Fire-Lite LCD-80FC User Manual

Remote Fire Indicator
LCD-80FC
Instruction Manual
Document 53244 5/13/2013 Rev:
P/N 53244:B ECN 13-439
B
2 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi­oelectriques depassant les limites applicables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc.Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
4 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

Table of Contents

Section 1: Overview..................................................................................................................6
1.1: Introduction....................................................................................................................................................6
1.2: Related Documentation .................................................................................................................................6
Section 2: The LCD-80FC Indicator......................................................................................... 7
2.1: Compatible Panels .........................................................................................................................................7
2.2: Features of the LCD-80FC ............................................................................................................................7
2.3: Components ...................................................................................................................................................8
2.4: SW1 DIP Switch Settings.............................................................................................................................8
2.5: Typical Configuration ..................................................................................................................................10
Section 3: Mounting................................................................................................................ 11
3.1: Indicator Preparation ...................................................................................................................................11
3.2: Semi-flush Mount Backbox.........................................................................................................................13
3.2.1: Mounting in SBB-3 Three Gang Electrical Box ...............................................................................13
3.2.2: Mounting in Three Electrical Boxes Ganged Together.....................................................................14
3.3: Surface Mount Backbox ..............................................................................................................................15
Section 4: Electrical Connections........................................................................................ 16
4.1: Power Connections ......................................................................................................................................16
4.2: EIA-485 Connections ..................................................................................................................................17
Section 5: EIA-485 Shield Termination .................................................................................20
5.1: Shield Not in Conduit ..................................................................................................................................20
5.2: Shield in Full Conduit..................................................................................................................................21
Section 6: Operation...............................................................................................................23
6.1: Display Patterns ...........................................................................................................................................23
6.2: Switch Functions .........................................................................................................................................23
6.2.1: Local Silence .....................................................................................................................................23
6.2.2: Lamp Test..........................................................................................................................................23
6.3: LED Indicators.............................................................................................................................................23
6.3.1: AC Power ..........................................................................................................................................23
6.3.2: Alarm.................................................................................................................................................24
6.3.3: Supervisory........................................................................................................................................24
6.3.4: Trouble...............................................................................................................................................24
6.3.5: Alarm Silenced ..................................................................................................................................24
Index......................................................................................................................................... 25
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 5

1.1 Introduction

This document contains information for installing, programming, and operating the LCD-80FC Remote Fire Indicator.

1.2 Related Documentation

The following table provides a list of document sources (manuals) containing additional information regarding the fire alarm control panels and components that ACS annunciators can be connected to. The FireLite document (DOC­FIR) chart provides the current document revision.
FireLite Device Compatibility Document 15384
MS-9200UDLS Instruction Manual 52750
MS-9600UDLSC Instruction Manual 52646
FCPS-24FS6/8 Instruction Manual 51883
MS-9200UD Instruction Manual (UL 8th) 51906
MS-9600 Instruction Manual (UL 8th) 51335

Section 1: Overview

Document Name P/N
6 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

Section 2: The LCD-80FC Indicator

LCD-80Fcanada.wmf
The LCD-80FC Indicator is a compact, 80-character, backlit LCD fire indicator designed for use with compatible FACPs (Fire Alarm Control Panels). It should be noted that the LCD-80FC Indi-
cator display will mimic the FACP display.
The LCD-80FC is capable of displaying English-language text of system point status including device type, independent point alarm, trouble or supervisory, zone and custom alpha labels pro­grammed into the control panel. The LCD-80FC also provides system status LEDs to display Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. The LCD-80FC is capable of performing local silence and local lamp test.
Communication between the FACP and the LCD-80FC is accomplished over a two-wire serial interface employing the EIA-485 communication standard. Up to 32 indicators may be connected to the two-wire EIA-485 circuit. The indicators may be powered from the host FACP or remote UL listed, filtered, power supplies.

