Fire-Lite MS-5UD User Manual

PN: 52626:A1 ECN 07-248
Fire Alarm Control Panels
MS-5UD & MS-10UD Series
Document #52626 5/11/07 Revision:
A1
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise follow­ing the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These docu­ments can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Manage­ment Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens­ing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flam­ing fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.). Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com­prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis­sion systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the require­ments of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso­ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room tempera­ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Table of Contents
Table of Contents
SECTION 1: Product Description .........................................................................................................................12
1.1: Product Features..........................................................................................................................................13
1.2: Specifications ..............................................................................................................................................14
1.3: Controls and Indicators................................................................................................................................15
1.4: Digital Alarm Communicator/Transmitter..................................................................................................17
1.5: Components.................................................................................................................................................17
1.6: Optional Modules and Accessories .............................................................................................................17
1.7: Telephone Requirements and Warnings......................................................................................................19
1.7.1: Telephone Circuitry...........................................................................................................................19
1.7.2: Digital Communicator.......................................................................................................................19
1.7.3: Telephone Company Rights and Warnings.......................................................................................20
1.7.4: For Canadian Applications................................................................................................................21
SECTION 2: Installation ........................................................................................................................................22
2.1: Backbox Mounting......................................................................................................................................22
2.2: Operating Power..........................................................................................................................................25
2.3: Input Circuits...............................................................................................................................................26
2.4: Output Circuits ............................................................................................................................................28
2.4.1: Notification Appliance Circuits ........................................................................................................28
2.4.2: Special Application DC Power Output Connections ........................................................................29
2.4.3: Relays - Programmable.....................................................................................................................29
2.4.4: Remote Synchronization Output.......................................................................................................30
2.5: Power-limited Wiring Requirements.................................................. ..................................... ....................31
2.6: Digital Communicator.................................................................................................................................32
2.7: Installation of Optional Modules.................................................................................................................33
2.7.1: CAC-5X Class A Converter Module ................................................................................................33
2.7.1.1 Installation ................................. ..............................................................................................33
2.7.1.2 Wiring NACs and IDCs for Class A .......................................................................................34
2.7.2: 4XTMF Option Module....................................................................................................................35
2.7.2.1 4XTMF Transmitter Module Installation ................................................................................36
2.8: ANN-BUS Devices .....................................................................................................................................37
2.8.1: ANN-BUS Wiring.............................................................................................................................37
2.8.1.1 Calculating Wiring Distance for ANN-BUS Modules ............................................................37
2.8.1.2 Wiring Configuration ............................................................. .................................................39
2.8.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply ................................................40
2.8.2: ANN-BUS Device Addressing..........................................................................................................40
2.8.3: ANN-80 Remote Fire Annunciator...................................................................................................41
2.8.4: Specifications....................................................................................................................................41
2.8.5: Installation.........................................................................................................................................41
2.8.5.1 Mounting .......................................................... .......................................................................41
2.8.5.2 Opening/Closing Annunciator ...........................................................................................
