Fire-Lite LDM-32F User Manual

PN 50055:C0 ECN 01-155
Lamp Driver Module
LDM-32F
Instruction Manual
Document 50055 03/20/2001 Rev:
C
This page intentionally left blank
4
LDM-32F PN 50055:C 03/20/01
Table of Contents
Table of Contents
1. Introduction
General................................................................................................... 9
Features ............................................................................................... 10
LDM-32F..........................................................................................10
LDM-E32F .......................................................................................11
Connectors........................................................................................ 12
J1 - Switch Matrix........................................................................12
J2 - Ribbon Cable Connection to J3.............................................12
J3 - Ribbon Cable Connection from J2........................................12
J4 - Key Switch Input...................................................................12
J5, J6, J7 and J8 - Lamp/LED Driver Outputs ............................. 12
J9 - 24 VDC Lamp Power/System Trouble .................................12
J10 - Relay Expander ...................................................................12
J11 - 5 VDC Lamp Power............................................................13
Switches............................................................................................13
SW1 and SW2 - Address Switches..............................................13
SW3 - Function DIP Switch.........................................................13
SW4 - Alarm/Trouble Mode Switch............................................13
Terminal Blocks ...............................................................................14
TB1 - 24 VDC Power, Earth Ground and Supervision................ 14
TB2- EIA-485 In/Out...................................................................14
Cables ...............................................................................................14
Expander Ribbon Cable ............................................................... 14
The LDM-CBL24 and LDM-CBL48...........................................14
Key-lock Control Switch Security ...............................................15
Related Documentation......................................................................15
2. Installation
External Cabinets ............................................................................... 17
CHS-4L Chassis ..................................................................................17
Wiring the Power Terminal Block ....................................................19
24 VDC Power and Earth Ground....................................................19
Supervision Input ............................................................................. 20
Wiring the EIA-485 Terminal Block.................................................20
Wiring Specifications....................................................................... 20
Wire Chart ..................................................................................21
EIA-485 Shield in Conduit ..........................................................21
EIA-485 Shield Not in Conduit ...................................................21
EIA-485 - TB2 Terminals ................................................................22
Wiring for Lamp/LED .......................................................................23
Wiring the Control Switch.................................................................24
Table of Contents
Configuring the LDMs .......................................................................25
Address Switches - SW1 and SW2...................................................25
Function DIP Switch - SW3 .............................................................25
Switch Settings.............................................................................26
Mode Switch - SW4 .........................................................................26
3. Operation
Lamp Test/Acknowledge ....................................................................27
On Line LED .......................................................................................27
Graphic Annunciator Lamps/LEDs..................................................27
4. LDM Communications
Receive Only LDM-32Fs ....................................................................29
Receive/Transmit LDM-32F ..............................................................29
5. Electrical Ratings and Current Calculations
Lamp Driver Electrical Ratings ........................................................31
Supervision of LDM points ................................................................31
Calculating Standby and Alarm Currents .......................................32
Appendix A: Sensiscan 2000
Capabilities ..........................................................................................33
Trouble Indication ..............................................................................33
Programming and Testing the LDM-32F.........................................33
Power Supply Connection ..................................................................34
MPS-24AF Main Power Supply.......................................................34
MPS-24BF Main Power Supply.......................................................34
EIA-485 Connection ...........................................................................34
Lamp/LED Driver Operation ............................................................35
Alarm Only Operation ......................................................................37
Alarm Only Operation with 8-Point Shift ........................................37
Alarm/Trouble Operation .................................................................38
Alarm/Trouble Operation with 8-Point Shift....................................38
Control Switch Operation ..................................................................40
Appendix B: MS-9200
Capabilities ..........................................................................................41
Trouble Indication ..............................................................................41
Programming and Testing the LDM-32F.........................................41
Power and EIA-485 Connections.......................................................41
Configuration ......................................................................................42
Alarm Only Annunciation of Zones.................................................42
Alarm Only Annunciation of Zones - With 8-Point Shift................42
Alarm/Trouble Annunciation of Zones ............................................43
Alarm/Trouble Annunciation of Zones - With 8-Point Shift ...........43
Alarm Only Annunciation of Points.................................................45
Detectors.......................................................................................45
Modules........................................................................................45
Table of Contents
Alarm Only Annunciation of Points - With 8-Point shift ................46
Detectors ......................................................................................46
Modules........................................................................................46
Alarm /Trouble Annunciation of Points........................................... 47
Detectors ......................................................................................47
Modules........................................................................................47
Alarm /Trouble Annunciation of Points - With 8-Point Shift.......... 48
Detectors ......................................................................................48
Modules........................................................................................48
Configuration Diagram.....................................................................49
Appendix C: MS-9600
Capabilities..........................................................................................51
Trouble Indication..............................................................................51
Programming and Testing the LDM-32F.........................................51
Power and EIA-485 Connections ......................................................51
Configuration ......................................................................................52
Setting Rotary Switches ...................................................................52
Alarm Only Annunciation of Zones.................................................53
Alarm Only Annunciation of Zones - With 8-Point Shift................ 53
Alarm/Trouble Annunciation of Zones............................................54
Alarm/Trouble Annunciation of Zones - With 8-Point Shift ........... 54
Alarm Only Annunciation of Points.................................................56
Alarm/Trouble Annunciation of Points............................................56
This page intentionally left blank
8
LDM-32F PN 50055:C 03/20/01

