Fire-Lite LDM-32F User Manual

PN 50055:C0 ECN 01-155
Lamp Driver Module
LDM-32F
Instruction Manual
Document 50055 03/20/2001 Rev:
C
This page intentionally left blank
4
LDM-32F PN 50055:C 03/20/01
Table of Contents
Table of Contents
1. Introduction
General................................................................................................... 9
Features ............................................................................................... 10
LDM-32F..........................................................................................10
LDM-E32F .......................................................................................11
Connectors........................................................................................ 12
J1 - Switch Matrix........................................................................12
J2 - Ribbon Cable Connection to J3.............................................12
J3 - Ribbon Cable Connection from J2........................................12
J4 - Key Switch Input...................................................................12
J5, J6, J7 and J8 - Lamp/LED Driver Outputs ............................. 12
J9 - 24 VDC Lamp Power/System Trouble .................................12
J10 - Relay Expander ...................................................................12
J11 - 5 VDC Lamp Power............................................................13
Switches............................................................................................13
SW1 and SW2 - Address Switches..............................................13
SW3 - Function DIP Switch.........................................................13
SW4 - Alarm/Trouble Mode Switch............................................13
Terminal Blocks ...............................................................................14
TB1 - 24 VDC Power, Earth Ground and Supervision................ 14
TB2- EIA-485 In/Out...................................................................14
Cables ...............................................................................................14
Expander Ribbon Cable ............................................................... 14
The LDM-CBL24 and LDM-CBL48...........................................14
Key-lock Control Switch Security ...............................................15
Related Documentation......................................................................15
2. Installation
External Cabinets ............................................................................... 17
CHS-4L Chassis ..................................................................................17
Wiring the Power Terminal Block ....................................................19
24 VDC Power and Earth Ground....................................................19
Supervision Input ............................................................................. 20
Wiring the EIA-485 Terminal Block.................................................20
Wiring Specifications....................................................................... 20
Wire Chart ..................................................................................21
EIA-485 Shield in Conduit ..........................................................21
EIA-485 Shield Not in Conduit ...................................................21
EIA-485 - TB2 Terminals ................................................................22
Wiring for Lamp/LED .......................................................................23
Wiring the Control Switch.................................................................24
Table of Contents
Configuring the LDMs .......................................................................25
Address Switches - SW1 and SW2...................................................25
Function DIP Switch - SW3 .............................................................25
Switch Settings.............................................................................26
Mode Switch - SW4 .........................................................................26
3. Operation
Lamp Test/Acknowledge ....................................................................27
On Line LED .......................................................................................27
Graphic Annunciator Lamps/LEDs..................................................27
4. LDM Communications
Receive Only LDM-32Fs ....................................................................29
Receive/Transmit LDM-32F ..............................................................29
5. Electrical Ratings and Current Calculations
Lamp Driver Electrical Ratings ........................................................31
Supervision of LDM points ................................................................31
Calculating Standby and Alarm Currents .......................................32
Appendix A: Sensiscan 2000
Capabilities ..........................................................................................33
Trouble Indication ..............................................................................33
Programming and Testing the LDM-32F.........................................33
Power Supply Connection ..................................................................34
MPS-24AF Main Power Supply.......................................................34
MPS-24BF Main Power Supply.......................................................34
EIA-485 Connection ...........................................................................34
Lamp/LED Driver Operation ............................................................35
Alarm Only Operation ......................................................................37
Alarm Only Operation with 8-Point Shift ........................................37
Alarm/Trouble Operation .................................................................38
Alarm/Trouble Operation with 8-Point Shift....................................38
Control Switch Operation ..................................................................40
Appendix B: MS-9200
Capabilities ..........................................................................................41
Trouble Indication ..............................................................................41
Programming and Testing the LDM-32F.........................................41
Power and EIA-485 Connections.......................................................41
Configuration ......................................................................................42
Alarm Only Annunciation of Zones.................................................42
Alarm Only Annunciation of Zones - With 8-Point Shift................42
Alarm/Trouble Annunciation of Zones ............................................43
Alarm/Trouble Annunciation of Zones - With 8-Point Shift ...........43
Alarm Only Annunciation of Points.................................................45
Detectors.......................................................................................45
Modules........................................................................................45
Table of Contents
Alarm Only Annunciation of Points - With 8-Point shift ................46
Detectors ......................................................................................46
Modules........................................................................................46
Alarm /Trouble Annunciation of Points........................................... 47
Detectors ......................................................................................47
Modules........................................................................................47
Alarm /Trouble Annunciation of Points - With 8-Point Shift.......... 48
Detectors ......................................................................................48
Modules........................................................................................48
Configuration Diagram.....................................................................49
Appendix C: MS-9600
Capabilities..........................................................................................51
Trouble Indication..............................................................................51
Programming and Testing the LDM-32F.........................................51
Power and EIA-485 Connections ......................................................51
Configuration ......................................................................................52
Setting Rotary Switches ...................................................................52
Alarm Only Annunciation of Zones.................................................53
Alarm Only Annunciation of Zones - With 8-Point Shift................ 53
Alarm/Trouble Annunciation of Zones............................................54
Alarm/Trouble Annunciation of Zones - With 8-Point Shift ........... 54
Alarm Only Annunciation of Points.................................................56
Alarm/Trouble Annunciation of Points............................................56
This page intentionally left blank
8
LDM-32F PN 50055:C 03/20/01

1. Introduction

General

The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic annunciator. The master module provides power and control for a maximum of three expander modules. Both these modules have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions.
The Lamp Driver Modules may be connected to an MS-9200, MS-9600 or Sensiscan 2000 fire alarm control panel (FACP) to provide remote annunciation of the following:
• General system status:
General alarm Municipal tie status
General trouble System silence
General supervisory Alarm relay status
NAC output status
• Alarm and trouble status of zones or individual points
• Alarm only status of zones or individual points
The modules also interface to remote control switches which may be used to provide:
•System reset
•System silence
• System acknowledge
• Temporary activation of NAC outputs
• Alarm relay activation
• Other control functions
The modules interface to the host fire alarm control panel via an EIA-485 communications bus circuit. A maximum of 32 LDM-32Fs may be connected to the power-limited EIA-485 bus, but if other types of devices are also connected to the EIA-485 bus, the maximum number of LDM-32Fs must be reduced by the total of such devices. The EIA-485 wiring distance must not exceed 6000 feet and cannot be T-tapped. Multiple LDM-32Fs may be used to annunciate duplicate information.
Power to the LDM-32Fs is typically provided by the host FACP and must be power-limited, regulated 24 VDC. An external UL listed battery backed power supply may also be used.
Note: Careful consideration must be given to system battery calculations when power for the LDM modules and lamps or LEDs is provided by the host FACP. Refer to the specifications in the appropriate FACP technical manual when making these calculations.
LDM-32F PN 50055:C 03/20/01
9
1. Introduction Features

Features

LDM-32F

The Lamp Driver Module LDM-32F has 32 alarm lamp/LED driver outputs which sink current to system common (–) on activation. A single positive (+) voltage is required to supply total operating power for all lamps or LEDs when all drivers are activated. The LDM-32F provides a separate driver for system trouble and inputs for a local lamp test switch. A maximum of 16 external control switches may be wired to the LDM-32F. DIP switch SW3 is used to enable or disable the onboard piezo, enable remote switch functions, select a flashing LED function for new alarms and troubles, and other functions. Switch SW4 is used to configure the module to annunciate 32 alarms or 16 troubles. A green
ON LINE
with the host FACP. One LDM-32F supports up to 3 LDM-E32F modules. The LDM-32F is supplied with 4 standoffs and screws for mounting to a CHS-4L chassis or custom backbox.
LED flashes to indicate ongoing communications
Output Connectors for Wiring to LEDs
Lamp Power (+5 VDC)
Security Key
Switch Terminal
Control Switch
Terminal
Address
Switches
Programming
DIP Switch
EIA-485
Terminal
24 VDC
Power
Terminal
J4
KEYSWITCH
SWITCH MATRIX
J1
SW1
SW2
SW3
SW4
J5
4 3 2 1
7 6 5 4 3 2 1
J6 J7 J8
TB2
TB1
Figure 1 LDM-32F
Not Used
J11
LAMP POWER
J10
J9
Lamp Power (+24 VDC)
System Trouble
Ribbon Cable Connection to LDM-E32F
J2
Alarm or Alarm/Trouble Slide Switch
LDM-32F.cdr
ON LINE
Indicates EIA-485 Communication Active
10
LDM-32F PN 50055:C 03/20/01
Features 1. Introduction

LDM-E32F

Each LDM-E32F expander module provides 32 additional lamp/LED driver outputs from J5, J6, J7 and J8. The expander module has a slide switch SW4 for selecting alarm or alarm and trouble annunciation and an input for a local lamp test switch. In alarm mode, use only one LDM-32F and one LDM-E32F for a maximum of 56 alarm indicators and 8 system status indicators. In alarm/ trouble mode, use one LDM-32F and three LDM-E32Fs for a maximum of 56 alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional control switch inputs. Multiple sets of LDM-32Fs with LDM-E32F expanders increase the system annunciation capabilities beyond 56 zones or points. This is possible by various settings of address switches SW1 and SW2 on the LDM­32F (refer to Appendices). Each LDM-E32F is supplied with a 26-conductor expander ribbon cable, 4 standoffs and 4 screws.
Output Connectors for Wiring to LEDs
Security Key
Switch Terminal
Control Switch
Te rm i n al
Alarm or
Alarm/Trouble
Slide Switch
Not Used
Ribbon Cable Connections to Next LDM-E32F
Ribbon Cable Connections from LDM-32F or Previous LDM-E32F
LDM-E32F.cdr
Figure 2 LDM-E32F
LDM-32F PN 50055:C 03/20/01
11
1. Introduction Features