2.1 Compatible Panels

MS-9200UDLS
MS-9600LS
MS-9200UD
MS-9600

2.2 Features of the LCD-80FC

80-character LCD display (20 characters x 4 lines) is backlit under normal and alarm conditions
System Status LEDs for AC Power (green), Alarm (red), Trouble (yellow), Supervisory (yellow) and Alarm Silenced (yellow)
No programming necessary — duplicates messages at control panel display.
NOTE: The FACP may require programming to function with the LCD-80FC. Refer to the specific FACP manual for programming information.
Local piezo sounder with alarm and trouble resound
Device type identifiers from the control panel
Device & zone custom alpha labels from the control panel
Time/date and device address from the control panel
EIA-485 connects to control panel terminal port
Plug-in terminal blocks for ease of installation and service
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 7
The LCD-80FC Indicator Components
Future use
ON = Piezo Enabled
ON = Membrane Function Buttons Enabled
OFF = Receive only
Top view
Note: See “DIP Switch Settings Example” on page 9.
The LCD-80FC sounder, if enabled, will be activated when any new
alarm or trouble is received from the panel. It is silenced by an
Acknowledge switch press at the FACP. Piezo must not be disabled
without approval of the local AHJ (Authority Having Jurisdiction).
Piezo Sounder
Membrane Connector
Cable connection to membrane
switches for Local Silence and Local
Lamp Test
FDU80brd.wmf
Panel Configuration
Figure 2.1 Components of the LCD-80FC
!
DIP switches control piezo enable/disable, transmit/receive mode, FACP selection, function switches and key-switch enable/disable.
Up to 32 LCD-80FC Indicators per FACP
Mounting options:
– Surface mounting in SBB-3 (2.75" depth) or three electrical boxes ganged together
– Semi-flush mounting in three-gang electrical box (P/N 10103) with a minimum depth of
2.187" or three electrical boxes ganged together
– Can be located up to 6,000 feet (1,829 m) from the panel
Backlight turns off during AC loss to conserve battery power but will turn back on if an alarm condition occurs.
Function switches for:
– Local Silence
– Local Lamp Test

2.3 Components

2.4 SW1 DIP Switch Settings

Refer to “DIP Switch Settings Example” on page 9, for an explanation of DIP switch positions. SW1 switch settings follow:
1 -ON = Function buttons enabled, OFF = Function buttons disabled.
2 -ON = Piezo sounder enabled, OFF = Piezo sounder disabled.
CAUTION: PIEZO SOUNDER DISABLE
THE PIEZO SOUNDER MUST NOT BE DISABLED WITHOUT PRIOR APPROVAL OF THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
8 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
3 -ON = Supervision Receive/Transmit, OFF = Supervision Receive Only.
SW1 DIP Switch Settings The LCD-80FC Indicator
switch 1 shown
in ON position
switch 2 shown in ON position
dipswflcd80dc.wmf
switches 3 through 8 shown in OFF position
Figure 2.2 DIP Switch Settings Example
One Indicator - if a single LCD-80FC is the only indicator connected to the EIA-485 loop,
Switch 3 must be set to the ON position to allow the FACP to supervise the indicator.
Multiple Indicators - if multiple LCD-80FC indicators are connected to the EIA-485 loop,
the indicator physically connected as the last device on the loop (farthest from the ‘OUT’ terminals on the FACP) must have Switch 3 set to the ON position in order to supervise all indicators on the loop. All remaining indicators must have Switch 3 set to the OFF position for proper supervision and operation.
It is important to note that the function switches on all LCD-80FC indicators will operate regardless of the setting of Switch 3.
A break (open circuit) in the power or EIA-485 connections creates an LCD-80FC Indicator fault at the control panel. All indicators before the break will continue to display information (but the func- tion switches on these LCD-80FCs will no longer operate).
4 through 6 = Configuration for use with a particular FACP.
Switches 4, 5 and 6 are used to select the FACP (Fire Alarm Control Panel) which is being con­nected to the LCD-80FC. Refer to the following table for the appropriate switch settings.
Fire Alarm Control Panel SW1-4 SW1-5 SW1-6
Use This Setting for: MS-9200UDLS, MS-9600LS, MS-9200UD, and MS-9600
OFF OFF OFF
Table 2.1 Dip Switch Settings
NOTE: Depending on the FACP which is connected to the LCD-80FC, it may be necessary to
enable communication with the indicator in the FACP programming. Refer to the appropriate FACP manual for programming information.
7 and 8 = Future use.
SW1 DIP switch settings as illustrated in Figure 2.2 are as follows:
1. DIP switch 1: ON = function buttons are enabled
2. DIP switch 2: ON = piezo sounder enabled
3. DIP switch 3: OFF = Receive Only. This setting is used for all indicators except the last or
only LCD-80FC Indicator on the EIA-485 line
4. DIP switches 4 through 6: OFF = Configured correctly for operation with the available
FACP (Refer to Table 2.1.)
5. DIP switches 7 and 8: OFF (these switches are not used)
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 9
The LCD-80FC Indicator Typical Configuration
FDU-80ms2.wmf
Indicator
Indicator
Indicator
Figure 2.3 Typical Configuration
Terminal Mode
EIA-485
(2-wires)
24VDC
(2-wires)
See Note 1
24VDC
EIA-485
Terminal Mode EIA-485
return (2-wires)
FACP