1. Introduction

General

The LDM Series Lamp Driver Modules, which consist of the LDM-32F master and LDM-E32F expander modules, are used to provide an interface to a custom graphic annunciator. The master module provides power and control for a maximum of three expander modules. Both these modules have output connectors which are used to drive lamps or LEDs and input connectors which are used for remote switch functions.
The Lamp Driver Modules may be connected to an MS-9200, MS-9600 or Sensiscan 2000 fire alarm control panel (FACP) to provide remote annunciation of the following:
• General system status:
General alarm Municipal tie status
General trouble System silence
General supervisory Alarm relay status
NAC output status
• Alarm and trouble status of zones or individual points
• Alarm only status of zones or individual points
The modules also interface to remote control switches which may be used to provide:
•System reset
•System silence
• System acknowledge
• Temporary activation of NAC outputs
• Alarm relay activation
• Other control functions
The modules interface to the host fire alarm control panel via an EIA-485 communications bus circuit. A maximum of 32 LDM-32Fs may be connected to the power-limited EIA-485 bus, but if other types of devices are also connected to the EIA-485 bus, the maximum number of LDM-32Fs must be reduced by the total of such devices. The EIA-485 wiring distance must not exceed 6000 feet and cannot be T-tapped. Multiple LDM-32Fs may be used to annunciate duplicate information.
Power to the LDM-32Fs is typically provided by the host FACP and must be power-limited, regulated 24 VDC. An external UL listed battery backed power supply may also be used.
Note: Careful consideration must be given to system battery calculations when power for the LDM modules and lamps or LEDs is provided by the host FACP. Refer to the specifications in the appropriate FACP technical manual when making these calculations.
LDM-32F PN 50055:C 03/20/01
9
1. Introduction Features