Connectors

J1 - Switch Matrix
Up to 16 optional external control switches and a local lamp test switch may be attached to the LDM-32F and LDM-E32F via J1 as shown in Figure 16 on page 24. In the Sensiscan 2000, the control switches may be mapped to the CPU function switches and all 9600, the switches may only be used for remote Acknowledge, Reset, Drill and Silence. External switches must be momentary type.
J2 - Ribbon Cable Connection to J3
A single 26-conductor ribbon cable may be connected from J2 on the LDM­32F or LDM-E32F (see Figure 6 on page 18) to J3 on adjacent LDM-E32Fs. The ribbon cable carries power, ground and signaling from the master module to up to three expander modules. The preformed cables are supplied in fixed lengths of 24 and 48 inches.
J3 - Ribbon Cable Connection from J2
This connector supports a single 26-conductor ribbon cable from J2 of the previous LDM-32F or LDM-E32F. Refer to Figure 6 on page 18.
J4 - Key Switch Input
This two pin connector is provided as an input on LDM-32F and LDM-E32F modules for an external security key switch. Key switch contacts must be Normally Closed. The key switch prevents unauthorized use of remote control switches wired to J1.
J5, J6, J7 and J8 - Lamp/LED Driver Outputs
input and output modules. In the MS-9200 and MS-
Each connector provides 8 driver outputs for a total of 32 drivers on each LDM­32F and LDM-E32F. Each driver is rated for a maximum of 30 volts and a current of 100 mA. Each bipolar Darlington open collector driver output must be current limited by an external resistor. 8-Point Shift and Flash functions are selectable by DIP switch SW3 (refer to "SW3 - Function DIP Switch" on page
13). Lamp/LEDs may function in ‘alarm only’ mode or ‘alarm/trouble’ mode as selected by switch SW4. Use the charts and examples shown in Appendices for additional information.
J9 - 24 VDC Lamp Power/System Trouble
Connector J9 is located only on the LDM-32F. J9 pin 1 provides 24 volts regulated power to all lamps/LEDs used in a custom graphic annunciator. The current limit of J9 pin 1 is dependent upon the current limits of the external power source being used. J9 pin 3 is a driver output for system trouble indication only. J9 pin 2 connects to system common.
J10 - Relay Expander
Not used on the Sensiscan 2000, MS-9200 and MS-9600.
12
LDM-32F PN 50055:C 03/20/01
Features 1. Introduction
J11 - 5 VDC Lamp Power
This connector is located only on the LDM-32F. J11 pin 1 provides 5 volts regulated power to all lamps/LEDs used in a custom graphic annunciator. The maximum current available from this output is 300 mA. This current is sufficient to power the maximum number of LEDs available with one LDM­32F and three LDM-E32Fs (from J5, J6, J7, J8 and one system trouble LED) provided the
current rating per LED is 2 mA.

Switches

SW1 and SW2 - Address Switches
Two rotary BCD switches, located only on the LDM-32F, are used to set the LDM Series system address. Switch SW1 represents the ‘ones’ position and switch SW2 represents the ‘tens’ position of the address setting. In system configurations of 56 zones or less, the switches must be set to address 01 for all LDMs in the system. For configurations larger than 56 zones, multiple sets of LDMs are required with sequential addresses, the first LDM starting at address 01. Each incremental setting adds 64 zones/points to the system.
For example, an MS-9200 system requiring annunciation of alarms and troubles for all 198 points would require four sets of LDMs with addresses 01, 02, 03 and 04. The MS-9600 is an exception (refer to "Appendix C: MS-9600" on page 51 for information).
SW3 - Function DIP Switch
SW3, which is located only on the LDM-32F, is used to set the annunciator functions. Function settings include:
• Number of expanders connected
• 8-Point Shift enabled
• Receive Only communications to host FACP
• Receive/Transmit communications to host FACP
• Control Switch disable
• Piezo disable
• Flash Inhibit
Refer to "Function DIP Switch - SW3" on page 25 for additional information.
SW4 - Alarm/Trouble Mode Switch
The Alarm/Trouble mode switch is installed on the LDM-32F and LDM-E32F. The switch setting on each
expander module must match the switch setting of the associated LDM-32F. ‘Alarm Only’ mode causes the driver outputs to turn on only for alarm conditions per associated zone or point at the host FACP. ‘Alarm/Trouble’ mode causes the driver outputs to turn on for both alarm and trouble conditions per associated zone or point at the host FACP. Since this switch affects the assignments of connectors J5, J6, J7 and J8, make certain to review the appendices in this manual for additional information on wiring to the lamp/LED drivers.
LDM-32F PN 50055:C 03/20/01
13
1. Introduction Features

Terminal Blocks

TB1 - 24 VDC Power, Earth Ground and Supervision
Removable terminal block TB1 appears only on the LDM-32F. 24 volts power­limited, regulated, non-resettable power from the host FACP or a compatible UL listed battery backed power supply must be connected to TB1­(+) and TB1-
COMMON OUT
COMMON IN
(-) may be used to daisy chain the 24 volts to other LDMs or devices. Earth ground must be connected to TB1­and TB1-
N.C. SUPERVISION INPUT
(-). Terminals TB1-
provide a supervised input which may be
POWER OUT
EARTH
(+) and TB1-
. Terminals TB1-6
POWER IN
used to supervise local power sources or other devices. A trouble signal is transmitted to the host FACP upon an open circuit across these terminals. The input must be power-limited. If these terminals are not used, a jumper must be installed.
TB2- EIA-485 In/Out
Removable terminal block TB2 appears only on the LDM-32F. All LDM-32Fs must connect to the EIA-485 communications bus circuit for proper operation. The EIA-485 bus carries commands and data sent between the host FACP and the LDMs. The input must be power-limited.

Cables

Expander Ribbon Cable
The Expander Ribbon Cable (PN 75120) is supplied with the LDM-E32F to allow for connection to the LDM-32F master module. The cable connects between J2 of the LDM-32F or LDM-E32F and J3 of the next LDM-E32F.
The LDM-CBL24 and LDM-CBL48
Cable sets for connecting LDM-32F and LDM-E32F connectors to lamps/ LEDs, switches, etc., are provided through the optional LDM-CBL24 (24" long) and LDM-CBL48 (48" long) cabling kits. Each cable has a plug on one end for connection to the LDM modules.
Each LDM-CBL24 cable kit includes:
• (4) P/N 75116, 24" cable consisting of 8 stranded, multicolored conductors. Cables connect to J5, J6, J7 and J8.
• (1) P/N 75122, 24" cable consisting of 10 stranded, multicolored conductors. Connects to J1, optional control switches.
• (1) P/N 75117, 24" cable consisting of 2 stranded, single color conductors. Connects to
J1, Lamp Test Switch.
• (1) P/N 75118, 24" cable consisting of 3 stranded, multicolored conductors. Connects to J9 or J11, Lamp Power.
14
LDM-32F PN 50055:C 03/20/01
Related Documentation 1. Introduction
Each LDM-CBL48 cable kit includes:
• (4) P/N 75147, 48" cable consisting of 8 stranded, multicolored conductors. Cables connect to J5, J6, J7 and J8.
• (1) P/N 75150, 48" cable consisting of 10 stranded, multicolored conductors. Connects to J1, optional control switches.
• (1) P/N 75148, 48" cable consisting of 2 stranded, single color conductors. Connects to J1, Lamp Test Switch
.
• (1) P/N 75149, 48" cable consisting of 3 stranded, multicolored conductors. Connects to J9 or J11, Lamp Power.
Key-lock Control Switch Security
A UL listed key-lock switch wired to J4 on the LDM-32F should be used to provide access security for all control switches wired to that set of LDM modules.
Note: Control switches will not function when the key-lock switch is in its closed position.
J4
2
Key Switch
Figure 3 Key-lock Switch Wiring Diagram
LDM-32F
1
LDM32F-keysw.cdr

Related Documentation

Further details about products referenced in this document can be found in the manuals for the particular fire alarm control panel and components.
Product
MS-9200 Fire Alarm Control Panel Instruction Manual 51003
MS-9600 Fire Alarm Control Panel Instruction Manual 51335
Sensiscan 2000 Fire Alarm Control Panel Instruction Manual 15017
CAB-3F Series Cabinets Installation Document 15391
LDM-32F PN 50055:C 03/20/01
Part Number
15
1. Introduction Related Documentation
NOTES
16
LDM-32F PN 50055:C 03/20/01

2. Installation

External Cabinets

The CAB-A3F and the CAB-B3F are UL listed cabinets suitable for use in graphic annunciator applications. For size and dimensions, refer to the CAB­3F Series Installation Document.
Select and remove the appropriate knockout(s) on the cabinet.
Securely mount the cabinet.
Ground the cabinet to a solid electrical ground per NEC Article 250.
Pull all wiring into the cabinet. (Refer to the appropriate FACP manual for UL Power-limited Wiring Requirements.)
Note: Other cabinets such as those provided by custom graphic annunciator manufacturers may be used provided they meet UL requirements as UL listed secured enclosures.

CHS-4L Chassis

The CHS-4L chassis will support one LDM-32F module and up to three LDM­E32F expander modules. The chassis is mounted inside the CAB-A3F or the CAB-B3F cabinet.
Mount the CHS-4L Chassis to a cabinet and secure with the hardware provided. The Grounding Cable must be connected to the chassis mounting stud for connection to the annunciator's earth ground terminal for proper operation as well as to aid in transient protection. For each LDM module to be installed on the chassis, connect two female-to-female standoffs (provided) to the upper mounting studs on the chassis.
LDM-32F PN 50055:C 03/20/01
LDM32-chs4l.cdr
Figure 4 CHS-4L Mounting
17
2. Installation CHS-4L Chassis
Slip the bottom edge of the module or expander board into the slot on the chassis and move the module toward the standoffs. Secure the board to the standoffs with the screws provided. Repeat for installation of additional modules or expanders.
Ldminchs.cdr
Figure 5 Installing LDM Modules in CHS-4L
Connect an expander ribbon cable (P/N 75120) from the LDM-32F connector J2 to J3 of the first LDM-E32F expander module. If multiple LDM-E32F modules are to be used, connect additional cables from J2 to J3 as shown below. One LDM-32F may support a maximum of three LDM-E32F modules.
18
Expander Ribbon Cables
LDM-32F LDM-E32F LDM-E32F LDM-E32F
Ldmincab.cdr
Figure 6 LDMs Mounted in UL Listed Cabinet
LDM-32F PN 50055:C 03/20/01
Wiring the Power Terminal Block 2. Installation

Wiring the Power Terminal Block

24 VDC Power and Earth Ground

24 VDC power supplied to the LDM must be power-limited. This power is inherently supervised (loss of power also results in a communication failure at the control panel).
• Limit the total wire resistance to 10 ohms.
• Connect the Grounding Cable from the chassis to the earth ground terminal of TB1 (
• Connect 24 VDC power to the terminals of TB1.
24 VDC
Power
Grounding Cable
Figure 7 24 VDC Power Terminals - TB1
EARTH
).
POWER IN
TB1
(+) and
N.C. Supervision
Inputs Common In (–) Common Out (–) Power In (+24 VDC) Power Out (+24 VDC) Earth
COMMON IN
(–)
LDM32F-TB1.cdr
Wiring of multiple LDM-32F modules.
Host FACP or Remote Power Supply
– 24 VDC
+ 24 VDC
Figure 8 Multiple Module Wiring - 24 VDC
LDM-32F PN 50055:C 03/20/01
First LDM-32F -- -- -- -- -- -- -- Last LDM-32F
TB1 TB1
LDM32F-power.cdr
19
2. Installation Wiring the EIA-485 Terminal Block

Supervision Input

The Supervision Input, which requires a normally-closed condition, can be used for supervising power sources or ot her devices. It must be power-limited. If employed, a change in status will be transmitted to the host control panel in the event of device failure or restoral.
If not used, a jumper must be installed across these terminals on TB1. A trouble signal will be registered by the control panel if a short circuit does not exist across terminals 6 & 7.
Device to be Supervised
Supervision Inputs (5 VDC @
0.5 mA) Normally Closed Trouble Contacts
Jumper
TB1
Figure 9 Wiring Supervision Terminals
TB1

Wiring the EIA-485 Terminal Block

A maximum of 32 LDM-32Fs may be connected to the EIA-485 bus, but if other types of devices are also connected to this bus, the maximum number of LDM-32Fs must be reduced by the total of such devices. Total annunciation and switch capability depends upon the number of expander modules used.
Communications between the Fire Alarm Control Panel and the LDM-32F is accomplished over a two-wire EIA-485 serial communications bus which must be power-limited. Communications between the host FACP and LDMs is supervised by the fire alarm control panel.

