Fire-Lite LED-10 User Manual

The LED-10 Series
Remote Fire Annunciators
for use with the Fire•Lite
MS-5210UD
Fire Alarm Control/Communicator
12 Clintonville Road, Northford, CT 06472
Document # 50400
10/27/97 Revision:
P/N 50400:B ECN 97-510
B
2
Document 50400 Rev B 10/27/97 P/N 50400:B
Contents
Section One: LED-10 Series Annunciators ...................................... 4
Features................................................................................................. 4
Figure 1-1: Component Summary......................................................... 5
Figure 1-2: Wiring to Terminals ............................................................. 6
SW1 DIP Switch Settings...................................................................... 7
Figure 1-3: SW1 DIP Switch Settings Example .................................... 7
Figure 1-4: SW2 DIP Switch Settings Example .................................... 8
Table 1-1: LED-10 Series Annunciator Addressing .............................. 9
Figure 1-5: Typical Configuration .......................................................... 9
LED Indicators and Piezo Sounder..................................................... 10
Switch Functions for LED-10 Only ...................................................... 11
Section Two: LED-10 Series Annunciators Mounting.................... 13
Figure 2-1: LED-10 Series Hardware.................................................. 13
Figure 2-2: LED-10 Series Backboxes ................................................ 13
Figure 2-3: LED-10 Series Semi-flush Mounting................................ 14
Figure 2-4: LED-10 Series Surface Mounting..................................... 15
Section Three: LED-10 Series Electrical Connections ................. 1 6
Figure 3-1: Power Connection............................................................. 1 6
Figure 3-2: LED-10IM Installation ....................................................... 1 7
Figure 3-3: EIA-485 Connection ......................................................... 1 8
Figure 3-4: Wiring FACP to LED-10 Series......................................... 19
Section Four: EIA-485 Shield Terminations ................................... 20
When the EIA-485 Shield is not in Conduit ........................................ 20
When the EIA-485 Shield is in Full Conduit ....................................... 21
Spare Slide-In Labels for LED-10 Series Annunciators................ 23
Document 50400 Rev B 10/27/97 P/N 50400:B
3
Section One: LED-10 Series Annunciators
LED-10
The Fire•Lite LED-10 Series Annunciators consist of the LED-10, LED-10L and LED­10LS2. They are compact, attractive LED-type fire annunciators designed for use with the MS-5210UD Fire Alarm Control Communicator. The LED-10L and LED-10LS2 are models which do not have function switches or a key-switch. The LED-10LS2 is intended primarily for Canadian installations since it provides zone 9 and 10 alarm LEDs that are yellow for supervisory functions.
The LED-10 Series Annunciators are capable of displaying independent zone process monitor alarm, trouble and supervisory status. They also provide system status LEDs to display Power, Alarm, Trouble, Supervisory and Signals Silenced conditions. The LED-10 model is also capable of performing system acknowledge, silence, drill and reset remotely.
Communication between the control panel and the LED-10 Series Annunciators is accomplished over a two-wire serial interface employing the EIA-485 communication standard. Up to 32 LED-10 Series Annunciators may be connected to the two-wire EIA­485 circuit. The annunciators may be powered from the host FACP or remote, UL listed, filtered, regulated power supplies.
LED-10L and LED-10LS2
fire alarm,
Features - all models
• Zone Alarm and Trouble LEDs.
• System Status LEDs for Power (green), Alarm (red), Trouble (yellow), Supervisory (yellow) and Signals Silenced (yellow).
• Local piezo sounder with alarm and trouble resound.
• Distinctly different flash rates for LEDs and piezo sounder distinguish system status:
üfire alarm = 1 second on and 1 second off üprocess monitor alarm = 1/4 second on and 1/4 second off üsupervisory alarm = 1/2 second on and 1/2 second off
• EIA-485 connects to control panel terminal port (requires LED-10IM module).
• Plug-in terminal blocks for ease of installation and service.
• DIP switch controls transmit/receive mode.