Features

LDM-32F

The Lamp Driver Module LDM-32F has 32 alarm lamp/LED driver outputs which sink current to system common (–) on activation. A single positive (+) voltage is required to supply total operating power for all lamps or LEDs when all drivers are activated. The LDM-32F provides a separate driver for system trouble and inputs for a local lamp test switch. A maximum of 16 external control switches may be wired to the LDM-32F. DIP switch SW3 is used to enable or disable the onboard piezo, enable remote switch functions, select a flashing LED function for new alarms and troubles, and other functions. Switch SW4 is used to configure the module to annunciate 32 alarms or 16 troubles. A green
ON LINE
with the host FACP. One LDM-32F supports up to 3 LDM-E32F modules. The LDM-32F is supplied with 4 standoffs and screws for mounting to a CHS-4L chassis or custom backbox.
LED flashes to indicate ongoing communications
Output Connectors for Wiring to LEDs
Lamp Power (+5 VDC)
Security Key
Switch Terminal
Control Switch
Terminal
Address
Switches
Programming
DIP Switch
EIA-485
Terminal
24 VDC
Power
Terminal
J4
KEYSWITCH
SWITCH MATRIX
J1
SW1
SW2
SW3
SW4
J5
4 3 2 1
7 6 5 4 3 2 1
J6 J7 J8
TB2
TB1
Figure 1 LDM-32F
Not Used
J11
LAMP POWER
J10
J9
Lamp Power (+24 VDC)
System Trouble
Ribbon Cable Connection to LDM-E32F
J2
Alarm or Alarm/Trouble Slide Switch
LDM-32F.cdr
ON LINE
Indicates EIA-485 Communication Active
10
LDM-32F PN 50055:C 03/20/01
Features 1. Introduction

LDM-E32F

Each LDM-E32F expander module provides 32 additional lamp/LED driver outputs from J5, J6, J7 and J8. The expander module has a slide switch SW4 for selecting alarm or alarm and trouble annunciation and an input for a local lamp test switch. In alarm mode, use only one LDM-32F and one LDM-E32F for a maximum of 56 alarm indicators and 8 system status indicators. In alarm/ trouble mode, use one LDM-32F and three LDM-E32Fs for a maximum of 56 alarm indicators, 56 trouble indicators, 16 status indicators and 64 optional control switch inputs. Multiple sets of LDM-32Fs with LDM-E32F expanders increase the system annunciation capabilities beyond 56 zones or points. This is possible by various settings of address switches SW1 and SW2 on the LDM­32F (refer to Appendices). Each LDM-E32F is supplied with a 26-conductor expander ribbon cable, 4 standoffs and 4 screws.
Output Connectors for Wiring to LEDs
Security Key
Switch Terminal
Control Switch
Te rm i n al
Alarm or
Alarm/Trouble
Slide Switch
Not Used
Ribbon Cable Connections to Next LDM-E32F
Ribbon Cable Connections from LDM-32F or Previous LDM-E32F
LDM-E32F.cdr
Figure 2 LDM-E32F
LDM-32F PN 50055:C 03/20/01
11
1. Introduction Features

Connectors

J1 - Switch Matrix
Up to 16 optional external control switches and a local lamp test switch may be attached to the LDM-32F and LDM-E32F via J1 as shown in Figure 16 on page 24. In the Sensiscan 2000, the control switches may be mapped to the CPU function switches and all 9600, the switches may only be used for remote Acknowledge, Reset, Drill and Silence. External switches must be momentary type.
J2 - Ribbon Cable Connection to J3
A single 26-conductor ribbon cable may be connected from J2 on the LDM­32F or LDM-E32F (see Figure 6 on page 18) to J3 on adjacent LDM-E32Fs. The ribbon cable carries power, ground and signaling from the master module to up to three expander modules. The preformed cables are supplied in fixed lengths of 24 and 48 inches.
J3 - Ribbon Cable Connection from J2
This connector supports a single 26-conductor ribbon cable from J2 of the previous LDM-32F or LDM-E32F. Refer to Figure 6 on page 18.
J4 - Key Switch Input
This two pin connector is provided as an input on LDM-32F and LDM-E32F modules for an external security key switch. Key switch contacts must be Normally Closed. The key switch prevents unauthorized use of remote control switches wired to J1.
J5, J6, J7 and J8 - Lamp/LED Driver Outputs
input and output modules. In the MS-9200 and MS-
Each connector provides 8 driver outputs for a total of 32 drivers on each LDM­32F and LDM-E32F. Each driver is rated for a maximum of 30 volts and a current of 100 mA. Each bipolar Darlington open collector driver output must be current limited by an external resistor. 8-Point Shift and Flash functions are selectable by DIP switch SW3 (refer to "SW3 - Function DIP Switch" on page
13). Lamp/LEDs may function in ‘alarm only’ mode or ‘alarm/trouble’ mode as selected by switch SW4. Use the charts and examples shown in Appendices for additional information.
J9 - 24 VDC Lamp Power/System Trouble
Connector J9 is located only on the LDM-32F. J9 pin 1 provides 24 volts regulated power to all lamps/LEDs used in a custom graphic annunciator. The current limit of J9 pin 1 is dependent upon the current limits of the external power source being used. J9 pin 3 is a driver output for system trouble indication only. J9 pin 2 connects to system common.
J10 - Relay Expander
Not used on the Sensiscan 2000, MS-9200 and MS-9600.
12
LDM-32F PN 50055:C 03/20/01
Features 1. Introduction
J11 - 5 VDC Lamp Power
This connector is located only on the LDM-32F. J11 pin 1 provides 5 volts regulated power to all lamps/LEDs used in a custom graphic annunciator. The maximum current available from this output is 300 mA. This current is sufficient to power the maximum number of LEDs available with one LDM­32F and three LDM-E32Fs (from J5, J6, J7, J8 and one system trouble LED) provided the
current rating per LED is 2 mA.

