While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
1.3: Controls and Indicators................................................................................................................................15
1.4: Digital Alarm Communicator/Transmitter..................................................................................................17
2.6: Digital Communicator.................................................................................................................................32
2.7: Installation of Optional Modules.................................................................................................................33
2.7.1: CAC-5X Class A Converter Module ................................................................................................33
3.1: User Programming ............................ ..........................................................................................................53
3.4: Programming and Passwords ......................................................................................................................54
3.5.4: System Setup.....................................................................................................................................70
3.5.4.3.1 Time .....................................................................................................................................74
3.5.4.3.2 Date ......................................................................................................................................75
3.5.4.3.3 Clock Format ........................................................................................................................75
3.5.4.3.4 Daylight Savings Time .........................................................................................................75
4.1: Panel Control Buttons..................................................................................................................................103
4.2: LED Indicators ............................................................................................................................................104
4.3: Normal Operation........................................................................................................................................104
4.7: Process Monitor Operation..........................................................................................................................108
4.17: Special System Timers..............................................................................................................................111
4.19.4: System Settings...............................................................................................................................115
6.2: Calculating the AC Branch Circuit..............................................................................................................123
6.3: Calculating the System Current Draw.........................................................................................................124
6.3.2: How to Use Table 6-3 on page 125 to Calculate System Current Draw...........................................124
6.4: Calculating the Battery Size........................................................................................................................126
Connection to FACP Dry Contacts ...........................................................................................................138
APPENDIX C: FACP with Keltron .....................................................................................................................139
7
MS-5UD/MS-10UD P/N: 52626:A1 5/11/07
Notes
8MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
•CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote
Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-5UD/MS-10UD Series PN 52626:A1 5/11/20079
MS-5UD Series Main Circuit Board
TB1
-
Style D (Class A) IDC
B
B
+
11
TB4/
TB6
J2
CAC5
Ω
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
+
Style Z (Class A) NAC
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
+
+
NO NC C
A Fail Safe Trouble
relay switches to the
Contacts shown below in normal
condition (AC power with no alarm,
trouble or supervisory activity).
Remote
Synchronization
Supervisory*
Trouble*
Alarm*
NC position during
trouble conditions and
under loss of all power.
(*)Factory default relay programming
Ω
and power-limited.
Requires ELR.4.7K
0.040 amps maximum.
Special Application Power
24 VDC filtered, supervised
Output (s e e note 2)
B
-
11 2
B
+
OUT1/3 OUT2/4
TB5/
TB7
OUT OUT
TB2
NO NC CNO NC C NO NC C
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
J5
J4
4XTMF OPT BD
JP24
TB8
TB2
JP49
Leave jumper JP49
installed if the FLPS-3
(3 amp Power Supply)
J7
Class A Converter Module
J9
Kiss-off LED
J6
Secondary Phone
Active LED
Secondary
JP30
(Nonpower-Limited)
J8
is installed.
Cut jumper JP49
if the FLPS-7 (7 amp
Power Supply) is
installed.
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Primary Phone
Active LED
DACT Phone Line Jacks
Primary
ANN-BUS
A B
- +
- +
GND PWR
TB3
JP43
+
NAC #4
+
NAC #3
Ω
PN 71252
4.7K , ½ watt
End-of-Line Resistor
Special Application Power
3.0 amps max. per circuit.
(See Style Z illustrated near right edge of board).
Notification Appliance Circuits (see note 1)
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
NAC #2
NAC #1
+
+
+
+
+
+
Ω
PN 71252
4.7K , ½ watt
Power Limited)
End-of-Line Resistor
(Class B) (Supervised,
(See Style D illustrated
IDCs 1 through 5, Style B
near right edge of board).
Initiating Device Circuits
+
+
+
+
B
-
B
+
22
B
-
B
+
11
OUT3 OUT4
+ - + -
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
FIRE ALARM
TB7
CAC5 Class A Converter Module
AC POWER
J3
B
-
+ - + - + - + - + -
11
B
+
TB4
B
-
22
B
+
-
B
11
B
+
+ - + -
TB5
J2
321
JP31
RST AUX
OUT1 OUT2
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
ALARM
TROUBLE
ST
1
DEF
3
ABC
2
1
ENTER
ESC
CLEAR
6
JKL
89
5
GHI
PRS TUV
7
4
RESET
DRILL
MODE
_/.
#
0
QZ_
*
- +
J12
BATTERY
nonpower-limited
24 VDC, supervised,
Battery (se e note 3)
J15
5-Zone Panel
Removing Ground Fault
Basic S y st em Connections
Special Application
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Notes:
1. MS-5UD-3(E) = 2.5 amps max. per NAC
MS-5UD-7(E)= 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-5UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-5UD-3(E)
26 Amp Hour max. for MS-5UD-7(E)
Important!
DisableJumper JP43 voids UL/NFPA
Style/Class identifications for circuits.
Remove jumper JP43 only with the
approval of the AHJ
(Authority Having Jurisdiction).
10MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Supervision required.
Nonresettable or Resett able Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper J P31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Power Supply Connector J15
MS-10UD Series Main Circuit Board
B
Style D (Cl ass A) IDC
-
B
+
11
TB1
J2
TB4/
TB6
CAC5
Ω
Dummy load all unused circuits with
4.7K , ½ watt End-of-Line resistors
+
Style Z (Class A) NAC
Nonsupervised relay contacts
Contact Ratings:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
3 Programmable Relays
Ω
Power Limited)
4.7K , ½ watt
(Class B) (Supervised,
(See Style D illustrated
near right edge of board).
IDCs 6 through 10, Style B
Initiating Device Circuits
+
NAC #4
+
NAC #3
Ω
PN 71252
4.7K , ½ watt
End-of-Line Resistor
Special Application Power
(See Style Z illustrated near right edge of board).
Notification Appliance Circuits (s e e n o te 1 )
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
+
NAC #2
+
NAC #1
+
+
Power Limited)
(Class B) (Supervised,
(See Style D illustrated
IDCs 1 through 5, Style B
near right edge of board).
Initiating Device Circuits
+
+
Contacts shown below in normal
End-of-Line Resistor
Ω
4.7K , ½ watt
condition (AC power with no alarm,
trouble or supervisory activity).
PN 71252
PN 71252
End-of-Line Resistor
+
+
NO NC C
A Fail Safe Trouble
relay switches to the
NC position during
Remote
Synchronization
+
+
+
+
Supervisory*
Trouble*
Alarm*
trouble conditions and
under loss of all power.
(*)Factory default relay programming
Ω
and power-limited.
Requires ELR.4.7K
0.040 amps maximum.
Special Application Power
24 VDC filtered, supervised
Output (s ee note 2)
B
-
B
+
66
B
-
B
+
44
B
-
B
+
33
B
-
B
+
B
-
B
+
B
-
B
+
NO NC CNO NC C NO NC C
+ - + - + - + - + -
+ - + -
+ - + - + - + - + -
11
22
11
B
-
11 2
B
+
OUT1/3 OUT2/4
TB5/
TB7
OUT OUT
TB2
Cut this jumper to
enable Supervisory
relay when 4XTMF
module is installed
J5
J4
4XTMF OPT BD
JP24
TB8
TB2
TB6
JP49
Leave jumper JP49
installed if the FLPS-3
(3 amp Power Supply)
J7
JP43
Remove jumper JP43
to disable Ground Fault
Detection circuit (only
with approval of AHJ).
OUT3 OUT4
TB7
CAC5 Class A Converter Module
J3
TB4
J2
321
JP31
RST AUX
OUT1 OUT2
+ - + -
TB5
PWR
RST/NONRST
AUXPWR
TB9
-
-
+
+
2
4
1
3
Class A Converter Module
Kiss-off LED
J6
J9
Secondary Phone
Active LED
Secondary
JP30
(Nonpower-Limited)
J8
is installed.
Cut jumper JP49
if the FLPS-7 (7 amp
Power Supply) is
installed.
Cut this jumper to supervise
the 4XTMF module when
installed (see J4 & J5)
Primary Phone
ANN-BUS
Active LED
DACT Phone Line Jacks
Primary
A B
- +
- +
GND PWR
TB3
ALARM
TROUBLE
FIRE ALARM
ST
1
DEF
AC POWER
3
ABC
2
1
ENTER
ESC
CLEAR
6
JKL
89
5
GHI
PRS TUV
4
RESET
DRILL
MODE
_/.
#
0
QZ_
7
*
- +
J12
BATTERY
nonpower-limited
24 VDC, supervised,
Battery (see note 3)
J15
10-Zone Panel
Removing Ground Fault
Basic System Connections
Special Applicatio n
DC Power Outputs (24 VDC)
Nonsupervised, power-limited circuits
Supervise with a power supervision relay EOLR-1
Resettable Power - 24 VDC filtered,
power-limited (0.500 amps maximum)
to smoke detectors (IDC).
Important!
DisableJumper JP43 voids UL/NFPA
Style/Clas s identifications for ci rcuits.
Remove jumper JP43 only with the
approval of the AHJ
Notes:
1. MS-10UD-3(E) = 2.5 amps max. per NAC
MS-10UD-7(E) = 3 amps max. per NAC
2. Remote Sync Output is required only for
the MS-10UD-3(E): refer to “Remote
Synchronization Output” on page 30
3. 18 Amp Hour max. for MS-10UD-3(E)
26 Amp Hour max. for MS-10UD-7(E)
(Authority Having Jurisdiction).
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200711
Supervision required.
Nonresettable or Resettable Power
Jumper selectable by JP31, 24 VDC filtered,
power-limited (0.500 amps maximum)
Supervision required. NonresettablePower
suitable for powering annunciators, Resettable
Power suitable for powering smoke detectors.
Configure TB9, Terminals 1 & 2
as Resettable or Nonresettable Power.
• Resettable Power - jumper JP31
pins 2 & 3.
• Nonresettable Power - jumper JP31 pins 1 & 2
(as shown).
Power Supply Connector J15
Product Description
SECTION 1Product Description
The MS-5UD is a five zone FACP (Fire Alarm Control Panel) and the MS-10UD is a ten zone
F ACP. The information in this manual refers to both the MS-5UD and MS-10UD unless otherwise
specified. The combination control and digital communicator panels provide reliable fire signaling
protection for small to medium sized commercial, industrial and institutional buildings. The FACP
is compatible with System Sensor’s i
transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a
supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating of
approximately 45
o
F (refer to System Sensor i3 Installation and Maintenance Instructions). In
addition, the control panel is compatible with conventional input devices such as two-wire smo ke
detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other
normally-open contact devices. Refer to Fire•Lite Device Compatibility Document for a complete
listing of compatible devices.
Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays
(factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application
resettable and nonresettable power outputs. The FACP supervises all wiring, AC voltage, battery
level and telephone line integrity.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicating LED, display alarm
information on the panel’s LCD, sound the piezo sounder at the FACP, activate the FACP alarm
relay and operate an optional module used to notify a remote station or initiate an auxiliary control
function.
3
detectors which are conventional smoke detectors that can
The following versions of the MS-5UD and MS-10UD are available:
FACP VersionDescription
MS-5UD-3Five Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7Five Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-5UD-7CFive Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator
MS-5UD-3EFive Zone Panel: 240 V AC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-5UD-7EFive Zone Panel: 240 V AC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-3Ten Zone Panel: 120 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7Ten Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
MS-10UD-7CTen Zone Panel: 120 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current. Includes built-in ANN-LED Annunciator
MS-10UD-3ETen Zone Panel: 240 VAC with FLPS-3 power supply providing 3.0 amps
total 24 VDC output current
MS-10UD-7ETen Zone Panel: 240 VAC with FLPS-7 power supply providing 7.0 amps
total 24 VDC output current
Note: Unless otherwise specified, the information in this manual applies to all versions of the
panels.