2.8.5.3 Wiring ANN-80 to FACP .......................................................................................................42
2.8.6: ANN-S/PG Serial/Parallel Printer Interface Installation...................................................................44
2.8.6.1 Specifications ..........................................................................................................................44
2.8.6.2 PRN Printer Installation ..........................................................................................................44
2.8.6.2.1 Connecting PRN Printer .......................................................................................................45
2.8.6.2.2 Setting Printer Options .........................................................................................................45
2.8.7: ANN-I/O LED Driver Module..........................................................................................................46
2.8.7.1 ANN-I/O Board Layout ..........................................................................................................46
2.8.7.2 Specifications ..........................................................................................................................46
2.8.7.3 ANN-I/O Connection to FACP ................................................. ..............................................47
2.8.7.4 ANN-I/O Module LED Wiring ................................................. ..............................................48
2.8.8: ANN-LED Annunciator Module.......................................................................................................49
2.8.8.1 ANN-LED Board Layout ........................................................................................................49
2.8.8.2 Specifications ..........................................................................................................................49
2.8.8.3 Mounting/Installation ..............................................................................................................49
.....41
4
MS-5UD/MS-10UD P/N: 52626:A1 5/11/07
Table of Contents
2.8.8.4 ANN-LED Connection to FACP ............................................................................................50
2.8.9: ANN-RLY Relay Module .................................................................................................................51
2.8.9.1 ANN-RLY Board Layout ........................................................................................................51
2.8.9.2 Specifications ..........................................................................................................................51
2.8.9.3 Mounting/Installation ..............................................................................................................51
2.8.9.4 ANN-RLY Connection to FACP ............................................................................................52
SECTION 3: Programming ..................................................................................................................................53
3.1: User Programming ............................ ..........................................................................................................53
3.2: Initial Power-up...................................... .....................................................................................................54
3.3: Programming Screens Description..............................................................................................................54
3.4: Programming and Passwords ......................................................................................................................54
3.5: Master Programming Level............................................................ .............................................................56
3.5.1: Input Zones........................................................................................................................................ 57
3.5.2: NAC (Notification Appliance Circuit)..............................................................................................64
3.5.2.1 Enabled ....................................................................................................................................65
3.5.2.2 NAC Coding ...........................................................................................................................65
3.5.2.2.1 Two Stage Operation ...........................................................................................................66
3.5.2.2.2 Synchronized NAC Operation .............................................................................................66
3.5.2.3 Silence .....................................................................................................................................67
3.5.2.4 Auto Silence ............................................................................................................................68
3.5.2.5 Silence Inhibited .....................................................................................................................68
3.5.3: Relays................................... .............................................................................................................68
3.5.4: System Setup.....................................................................................................................................70
3.5.4.1 Timers .....................................................................................................................................71
3.5.4.1.1 PAS (Positive Alarm Sequence) Delay ................................................................................71
3.5.4.1.2 Pre-signal Delay ...................................................................................................................71
3.5.4.1.3 Waterflow Delay ..................................................................................................................72
3.5.4.1.4 AC Loss Delay .....................................................................................................................72
3.5.4.2 Banner .....................................................................................................................................73
3.5.4.3 Time-Date ...............................................................................................................................74
3.5.4.3.1 Time .....................................................................................................................................74
3.5.4.3.2 Date ......................................................................................................................................75
3.5.4.3.3 Clock Format ........................................................................................................................75
3.5.4.3.4 Daylight Savings Time .........................................................................................................75
3.5.4.4 Trouble Reminder ...................................................................................................................76
3.5.4.5 Charger Disable .......................................................................................................................76
3.5.5: Option Modules................................................................................................................................ 76
3.5.5.1 ANN-BUS ...............................................................................................................................77
3.5.5.1.1 ANN-BUS Enabled ..............................................................................................................77
3.5.5.1.2 BUS Modules .......................................................................................................................77
3.5.5.1.3 Auto-Configure ....................................................................................................................78
3.5.5.1.4 ANN-S/PG Options ..............................................................................................................79
3.5.5.1.5 ANN-I/O LED Zone Assignments .......................................................................................80
3.5.5.1.6 ANN-80 Options ..................................................................................................................81
3.5.5.2 ANN-RLY Options .................................................................................................................82
3.5.5.3 Onboard DACT ..........................................................................................................