Wiring Specifications

• The EIA-485 circuit cannot be T-tapped; it must be wired in a continuous fashion from the control panel to the LDMs.
• The maximum wiring distance between the panel and LDMs is 6000 feet.
• The wiring must be a 18 AWG to 14 AWG twisted shielded pair cable having a characteristic impedance of 120 ohms, +/- 20%.
• Limit the total wire resistance to 100 ohms.
• Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 V power circuits.
Note: Never use the shield for grounding purposes. Terminate the EIA-485 shield at the Fire Alarm Control Panel only.
20
, motor control circuits, or SCR
RMS
LDM-32F PN 50055:C 03/20/01
LDM32F-super.cdr
Wiring the EIA-485 Terminal Block 2. Installation
Wire Chart
Standard Annealed Copper Wire
Wire Size
A.W.G
14 64 4110 0.00323 2.85 2.97 12.4
16 51 2580 0.00203 4.09 4.73 7.82
18 40 1620 0.00128 6.51 7.51 4.92
Diameter
in Mils
Cross Section Ohms per 1000 feet
Circ. Mils Sq. Inch @ 77°F. @ 149°F.
Pounds per
1000 feet
Table 1 Wire Specifications
EIA-485 Shield in Conduit
When the EIA-485 wiring is in conduit, connect the shield to system common. The shield can enter the cabinet, but must be insulated from the cabinet (no electrical contact). Between LDMs, wire-nut multiple shields together (which can be inside of the respective LDM enclosure but ensure that the shield does not contact earth ground).
TB2
– – + +
LDM32F-term1.cdr
Figure 10 Terminating the Shield in Conduit
EIA-485 Shield Not in Conduit
When the EIA-485 wiring is not in conduit, terminate the shield at the outside of the FACP cabinet. Do not allow the shield to enter or even touch the cabinet housing the LDMs. Between LDMs, wire-nut multiple shields toget her outside of the respective enclosures. Ensure that the shield does not touch earth ground at any junction points.
TB2
– – + +
Figure 11 Terminating the Shield with No Conduit
LDM-32F PN 50055:C 03/20/01
LDM32F-term2.cdr
21
2. Installation Wiring the EIA-485 Terminal Block

EIA-485 - TB2 Terminals

Wire as shown below.
Note: Leave a 120 ohm ELR installed across the EIA-485 Out terminals at the last LDM­32F on the circuit (see below). All other LDM-32Fs should not have a resistor installed.
TB2
In (–)
Out (–)
Out (+)
In (+)
LDM32F-TB2.cdr
Figure 12 EIA-485 Terminal Block - TB2
Multiple wiring of EIA-485 circuits.
First LDM-32F -- -- -- -- -- -- Last LDM-32F
Host FACP
Host FACP
TB2 TB2
EIA-485 (–)
ELR
EIA-485 (+)
LDM32F-mult.cdr
Figure 13 Wiring Multiple LDM-32Fs - EIA-485
22
LDM-32F PN 50055:C 03/20/01
Wiring for Lamp/LED 2. Installation

Wiring for Lamp/LED

• All LEDs must be located in the same room as the LDM modules.
• For 5 volt output use a 680 ohm, 1/4-watt resistors for each point if using 2 mA LEDs.
• For 24 volt output use a 10K ohm, 1/4-watt resistors for each point if using 2 mA LEDs.
• LEDs: use red for alarm points, yellow for trouble points and green for output points.
• Use the cables supplied in the cable kit to wire connectors on LDM.
The figure below illustrates LEDs being powered by the 5 volt output from LDM-32F, J11 pin 1.
Custom Graphic Display Wiring is not
supervised
Point Status LEDs
System Trouble LED
Resistor
J5 J6 J7 J8
1234567
8
9101112131415
16
J11
LDM-32F
171819202122232425262728293031
LAMP POWER
32
J10
J9
Figure 14 Typical LDM-to-Graphics Display Connection @ 5VDC
The figure below illustrates LEDs being powered by the 24 volt output from LDM-32F, J9 pin 3.
Custom Graphic Display
Point Status LEDs
Resistor
J5 J6 J7 J8
1234567
8
9101112131415
16
J11
LDM-32F
171819202122232425262728293031
LAMP POWER
32
J10
J9
Figure 15 Typical LDM-to-Graphics Display Connection @ 24VDC
Wiring is not supervised
System Trouble LED
LDM32F-5voltout.cdr
LDM32F-24voltout.cdr
LDM-32F PN 50055:C 03/20/01
23
2. Installation Wiring the Control Switch

Wiring the Control Switch

Each LDM must be set for Alarm/Trouble mode by positioning slide switch SW4 to the right, for the optional control switches to function (the acknowledge/lamp test switch will work in either mode). In this configuration, each LDM-32F and LDM-E32F provides 16 alarm drivers, 16 trouble drivers and 16 control switches. The alarm and trouble drivers are assigned to host FACP zones/points via user setup. Not all switches must be used - switches can be wired only for desired functions.
• Switches must be UL listed to switch 5 volts DC @ 0.5mA.
• Switches must be key-lock type, secured in a locked enclosure or a security key switch must be installed to control access.
• All switches must be installed in the same room as, and no more than 20 feet from, the LDM enclosure. Wiring must be in conduit.
• Optional zone/point control switches must be momentary type.
• Use the cables supplied in the cable kit to wire the control switches.
• See Appendices for specific FACP information.
Switch #16
Switch #15
Switch #14
Switch #13
Switch #12
Switch #11
Switch #10
Switch #9
Lamp Test/Acknowledge Switch (momentary)
J5
J4
24
Switch #8
Switch #7
Switch #6
Switch #5
Switch #4
Switch #3
Switch #2
Switch #1
Manual Evacuate
System Reset
Signal Silence
Acknowledge
Note: Switches 5 - 16 are not used in this example.
Figure 16 Optional Zone/Point Control Switch Wiring
J1
SWITCH MATRIX
SW1
SW2
12345
SW3
6
78
SW4
Ldmswtwr.cdr
LDM-32F PN 50055:C 03/20/01
Configuring the LDMs 2. Installation

Configuring the LDMs

Address Switches - SW1 and SW2

It is critical to the operation of the LDMs that the Address Switches be set correctly.
To set the LDM-32F’s address to ‘01’, position the arrow on SW2 (tens) so it points to 0 and position the arrow on SW1 (ones) so it points to 1.
SW2 SW1
LDM32F-SW1-2
Figure 17 Address Switches SW1 & SW2

Function DIP Switch - SW3

These switches are used to determine how the LDM-32F operates. The following illustration provides details on DIP switch placement in the On and Off position:
Side View of Switch Shown in the OFF Position
O
F
F
OFF
1
2
345
678
LDM32F-SW3.cdr
Figure 18 Function DIP Switch
LDM-32F PN 50055:C 03/20/01
25
2. Installation Configuring the LDMs
Switch Settings
1 - Not Used: This switch must be set “OFF” 2 - Expanders Installed: None = OFF; One = ON; Two = OFF; Three = ON 3 - Expanders Installed: None = OFF; One = OFF; Two = ON; Three = ON 4 - Eight-Point Shift: Set switch “ON” to switch the FACP LED function
annuciation from the first eight annunciator positions on the LDM-32F to the last LDM-E32F expander positions 57 - 64. This shift can only be set on an LDM-32F set for address 01 (system using 56, or less, software zones). 5 - Receive Only: Set this switch “ON” for each LDM series that will provide the same information as another LDM series in a different physical location.
Note: When two or more LDM series hold the same address, all but one must be configured as “Receive Only”.
6 - Piezo Disable: Set this switch “ON” to disable the piezo from sounding for any event. (The piezo will also be disabled if Flash Inhibit is “ON”.) 7 - Switch Inhibit: To disable the point control switches on the LDMs from functioning, set this switch “ON”. When inhibited, the local lamp test switch continues to function. In addition, the acknowledge/lamp test switch will function only in a local capacity, unrecognized by the host FACP. 8 - Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also disables the piezo from sounding.

Mode Switch - SW4

Set the mode of operation to:
“Alarm/Trouble” by sliding the switch to the right “Alarm Only” mode by sliding the switch to the left.
Alarm Only
Mode
Figure 19 Mode Select Switch - SW4
26
Alarm/Trouble Mode
LDM32F-SW4.cdr
LDM-32F PN 50055:C 03/20/01

3. Operation

Lamp Test/Acknowledge

A separate, dedicated lamp test switch is required for each LDM-32F and LDM-E32F (see "Wiring the Control Switch" on page 24). A switch installed for LAMP TEST/ACKNOWLEDGE performs two functions:
1. When pressed, it will light all LEDs wired to the specific LDM module (except the On Line LED) and will sound the integral piezo (if enabled) for as long as the switch is held down. The Lamp Test switch will light
only the LEDs on the module to which it is wired.
2. The switch connected to the LDM-32F, when pressed, acknowledges all status changes (for both the LDM-32F and any LDM-E32F expanders). Flashing LEDs will latch on solid and the piezo will be silenced.

On Line LED

This green LED, located on the LDM-32F module (see Figure 1 on page 10), flashes during communication with the host control panel.