Switches

SW1 and SW2 - Address Switches
Two rotary BCD switches, located only on the LDM-32F, are used to set the LDM Series system address. Switch SW1 represents the ‘ones’ position and switch SW2 represents the ‘tens’ position of the address setting. In system configurations of 56 zones or less, the switches must be set to address 01 for all LDMs in the system. For configurations larger than 56 zones, multiple sets of LDMs are required with sequential addresses, the first LDM starting at address 01. Each incremental setting adds 64 zones/points to the system.
For example, an MS-9200 system requiring annunciation of alarms and troubles for all 198 points would require four sets of LDMs with addresses 01, 02, 03 and 04. The MS-9600 is an exception (refer to "Appendix C: MS-9600" on page 51 for information).
SW3 - Function DIP Switch
SW3, which is located only on the LDM-32F, is used to set the annunciator functions. Function settings include:
• Number of expanders connected
• 8-Point Shift enabled
• Receive Only communications to host FACP
• Receive/Transmit communications to host FACP
• Control Switch disable
• Piezo disable
• Flash Inhibit
Refer to "Function DIP Switch - SW3" on page 25 for additional information.
SW4 - Alarm/Trouble Mode Switch
The Alarm/Trouble mode switch is installed on the LDM-32F and LDM-E32F. The switch setting on each
expander module must match the switch setting of the associated LDM-32F. ‘Alarm Only’ mode causes the driver outputs to turn on only for alarm conditions per associated zone or point at the host FACP. ‘Alarm/Trouble’ mode causes the driver outputs to turn on for both alarm and trouble conditions per associated zone or point at the host FACP. Since this switch affects the assignments of connectors J5, J6, J7 and J8, make certain to review the appendices in this manual for additional information on wiring to the lamp/LED drivers.
LDM-32F PN 50055:C 03/20/01
13
1. Introduction Features

Terminal Blocks

TB1 - 24 VDC Power, Earth Ground and Supervision
Removable terminal block TB1 appears only on the LDM-32F. 24 volts power­limited, regulated, non-resettable power from the host FACP or a compatible UL listed battery backed power supply must be connected to TB1­(+) and TB1-
COMMON OUT
COMMON IN
(-) may be used to daisy chain the 24 volts to other LDMs or devices. Earth ground must be connected to TB1­and TB1-
N.C. SUPERVISION INPUT
(-). Terminals TB1-
provide a supervised input which may be
POWER OUT
EARTH
(+) and TB1-
. Terminals TB1-6
POWER IN
used to supervise local power sources or other devices. A trouble signal is transmitted to the host FACP upon an open circuit across these terminals. The input must be power-limited. If these terminals are not used, a jumper must be installed.
TB2- EIA-485 In/Out
Removable terminal block TB2 appears only on the LDM-32F. All LDM-32Fs must connect to the EIA-485 communications bus circuit for proper operation. The EIA-485 bus carries commands and data sent between the host FACP and the LDMs. The input must be power-limited.