•Real-time clock/calendar with daylight savings time control
•History log with 256 event storage
•Control Buttons
ACK (Acknowledge)
Alarm Silence
System Reset/Lamp Test
Drill
•LED Indicators
Fire Alarm
Supervisory
Trouble
AC Power
Alarm Silence
Primary and Secondary Phone Line Active LEDs
•Piezo sounder for alarm, trouble and supervisory
•24 volt operation
•Low AC voltage sense
•Alarm Ve ri fication
•NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization (System Sensor, Wheelock, Gentex, Faraday, Amseco)
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
•Automatic battery charger with charger supervision
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200713
Product DescriptionSpecifications
•Silent or audible walktest capabilities
•Optional CAC-5X Class A Converter Module for NACs and IDCs
•Optional 4XTMF Transmitter Module
1.2 Specifications
AC Power
MS-5UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
MS-5UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.80 amps
MS-10UD-3 (FLPS-3 Power Supply): 120 VAC, 60 HZ, 1.00 amps
MS-10UD-7 (FLPS-7 Power Supply): 120 VAC, 60 HZ, 3.80 amps
MS-5UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
MS-5UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
MS-10UD-3E (FLPS-3 Power Supply): 240 VAC, 50 HZ, 0.54 amps
MS-10UD-7E (FLPS-7 Power Supply): 240 VAC, 50 HZ, 2.20 amps
Wire size: minimum #14 AWG (2.0 mm
Supervised, nonpower-limited
Battery (sealed lead acid only) - J12
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp
Supervised, nonpower-limited
Maximum Charger Capacity: 18 Amp Hour battery for MS-5UD-3(E), MS-10UD-3(E) and 26
Amp Hour battery for MS-5UD-7(E), MS-10UD-7(E) [two 18 Amp Hour batterie s can be
housed in the FACP cabinet. Larger batteries require separate battery box such as BB-26 or
BB-55]
Minimum Battery Size: 7 Amp Hour
2
) with 600V insulation
Initiating Device Circuits - TB4 (and TB6 on MS-10UD only)
Alarm Zones 1 - 5 on TB 4 (MS-5UD and MS-10UD)
Alarm Zones 6 - 10 on TB6 (MS-10UD only)
Supervised and power-limited circuitry
Operation: All zones Style B (Class B)
Normal Operating Voltage: Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit Current: 40 mA max.
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Standby Current: 2 mA
Refer to Fire•Lite Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB5 and TB7
1
Four NACs
Operation: Style Y (Class B)
Special Application power
Supervised and power-limited circuitry
Normal Operating Voltage: Nominal 24 VDC
Maximum Signaling Current: 3.0 amps for MS-5UD-3(E), MS-10UD-3(E) (2.5 amp maximum
per NAC); 7.0 amps for MS-5UD-7(E), MS-10UD-7(E) (3.0 amps maximum per NAC)
End-of-Line Resistor: 4.7KΩ, 1/2 watt (Part #71252)
Max. Wiring Voltage Drop: 2 VDC
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
1. T otal current for resettable power, nonresettable power and Notification Appliance Circuits
must not exceed 3.0 amps for the FACP versions which are powered by the FLPS-3 power
supply or 7.0 amps for the FACP versions which are powered by the FLPS-7 power supply.
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see
note 1)
Power-limited Circuitry
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Special Application Resettable or Nonresettable Power - TB9
Operating Voltage: Nominal 24 VDC
Maximum Available Current: 500 mA (see note 1)
Power-limited Circuitry
Jumper selectable by JP31 for resettable or nonresettable power:
Jumper pins 1 & 2 on JP31 for nonresettable power
Jumper pins 2 & 3 on JP31 for resettable power
Refer to Fire•Lite Device Compatibility Document for compatible listed devices
Remote Sync Output - TB2
Remote power supply synchronization output, only required for the MS -5UD-3(E), MS-10UD3(E) [refer to "Remote Synchronization Output" on page 30]
24 VDC nominal special application power
Maximum current is 40 mA
End-of-Line Resistor: 4.7KΩ
Supervised and power-limited circuit
Auxiliary Trouble Input - J6
The Auxiliary Trouble Input is an open collector circuit which can be used to monitor an
external device for trouble conditions. It can be connected to the trouble bus of a peripheral,
such as a power supply, which is compatible with open collector circuits.
All connections must be in conduit, less than 20 ft. (610 cm) in length in the same room.
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle
LCD display. The display includes a long life
LED backlight that remains illuminated. If AC
power is lost and the system is not in alarm, the
LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
SYSTEM ALL NORMAL
10:00A 012105
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200715
Product DescriptionControls and Indicators
Function keys:
•Acknowledge/Step
•Alarm Silence
•Drill
•System Reset (lamp test)
Service/program keys:
•Keys labeled 1 to 9
•* key
•# key
•0 (recall) key
Figure 1.1 Membrane/Display Panel
•1st Event key
•Clear key
•Escape key
•Mode key
•Four cursor keys (up, down, left and right)
•Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory
conditions.
LED Indicators
LEDs are provided to annunciate the following conditions:
•Fire Alarm - red LED
•Supervisory - yellow LED
•AC Power - green LED
9050udkypd.cdr
•System Trouble - yellow LED
•Alarm Silence - yellow LED
•Primary Phone Line Active (on circuit board) - red LED
•Secondary Phone Line Active (on circuit board) - red LED
•Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:
•Alarm - on steady
•Trouble - pulse 1 second on and 1 second off
•Maintenance - pulse ½ second on and ½ second off
•Supervisory - pulse ½ second on and ½ second off
16MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Digital Alarm Communicator/TransmitterProduct Description
1.4 Digital Alarm Communicator/Transmitter
T wo modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the
following functions:
•Line Seizure: takes control of the phone lines disconnecting any premises phones
•Off/On Hook: performs on and off-hook status to the phone lines
•Listen for dial tone: 440 Hz tone typical in most networks
•Dialing the Central Station(s) number: default is Touch-Tone
•For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
•Communicate in the following formats:
Ademco Contact ID
SIA-DCS-8
SIA-DCS-20
®
, programmable to rotary
1.5 Components
Main Circuit Board
The main circuit board contains the system’s CPU, DACT and other primary components and
wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
•FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
•FLPS-7 for the MS-5UD-7(E), MS-10UD-7(E)
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE).
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.
1.6 Optional Modules and Accessories
CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200717
Product DescriptionOptional Modules and Accessories
ANN-80 LCD Annunciator
The ANN-80 is a remote LCD annunciator which mimics the information displayed on the FACP
LCD display.
ANN-LED Annunciator Module
The ANN-LED Annunciator Module provides three LEDs for each zone: Alarm, Trouble and
Supervisory.
ANN-RLY Relay Module
The ANN-RLY Module, which can be mounted inside the cabinet, provides 10 Form-C relays.
ANN-S/PG Serial/Parallel Printer Gateway
The ANN-S/PG module provides a connection for a serial or parallel printer.
ANN-I/O LED Driver Module
The ANN-I/O module provides connections to a user supplied graphic annunciator.
DP-51050 Dress Panel
A dress panel DP-51050 is available as an option. The dress panel restricts access to the system
wiring while allowing access to the membrane switch panel.
TR-CE Trim-ring
A trim-ring TR-CE is available as an option. The trim-ring allows semi-flushing mounting of the
cabinet.
Battery Box
The BB-26 or BB-55 battery box may be used to house two batteries greater than 18 Amp Hour.
The battery box mounts directly below the control panel cabinet, centered to the main circuit board.
18MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Telephone Requirements and WarningsProduct Description
1.7 Telephone Requirements and Warnings
1.7.1 Telephone Circuitry
Ringer Equivalence Number (REN) = 0.0B
AC Impedance: 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: loss of phone line voltage for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone
line. Excessive RENs on the telephone line may result in the devices not ringing in response to an
incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be
certain of the number of devices that may be connected to the line as determined by the total RENs,
contact the telephone company to determine the maximum REN for the calling area.
1.7.2 Digital Communicator
Before connecting the control panel to the public switched telephone network, the installation of
two RJ31X jacks is necessary. If trouble is experienced with this equipment, for repair or warranty
information, please contact:
Manufacturer:Fire•Lite Alarms
One Fire-Lite Place
Northford, CT 06472
(203) 484-7161
Note: This equipment complies with Part 68 of the FCC rules and the requirements
adopted by the ACTA. On the inside of the FACP door is a label that contains,
among other information, a product identifier in the format
US:AAAEQ##TXXXX. If requested, this number must be provided to the
telephone company .
Alarm dialing equipment must be able to seize the telephone line and place a call in an emergency
situation. It must be able to do this even if other equipment (telephone, answering system,
computer modem, etc.) already has the telephone line in use. To do so, alarm dialing equipment
must be connected to a properly installed RJ31X jack that is electrically in series with and ahead of
all other equipment attached to the same telephone line. If there are any questions concerning these
instructions, consult the telephone company or a qualified installer about installing the RJ31X jack
and alarm dialing equipment. Refer to "Digital Communicator" on page 32 for an illustration of
the proper installation of this equipment.
be used to dial a phone number that is call-forwarded.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200719
Product DescriptionTelephone Requirements and Warnings
1.7.3 Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue services and/or
make changes in its facilities, services, equipment or procedures which may affect the operation of
this control panel. However, the telephone company is required to give advance notice of such
changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right
to temporarily discontinue service. Advance notification will be provided except in cases when
advance notice is not practical. In such cases, notification will be provided as soon as possible.
The opportunity will be given to correct any problems and to file a complaint with the FCC if you
believe it is necessary.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY
LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same
telephone line.
The control panel must be connected to the public switched telephone network upstream (as first
device) of any private telephone system at the protected premises.
A plug and jack used to connect this equipment to the premises wiring and telephone network must
comply with the applicable FCC Part 68 rules and requirements adopted by ACT A. This equipment
is designed to be connected to the telephone network or premises wiring using a compliant RJ31X
male modular plug and compatible modular jack that is also compliant.
20MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Telephone Requirements and WarningsProduct Description
1.7.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means
that the equipment meets certain telecommunications network protective, operational and safety
requirements as prescribed in the appropriate Terminal Equipment Technical Requirements
document(s). The Department does not guarantee the equipment will operate to the users’s
satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the
facilities of the local telecommunications company. The equipment must also be installed using an
acceptable method of connection. The customer should be aware that compliance with the above
conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility
designated by the supplier. Any repairs or alterations made by the user to this equipment, or
equipment malfunctions, may give the telecommunications company cause to request the user to
disconnect the equipment.
Users should ensure, for their own protection, that the electrical ground connections of the power
utility, telephone lines and internal metallic water pipe system, if present, are connected together.
This precaution may be particularly important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate
electric inspections authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication
of the maximum number of terminals allowed to be connected to a telephone interface. the
termination of an interface may consist of any combination of devices subject only to the
requirement that the sum of the REN of all devices does not exceed 5.”
DOC Compliance - “This digital apparatus does not exceed the Class A limits for radio noise
emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian
Department of Communications.”
IC Certificate Number:
Ringer Equivalence Number (REN): 1.3B
Load Number: 2
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200721
InstallationBackbox Mounting
SECTION 2Installation
The cabinet can be surface mounted or semi-flush mounted. The door is removable during the
installation period by opening and lifting it off the hinges. The cabinet mounts using two key slots
at the top of the backbox and two additional securing holes located at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the
cabinet approximately 5 feet (1.5 m) above the floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed. Sufficient knockouts
are provided for wiring convenience. Select the appropriate knockout(s) and pull the conductors
into the box. All wiring should be in accordance with the National and/or Local codes for fire
alarm systems.
2.1 Backbox Mounting
The circuit board contains static-sensitive components. Always ground yourself with a proper wrist
strap before handling any boards so that static charges are removed from the body. Use static
!
suppressive packaging to protect electronic assemblies.
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with main
circuit board and transformer can be easily removed. Loosen the two 3/8” nuts securing the top
flanges of the chassis, then slide the chassis up to free it from the lower tabs. Place the chassis
assembly in a protective antistatic bag in a safe location until it can be reinstalled in the backbox.
See Page
grounding stud:
attach solid earth
ground wire (refer to
Figure 2.4 on page 25)
Mark and predrill hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2 on page 23
Install center top fastener in the wall with the screw head protruding
Place backbox over the top screw, level and secure
Mark and drill the left and right upper and lower mounting holes
Note: outer holes (closest to sidewall) are used for 16” O.C. stud mounting
Install remaining fasteners and tighten
MS-5UD Board on Chassis
mounting holes
mounting slots
mounting studs
mounting slots
mounting tabs
MS-5UD Backbox
5UDBRDINBOX.CDR
Figure 2.1 Chassis Mounting in Backbox
22MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Backbox MountingInstallation
Semi-Flush Mounting
Do not recess box more
than 3.875” into wall to
Hinge Slot for
optional Dress Panel
avoid covering venting
holes on top of box.
Mounting
slots for
optional
Trim Ring
Semi-Flush
mounting hole
Hinge Slot for optional
Dress Panel
Figure 2.2 Cabinet Dimensions
9050UDencl.cdr
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200723
InstallationBackbox Mounting
Figure 2.3 Backbox and Battery Box
9050UDcab.cdr
24MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Operating PowerInstallation
2.2 Operating Power
WARNING: Several different sources of power can be connected to this panel. Disconnect all
sources of power before servicing. The panel and associated equipment may be damaged by
removing and/or inserting cards, modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Refer to AC Power in the
section titled "Specifications" on page 14, for power and current requirements for each FACP
version. Run a pair of wires (with ground conductor) from the protected premises main breaker
box to the AC terminal block TB1 on the main power supply. As per the National Electrical Code,
use 14 AWG (2.00 mm
equipment may be connected to this circuit. In addition, this circuit must be provided with
overcurrent protection and may not contain any power disconnect devices. A separate Earth
Ground connection must be made to ensure proper panel operation and lightning and transient
protection. Connect the Earth Ground wire [minimum 14 A WG (2.00 mm
in the backbox. Do not use conduit for the Earth Ground connection since this does not provide
reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J12 on the main circuit
board using the plug-in connector and cable provided. The battery charger is current-limited and
capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
2
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other
2
)] to the grounding stud
WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with
!
water for 15 minutes and seek immediate medical attention.
