An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control with
remote notification capability–can provide early warning
of a developing fire. Such a system, however, does not
assure protection against property damage or loss of life
resulting from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of
the National Fire Protection Association Standard 72
(NFPA 72), manufacturer's recommendations, State and
local codes, and the recommendations contained in the
Guide for Proper Use of System Smoke Detectors, which
is made available at no charge to all installing dealers.
A study by the Federal Emergency Management Agency
(an agency of the United States government) indicated
that smoke detectors may not go off in as many as 35%
of all fires. While fire alarm systems are designed to
provide early warning against fire, they do not guarantee
warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply
may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke
cannot reach the detectors such as in chimneys, in or
behind walls, on roofs, or on the other side of closed
doors. Smoke detectors also may not sense a fire on
another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or
basement fire.
Particles of combustion or "smoke" from a developing
fire may not reach the sensing chambers of smoke
detectors because:
• Barriers such as closed or partially closed doors,
walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors
by air outlets.
• Smoke detectors may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to
alarm smoke detectors. Smoke detectors are designed
to alarm at various levels of smoke density. If such
density levels are not created by a developing fire at the
location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering
fires. Because fires develop in different ways and are
often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may
not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide
adequate warning of fires caused by arson, children
playing with matches (especially in bedrooms), smoking
in bed, and violent explosions (caused by escaping gas,
improper storage of flammable materials, etc.).
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
detectors are designed to protect property, not life.
IMPORTANT!
the same room as the control panel and in rooms used
by the system for the connection of alarm transmission
Smoke detectors must be installed in
wiring, communications, signaling, and/or power.
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal. It is the
property owner's responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the
requirements of Chapter 7 of NFPA 72 shall be followed.
Environments with large amounts of dust, dirt or high air
velocity require more frequent maintenance. A maintenance agreement should be arranged through the local
manufacturer's representative. Maintenance should be
scheduled monthly or as required by National and/or
local fire codes and should be performed by authorized
professional fire alarm installers only. Adequate written
records of all inspections should be kept.
Heat
If
LimWarSm.p65 01/10/2000
Installation Precautions
WARNING -
connected to the fire alarm control panel.
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is
read and understood.
CAUTION -
Changes.
product must be tested in accordance with NFPA 72
Chapter 7 after any programming operation or change in
site-specific software. Reacceptance testing is required
after any change, addition or deletion of system components, or after any modification, repair or adjustment to
system hardware or wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be
100% tested. In addition, to ensure that other operations
are not inadvertently affected, at least 10% of initiating
devices that are not directly affected by the change, up
to a maximum of 50 devices, must also be tested and
proper system operation verified.
This system meets NFPA requirements for operation
at 0-49° C/32-120° F
RH (non-condensing) at 30°
useful life of the system's standby batteries and the
electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore,
it is recommended that this system and all peripherals
be installed in an environment with a nominal room
temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Several different sources of power can be
Disconnect all
System Reacceptance Test after Software
To ensure proper system operation, this
and at a relative humidity of 85%
C/86° F. However, the
Adherence to the following will aid in problem-free
installation with long-term reliability:
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected
to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended,
due to an increased susceptibility to nearby lightning
Consult with the Technical Services Department
strikes.
if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit
board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains staticsensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that
static charges are removed from the body. Use staticsuppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must
be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not installed and used in accordance with the instruction
manual, may cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against
such interference when operated in a commercial
environment. Operation of this equipment in a
residential area is likely to cause interference, in
which case the user will be required to correct the
interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the
Class A limits for radiation noise emissions from
digital apparatus set out in the Radio Interference Regulations of the Canadian Department
of Communications.
Le present appareil numerique n'emet pas de
bruits radioelectriques depassant les limites
applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le
brouillage radioelectrique edicte par le
ministere des Communications du Canada.