2.5 Typical Configuration

The LCD-80FC Indicator mimics the FACP display, has full point-display capacity and requires no programming. Note that the FACP may require programming to allow communication with the LCD-80FC. Refer to the appropriate FACP manual for programming information.
The LCD-80FC offers multiple indicator locations with the capability of Local Silence and Local Lamp Test functions.
NOTE:
1. 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm2) between the FACP and the first LCD-80FC, between each LCD-80FC and from the last LCD-80FC back to the FACP.
2. Up to 32 LCD-80FC Indicators may be used on the EIA-485 circuit. Refer to the specific FACP manual to determine the maximum current available for powering the LCD-80FC. If additional indicators are connected, the FCPS-24 may be used to supply additional power. Power supplies used for this purpose must have their negative terminals commoned together.
3. Between each LCD-80FC Indicator are four wires - a twisted shielded pair for data communications and a pair for 24 VDC power. The return circuit only requires two wires for data communication supervision, wired from the last or only indicator on the line.
10 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

Section 3: Mounting

Screw
Screw
LCD-80Fcanada.wmf
Figure 3.1 Trim Ring Removal

3.1 Indicator Preparation

The LCD-80FC Indicator can be surface mounted in a three-gang electrical box such as the P/N SBB-3 (2.75" depth) or semi-flush mounted in a three-gang electrical box, P/N 10103 or equiva­lent, with a minimum depth of 2-3/16". The LCD-80FC Indicator can also be mounted in three gangable electrical switch boxes connected together. Select and remove the appropriate knock­out(s), pull the necessary wires through the knockouts and mount the box in or on the wall depend­ing on the type of installation desired. Be certain that power is not applied to the wiring during the
installation procedure.
NOTE: To ensure static protection, all enclosures, including the LCD-80FC electrical box, must be connected to earth ground! Never use the shield for grounding purposes.
To mount the LCD-80FC Indicator in an electrical box, the trim ring must first be removed. The trim ring is held in place by two screws inserted through the top and bottom edge as illustrated in Figure 3.1. Removal of the trim ring will expose a metal flange with mounting holes. Refer to “Hardware and Backboxes” on page 12.
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 11
Mounting Indicator Preparation
Local
Silence
Lamp
Test
Hold 3 sec.
LCD-80FC flangeLCD-80FC Trim Ring
(replacement P/N 23165)
3-Gang Electrical Box P/N 10103
(semi-flush mount)
3-Gang Electrical Box P/N SBB-3
(surface mount)
LCD80fcflg.wmf
LCD2X20tr.wmf
10103box.wmf
Sbb-3.wmf
Three Ganged Electrical Boxes
3gngbox.wmf
Figure 3.2 Hardware and Backboxes
12 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
Semi-flush Mount Backbox Mounting
Local
Silence
Lamp
Test
Hold 3 sec.
LCD-80FC flange
3-gang electrical box P/N 10103
Three-gang electrical box P/N 10103
flange
EIA-485 and power wiring
LCD80fcflg.wmf
10103box.wmf
Lcd40box.wmf
The LCD-80FC can be semi-flush mounted in a three­gang electrical box, P/N 10103 or equivalent, with a minimum depth of 2-3/16". The LCD-80FC can also be mounted in three gangable electrical switch boxes connected together as illustrated in Figure 3.4 on page 14.
mounting holes (4)
Important! When installing conduit in a 3-gang electrical box, use knockouts on the top or bottom. Installing conduit on the sides or back of some boxes may interfere with mounting of the LCD-80FC in the box.
LCD-80FC
Figure 3.3 Mounting in SBB-3 Box

