Fire-Lite MMF-300 User Manual

MMF-300 Monitor Module
Installation Instructions
Specifications
Normal Operating Voltage: 15 to 32 VDC EOL Resistance: 47K Ohms Maximum IDC Resistance: 1,500 Ohms Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Noncondensing Dimensions: 4 Accessories: SMB500 Electrical Box
Before Installing
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment. General Description
The MMF-300 Monitor Module is intended for use in addressable, two-wire systems, where the individual address of each module is se­lected using the built-in rotary switches. It provides either a 2-wire or 4-wire fault tolerant Initiating Device Circuit (IDC) for normally open contact fire alarm or supervisory devices. The module has a panel controlled LED indicator. The MMF-300 can be used to replace an M300 module in existing systems.
Compatibility Requirements
To ensure proper operation, these modules shall be connected to listed compatible system control panels only.
Mounting
The MMF-300 mounts directly to 4” square electrical boxes (see Figure 2). The box must have a minimum depth of 2 mounted electrical boxes (SMB500) are available.
Wiring NOTE:
All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
2. Set the address on the module per job drawings. NOTE: Some panels support extended addressing. In order to set the module above address 99 on Fire•Lite compatible systems,
carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2.
1
/2” H x 4” W x 11/4” D (Mounts to a 4” square by 21/8” deep box.)
1
/8”. Surface
Figure 1. Controls and indicators:
Figure 2. Module mounting:
7
0
7
6
0
8
9
10
11
12
13
14
15
8
9
ADDRESS
0 1
0
1
0
9
1
1
1
8
2
2
7
2 3
1
3
6
1
4
5
3
1
9
4
5
1
3
9
8
0
4
2
1
8
7
6
N
S
TE
S
5
7
E
R
4
D
D
A
3
6
0
2
1
S
E
N
5
O
4
A78-2318-07
A78-2610-10
LOOP
9
6
5
4
8
3
2
1
7
TENS
5
6
4
3
2
5
1
ONES
F300-02-00 1 I56-1191-01
Fire•Lite Alarms, Inc., One Fire-Lite Place., Northford, CT 06472, 203-484-7161
Figure 3. Typical 2-wire Initiating Device Circuit (IDC) configuration, NFPA Style B (Class B):
TO NEXT DEVICE
(–) (+)
(–)
FROM PANEL OR
(+)
PREVIOUS DEVICE
MONITOR
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
47 K EOL RESISTOR ELR-47K
LOOP
MODULE
9
6
5
4
8
3
2
1
7
0
TENS
6
5
6
4 3
2
5
1
ONES
7
0
8
15
8
7
9
10
11 12 13
14 9
ADDRESS
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
0 1 2 3 4
(–) (+)
COMMUNICATION LINE
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
ER LIMITED: 230
POW
µA MAX @
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
12 VDC MAX
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
Figure 4. Typical 4-wire fault tolerant Initiating Device Circuit (IDC) configuration, NFPA Style D (Class A):
TO NEXT
DEVICE
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
EOL RESISTOR IS INTERNAL AT TERMINALS 8 & 9.
(–) (+)
MONITOR
MODULE
LOOP
CONNECT MODULES TO LISTED COMPATIBLE
TENS
ONES
0
7
8
9
6
5
10
11
4
1
3
12 13
2
1
14
2
0
15
8
7
6
9
5
3
4
3
2
4
1
0
ADDRESS
(–) (+)
COMMUNICATION LINE
9 8 7 6 5
CONTROL PANELS ONLY
32 VDC MAX
SHIELDED-TWISTED PAIR
IS RECOMMENDED
(-)
FROM PANEL OR
(+)
PREVIOUS DEVICE
A78-2280-15
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
A78-2281-62
F300-02-00 2 I56-1191-01
©1999 Fire•Lite Alarms, Inc.