Alarm Only Annunciation of Zones.................................................53
Alarm Only Annunciation of Zones - With 8-Point Shift................ 53
Alarm/Trouble Annunciation of Zones............................................54
Alarm/Trouble Annunciation of Zones - With 8-Point Shift ........... 54
Alarm Only Annunciation of Points.................................................56
Alarm/Trouble Annunciation of Points............................................56
This page intentionally left blank
8
LDM-32F PN 50055:C 03/20/01
1. Introduction
General
The LDM Series Lamp Driver Modules, which consist of the LDM-32F master
and LDM-E32F expander modules, are used to provide an interface to a custom
graphic annunciator. The master module provides power and control for a
maximum of three expander modules. Both these modules have output
connectors which are used to drive lamps or LEDs and input connectors which
are used for remote switch functions.
The Lamp Driver Modules may be connected to an MS-9200, MS-9600 or
Sensiscan 2000 fire alarm control panel (FACP) to provide remote
annunciation of the following:
• General system status:
General alarmMunicipal tie status
General troubleSystem silence
General supervisoryAlarm relay status
NAC output status
• Alarm and trouble status of zones or individual points
• Alarm only status of zones or individual points
The modules also interface to remote control switches which may be used to
provide:
•System reset
•System silence
• System acknowledge
• Temporary activation of NAC outputs
• Alarm relay activation
• Other control functions
The modules interface to the host fire alarm control panel via an EIA-485
communications bus circuit. A maximum of 32 LDM-32Fs may be connected
to the power-limited EIA-485 bus, but if other types of devices are also
connected to the EIA-485 bus, the maximum number of LDM-32Fs must be
reduced by the total of such devices. The EIA-485 wiring distance must not
exceed 6000 feet and cannot be T-tapped. Multiple LDM-32Fs may be used
to annunciate duplicate information.
Power to the LDM-32Fs is typically provided by the host FACP and must be
power-limited, regulated 24 VDC. An external UL listed battery backed power
supply may also be used.
Note: Careful consideration must be given to system battery calculations when power for
the LDM modules and lamps or LEDs is provided by the host FACP. Refer to the
specifications in the appropriate FACP technical manual when making these calculations.
LDM-32F PN 50055:C 03/20/01
9
1. IntroductionFeatures
Features
LDM-32F
The Lamp Driver Module LDM-32F has 32 alarm lamp/LED driver outputs
which sink current to system common (–) on activation. A single positive (+)
voltage is required to supply total operating power for all lamps or LEDs when
all drivers are activated. The LDM-32F provides a separate driver for system
trouble and inputs for a local lamp test switch. A maximum of 16 external
control switches may be wired to the LDM-32F. DIP switch SW3 is used to
enable or disable the onboard piezo, enable remote switch functions, select a
flashing LED function for new alarms and troubles, and other functions.
Switch SW4 is used to configure the module to annunciate 32 alarms or 16
troubles. A green
ON LINE
with the host FACP. One LDM-32F supports up to 3 LDM-E32F modules. The
LDM-32F is supplied with 4 standoffs and screws for mounting to a CHS-4L
chassis or custom backbox.
