as 017.
MS-9050UD PN 52413:B 8/29/0757
ProgrammingMaster Programming Level
When the last digit is keyed-in, if the selected address has not been added to programming, a
screen showing information about a device that is
selected address, will be displayed.
If no
detectors have been installed on the loop, the following will be displayed:
installed with a lower address, closest to the
NO DETECTOR
INSTALLED
Edit Detector Screen #1
If the selected address has been added to programming, device summary screens will be
displayed. These screens allow the programmer to view all device settings at a single glance.
Pressing the left or right arrow keys will allow the programmer to rapidly view the devices at
the previous or next address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not physically
installed on the SLC or has a communication fault but the address is programmed in the system,
the following screen will be displayed:
TROUBL SMOKE(PHOTO)
<ADJ><NOUN>
ZNNN
* 1D017
Edit Detector Screen #1
If the selected address has been added to programming and a detector (such as a photoelectric
detector) with the selected address is physically installed on the SLC and is communicating
with the control panel, the following will be displayed:
NORMAL SMOKE (PHOTO)
<ADJ><NOUN>
ZNNN
V 1D017
Edit Detector Screen #1
To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to
view the Edit Detector screens.
In the preceding example:
Normal - indicates that the detector with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - rep resents the adjective and noun, which have been programmed,
describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the detector is assigned to
(NNN = the three digit zone number from 000 - 019)
V or * - indicates whether or not alarm verification is enabled (V = alarm verification
enabled and * = alarm verification disabled)
1D017 - represents the Loop, Device type and Device address (1 = SLC Loop, D=Detector
and 017 = Detector Address 017)
58MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
The following examples show the editing of a photoelectric smoke detector with address 017,
located on the SLC loop:
EDIT DETECTOR 1D017
1=ENABLED YES
2=TYPE SMOKE(PHOTO)
3=VERIFICATION OFF
Edit Detector Screen #2
EDIT DETECTOR 1D017
1=WALKTEST NO
2=PAS NO
3=PRE-SIGNAL NO
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2.
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the detector will not be polled by the control panel, preventing the detector from
reporting alarms and troubles to the panel. The control panel will display the device type and
address which has been disabled and will turn on the Trouble LED.
MS-9050UD PN 52413:B 8/29/0759
ProgrammingMaster Programming Level
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit
Detector Screen #2. This will cause the control panel to display the following Detector Type
Screen:
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE (ION)
Edit Detector Screen #2
Detector Type Screen #1
Pressing the down arrow key will display additional detector types as indicated in the following
table.
Detector TypeAction When Activated
Smoke PhotoFire Alarm
User-Defined-1same as previous (Smoke Photo)
Smoke IonFire Alarm
User-Defined-2same as previous (Smoke Ion)
Heat DetectFire Alarm
User-Defined-3same as previous (Heat Detect)
Smoke DuctPFire Alarm
User-Defined-4same as previous (Smoke DuctP)
Photo w/HeatFire Alarm
User-Defined-5same as previous (Photo w/Heat)
Duct SupervSupervisory, latching
User-Defined-6same as previous (Duct Superv)
Photo SupervSupervisory, latching
User-Defined-7same as previous (Photo Super)
futurenot used
While viewing any Detector Type screen, select the type of detector being programmed by
pressing the corresponding keyboard number key. The display will return to Edit Detector
Screen #2 and indicate the selection next to the Type option.
See Page
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
60MS-9050UD PN 52413:B 8/29/07
Note: If a detector is selected to be a SUPERV DUCTP type, it will function like a supervisory
point not a fire alarm point. The supervisory LED and supervisory relay will activate, not the
fire alarm LED or alarm relay, if the detector senses smoke.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition
and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Detector
Screen #2 so that the display reads Verification On. Each time the 3 key is pressed, the display
will toggle between Verification On and Verification Off. For a detailed description, refer to
"Alarm Verification (None or One Minute)" on page 158.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of
manually resetting the control panel after each device activation. To enable a device for the
Walktest feature, press 1 while viewing the Edit Detector Screen #3 until the display reads
Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and
Walktest No. Refer to "Walktest" on page 158.
Master Programming LevelProgramming
PAS
The PAS (Positive Alarm Sequence) option will program the detector to delay panel acti vation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time
of up to 3 minutes. Zone 17, however, will activate immediately and may be used to connect a
signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this purpose). To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until
See Page
the display reads PAS Yes. Each press of the 2 key will cause the display to toggle between PAS
Yes and PAS N o. Refer to "Positive Alarm Sequence" on page 156.
For example, if a detector with address 005 is to be configured for PAS operation:
Select PAS Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this example Z001
Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
Program an output, such as a control module, for P AS activation by assigning zone Z17 to
it. This control module may be connected to a signaling device used to indicate a PAS
condition (do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone PAS 17 and set the PAS delay timer to some
value
With the preceding program settings, when the detector with address 005 is activated, zone Z17
will cause its associated control module to activate immediately, sounding the connected PAS
signaling device. Following the PAS delay time, zone Z001 will cause its associated control
module to activate and the control panel will initiate an alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
EDIT DETECTOR
1=WALKTEST
2=PAS
3=PRE-SIGNAL
Edit Detector Screen #3
See Page
Pre-signal
The Pre-signal option programs the detector to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the
alarm relay and communicator will respond to the initial alarm immediately. In addition, Zone
18 will activate. This zone can be programmed to a control module which may be used to
activate a sounder or indicator which the installer designates as a Presignal indication (do not use a Notification Appliance Circuit for this purpose). To enable the Pre-signal feature, press 3
while viewing Edit Detector Screen #3 until the display reads Pre-signal Yes. Each press of the 3 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to
"Presignal" on page 155.