3.2 Semi-flush Mount Backbox

3.2.1 Mounting in SBB-3 Three Gang Electrical Box

Remove the plug-in terminal blocks from the LCD-80FC circuit board. Connect the EIA-485 and power wiring into the terminal block positions illustrated in Sections 4.1 and Section 4.2. Plug the terminal blocks back into the P2 and P1 connectors on the back of the indicator. Set DIP switch SW1 for the desired options. Refer to Figure 2.2 on page 9.
Carefully insert the LCD-80FC into the three-gang electrical box P/N: 10103 or three electrical boxes ganged together and attach it using the four mounting holes on the LCD-80FC flange and the four screws provided for this purpose. Replace the trim ring and secure with the two screws which were previously loosened. Adjust the plastic trim ring to the surface of the wall before tightening the screws. Do not overtighten.
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 13
Mounting Semi-flush Mount Backbox
Local
Silence
Lamp
Test
Hold 3 sec.
LCD-80FC flange
Three electrical boxes ganged together
flange
EIA-485 and power wiring
LCD80fcflg.wmf
Lcd4xbox.wmf
Three ganged electrical boxes
3gngbox.wmf
mounting holes (4)
The LCD-80FC can be surface mounted in three gangable electrical switch boxes connected together.
Important! When installing conduit in three ganged electrical boxes, use knockouts on the top or bottom. Installing conduit on the sides or back of some boxes may interfere with mounting of the LCD-80FCin the box.
LCD-80FC
Figure 3.4 Mounting in 3 Ganged Electrical Boxes

3.2.2 Mounting in Three Electrical Boxes Ganged Together

Remove the plug-in terminal blocks from the LCD-80FC circuit board. Connect the EIA-485 and power wiring into the terminal block positions illustrated in Sections 4.1 and 4.2. Plug the terminal blocks back into the P2 and P1 connectors on the back of the indicator. Set DIP switch SW1 for the desired options. Refer to Figure 2.2 on page 9.
Carefully insert the LCD-80FC into the three electrical boxes ganged together and attach it using the four mounting holes on the LCD-80FC flange and the four screws provided for this purpose. Replace the trim ring and secure with the two screws which were previously loosened. Adjust the plastic trim ring to the surface of the wall before tightening the screws. Do not overtighten.
14 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
Surface Mount Backbox Mounting
Local
Silence
Lamp
Test
Hold 3 sec.
LCD-80FC flange
Mounting holes (4)
The LCD-80FC can be surface mounted in a three-gang electrical box, P/N SBB-3 or equivalent, with a minimum depth of 2.75".
LCD-80FC
Three-gang surface box P/N SBB-3
flange
EIA-485 and power wiring
LCD80fcflg.wmf
Sbb-3.wmf
Lcd40box.wmf
Figure 3.5 Surface Mounting

3.3 Surface Mount Backbox

Remove the plug-in terminal blocks from the LCD-80FC circuit board. Connect the EIA-485 and power wiring into the terminal block positions illustrated in Sections 4.1 and 4.2. Plug the terminal blocks back into the P2 and P1 connectors on the back of the indicator circuit board. Set DIP switch SW1 for the desired options. Refer to Figure 2.2 on page 9.
Carefully insert the LCD-80FC into the three-gang electrical box and attach it using the four mounting holes on the LCD-80FC flange and the four screws provided for this purpose. Replace the trim ring and secure with the two screws which were previously loosened. Do not overtighten.
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 15

Section 4: Electrical Connections

P2
LCD-80FC
no connection
+24 VDC OUT
-24 VDC OUT
Earth Ground Option
- +
MS-9200UDLS
Figure 4.1 Power Wiring to the MS-9200UDLS

4.1 Power Connections

The LCD-80FC Indicator can be powered by the FACP (refer to the specific technical manual for the proper connection of the LCD-80FC) or from a remote UL listed, filtered power supply such as the FCPS-24FS6/8C. The power run to the indicator must be power-limited but need not contain a power supervision relay since loss of power is inherently supervised through loss of communica­tion with the indicator. Maximum LCD-80FC current draw from the power supply (under normal and alarm conditions) is 64.3 mA. Maximum current draw from the control panel's secondary power source (batteries) under loss of AC power is 25 mA, since the LCD backlight is turned off during AC loss. Backlighting is turned back on during AC loss only for alarm conditions in the system. 12 - 18 AWG (0.75 - 3.25 mm tance limitation is set by 1.2 volt maximum line drop from source to end of circuit.