LED flashes to indicate ongoing communications
Output Connectors
for Wiring to LEDs
Lamp Power
(+5 VDC)
Security Key
Switch Terminal
Control Switch
Terminal
Address
Switches
Programming
DIP Switch
EIA-485
Terminal
24 VDC
Power
Terminal
J4
KEYSWITCH
SWITCH
MATRIX
J1
SW1
SW2
SW3
SW4
J5
4
3
2
1
7
6
5
4
3
2
1
J6J7J8
TB2
TB1
Figure 1 LDM-32F
Not Used
J11
LAMP
POWER
J10
J9
Lamp Power
(+24 VDC)
System Trouble
Ribbon Cable
Connection to
LDM-E32F
J2
Alarm or
Alarm/Trouble
Slide Switch
LDM-32F.cdr
ON LINE
Indicates EIA-485
Communication
Active
10
LDM-32F PN 50055:C 03/20/01
Features1. Introduction
LDM-E32F
Each LDM-E32F expander module provides 32 additional lamp/LED driver
outputs from J5, J6, J7 and J8. The expander module has a slide switch SW4
for selecting alarm or alarm and trouble annunciation and an input for a local
lamp test switch. In alarm mode, use only one LDM-32F and one LDM-E32F
for a maximum of 56 alarm indicators and 8 system status indicators. In alarm/
trouble mode, use one LDM-32F and three LDM-E32Fs for a maximum of 56
alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional
control switch inputs. Multiple sets of LDM-32Fs with LDM-E32F expanders
increase the system annunciation capabilities beyond 56 zones or points. This
is possible by various settings of address switches SW1 and SW2 on the LDM32F (refer to Appendices). Each LDM-E32F is supplied with a 26-conductor
expander ribbon cable, 4 standoffs and 4 screws.
Output Connectors
for Wiring to LEDs
Security Key
Switch Terminal
Control Switch
Te rm i n al
Alarm or
Alarm/Trouble
Slide Switch
Not Used
Ribbon Cable
Connections to
Next LDM-E32F
Ribbon Cable
Connections from
LDM-32F or
Previous LDM-E32F
LDM-E32F.cdr
Figure 2 LDM-E32F
LDM-32F PN 50055:C 03/20/01
11
1. IntroductionFeatures
Connectors
J1 - Switch Matrix
Up to 16 optional external control switches and a local lamp test switch may
be attached to the LDM-32F and LDM-E32F via J1 as shown in Figure 16 on
page 24. In the Sensiscan 2000, the control switches may be mapped to the CPU
function switches and all
9600, the switches may only be used for remote Acknowledge, Reset, Drill and
Silence. External switches must be momentary type.
J2 - Ribbon Cable Connection to J3
A single 26-conductor ribbon cable may be connected from J2 on the LDM32F or LDM-E32F (see Figure 6 on page 18) to J3 on adjacent LDM-E32Fs.
The ribbon cable carries power, ground and signaling from the master module
to up to three expander modules. The preformed cables are supplied in fixed
lengths of 24 and 48 inches.
J3 - Ribbon Cable Connection from J2
This connector supports a single 26-conductor ribbon cable from J2 of the
previous LDM-32F or LDM-E32F. Refer to Figure 6 on page 18.
J4 - Key Switch Input
This two pin connector is provided as an input on LDM-32F and LDM-E32F
modules for an external security key switch. Key switch contacts must be
Normally Closed. The key switch prevents unauthorized use of remote control
switches wired to J1.
J5, J6, J7 and J8 - Lamp/LED Driver Outputs
input and output modules. In the MS-9200 and MS-
Each connector provides 8 driver outputs for a total of 32 drivers on each LDM32F and LDM-E32F. Each driver is rated for a maximum of 30 volts and a
current of 100 mA. Each bipolar Darlington open collector driver output must
be current limited by an external resistor. 8-Point Shift and Flash functions are
selectable by DIP switch SW3 (refer to "SW3 - Function DIP Switch" on page
13). Lamp/LEDs may function in ‘alarm only’ mode or ‘alarm/trouble’ mode
as selected by switch SW4. Use the charts and examples shown in Appendices
for additional information.
J9 - 24 VDC Lamp Power/System Trouble
Connector J9 is located only on the LDM-32F. J9 pin 1 provides 24 volts
regulated power to all lamps/LEDs used in a custom graphic annunciator. The
current limit of J9 pin 1 is dependent upon the current limits of the external
power source being used. J9 pin 3 is a driver output for system trouble
indication only. J9 pin 2 connects to system common.
J10 - Relay Expander
Not used on the Sensiscan 2000, MS-9200 and MS-9600.