Cables

Expander Ribbon Cable
The Expander Ribbon Cable (PN 75120) is supplied with the LDM-E32F to allow for connection to the LDM-32F master module. The cable connects between J2 of the LDM-32F or LDM-E32F and J3 of the next LDM-E32F.
The LDM-CBL24 and LDM-CBL48
Cable sets for connecting LDM-32F and LDM-E32F connectors to lamps/ LEDs, switches, etc., are provided through the optional LDM-CBL24 (24" long) and LDM-CBL48 (48" long) cabling kits. Each cable has a plug on one end for connection to the LDM modules.
Each LDM-CBL24 cable kit includes:
• (4) P/N 75116, 24" cable consisting of 8 stranded, multicolored conductors. Cables connect to J5, J6, J7 and J8.
• (1) P/N 75122, 24" cable consisting of 10 stranded, multicolored conductors. Connects to J1, optional control switches.
• (1) P/N 75117, 24" cable consisting of 2 stranded, single color conductors. Connects to
J1, Lamp Test Switch.
• (1) P/N 75118, 24" cable consisting of 3 stranded, multicolored conductors. Connects to J9 or J11, Lamp Power.
14
LDM-32F PN 50055:C 03/20/01
Related Documentation 1. Introduction
Each LDM-CBL48 cable kit includes:
• (4) P/N 75147, 48" cable consisting of 8 stranded, multicolored conductors. Cables connect to J5, J6, J7 and J8.
• (1) P/N 75150, 48" cable consisting of 10 stranded, multicolored conductors. Connects to J1, optional control switches.
• (1) P/N 75148, 48" cable consisting of 2 stranded, single color conductors. Connects to J1, Lamp Test Switch
.
• (1) P/N 75149, 48" cable consisting of 3 stranded, multicolored conductors. Connects to J9 or J11, Lamp Power.
Key-lock Control Switch Security
A UL listed key-lock switch wired to J4 on the LDM-32F should be used to provide access security for all control switches wired to that set of LDM modules.
Note: Control switches will not function when the key-lock switch is in its closed position.
J4
2
Key Switch
Figure 3 Key-lock Switch Wiring Diagram
LDM-32F
1
LDM32F-keysw.cdr

Related Documentation

Further details about products referenced in this document can be found in the manuals for the particular fire alarm control panel and components.
Product
MS-9200 Fire Alarm Control Panel Instruction Manual 51003
MS-9600 Fire Alarm Control Panel Instruction Manual 51335
Sensiscan 2000 Fire Alarm Control Panel Instruction Manual 15017
CAB-3F Series Cabinets Installation Document 15391
LDM-32F PN 50055:C 03/20/01
Part Number
15
1. Introduction Related Documentation
NOTES
16
LDM-32F PN 50055:C 03/20/01

2. Installation

External Cabinets

The CAB-A3F and the CAB-B3F are UL listed cabinets suitable for use in graphic annunciator applications. For size and dimensions, refer to the CAB­3F Series Installation Document.
Select and remove the appropriate knockout(s) on the cabinet.
Securely mount the cabinet.
Ground the cabinet to a solid electrical ground per NEC Article 250.
Pull all wiring into the cabinet. (Refer to the appropriate FACP manual for UL Power-limited Wiring Requirements.)
Note: Other cabinets such as those provided by custom graphic annunciator manufacturers may be used provided they meet UL requirements as UL listed secured enclosures.