Specifications for the LCD-80FC

Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 64.3 mA
Trouble Condition: 64.3 mA
Alarm: 64.3 mA
AC Fail (not backlit): 25 mA
2
) wire for 24 VDC circuit is acceptable. Power wire dis-
Refer to the illustrations on the following pages for power connections from the LCD-80FC to the MS-9200UDLS, MS-9600LS, and FCPS-24FS6/8C
NOTE: These connections must be power-limited and the +24 VDC nominal power input must be filtered and nonresettable.
16 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
EIA-485 Connections Electrical Connections
TB3
TB4
P2
LCD-80FC
no connection
+24 VDC OUT
-24 VDC OUT
Earth Ground Option
+ -
MS-9600LS
24 VDC Non-Rst
Power
24
VDC
Rst
Figure 4.2 Power Wiring to the MS-9600LS
P2
LCD-80FC
no connection
+24 VDC OUT
-24 VDC OUT
Earth Ground Option
- +
TB4
FCPS-24FS6/8C
Figure 4.3 Power Wiring to the FCPS-24FS6/8C
NOTE:
1. All connections are power-limited and supervised
2. 12 - 18 AWG (0.75 - 3.25 mm2) wire for 24 VDC circuit is acceptable
3. Power wire distance limitation is set by 1.2 volt maximum line drop from source to end of circuit.

4.2 EIA-485 Connections

LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 17
EIA-485 connections are made to P1 on the LCD-80FC. All connections must be power-limited and supervised. Enable FACP communication with the LCD-80FC in the FACP programming if appropriate (refer to FACP manual). A maximum of 32 LCD-80FC indicators may be connected to this circuit. A maximum distance of 6,000 feet (1,829 m) @ 18 AWG (0.75 mm2) is allowed between the FACP and first LCD-80FC, between each LCD-80FC and return to the FACP from last LCD-80FC. Use overall foil/braided-shielded twisted pair cable suitable for EIA-485 applications (refer to “EIA-485 Shield Termination” on page 20, for shield termination information). Six con­ductor overall shielded wire may be used for the four EIA-485 wires and the two power wires. It is, however, strongly recommended that the power and communication wires be separate whenever possible. A Ferrite Core P/N FBD-1 is required to meet FCC Part 15 requirements if the EIA-485 wiring is not in conduit. The EIA-485 circuit is rated at 5.5 VDC maximum and 60 mA maximum.
Electrical Connections EIA-485 Connections
LCD-80FC
MS-9200UDLS
+ EIA-485 Out to Next Device
- EIA-485 Out to Next Device
(or back to FACP)
EIA-485
+ -
- - + +
Figure 4.4 EIA-485 Wiring to the MS-9200UDLS
TB7
TB8
- - + +
LCD-80FC
P1
+ EIA-485 Out to Next Device
- EIA-485 Out to Next Device
(or back to FACP)
+ -
MS-9600LS
OUT +
OUT -
Figure 4.5 EIA-485 Wiring to the MS-9600LS
The LCD-80FC indicator has resistors built into the circuit board at the In (Terminals 2 & 4) and the Out (Terminals 1 & 3) for impedance matching. There is no need for the installer to add imped­ance matching resistors.
Refer to the following illustrations for EIA-485 connections from the LCD-80FC to the MS­9200UDLS and MS-9600LS.
18 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
EIA-485 Connections Electrical Connections
NOTE:
1. All connections are power-limited and supervised.
2. A maximum of 32 LCD-80FC indicators may be connected to this circuit.
3. 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm2) between the FACP and first LCD-80FC, between each LCD-80FC and return to the FACP from the last LCD-80FC.
4. Use overall foil/braided-shielded twisted pair cable suitable for EIA-485 applications (refer to “EIA-485 Shield Termination” on page 20, for shield termination information). Six conductor overall shielded wire may be used for the four EIA-485 wires and the two power wires. It is, however, strongly recommended that the power and communication wires be separate whenever possible.
5. Ferrite Core P/N FBD-1 is required to meet FCC Part 15 requirements if the EIA-485 wiring is not in conduit.
6. The EIA-485 circuit is rated at 5.5 VDC maximum and 60 mA maximum.
7. The LCD-80FC indicator has resistors built into the circuit board at the In (Terminals 2 & 4) and the Out (Terminals 1 & 3) for impedance matching. There is no need for the installer to add impedance matching resistors.
8. Enable FACP communication with the LCD-80FC in the FACP programming if appropriate (refer to FACP manual).
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 19