Graphic Annunciator Lamps/LEDs

To adhere to standard fire alarm control panel convention and remain consistent with other products that may exist in the system, the following color convention is employed:
Red Alarm LEDs - To indicate an alarm condition for an Initiating Device Circuit or a software zone.
Yellow Trouble LEDs - To indicate a trouble condition exists on an initiating or indicating device circuit or zone. Yellow trouble LEDs also are used to indicate general system trouble conditions such as low battery, earth fault, general system trouble, etc.
Green Controlled Output LEDs - Indicates that power is applied or that the controlled output circuit or device has been activated. Applicable to notification appliance, relay, speaker, telephone, and time control circuits.
Note: The graphic annunciator may contain a yellow System Trouble LED and a red System Alarm LED which will light for all trouble or alarm conditions (respectively) in the
system (not just for those points of zones mapped to the LDM master/expanders).
LDM-32F PN 50055:C 03/20/01
27
3. Operation Graphic Annunciator Lamps/LEDs
NOTES
28
LDM-32F PN 50055:C 03/20/01

4. LDM Communications

Receive Only LDM-32Fs

For duplicate annunciation of system points, LDMs can be configured for Receive Only annunciation. Receive Only LDMs must be set to the same address as the LDM they duplicate, but are not fully supervisable. Receive Only LDMs intercept information being transmitted to a Receive/Transmit LDM so that this information can be duplicated at an intermediate display location. When configured for Receive Only operation, LDMs cannot transmit information to the host control panel. Remote Acknowledge, Silence, or Reset cannot be performed. Control switches on Receive Only LDMs are for local lamp test only. If a Receive/Transmit LDM is located at the end of the EIA­485 bus, it will provide supervision of Receive Only LDMs located on the EIA­485 bus between the Receive/Transmit LDM and the FACP.

Receive/Transmit LDM-32F

LDMs that are configured to serve as full-function annunciators can both receive status information for annunciation as well as transmit commands to the control panel through custom-wired point control switches. This allows the LDM to initiate control panel switch functions from a remote location in addition to displaying the status of the system. In order for wiring connecting all Receive/Transmit LDMs to be supervised, the LDM-32F addressed as '01' must be placed at the end of the EIA-485 loop farthest from the FACP. Only address '01' is supervised.
Receive Only LDM-32F
Fire Alarm Control Panel
Set to Address X
LDM-32F PN 50055:C 03/20/01
EIA-485 Circuit
LDM-32F LDM-E32F
Receive/Transmit LDM-32F Set to Address X
LDM-32F LDM-E32F
Figure 20 LDM-32F Supervision
Ldmsupv.cdr
29
4. LDM Communications Receive/Transmit LDM-32F
NOTES
30
LDM-32F PN 50055:C 03/20/01

5. Electrical Ratings and Current Calculations

Lamp Driver Electrical Ratings

LDM modules may use either 24 VDC (regulated) or internal 5 VDC for powering connected LEDs. 5 volt usage conserves power but is limited in the current available to drive the LEDs. Refer to "Wiring for Lamp/LED" on page 23 for connection illustrations.
5 Volt LED Power Limitations
LED Current Desired (mA)
2 13013
56611
10 34 1 0
Note: The LDM-32F drives 32 LEDs and each LDM-E32F drives 32 more LEDs. An LDM system configured for Alarm and Trouble Display Mode and employing three expanders could have as many as 128 LEDs, all of which are activated during Lamp Test.
Max Number of LEDs
Table 2 Power Limitations
Number of Modules
LDM-32F LDM-E32F
Maximum Current per Driver: 100 mA (external circuit must limit current)
Maximum Voltage rating per output driver: 30 VDC
Supervised circuit (typical rating): 5 volts DC @ 0.5 mA
Bipolar Darlington Open Collector NPN Transistor

Supervision of LDM points

Any LEDs or lamps connected to the LDM-32F or LDM-E32F are not supervised for failure. Therefore, all LEDs or lamps, must be located in the same room as the LDM modules.
LDM-32F PN 50055:C 03/20/01
31
5. Electrical Ratings and Current Calculations Calculating Standby and

Calculating Standby and Alarm Currents

The LDM series annunciators draw their power from the Fire Alarm Control Panel and must be considered when calculating primary and secondary power requirements. Refer to the installation manual for the particular control panel employed for the calculation of power requirements for the entire system.
1. Enter Standby Total obtained here into the standby calculation tables of the installation manual.
2. Enter Alarm Current Total obtained here into the alarm calculation tables of the installation manual.
Standby Current
Numb er of LDM-32F Modules [ ]
Number of LDM-E32F Expanders [ ] X 2 mA =
Standby Total = [ ] amps
Alarm Current
Numb er of LDM-32F Modules [ ] X 56 mA =
Numb er of LDM-E32F Expander [ ] X 18 mA =
Number of LEDs
Number of LEDs
1. The 0.040 amps can be reduced to 0.030 for modules with Piezo disable or Flash Inhibit selected.
2. Use this line for calculations if LEDs are powered from 24 VDC source.
3. Use this line for calculations if LEDs are powered from the 5 VDC source from J1 on the LDM-32F.
2
3
[ ] X [ ]mA per LED=
[ ] X [( )mA/3]=
Alarm Current Total = [ ] amps
X 40 mA
1
=
Table 3 Power Requirement Calculations
32
LDM-32F PN 50055:C 03/20/01

Appendix A: Sensiscan 2000

Capabilities

When installed with a Sensiscan 2000, the LDM Series modules can annunciate general system status; the status of all initiating and notification circuits and output relays. Plus, manually activate all points via control switches. Each lamp driver output may be assigned to one and only one system I/O point:
Optional Sensiscan 2000 plug in Modules -
IZ-8F - Initiating Device Circuits (alarm and trouble) IZ-4F/IZE-AF - Initiating Device Circuits (alarm and trouble) IC-4F/IC-4CCF - Notification Appliance Circuits (trouble) ICE-4F - Notification Appliance Circuits (trouble) CR-4F/CRE-4F - Control Relay Modules TC-2F/TC-4F - Time Control Modules
Sensiscan 2000 modules are user configurable. Refer to the Sensiscan 2000 Manual.
System Control Switches -
Acknowledge Signal Silence System Reset Activate selected system outputs (notification circuits, relays)
System Control Switches on the Sensiscan 2000 CPU may be remoted via the LDM series modules. Also, zone/point control switches may be configured.

Trouble Indication

Communication between the CPU and the LDMs is accomplished over a two­wire EIA-485 serial communication bus. The EIA-485 bus is supervised by the Sensiscan 2000. Loss of communication results in System Trouble and Module Failure indications at the CPU.

Programming and Testing the LDM-32F

After complete installation, the Lamp Driver Module(s) must be programmed into the control panel as if it were an annunciator. After programming the fire alarm control panel to accept them, fully test the LDM(s) by ensuring that each switch and LED performs its intended function, and that the LDM(s) can perform the functions outlined in "3. Operation" on page 27.
LDM-32F PN 50055:C 03/20/01
33
Appendix A: Sensiscan 2000 Power Supply Connection

Power Supply Connection

The LDMs may be powered by an MPS-24AF or an MPS-24BF. The power run to the LDMs need not contain a Power Supervision Relay since loss of power is inherently supervised.

MPS-24AF Main Power Supply

Connect the power run for the LDMs to MPS-24AF TB3, Terminals 1 (+) and 2 (–). Maximum current is 1 amp.
To LDM-32F TB1
Power In (+)
+24R COMMON +24 COMMON
BAT + BAT -
TB2
Figure 21 MPS-24AF Power Supply Connections

MPS-24BF Main Power Supply

Connect the power run for the LDMs to MPS-24BF TB2, Terminals 1 (+) and 2 (–). No more than 200 mA current can be drawn from these terminals in standby or alarm.
To LDM-32F TB1
Power In (+)
To LDM-32F TB1 Common In (–)
POWER L IMI TED
P3
To LDM-32F TB1 Common In (–)
P2
P5
P4
R27
LDM32F-mps24af.cdr
6 7 8
TB2
+24 VRESET +24 VPOWER
1 2 3 4
BATT +
1 2
BATT -
TB3
P3
COMMON COMMON
Figure 22 MPS-24BF Power Supply Connections

EIA-485 Connection

The EIA-485 bus that communicates with the LDM must be connected to the CPU as illustrated below.
Note: The CPU must be Revision D or greater. (The revision level of the CPU is marked on a label affixed to the upper board.)
EIA-485
To TB 2 I n ( – )
Sensiscan 2000 CPU
Figure 23 EIA-485 Connection to CPU
34
EIA-485 To TB2 I n ( + )
LDM-32F PN 50055:C 03/20/01
LDM32F-mps24bf.cdr
LDM32F-s2000.cdr
Lamp/LED Driver Operation Appendix A: Sensiscan 2000

Lamp/LED Driver Operation

LDM Address Switches (SW1 & SW2) must be set to address ‘01’.
Lamp Driver outputs do not latch - they track or follow the status of each zone/ point that they are assigned to annunciate. The table below defines the ON status of each lamp driver output.
Note: Control Switches marked 'Not Used' will still function as local LAMP TEST or local ACKNOWLEDGE switches for their respective points.
Note: If Alarm Only mode is selected, column labeled Yellow LED is not applicable and control switches do not function.
CPU Points
1
Annunciator Point #1
Annunciator Point #2
Annunciator Point #3
Annunciator Point #4
Annunciator Point #5
Annunciator Point #6
Annunciator Point #7
Annunciator Point #8
1. If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight Sensiscan 2000 CPU functions (ACK, SIL, RESET, LAMP TEST, NAC1, NAC2, MUNTIE, RELAY) will be shifted from annunciator points 1 through 8 (as shown above) to points 57 through 64 (provided those points exist in the system and the LDM-32F is set to address 01).
2. Optional control switches are active only if all of these conditions are met: a) '8-Point Shift' (DIP switch #4) is set to OFF. b) Receive Only (DIP Switch #5) is set to OFF. c) Switch Inhibit (DIP Switch #7) is set to OFF.
3. Use green LEDs to indicate activation on controlled output circuits.
Alarm
(Red LED)
System Alarm System Trouble Acknowledge
Not Used Signal Silence Signal Silence
Not Used Not Used System Reset
Not Used
NAC #1 Activated
NAC #2 Activated
Remote Signaling of Municipal Tie
Activated
3
Alarm Relay
Activated
3
Trouble/Supv (Yellow LED)
Supervisory Condition
Trouble Status of
3
Circuit
Trouble Status of
3
Circuit
Trouble Status of Circuit
Module Trouble, Power Failure, or Disabled Circuit
Control Switches
Not Used
NAC #1
NAC #2
Remote Signaling of Municipal Tie
Alarm Relay
Table 4 Annunciator Point Assignment to LDMs
2
LDM-32F PN 50055:C 03/20/01
35
Appendix A: Sensiscan 2000 Lamp/LED Driver Operation
The following table defines the point assignments if incorporating the optional modules available on the Sensiscan 2000.
Optional
Modules
IZ-8F Alarm Status per
IZ-4F/IZE-4F Alarm Status per
IC-4F/IC-4CCF
ICE-4F
CR-4F/CE-4F Indicates
TC-2F/TC-4F Indicates
1. Optional control switches are active only if all of these conditions are met: a) '8-Point Shift' (DIP switch #4) is set to OFF. b) Receive Only (DIP Switch #5) is set to OFF. c) Switch Inhibit (DIP Switch #7) is set to OFF.
2. These Status LEDs are active only when the Sensiscan 2000 is programmed for Output Status. Use green LEDs to indicate activation on controlled output circuits.
3. These control switches require that the Sensiscan 2000 be programmed for Output Control.
Alarm
(Red LED)
Circuit
Circuit
Indicates
Activation
Indicates
Activation
Activation
Activation
Trouble/Supv (Yellow LED)
Trouble Status per Circuit
Trouble Status per Circuit
2
2
2
2
Indicates Trouble per Circuit
Indicates Trouble per Circuit
Indicates Trouble per Circuit
Indicates Trouble per Circuit
Control Switches
Not Used
Not Used
Momentarily Turns On NAC Output
When Pressed
Momentarily Turns On NAC Output
When Pressed
3
Relays
Remote Switch
Functions
1
3
3
3
Table 5 Optional Modules Annunciator Point Assignment to LDMs
36
LDM-32F PN 50055:C 03/20/01
Lamp/LED Driver Operation Appendix A: Sensiscan 2000