For example, if a detector with address 005 is to be configured for Pre-Signal operation:
Select Pre-signal Yes when editing the detector set to address 005
Program the desired zone or zones to be activated by this detector, in this example Z001
Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001
Program an output, such as a control module, for Pre-signal activation by assigning zone
Z18 to it. This control module may be connected to a signaling device used to indicate a
Pre-signal condition (do not use a Notification Appliance Circuit for this purpose)
Enable zones Z001 and Special Purpose Zone Pre-signal 18 and set the Pre-signal delay
timer to some value
MS-9050UD PN 52413:B 8/29/0761
ProgrammingMaster Programming Level
With the preceding program settings, when the detector with address 005 is activated, zone Z18
will cause its associated control module to activate immediately, sounding the connected
signaling device to indicate the Pre-signal condition. Following the Pre-signal delay time, zone
Z001 will cause its associated control module to activate and the control panel will initiate an
alarm condition.
Note that a detector can be enabled for either PAS or Pre-signal but not both.
A maximum of five zones can be programmed to each addressable detector. Pressing 1 while
viewing Edit Detector Screen #4 displays the following screen:
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default
for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on
the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this device. The cursor moves to the next Z** designation. Continue entering zone
assignments or the remaining zones can be left blank or programmed as general alarm zone
Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Detector Screen #4. Note that the left and right
arrow keys can be used to navigate through the zones and the CLEAR key can be used to
quickly clear a zone.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
detector currently being programmed. Pressing 1 while viewing Edit Detector Screen #5 will
cause the following screen to be displayed:
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective
screens. Press the number corresponding to the adjective that is to be used as a descriptor for
the location of the detector currently being programmed. When an adjective has been selected,
it will appear at the top of the display as indicated by the asterisks.
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
Press the number corresponding to the noun that is to be used as a descriptor for the location of
the detector currently being programmed. When a noun has been selected, it will appear at the
top of the display as indicated by the asterisks.
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the
previous Adjective and Noun Screens. The new screens will list custom Adjectives and Nouns
which have been programmed into the control panel by the user utilizing the PK-CD
programming kit. These descriptors are selected as described in the previous sections.
Description
The Description selection allows the programmer to enter additional information about the
detector currently being programmed. This information will be displayed as part of the device
label on the display. Pressing 2 while viewing Edit Detector Screen #5 will cause the following
screen to be displayed:
DESCRIPTION 1D002
1=NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter
additional descriptive information about the device being programmed. This information will
appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric
characters from the keypad, repeatedly press the appropriate key until the desired character is
displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three
times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor
one position to the right and repeat the process to enter the next character. To enter a space,
press the * (QZ) key four times until a blank appears in the desired position. When all
characters have been entered, press the Enter key to store the information. The display will
return to the Edit Detector Screen #5, displaying the new information at the bottom of the
screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on
the first letter of the Description, Adjective or Noun field as follows:
•If the zero key is pressed, a 0 is placed in the first letter position
•If the zero key is then pressed a second time with no intervening key actions, the entire field
is replaced with the field entered for the previous device programmed
, and the cursor moves
to the last character of the field (Recall function). The Recalled Adjective or Noun field may
now be changed letter-by-letter
•If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one (9 will change to 0). If the last
character is a letter, it changes to a 0.
•The above increment function may be repeated with each press of the zero key
MS-9050UD PN 52413:B 8/29/0765
ProgrammingMaster Programming Level
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 19. Z00 (default zone) is the general alarm zone. Z01
through Z19 may be selected to link software zones
3.6.2.2 Module Programming
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or
change the programming of an addressable module. The following screen will be displayed by
the control panel:
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
3.6.2.2.1 Add Module
Pressing 1 while viewing the Modules Screen will display the following screen which allows
the programmer to add a new module address to programming:
ADD MODULE
ENTER MODULE#
***
Add Module Screen #1
A flashing cursor will appear in the position of the first asterisk to the left. The programmer
keys in the three digit module address, such as 006.
When the last digit is keyed-in, the following screen will be displayed:
ADD MODULE
1=CONTROL
2=MONITOR
Add Module Screen #2
66MS-9050UD PN 52413:B 8/29/07
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
Master Programming LevelProgramming
Pressing 1 for Control Module or 2 for Monitor Module will cause the following screen to be
displayed:
ADD MODULE
MODULE# 006
IS ADDED
Add Module Screen #3
The programmer can continue adding modules by pressing the ESC or left arrow key which will
return the display to the Add Module Screen #1.
3.6.2.2.2 Delete Module
Pressing 2 in the Modules Screen will display the Delete Module Screen which allows the
programmer to delete a specific module:
DELETE MODULE
ENTER MODULE#
***
Delete Module Screen
A flashing cursor will appear in the position of the first asterisk to the left. Using the panel
keypad, key in the module address such as 006. When the last digit is keyed in, the following
confirmation that the module has been deleted will be displayed:
DELETE MODULE
MODULE# 006
IS DELETED
3.6.2.2.3 Edit Module Screen for Monitor Module
The programmer can change a modules existing or factory default programming by pressing 3
in the Modules Screen. The following screen will be displayed:
EDIT MODULE
ENTER MODULE ADDRESS
***
Edit Module Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer
keys in the three digit module address, such as 012.
