Fire-Lite MBT-1 User Manual

MBT-1 Municipal Box Trip
for Fire-Lite Fire Alarm Control Panels
One Fire-Lite Place, Northford, CT 06472
The CMF-300 must be programmed as 'Silenceable' and 'General Alarm.'
Alarm polarity shown!
+ -
­+
­+
CMF-300*
+ -
- To next device + on SLC Loop
Braided-shield/Drain Wire
24VDC, Nonresettable
TB4
MS-9200
Shield
B
Brown Wire
Power Supervision Relay
+ -
EOLR-1
B SLC LOOP
TB6
Document 52033 Rev C 02/19/08 ECN 08-116
MBT-1
Red Black
(Contacts shown in energized position)
Connect wires to two red terminals on box
Gamewell Model M34-56
Local Energy Municipal Box
Note: 10 ohms maximum loop re­sistance due to wiring from power supply to Municipal Box.
* If the SLC device does not match the one in this figure, refer to the SLC Manual (document #51309) wiring conversion charts for legacy and newer versions of the modules.
NFPA 72 Auxiliary Protective Signaling System
For connection of initiating devices and modules in this system, refer to the MS-9200 Installation Manual, Document 51003.
This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.
1 of 5
MS-9200
(Alarm Signal Transmission)
Document 52033 Rev. C 02/19/08
The CMF-300 must be programmed as 'Silenceable' and 'General Alarm.'
Alarm polarity shown!
+ -
­+
­+
CMF-300*
- To next device + on SLC Loop
Braided-shield/Drain Wire
White Wire
Brown Wire
EOLR-1
Power Supervision Relay
Red Black
MBT-1
Connect wires to two red terminals on box
(Contacts shown in energized position)
Gamewell Model M34-56
Local Energy Municipal Box
Note: 10 ohms maximum loop re­sistance due to wiring from power supply to Municipal Box.
+ -
24VDC, Nonresettable
TB1
* If the SLC device does not match the one in this figure, refer to the SLC Manual (document #51309) wiring conversion charts for legacy and newer versions of the modules.
MS-9200UD
NFPA 72 Auxiliary Protective Signaling System
For connection of initiating devices and modules in this system, refer to the MS-9200UD Installation Manual, Document 51906.
This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.
SLC LOOP B
+ -
B
Shield
TB10
MS-9200UD & MS-9200UDLS
(Alarm Signal Transmission)
Document 52033 Rev. C 02/19/08
2 of 5
Loading...
+ 3 hidden pages