AC Power
Hot (L1)
Ground
Neutral (L2)
Ground Wire
J12
-
Batteries
+
5udpowr.cdr
Figure 2.4 Operating Power Connections
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200725
InstallationInput Circuits
2.3 Input Circuits
The MS-5UD has five IDCs (Initiating Device Circuits) and the MS-10UD has ten IDCs. Each
circuit is compatible with System Sensor’s i
3
when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient
temperature falls below the detector rating of approximately 45
limit for each IDC is 100 ohms. The maximum number of detectors per zone is 25. The field
wiring for each zone is supervised for opens, shorts and ground faults. All conditions are visually
and audibly annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i
normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.
Refer to the Fire•Lite Device Compatibility Document for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A
Converter module. Refer to "CAC-5X Class A Converter Module" on page 33.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)
UL listed Power Supervision Relay
UL listed compatible 4-wire smoke detector
manual pull stations
heat detectors
smoke detectors which generate a maintenance signal
o
F. The maximum loop resistance
3
smoke detectors, any
UL listed compatible
2-wire smoke detectors
Dummy load all unused
circuits - 4.7 K
resistor (P/N: 71245)
Ω, ½ watt
Figure 2.5 IDC Connections
26MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ms-10UDidc.cdr
Input CircuitsInstallation
Combination Waterflow/Su pervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm
switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any
circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of
Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Class B Initiating Device Circuits (supervised and power-limited)
4.7 KΩ, ½ watt resistor P/N:71252
Supervisory Switch
(tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch
(waterflow)
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
Figure 2.6 Style B Combination Circuit on Zone 2
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-
Line Resistor as shown in Figure 2.6
ms10udcomboIDC.cdr
Program the FACP Initiating Device Circuit as a Combin ation circuit as described in
"Input Zones" on page 57. Note that since a Waterflow Supervisory Switch is included in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to
"Waterflow Delay" on page 72.
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition
is cleared) if the Combo Autoresettable Supervisory type code is selected
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200727
InstallationOutput Circuits
2.4 Output Circuits
2.4.1 Notification Appliance Circuits
T otal current drawn from the four Style Y (Class B) Notification Appliance Circuits as well as other
DC power outputs cannot exceed 3.0 amps for the MS-5UD-3(E), MS-10UD-3(E) [2.5 amp
maximum per NAC] powered by the FLPS-3 power supply or 7.0 amps for the MS-5UD-7(E), MS10UD-7(E) [3.0 amps maximum per NAC] powered by the FLPS-7 power supply (refer to "Power
Supply Calculations" on page 123). Each circuit is supervised, power-limited and provides special
application power. Refer to the Fire•Lite Device Compatibility Document for a listing of
compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing the optional Class A Converter
module. Refer to "CAC-5X Class A Converter Module" on page 33.
Class B Notification Appliance Circuits (supervised and power-limited)
Ω, ½ watt resistor P/N:71252
4.7 K
Polarized Bell
Polarized Strobe
Polarized Horn
Ferrite Bead (P/N 29150)Ferrite Bead (P/N 29150)
Notification Appliance Circuit
polarity shown in alarm condition
+ - + -
Polarized Bell
Polarized Horn-Strobe
Polarized Horn
Dummy load any unused circuits (P/N: 71245)
Figure 2.7 NAC Connections
ms-10UDnac.cdr
Large gauge wire should be
looped through bead at least once
as illustrated. Smaller gauge wire
can be looped more often.
Ferrite Bead in open position
28MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Ferrite Bead in closed position
2550ferr.cdr
Output CircuitsInstallation
2.4.2 Special Application DC Power Output Connections
Special Application Resettable and Nonresettable 24 VDC power is available on the MS-5UD and
MS-10UD control panel.
Special Application
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable power for 4-wire smoke detectors
can be obtained from these terminals (power-limited)
Special Application
Resettable or Nonresettable Power (500 mA)
24 VDC filtered, resettable or nonresettable power can be
obtained from these terminals (power-limited)
•Jumper JP31 pins 1 & 2 for nonresettable power (as
illustrated in figure to right)
-
4
+
3
-
2
+
1
ms-10UDtb9.cdr
•Jumper JP31 pins 2 & 3 for resettable power
Figure 2.8 Special Application Auxiliary Power
2.4.3 Relays - Programmable
The MS-5UD and MS-10UD control panels provide a factory default programmed alarm relay, failsafe trouble relay and supervisory relay. Each relay can be programmed to activate for other
conditions (refer to "Relays" on page 68). Each Form-C relay is rated for 2 amps @ 30VDC
(resistive) and 0.5 amps @ 30 VAC (resistive).
Note that relay connections must be power-limited.
Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or
total power failure.
ms10udrelay.cdr
Figure 2.9 Relay Terminals
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200729
InstallationOutput Circuits
2.4.4 Remote Synchronization Output
Synchronization is a feature that controls the activation of notification appliances in such a way that
all devices will turn on and off at exactly the same time. This is particularly critical when
activating strobes which must be synchronized to avoid random activation and a potential hazard to
individuals. Devices connected directly to the control panel’s NAC can be synchronized as
described in "Synchronized NAC Operation" on page 66.
Notification appliances connected to remote power sources may require synchronization with the
FACP’s devices. For the MS-5UD-3(E), MS-10UD-3(E), this can be accomplished by connecting
the Remote Synchronization Output from TB2 of the FACP to a compatible sync input of a power
supply such as the FCPS-24FS6/8. The 24 VDC, 40 mA signal from TB2 follows, that is mimics
the signal on NAC 1 (Out 1). This allows the devices connected to the power supply to be
synchronized with the devices connected to Out 1 on the FACP.
For the MS-5UD-7(E), MS-10UD-7(E), the Remote Sync Output is not
required. Synchronization
for remote power supplies is provided directly from NAC1 (Out 1). Note that NAC 1 (Out 1) must
be programmed for sync operation when used for this purpose.
The Remote Synchronization Output is power-limited and supervised and requires a 4.7KΩ ELR
resistor at the remote power supply end of the wiring.
Remote Power Supply
Sync Input
4.7KΩ ELR
Remote Sync Output
FACP main circuit board
Figure 2.10 Remote Sync Output
30MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Power-limited Wiring RequirementsInstallation
2.5 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpowerlimited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
AC Power
Hot (L1)
Ground
Neutral (L2)
earth
ground
Power-limited Circuits
(Class 2)
CAC-5X
Power-limited Circuits (Class 2)
Power-limited
Circuits
(Class 2)
CAC-5X
4XTMF
Nonpowerlimited
Circuit
Nonpowerlimited
Circuit
Power-limited
Circuit
(Class 2)
MS-10UD FACP
Figure 2.11 Typical UL Power-limited Wiring Requirements
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200731
10udULwire.cdr
InstallationDigital Communicator
2.6 Digital Communicator
T wo independent telephone lines can be connected to the control panel. Telephone line control/
command is made possible via double line seizure as well as usage of an RJ31X style
interconnection. Note that it is critical that the panel's digital communicator be located as the first
device on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Customer Premises Equipment and Wiring
Network
Service
Provider’s
Facilities
Telephone
Line
Network
Demarcation
Point
RJ31X
Jack
Telephone
Unused
RJ-11 Jack
FACP with DACT
Fax Machine
Answering
System
Telephone
Computer
Telephone
Unused
RJ-11 Jack
Figure 2.12 DACT Installation
The control panel's digital communicator is built into the main circuit board. Connection and
wiring of two phone lines is required as shown below.
9050ACTAdact.cdr
10UDJACK.cdr
Figure 2.13 Wiring Phone Jacks
32MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Installation of Optional ModulesInstallation
2.7 Installation of Optional Modules
CAUTION: Remove all power (AC and DC) before installing or removing modules or wiring.
2.7.1 CAC-5X Class A Converter Module
2.7.1.1 Installation
The CAC-5X Module can be used to convert five Style B (Class B) Initiating Device Circuits to
Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z
(Class A). The module plugs into connector J2 which is located at the top left of the MS-5UD
and MS-10UD main circuit board and J7 which is located at the top center of the MS-10UD.
Note that two CAC-5X modules are requir ed to convert all NACs and IDCs on the MS-10UD to
Class A circuits.
To install the CAC-5X in the MS-5UD or MS-10UD, remove the two main circuit board
mounting screws referenced in the following illustration and replace with the two supplied
male/female standoffs in the locations indicated in the following figure. Carefully align the
connector on the CAC-5X with J2 on the FACP main circuit board and press the module
securely into place. Make certain the pins are properly aligned to prevent bending or breaking
of any connector pins. Secure the CAC-5X to the standoffs with the screws that were just
removed.
T o install the second CAC-5X on J7 of the MS-10UD, remove the main circuit board mounting
screw referenced in the following illustration and replace with the supplied male/female
standoff. Insert the supplied plastic standoff in the location indicated in the following
illustration. Carefully align the connector on the CAC-5X with J7 and press the module
securely into place. Make certain the pins are properly aligned to prevent bending or breaking
of any connector pins. Secure the CAC-5X to the metal standoff with the screw that was just
removed.
Installation in MS-5UD or MS-10UD
CAC-5X Module
Metal
Standoff
Metal
Standoff
MS-10UD Main Circuit Board
Figure 2.14 CAC-5X Module Installation
Installation in MS-10UD
CAC-5X Module
Plastic
Standoff
Metal
Standoff
ms-10udcac5mnt.cdr
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200733
InstallationInstallation of Optional Modules
2.7.1.2 Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB5 of the MS-5UD/MS10UD and TB2 of the CAC-5X module. Wire the Style D (Class A) Initiating Device Circuits
using TB4 of the MS-5UD/MS-10UD and TB1 of the CAC-5X. Note that the wiring will be
identical when using TB7 NAC and TB6 IDC of the MS-10UD. Make certain to observe
polarity when connecting the devices to the circuits. The B+ and A+ terminals must comprise
the feed and return for the positive side of a device and the B- and A- terminals must comprise
the feed and return for the negative side of a device. To configure any of the zones for Class B
when the CAC-5X is installed, simply wire to the B+ and B- input on the FACP terminal(s) and
install the End-of-Line Resistor after the last device on the circuit. Do not wire to the
corresponding A+ and A- terminals on the CAC-5X module.
Class B (Style B) IDC - 4.7 KΩ
½ watt ELR resistor
P/N:71252 (supervised and power-limited)
Class A (Style Z) NAC
(supervised and power-limited)
Polarized
Bell
Polarized
Strobe
Polarized
Horn
Ferrite Bead
P/N 29150)
Circuit polarities
shown in alarm
condition
B+ B-B+ B-
A+ A-
A+ A-
Smoke
Pull Station
Heat
B+ B- B+ B- B+ B- B+ B- B+ B-
Smoke
Pull Station
Heat
A+ A- A+ A- A+ A- A+ A- A+ A-
Class A (Style D) IDC
(supervised and power-limited)
Dummy load all unused
circuits - 4.7 K
½ watt resistor
(P/N: 71245)
MS-5UD
Circuit Board
Ω
CAC-5X Class A Converter Module
Large gauge wire should be looped through
bead at least once as illustrated. Smaller
gauge wire can be looped more often.
Ferrite Bead in open position
2550ferr.cdr
Ferrite Bead in closed position
ms10udclassa.cdr
Figure 2.15 Wiring NACs and IDCs for Class A Operation
34MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Installation of Optional ModulesInstallation
2.7.2 4XTMF Option Module
The 4XTMF module can be plugged into connectors J4 and J5 on the main circuit board.
The following steps must be followed when installing the 4XTMF module:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP30 on the main circuit board to allow the con trol panel to supervise the
placement of the 4XTMF option module
3. Install the two supplied metal st andoffs in the locations indicated. These standoffs provide
the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J4 and J5 on the FACP
main circuit board, being careful not to bend any pins
5. Secure the option module to the standoff on the main circuit board with the supplied screws
6. When the installation has been completed, connect the wiring to the modules as indicated in
the following sections
7. Test system for proper operation
Note: This illustration shows the installation of the Option Module on the 5-zone
panel. The module is installed in the same location on the 10-zone panel.
Figure 2.16 4XTMF Option Module Connection to MS-5UD
Standoffs
J4
J5
ms5udbord.cdr
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200735
InstallationInstallation of Optional Modules
2.7.2.1 4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in
addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity
circuit to open with a system trouble condition if no alarm condition exists. A disable switch
allows disabling of the transmitter output during testing to prevent accidental calling of the
monitoring service.