MS-9050UD PN 52413:B 8/29/0767
ProgrammingMaster Programming Level
When the last digit is keyed-in, if the selected address has not been added to programming, a
screen showing information about a device that is
selected address, will be displayed. If no modules are installed on the loop, the following
screen will be displayed:
installed with a lower address, closest to the
NO MODULE
INSTALLED
Edit Module Screen
If the selected address has been added to programming but a module (such as a monitor
module) with the selected address is not physically installed on the SLC or has a
communication fault, the following screen will be displayed:
TROUBL MONITOR
<ADJ><NOUN>
ZNNN
* 1M012
If the selected address has been added to programming and a module (such as a monitor
module) with the selected address is physically installed on the SLC and is communicating with
the control panel, the following screen will be displayed:
NORMAL MONITOR
<ADJ><NOUN>
ZNNN
W 1M012
To change the programming for the displayed module, press the keyboard down arrow key to
view the following Edit Monitor screens. In the preceding example:
Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - rep resents the adjective and noun, which have been programmed,
describing the location of the displayed device
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the two digit zone number from 000 - 019)
1M012 - rep resents the Loop , Device type and Device address (1 = SLC Loop 1,
M=Module and 012 = Module Address 012)
W or * - indicates whether or not the device is programmed for Walktest (W =
programmed for walktest, * = not programmed for walktest).
68MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
If the selected address corresponds to a control module, a screen displaying information about
See Page
the control module with the selected address will be displayed as shown in "Edit Module
Screen for Control Modules" on page 76.
If the selected address corresponds to a monitor
the module with the selected address will be displayed as illustrated in the following:
To Enable or Disable the monitor module, press the 1 key while viewing th e Edit Modu le
Screen #2. Each press of the key will toggle the screen between Enabled Yes and Enabled No.
If Enabled No is selected, the module will not be polled by the control panel, preventing the
module from reporting alarms and troubles to the panel. The control panel will indicate a
system trouble condition if any devices are disabled.
EDIT MONITOR
1=ENABLED
2=TYPE MONITOR
Edit Monitor Screen #2
Type Monitor
Using the PK-CD Upload/Download utility program, unique user-defined monitor types can be
created and loaded into the FACP for later use. The FACP response to the activation of a userdefined type is the same as most previous standard types in the list, thus allowing a variety of
user-defined types and responses. To select the type of monitor module being programmed,
press the 2 key while viewing the Edit Monitor Screen #2. This will cause the control panel to
display the first Monitor Type Screen as illustrated below
MONITOR TYPE
1=PULL-STATION
2=USER-DEFINED-1
3=WATERFLOW
Monitor T ype Screen #1
T o view additional Monitor T ype Screens, press the down arrow key. While viewing one of the
Monitor Type screens, select the type of monitor module being programmed by pressing the
corresponding keypad number key. The display will return to the Edit Monitor Screen #2 which
will show the new type selection. The following table lists all of the Monitor Types available
for programming and their respective functions.
70MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
Monitor module type selection will affect the function of the point as follows:
Medic-Alert Supervisory, latching
User-Defined-7Supervisory, latching
Hazard-AlertSupervisory, latching
User-Defined-8Supervisory, latching
Tornado-AlertSupervisory, latching
User-Defined-9Supervisory, latching
Future UseFuture Use
Future UseFuture Use
TamperSupervisory, nonlatching (tracking)
User-Defined-11Supervisory, nonlatching (tracking)
SupervisorySupervisory, latching
User-Defined-12Supervisory, latching
Supervisory-ARSupervisory, nonlatching (tracking)
User-Defined-13Supervisory, nonlatching (tracking)
HVAC OVRRIDESwitch Supervisory, nonlatching (tracking)
Power-MonitorAC Fault
User-Defined-14AC Fault
Trouble-MonitorTrouble
User-Defined-15Trouble
Proc-MonPiezo
User-Defined-16Piezo
Procmon-ARPiezo, nonlatching (tracking)
User-Defined-17Piezo, nonlatching (tracking)
Future UseFuture Use
Future UseFuture Use
Ack-SwitchActs like panel Acknowledge Key
Sil-SwitchActs like panel Alarm Silence Key
Reset-SwitchActs like panel Reset Key
Drill-SwitchActs like panel Drill Key
PAS-BypassPAS Disable
HVAC RESTARTSwitch
Drill-Switch AR
4, 5
5
5
5
Fire Alarm
Fire Alarm
Fire Alarm
Fire Alarm
Acts like panel Drill Key, nonlatching (tracking)
3
Notes:
1. For the SUPERVISORY-AR and PROCMON-AR selections, AR refers to AutoResettable.
2. For HVAC RESTART AND HVAC OVRRIDE descriptions, refer to "HVAC Control" on
page 198.
3. Drill Switch Auto-Resettable turns on the NACs and any control module mapped to the Drill
Switch zone.
4. Conventional 2-wire smoke detectors may be powered using an external power supply with
an SLC Control Relay Module programmed for Resettable Power operation. A Control
Relay Module set to the Resettable Power type will follow the main circuit board 24 VDC
resettable power unless the control module is disabled.
5. Use only these Monitor Type IDs for the Zone Modules (MMF-302). The Zone Modules
will not function correctly if any other Type ID is used.
T o enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display
reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to "Presignal" on page 155 for additional information.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of
manually resetting the control panel after each device activation. To enable devices, which are
connected to a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor
Screen #4 until the display reads Walktest Yes. Each press of the 1 key will cause the display to
toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 158 for additional
information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2
while viewing Edit Monitor Screen #4 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default
for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on
the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this device. The cursor moves to the next Z** designation. Continue entering zone
assignments or the remaining zones can be left blank or programmed as general alarm zones
Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Monitor Screen #4.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen
#5 will cause the following screen to be displayed:
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective
screens. Press the number corresponding to the adjective that is to be used as a descriptor for
the location of the monitor module currently being programmed.
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
Press the number corresponding to the noun that is to be used as a descriptor for the location of
the monitor module currently being programmed.
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the
previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns
which have been programmed into the control panel using the PK-CD.