.............83
3.5.5.3.1 Primary Phone ......................................................................................................................83
3.5.5.3.2 Secondary Phone ..................................................................................................................84
3.5.5.3.3 Central Station ......................................................................................................................84
3.5.6: History........................................................ .......................................................................................96
3.5.6.1 View Events ............................................................................................................................96
3.5.6.2 Erase History ...........................................................................................................................96
3.5.7: Walktest.............................................................................................................................................97
3.5.8: Clear Program ....................................................................................... ............................................ 98
3.5.9: Password Change.................................... ..................................... .....................................................98
MS-5UD/MS-10UD P/N: 52626:A1 5/11/07 5
Table of Contents
3.6: Maintenance Programming Level ...............................................................................................................99
3.6.1: Input Zones - Enable/Disable............................................................................................................100
3.6.2: History...............................................................................................................................................100
3.6.3: Walktest.............................................................................................................................................101
3.6.4: Time-Date..........................................................................................................................................102
SECTION 4: Operating Instructions ....................................................................................................................103
4.1: Panel Control Buttons..................................................................................................................................103
4.1.1: Acknowledge/Step.............................................................................................................................103
4.1.2: Alarm Silenced..................................................................................................................................103
4.1.3: Drill/Hold 2 Sec ................................................................................................................................103
4.1.4: Reset..................................................................................................................................................103
4.2: LED Indicators ............................................................................................................................................104
4.3: Normal Operation........................................................................................................................................104
4.4: Trouble Operation........................................................................................................................................105
4.5: Alarm Operation..........................................................................................................................................106
4.6: Supervisory Operation.................................................................................................................................107
4.7: Process Monitor Operation..........................................................................................................................108
4.8: Hazard/Tornado Condition Operation.........................................................................................................108
4.9: Medical Alert Condition Operation.............................................................................................................108
4.10: Disable/Enable Operation..........................................................................................................................109
4.11: Waterflow Circuits Operation....................................................................................................................109
4.12: Detector Functions.....................................................................................................................................109
4.13: Time Functions: Real-Time Clock ............................................................................................................109
4.14: Coded Operation........................................................................................................................................109
4.15: Presignal....................................................................................................................................................110
4.16: Positive Alarm Sequence...........................................................................................................................110
4.17: Special System Timers..............................................................................................................................111
4.17.1: Silence Inhibit Timer.......................................................................................................................111
4.17.2: Autosilence Timer...........................................................................................................................111
4.17.3: Trouble Reminder............................................................................................................................111
4.17.4: Waterflow Retard Timer..................................................................................................................111
4.17.5: Alarm Verification (None or One Minute)......................................................................................112
4.18: Walktest.....................................................................................................................................................112
4.19: Read Status................................................................................................................................................113
4.19.1: Input Zones......................................................................................................................................114
4.19.2: NAC ................................................................................................................................................114
4.19.3: Relays..............................................................................................................................................115
4.19.4: System Settings...............................................................................................................................115
4.19.5: Timers..............................................................................................................................................116
4.19.6: Daylight Savings.............................................................................................................................116
4.19.7: History.............................................................................................................................................117
4.19.8: Print.................................................................................................................................................117
4.19.9: ANN-BUS.......................................................................................................................................118
4.19.10: Central Station.............................. ..................................... .................................... ........................119
4.19.11: Phone Line.................................. .................................... ...............................................................119
SECTION 5: Central Station Communications .....................................................................................
..............120
5.1: Transmittal Priorities...................................................................................................................................121
SECTION 6: Power Supply Calculations .............................................................................................................123
6.1: Overview .....................................................................................................................................................123
6.2: Calculating the AC Branch Circuit..............................................................................................................123
6.3: Calculating the System Current Draw.........................................................................................................124
6.3.1: Overview...........................................................................................................................................124
6.3.2: How to Use Table 6-3 on page 125 to Calculate System Current Draw...........................................124
6.4: Calculating the Battery Size........................................................................................................................126
6
MS-5UD/MS-10UD P/N: 52626:A1 5/11/07
Table of Contents
6.4.1: NFPA Battery Requirements.............................................................................................................126
6.4.2: Selecting and Locating Batteries.......................................................................................................126
APPENDIX A: Ademco Contact ID Format
Event Code Descriptions ........................................................................................................................................127
A.1: Transmission Format Between DACT and Receiver ................................................................................127
A.2: Ademco Contact ID Typical Printout ........................................................................................................127
APPENDIX B: NFPA Standard-Specific Requirements ............................................................ .......................132
B.1: Central Station/Remote Station Transmitter:
Connection to FACP Dry Contacts ...........................................................................................................138
APPENDIX C: FACP with Keltron .....................................................................................................................139
7
MS-5UD/MS-10UD P/N: 52626:A1 5/11/07
Notes
8 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems Other: NEC Article 250 Grounding
NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document Document #15384 411UD Manual Document #50759 411UDAC Manual Document #51073
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 9
MS-5UD Series Main Circuit Board
TB1
-
Style D (Class A) IDC
B B
+
11
TB4/
TB6
J2
CAC5
Ω
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
+
Style Z (Class A) NAC
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
+
+
NO NC C
A Fail Safe Trouble
relay switches to the
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
Remote
Synchronization
Supervisory*
Trouble*
Alarm*
NC position during
trouble conditions and
under loss of all power.