Section 5: EIA-485 Shield Termination

Connect the drain wire to the outside of the
FACP cabinet via a BX-type connector.
Shield Drain Wire
FACP Backbox
(+) EIA-485
(-) EIA-485
FACP
fdu80shl.wmf
FACP
indicator
indicator
indicator
Figure 5.1 EIA-485 Without Conduit
shield
EIA-485 Loop
not in conduit
The EIA-485 circuit must be wired using a twisted, shielded pair cable with a characteristic imped­ance of 120 ohms (+/- 20%). Do not run cable adjacent to or in the same conduit as 120 VAC ser­vice, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 V
, motor control circuits or SCR power circuits.
RMS
NOTE: To ensure static (ESD - electrostatic discharge) protection, all enclosures, including the LCD-80FC electrical box, must be connected to earth ground! Never use the EIA-485 shield for this purpose. The EIA-485 shield is for radiated noise emission protection (RFI, EMI). Refer to the following figures for details on EIA-485 shield termination.

5.1 Shield Not in Conduit

The EIA-485 line allows the FACP to communicate with the LCD-80FC Indicator. The shield for the EIA-485 line must be connected to earth ground at the FACP but must be left floating (no con­nection) at the indicator if it is the first or only device on the EIA-485 line. If a second indicator is connected, the shield leaving the first indicator must be left floating. The shield entering the sec­ond indicator must be connected to the three-gang box or Earth Ground terminal (P2-7) on the sec­ond indicator. If additional indicators are connected, the shield leaving each enclosure must be left floating and the shield entering each must be connected to the three-gang box or the Earth Ground terminal (P2-7) on the indicator.
20 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
Shield in Full Conduit EIA-485 Shield Termination
!
LCD-80FC Box
LCD-80FC
P1-2 (+) EIA-485 (IN)
P1-4 (-) EIA-485 (IN)
P2-7 Earth Ground (IN)
Connect the shield drain wire to the Earth
Ground Terminal on the Indicator
Shield Drain Wire
fdu80nos.wmf
indicator
indicator
indicator
FACP
Figure 5.2 EIA-485 in Conduit
earth ground
earth ground
Shield
EIA-485 Loop
in conduit

5.2 Shield in Full Conduit

The EIA-485 line allows the FACP to communicate with the LCD-80FC Indicator. The shield for the EIA-485 line must be connected to earth ground at the FACP (both exiting and entering the FACP) but must be left floating (no connection) at the indicator if it is the first or only device on the EIA-485 line. If a second indicator is connected, the shield leaving the first indicator must be float­ing. The shield entering the second indicator must be connected to the Earth Ground terminal (P2-
7) on the second indicator. If additional indicators are connected, the shield leaving each indicator
must be left floating and the shield entering the following unit must be connected to the Earth Ground terminal (P2-7) on the indicator.
CAUTION: INSULATE FLOATING END
DO NOT ALLOW THE FLOATING SHIELD END (NO CONNECTION) TO CONTACT THE CONDUIT. THE FLOATING END SHOULD BE INSULATED FROM EARTH GROUND.
NOTE:
1. Power-limited 24 VDC power may be run in the same conduit as the EIA-485 wiring.
2. Twisted, shielded wire is recommended for the EIA-485 communications loop.
3. Each electrical backbox is connected to earth ground via the conduit.
4. Shield is connected to the FACP cabinet (earth ground) leaving and entering the FACP.
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 21
Notes
22 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

Section 6: Operation

INITIALIZING... PLEASE WAIT
COMMUNICATION FAULT!

6.1 Display Patterns

The LCD-80FC Indicator directly displays (mimics) the information on the FACP display with the following exceptions:
Upon Power-up, the LCD-80FC may display the following message until a valid message is received from the FACP:
If an LCD-80FC Indicator fails to receive communications from the panel for a period of over 30 seconds, it will activate its local sounder (if so programmed) and display the following message:
A Communication Fault may be due to one of the following conditions:
FACP has not been programmed to communicate with the LCD-80FC. Refer to the
appropriate FACP manual programming section.
EIA-485 wiring between the LCD-80FC and FACP has an open.
Polarity of the EIA-485 wiring between the LCD-80FC and FACP has been reversed. EIA-
485 (-) on the LCD-80FC must be connected to EIA-485 (-) on the FACP and EIA-485 (+) on the LCD-80FC must be connected to EIA-485 (+) on the FACP.