12
LDM-32F PN 50055:C 03/20/01
Features1. Introduction
J11 - 5 VDC Lamp Power
This connector is located only on the LDM-32F. J11 pin 1 provides 5 volts
regulated power to all lamps/LEDs used in a custom graphic annunciator. The
maximum current available from this output is 300 mA. This current is
sufficient to power the maximum number of LEDs available with one LDM32F and three LDM-E32Fs (from J5, J6, J7, J8 and one system trouble LED)
provided the
current rating per LED is 2 mA.
Switches
SW1 and SW2 - Address Switches
Two rotary BCD switches, located only on the LDM-32F, are used to set the
LDM Series system address. Switch SW1 represents the ‘ones’ position and
switch SW2 represents the ‘tens’ position of the address setting. In system
configurations of 56 zones or less, the switches must be set to address 01 for
all LDMs in the system. For configurations larger than 56 zones, multiple sets
of LDMs are required with sequential addresses, the first LDM starting at
address 01. Each incremental setting adds 64 zones/points to the system.
For example, an MS-9200 system requiring annunciation of alarms and
troubles for all 198 points would require four sets of LDMs with addresses 01,
02, 03 and 04. The MS-9600 is an exception (refer to "Appendix C: MS-9600"
on page 51 for information).
SW3 - Function DIP Switch
SW3, which is located only on the LDM-32F, is used to set the annunciator
functions. Function settings include:
• Number of expanders connected
• 8-Point Shift enabled
• Receive Only communications to host FACP
• Receive/Transmit communications to host FACP
• Control Switch disable
• Piezo disable
• Flash Inhibit
Refer to "Function DIP Switch - SW3" on page 25 for additional information.
SW4 - Alarm/Trouble Mode Switch
The Alarm/Trouble mode switch is installed on the LDM-32F and LDM-E32F.
The switch setting on each
expander module must match the switch setting of
the associated LDM-32F. ‘Alarm Only’ mode causes the driver outputs to turn
on only for alarm conditions per associated zone or point at the host FACP.
‘Alarm/Trouble’ mode causes the driver outputs to turn on for both alarm and
trouble conditions per associated zone or point at the host FACP. Since this
switch affects the assignments of connectors J5, J6, J7 and J8, make certain to
review the appendices in this manual for additional information on wiring to
the lamp/LED drivers.
LDM-32F PN 50055:C 03/20/01
13
1. IntroductionFeatures
Terminal Blocks
TB1 - 24 VDC Power, Earth Ground and Supervision
Removable terminal block TB1 appears only on the LDM-32F. 24 volts powerlimited, regulated, non-resettable power from the host FACP or a compatible
UL listed battery backed power supply must be connected to TB1(+) and TB1-
COMMON OUT
COMMON IN
(-) may be used to daisy chain the 24 volts to other LDMs or
devices. Earth ground must be connected to TB1and TB1-
N.C. SUPERVISION INPUT
(-). Terminals TB1-
provide a supervised input which may be
POWER OUT
EARTH
(+) and TB1-
. Terminals TB1-6
POWER IN
used to supervise local power sources or other devices. A trouble signal is
transmitted to the host FACP upon an open circuit across these terminals. The
input must be power-limited. If these terminals are not used, a jumper must
be installed.
TB2- EIA-485 In/Out
Removable terminal block TB2 appears only on the LDM-32F. All LDM-32Fs
must connect to the EIA-485 communications bus circuit for proper operation.
The EIA-485 bus carries commands and data sent between the host FACP and
the LDMs. The input must be power-limited.
Cables
Expander Ribbon Cable
The Expander Ribbon Cable (PN 75120) is supplied with the LDM-E32F to
allow for connection to the LDM-32F master module. The cable connects
between J2 of the LDM-32F or LDM-E32F and J3 of the next LDM-E32F.