(* )Factory default relay programming
Ω
and power-limited.
Requires ELR.4.7K
0.040 amps maximum.
Special Application Power
24 VDC filtered, supervised
Output (s e e note 2)
B
-
11 2
B
+
OUT1/3 OUT2/4
TB5/
TB7
OUT OUT
TB2
NO NC CNO NC C NO NC C
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
J5
J4
4XTMF OPT BD
JP24
TB8
TB2
JP49
Leave jumper JP49
installed if the FLPS-3
(3 amp Power Supply)
J7
Class A Converter Module
J9
Kiss-off LED
J6
Secondary Phone
Active LED
Secondary
JP30
(Nonpower-Limited)
J8
is installed.
Cut jumper JP49
if the FLPS-7 (7 amp
Power Supply) is
installed.
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Primary Phone
Active LED
DACT Phone Line Jacks
Primary
ANN-BUS
A B
- +
- +
GND PWR
TB3
JP43
+
NAC #4
+
NAC #3
Ω
PN 71252
4.7K , ½ watt End-of-Line Resistor
Special Application Power
3.0 amps max. per circuit.
(See Style Z illustrated near right edge of board).
Notification Appliance Circuits (see note 1)
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
NAC #2
NAC #1
+
+
+
+
+
+
Ω
PN 71252
4.7K , ½ watt
Power Limited)
End-of-Line Resistor
(Class B) (Supervised,
(See Style D illustrated
IDCs 1 through 5, Style B
near right edge of board).
Initiating Device Circuits
+
+
+
+
B
-
B
+
22
B
-
B
+
11
OUT3 OUT4
+ - + -
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
FIRE ALARM
TB7
CAC5 Class A Converter Module
AC POWER
J3
B
-
+ - + - + - + - + -
11
B
+
TB4
B
-
22
B
+
-
B
11
B
+
+ - + -
TB5
J2
321
JP31
RST AUX
OUT1 OUT2
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
ALARM
TROUBLE
ST
1
DEF
3
ABC
2 1
ENTER
ESC
CLEAR
6
JKL
89
5
GHI
PRS TUV
7
4
RESET
DRILL
MODE
_/.
#
0
QZ_
*
- +
J12
BATTERY
nonpower-limited
24 VDC, supervised,
Battery (se e note 3)
J15
5-Zone Panel
Removing Ground Fault
Basic S y st em Connections
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Notes:
1. MS-5UD-3(E) = 2.5 amps max. per NAC
MS-5UD-7(E)= 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-5UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-5UD-3(E)
26 Amp Hour max. for MS-5UD-7(E)
Important!
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
10 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Supervision required.
Nonresettable or Resett able Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper J P31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Power Supply Connector J15
MS-10UD Series Main Circuit Board
B
Style D (Cl ass A) IDC
-
B
+
11
TB1
J2
TB4/
TB6
CAC5
Ω
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
+
Style Z (Class A) NAC
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
Ω
Power Limited)
4.7K , ½ watt
(Class B) (Supervised,
(See Style D illustrated
near right edge of board).
IDCs 6 through 10, Style B
Initiating Device Circuits
+
NAC #4
+
NAC #3
Ω
PN 71252
4.7K , ½ watt End-of-Line Resistor
Special Application Power
(See Style Z illustrated near right edge of board).
Notification Appliance Circuits (s e e n o te 1 )
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
+
NAC #2
+
NAC #1
+
+
Power Limited)
(Class B) (Supervised,
(See Style D illustrated
IDCs 1 through 5, Style B
near right edge of board).
Initiating Device Circuits
+
+
Contacts shown below in normal
End-of-Line Resistor
Ω
4.7K , ½ watt
condition (AC power with no alarm,
trouble or supervisory activity).
PN 71252
PN 71252
End-of-Line Resistor
+
+
NO NC C
A Fail Safe Trouble
relay switches to the
NC position during
Remote
Synchronization
+
+
+
+
Supervisory*
Trouble*
Alarm*
trouble conditions and
under loss of all power.