Alarm Only Operation

The table below illustrates the configuration of the LDM Series modules to annunciate alarms for up to 56 zones/points (no troubles) with the first eight points (P1 through P8) dedicated to the Sensiscan 2000 system status annunciation (see Figure 24 below).
Note: Control switches do not function in Alarm Only configuration.
Note: The Address switch sets the limit of annunciator points per LDM series. With the
address set to 01, the limit is 64 annunciated points.
LDM Module Address ‘01’
LDM-32F System Status 1 to 8 9 to 16 17 to 24
LDM-E32F 25 to 32 33 to 40 41 to 48 49 to 56
J5 J6 J7 J8
LDM Output Connectors
Table 6 Alarm Only Operation

Alarm Only Operation with 8-Point Shift

The table below illustrates the configuration of the LDM Series modules to annunciate alarms for up to 56 zones/points (no troubles) with the last eight points (P57 through P64) dedicated to the Sensiscan 2000 system status annunciation (see Figure 24 below).
It is assumed that the ‘8-Point Shi ft’ will be selected only on systems containing 56 zones/points or less, or a total of 64 annunciator points or less.
Note: Control Switches do not function in Alarm Only mode.
Note: Addres s switch sets the limit of annunciator points per LDM series. With the address
set to 01, the limit is 64 annunciated points.
LDM Module Address ‘01’
LDM-32F 1 to 8 9 to 16 17 to 24 25 to 32
LDM-E32F 33 to 40 41 to 48 49 to 56 System Status
J5 J6 J7 J8
LDM Output Connectors
System Status Indicators
NAC #1 ON (Green LED)
System Alarm (Red LED)
Figure 24 System Functions to Output Connectors - 1
LDM-32F PN 50055:C 03/20/01
Table 7 Alarm Only Operation with Shift
NAC #2 ON (Green LED)
Not
Used
Municipal Tie ON (Red LED)
J5
1234567
J8
25262728293031
8
32
LDM32F-J5.cdr
37
Appendix A: Sensiscan 2000 Lamp/LED Driver Operation

Alarm/Trouble Operation

The table below (also see Figure 25 on page 39) illustrates the configuration of the LDM Series modules to annunciate alarms and troubles for up to 56 zones/points with the first eight points - 16 LEDs (J5: P1 through P8 and J6: P1 through P8) dedicated to Sensiscan 2000 system status annunciation (see Figure 26 on page 39).
LDM Module Address ‘01’
LDM-32F System Status 1 to 4 5 to 8
1st LDM-E32F 9 to 12 13 to 16 17 to 20 21 to 24
2nd LDM-E32F 25 to 28 29 to 32 33 to 36 37 to 40
3rd LDM-E32F 41 to 44 45 to 48 49 to 52 53 to 56
J5 J6 J7 J8
LDM Output Connectors
Table 8 Alarm/Trouble Operation

Alarm/Trouble Operation with 8-Point Shift

The table below (also see Figure 25 on page 39) illustrates the configuration of the LDM Series modules to annunciate alarms and troubles for up to 56 zones/points with the last eight points - 16 LEDs (J7: P1 through P8 and J8: P1 through P8) dedicated to Sensiscan 2000 system status annunciation (see Figure 27 on page 39).
LDM Module Address ‘01’
LDM-32F 1 to 4 5 to 8 9 to 12 13 to 16
1st LDM-E32F 17 to 20 21 to 24 25 to 28 29 to 32
2nd LDM-E32F 33 to 36 37 to 40 41 to 44 45 to 48
3rd LDM-E32F 49 to 52 53 to 56 System Status
J5 J6 J7 J8
Table 9 Alarm/Trouble Operation
LDM Output Connectors
38
LDM-32F PN 50055:C 03/20/01
Lamp/LED Driver Operation Appendix A: Sensiscan 2000
The figure below is an example of the connections used when setting the LDM module for Alarm/Trouble mode.
Alarm - First 4 Zones or Points Trouble - First 4 Zones or Points
Alarm - Second 4 Zones or Points Trouble - Second 4 Zones or Points
Alarm - Third 4 Zones or Points Trouble - Third 4 Zones or Points
Alarm - Fourth 4 Zones or Points Trouble - Fourth 4 Zones or Points
J5 J6 J7 J8
1234567
8
9101112131415
16
171819202122232425262728293031
32
LCM32F-conn.cdr
Figure 25 Connections for Alarm/Trouble
The figure below illustrates pin usage of output connectors for system functions in Alarm/Trouble mode.
System Status Indicators
Supervisory (Yellow)
Not Used
Signals Silenced (Yellow)
System Trouble (Yellow)
System Alarm (Red)
Not
Used
NAC #1 ON (Green) NAC #2 ON (Green) Municipal Tie ON (Red) Alarm Relay ON (Red) NAC #1 Trbl (Yellow) NAC #2 Trbl (Yellow) Municipal Tie Trbl (Yellow) Alarm Relay Trbl (Yellow)
J5 J6
1234567
8
9101112131415
16
LCM32F-J5J6.cdr
Figure 26 System Functions to Output Connectors - 1
The figure below illustrates pin usage of output connectors for system functions in alarm/trouble mode with 8-Point shift selected.
System Status Indicators
Supervisory (Yellow)
Signals Silenced (Yellow)
System Trouble (Yellow)
System Alarm (Red)
Figure 27 System Functions to Output Connectors - 2
LDM-32F PN 50055:C 03/20/01
Not Used
J7 J8
Not
Used
17181820212223
24
25262728293031
NAC #1 ON (Green) NAC #2 ON (Green) Municipal Tie ON (Red) Alarm Relay ON (Red) NAC #1 Trbl (Yellow) NAC #2 Trbl (Yellow) Municipal Tie Trbl (Yellow) Alarm Relay Trbl (Yellow)
32
LCM32F-J7J8.cdr
39
Appendix A: Sensiscan 2000 Control Switch Operation

Control Switch Operation

Circuit corresponds to a specific I/O module installed in user configured Sensiscan 2000.
The first 8 control switches of the LDM-32F will correspond to CPU switch functions as shown below, if “8-Point Shift” is not selected.
With “8-Point Shift” selected, the first 8 control switches move to the 3rd LDM­E32F and are assigned to Circuits 57 through 64 as shown below.
Note: It is assumed that Sensiscan 2000 systems with “8-Point Shift” selected will be 56 zones/points or less.
Switch
Position
1 Acknowledge Not Used
2 Signal Silence Not Used
3System Reset Not Used
4 Not Used Not Used
5 NAC #1 Not Used
6 NAC #2 Not Used
7 Municipal Tie Not Used
8 Alarm Relay Not Used
9 Not Used Acknowledge
10 Not Used Signal Silence
11 Not Used System Reset
12 Not Used Not Used
13 Not Used NAC #1
14 Not Used NAC #2
15 Not Used Municipal Tie
16 Not Used Alarm Relay
LDM-32F ----- 3rd LDM-E32F
Table 10 Switch Control Functions
40
LDM-32F PN 50055:C 03/20/01

Appendix B: MS-9200

Capabilities

When installed with a MS-9200, the LDM Series modules can annunciate the status of 56 software zones or 198 points plus system status. Each lamp driver output is assigned to one and only one system I/O point:
Addressable Devices -
Detectors - SD350, SD350T, CP350, H350, H350R, D350P & D350LP Monitor Modules - MMF-300, MMF-301, MMF-302 & MDF-300 Control Modules - CMF-300 Addressable Pull Stations - BG-12LX
System Control Switches -
Acknowledge, Signal Silence, System Reset & Drill

Trouble Indication

Communication between the MS-9200 and the LDMs is accomplished over a two-wire EIA-485 serial communication bus. The EIA-485 bus is supervised by the MS-9200. Loss of communication results in system trouble message on the panel’s display.

Programming and Testing the LDM-32F

After complete installation, the Lamp Driver Module(s) must be programmed into the control panel as if it were an annunciator. After programming the fire alarm control panel to accept them, fully test the LDM(s) by ensuring that each switch and LED performs its intended function, and that the LDM(s) can perform the functions outlined in "3. Operation" on page 27.

Power and EIA-485 Connections

Regulated 24 VDC power and the EIA-485 communication circuit must be connected to the MS-9200 as illustrated below.
Note: An external power source may be used to power the LDM Series.
To LDM TB2 ­EIA-485 IN (+) EIA-485 IN (–)
ACS SHIELD SLC SL C
1 COMM 2
T B 5
24V UNREG24V NONRS 24V RST BELL 2 POWER BELL 1 POWER SUPV ALARM TROUBLE
T B 4
Figure 28 MS-9200 Circuit Board connections
LDM-32F PN 50055:C 03/20/01
To LDM TB1 ­Power IN (+) Power IN (–)
B+ A + A- B-
B+ A + A- B-
T B 2
NO C NO NC C NO NC C A B B+ A+ B- A-
T B 1
OU T+ IN+ OUT- IN -
T B 3
T B 7
T B 6
LDM32F-9200.cdr
41
Appendix B: MS-9200 Configuration

Configuration

The control panel needs to be programmed to either “Points” or “Zones”, depending on which type of address is to be annunciated.
LDM Address Switches (SW1 & SW2) must be set to address ‘01’, ‘02’, ‘03’ or ‘04’. The CPU will differentiate between the addresses.
• For Zones use address 01 (56 zones).
• For Points use addresses 01, 02, 03 and 04 (198 points).
Note: Do not omit any address when annunciating 198 points or the MS-9200 will indicate a constant trouble.