The LDM-CBL24 and LDM-CBL48
Cable sets for connecting LDM-32F and LDM-E32F connectors to lamps/
LEDs, switches, etc., are provided through the optional LDM-CBL24 (24"
long) and LDM-CBL48 (48" long) cabling kits. Each cable has a plug on one
end for connection to the LDM modules.
Each LDM-CBL24 cable kit includes:
• (4) P/N 75116, 24" cable consisting of 8 stranded, multicolored
conductors. Cables connect to J5, J6, J7 and J8.
• (1) P/N 75122, 24" cable consisting of 10 stranded, multicolored
conductors. Connects to J1, optional control switches.
• (1) P/N 75117, 24" cable consisting of 2 stranded, single color
conductors. Connects to
J1, Lamp Test Switch.
• (1) P/N 75118, 24" cable consisting of 3 stranded, multicolored
conductors. Connects to J9 or J11, Lamp Power.
14
LDM-32F PN 50055:C 03/20/01
Related Documentation1. Introduction
Each LDM-CBL48 cable kit includes:
• (4) P/N 75147, 48" cable consisting of 8 stranded, multicolored
conductors. Cables connect to J5, J6, J7 and J8.
• (1) P/N 75150, 48" cable consisting of 10 stranded, multicolored
conductors. Connects to J1, optional control switches.
• (1) P/N 75148, 48" cable consisting of 2 stranded, single color
conductors. Connects to J1, Lamp Test Switch
.
• (1) P/N 75149, 48" cable consisting of 3 stranded, multicolored
conductors. Connects to J9 or J11, Lamp Power.
Key-lock Control Switch Security
A UL listed key-lock switch wired to J4 on the LDM-32F should be used to
provide access security for all control switches wired to that set of LDM
modules.
Note: Control switches will not function when the key-lock switch is in its closed position.
J4
2
Key Switch
Figure 3 Key-lock Switch Wiring Diagram
LDM-32F
1
LDM32F-keysw.cdr
Related Documentation
Further details about products referenced in this document can be found in the
manuals for the particular fire alarm control panel and components.
Product
MS-9200 Fire Alarm Control Panel Instruction Manual51003
MS-9600 Fire Alarm Control Panel Instruction Manual51335
Sensiscan 2000 Fire Alarm Control Panel Instruction Manual15017
CAB-3F Series Cabinets Installation Document15391
LDM-32F PN 50055:C 03/20/01
Part
Number
15
1. IntroductionRelated Documentation
NOTES
16
LDM-32F PN 50055:C 03/20/01
2. Installation
External Cabinets
The CAB-A3F and the CAB-B3F are UL listed cabinets suitable for use in
graphic annunciator applications. For size and dimensions, refer to the CAB3F Series Installation Document.
Select and remove the appropriate knockout(s) on the cabinet.
Securely mount the cabinet.
Ground the cabinet to a solid electrical ground per NEC Article 250.
Pull all wiring into the cabinet. (Refer to the appropriate FACP manual for UL
Power-limited Wiring Requirements.)
Note: Other cabinets such as those provided by custom graphic annunciator
manufacturers may be used provided they meet UL requirements as UL listed secured
enclosures.
CHS-4L Chassis
The CHS-4L chassis will support one LDM-32F module and up to three LDME32F expander modules. The chassis is mounted inside the CAB-A3F or the
CAB-B3F cabinet.
Mount the CHS-4L Chassis to a cabinet and secure with the hardware provided.
The Grounding Cable must be connected to the chassis mounting stud for
connection to the annunciator's earth ground terminal for proper operation as
well as to aid in transient protection. For each LDM module to be installed on
the chassis, connect two female-to-female standoffs (provided) to the upper
mounting studs on the chassis.
LDM-32F PN 50055:C 03/20/01
LDM32-chs4l.cdr
Figure 4 CHS-4L Mounting
17
2. InstallationCHS-4L Chassis
Slip the bottom edge of the module or expander board into the slot on the chassis
and move the module toward the standoffs. Secure the board to the standoffs
with the screws provided. Repeat for installation of additional modules or
expanders.