Local Energy Municipal Box Service (NFP A 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for
connection to a polarity reversal circuit or a Remote Station receiving unit having
compatible ratings:
Maximum load for each circuit: 10 mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to
prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate
after the module is installed in the FACP. In addition, the System Trouble LED will turn on to
indicate the Disconnect condition.
Note: the 4XTMF Module is not directly suitable for transmitting reverse polarity
supervisory signal. For an application of reverse polarity of a supervisory signal,
refer to the Appendix titled "FACP with Keltron" on page 139.
TBL Jumper
Disconnect
Switch
shown in
disconnect
position
TB1
TBL
J1
J2
Connect to FACP Connectors J4 & J5
Polarities are shown for module activation
1+
}Remote Alarm - Class 2
2-
(power-limited)*
3+
}Remote Trouble - Class 2
(power-limited)*
4-
No connection
5
6+
}Municipal Box (nonpower-limited)*
7-
* Wiring from these terminals can
exit the protected premises.
Dummy load terminals 6 and 7
(4.7kΩ, ¼ watt resistor) if
Municipal Box is not connected.
4xtmf.cdr
Disconnect LED
Figure 2.17 4XTMF Transmitter Module
36MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
2.8 ANN-BUS Devices
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any
modules or wiring.
A variety of optional devices can be connected to the FACP ANN-BUS communication circuit.
Compatible devices include:
This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).
2.8.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the
maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
T o calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is
necessary to calculate the total worst case current draw for all modules on a single 4-conductor
bus. The total worst case current draw is calculated by adding the individual worst case
currents for each module. The individual worst case values are shown in the following table:
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200737
InstallationANN-BUS Devices
After calculating the total worst case current draw, Table 2.1 specifies the maximum distance
the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of
line drop maximum. In general, the wire length is limited by resistance, but for heavier wi re
gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more
than 6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is
shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
Total Worst Case
Current Draw (amps)
0.1001,852 ft.4,688 ft.* 6,000 ft.*6,000 ft.
0.200926 ft.2,344 ft.3,731 ft.5,906 ft.
0.300617 ft.1,563 ft.2,488 ft.3,937 ft.
0.400463 ft.1,172 ft.1,866 ft.2,953 ft.
0.500370 ft.938 ft.1,493 ft.2,362 ft.
22 Gauge18 Gauge16 Gauge14 Gauge
Table 2.1 Wiring Distances
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) =6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)=Maximum Resistance (Ohms)*500
(6,000 feet maximum)Rpu
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire GaugeOhms per 1,000 feet (Rpu)
2216.2
186.4
164.02
142.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring
limitations:
Wire GaugeMaximum Wire Length
18312 feet
16497 feet
14787 feet
121,250 feet
38MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
The total worst case current is calculated as follows:
ANN-80 Current Draw= 2 X 0.040 amps= 0.080 amps
ANN-S/PG Current Draw= 1 X.0.040 amps= 0.040 amps
ANN-I/O Current Draw= 1 X.0.200 amps= 0.200 amps
Total Worst Case Current Draw= 0.320 amps
Using this value and referring to the Wiring Distance Table 2.1 on page 38, it can be found that
the available options are:
463 feet maximum using 22 Gauge wire
1,172 feet maximum using 18 Gauge wire
1,866 feet maximum using 16 Gauge wire
2,953 feet maximum using 14 Gauge wire
2.8.1.2 Wiring Configuration
Figure 2.18 illustrates the wiring between the FACP and ANN-BUS devices.
FACP
TB3
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
Figure 2.18 FACP wiring to ANN-BUS Device
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200739
InstallationANN-BUS Devices
2.8.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 2.19 illustrates the powering of ANN-BUS devices from an auxiliary power supply such
as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANNBUS power requirements.
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
FCPS-24FS6/8
Figure 2.19 Powering ANN-BUS Devices from FCPS-24FS6/8
2.8.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
F ACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 77).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions.
Unless otherwise specified in the documentation supplied with each device, switch positions 6 and
above must be set to OFF.
AddressSwitch 5Switch 4Switch 3Switch 2Switch 1
not validOFFOFFOFFOFFOFF
01OFFOFFOFFOFFON
02OFFOFFOFFONOFF
03OFFOFFOFFONON
04OFFOFFONOFFOFF
05OFFOFFONOFFON
06OFFOFFONONOFF
07OFFOFFONONON
08OFFONOFFOFFOFF
40MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
2.8.3 ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator which
mimics the FACP display. It also provides system status indicators for AC Power, Alarm, Trouble,
Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and FACP is
accomplished over a two wire serial interface employing the ANN-BUS communication format.
The devices are powered, via two additional wires, from either the host FACP or remote UL-listed,
filtered, power supply.
2.8.4 Specifications
•Operating Voltage Range: 18 VDC to 28 VDC
•Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail ( not backlit): 15.0 mA
•For use indoors in a dry location
2.8.5 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the
annunciator.
2.8.5.1 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical
box. Select and remove the appropriate knockout(s), pull the necessary wires through the
knockouts and mount the annunciator in or on the wall depending on the type of installation
desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the
annunciator to the electrical box/wall. The cover cannot be reattached or removed after the
annunciator has been mounted.
2.8.5.2 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the
terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
Annunciator cover with LCD display
Annunciator backplate
Press in latch and pull
annunciator cover open
Key switch shown in ON position
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200741
InstallationANN-BUS Devices
2.8.5.3 Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator . Make certain all power has
been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1
wiring channel
wires
TB1
2. Remove appropriate amount of wire insulation
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1
terminals 3 & 4. Make certain to connect A to A and B to B
5. Connect the wiring from the 24 VDC power source to annunci ator TB1 terminals 1 (-) & 2
(+). Make certain to observe proper polarity
6. If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity
7. After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical
box
42MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
FACP
TB3
4 3 2 1
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
Figure 2.20 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the MS-5UD/MS-10UD.
MS-5UD/MS-10UD (TB3)ANN-80 (TB1)
Te rminal 4 GND (-)Terminal 1 (-)
Terminal 3 PWR (+)Terminal 2 (+)
Terminal 2 A (ANN-BUS)Terminal 3 (A)
Terminal 1 B (ANN-BUS)Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS" on page 77 in this manual for detailed programming information. Select the LCD
option for programming.
The ANN-S/PG Serial/Parallel Printer Interface module allows the ancillary connection of a serial
or parallel printer to the FACP for a real-time log of system events, detector status reports and event
history. Proceed with the installation as described in the following:
1. Ensure that all power (AC and DC) has been removed from the FACP.
2. Connect the ANN-S/PG to the FACP as illustrated in Figure 2.21
TB3
MS-5UD/MS-10UD
ANN-S/PG Module
ANN-BUS and power wiring are
supervised and power-limited
3. Using the DIP switches on the back of the ANN-S/PG module, assign an ID number
(address) to the module
4. Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to "ANN-BUS" on page 77)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to "Auto-Configure" on page 78)
5. Connect a printer to the ANN-S/PG Parallel and/or Serial connectors (refer to Figure 2.21 on
page 44)
2.8.6.1 Specifications
•Operating Voltage: 24 VDC
•Current (Alarm and Standby): 45 mA
•Ambient Temperature: 32
Figure 2.21 ANN-S/PG Connection to FACP
o
F to 120oF (0oC to 49oC)
Parallel
Cable
Connectors for
connection to
printer
Serial
•Max. Wiring Distance from FACP: 6,000 ft. (1,800 m)
•Mounting: Surface
•Dimensions: 6”W x 7-3/4”H x 1-7/16”D (15.2 cm W x 19.7 cm H x 3.7 cm D)
•For indoor use in a dry location only
2.8.6.2 PRN Printer Installation
When connected to the FACP via the ANN-S/PG module, the PRN prints the status changes
within the control panel and time-stamps the printout with the time of day and date that the
event occurred. It provides 80 columns of data on standard 9” x 11” tractor-feed paper. This
section contains information on connecting a printer to the control panel and setting the printer
options.
44MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
2.8.6.2.1 Connecting PRN Printer
Remote printers require a primary AC power source. If required for the fire alarm system
configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Since a secondary power source is not provided as a
standard feature, a separate UL-listed Uninterruptible Power Supply (UPS) should be used.
The building emergency power supply may be used, as long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the FACP via the ANN-S/PG module using a standard DB-25
cable. One end of the cable will plug into the DB-25 connector on the PRN printer and the
other end plugs into the parallel connector on the ANN-S/PG module. Note that the 9-pin DB9 port on the ANN-S/PG is used to connect a serial printer. The 25-pin port is used for a
Centronics parallel printer cable. Connect either a serial or parallel printer, but not both at the
same time.
2.8.6.2.2 Setting Printer Options
Refer to the documentation supplied with the PRN printer for instructions on using the printer
menu controls. Set the printer options (under the menu area) as shown in the following table:
Auto LFOn
PAPER
BIN 112/72”
BIN 212/72”
SINGLE12/72”
PUSH TRA12/72”
PULL TRA12/72”
PAP ROLL12/72”
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200745
InstallationANN-BUS Devices
2.8.7 ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including
as an interface with most customized graphic annunciators. The ANN-I/O can drive up to 40
LEDs. The following sections describe hardware installation. Refer to the section titled "ANNBUS" on page 77 for programming information.
2.8.7.1 ANN-I/O Board Layout
Figure 2.22 illustrates the ANN-I/O board showing locations of screw terminals for connection
to the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANNBUS ID number.
Terminals not used (future)
ANN-BUS Connector
Figure 2.22 ANN-I/O Board Layout
2.8.7.2 Specifications
•Max. ANN-BUS Voltage: 28 VDC
•Max. Current:
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
•Operating Temperature: 32
•For indoor use in a dry location only
o
F to 120oF (0oC to 49oC)
ANN-BUS (ID#)
Address DIP
switch
46MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
2.8.7.3 ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.23. After the
ANN-I/O is connected to the panel, it must be added to the system via FACP programming.
TB3
MS-5UD/MS-10UD
ANN-I/O Module
ANN-BUS and power wiring are
supervised and power-limited
Figure 2.23 ANN-I/O Connection to FACP
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200747
InstallationANN-BUS Devices
2.8.7.4 ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10
LEDs get their power from Pin 11 of the corresponding connector. Internal resistors are sized
so that there is approximately 10 mA of current for each LED. No series resistors are required.
LED outputs are mapped to output circuits. Refer to the section titled "ANN-I/O LED Zone
Assignments" on page 80 of this manual.
The LEDs are wired as illustrated in Figure 2.24. Note that the illustration depicts only
connectors P1 and P2. Wiring is identical for P3 (LEDs 21-30) and P4 (LEDs 31-40).
Figure 2.24 ANN-I/O Board Layout
48MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
2.8.8 ANN-LED Annunciator Module
The ANN-LED annunciator module provides LED annunciation of general system faults and input
zones when used with a compatible FACP. The ANN-LED module provides alarm (red), trouble
(yellow) and supervisory (yellow) indication for up to ten input zones.
Canadian Applications: The ANN-LED is supplied standard with the MS-5UD-7C and MS-10UD7C models. It is mounted to the dress panel included with these models.
2.8.8.1 ANN-LED Board Layout
Figure 2.25 illustrates the ANN-LED board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.25 ANN-LED Board Layout
2.8.8.2 Specifications
•Max. ANN-BUS Voltage: 24 VDC
•Max. Current:
Alarm: 68 mA
Standby: 28 mA
•Operating Temperature: 32
o
F to 120o F (0o C to 49o C)
•For indoor use in a dry location only
2.8.8.3 Mounting/Installation
Install the ANN-LED Module as described in the documentation supplied with the annunciator.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200749
InstallationANN-BUS Devices
2.8.8.4 ANN-LED Connection to FACP
Figure 2.26 illustrates the ANN-LED board wiring connections to the FACP.
FACP
-24 VDC
+24 VDC
ANN-BUS
Figure 2.26 ANN-LED Connection to FACP
ANN-LED
50MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
ANN-BUS DevicesInstallation
2.8.9 ANN-RLY Relay Module
The ANN-RLY relay module provides 10 programmable Form-C relays when used with a
compatible FACP.
2.8.9.1 ANN-RLY Board Layout
Figure 2.27 illustrates the ANN-RLY board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
The ANN-RLY relay module can be mounted inside the FACP main circuit board chassis.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200751
InstallationANN-BUS Devices
2.8.9.4 ANN-RLY Connection to FACP
Figure 2.28 illustrates the ANN-RLY board wiring connections to the FACP.