(* )Factory default relay programming
Ω
and power-limited.
Requires ELR.4.7K
0.040 amps maximum.
Special Application Power
24 VDC filtered, supervised
Output (s ee note 2)
B
-
B
+
66
B
-
B
+
44
B
-
B
+
33
B
-
B
+
B
-
B
+
B
-
B
+
NO NC CNO NC C NO NC C
+ - + - + - + - + -
+ - + -
+ - + - + - + - + -
11
22
11
B
-
11 2
B
+
OUT1/3 OUT2/4
TB5/
TB7
OUT OUT
TB2
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
J5
J4
4XTMF OPT BD
JP24
TB8
TB2
TB6
JP49
Leave jumper JP49
installed if the FLPS-3
(3 amp Power Supply)
J7
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
OUT3 OUT4
TB7
CAC5 Class A Converter Module
J3
TB4
J2
321
JP31
RST AUX
OUT1 OUT2
+ - + -
TB5
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
Class A Converter Module
Kiss-off LED
J6
J9
Secondary Phone
Active LED
Secondary
JP30
(Nonpower-Limited)
J8
is installed.
Cut jumper JP49
if the FLPS-7 (7 amp
Power Supply) is
installed.
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Primary Phone
ANN-BUS
Active LED
DACT Phone Line Jacks
Primary
A B
- +
- +
GND PWR
TB3
ALARM
TROUBLE
FIRE ALARM
ST
1
DEF
AC POWER
3
ABC
2 1
ENTER
ESC
CLEAR
6
JKL
89
5
GHI
PRS TUV
4
RESET
DRILL
MODE
_/.
#
0
QZ_
7
*
- +
J12
BATTERY
nonpower-limited
24 VDC, supervised,
Battery (see note 3)
J15
10-Zone Panel
Removing Ground Fault
Basic System Connections
Special Applicatio n
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Important!
DisableJumper JP43 voids UL/NFPA
Style/Clas s identifications for ci rcuits.
Remove jumper JP43 only with the
approval of the AHJ
Notes:
1. MS-10UD-3(E) = 2.5 amps max. per NAC
MS-10UD-7(E) = 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-10UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-10UD-3(E)
26 Amp Hour max. for MS-10UD-7(E)
(Authority Having Jurisdiction).
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 11
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Power Supply Connector J15
Product Description
SECTION 1 Product Description
The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone F ACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise specified. The combination control and digital communicator panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s i transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of approximately 45
o
F (refer to System Sensor i3 Installation and Maintenance Instructions). In addition, the control panel is compatible with conventional input devices such as two-wire smo ke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to Fire•Lite Device Compatibility Document for a complete listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery level and telephone line integrity.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, display alarm information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.
3
detectors which are conventional smoke detectors that can
The following versions of the MS-5UD and MS-10UD are available:
FACP Version Description
MS-5UD-3 Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7 Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-5UD-7C Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator
MS-5UD-3E Five Zone Panel: 240 V AC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7E Five Zone Panel: 240 V AC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-3 Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7 Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-7C Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator
MS-10UD-3E Ten Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7E Ten Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
Note: Unless otherwise specified, the information in this manual applies to all versions of the panels.