6.2 Switch Functions

6.2.1 Local Silence

When the Local Silence switch is pressed, the piezo sounder at the LCD-80FC Indicator will be silenced.

6.2.2 Lamp Test

Pressing the Lamp Test switch will turn on all local Indicator LEDs, piezo sounders and LCD dis­play segments as long as the Lamp Test switch is held.

6.3 LED Indicators

6.3.1 AC Power

This is a green LED which illuminates if AC power is applied to the host FACP. The green LED will turn off if AC power to the host FACP is lost.
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 23
Operation LED Indicators

6.3.2 Alarm

This is a red LED that turns on steady when one or more fire alarms occur. The Alarm LED turns off when the FACP Reset switch is pressed.

6.3.3 Supervisory

This is a yellow LED that turns on steady when one or more supervisory conditions occur, such as a sprinkler valve tamper condition. It turns off when the FACP Reset switch is pressed.

6.3.4 Trouble

This is a yellow LED that turns on steady when one or more trouble conditions occur. The LED turns off when all trouble conditions are cleared. This LED will also illuminate if the microproces­sor watchdog circuit within the LCD-80FC is activated.

6.3.5 Alarm Silenced

This is a yellow LED that turns on when the FACP Silence switch is pressed to turn off the Notifi­cation Appliance Circuits. The LED turns off when the NACs turn back on or when the alarm con­dition is cleared and the FACP is reset back to a normal condition.
24 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013

Index

Numerics
80-character 7
A
AC loss 8 AHJ
8
alarm LED alarm silenced LED annunciator, maximum application
Authority Having Jurisdiction
7, 24
7, 24
10
see also typical configuration
see also AHJ
8
B
backboxes 8, 11 backlit
7
C
communication 7, 9 communication failure Communication Fault components configuration
current specifications custom alpha labels
8
see also FACP selection
23
23
16
7
D
device type identifiers 7 DIP switch settings
see also switch settings, example
DIP switches display information display on powerup distance, maximum
8
7 23 8, 10
FCC Part 15 requirements FCPS-24FS6/8C Power ferrite core flange function switches
17
13, 15
8
17, 19
17
G
grounding 11, 20, 21
I
10
indicator 7
L
LAHJ 8 Lamp Test switch LCD display
see also display on powerup
LED
7
see also system status
LEDs
23
local lamp test switch Local Silence switch local silence switch
9
9
M
maximum indicators 7, 8 mounting mounting options MS-9200UDLS
MS-9600LS
11, 14, 15
EIA-485 Power
EIA-485 connection
23
7
23
7
8
23
8
8
18
16
18
O
operation 23
E
earth ground 11 EIA-485
EIA-485 wiring electrical connections
7, 9, 10, 13, 15, 17, 19, 21
shield
20
17
16
F
FACP compatibility 7 FACP selection Fault
23
FBD-1 Ferrite Core
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 25
9
17
P
piezo sounder 7, 8 power for indicator power LED power requirements power source power-limited programming
7, 23
16
16
7
R
receive only
see also communication
7
10, 16
8
S–W Index
receive/transmit
see also communication
resound, piezo
7
8
S
SBB-3 backbox 11, 13 semi-flush mounting shield
no conduit see also EIA-485
specifications static protection supervision supervisory LED surface mounting SW1
switch functions switch settings switch settings, example system status
9, 10, 16
see also DIP switches
13
20
20
16
11, 20
7, 24
15
8
23
8, 9
9
7
T
terminal block 7, 14, 15 three gang electrical boxes three ganged electrical boxes trim ring trouble LED typical configuration
11, 12, 13, 14, 15
7, 24
11, 12
10
W
wiring
conduit distance EIA-485 ferrite core no conduit power type
wiring requirements
21
19
17
17, 19
20
16, 17
17, 19
10
14
26 LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to the extent possible, any warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, serviced or repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if there is a failure to maintain the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS, TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION, INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
LCD-80FC Instruction Manual — P/N 53244:B 5/13/2013 27
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Loading...