CHS-4L Chassis

The CHS-4L chassis will support one LDM-32F module and up to three LDM­E32F expander modules. The chassis is mounted inside the CAB-A3F or the CAB-B3F cabinet.
Mount the CHS-4L Chassis to a cabinet and secure with the hardware provided. The Grounding Cable must be connected to the chassis mounting stud for connection to the annunciator's earth ground terminal for proper operation as well as to aid in transient protection. For each LDM module to be installed on the chassis, connect two female-to-female standoffs (provided) to the upper mounting studs on the chassis.
LDM-32F PN 50055:C 03/20/01
LDM32-chs4l.cdr
Figure 4 CHS-4L Mounting
17
2. Installation CHS-4L Chassis
Slip the bottom edge of the module or expander board into the slot on the chassis and move the module toward the standoffs. Secure the board to the standoffs with the screws provided. Repeat for installation of additional modules or expanders.
Ldminchs.cdr
Figure 5 Installing LDM Modules in CHS-4L
Connect an expander ribbon cable (P/N 75120) from the LDM-32F connector J2 to J3 of the first LDM-E32F expander module. If multiple LDM-E32F modules are to be used, connect additional cables from J2 to J3 as shown below. One LDM-32F may support a maximum of three LDM-E32F modules.
18
Expander Ribbon Cables
LDM-32F LDM-E32F LDM-E32F LDM-E32F
Ldmincab.cdr
Figure 6 LDMs Mounted in UL Listed Cabinet
LDM-32F PN 50055:C 03/20/01
Wiring the Power Terminal Block 2. Installation

Wiring the Power Terminal Block

24 VDC Power and Earth Ground

24 VDC power supplied to the LDM must be power-limited. This power is inherently supervised (loss of power also results in a communication failure at the control panel).
• Limit the total wire resistance to 10 ohms.
• Connect the Grounding Cable from the chassis to the earth ground terminal of TB1 (
• Connect 24 VDC power to the terminals of TB1.
24 VDC
Power
Grounding Cable
Figure 7 24 VDC Power Terminals - TB1
EARTH
).
POWER IN
TB1
(+) and
N.C. Supervision
Inputs Common In (–) Common Out (–) Power In (+24 VDC) Power Out (+24 VDC) Earth
COMMON IN
(–)
LDM32F-TB1.cdr
Wiring of multiple LDM-32F modules.
Host FACP or Remote Power Supply
– 24 VDC
+ 24 VDC
Figure 8 Multiple Module Wiring - 24 VDC
LDM-32F PN 50055:C 03/20/01
First LDM-32F -- -- -- -- -- -- -- Last LDM-32F
TB1 TB1
LDM32F-power.cdr
19
2. Installation Wiring the EIA-485 Terminal Block

Supervision Input

The Supervision Input, which requires a normally-closed condition, can be used for supervising power sources or ot her devices. It must be power-limited. If employed, a change in status will be transmitted to the host control panel in the event of device failure or restoral.
If not used, a jumper must be installed across these terminals on TB1. A trouble signal will be registered by the control panel if a short circuit does not exist across terminals 6 & 7.
Device to be Supervised
Supervision Inputs (5 VDC @
0.5 mA) Normally Closed Trouble Contacts
Jumper
TB1
Figure 9 Wiring Supervision Terminals
TB1

Wiring the EIA-485 Terminal Block

A maximum of 32 LDM-32Fs may be connected to the EIA-485 bus, but if other types of devices are also connected to this bus, the maximum number of LDM-32Fs must be reduced by the total of such devices. Total annunciation and switch capability depends upon the number of expander modules used.
Communications between the Fire Alarm Control Panel and the LDM-32F is accomplished over a two-wire EIA-485 serial communications bus which must be power-limited. Communications between the host FACP and LDMs is supervised by the fire alarm control panel.

Wiring Specifications

• The EIA-485 circuit cannot be T-tapped; it must be wired in a continuous fashion from the control panel to the LDMs.
• The maximum wiring distance between the panel and LDMs is 6000 feet.
• The wiring must be a 18 AWG to 14 AWG twisted shielded pair cable having a characteristic impedance of 120 ohms, +/- 20%.
• Limit the total wire resistance to 100 ohms.
• Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 V power circuits.
Note: Never use the shield for grounding purposes. Terminate the EIA-485 shield at the Fire Alarm Control Panel only.
20
, motor control circuits, or SCR
RMS
LDM-32F PN 50055:C 03/20/01
LDM32F-super.cdr
Loading...
+ 44 hidden pages