FACP
-24 VDC
+24 VDC
ANN-BUS
Figure 2.28 ANN-RLY Connection to FACP
ANN-RLY
52MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
User ProgrammingProgramming
SECTION 3Programming
3.1 User Programming
The MS-5UD/MS-10UD FACP is completely field programmable using the panel keypad and
requires no special software skills. While programming the F ACP, the fire pr otection capabilities of
!!!
the control panel are
Site-specific programming may be accomplished:
•Manual programming or editing, using the FACP keypad
The System All Normal screen will be displayed in a programmed system with no active alarms,
troubles or supervisories, as illustrated below:
enabled.
SYSTEM ALL NORMAL
10:00A 092105
See Page
Read Status mode can be entered while the panel is in any
supervisory event exists at the panel, the event must be cleared before entering Programming mode.
To access any of the programming or read status features, the Enter or Mode key must be pressed,
which will cause the LCD to display the following:
mode of operation. If an alarm or
1=READ STATUS MODE
2=PROGRAMMING MODE
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read
Status Mode which allows the user to view the programmed features and status of the control panel
The Read Status feature is not password protected. Refer to "Read Status" on page 113 for a
detailed description of this feature.
Pressing 2 will select user Programming Mode which may only be accomplished by an authorized
person. After pressing 2, a screen will prompt for a password. After entering the correct password,
the user may select from a list of programming options.
Exit Programming and Read Status Mode
The programmer can exit any mode by repeatedly pressing the keypad ESC (Escape) key until the
display reads System All Normal. Note that the data which is entered during Programming mode
is not
saved until the programmer exits this mode by repeatedly pr essing the ‘ESC’ key. If the Reset
key is pressed or power is lost before exiting Programming mode, all data just entered will be lost.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200753
ProgrammingInitial Power-up
User Programming Levels
There are two user programming levels:
•User Master Program Level 1 is used for programming panel specific data relating to device
types, zoning, messages, control panel functions, etc.
•User Maintenance Program Level 2 is used by a qualified operator to access features such as
Disable/Enable, View and Clear History, Walktest and System Time Change.
3.2 Initial Power-up
The following sections describe the initial programming procedures for a new system. The same
procedures are used to modify programming in an existing system.
After completing the wiring of devices to the FACP, apply power to the control panel. If wiring has
not been completed and/or End-of-Line resistors are not installed at the panel, a trouble condition
will be indicated at the panel and a trouble message will be displayed on the LCD. Following is an
example of a possible trouble message that may be displayed.
TROUBL PULL STATION
ZONE 1 OPEN FAULT
09:03A 012106
3.3 Programming Screens Description
Two options are available when the Enter key is pressed: Read Status and Programming Mode.
The Read Status and Programming options have multiple functions or features whi ch may be
chosen. To view all of the choices, it is necessary that the programmer scroll through a number of
additional subscreens. These selections are displayed on multiple screens to make them more
See Page
readable for the programmer. Refer to "Master Programming Level" on page 56, for additional
information on the various screens.
The title of the main option screen will always be displayed at the top of the subscreens for the
programmer’s convenience. If additional subscreens exist, an Up or Down arrow will be displayed
in the upper right corner of the screen being viewed. The programmer can then press the keypad
Up or Down arrow key to view the new subscreen. To select one of the choices in a screen, the
programmer presses the keypad numerical key corresponding to the desired choice.
Note that subscreens may also have multiple options which require viewing more than one screen.
The same process, as detailed in the previous paragraphs, is follo w ed to view all option choices.
3.4 Programming and Passwords
There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in
See Page
nonvolatile memory. The factory set passwords can be changed by the user as described in
"Password Change" on page 98. If an invalid password is entered, the blinking cursor will return to
the first password character position. To exit Programming or Read Status mode at any time, press
the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC key
in order to store the program data entered during this mode. If the Reset key is pressed or power is
lost before exiting Programming mode, the data just entered will not be saved.
54MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Programming and PasswordsProgramming
To access user Programming mode, press the Enter or Mode key. The LCD will display the
following:
1=READ STATUS MODE
2=PROGRAMMING MODE
To enter the user Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
*****
Entering the Master
If the Maintenance
level password (default 00000) will cause the following screen to appear:
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200755
ProgrammingMaster Programming Level
3.5 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble LED flashes until Programming mode is exited. The following display will
appear:
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as
illustrated below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
56MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
3.5.1 Input Zones
The Input Zones option allows the user to initially program or change the programming for the five
input zones (circuits) on the MS-5UD or the ten input zones (circuits) on the MS-10UD. Pressing
1, while viewing Programming Screen #1, will select the Input Zones option and display a screen
similar to the following:
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
INPUT ZONES
1=ZONE 1
2=ZONE 2
3=ZONE 3
Input Zone Screen #1
Pressing the down arrow key will display additional screens for Input Zones 4 through 5 in the MS5UD or Input Zones 4 through 10 in the MS-10UD. To program a specific zone, press the number
key corresponding to the desired zone while viewing one of the Input Zone screens. To program
Input Zone 1, press the 1 key while viewing Input Zone Screen #1. The following screens will be
displayed:
PULL STATION
Normal
ZONE 1
PRESS TO EDIT
Edit Input Zone Screen #1
To change the programming for the displayed zone, press the keyboard ‘down’ arrow key to
view the Edit Zone screens.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200757
ProgrammingMaster Programming Level
The following examples show the editing of Input Zone 1:
INPUT ZONE 1
1=ENABLED YES
2=TYPE PULL STATION
3=VERIFICATION NO
Edit Input Zone Screen #2
INPUT ZONE 1
1=PAS/PRE-SIGNAL DLY
NO DELAY
Edit Input Zone Screen #3
INPUT ZONE 1
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
Edit Input Zone Screen #4
Enable/Disable Zone
To Enable or Disable the zone, press the 1 key while viewing the Edit Input Zone Screen #2.
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No is selected, the zone will be disabled by the control panel, preventing the circuit from
reporting alarms and troubles to the panel. The control panel LCD will display the zone which
has been disabled and FACP will turn on the Trouble LED.
Type
T o select the type of zone being programmed, press the 2 key while viewing the Edit Input Zone
Screen #2. This will cause the control panel to display the following Zone Type Screen:
ZONE TYPE
1=PULL STATION
2=WATERFLOW
3=WATERFLOW NS
Zone Type Screen #1
58MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
Pressing the down arrow key will display additional zone types as indicated in the following
table.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
Verification
See Page
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition
and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Zone Screen
#2 so that the display reads Verification On. Each time the 3 key is pressed, the display will
toggle between V e rification On and Verification Off. For a detailed description, refer to "Alarm
Verificati on (None or One Minute)" on page 112.
Note that verification can only be enabled for a zone that is programmed as a smoke detector
type. Zones programmed for any other type will not allow the Verification feature to be
enabled. Do not
use the verification feature if a mix of smoke detectors and normally open
contact devices are connected to the same zone.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200759
ProgrammingMaster Programming Level
INPUT ZONE #
1=PAS/PRE-SIGNAL DLY
NO DELAY
Edit Input Zone Screen #3
See Page
See Page
PAS/Pre-Signal Delay
Pressing 1 while viewing Edit Input Zone Screen #3 will display the following screen:
The Pre-signal option programs the zone to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the
alarm relay and communicator will respond to the initial alarm immediately. To enable the Presignal feature, press 2 while viewing P AS/Pre-Signal Screen. Refer to "Presignal" on page 1 10.
PAS
The PAS (Positive Alarm Sequence) option will program the zone to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time
of up to 3 minutes. To enable the PAS feature, press 3 while viewing the PAS/Pre-Signal
Screen. This option is available only for circuits programmed as smoke detector circuits. Refer
to "Positive Alarm Sequence" on page 110.
Noun/Adjective
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
*****************
Edit Input Zone Screen #4
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
detector currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #4 will
cause the following screen to be displayed:
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=FUTURE USE
4=FUTURE USE
Noun/Adjective Screen
60MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
Pressing 1 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Adjective
screens. Press the number corresponding to the adjective that is to be used as a descriptor for
the location of the detector currently being programmed. When an adjective has been selected,
it will appear at the top of the display as indicated by the asterisks.
Pressing 2 while viewing the Noun/Adjective Screen will cause the following screen(s) to be
displayed. Note that the keyboard down arrow key must be pressed to see all the Noun screens.
Press the number corresponding to the noun that is to be used as a descriptor for the location of
the detector currently being programmed. When a noun has been selected, it will appear at the
top of the display as indicated by the asterisks.
The Description selection allows the programmer to enter additional information about the zone
currently being programmed. This information will be displayed as part of the device label on
the display. Pressing 2 while viewing Edit Input Zone Screen #4 will cause the following
screen to be displayed:
INPUT ZONE #
1=NOUN/ADJECTIVE
2=DESCRIPTION
ZONE # DESCRIPTION
Edit Input Zone Screen #4
PRESS ENTER IF DONE
********************
Adjective/Noun Screen
A flashing cursor will appear at the first asterisk to the left. The programmer can enter
additional descriptive information about the device being programmed. This information will
appear on the display along with the standard device label information.
A maximum of 20 characters (including spaces) can be entered. To enter alphanumeric
characters from the keypad, repeatedly press the appropriate key until the desired character is
displayed in the first position. For example, to enter the letter B, press the 2 (ABC) key three
times to toggle through the characters 1, A and B. Press the right arrow key to move the cursor
one position to the right and repeat the process to enter the next character. To enter a space,
press the * (QZ) key four times until a blank appears in the desired position. When all
characters have been entered, press the Enter key to store the information. The display will
return to the Edit Detector Screen #5, displaying the new information at the bottom of the
screen.
Recall/Increment Function
In addition, the user may use the Recall/Increment function at any time when the cursor is on
the first letter of the Description, Adjective or Noun field as follows:
•If the zero key is pressed, a 0 is placed in the first letter position
•If the zero key is then pressed a second time with no intervening key actions, the entire field
is replaced with the field entered for the previous device programmed
, and the cursor moves
to the last character of the field (Recall function). The Recalled Adjective or Noun field may
now be changed letter-by-letter
•If the zero key is pressed again with no other intervening key actions and the last character in
the field is a number 0-9, the number is incremented by one. If the last character is a letter, it
changes to a 0. If the last character goes from 9 to 0 and the characters to the left of the last
character are also numbers, they are also incremented (overflow)
•The above increment function may be repeated with each press of the zero key
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200763
ProgrammingMaster Programming Level
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
As an example, the user could quickly enter ‘FLR_3_ROOM_305’ as follows:
1. The cursor is on the first letter of the Adjective field. Press the zero key twice to display
FLR_3
2. With the cursor on the first letter of the Noun field, press the zero key twice to recall the
display ROOM_304. The cursor automatically jumps from the first to the last letter of the
Noun field
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305
4. Press the Enter key to store the information
3.5.2 NAC (Notification Appliance Circuit)
The options for the NACs on the control panel main circuit board can be configured by pressing 2
while viewing Programming Screen #2. The following screens will be displayed:
NACS
1=NAC 1 3=NAC 3
2=NAC 2 4=NAC 4
NAC Selection Screen
The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3 or 4 for NAC 4.
To program an NAC circuit, press the number corresponding to the NAC to be programmed. The
following screens will be displayed for each selection:
NAC #
1=ENABLED YES
2=CODING
STEADY
NAC Screen #1
NAC #
1=SILENCE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
NAC Screen #2
64MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
3.5.2.1 Enabled
Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This
will prevent the selected main circuit board NAC from activating its devices. Each press of the
1 key will cause the display to toggle between Enabled Yes and Enabled No.
Note that if a circuit is disabled, a trouble will be logged on the FACP until the circuit is
enabled.
NAC #
1=ENABLED
2=CODING
STEADY
NAC Screen #1
3.5.2.2 NAC Coding
The Coding feature allows the programmer to select the type of output that the main circuit
board notification appliances will generate when activated. Pressing 2 while viewing NAC
Screen #1 will cause the following displays to appear:
CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen #1
CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2
CODING
1=SYNC SYSTEM SENSR
2=SYNC WHEELOCK
3=SYNC GENTEX
Coding Screen #3
CODING
1=SYNC FARADAY
2=SYNC AMSECO
Coding Screen #4
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200765
ProgrammingMaster Programming Level
The programmer can select the notification appliance output by pressing the number
corresponding to the desired output. The coding selections are:
•Steady - a continuous output with no coding
•March Time - 120 ppm (pulse-per-minute) output
•California - 10 seconds on and 5 seconds off
•Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ second
off
•Two Stage 3 Minutes or 5 Minutes - Refer to “Two Stage Operation” on page 66. for a
description of this feature
•Synchronized output for System Sensor, Wheelock, Gentex, Faraday or Amseco - Refer to
"Synchronized NAC Operation" on page 66 for additional information.
Selection of one of the above options will cause the control panel to store the information in
memory and return the display to NAC Screen #1, which will display the new coding choice.