Alarm Only Annunciation of Zones

The table below illustrates the configuration of the LDM Series modules to annunciate the alarm state of all 56 software zones (no zone troubles), and two NACs, with the first eight points of address ‘01’ dedicated to the MS-9200 system function LEDs (see Figure 29 below).
LDM Module Address ‘01’
LDM-32F Sys Funct Z1 to Z8 Z9 to Z16 Z17 to Z24
LDM-E32F Z25 to Z32 Z33 to Z40 Z41 to Z48 Z49 to Z56
J5 J6 J7 J8
LDM Output Connectors
Table 11 Alarm Only Setup

Alarm Only Annunciation of Zones - With 8-Point Shift

The table below illustrates the configuration of the LDM Series modules to annunciate the alarm state of all 56 software zones (no zone troubles), and two NACs, with the last eight points of address ‘01’ dedicated to the MS-9200 system function LEDs (see Figure 29 below).
LDM Module Address ‘01’
LDM-32F Z1 to Z8 Z9 to Z16 Z17 to Z24 Z25 to Z32
LDM-E32F Z33 to Z40 Z41 to Z48 Z49 to Z56 Sys Funct
J5 J6 J7 J8
Table 12 Alarm Only Setup with Shift
System Alarm
Not Used
J5
1234567
Figure 29 System Functions to Output Connectors - 1
LDM Output Connectors
System Alarm
8
J8
25262728293031
Not Used
32
LDM32F-J5J8.cdr
42
LDM-32F PN 50055:C 03/20/01
Configuration Appendix B: MS-9200

Alarm/Trouble Annunciation of Zones

The table below (also see Figure 30 on page 44) illustrates the configuration of the LDM Series modules to annunciate the alarm and trouble states for all 56 software zones with the first eight points of address ‘01’ dedicated to the MS-9200 system functions (see Figure 31 on page 44).
LDM Module Address ‘01’
LDM-32F System Functions Z1 to Z4 Z5 to Z8
1st LDM-E32F Z9 to Z12 Z13 to Z16 Z17 to Z20 Z21 to Z24
2nd LDM-E32F Z25 to Z28 Z29 to Z32 Z33 to Z36 Z37 to Z40
3rd LDM-E32F Z41 to Z44 Z45 to Z48 Z49 to Z52 Z53 to Z56
J5 J6 J7 J8
LDM Output Connectors
Table 13 Alarm/Trouble Setup
Alarm/Trouble Annunciation of Zones ­With 8-Point Shift
The table below (also see Figure 30 on page 44) illustrates the configuration of the LDM Series modules to annunciate the alarm and trouble states for all 56 software zones with the last eight points of address ‘01’ dedicated to the MS­9200 system functions as listed below (see Figure 32 on page 44).
LDM Module Address ‘01’
LDM-32F Z1 to Z4 Z5 to Z8 Z9 to Z12 Z13 to Z16
1st LDM-E32F Z17 to Z20 Z21 to Z24 Z25 to Z28 Z29 to Z32
2nd LDM-E32F Z33 to Z36 Z37 to Z40 Z41 to Z44 Z45 to Z48
3rd LDM-E32F Z49 to Z52 Z53 to Z56 System Functions
J5 J6 J7 J8
Table 14 Alarm/Trouble Setup with Shift
LDM Output Connectors
LDM-32F PN 50055:C 03/20/01
43
Appendix B: MS-9200 Configuration
The figure below is an example of the connections used when setting the LDM module for Alarm/Trouble mode.
Alarm - First 4 Zones or Points Trouble - First 4 Zones or Points
Alarm - Second 4 Zones or Points Trouble - Second 4 Zones or Points
Alarm - Third 4 Zones or Points Trouble - Third 4 Zones or Points
Alarm - Fourth 4 Zones or Points Trouble - Fourth 4 Zones or Points
J5 J6 J7 J8
1234567
8
9101112131415
16
171819202122232425262728293031
32
LCM32F-conn.cdr
Figure 30 Connections for Alarm/Trouble
The figure below illustrates pin usage of output connectors for system functions in alarm/trouble mode.
System Status Indicators
Signals Silenced (Yellow)
System Trouble (Yellow)
System Alarm (Red)
Supervisory (Yellow) AC Fail (Red)
J5 J6
1234567
Note: Pins not marked are not used
8
9101112131415
16
Figure 31 System Functions to Output Connectors - 1
The figure below illustrates pin usage of output connectors for system functions in alarm/trouble mode with 8-Point shift selected.
System Status Indicators
Signals Silenced (Yellow)
System Trouble (Yellow)
System Alarm (Red)
Figure 32 System Functions to Output Connectors - 2
44
J7 J8
17181820212223
Note: Pins not marked are not used
24
25262728293031
Supervisory (Yellow) AC Fail (Red)
32
LDM-32F PN 50055:C 03/20/01
LCM32F-J5J6.cdr
LCM32F-J7J8.cdr
Configuration Appendix B: MS-9200

Alarm Only Annunciation of Points

The tables below illustrate the configuration of the LDM Series modules to annunciate the alarm state of all 99 points (detectors or modules) with the first eight points of address ‘01’ dedicated to the MS-9200 system functions (see Figure 29 on page 42).
Detectors
Set address ‘01’ and ‘02’ for detectors.
LDM Module Address ‘01’
LDM-32F Sys Funct 1 to 8 9 to 16 17 to 24
LDM-E32F 25 to 32 33 to 40 41 to 48 49 to 56
LDM Module Address ‘02’
LDM-32F 57 to 64 65 to 72 73 to 80 81 to 88
LDM-E32F 89 to 96 97 to 99 Not Used Not Used
J5 J6 J7 J8
J5 J6 J7 J8
LDM Output Connectors
LDM Output Connectors
Table 15 Alarm Only Setup - Detectors
Modules
Set address ‘03’ and ‘04’ for modules.
LDM Module Address ‘03’
LDM-32F 1 to 8 9 to 16 17 to 24 25 to 32
LDM-E32F 33 to 40 41 to 48 49 to 56 57 to 64
LDM Module Address ‘04’
LDM-32F 65 to 72 73 to 80 81 to 88 89 to 96
LDM-E32F 97 to 99 Not Used Not Used Not Used
J5 J6 J7 J8
J5 J6 J7 J8
LDM Output Connectors
LDM Output Connectors
LDM-32F PN 50055:C 03/20/01
Table 16 Alarm Only Setup - Modules
45
Appendix B: MS-9200 Configuration
Alarm Only Annunciation of Points ­With 8-Point shift
The tables below illustrate the configuration of the LDM Series modules to annunciate the alarm state of all 99 points (detectors or modules) with the last eight points of address ‘01’ dedicated to the MS-9200 system functions (see Figure 29 on page 42).
Detectors
Set address ‘01’ and ‘02’ for detectors.
LDM Module Address ‘01’
LDM-32F 1 to 8 9 to 16 17 to 24 25 to 32
LDM-E32F 33 to 40 41 to 48 49 to 56 Sys Funct
LDM Module Address ‘02’
LDM-32F 57 to 64 65 to 72 73 to 80 81 to 88
LDM-E32F 89 to 96 97 to 99 Not Used Not Used
J5 J6 J7 J8
J5 J6 J7 J8
LDM Output Connectors
LDM Output Connectors
Table 17 Alarm Only Setup - Detectors (shift)
Modules
Set address ‘03’ and ‘04’ for modules.
LDM Module Address ‘03’
LDM-32F 1 to 8 9 to 16 17 to 24 25 to 32
LDM-E32F 33 to 40 41 to 48 49 to 56 57 to 64
LDM Module Address ‘04’
LDM-32F 65 to 72 73 to 80 81 to 88 89 to 96
LDM-E32F 97 to 99 Not Used Not Used Not Used
J5 J6 J7 J8
J5 J6 J7 J8
LDM Output Connectors
LDM Output Connectors
46
Table 18 Alarm Only Setup - Modules (shift)
LDM-32F PN 50055:C 03/20/01
Configuration Appendix B: MS-9200

Alarm /Trouble Annunciation of Points

The table below (also see Figure 30 on page 44) illustrates the configuration of the LDM Series modules to annunciate the alarm and trouble states for all 99 points (detectors or modules) with the first eight points of address ‘01’ dedicated to the MS-9200 system functions (see Figure 31 on page 44).
Detectors
Set address ‘01’ and ‘02’ for detectors.
LDM Module Address ‘01’
LDM-32F System Functions 1 to 4 5 to 8
1st LDM-E32F 9 to 12 13 to 16 17 to 20 21 to 24
2nd LDM-E32F 25 to 28 29 to 32 33 to 36 37 to 40
3rd LDM-E32F 41 to 44 45 to 48 49 to 52 53 to 56
LDM Module Address ‘02’
LDM-32F 57 to 60 61 to 64 65 to 68 69 to 72
1st LDM-E32F 73 to 76 77 to 80 81 to 84 85 to 88
2nd LDM-E32F 89 to 92 93 to 96 97 to 99 Not Used
J5 J6 J7 J8
J5 J6 J7 J8
LDM Output Connectors
LDM Output Connectors
Table 19 Alarm/Trouble Setup - Detectors
Modules
Set address ‘03’ and ‘04” for modules
LDM Module Address ‘03’
LDM-32F 1 to 4 5 to 8 9 to 12 13 to 16
1st LDM-E32F 17 to 20 21 to 24 25 to 28 29 to 32
2nd LDM-E32F 33 to 36 37 to 40 41 to 44 45 to 48
3rd LDM-E32F 49 to 52 53 to 56 57 to 60 61 to 64
J5 J6 J7 J8
LDM Output Connectors
LDM Module Address ‘04’
LDM-32F 65 to 68 69 to 72 73 to 76 77 to 80
1st LDM-E32F 81 to 84 85 to 88 89 to 92 93 to 96
2nd LDM-E32F 97 to 99 Not Used Not Used Not Used
LDM-32F PN 50055:C 03/20/01
LDM Output Connectors
J5 J6 J7 J8
Table 20 Alarm/Trouble Setup - Modules
47
Appendix B: MS-9200 Configuration
Alarm /Trouble Annunciation of Points ­With 8-Point Shift
The table below (also see Figure 30 on page 44) illustrates the configuration of the LDM Series modules to annunciate the alarm and trouble states for all 99 points (detectors or modules) with the last eight points of address ‘01’ dedicated to the MS-9200 system functions (see Figure 32 on page 44).
Detectors
Set address ‘01’ and ‘02’ for detectors.
LDM Module Address ‘01’
LDM-32F 1 to 4 5 to 8 9 to 12 13 to 16
1st LDM-E32F 17 to 20 21 to 24 25 to 28 29 to 32
2nd LDM-E32F 33 to 36 37 to 40 41 to 44 45 to 48
3rd LDM-E32F 49 to 52 53 to 56 System Functions
LDM Module Address ‘02’
LDM-32F 57 to 60 61 to 64 65 to 68 69 to 72
1st LDM-E32F 73 to 76 77 to 80 81 to 84 85 to 88
2nd LDM-E32F 89 to 92 93 to 96 97 to 99 Not Used
J5 J6 J7 J8
J5 J6 J7 J8
LDM Output Connectors
LDM Output Connectors
Table 21 Alarm/Trouble Setup - Detectors (shift)
Modules
Set address ‘03’ and ‘04” for modules
LDM Module Address ‘03’
LDM-32F 1 to 4 5 to 8 9 to 12 13 to 16
1st LDM-E32F 17 to 20 21 to 24 25 to 28 29 to 32
2nd LDM-E32F 33 to 36 37 to 40 41 to 44 45 to 48
3rd LDM-E32F 49 to 52 53 to 56 57 to 60 61 to 64
J5 J6 J7 J8
LDM Output Connectors
48
LDM Module Address ‘04’
LDM-32F 65 to 68 69 to 72 73 to 76 77 to 80
1st LDM-E32F 81 to 84 85 to 88 89 to 92 93 to 96
2nd LDM-E32F 97 to 99 Not Used Not Used Not Used
J5 J6 J7 J8
LDM Output Connectors
Table 22 Alarm/Trouble Setup - Modules (shift)
LDM-32F PN 50055:C 03/20/01
Configuration Appendix B: MS-9200