The Description selection allows the programmer to enter additional information about the
monitor module currently being programmed. This information will be displayed as part of the
device label on the LCD display. Pressing 2 while viewing Edit Monitor Screen #5 will cause
the following screen to be displayed:
DESCRIPTION 1M012
1=NOUN/ADJECTIVE
********************
Noun/Adjective Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter
additional descriptive information about the device being programmed. This information will
appear on the LCD display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric
characters from the keypad, repeatedly press the appropriate key until the desired character is
displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three
times to toggle through the characters 2, A and B. Press the right arrow key to move the cursor
one position to the right and repeat the process to enter the next character. To enter a space,
press the * (QZ) key four times until a blank appears in the desired position. When all
characters have been entered, press the Enter key to store the information. The display will
return to the Edit Monitor Screen #4, displaying the new information at the bottom of the
screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on
the first letter of the Adjective or Noun field as follows:
•If the zero key is pressed, a 0 is placed in the first letter position
•If the zero key is then pressed a second time with no intervening key actions, the entire
Adjective field is replaced with the field entered for the previous device programmed
, and the
cursor moves to the last character of the field (Recall function). The Recalled Adjective or
Noun field may now be changed letter-by-letter
•If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one (9 will change to 0). If the last
character is a letter, it changes to a 0.
•The above increment function may be repeated with each press of the zero key
MS-9050UD PN 52413:B 8/29/0775
MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
ProgrammingMaster Programming Level
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 19. Z00 (default zone) is the general alarm zone. Z01
through Z19 may be selected to link software zones
3.6.2.2.4 Edit Module Screen for Control Modules
The programmer can change a module’s existing or factory default programming by pressing 3
in the Modules Screen. The following screen will be displayed:
EDIT MODULE
ENTER MODULE ADDRESS
***
Edit Module Screen
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is
keyed-in, if the selected address corresponds to a control module, a screen displaying
information about the control module with the selected address will be displayed as illustrated
in the following:
NORMAL CONTROL
<ADJ><NOUN>
ZNNN
SW 1M002
Edit Control Screen #1
In the preceding example:
Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - rep resents the adjective and noun, which have been programmed,
describing the location of the displayed device
Control - indicates that the selected module is a control module
S or * - represents Silenceable (S) or Nonsilenceable (*)
W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled)
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 019)
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module
and 002 = Module Address 02)
76MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
To change the programming for the displayed module, press the keyboard down arrow key to
view the following Edit Control screens:
EDIT CONTROL
1=ENABLED YES
2=TYPE CONTROL
3=SILENCEABLE YES
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Control Screen #4
Enable/Disable Module
T o Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen
#2. Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the module will not be polled by the control panel, preventing the
module from activating its output devices. The control panel will indicate a system trouble
condition and the Disable LED will turn on if any devices are disabled.
MS-9050UD PN 52413:B 8/29/0777
ProgrammingMaster Programming Level
Type
T o select the type of control module being programmed, press the 2 key while viewing the Edit
Control Screen #2. This will cause the control panel to display the following Control Type
Screens:
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
CONTROL TYPE
1=BLANK
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
While viewing one of the Control Type screens, select the type of control module being
programmed by pressing the corresponding keypad number key. The display will return to the
Edit Control Screen #2 and indicate the new type selection.
Notes:
1. A control r elay module set to the Resettable Power type will follow the main circuit boar d 24
VDC resettable power unless the control r elay module is disabled.
The following table contains control module type codes and their functions which are displayed
in the Control Type screens:
Control Type Special Function
BlankNAC Type - Supervised
Bell CircuitNAC Type - Supervised
Horn CircuitNAC Type - Supervised
SoundersNAC Type - Supervised
RelayIgnore Open Circuit
Strobe CircuitNAC Type - Supervised
ControlNAC Type - Supervised
Resettable PowerRelay Type - Ignore Open Circuit
HVAC SHUTDNRelay Type - Ignore Open Circuit
Note: For HVAC SHUTDN descriptio n, refer to "Control Module Operation" on page 198.
78MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to
the control module can be silenced, either by pressing the Alarm Silence key or by enabling
Autosilence. Pressing the 3 key while viewing Edit Control Screen #2 will enable the
Silenceable feature causing the display to read Silenceable Yes. Repeated presses of the 3 key
will cause the display to toggle between Silenceable Yes and Silenceable No.
Note that nonsilenceable outputs will not
be activated for Fire Drill.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of
manually resetting the control panel after each device activation. To enable devices, which are
connected to a control module, for the Walktest feature, press 1 while viewing the Edit Control
Screen #3 until the display reads Walktest Yes. Each press of the 1 key will cause the display to
toggle between Walktest Yes and Walktest No. Refer to "Walktest" on page 158 for additional
information.
Zone Assignment
A maximum of five zones can be programmed to each addressable control module. Pressing 2
while viewing Edit Control Screen #3 displays the following screen:
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Control Screen #4
ZONE ASSIGNMENT
Z00 Z** Z** Z** Z**
Zone Assignment Screen
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default
for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on
the first 0 to the left. Enter the two digit number corresponding to the zone that is to be assigned
to this device. The cursor moves to the next Z** designation. Continue entering zone
assignments or the remaining zones can be left blank or programmed as general alarm zones
Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the Edit Control Screen #3.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
control module currently being programmed. Pressing 1 while viewing Edit Control Screen #4
will cause the following screen to be displ a yed:
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective
screens. Press the number corresponding to the adjective that is to be used as a descriptor for
the location of the control module currently being programmed.
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
Press the number corresponding to the noun that is to be used as a descriptor for the location of
the control module currently being programmed.