•2nd stage output - Temporal coding as described above
If Two Stage operation is programmed as the Coding option, the following sequence of events
will occur during an alarm.
1. The on-board NACs will activate with a 1st stage output upon activation of any alarm
2. If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not
been
pressed, all NACs presently in 1st stage activation will go to 2nd stage activation
3. If an Acknowledge switch has been pressed, any NACs currently in 1st stage activation
will remain in 1st stage. Pressing the Acknowledge switch does not affect NACs already
in 2nd stage activation
4. If another alarm point is activated and the countdown timer is counting, the alarm point
will have no effect on the NACs
5. If another alarm point is activated and the countdown timer has stopped countin g due to
the Acknowledge switch being pressed, the countdown timer will restart and the NACs
will respond as outlined in step 1. NACs already in 2nd stage activation will not be
affected
3.5.2.2.2 Synchronized NAC Operation
Synchronization is a panel feature that controls the activation of notification appliances in such
a way that all devices will turn on and off at exactly the same time. This is particularly critical
when activating strobes which must be synchronized to avoid random activation and a potential
hazard or confusion. The F ACP can be programmed to operate with a variety of manufacturer’s
devices.
66MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
3.5.2.2.2.1 Maximum Number of Strobes for Synchronization
The maximum current draw for a Notification Appliance Circuit cannot exceed 2.5 amps for
models with the FLPS-3 power supply or 3.0 amps for models with the FLPS-7 power supply
(refer to the AC Power section under "Specifications" on page 14). Refer to the
manufacturer’s documentation supplied with the Strobes to determine the maximum current
draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that
can be attached to each circuit. Following is a list of the strobes that have been tested with this
FACP and the maximum number that can be connected to each NAC. Make sure that the NAC
maximum current is not exceeded:
NAC #
1=SILENCE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
NAC Screen #2
Strobe ManufacturerF ACP with FLPS-3 Power Supply:
Maximum Number of Strobes
System Sensor3546
Wheelock2450
Gentex2239
Faraday2233
Amseco1934
FACP with FLPS-7 Power Supply:
Maximum Number of Strobes
3.5.2.3 Silence
Pressing 1 while viewing NAC Screen #2 will cause the following screen to be displayed:
Pressing 1 while viewing the Silenceable Screen will program the selected NAC as a
silenceable circuit. This will allow the NAC to be silenced by pressing the Alarm Silence key
or by the Auto Silence feature.
Pressing 2 while viewing the Silenceable Screen will program the selected NAC as a
nonsilenceable circuit. This will prevent the selected main circuit board NAC from being
silenced by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing 3 while viewing the Silenceable Screen will program the selected NAC as a
synchronized mute circuit. Refer to "Synchronized NAC Operation" on page 66 for a
description of synchronization.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for Sync Mute, only the audible devices will be turned off if the Silence key is
pressed or if the Autosilence feature is enabled. The visual devices (strobes, etc.) will continue
to operate.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200767
ProgrammingMaster Programming Level
PROGRAM NAC #
1=SILENCEABLE YES
2=AUTO SILENCE NO
3=SIL INHIBITED NO
NAC Screen #2
3.5.2.4 Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board
silenceable notification appliances after a programmed length of time. To enable this feature
and program the time delay before Auto Silence activation, press 2 while viewing NAC Screen
#2. The following screens will be displayed:
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
Programming Screen #1
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the
display will return to NAC Screen #1.
3.5.2.5 Silence Inhibited
The Silence Inhibit feature, when enabled, prevents the silencing of the selected main circuit
board NAC for a period of one minute. Resetting the F ACP will also be prevented for one
minute while the NAC programmed for silence inhibit is activated. Pressing 3 while viewing
NAC Screen #2 will cause the display to change from the factory default of Silence Inhibit No
to Silence Inhibit Yes. Each press of the 3 key will cause the display to toggle between the two
options.
3.5.3 Relays
Pressing 3 while viewing Programming Screen #1 will allow the programmer to configure the three
main circuit board Form-C relays. The following screen will be displayed:
To program Relay 1, 2 or 3, press the number corresponding to the selected relay. The following
screens will appear for each relay to be programmed:
RELAY TYPE
1=ALARM
2=TROUBLE
3=SUPERVISORY
Relay Screen #1
RELAY TYPE
1=PROCESS MONITOR
2=AC LOSS
3=HAZARD
Relay Screen #2
While viewing the selected screen, press the number corresponding to the desired relay type to
program the main circuit board relay. The choice will be stored in memory and the display will
return to the Relay Type Screen which will show the programmed type choice. Press the Escape
key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining
relays.
RELAY TYPE
1=COMM FAIL
2=MEDICAL
3=SILENCEABLE ALARM
Relay Screen #3
Note: A relay programmed with the Silenceable Alarm type will deactivate when the FACP Alarm
Silenced LED is illuminated.
System Setup allows the programmer to configure the following control panel features:
•Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
•Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout, which is blank, to a user defined readout when the control panel is in
Normal condition.
•Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
•Tr ouble Reminder: This feature, when enabled, provides an audible reminder that an alarm or
trouble still exists on the FACP after the control panel has been silenced. The control panel
piezo sounder will pulse once every 15 seconds during an alarm and every two minutes
during a trouble condition, after the Alarm Silence or Acknowledge key is pressed. The
piezo will continue to sound at these rates until the alarm or trouble condition is cleared. If
the Trouble Reminder feature is not
hours, the panel will reactivate the trouble sounder and retransmit the trouble condition to the
central station if connected.
•Charger Disable: This option allows the programmer to disable the onboard battery charger
in the event an external battery charger is being used.
Pressing 1 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
enabled and a trouble condition is not cleared within 24
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TROUBLE REMIND NO
2=FUTURE USE
3=CHARGR DISABLE NO
System Setup Screen #2
70MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
3.5.4.1 Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1
while viewing System Setup Screen #1. The following screen will be displayed:
TIMERS
1=PAS DELAY 120
2=PRE SIGNAL 120
3=WATERFLW DELAY 0
Timer Screen #1
TIMERS
1=AC LOSS DELAY 2
Timer Screen #2
TIMERS
1=PAS DELAY 120
2=PRE SIGNAL 120
3=WATERFLW DELAY 0
Timer Screen #1
3.5.4.1.1 PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay. To select a PAS delay of 001 to 180
seconds for all devices programmed for PAS, press 1 while viewing Timer Screen #1. The
following display will appear:
PAS DELAY
RANGE 000-180 SECONDS
PAS Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 005 for five seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
3.5.4.1.2 Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay. To select a Pre-signal delay
of 001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer
Screen #1. The following screen will be displayed:
PRESIGNAL DELAY
RANGE 000-180 SECONDS
Pre-signal Delay Screen
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200771
ProgrammingMaster Programming Level
TIMER
1=PAS DELAY 120
2=PRE SIGNAL 120
3=WATERFLW DELAY 0
Timer Screen #1
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
Note that the FACP can have both PAS and Pre-signal timers programmed with values but a
zone can only use either the PAS or Pre-signal feature, but not both.
3.5.4.1.3 Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any
built-in delays of the waterflow device. The factory default setting for Waterflow delay is 000
for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for
Waterflow delay, press 3 while viewing Timer Screen #1. The following screen will be
displayed:
WATERFLOW DELAY
RANGE 00-90 SECONDS
TIMER
1=AC LOSS DELAY 2
Timer Screen #2
Waterflow Delay Screen
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the
time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
3.5.4.1.4 AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the
length of the desired delay. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY
RANGE 00-23 HOURS
AC Loss Delay Screen #1
A flashing cursor will appear in the lower left corner of the display. The factory default setting
is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 23 hour delay). When
the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC
Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC Loss Delay setting.
72MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
3.5.4.2 Banner
The top line of the display, which appears when the control panel is in normal mode, can be
changed by using the Banner option. Pressing 2 while viewing System Setup Screen #1 will
cause the following to be displayed:
SELECT BANNER
1=FACTORY BANNER
2=USER BANNER
Select Banner Screen
Pressing 1 while viewing the Select Banner Screen will display the following screen:
FACTORY BANNER
PRESS ENTER IF OK
User Defined Banner Screen #1
This screen allows the user to select the factory default Banner which will be displayed when
the system is in Normal Mode of operation. Press the Enter key to accept this as the default
display. Press the Escape key to cancel and return to the Select Banner Screen.
Pressing 2 wile viewing the Select Banner Screen will display the following screen:
USER BANNER-LINE 1
PRESS ENTER IF OK
User Defined Banner Screen
This screen allows the programmer to enter a custom banner. A flashing cursor will appear in
the bottom left corner of the display. A maximum of 20 characters (including spaces) can be
entered into the screen. After entering up to 20 characters in the screen, press Enter to store the
entry. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until
the desired character is displayed in the first position. For example, to enter the letter B, press
the 2 (ABC) key three times to toggle through the characters 1, A and B. Press the right arrow
key to move the cursor one position to the right and repeat the process to enter the next
character. To enter a space, press the * (QZ) key four times to place a blank in the desired
position. When all characters have been entered, press the Enter key to store the information.
The display will return to the Select Banner Screen.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200773
ProgrammingMaster Programming Level
SYSTEM SETUP
1=TIMERS
2=BANNER
3=TIME-DATE
System Setup Screen #1
3.5.4.3 Time-Date
The control panel time and date can be changed by pressing 3 while viewing the System Setup
Screen #1. The following screen will be displayed:
TIME AND DATE
1=TIME 10:00 AM
2=DATE 04072005
3=CLOCK FORMAT 12HR
Time-Date Screen #1
TIME AND DATE
1=DAYLIGHT SAVINGS
Time-Date Screen #2
3.5.4.3.1 Time
T o change the time, press 1 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER TIME AS 12HRS
10:00 AM
1=AM 2=PM
Time Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
time. To change the time, enter the two-digit hours followed by the two-digit minutes. The
cursor will move one position to the right each time a digit is entered. After the last minutes
digit is entered, the cursor will again move one position to the right. At this point enter 1 for
AM or 2 for PM. The display will then return to the Time-Date Screen which will show the
new time entry. If an error is made while entering a digit, press the CLR key to delete the entire
entry and beginning again.
74MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
3.5.4.3.2 Date
T o change the date, press 2 while viewing the Time-Date Screen. The following screen will be
displayed:
ENTER DATE
**-**-****
MONTH DAY YEAR
04-07-2005
Date Screen
A flashing cursor is located toward the top left of the display. Below the cursor is the current
date. To change the date, enter the two-digit month followed by the two-digit day and then the
two-digit year (01 for 2001, 02 for 2002, etc.). The cursor will move one position to the right
each time a digit is entered. After the last year digit is entered, the display will return to the
Time-Date Screen which will show the new date entry. If an error is made while entering a
digit, press the CLR key to delete the entire entry and beginning again.
3.5.4.3.3 Clock Format
The clock can be configured to display 12 hour (AM & PM) or 24 hour (military) time.
Pressing 3 while viewing the Time-Date screen will cause the display to toggle between 12HR
and 24HR. Select 12HR for 12 hour display or 24HR for 24 hour display.
Note: If the clock is changed to 24 hour (military) format, the date will change to the European
standard of Day-Month-Year (for display purposes only).
TIME AND DATE
1=DAYLIGHT SAVINGS
Time & Date Screen #2
3.5.4.3.4 Daylight Savings Time
Pressing 1 while viewing Ti me-Date Screen #2 will cause the following screens to be displayed:
Pressing 1 while viewing Daylight Savings Screen #1 will cause the display to toggle between
Enabled Yes and Enabled No. The control panel will automatically update the time for daylight
savings time when Enabled Yes is selected.
Pressing 2 while viewing Daylight Savings Screen #1 will display another screen which allows
the programmer to select the month that daylight savings time will begin. In this sub-screen,
pressing 1 will select March, 2 will select April and 3 will select May.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200775
ProgrammingMaster Programming Level
SYSTEM SETUP
1=TROUBLE REMIND NO
2=FUTURE USE
3=CHARGR DISABLE NO
System Setup Screen #2
See Page
Pressing 3 while viewing Daylight Savings Screen #1 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will begin. In the
first sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will
select the third week, while in the second sub-screen, pressing 1 will select the fourth week and
2 will select the last week of the selected month.
Pressing 1 while viewing Daylight Savings Screen #2 will display another screen which allows
the programmer to select the month that daylight savings time will end. In this sub-screen,
pressing 1 will select September, 2 will select October and 3 will select November.
Pressing 2 while viewing Daylight Savings Screen #2 will display two sub-screens which allow
the programmer to select the week of the month that daylight savings time will end. In the first
sub-screen, pressing 1 will select the first week, 2 will select the second week and 3 will select
the third week, while in the second sub-screen, pressing 4 will select the fourth week and 5 will
select the last week of the selected month.