Configuration Diagram

The following diagram illustrates the configuration of LDM modules for 198 point Alarm/Trouble annunciation.
All LDM modules are set to “Receive/Transmit”.
The LDM-32F addressed as ‘01’ must be placed at the end of the EIA-485 circuit in order to provide electrical supervision of the wiring between all LDMs on the loop.
EIA-485 Line
MS-9200 FACP
LDM-32F LDM-E32F LDM-E32F Address 04 (Modules)
LDM-32F LDM-E32F LDM-E32F LDM-E32F Address 03 (Modules)
LDM-32F LDM-E32F LDM-E32F Address 02 (Detectors)
Ldm198pt .cdr
Figure 33 Configuration for 198 Point Alarm/Trouble
LDM-32F PN 50055:C 03/20/01
LDM-32F LDM-E32F LDM-E32F LDM-E32F Address 01 (Detectors)
49
Appendix B: MS-9200 Configuration
NOTES
50
LDM-32F PN 50055:C 03/20/01

Appendix C: MS-9600

Capabilities

When installed with a MS-9600, the LDM Series modules can annunciate the status of 99 software zones or 318 points (per SLC Loop) plus system status. Each lamp driver output is assigned to one and only one system I/O point:
Addressable Devices -
Detectors - SD350, SD350T, CP350, H350, H350R, D350P & D350LP Monitor Modules - MMF-300, MMF-301, MMF-302 & MDF-300 Control Modules - CMF-300 Addressable Pull Stations - BG-12LX
System Control Switches -
Acknowledge, Signal Silence, System Reset & Drill

Trouble Indication

Communication between the MS-9600 and the LDMs is accomplished over a two-wire EIA-485 serial communication bus. The EIA-485 bus is supervised by the MS-9600. Loss of communication results in system trouble message on the panel’s display.

Programming and Testing the LDM-32F

After complete installation, the Lamp Driver Module(s) must be programmed into the control panel as if it were an annunciator. After programming the fire alarm control panel to accept them, fully test the LDM(s) by ensuring that each switch and LED performs its intended function, and that the LDM(s) can perform the functions outlined in "3. Operation" on page 27.

Power and EIA-485 Connections

Regulated 24 VDC power and the EIA-485 communication circuit must be connected to the MS-9600 as illustrated below.
Note: An external power source may be used to power the LDM Series.
To LDM TB1 ­Power IN (+) Power IN (–)
TB3
Figure 34 MS-9600 Circuit Board connections
LDM-32F PN 50055:C 03/20/01
TB4
TB5
TB6 TB7
To LDM TB2 ­EIA-485 IN (+) EIA-485 IN (–)
TB8
LCM32F-9600.cdr
51
Appendix C: MS-9600 Configuration

Configuration

Setting Rotary Switches

LDM Address Switches (SW1 & SW2) must be set to an address. Use the following table to set these switches.
Note: Do not omit any address when annunciating 636 points or the MS-9600 will indicate a constant trouble.
M = Module D = Detector
FACP
Address
13 - 19 Not Used
SW1 SW2 Relay Activation for:
1 0 1 8 System Points & Zones 1-56
2 0 2 Zones 57-99 & 2 NACs
3 0 3 Loop 1, Address M1 - M64
4 0 4 Loop 2, Address M1 - M64
5 0 5 Loop 1, Address M65 - M128
6 0 6 Loop 2, Address M65 - M128
707
8 0 8 Loop 1, Address D1 - D64
9 0 9 Loop 2, Address D1 - D64
10 1 0 Loop 1, Address D65 - D128
11 1 1 Loop 2, Address D65 - D128
12 1 2
20 2 0 8 System Points & Zones 1-56
21 2 1 Zones 57-99 & 2 NACs
22 2 2 Loop 1, Address M1 - M64
23 2 3 Loop 2, Address M1 - M64
24 2 4 Loop 1, Address M65 - M128
25 2 5 Loop 2, Address M65 - M128
26 2 6
27 2 7 Loop 1, Address D1 - D64
28 2 8 Loop 2, Address D1 - D64
29 2 9 Loop 1, Address D65 - D128
30 3 0 Loop 2, Address D65 - D128
31 3 1
Loop 1, Address M129 - M159 & Loop 2, Address M129 - M159
Loop 1, Address D129 - D159 & Loop 2, Address D129 - D159
Loop 1, Address M129 - M159 & Loop 2, Address M129 - M159
Loop 1, Address D129 - D159 & Loop 2, Address D129 - D159
Table 23 SW1 & SW2 Switch Settings
Note: If a UDACT-F is installed and selected in control panel programming, it will
automatically assign addresses 20 - 31 to the UDACT-F and disable the selection of these addresses.
52
LDM-32F PN 50055:C 03/20/01
Configuration Appendix C: MS-9600

Alarm Only Annunciation of Zones

The table below illustrates the configuration of the LDM Series modules to annunciate the alarm state of all 99 software zones (no zone troubles), and two NACs, with the first eight points of address ‘01’ dedicated to the MS-9600 system functions (see Figure 35 below).
LDM Module Address ‘01’
LDM-32F Sys Funct Z1 to Z8 Z9 to Z16 Z17 to Z24
LDM-E32F Z25 to Z32 Z33 to Z40 Z41 to Z48 Z49 to Z56
J5 J6 J7 J8
LDM Output Connectors
LDM Module Address ‘02’
LDM-32F Z57 to Z64 Z65 to Z72 Z73 to Z80 Z81 to Z88
LDM-E32F Z89 to Z96 Z97 to Z99 &
J5 J6 J7 J8
LDM Output Connectors
NAC1, NAC2
ON
Table 24 Alarm Only Setup

Alarm Only Annunciation of Zones - With 8-Point Shift

The table below illustrates the configuration of the LDM Series modules to annunciate the alarm state of all 99 software zones (no zone troubles), and two NACs, with the last eight points of address ‘01’ dedicated to the MS-9600 system functions (see Figure 35 below).
LDM Module Address ‘01’
LDM-32F Z1 to Z8 Z9 to Z16 Z17 to Z24 Z25 to Z32
LDM-E32F Z33 to Z40 Z41 to Z48 Z49 to Z56 Sys Funct
LDM Module Address ‘02’
LDM-32F Z57 to Z64 Z65 to Z72 Z73 to Z80 Z81 to Z88
LDM-E32F Z89 to Z96 Z97 to Z99 &
J5 J6 J7 J8
J5 J6 J7 J8
Table 25 Alarm Only Setup with Shift
System Alarm
Not Used
LDM Output Connectors
LDM Output Connectors
NAC1, NAC2
ON
System Alarm
Not Used
J5
Figure 35 System Functions to Output Connectors - 1
LDM-32F PN 50055:C 03/20/01
1234567
J8
8
25262728293031
32
LDM32F-J5J8.cdr
53
Appendix C: MS-9600 Configuration

Alarm/Trouble Annunciation of Zones

The table below (also see Figure 36 on page 55) illustrates the configuration of the LDM Series modules to annunciate the alarm and trouble states for all 99 software zones, and two NACs, with the first eight points of address ‘01’ dedicated to the MS-9600 system functions (see Figure 37 on page 55).
LDM Module Address ‘01’
LDM-32F System Functions Z1 to Z4 Z5 to Z8
1st LDM-E32F Z9 to Z12 Z13 to Z16 Z17 to Z20 Z21 to Z24
2nd LDM-E32F Z25 to Z28 Z29 to Z32 Z33 to Z36 Z37 to Z40
3rd LDM-E32F Z41 to Z44 Z45 to Z48 Z49 to Z52 Z53 to Z56
J5 J6 J7 J8
LDM Output Connectors
LDM Module Address ‘02’
LDM-32F Z57 to Z60 Z61 to Z64 Z65 to Z68 Z69 to Z72
1st LDM-E32F Z73 to Z76 Z77 to Z80 Z81 to Z84 Z85 to Z88
2nd LDM-E32F Z89 to Z92 Z93 to Z96 Z97 to Z99 &
J5 J6 J7 J8
LDM Output Connectors
NAC1, NAC2
ON
Table 26 Alarm/Trouble Setup