• Up to 32 LED-10 Series Annunciators per MS-5210UD.
• Mounting options:
üSurface mount in three gang electrical box P/N: SBB-3 üSemi-flush mount in three-gang electrical box P/N: 10103 (2 3/16" min. depth) üCan be located up to 6,000 feet (1,800 m) from the panel using 18 AWG wire
• Slide-in labels for custom labeling.
• Simple programming at MS-5210UD panel enables communications to LED-10 Series annunciators.
4
Document 50400 Rev B 10/27/97 P/N 50400:B
LED-10 only:
• Function switches for: üAcknowledge üSignal Silence üDrill üSystem Reset
• Enable/Disable key-switch for function switches.
• DIP switches control local functions such as piezo enable/disable, function
switches and key-switch enable/disable.
Key-switch Enable/Disable for LED-10 Only
Receive-Transmit/Receive only not used LED-10 Series Address
Note: TB1 & TB2 are
located on backside of PCB
(not used on the LED-10L or LED-10LS2)
Top view
Piezo Enable/Disable
ROM
Membrane Connectors
Membrane switch connectors
Figure 1-1: Component Summary
Piezo Sounder
The LED-10 Series sounder, if enabled, will be activated when any new alarm or trouble is received from the panel. It is silenced by pressing an ACKNOWLEDGE or SILENCE switch. Piezo must not be disabled without approval of LAHJ (Local Authority Having Jurisdiction).
Document 50400 Rev B 10/27/97 P/N 50400:B
5
Side view
(rotated 180
from above [Top] view)
o
Earth Ground Option
-24 VDC OUT
-24 VDC IN
+24 VDC OUT
+24 VDC IN
No connection
+EIA-485
-EIA-485 Shield No connection
Note: These connections must be power-limited and the +24 volt nominal power (18 VDC to 26 VDC) must be filtered.
Current Consumption @ 24 VDC nominal (filtered)
Normal/Standby (no activity): 23 mA Trouble Condition: 31 mA Alarm: 28 mA (1 zone in alarm) 40 mA (all 10 zones in alarm) AC Fail: 24 mA
Figure 1-2: Wiring to Terminals
6
Document 50400 Rev B 10/27/97 P/N 50400:B
SW1 DIP Switch Settings
The OPEN position on SW1 is the OFF state. Refer to Figure 1-3 for an explanation of DIP switch positions. SW1 switch settings are as follows:
1 through 6 - LED-10 Series annunciator address switches.
The first six switches are used to set the address of the annunciator. The OFF (OPEN) up position equals a binary 1 and the ON down position equals a binary 0. Refer to Table 1-1 for information on setting these switches for specific addresses. Each LED-10 Series annunciator connected to the EIA­485 communication bus must have a unique address.
7 - Not used 8 - ON = Receive/Transmit, OFF (OPEN) = Receive Only
Switch 8 set to ON position enables Receive/Transmit mode for the LED-10 Series annunciator. This allows the annunciator to receive and display system status information and to transmit supervision status. It also allows the LED-10 model to transmit system control data such as Acknowledge/Step, Reset, Signal Silence and Drill. Switch 8 set to the OFF position enables Receive Only mode which allows the annunciator to receive and display system status information but prevents supervision status from being transmitted back to the FACP. It also prevents function switch operation on the LED-10 model. To ensure annunciator supervision for all LED-10 Series annunciators and function switch capability for the LED-10 model, each annunciator connected to the EIA-485 communication bus must have a unique address and should be set to enable Receive/Transmit Mode.
DOWN POSITION = ON
NOTE - SW1 DIP switch settings as illustrated in Figure 1-3 are as follows:
1) DIP switches 1 - 6: Address 08 (see Table 1-1).
2) DIP switch 7: Not used.