12 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Product Features Product Description
1.1 Product Features
Built-in DACT (Digital Alarm Communicator/Transmitter)
Style B (Class B) IDC (Initiating Device Circuit)
MS-5UD - five programmable IDCsMS-10UD - ten programmable IDCs
Four Style Y (Class B) NAC (Notification Appliance Circuit)
- special application power
Three programmable Form-C relays
Built-in Programmer
Touchtone/Rotary dialing
Programmable Make/Break Ratio
Optional Dress Panel DP-51050
Dress Panel DP-51050LED is provided standard with Canadian models: includes an ANN­LED Annunciator module
Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet
ANN-BUS for connection to optional:
ANN-80 Remote LCD AnnunciatorANN-I/O LED DriverANN-S/PG Printer ModuleGFANN-RLY Relay ModuleGFANN-LED Annunciator Module
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History log with 256 event storage
Control Buttons
ACK (Acknowledge)Alarm SilenceSystem Reset/Lamp TestDrill
LED Indicators
Fire AlarmSupervisoryTroubleAC PowerAlarm SilencePrimary and Secondary Phone Line Active LEDs
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Ve ri fication
NACs Programmable for:
Silence Inhibit Auto-Silence Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)Selective Silence (horn-strobe mute)Temporal or Steady SignalSilenceable or Nonsilenceable
Automatic battery charger with charger supervision
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 13
Product Description Specifications
Silent or audible walktest capabilities
Optional CAC-5X Class A Converter Module for NACs and IDCs
Optional 4XTMF Transmitter Module
1.2 Specifications
AC Power
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.80 amps MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.80 amps MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps Wire size: minimum #14 AWG (2.0 mm Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp Supervised, nonpower-limited Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-10UD-3(E) and 26 Amp Hour battery for MS-5UD-7(E), MS-10UD-7(E) [two 18 Amp Hour batterie s can be housed in the FACP cabinet. Larger batteries require separate battery box such as BB-26 or BB-55] Minimum Battery Size: 7 Amp Hour
2
) with 600V insulation
Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)
Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD) Alarm Zones 6 - 10 on TB6 (MS-10UD only) Supervised and power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA max. Maximum Loop Resistance: 100 ohms End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Standby Current: 2 mA Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB7
1
Four NACs Operation: Style Y (Class B) Special Application power Supervised and power-limited circuitry Normal Operating Voltage: Nominal 24 VDC Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC) End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252) Max. Wiring Voltage Drop: 2 VDC Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1. T otal current for resettable power, nonresettable power and Notification Appliance Circuits must not exceed 3.0 amps for the FACP versions which are powered by the FLPS-3 power supply or 7.0 amps for the FACP versions which are powered by the FLPS-7 power supply.
14 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Controls and Indicators Product Description
Form-C Relays - Programmable - TB8
Relay 1 (factory default programmed as Alarm Relay) Relay 2 (factory default programmed as fail-safe Trouble Relay) Relay 3 (factory default programmed as Supervisory Relay) Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Special Application Resettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see note 1) Power-limited Circuitry Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA (see note 1) Power-limited Circuitry Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable powerJumper pins 2 & 3 on JP31 for resettable power
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Remote Sync Output - TB2
Remote power supply synchronization output, only required for the MS -5UD-3(E), MS-10UD­3(E) [refer to "Remote Synchronization Output" on page 30] 24 VDC nominal special application power Maximum current is 40 mA End-of-Line Resistor: 4.7KΩ Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an external device for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits. All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
1.3 Controls and Indicators
LCD Display The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
SYSTEM ALL NORMAL
10:00A 012105
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 15
Product Description Controls and Indicators
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
Figure 1.1 Membrane/Display Panel
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
LED Indicators
LEDs are provided to annunciate the following conditions:
Fire Alarm - red LED
Supervisory - yellow LED
AC Power - green LED
9050udkypd.cdr
System Trouble - yellow LED
Alarm Silence - yellow LED
Primary Phone Line Active (on circuit board) - red LED
Secondary Phone Line Active (on circuit board) - red LED
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervisory conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse ½ second on and ½ second off
Supervisory - pulse ½ second on and ½ second off
16 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Digital Alarm Communicator/Transmitter Product Description
1.4 Digital Alarm Communicator/Transmitter
T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact IDSIA-DCS-8SIA-DCS-20
®
, programmable to rotary
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
FLPS-7 for the MS-5UD-7(E), MS-10UD-7(E)
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE).
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.
1.6 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS­10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 17
Product Description Optional Modules and Accessories
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and Supervisory.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel.
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flushing mounting of the cabinet.
Battery Box
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
18 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Telephone Requirements and Warnings Product Description
1.7 Telephone Requirements and Warnings
1.7.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B AC Impedance: 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
1.7.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty information, please contact:
Manufacturer:Fire•Lite Alarms One Fire-Lite Place Northford, CT 06472 (203) 484-7161
Product Model Number: MS-5UD/MS-10UD FCC Registration Number: 1W6AL00B10UD Ringer Equivalence: 0.0B
Important! The DACT must not
Note: This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the FACP door is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If requested, this number must be provided to the telephone company .