Pressing 3 or 4 while viewing the Noun/Adjective Screen will display screens similar to the
previous Adjective and Noun Screens. The new screens will list Custom Adjectives and Nouns
which have been programmed into the control panel using the PK-CD programming kit.
The Description selection allows the programmer to enter additional information about the
control module currently being programmed. This information will be displayed as part of the
device label on the display. Pressing 2 while viewing Edit Control Screen #4 will cause the
following screen to be displayed:
EDIT CONTROL
1=ADJECTIVE/NOUN
2=DESCRIPTION
Edit Control Screen #4
DESCRIPTION 1M002
1=NOUN/ADJECTIVE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter
additional descriptive information about the device being programmed. This information will
appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric
characters from the keypad, repeatedly press the appropriate key until the desired character is
displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three
times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor
one position to the right and repeat the process to enter the next character. To enter a space,
press the * (QZ) key four times until a blank appears in the desired position. When all
characters have been entered, press the Enter key to store the information. The display will
return to the Edit Control Screen #4, displaying the new information at the bottom of the screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on
the first letter of the Adjective or Noun field as follows:
•If the zero key is pressed, a 0 is placed in the first letter position
•If the zero key is then pressed a second time with no intervening key actions, the entire
Adjective field is replaced with the field entered for the previous device programmed
cursor moves to the last character of the field (Recall function). The Recalled Adjective or
Noun field may now be changed letter-by-letter
•If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one (9 will change to 0). If the last
character is a letter, it changes to a 0.
•The above increment function may be repeated with each press of the zero key
, and the
As an example, the user could quickly enter ‘FLR_3_ROOM 305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305
4. Press the right arrow key to advance the zone field
5. Select a zone number from 00 to 19. Z00 (default zone) is the general alarm zone. Z01
through Z19 may be selected to link software zones
82MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
3.6.3 Zone Setup
Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated
below:
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #2
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 17 18 19
Zone Setup Screen #1
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=FUTURE USE
Zone Setup Screen #3
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 17 18 19
Zone Setup Screen #1
3.6.3.1 Enable
Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:
ZONE TO ENABLE
Z
Enable Screen
This screens allows the programmer to enable zones, one at a time. A flashing cursor appears
next to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the
second digit is entered, the zone will be enabled and the cursor returns to the original position
next to the Z. Another zone can then be enabled.
MS-9050UD PN 52413:B 8/29/0783
ProgrammingMaster Programming Level
ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 17 18 19
Zone Setup Screen #1
3.6.3.2 Disable
Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:
ZONE TO DISABLE
Z
Disable Screen
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears
next to the Z, prompting the programmer to enter a two digit zone number (01 - 19). When the
second digit is entered, the zone will be disabled and the cursor will return to the original
position next to the Z. Another zone can then be disabled.
3.6.3.3 Zone 17, 18 and 19
Pressing 3 for Zone 17, 18 and 19, while viewing Zone Setup Screen #1, will display the
following screen:
SPEC PURPOSE ZONE
1=PAS 17 OFF
2=PRE-SIGNAL 18 OFF
3=TWO STAGE 19 OFF
Zone 17, 18 and 19 Screen
Zones 17, 18 and 19 can be programmed for normal zone operation or for special purpose
applications. In the above illustration, the three zones are shown Off, which means they can be
programmed to function in the same manner as all other zones, by assigning them to input and
output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 17 On. Each press of the 1 key will cause the
display to toggle between PAS 17 On and PAS 17 Off. When Zone 17 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 17 to activate. By
assigning Zone 17 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 17 to a Notification Appliance Circuit when using this zone to
indicate a PAS condition. Attempting to do so will generate an error message and will be
prevented by software checks .
Pressing 2 will cause the display to change to Pre-signal 18 On. Each press of the 2 key will
cause the display to toggle between Pre-signal 18 On and Pre-signal 18 Off. When Zone 18 is
programmed On, a Pre-signal activation of any device will cause Zone 18 to activate. By
assigning Zone 18 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a Pre-signal condition in the
control panel. Do not assign Zone 18 to a Notification Appliance Circuit when using this zone
to indicate a Pre-signal condition. Attempting to do so will generate an error message and will
be prevented by software checks.
Pressing 3 will cause the display to change to Two Stage 19 On. Each press of the 3 key will
cause the display to toggle between Two Stage 19 On and Two Stage 19 Off. Refer to "Two
Stage Operation" on page 98 for a description of this feature.
84MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
3.6.3.4 Zones Installed
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen
similar to the following:
ZONES INSTALLED
00 01 02 03 04 05
Zones Installed Screen
This display will show all of the zones that have been programmed into the control panel.
3.6.3.5 Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen
similar to the following:
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=FUTURE
Zone Setup Screen #3
Zones Enabled Screen
This display will show all of the zones that are enabled in the control panel.
3.6.3.6 Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen
similar to the following:
ZONES DISABLED
03
Zones Disabled Screen
This display will show all of the zones that are disabled in the control panel.
3.6.3.7 Zone Type
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed
on the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will
display a screen similar to the following:
ZONE TYPE PROG
1=Z00 MONITOR
2=Z01 MONITOR
3=Z02 MONITOR
Zones Installed Screen
MS-9050UD PN 52413:B 8/29/0785
ProgrammingMaster Programming Level
The Zones Installed screen will show the system zones (default and user programmed) and their
associated types. Note that an up and/or down arrow will appear in the upper right corner of the
display, indicating that additional screens of zone information exists. Press the up or down
arrow keys to view zones Z00 through Z19.
Zone types can be changed by pressing the keypad number key corresponding to the zone in
each Zones Installed Screen. Available zone types will be displayed in the resultant screens.
