Fire-Lite I300A User Manual

M300(A) MONITOR MODULE, C304(A) CONTROL MODULE, AND
STATUS LED
ROTARY DECADE ADDRESS SWITCHES
MODE TABS
M300(A) MAGNET TEST POSITION
ISOLATED
QUADRANT
I300(A) FAULT ISOLATOR MODULE INSTALLATION INSTRUCTIONS
This information is included as a quick reference installation guide. Refer to the appropriate Fire-Lite control panel installation man­ual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION
M300(A) MONITOR MODULES provide a two-wire, or fault-tolerant, initiating
circuit for normally open contact fire alarm and supervisory devices, or either normally open or normally closed security devices. The LED indicator can be latched on or returned to the normal mode by code command from the panel. Rotary decade switches are used to set the address of each module.
C304(A) CONTROL MODULES allow a compatible control panel to switch dis­crete contacts by code command. The control module offers a status LED that can be latched on or returned to the normal mode by code command from the panel. Rotary decade switches are used to set the address of each module.
The control module offers two modes of switching operation. As shipped, the
Figure 1. Montior and Control Module
Conrols and Indicators
module is configured for switching an external power source to notification ap­pliances. The external power source can be a DC power supply or an audio amplifier (up to 70.7 Vrms). In this mode, the mod­ule reports supervision status of the connected loads to the control panel. Load circuit status is reported as a normal, open, or shorted circuit. Two pairs of output termination points are available for fault-tolerant wiring. The second mode of switching op­eration allows the panel to control one Form-C (SPDT) set of contacts.
by the module.
This mode is enabled by breaking two external tabs on the module.
Circuit connections to the contacts are not supervised
A78-2318-01
I300(A) FAULT ISOLATOR MODULES enable part of the communications loop to continue operating when a short circuit oc­curs on it. An LED indicator blinks in the normal condition and turns on during a short circuit condition. The module will auto­matically restore the entire communications loop to the normal condition when the short circuit is removed. (The isolator mod­ule does not have decade switches.)
COMPATIBILITY REQUIREMENTS
To insure proper operation, these modules must be connected to addressable, listed compatible Fire-Lite control panels only.
MOUNTING M300(A), C304(A), AND I300(A) DEVICES
M300(A), C304(A), and I300(A) modules mount directly to 4 inch square elec-
1
trical boxes as shown in Figure 2A. The box must have a min. depth of 2
/8".
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. When using control modules in nonpower limited applica­tions, the CB500 Module Barrier must be used to meet UL require­ments for the separation of power-limited and nonpower-limited termi-
1
nals and wiring. The barrier must be inserted in a 4"x4"x2
/8" junction box, and the control module must be placed into the barrier and at­tached to the junction box (Figure 2A). The power-limited wiring must be placed into the isolated quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams (Figures 3 - 10).
2. Set the address on the M300 and C304 per job drawings. Record this ad­dress and loop on the front of the module, if desired.
Figure 2B.
A78-2611-00
3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.
M300(A) MAGNET TEST
The M300(A) Monitor module can be tested with Fire-Lite's M02-04-01 Test Magnet (see Figure 1). The magnet test checks the module electronics and connections to the control panel. Interfaced initiating and indicating devices must be tested independently.
F300-03-01 1 I56-570-05
Fire-Lite Alarms, Inc., 12 Clintonville Rd, Northfield , CT 06472-1652 (203) 484-7161
Figure 2A. Module
Mounting with Barrier
A78-2610-00
1 (-) 2 (+)
MODULE
FROM PANEL OR
(+)
(-)
TO NEXT
(+)
(-)
DEVICE
(+)
(-)
3 (-) 4 (+)
(+) 9
(-) 8
(-) 7
(+) 6
XXX 5
CONTROL
(-)
(+)
(-)
(+)
47K EOL RESISTOR A2143-00
UL LISTED EOL RELAY SHOWN ENERGIZED
A77-716B
XXX - DO NOT
USE TERMINAL 5
TO NEXT CONTROL MODULE OR END
OF LINE RELAY (EOLR); ONE EOLR REQUIRED PER BRANCH CIRCUIT
MODULE POLARITIES ARE
SHOWN IN ALARM
CONNECT MODULES TO LISTED COMPATIBLE
USE UL LISTED INDICATING APPLIANCES
RESISTIVE: 2 A @ 30 VDC INDUCTIVE: 1 A @ 30 VDC (.6 PF) PILOT DUTY: .6 A @ 30 VDC (.35 PF)
MAXIMUM LOAD:
SEE FIRE-LITE PRODUCT
MANUAL FOR
WIRE SPECIFICATIONS
BRANCH CIRCUIT
3 & 4. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
DO NOT LOOP WIRE ON TERMINALS
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
(-)
(+)
IS
OLATED, REGULATED
POWER SUPPLY, LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP (MONITOR LOSS OF PRIMARY POWER)
C304(A)
FIRE-LITE CONTROL PANELS ONLY
INDICATING APPLIANCE CIRCUIT (IAC) - NFPA STYLE W
COMMUNICATION LINE
PREVIOUS DEVICE
EXTERNAL POWER SOURCE MUST BE
POWER LIMITED PER NFPA 70
FROM PANEL OR
PREVIOUS DEVICE
(–) (+)
(–)
TO NEXT
(+)
DEVICE
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
47 K EOL RESISTOR A2143-00
INITIATING DEVICE CIRCUIT - NFPA STYLE A OR B
POWER LIMITED: 230 µA MAX @ 12 VDC MAX
IDC INSTALLATION WIRING SHALL NOT
EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONNECT MODULES TO LISTED COMPATIBLE
FIRE-LITE CONTROL PANELS ONLY
COMMUNICATION LINE
SEE FIRE-LITE PRODUCT
MANUAL FOR WIRE SPECIFICATIONS
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
MONITOR
MODULE M300(A)
(–) (+)
1 (–)
2 (+)
(–)9 (+)8
(+)7
(–)6
FIGURE 3. TYPICAL M300 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE A OR B
CONNECT MODULES TO LISTED COMPATIBLE
FIRE-LITE CONTROL PANELS ONLY
FROM PANEL OR
PREVIOUS DEVICE
(-) (+)
COMMUNICATION LINE
SEE FIRE-LITE PRODUCT
MONITOR
MODULE M300(A)
(–) (+)
MANUAL FOR WIRE
SPECIFICATIONS
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
1 (–) 2 (+)
(–)
TO NEXT
(+)
DEVICE
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USE. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICE ON THE SAME MODULE.
(–)9 (+)8 (+)7 (–)6
INITIATING DEVICE CIRCUIT - NFPA STYLE D
POWER LIMITED: 230 µA MAX @ 12 VDC MAX
IDC INSTALLATION WIRING SHALL NOT
EXCEED 40 OHMS OR 2500 FEET, 12 - 18 AWG.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS.
EOL RESISTOR IS INTERNAL AT TERMINALS 8 & 9.
FIGURE 4. TYPICAL M300 FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION, NFPA STYLE D
A78-2280-05
A78-2281-03
FIGURE 5. TYPICAL C304 INDICATING CIRCUIT CONFIGURATION, NFPA STYLE W
F300-03-01 2 I56-570-05
A78-2282-05
Loading...
+ 2 hidden pages