Fire-Lite MDF-300 User Manual

MDF-300 Dual Monitor Module
Installation Instructions
Specifications
Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.7 mA (LED on) Average Operating Current: 750µA (LED flashing) EOL Resistance: 47K Ohms Maximum IDC wiring resistance: 1,500 Ohms Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Noncondensing Dimensions: 4 Accessories: SMB500 Electrical Box
Before Installing
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment. General Description
Compatibility Requirements
To ensure proper operation, this module shall be connected to a compatible Fire•Lite system control panel (list available from Fire•Lite).
Mounting
Mounts directly to 4” square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8”. Surface mounted elec­trical boxes (SMB500) are available from Fire•Lite.
1
/2” H x 4”W x 11/4” D (Mounts to a 4” square by 21/8” deep box.)
Wiring NOTE: All wiring must conform to applicable local codes, ordinances, and regula-
tions. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropriate wir­ing diagrams.
2. Set the address on the module per job drawings. Note: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1. Note: Monitor module L (using terminals 6 and 7) responds at the address set on the code switches. Monitor module H (using terminals 8 and 9) will automati­cally respond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at ad­dress 77. Use caution to avoid duplicate addressing of modules on the system.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.
Figure 1. Removing Rotary Switch Stop:
4 3
TENS
4
ONES
0
7
8
9
6
5
10
11
1
12 13
2
1
14
2
0
15
8
3
6
4
2
0
ADDRESS
9 8 7 6 5
LOOP
Figure 2A. Module mounting:
Figure 2B:
0
1
9
10
11
8
2
7
12
6
13
5
3
14
9
4
15
3
0
4
2
1
8
8
TENS
7
6
4
ADDRESS
0
2
6
5
ONES
A78-2610-14
9
8
6
5
7
4
8
3
7
9
2
TENS
10
0
1
6
LOOP
11
0
12
15
8
6
13
14
2
0 ADDRESS
1
4
2
3
4
5
ONES
A78-2611-19
A78-2318-13
F300-09-00 1 I56-0013-01R
Fire•Lite Alarms, Inc., One Fire-Lite Place., Northford, CT 06472-1653, (203)484-7161
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:
TWO INITIATING DEVICE CIRCUITS (L & H),
EACH POWER LIMITED TO 230 A @ 12VDC MAX.
47 K EOL RESISTOR ELR-47K
H
47 K EOL RESISTOR ELR-47K
L
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE ALARM
INITIATING, SUPERVISORY, OR SECURITY DEVICES
ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURERS INSTALLATION INSTRUCTIONS.
TO NEXT DEVICE
() (+)
MONITOR
MODULE
TENS
ONES
0
7
8
9
6
5
10
11
4
1
3
12 13
2
1
14
2
0
15
8
3
6
4
4
2
0
ADDRESS
() (+)
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
COMMUNICATION LINE
9 8 7 6 5
LOOP
SHIELDED-TWISTED PAIR
MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9) RESPONDS AT NEXT HIGHER ADDRESS.
()
FROM PANEL OR
(+)
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
32 VDC MAX.
IS RECOMMENDED
A78-2280-38
F300-09-00 2 I56-0013-01R
©2000 Fire•Lite Alarms, Inc.
Loading...