For example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The
following screens will be displayed:
ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
ZONE TYPE PROG
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
Zone Type Program Screen #4
ZONE TYPE PROG
1=NONE
Zone Type Program Screen #5
Zone Type Program Screen #3
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program
Screen #2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will
return to the Zones Installed Screen showing zone Z02 and the Pull Station program type.
Repeat the procedure for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a
Waterflow silenceable
same zone can
feature.
To program a waterflow circuit as nonsilenceable
Note: Zone Types are only relevant for Central Station reporting. Changing a zone type will
only
change how it is reported to the Central Station.
86MS-9050UD PN 52413:B 8/29/07
zone type to the selected zone. Any signaling devices programmed to the
be silenced by pressing the Alarm Silence key or by using the auto-silence
, refer to "System Setup" on page 88.
Master Programming LevelProgramming
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=FUTURE
Zone Setup Screen #3
3.6.3.8 Zones Available
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
Loop Setup allows the programmer to configure the SLC Loop for NFPA Style 4, 6 or 7 wiring and
to select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the
following screen to be displayed:
LOOP SETUP
1=STYLE 4
2=PROTOCOL CLIP
Loop Setup Screen
3.6.4.1 Style
T o program the SLC Style for the loop, press 1 for Style, while viewing Loop Setup Screen. In
the preceding example, the control panel is programmed for Style 4 SLC wiring as indicated by
the 4 to the right of Style in the display. To change the style, press 1 to toggle the display to read
Style 6. Each press of the 1 key will cause the display to toggle between Style 4 and Style 6.
Note that, when programming the Loop Style, the programmer can only select between Style 4
and Style 6. To program a system for Style 7 wiring, the programmer must select the Loop Setup
for Style 6. S tyle 7 wiring is the same as Style 6 with the added requir ement that each device on
the loop must have a pair of isolator modules, one on each side. The factory default setting is
Style 4.
Note on SLC Troubles: If the FACP reports an open fault on an SLC Loop programmed for
Style 6, the trouble condition will latch at the FACP. When the SLC Loop has been repaired,
the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been
repaired) to clear the SLC trouble.
3.6.4.2 Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. The only mode available is CLIP
(Classic Loop Interface Protocol) which is used for the older legacy addressable devices such as
the M300 Series modules and detectors as well as the newer devices. Pressing 2 while viewing
the Loop Setup Screen will have no effect on programming.
Device Addressing
It is important to note that the MS-9050UD addressable device capacity is 50 detectors and
control/monitor modules. Addressable devices must not
Programming will not allow addresses higher than 50.
Important: Detectors and Modules cannot have the same address. For example, if a detector is
installed at address 04, you cannot also have a module at address 04.
Note that It is permissible to mix old and new devices on the same loop.
MS-9050UD PN 52413:B 8/29/0787
be set to addresses higher than 50.
ProgrammingMaster Programming Level
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
•Tr ouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The
piezo will continue to sound at these rates until the alarm or trouble condition is cleared.
Trouble Resound is independent of Trouble Reminder. If a silenced trouble condition is not
cleared by midnight, the panel will reactivate the trouble sounder.
•Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout to a user defined readout when the control panel is in Normal
condition.
•Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
•Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
•NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.
•Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.
•Canadian Option: This option allows the automatic programming of ionization smoke
detector sensitivity thresholds to Canadian specifications.
•W aterflow Silenceable: This option provides the ability to silence any output circuit activated
by a monitor module programmed as a waterflow type.
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
SYSTEM SETUP
1=TROUBLE REM OFF
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
88MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
See Page
3.6.5.1 Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 88, for
a detailed description of this feature. Pressing 1 while viewing System Setup Screen #1 will
cause the display to toggle to Trouble Rem On, which enables this feature. Each press of the 1
key will cause the display to toggle between Trouble Rem On and Trouble Rem Off.
3.6.5.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will
cause the following to be displayed:
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
Pressing 1 while viewing the Banner Screen will select the factory default banner setting and
display the following screen:
FACTORY BANNER
Factory Banner Screen
Pressing the Enter key will store this selection in nonvolatile memory and return the display to
the Banner Screen.
Pressing 2 while viewing the Banner Screen will cause the following screens to be displayed:
USER DEFINED BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
USER BANNER - LINE 2
PRESS ENTER IF OK
************
User Defined Banner Screen #2
MS-9050UD PN 52413:B 8/29/0789
ProgrammingMaster Programming Level
SYSTEM SETUP
1=TROUBLE REM
2=BANNER
3=TIME-DATE
System Setup Screen #1
These screens allow the programmer to enter a two line custom banner. A flashing cursor will
appear in the bottom left corner of each display. A maximum of 20 characters (including
spaces) can be entered into each screen for a total of two lines with 40 characters. After
entering up to 20 characters in the first screen, press Enter to view the second screen. Enter up
to 20 characters in the second screen in the same manner or just press Enter if a second banner
line is not being entered. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until
the desired character is displayed in the first position. For example, to enter the letter B, press
the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow
key to move the cursor one position to the right and repeat the process to enter the next
character. To enter a space, press the * (QZ) key four times to place a blank in the desired
position. When all characters have been entered, press the Enter key to store the information.
The display will return to the Banner Screen.
3.6.5.3 Time-Date
The control panel time and date can be changed by pressing 3 while viewing the System Setup
Screen #1. The following screen will be displayed:
TIME AND DATE
1=TIME 10:00 AM
2=DATE 09-07-2009
3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE
1=DAYLIGHT SAVINGS
Time-Date Screen #2
3.6.5.3.1 Time
T o change the time, press 1 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER TIME
10:00 AM
1=AM 2=PM
Time Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
time. To change the time, enter the two-d igi t hours followed by the two-dig it minutes. The
cursor will move one position to the right each time a digit is entered. After the last minutes
digit is entered, the cursor will again move one position to the right. At this point enter 1 for
AM or 2 for PM. The display will then return to the Time-Date Screen which will show the
new time entry. If an error is made while entering a digit, press the CLR key to delete the entire
entry and begin again.
90MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
3.6.5.3.2 Date
T o change the date, press 2 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER DATE
MONTH DAY YEAR
09-07-2005
Date Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
date. To change the date, enter the two-digit month fol lowed by the two-digit day and then the
two-digit year (01 for 2001, 02 for 2002, etc.). The cursor will move one position to the right
each time a digit is entered. After the last year digit is entered, the display will return to the
Time-Date Screen which will show the new date entry. If an error is made while entering a
digit, press the CLR key to delete the entire entry and begin again.
3.6.5.3.3 Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time.
Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR
and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display .
Note: If the clock is changed to 24 hour (military) format, the date will change to the European
standard of Day-Month-Year (for display purposes only).
TIME AND DATE
1=DAYLIGHT SAVINGS
Time & Date Screen #2
3.6.5.3.4 Daylight Savings Time
Pressing 1 while viewing Ti me-Date Screen #2 will cause the following screens to be displayed:
DAYLIGHT SAVINGS
1=ENABLED YES
2=START MONTH MAR
3=START WEEK WEEK-1
Daylight Savings Screen #1
DAYLIGHT SAVINGS
1=END MONTH NOV
2=END WEEK LAST-W
Daylight Savings Screen #2
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows
the programmer to select the month that daylight savings time will begin. In this sub-screen,
pressing 1 will select March, 2 will select April and 3 will select May.
MS-9050UD PN 52413:B 8/29/0791
ProgrammingMaster Programming Level
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will begin. In the
first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will
select the third week, while in the second sub-screen, pressing 1 will select the fourth week and
2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows
the programmer to select the month that daylight savings time will end. In this sub-screen,
pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will end. In the first
sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select
the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will
select the last week of the selected month.
3.6.5.4 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1
while viewing System Setup Screen #2. The following screen will be displayed:
TIMERS
1=PAS DELAY 000
2=PRE SIGNAL 000
3=WATERFLOW 000
TIMERS
1=PAS DELAY 000
2=PRE SIGNAL 000
3=WATERFLOW 000
Timer Screen #1
Timer Screen #1
TIMERS
1=AC LOSS DELAY 000
Timer Screen #2
3.6.5.4.1 PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180
seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The
following display will appear:
PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
92MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
3.6.5.4.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay
of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer
Screen #1. The following screen will be displayed:
PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
TIMER
1=PAS DELAY 000
2=PRE SIGNAL 000
3=WATERFLOW 000
Timer Screen #1
Note that detectors can be programmed for either PAS or Pre-signal operation, not both. Refer
to "Edit Detector" on page 57 for programming details.
3.6.5.4.3 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any
built-in delays of the waterflow device. The factory default setting for Waterflow delay is 000
for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for
Waterflow delay, press 3 while viewing Timer Screen #1. The following screen will be
displayed:
WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Scr een
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the
time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
MS-9050UD PN 52413:B 8/29/0793
ProgrammingMaster Programming Level
TIMER
1=AC LOSS DELAY
Timer Screen #2
3.6.5.4.4 AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the
length of the desired delay. The factory default setting is 2 hours. Press 1 while viewing Timer
Screen #2 to display the following:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC
Loss report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
AC LOSS DELAY
RANGE 00-23
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
AC Loss Delay Screen #2
A flashing cursor will appear in the lower left corner of the display. The factory default setting
is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When
the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note: Upon the loss of AC power at the control panel, relays programmed for ‘AC Loss’ will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles exist at the panel
other than AC Loss, the System Trouble relay will delay its activation for the duration of the
AC Loss Delay setting.
3.6.5.5 NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configure by pressing
2 while viewing System Setup Screen #2. The following screens will be displayed:
NACS
1=NAC 1
2=NAC 2
NAC Selection Screen
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1
or 2 for NAC 2.
94MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
The following screens will be displayed for each selection:
NAC #
1=ENABLED YES
2=TYPE BELL
3=SILENCEABLE YES
NAC Screen #1
NAC #
1=AUTO SILENCE 00
2=CODING
TEMPORAL
NAC Screen #2
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED NO
NAC Screen #3
NAC #
1=SYNC TYPE S
NAC Screen #4
3.6.5.5.1 Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This
will prevent the selected main circuit board NAC from activating its devices. Each press of the
1 key will cause the display to toggle between Enabled Yes and Enabled No.
MS-9050UD PN 52413:B 8/29/0795
ProgrammingMaster Programming Level
3.6.5.5.2 Type
The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen
#1. The following screen will be displayed. Press the down arrow key to view additional
screens:
NAC #
1=ENABLED
2=TYPE
3=SILENCEABLE
NAC Screen #1
NAC TYPE
1=BELL
2=HORN
3=STROBE
Type Screen #1
Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.
The following table contains NAC type codes and their functions:
NAC Type CodeSpecial Function
BellNone
HornNone
StrobeNone
Synced StrobeSynchronized to manufacturer
Strobe Sil SyncSame as Synced Strobe but Silence turns off audible & visual devices
Door Holder
Reset Power
Non-Reset Power
Table Footnote
NAC normally active
NAC normally active
NAC normally active
1. Important: User should be aware that selecting Door Holder, Reset Power
or Non-Reset Power types for an NAC will immediately activate (turn on)
the NAC circuit and any devices connected to it.
1
1
1
3.6.5.5.3 Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No.
This will prevent the selected main circuit board NAC from being silenced by pressing the
Alarm Silence key or by the Auto Silence feature. Each press of the 3 key will cause the
display to toggle between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for silenceable and the synchronization feature is selected, only the audible
devices will be turned off if the Silence key is pressed or if the Autosilence feature is enabled.