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency situation. It must be able to do this even if other equipment (telephone, answering system, computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of all other equipment attached to the same telephone line. If there are any questions concerning these instructions, consult the telephone company or a qualified installer about installing the RJ31X jack and alarm dialing equipment. Refer to "Digital Communicator" on page 32 for an illustration of the proper installation of this equipment.
be used to dial a phone number that is call-forwarded.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 19
Product Description Telephone Requirements and Warnings
1.7.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint with the FCC if you believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same
telephone line. The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises. A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACT A. This equipment is designed to be connected to the telephone network or premises wiring using a compliant RJ31X male modular plug and compatible modular jack that is also compliant.
20 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Telephone Requirements and Warnings Product Description
1.7.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5: NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the equipment will operate to the users’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspections authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. the termination of an interface may consist of any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.”
Representative: NOTIFIER/FIRE•LITE, CANADA
24 Viceroy Road Concord, Ontario L4K2L9 Phone: (905) 660-7210 FAX: (905) 660-7204
IC Certificate Number: Ringer Equivalence Number (REN): 1.3B Load Number: 2
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 21
Installation Backbox Mounting
SECTION 2 Installation
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
2.1 Backbox Mounting
The circuit board contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any boards so that static charges are removed from the body. Use static
!
suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
See Page
grounding stud: attach solid earth ground wire (refer to Figure 2.4 on page 25)
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2 on page 23
Install center top fastener in the wall with the screw head protrudingPlace backbox over the top screw, level and secureMark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
Install remaining fasteners and tighten
MS-5UD Board on Chassis
mounting holes
mounting slots
mounting studs
mounting slots
mounting tabs
MS-5UD Backbox
5UDBRDINBOX.CDR
Figure 2.1 Chassis Mounting in Backbox
22 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Backbox Mounting Installation
Semi-Flush Mounting
Do not recess box more than 3.875” into wall to
Hinge Slot for optional Dress Panel
avoid covering venting holes on top of box.
Mounting slots for optional Trim Ring
Semi-Flush mounting hole
Hinge Slot for optional Dress Panel
Figure 2.2 Cabinet Dimensions
9050UDencl.cdr
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 23
Installation Backbox Mounting
Figure 2.3 Backbox and Battery Box
9050UDcab.cdr
24 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Operating Power Installation
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all sources of power before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Refer to AC Power in the section titled "Specifications" on page 14, for power and current requirements for each FACP version. Run a pair of wires (with ground conductor) from the protected premises main breaker box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code, use 14 AWG (2.00 mm equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 A WG (2.00 mm in the backbox. Do not use conduit for the Earth Ground connection since this does not provide
reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
2
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other
2
)] to the grounding stud
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
!
water for 15 minutes and seek immediate medical attention.
AC Power
Hot (L1)
Ground
Neutral (L2)
Ground Wire
J12
-
Batteries
+
5udpowr.cdr
Figure 2.4 Operating Power Connections
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 25
Installation Input Circuits
2.3 Input Circuits
The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs. Each circuit is compatible with System Sensor’s i
3
when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the detector rating of approximately 45
limit for each IDC is 100 ohms. The maximum number of detectors per zone is 25. The field wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to "CAC-5X Class A Converter Module" on page 33.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC 4-wire smoke detector power (500 mA maximum)
UL listed Power Supervision Relay
UL listed compatible 4-wire smoke detector
manual pull stations
heat detectors
smoke detectors which generate a maintenance signal
o
F. The maximum loop resistance
3
smoke detectors, any
UL listed compatible 2-wire smoke detectors
Dummy load all unused circuits - 4.7 K resistor (P/N: 71245)
Ω, ½ watt
Figure 2.5 IDC Connections
26 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ms-10UDidc.cdr
Input Circuits Installation
Combination Waterflow/Su pervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch (tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch (waterflow)
Dummy load all unused circuits - 4.7 KΩ, ½ watt resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-
Line Resistor as shown in Figure 2.6
ms10udcomboIDC.cdr
Program the FACP Initiating Device Circuit as a Combin ation circuit as described in
"Input Zones" on page 57. Note that since a Waterflow Supervisory Switch is included in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to "Waterflow Delay" on page 72.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition is cleared) if the Combo Autoresettable Supervisory type code is selected
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 27
Installation Output Circuits
2.4 Output Circuits
2.4.1 Notification Appliance Circuits
T otal current drawn from the four Style Y (Class B) Notification Appliance Circuits as well as other DC power outputs cannot exceed 3.0 amps for the MS-5UD-3(E), MS-10UD-3(E) [2.5 amp maximum per NAC] powered by the FLPS-3 power supply or 7.0 amps for the MS-5UD-7(E), MS­10UD-7(E) [3.0 amps maximum per NAC] powered by the FLPS-7 power supply (refer to "Power Supply Calculations" on page 123). Each circuit is supervised, power-limited and provides special application power. Refer to the Fire•Lite Device Compatibility Document for a listing of compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing the optional Class A Converter module. Refer to "CAC-5X Class A Converter Module" on page 33.