3.5.4.4 Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for
alarms and troubles, after the panel has been silenced. Refer to "System Setup" on page 70, for
a detailed description of this feature. Pressing 1 while viewing System Setup Screen #2 will
cause the display to toggle to Trouble Rem Yes , which enables this feature. Each press of the 1
key will cause the display to toggle between Trouble Rem Yes and Trouble Rem No.
Note that if the Trouble Reminder feature is not enabled, a trouble existing on the panel for
more than 24 hours will cause the FACP to resound the trouble sounder.
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to enable or
disable the onboard battery charger . If an external battery charger is being used, the onboard
battery charger must be disabled. Each press of the 3 key will toggle between Chrgr Disable No
and Chrgr Disable Yes.
3.5.5 Option Modules
Options available for the FACP include annunciators, printer connection for acquiring hardcopy
printouts of panel data and onboard DACT.
Pressing 2 while viewing Programming Screen #2 will display the following screen:
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT
Options Screen
76MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
3.5.5.1 ANN-BUS
Pressing 1 while viewing the Option Modules screen will cause the control panel to display the
following screens.
ANN-BUS
1=BUS ENABLED NO
2=BUS MODULES
3=AUTO CONFIGURE
A variety of ANN-BUS option modules can be installed in the FACP. These devices
communicate with the FACP over the ANN-BUS terminals on the control panel.
3.5.5.1.1 ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are installed on the ANN-BUS terminals. To
enable the ANN-BUS, press 1 while viewing ANN-BUS screen #1 so that the display reads
ANN-BUS Enabled Yes. Each press of the 1 key will cause the display to toggle between ANNBUS Enabled Yes and ANN-BUS Enabled No.
3.5.5.1.2 BUS Modules
If an ANN-BUS module is installed, press 2 while viewing ANN-BUS screen #1 to select
ANN-BUS addresses for the module(s). The following screen will be displayed.
Pressing the down arrow key will allow the programmer to view additional screens displaying
Addresses 1 - 8. Pressing the number corresponding to the desired address will display a screen
with technical information about the selected module.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200777
ProgrammingMaster Programming Level
In the technical information screen, pressing 1 for Type will display the following screens:
ANN-BUS MODULE TYPE
1=NONE
2=ANN-80
3=ANN-I/O
Module Type Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
Press the number corresponding to the module type, if any, that is installed with the selected
address. This will enable the module.
3.5.5.1.3 Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and
automatically program the device type and address into the system. Pressing 3 while viewing
ANN-BUS Screen #1 will begin the Auto-Configure process and cause the following screen to
be displayed:
The Printer Option allows the user to configure the optional printer. Pressing 1 while viewing
the ANN-BUS Screen #2 will display the following screens:
ANN-S/PG OPTIONS
1=PORT PARALLEL
2=PRINTER SUPV NO
3=OFFLINE TIMER 60
Pressing 1 for Port while viewing Printer Options screen #1 will allow the programmer to select
between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause the
display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that
the interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select
an offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print
Options screen #1. Each press of the 2 key will cause the display to toggle between Printer Supv NO for no supervision and Printer Supv YES for printer supervision. Note that this option
is not selectable if the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an Offline Timer by
pressing 3 while viewing Print Options screen #1. The resultant screen allows the programmer
to program the Offline Timer for a delay of between 0 and 255 seconds before loss of printer
supervision is reported as a trouble.
If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be
available. The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the
Serial Port option has been selected.
Pressing 1 for Baud Rate while viewing Printer Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of 19200, 9600 or 2400.
Pressing 2 for Data Bits while viewing Printer Options screen #2 will cause screens to appear
which allow the user to select 5, 6, 7 or 8 Data Bits.
Pressing 3 for Parity while viewing Printer Options screen #2 will cause a screen to appear
which allows the user to select between No Parity, Even Parity or Odd Parity.
Pressing 1 for Stop Bits while viewing Printer Options screen #3 will cause a screen to appear
which allows the user to select between 0.5, 1.0 or 2.0 Stop Bits.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200779
ProgrammingMaster Programming Level
3.5.5.1.5 ANN-I/O LED Zone Assignments
The information displayed by LEDs on every ANN-I/O module is not programmable and will
therefore be as indicated in the following table.
The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options
Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not the ANN-80
annunciator must be unlocked by its key before any annunciator key presses will function.
Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Y es (annunciator must be unlocked for keys to function) and Lock Enable No (lock
position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display
to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step button never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether
the Silence button on any installed ANN-80 annunciator will function normally or always be
ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence
button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether
the Reset button on any installed ANN-80 annunciator will function normally or always be
ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset
button never functions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether
the Drill button on any installed ANN-80 annunciator will function normally or always be
ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill
button never functions).
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200781
ProgrammingMaster Programming Level
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
3.5.5.2 ANN-RLY Options
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen
The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Opti on
screen, press the number key corresponding to the relay to be programmed. Following is a list
of the available programming options for each relay:
•General Alarm
•General Trouble
•General Supervisory
•AC Loss
•Waterflow Delay
•Input Zone 1
•Input Zone 2
•Input Zone 3
•Input Zone 4
•Input Zone 5
•Input Zone 6
•Input Zone 7
•Input Zone 8
•Input Zone 9
•Input Zone 10
•Silenceable Alarm
•Not Assigned
82MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
OPTION MODULES
1=ANN-BUS
2=ON BOARD DACT
3.5.5.3 Onboard DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides communication to a
central station. Pressing 2 while viewing the Option Module Screen will cause the following
screens to be displayed:
ON BOARD DACT
1=PRIM PHONE TCH TNE
2=SCND PHONE TCH TNE
3=CENTRAL STATION
Option Module Screen
3.5.5.3.1 Primary Phone
Press 1 while viewing Onboard DACT Screen to program the type of primary phone line being
connected to the DACT. The following screen will be displayed:
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33 (EURO)
3=ROTARY 60/40 (U.S.)
Primary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33
or 3 to select Rotary dialing with a make/break ratio of 60/ 40.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200783
ProgrammingMaster Programming Level
ON BOARD DACT
1=PRIM PHONE
2=SCND PHONE
3=CENTRAL STATION
Onboard DACT
3.5.5.3.2 Secondary Phone
Press 2 while viewing Onboard DACT Screen to program the type of secondary phone line
being connected to the DACT. The following screen will be displayed::
PHONE LINE
1=TOUCHTONE
2=ROTARY 67/33 (EURO)
3=ROTARY 60/40 (U.S.)
Secondary Phone Type Screen
Press 1 to select Touchtone dialing, 2 to select Rotary dialing with a make/break ratio of 67/33
or 3 to select Rotary dialing with a make/break ratio of 60/ 40.
3.5.5.3.3 Central Station
Central Station programming configures the control panel DACT for contacting the central
station. Pressing 3 while viewing Onboard DACT Screen will cause the following screens to be
displayed:
CENTRAL STATION
1=REPORTING NO
2=REPORT STYLE
BACKUP ONLY
Central Station Screen #1
CENTRAL STATION
1=PRIMARY
2=SECONDARY
Central Station Screen #2
3.5.5.3.3.1 Reporting
To enable the DACT for reporting FACP activity to the central station, press 1 while viewing
Central Station Screen #1 so the display reads Reporting Yes. Each press of the 1 key will
toggle the display between Reporting Yes and Reporting No.
3.5.5.3.3.2 Report Style
The DACT can be programmed to transmit reports to primary and/or secondary central station
phone numbers as a backup. Press 2 while viewing Central Station Screen #1 to display the
following screen:
REPORT STYLE
1=BACKUP ONLY
2=BOTH
3=FIRST AVAILABLE
Backup Reporting Screen
Press 1 to have all reports transmitted to the central station secondary phone number as a
backup only if the primary phone line fails, 2 to transmit all reports to both the primary and
secondary phone numbers all of the time or 3 to send reports to the first available phone
number.
84MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3.5.5.3.3.3 Central Station Primary and Secondary Phone Numbers
Pressing 1 for Primary or 2 for Secondary , while viewing Central Station Screen #2, will display
the following screens.
Note that the following information must be entered for both the Primary and Secondary
Central Station Phone Numbers.
CENTRAL STATION #
1=TEST TIME INT 24
2=ACCOUNT CODE 0000
3=24HR T TIME 0021
Central Station Screen #2
Primary/Secondary Screen #1
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
CENTRAL STATION
1=COMM FORMAT
ADEMCO CONTACT ID
2=EVENT CODES
Primary/Secondary Screen #3
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200785
ProgrammingMaster Programming Level
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
Test Time Interval
Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be
displayed:
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24
hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens
shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
ACCOUNT CODE
RANGE 0000-FFFF
Account Codes Screen
The Account Code, which is assigned by a Central Station, depends on the communication
format being used. The Account Code screen will have a flashing cursor in the lower left
corner. Program the supplied 4-digit account code using 0 - 9 and A- F keys. Enter the first
digit, then press the right arrow key to move the cursor to the right, one position. Repeat the
process until all digits are entered. Press the Enter key to store the account code in memory.
86MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR T TIME
Primary/Secondary Screen #1
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
Use the 24 Hour T est T ime screen to program the time that the DACT will transmit the 24 Hour
T est to the Central Station. A flashing cursor will appear in the lower left corner of the screen.
Enter a four digit number representing the test time using military time (0000 = midnight and
2359 = 11:59PM).
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following screen to be
displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
The Phone Number screen is used to enter the Central Station phone number that the DACT
will be contacting. A maximum of 20 characters can be entered with valid entries being 0 - 9
and A - F where A = *, B = #, C = look for secondary dial tone for up to 2 seconds (then dial
anyway), D = 3 second pause, E = 5 second pause and F = end of phone number (must be
entered at end of phone number).
A flashing cursor will appear in the lower left corner of the screen. Enter the first digit then
press the right arrow key to move the cursor to the right one position. Enter the second digit
and repeat the process until all digits are entered. Press the Enter key to store the phone number
in memory.
Enter the digits as you would like the number to be dialed. For example, if it’s necessary to dial
9 before dialing a number outside the building, you may wish to pause after dialing 9. Enter 9
followed by D for a three second pause or E for a five second pause then the phone number
followed by an F to indicate the end of the number.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200787
ProgrammingMaster Programming Level
Communication Format
Pressing 1 while viewing Primary/Secondary Screen #3 will cause the following screen to be
displayed:
CENTRAL STATION
1=COMM FORMAT
Primary/Secondary Screen #3
COMM FORMAT
1=ADEMCO CONTACT ID
2=SIA-DCS-8
3=SIA-DCS-20
The Communication Format is determined by the type of receiver that the DACT is transmitting
to. Consult your Central Station for proper selection or consult our factory representatives.
For any format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
Comm Format screen. The following table describes each format:
Table 3.1 Communication Formats
Screen SelectionCommunication Format Description
ADEMCO CONTACT IDContact ID, DTMF, 1400/2300 ACK
SIA-DCS-8Security Industry Association, 8 messages per call
SIA-DCS-20Security Industry Association, 20 messages per call
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be
displayed:
Pressing the down arrow key allows viewing of all Events associated with the selected
Communication Format. Pressing the number corresponding to the event displayed in each
screen will display its default active and restoral event codes which can be customized by the
programmer.
For example, if Ademco Contact ID is the selected format, pressing 3 for Zone 3 Alarm will
display the following screen which allows the Event Code to be changed from the default value.
ZONE 3 ACTIVE
115
88MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10
and the corresponding Event Codes for Ademco Contact ID and SIA DCS Formats. Note that
Table 3.3 on page 90, Table 3.4 on page 91, Table 3.5 on page 92 and Table 3.6 on page 94 list
the default settings for Zone 1 through Zone 10. These can be changed to any of the Types
listed in Table 3.2 .
Note: The third character in the SIA-DCS Format (x in the table below) represents the zone
number.
The following tables list all of the Events and their default Event Codes for the Ademco Contact
ID and SIA-DCS Communication Formats.
Note: A detector freeze condition will be reported as a Supervisory Event Code.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200789
ProgrammingMaster Programming Level
Ademco Contact ID Format - Primary Central Station Phone Number
The information shown in Table 3.3 is automatically programmed for the Primary Central
Station phone number Event Codes when Ademco Contact ID Format is selected. To disable
event reporting, select the desired Event Code to be disabled and press 0 or Clear and then
Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save
the selection). Note that disabling the Event Code for the Primary Central Station Phone
Number Event Code will also disable that Event Code for the Secondary Central Station Phone.
Ademco Contact ID Format - Secondary Central Station Phone Number
The information shown in Table 3.4 is automatically programmed for the Secondary Central
Station phone number Event Codes when Ademco Contact ID Format is selected. To disable
event reporting, select the desired Event Code to be disabled and press 0 or Clear and then
Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save
the selection). Note that disabling the Event Code for the Primary Central Station Phone
Number Event Code will also disable that Event Code for the Secondary Central Station Phone.