3) DIP switch 8: ON = Receive/Transmit
UP (OPEN) POSITION = OFF
Figure 1-3: SW1 DIP Switch Settings Example
Document 50400 Rev B 10/27/97 P/N 50400:B
7
SW2 DIP Switch Settings
SW2 switch settings are as follows:
1 - LED-10 Only (not used on LED-10L and LED-10LS2) ON = Key-switch Enable, OFF = Key-switch Disable.
Switch 1 set to the ON position enables the key-switch operation. The key­switch may now be used to enable LED-10 model membrane (control) switches, allowing remote switch functions, or lockout the switches, preventing remote switch functions. Switch 1 set to the OFF position disables the key-switch operation. Refer to Operation Section for key-switch function description.
2 - ON = Piezo sounder enabled, OFF = Piezo sounder disabled.
CAUTION: Piezo sounder must not be disabled without prior approval of the Local Authority Having Jurisdiction.
UP POSITION = OFF
DOWN POSITION = ON
Figure 1-4: SW2 DIP Switch Settings Example
LED-10 Series Addressing
SW1 DIP switches 1 through 6 are used for addressing the LED-10 Series annuncia­tors.
Each device connected to the EIA-485 communication bus must have a unique
address.
and for individual supervision of each annunciator by the FACP. Switch settings and the corresponding addresses are shown in Table 1-1. (Address '00' is invalid).
Note: 1 = Switch in the UP (OPEN) position.
8
This allows specific data to be transmitted between the FACP and that device
0 = Switch in the DOWN position.
Example: ADDRESS SWITCH SETTINGS
1 2 3 4 5 6
08 0 0 1 0 0 0
Addressing Switches
Document 50400 Rev B 10/27/97 P/N 50400:B
ADDRESS SWITCH SETTINGS ADDRESS SWITCH SETTINGS
1 2 3 4 5 6 1 2 3 4 5 6
INVALID 0 0 0 0 0 0 17 0 1 0 0 0 1
01 0 0 0 0 0 1 18 0 1 0 0 1 0 02 0 0 0 0 1 0 19 0 1 0 0 1 1 03 0 0 0 0 1 1 20 0 1 0 1 0 0 04 0 0 0 1 0 0 21 0 1 0 1 0 1 05 0 0 0 1 0 1 22 0 1 0 1 1 0 06 0 0 0 1 1 0 23 0 1 0 1 1 1 07 0 0 0 1 1 1 24 0 1 1 0 0 0 08 0 0 1 0 0 0 25 0 1 1 0 0 1 09 0 0 1 0 0 1 26 0 1 1 0 1 0 10 0 0 1 0 1 0 27 0 1 1 0 1 1 11 0 0 1 0 1 1 28 0 1 1 1 0 0 12 0 0 1 1 0 0 29 0 1 1 1 0 1 13 0 0 1 1 0 1 30 0 1 1 1 1 0 14 0 0 1 1 1 0 31 0 1 1 1 1 1 15 0 0 1 1 1 1 32 1 0 0 0 0 0 16 0 1 0 0 0 0
Table 1-1: LED-10 Series Annunciator Addressing
Typical Configuration
The LED-10 Series annunciators indicate the status of the MS-5210UD, display zone status and require no programming. In addition, the LED-10 model offers multiple annunciator locations with the capability of remote Acknowledge, Signal Silence, Drill and Reset functions.
NOTES:
1) EIA-485: Maximum of 6,000 feet (1,800 m) total cable length from FACP to LED-10 Series annunciators. Circuit is power-limited.
2) Up to 32 LED-10 Series annunciators may be used on the EIA-485 circuit. The MS-5210UD can power a maximum of seven annunciators. If additional annunciators are connected, the Fire•Lite FCPS-24F may be used to supply additional power. (Power supplies used for this purpose must have their negative terminals commoned together).
3) Between each annunciator are four wires: A twisted-shielded pair for data communications and a pair for 24 VDC power.
4) A mix of LED-10 Series annunciators can be connected to the same EIA-485 circuit.
Figure 1-5: Typical Configuration
Document 50400 Rev B 10/27/97 P/N 50400:B
9
Loading...
+ 19 hidden pages