Class B Notification Appliance Circuits (supervised and power-limited)
Ω, ½ watt resistor P/N:71252
4.7 K
Polarized Bell
Polarized Strobe
Polarized Horn
Ferrite Bead (P/N 29150) Ferrite Bead (P/N 29150)
Notification Appliance Circuit polarity shown in alarm condition
+ - + -
Polarized Bell
Polarized Horn-Strobe
Polarized Horn
Dummy load any unused circuits (P/N: 71245)
Figure 2.7 NAC Connections
ms-10UDnac.cdr
Large gauge wire should be looped through bead at least once as illustrated. Smaller gauge wire can be looped more often.
Ferrite Bead in open position
28 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Ferrite Bead in closed position
2550ferr.cdr
Output Circuits Installation
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and Nonresettable 24 VDC power is available on the MS-5UD and MS-10UD control panel.
Special Application 4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from these terminals (power-limited)
Special Application Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be obtained from these terminals (power-limited)
Jumper JP31 pins 1 & 2 for nonresettable power (as illustrated in figure to right)
-
4
+
3
-
2
+
1
ms-10UDtb9.cdr
Jumper JP31 pins 2 & 3 for resettable power
Figure 2.8 Special Application Auxiliary Power
2.4.3 Relays - Programmable
The MS-5UD and MS-10UD control panels provide a factory default programmed alarm relay, fail­safe trouble relay and supervisory relay. Each relay can be programmed to activate for other conditions (refer to "Relays" on page 68). Each Form-C relay is rated for 2 amps @ 30VDC (resistive) and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
Note: Relay contacts are shown with power applied to the panel and no active troubles, alarms or supervisories. The Trouble Relay is a fail-safe relay which will transfer on any trouble or total power failure.
ms10udrelay.cdr
Figure 2.9 Relay Terminals
MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007 29
Installation Output Circuits
2.4.4 Remote Synchronization Output
Synchronization is a feature that controls the activation of notification appliances in such a way that all devices will turn on and off at exactly the same time. This is particularly critical when activating strobes which must be synchronized to avoid random activation and a potential hazard to individuals. Devices connected directly to the control panel’s NAC can be synchronized as described in "Synchronized NAC Operation" on page 66.
Notification appliances connected to remote power sources may require synchronization with the FACP’s devices. For the MS-5UD-3(E), MS-10UD-3(E), this can be accomplished by connecting the Remote Synchronization Output from TB2 of the FACP to a compatible sync input of a power supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics the signal on NAC 1 (Out 1). This allows the devices connected to the power supply to be synchronized with the devices connected to Out 1 on the FACP.
For the MS-5UD-7(E), MS-10UD-7(E), the Remote Sync Output is not
required. Synchronization for remote power supplies is provided directly from NAC1 (Out 1). Note that NAC 1 (Out 1) must be programmed for sync operation when used for this purpose.
The Remote Synchronization Output is power-limited and supervised and requires a 4.7KΩ ELR resistor at the remote power supply end of the wiring.
Remote Power Supply
Sync Input
4.7KΩ ELR
Remote Sync Output
FACP main circuit board
Figure 2.10 Remote Sync Output
30 MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Loading...
+ 118 hidden pages