The visual devices (strobes, etc.) will continue to operate.
96MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
3.6.5.5.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board
silenceable notification appliances after a programmed length of time. To enable this feature
and program the time delay before Auto Silence activation, press 1 while viewing NAC Screen
#2. The following screens will be displayed:
NAC #
1=AUTO SILENCE
2=CODING
TEMPORAL
NAC Screen #2
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the
display will return to NAC Screen #2.
Note: All silenceable contro l modules will be controlled by the Autosilence timer for NAC 1.
3.6.5.5.5 Coding (only for NACs not programmed as Sync Strobe Type)
The Coding feature allows the programmer to select the type of output that the main circuit
board notification appliances will generate when activated. Pressing 2 while viewing NAC
Screen #2 will cause the following displays to appear:
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2
MS-9050UD PN 52413:B 8/29/0797
ProgrammingMaster Programming Level
The programmer can select the notification appliance output by pressing the number
corresponding to the desired output. The coding selections are:
•Steady - a continuous output with no coding
•March Time - 120 ppm (pulse-per-minute) output
•California - 10 seconds on and 5 seconds off
•Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second
off
•Two Stage 3 Minutes or 5 Minutes - Refer to “Two Stage Operation” on page 98. for a
description of this feature
Selection of one of the above options will cause the control panel to store the information in
memory and return the display to NAC Screen #2, which will display the new coding choice.
•2nd stage output - Temporal coding as described above
If Two Stage operation is programmed as the Coding option, the following sequence of events
will occur during an alarm.
1. The on-board NACs which are programmed to General Alarm Zone 0 will activate with a
1st stage output upon activation of any alarm point
2. If the activated alarm point is directly mapped to a zone which is programmed to an on-
board NAC, that NAC will go directly to 2nd stage coding output. All other NACs not
directly mapped to the activated alarm point’s zone but assigned to Zone 0 will activate
with a 1st stage output
3. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not
been
pressed, all NACs presently in 1st stage activation will go to 2nd stage activation
4. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation
will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already
in 2nd stage activation
5. If another alarm point is activated and the countdown timer is counting, the alarm point
will have no effect on the NACs unless the alarm point’s zones are directly mapped to
one of the NACs, in which case it will follow the procedure outlined in step 2
6. If another alarm point is activated and the countdown timer has stopped counting due to
the Acknowledge switch being pressed, the countdown timer will restart and the NACs
will respond as outlined in step 2. NACs already in 2nd stage activation will not be
affected
7. Any control modules assigned to special Zone 19 will be activated either by direct
mapping of an input device programmed to Zone 19 or if an NAC enters 2nd stage
operation
8. Control modules that are programmed to the same zone as the activated input device will
not be delayed for activation
98MS-9050UD PN 52413:B 8/29/07
Master Programming LevelProgramming
3.6.5.5.6 Zone
A maximum of five zones can be programmed to each main circuit board NAC. Pressing 1
while viewing NAC Screen #3 displays the following screen:
ZONE ASSIGNMENT
NAC #
1=ZONE
00 00 00 00 00
2=SIL INHIBITED NO
NAC Screen #3
Z00 Z** Z** Z** Z**
Zone Screen
Note that Z** represents the Zone Number(s) corresponding to the selected NAC. The factory
default for an unprogrammed device is Z00 for general alarm zone. A flashing cursor will
appear on the first 0 to the left. Enter the two digit number corresponding to the zone that is to
be assigned to this NAC. The cursor moves to the next Z** designation. Continue entering
zone assignments or the remaining zones can be left blank or programmed as general alarm
zone Z00. When all desired changes have been made, press the Enter key to store the zone
assignments. The display will return to the NAC Screen #3 which will show the zone
assignments just entered.
Note: Zones do not apply to NACs programmed as Door Holder, Reset Power or Non-Reset
Power.
3.6.5.5.7 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit
board NAC for a period of one minute. Resetting the FACP will also be prevented for one
minute while the NAC programmed for silence inhibit is activated. Pressing 2 while viewing
NAC Screen #3 will cause the display to change from the factory default of Silence Inhibit No
to Silence Inhibit Yes. Each press of the 2 key will cause the display to toggle between the two
options.
3.6.5.5.8 Sync Type
If synchronized strobes were selected as the Type of device installed, the type of
synchronization must be selected in this option. Pressing 1 while viewing NAC Screen #4 will
cause the following screen to be displayed:
NAC #
1=SYNC TYPE
NAC Screen #4
NAC SYNC TYPE
1=SYSTEM SENSOR
2=WHEELOCK
3=GENTEX
Pressing 1 while viewing this screen will select System Sensor synchronization, 2 will select
Wheelock and 3 will select Gentex.
3.6.5.5.8.1 Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer
to the manufacturer’s documentation supplied with the Strobes to determine the maximum
current draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that
can be attached to each circuit. Following is a list of the strobes that have been tested with this
FACP and the maximum number that can be connected to each NAC. Make sure that the NAC
maximum current is not exceeded:
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two
main circuit board Form-C relays from the following screen:
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
T o program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that
Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no effect on its programming.
The following screen will appear for each relay to be programmed:
RELAY #
1=TYPE
ALARM
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be
displayed:
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS MON
Relay Screen #2
While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the
Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the
remaining relays.
Relay Type Screen
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
Relay Screen #4
Notes:
1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the
Supervisory and/or Process Monitor type code, when activated, will automatically reset
when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and reset
when the alarm is cleared and/or when the Alarm Silence button is pressed.
100MS-9050UD PN 52413:B 8/29/07
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.