Alarm/Trouble Annunciation of Zones - 8-Point Shift

The table below (also see Figure 36 on page 55) illustrates the configuration of the LDM Series modules to annunciate the alarm and trouble states for all 99 software zones, and one NAC, with the last eight points of address ‘01’ dedicated to the MS-9600 system functions as listed below (see Figure 38 on page 55).
LDM Module Address ‘01’
LDM-32F Z1 to Z4 Z5 to Z8 Z9 to Z12 Z13 to Z16
1st LDM-E32F Z17 to Z20 Z21 to Z24 Z25 to Z28 Z29 to Z32
2nd LDM-E32F Z33 to Z36 Z37 to Z40 Z41 to Z44 Z45 to Z48
3rd LDM-E32F Z49 to Z52 Z53 to Z56 System Functions
J5 J6 J7 J8
LDM Output Connectors
54
LDM Module Address ‘02’
LDM-32F Z57 to Z60 Z61 to Z64 Z65 to Z68 Z69 to Z72
1st LDM-E32F Z73 to Z76 Z77 to Z80 Z81 to Z84 Z85 to Z88
2nd LDM-E32F Z89 to Z92 Z93 to Z96 Z97 to Z99 &
J5 J6 J7 J8
LDM Output Connectors
NAC1, NAC2
ON
Table 27 Alarm/Trouble Setup with Shift
LDM-32F PN 50055:C 03/20/01
Configuration Appendix C: MS-9600
The figure below is an example of the connections used when setting the LDM module for Alarm/Trouble mode.
Alarm - First 4 Zones or Points Trouble - First 4 Zones or Points
Alarm - Second 4 Zones or Points Trouble - Second 4 Zones or Points
Alarm - Third 4 Zones or Points Trouble - Third 4 Zones or Points
Alarm - Fourth 4 Zones or Points Trouble - Fourth 4 Zones or Points
J5 J6 J7 J8
1234567
8
9101112131415
16
171819202122232425262728293031
32
LCM32F-conn.cdr
Figure 36 Connections for Alarm/Trouble
The figure below illustrates pin usage of output connectors for system functions in alarm/trouble mode.
System Status Indicators
Program Mode (Yellow)
Signals Silenced (Yellow)
System Trouble (Yellow)
Power (Green)
System Alarm (Red)
Supervisory (Yellow) Walktest Battery Trouble (Yellow) AC Fail (Red)
J5 J6
1234567
Note: Pins not marked are not used
8
9101112131415
16
Figure 37 System Functions to Output Connectors - 1
The figure below illustrates pin usage of output connectors for system functions in alarm/trouble mode with 8-Point shift selected.
System Status Indicators
Program Mode (Yellow)
Signals Silenced (Yellow)
System Trouble (Yellow)
Power (Green)
System Alarm (Red)
Figure 38 System Functions to Output Connectors - 2
LDM-32F PN 50055:C 03/20/01
J7 J8
17181820212223
Note: Pins not marked are not used
24
25262728293031
Supervisory (Yellow) Walktest Battery Trouble (Yellow) AC Fail (Red)
32
LCM32F-J5J6.cdr
LCM32F-J7J8.cdr
55
Appendix C: MS-9600 Configuration

Alarm Only Annunciation of Points

The following table displays an example of setting up an LDM Series to annunciate the control panel’s SLC Loop #1, Modules M65 to M128 in Alarm Only mode.
By referring to Table 23 on page 52 it can be determined what address can be set to annunciate any other group of address points.
LDM Module Address ‘05’ (SLC Loop #1)
LDM-32F M65 to M72 M73 to M80 M81 to M88 M89 to M96
LDM-E32F M97 to M104 M105 to M112 M113 to M120 M121 to M128
J5 J6 J7 J8
LDM Output Connectors
Table 28 Alarm Only Setup

Alarm/Trouble Annunciation of Points

The following table displays an example of setting up an LDM Series to annunciate the control panel’s SLC Loop #1, Modules M65 to M128 in Alarm/Trouble mode. (See Figure 36 on page 55).
By referring to Table 23 on page 52 it can be determined what address can be set to annunciate any other group of address points.
LDM Module Address ‘05’ (SLC Loop #1)
LDM-32F M65 to M68 M69 to M72 M73 to M76 M77 to M80
1st LDM-E32F M81 to M84 M85 to M88 M89 to M92 M93 to M96
2nd LDM-E32F M97 to M100 M101 to M104 M105 to M108 M109 to M112
3rd LDM-E32F M113 to M116 M117 to M120 M121 to M124 M125 to M128
J5 J6 J7 J8
Table 29 Alarm/Trouble Setup
LDM Output Connectors
56
LDM-32F PN 50055:C 03/20/01
Numerics
120 volts AC 24 VDC 24 VDC power 24 volt output 24 volts regulated power 5 VDC 5 volt output 5 volts 5 volts regulated power 8-Point Shift 8-Point shift
20
31, 41, 51
9, 19
23
12
31
23
24
13
12, 13, 37, 40, 48
26, 39, 44, 46, 55
A
Acknowledge acknowledge/lamp test switch address address points Address Switches Addressable Pull Stations Alarm
11
alarm alarm and trouble states
12, 29, 33, 41, 51
29, 42
56
25, 35, 42, 52
41, 51
56
43, 47, 48,
54
alarm condition Alarm Current Total alarm drivers Alarm Only Alarm Only mode alarm points alarm state Alarm/Trouble Alarm/Trouble annunciation Alarm/Trouble mode
27
32
24
26
13, 35, 56
23
42, 45, 46, 53
26
13, 24, 39,
44, 55, 56
10, 37
alarms alarms and troubles annunciation capabilities annunciator functions annunciators
38
11
13
29
B
9
battery BCD switches
13
24, 26
49
Index
12, 31
bipolar
C
CAB-A3F and CAB-B3F
21
cabinet cabinets cable cable kit calculation table calculations change in status CHS-4L chassis color convention communication failure communications conduit configuration connections Control Modules Control Switch disable control switch inputs control switches
33, 40
Copper Wire CPU function switches CPU switch functions current limit current rating custom backbox
D
daisy chain Darlington Detector Detectors detectors device failure or restoral DIP switch display Drill driver outputs drivers duplicate annunciation
17
20
14, 15, 23, 24
21, 24
52
41, 51
12, 41, 51
24
Index
17
32
9
20
10, 17
27
19
10, 13
37, 38
39, 44, 55
41, 51
13
11
10, 12, 15, 24, 29,
21
12
40
12
13
10
14
12, 31
41, 51
45, 46, 47, 48
20
10, 12, 25
10, 11, 12, 13
29
LDM-32F PN 50055:C 03/20/01
57
Index
E
earth fault earth ground earth ground terminal EIA-485 bus
27
14, 17, 21
19
9, 14, 20, 29, 33, 34,
41, 51
electrical supervision
22
ELR enclosure example of setting up expander module expander ribbon cable Expanders external control switches external power source external resistor
21, 24
26
49
56
9, 11, 12, 13, 18
11, 18
12, 41, 51
12
F
first eight points
37, 38, 42, 43, 45,
47, 53, 54
Flash functions Flash Inhibit full-function annunciators Function settings functions
12
13, 26, 32
13
13
G
general system status general system trouble graphic annunciator
33
27
9, 12, 13, 17,
27
23
green Grounding Cable grounding purposes group of address points
17, 19
20
56
I
I/O module I/O point impedance indicating device circuit initiating circuits initiating device circuit intermediate display
40
33, 41, 51
20
33
27
29
J
32
J1
10
29
27
14, 18
J2
14, 18
J3
15
J4 J5, J6, J7 and J8
14, 20
jumper
11, 13
K
key-lock switch key-lock type knockout
15
24
17
L
lamp driver output lamp test lamp test switch lamps last eight points
29
10, 11, 12, 26, 27
31
37, 38, 42, 43, 46,
48, 53, 54
27, 35
latch LDM-CBL24 LDM-CBL48
23, 26, 27, 31, 38
LEDs local power sources low battery
14 14
27
M
manually activate mapped master module Maximum Current Maximum Voltage message mode mode of operation Module Module Failure Modules modules momentary type Monitor Modules MPS-24AF MPS-24BF multiple modules multiple shields multiple wiring
12
41
11
52
56 12, 45, 46, 47, 48
33
9, 12, 14
33
12, 24
41, 51 34 34
19
21
22
33, 35, 41, 51
14
31
31
26
58
LDM-32F PN 50055:C 03/20/01
N
42, 53, 54
NACs NEC Article 250 non-resettable normally-closed notification appliance circuits notification circuits
17
14
20
27
33
O
On Line on line LED open circuit Open Collector open collector driver output operation optional modules output connectors
27
10
14
31
12
26
36
37, 39, 42, 44,
55
output points output relays
23
33
P
10, 27
piezo Piezo disable pin usage plug in modules
13, 23
point point assignments point control switches points
13, 26, 32
39, 44, 55
33
36
26
9, 24, 37, 38, 41, 42, 45,
46, 47, 48, 51
power requirements power run power sources Power Supervision Relay power supply power-limited Power-limited Wiring Requirements
34
32
20
34
9, 14
14, 19, 20
17
primary power programmed
32
33, 41, 42, 51
R
Receive Only Receive/Transmit
23
red regulated
LDM-32F PN 50055:C 03/20/01
13, 26
13, 49
14
relay circuits remote control switches remote location remote switch functions removable terminal block
12, 29
Reset resistance resistor revision level ribbon cable rotary switches
27
9, 12
29
10
20
22, 23
34
12, 18
13, 52
S
secondary power security key switch
24
setup
21
shield short circuit Signal Silence
12, 29
Silence SLC Loop slide switch software zone software zones
32
12, 24
20
33, 41, 51
51, 56
24
27
26, 41, 42, 43, 51,
53, 54
speaker circuits Standby Total
9
status status changes status indicators supervised Supervised circuit supervised input supervising power sources supervision
11, 25, 35, 42, 52
SW1
11, 25, 35, 42, 52
SW2
10, 12, 25
SW3
10, 11, 12, 24, 26
SW4
26
switch Switch Inhibit system address system common system function LEDs system functions
27
32
27
11
19
31
14
29
26
13
21
42
39, 43, 44, 45,
46, 47, 48, 53, 54, 55
Index
14
20
59
Index
system points System Reset system status System Trouble system trouble message
29
33, 41, 51
9, 37, 38, 41, 51
33
41, 51
T
telephone circuits
33, 41, 51
Testing time control circuits
35
track transient protection
11
trouble trouble condition trouble drivers trouble indication trouble indicators trouble points trouble signal troubles T-tapped twisted shielded pair cable
10
9, 20
27
27
17
27
24
12
11 23 14, 20
U
UDACT-F
52
20
W
Wire Specifications wire-nut wiring wiring distance
21
49
21
9, 20
Y
23, 35
yellow
Z
13, 27
zone
9, 13, 24, 26, 37, 38, 42
zones
60
LDM-32F PN 50055:C 03/20/01
LDM-32F PN 50055:C 03/20/01
61
62
LDM-32F PN 50055:C 03/20/01
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com
Loading...