Ldminchs.cdr
Figure 5 Installing LDM Modules in CHS-4L
Connect an expander ribbon cable (P/N 75120) from the LDM-32F connector
J2 to J3 of the first LDM-E32F expander module. If multiple LDM-E32F
modules are to be used, connect additional cables from J2 to J3 as shown below.
One LDM-32F may support a maximum of three LDM-E32F modules.
18
Expander Ribbon Cables
LDM-32F LDM-E32F LDM-E32F LDM-E32F
Ldmincab.cdr
Figure 6 LDMs Mounted in UL Listed Cabinet
LDM-32F PN 50055:C 03/20/01
Wiring the Power Terminal Block2. Installation
Wiring the Power Terminal Block
24 VDC Power and Earth Ground
24 VDC power supplied to the LDM must be power-limited. This power is
inherently supervised (loss of power also results in a communication failure at
the control panel).
• Limit the total wire resistance to 10 ohms.
• Connect the Grounding Cable from the chassis to the earth ground
terminal of TB1 (
• Connect 24 VDC power to the
terminals of TB1.
24 VDC
Power
Grounding Cable
Figure 7 24 VDC Power Terminals - TB1
EARTH
).
POWER IN
TB1
(+) and
N.C. Supervision
Inputs
Common In (–)
Common Out (–)
Power In (+24 VDC)
Power Out (+24 VDC)
Earth
COMMON IN
(–)
LDM32F-TB1.cdr
Wiring of multiple LDM-32F modules.
Host FACP or Remote
Power Supply
– 24 VDC
+ 24 VDC
Figure 8 Multiple Module Wiring - 24 VDC
LDM-32F PN 50055:C 03/20/01
First LDM-32F -- -- -- -- -- -- -- Last LDM-32F
TB1TB1
LDM32F-power.cdr
19
2. InstallationWiring the EIA-485 Terminal Block
Supervision Input
The Supervision Input, which requires a normally-closed condition, can be
used for supervising power sources or ot her devices. It must be power-limited.
If employed, a change in status will be transmitted to the host control panel in
the event of device failure or restoral.
If not used, a jumper must be installed across these terminals on TB1. A trouble
signal will be registered by the control panel if a short circuit does not exist
across terminals 6 & 7.
Device to be
Supervised
Supervision
Inputs
(5 VDC @
0.5 mA)
Normally Closed
Trouble Contacts
Jumper
TB1
Figure 9 Wiring Supervision Terminals
TB1
Wiring the EIA-485 Terminal Block
A maximum of 32 LDM-32Fs may be connected to the EIA-485 bus, but if
other types of devices are also connected to this bus, the maximum number
of LDM-32Fs must be reduced by the total of such devices. Total annunciation
and switch capability depends upon the number of expander modules used.
Communications between the Fire Alarm Control Panel and the LDM-32F is
accomplished over a two-wire EIA-485 serial communications bus which must
be power-limited. Communications between the host FACP and LDMs is
supervised by the fire alarm control panel.
Wiring Specifications
• The EIA-485 circuit cannot be T-tapped; it must be wired in a
continuous fashion from the control panel to the LDMs.
• The maximum wiring distance between the panel and LDMs is 6000
feet.
• The wiring must be a 18 AWG to 14 AWG twisted shielded pair cable
having a characteristic impedance of 120 ohms, +/- 20%.
• Limit the total wire resistance to 100 ohms.
• Do not run cable adjacent to, or in the same conduit as, 120 volts AC
service, noisy electrical circuits that are powering mechanical bells or
horns, audio circuits above 25 V
power circuits.
Note: Never use the shield for grounding purposes. Terminate the EIA-485 shield at the
Fire Alarm Control Panel only.
20
, motor control circuits, or SCR
RMS
LDM-32F PN 50055:C 03/20/01
LDM32F-super.cdr
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.