Table 3.4 Ademco Contact ID Secondary # Event Codes
SIA-DCS Format - Primary Central Station Phone Number
The information shown in Table 3.5 is automatically programmed for the Primary Central
Station phone number Event Codes when SIA-DCS Format is selected. To disable event
reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to
disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the
selection). Note that disabling the Event Code for the Primary Central Station Phone Number
Event Code will also disable that Event Code for the Secondary Central Station Phone.
Table 3.5 SIA-DCS Primary # Event Codes
Event DescriptionEvent Code Settings
ActiveRestoral
Primary # Zone 1 Alarm FA1FH1
Primary # Zone 2 AlarmFA2FH2
Primary # Zone 3 AlarmFA3FH3
Primary # Zone 4 AlarmFA4FH4
Primary # Zone 5 AlarmFA5FH5
Primary # Zone 6 AlarmFA6FH6
Primary # Zone 7 AlarmFA7FH7
Primary # Zone 8 AlarmFA8FH8
Primary # Zone 9 AlarmFA9FH9
Primary # Zone 10 AlarmF A10FH10
Primary # Zone 1 Disabled FB1FU1
Primary # Zone 2 Disabled FB2FU2
Primary # Zone 3 Disabled FB3FU3
Primary # Zone 4 Disabled FB4FU4
Primary # Zone 5 Disabled FB5FU5
Primary # Zone 6 Disabled FB6FU6
Primary # Zone 7 Disabled FB7FU7
Primary # Zone 8 Disabled FB8FU8
Primary # Zone 9 Disabled FB9FU9
Primary # Zone 10 Disabled FB10FU10
Primary # Drill FIFK
Primary # AC Fault ATAR
Primary # Zone 1 Fault FT1FJ1
Primary # Zone 2 Fault FT2FJ2
Primary # Zone 3 Fault FT3FJ3
Primary # Zone 4 Fault FT4FJ4
Primary # Zone 5 Fault FT5FJ5
Primary # Zone 6 Fault FT6FJ6
Primary # Zone 7 Fault FT7FJ7
Primary # Zone 8 Fault FT8FJ8
Primary # Zone 9 Fault FT9FJ9
Primary # Zone 10 Fault FT10FJ10
Primary # Zone 1 Dirty FT1FJ1
Primary # Zone 2 Dirty FT2FJ2
Primary # Zone 3 Dirty FT3FJ3
Primary # Zone 4 Dirty FT4FJ4
Primary # Zone 5 Dirty FT5FJ5
Primary # Zone 6 Dirty FT6FJ6
Primary # Zone 7 Dirty FT7FJ7
Primary # Zone 8 Dirty FT8FJ8
Primary # Zone 9 Dirty FT9FJ9
Primary # Zone 10 Dirty FT10FJ10
Primary # Earth Fault ET38ER38
Primary # Low Battery Fault YT0YR0
Primary # No Battery Fault YT0YR0
Primary # Telco Primary Line Fault LT1LR1
Primary # Telco Secondary Line Fault LT2LR2
Primary # NAC #1 Fault ET32ER32
Primary # NAC #2 Fault ET33ER33
Primary # NAC #3 Fault ET34ER34
Primary # NAC #4 Fault ET35ER35
Primary # NAC #1 Disable ET101ER101
Primary # NAC #2 Disable ET102ER102
Primary # NAC #3 Disable ET103ER103
Primary # NAC #4 Disable ET104ER104
Primary # Charger Fault YPYQ
Primary # Comm Trouble Primary # YC1YK1
Primary # Comm Trouble Secondary # YC2YK2
Primary # Printer FaultVTVR
Primary # ANN-Bus FaultET61ER61
Primary # Option Card FaultETER
Primary # Memory Fault YF000
Future000000
Primary # System Off Normal LBLX
Primary # System Test MessageRP000
Primary # System Abnormal Te st MessageRP99000
Primary # Power Supply Sync FaultOUOV
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200793
ProgrammingMaster Programming Level
SIA-DCS Format - Secondary Central Station Phone Number
The information shown in Table 3.6 is automatically programmed for the Secondary Central
Station phone number Event Codes when SIA-DCS Format is selected. To disable event
reporting, select the desired Event Code to be disabled and press 0 or Clear and then Enter to
disable it. (Enter must be pressed to save the selection. Pressing Escape will not save the
selection). Note that disabling the Event Code for the Primary Central Station Phone Number
Event Code will also disable that Event Code for the Secondary Central Station Phone.
Table 3.6 Event Codes
Event DescriptionEvent Code Settings
ActiveRestoral
Secondary # Zone 1 Alarm FA1FH1
Secondary # Zone 2 Alarm FA2FH2
Secondary # Zone 3 Alarm FA3FH3
Secondary # Zone 4 Alarm FA4FH4
Secondary # Zone 5 Alarm FA5FH5
Secondary # Zone 6 Alarm FA6FH6
Secondary # Zone 7 Alarm FA7FH7
Secondary # Zone 8 Alarm FA8FH8
Secondary # Zone 9 Alarm FA9FH9
Secondary # Zone 10 Alarm FA10FH10
Secondary # Zone 1 Disabled FB1FU1
Secondary # Zone 2 Disabled FB2FU2
Secondary # Zone 3 Disabled FB3FU3
Secondary # Zone 4 Disabled FB4FU4
Secondary # Zone 5 Disabled FB5FU5
Secondary # Zone 6 Disabled FB6FU6
Secondary # Zone 7 Disabled FB7FU7
Secondary # Zone 8 Disabled FB8FU8
Secondary # Zone 9 Disabled FB9FU9
Secondary # Zone 10 Disabled FB10FU10
Secondary # Drill FIFK
Secondary # AC Fault ATAR
Secondary # Zone 1 Fault FT1FJ1
Secondary # Zone 2 Fault FT2FJ2
Secondary # Zone 3 Fault FT3FJ3
Secondary # Zone 4 Fault FT4FJ4
Secondary # Zone 5 Fault FT5FJ5
Secondary # Zone 6 Fault FT6FJ6
Secondary # Zone 7 Fault FT7FJ7
Secondary # Zone 8 Fault FT8FJ8
Secondary # Zone 9 Fault FT9FJ9
Secondary # Zone 10 Fault FT10FJ10
Secondary # Zone 1 Dirty FT1FJ1
94MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
Table 3.6 Event Codes (Continued)
Secondary # Zone 2 Dirty FT2FJ2
Secondary # Zone 3 Dirty FT3FJ3
Secondary # Zone 4 Dirty FT4FJ4
Secondary # Zone 5 Dirty FT5FJ5
Secondary # Zone 6 Dirty FT6FJ6
Secondary # Zone 7 Dirty FT7FJ7
Secondary # Zone 8 Dirty FT8FJ8
Secondary # Zone 9 Dirty FT9FJ9
Secondary # Zone 10 Dirty FT10FJ10
Secondary # Earth Fault ET38ER38
Secondary # Low Battery Fault YT0YR0
Secondary # No Battery Fault YT0YR0
Secondary # Telco Primary Line Fault LT1LR1
Secondary # Telco Secondary Line Fault LT2LR2
Secondary # NAC #1 Fault ET32ER32
Secondary # NAC #2 Fault ET33ER33
Secondary # NAC #3 Fault ET34ER34
Secondary # NAC #4 Fault ET35ER35
Secondary # NAC #1 Disable ET101ER101
Secondary # NAC #2 Disable ET102ER102
Secondary # NAC #3 Disable ET103ER103
Secondary # NAC #4 Disable ET104ER104
Secondary # Charger Fault YPYQ
Secondary # Comm Trouble Primary # YC1YK1
Secondary # Comm Trouble Secondary # YC2YK2
Secondary # Printer FaultVTVR
Secondary # ANN-Bus FaultET61ER61
Secondary # Option Card FaultETER
Secondary # Memory Fault YF000
Future000000
Secondary # System Off Normal LBLX
Secondary # System Test MessageRP000
Secondary # System Abnormal Test MessageRP99000
Secondary # Power Supply Sync FaultOUOV
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 3 while viewing Programming Screen #2 will display the History options
as shown in the following display:
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
3.5.6.1 View Events
Pressing 1 while viewing the History Screen will allow the user to select the events to be
viewed as illustrated in the following:
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen
While displaying the V iew Events screen, press 1 to view all events, 2 to view only alarms or 3
to view other events. Use the up and down arrow keys to scroll through all of the displayed
events.
3.5.6.2 Erase History
The Erase History option allows a user to erase all events from the history file. This will
provide a clean slate in order to use the history file to track future events. Pressing 2 while
viewing the History Screen will display the following screen:
ERASE HISTORY
PROCEED ?
1=YES 2=NO
Erase History Screen
Pressing 1 while viewing the Erase History Screen will erase all events from the History file.
During this process, the display will read as follows:
ERASING HISTORY
PLEASE WAIT
Erase History Wait Screen
After the History file has been erased, the display will return to the History Screen.
96MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Master Programming LevelProgramming
3.5.7 Walktest
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
panel after each device activation. Refer to the sections titled "Walktest" on page 101 and
"W alktest" on page 1 12 for additional information regarding the W alktest feature. Pressing 1 while
viewing the Programming Screen #3 will cause the following Walktest options to be displayed:
WALKTEST
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the
following screen will be displayed:
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
UNIT IN WALKTEST
Walktest Active Screen
The user can now perform a one-person walktest by activating devices throughout the system. As
each device is activated, the screen will display the information about the activated device as shown
below. Note that the colon (:) in the time is replaced with an asterisk (*) to distinguish the
walktest screen from an actual alarm screen.
ALARM ZONE 1
<ADJ> <NOUN>
Z01
10*00A 010805
After completion of the Walktest, press the Esc (Escape) key to exit Walktest Mode and return to
the Walktest Screen. The results of the Walktest can now be viewed by pressing 3 while viewing
the Walktest Screen. The following screen will be displayed:
WALKTEST RESULTS
Use the up and down arrow keys to view all of the walktest results which will be displayed as
illustrated in the preceding screen. Note that the Walktest log is stored in RAM. If all power (AC
and DC) is removed from the FACP, the Walktest log information will be lost. This information is
also overwritten when subsequent walktests are performed.
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200797
ProgrammingMaster Programming Level
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
PROGRAMMING
1=WALKTEST
2=CLEAR PROGRAM
3=PASSWORD CHANGE
Programming Screen #3
3.5.8 Clear Program
Pressing 2 while viewing Programming Screen #3, will select the Clear Program option. The
control panel will provide a warning to the user by prompting with the following display:
WARNING!
SYSTEM CHANGE
PROCEED?
1=YES 2=NO
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will
prevent programming from being cleared.
3.5.9 Password Change
The factory set passwords, which have been programmed into the control panel, can be changed by
selecting the Password Change option. Pressing 3 while viewing Programming Screen #3 will
cause the following screen to be displayed:
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
Password Change Screen
Press 1 to change the Master Programming Level password or 2 to change the Maintenance Level
password. Note that the passwords will not
be displayed on annunciators.
The following screen will appear when either change option is selected:
ENTER NEW FIVE DIGIT
PASSWORD
Enter Password Screen
A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:
VERIFY NEW
PASSWORD
Password Change Screen
The new five digit password must be re-entered to accept the change. The display will then return
to the initial Password Change Screen.
98MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Maintenance Programming LevelProgramming
3.6 Maintenance Programming Level
To access Maintenance Programming mode, press the Enter key . The LCD will display the
following:
1=READ STATUS
2=PROGRAMMING
To enter the Maintenance Programming mode, press 2. The display will read as follows:
PROGRAMMING
ENTER PASSWORD
When the Maintenance
level password (default 11111) is entered, the following screen will appear:
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Note that in the preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key, as shown in the following screen.
PROGRAMMING
1=TIME-DATE
MS-5UD/MS-10UD Series PN 52626:A1 5/11/200799
ProgrammingMaintenance Programming Level
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Maintenance Screen #1
3.6.1 Input Zones - Enable/Disable
The Zone Setup option allows the user to enable or disable desired zones. Pressing 1 for Zone
Setup, while viewing Maintenance Screen #1 will cause the following screens to be displayed:
POINT PROGRAM
1=ZONE 1
2=ZONE 2
3=ZONE 3
Zone Select Screen
Pressing the down arrow key will display additional Zones (Zones 4 - 5 for MS-5UD and Zones 4 10 for MS-10UD). Select the number corresponding to the desired zone. A screen will appear
which will allow enabling or disabling of the selected zone, as illustrated in the following example:
ZONE 1
1=ENABLED YES
Enable/Disable Select Screen
Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled No.
3.6.2 History
Pressing 2 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
The History feature allows the operator to view control panel events which have been stored in a
history file in memory and erase the contents of the history file
100MS-5UD/MS-10UD Series PN 52626:A1 5/11/2007
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.