One Fire-Lite Place
Northford, CT 06472
Phone (203) 484-7161
FAX: (203) 484-7118
Document #51073
12/09/2008 Rev.
P/N 51073:D ECN 08-870
D
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications. This Class A
digital apparatus complies with Canadian ICES-003.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada. Cet
appareil numerique de la Classe A est conforme a la
norme NMB-003 du Canada.
Notes
4 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Controls and Indicators................................................................................................................................. 13
411UDAC Controls and Indicators ................................................................................................... 13
Components and Accessories........................................................................................................................14
Digital Communicator Operation.................................................................................................................. 14
Normal Mode......................................................................................................................................... 15
Real Time Clock Mode.......................................................................................................................... 15
Program Mode....................................................................................................................................... 15
T elephone Circuits........................................................................................................................................28
Programmer Connection to 411UDAC ............................................................................................. 29
UL Power-limited Wiring Requirements...................................................................................................... 30
Typical UL Power-limited Wiring Diagram ...................................................................................... 30
CHAPTER 3: Modes of Operation..................................................................................................................... 31
Normal Mode................................................................................................................................................ 31
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D5
Real Time Clock Mode.................................................................................................................................34
Program Mode .............................................................................................................................................. 35
Downloading to the Communicator..............................................................................................................63
Uploading From the Communicator............................................................................................................. 63
Simultaneous Data Transfers .........................................................................................................................64
Canadian Applications ..........................................................................................................................................82
6411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
This digital communicator/transmitter has been designed to comply with standards set forth by the following
regulatory agencies:
• Underwriters Laboratories Standard
• NFPA 72 National Fire Alarm Code
• CAN/ULC - S527-M99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
Central Station Signaling Systems Protected Premises Unit (Automatic, Manual and Waterflow)
Proprietary Fire Alarm Systems (Protected Premises Unit)
Remote Station Fire Alarm Systems
Automatic Fire Detectors
Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
Inspection, Testing and Maintenance for Fire Alarm Systems
Underwriters Laboratories Documents:
UL 217 Smoke Detectors, Single and Multiple Station
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1635 Digital Alarm Communicator System Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
CAN/ULC - S559-04 Equipment for Fire Signal Receiving Centers and Systems
This Class (A) digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe (A) est conforme à la norme NMB-003 du Canada.
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL
864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the
approval of the local Authority Having Jurisdiction (AHJ).
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D7
TB1
NONONCNCCC
(nonsupervised)
NC Contact
NO Contact
(nonsupervised)
NC Contact
NO Contact
Relay K5 and K6
RELAY 2RELAY 1
Relay 2
Common
Relay 1
Common
411AREL.CDR
All Circuits on TB2 and TB4 are
supervised and power-limited
NAC B+
NAC B+12 VDC Resettable
- Resettable (common)
Zone 1 B+
Zone 1 BZone 2 B+
Zone 2 BZone 3 B+
Zone 3 A+
Zone 3 AZone 3 BZone 4 B+
Zone 4 B-
+
+
+
TB4
Phone Line 1
Phone Line 2
+B--
+12V POWER
411ANAC.CDR
B+
NAC
HIGH VOLTAGE
Transformer
(supervised, nonpower-limited)
AC Power Connector
CAUTION!
Earth
AC Neutral
AC Hot
hinged cover must be
closed after wiring
- +
Battery Connector
(supervised, nonpower-limited)
8 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Jumper J8 must
be installed for
proper panel
operation
PRO-411
DACT
Programmer
411UDABD.CDR
Product Description
CHAPTER 1Pr oduct Description
The 411UDAC is a fire alarm communicator with four input/channels and dual telephone lines. The four inputs use
conventional input devices. The 411UDAC accepts waterflow devices, two-wire smoke detectors, four-wire smoke
detectors, pull stations and other nor mally-open contact devices. The unit also supervises AC voltage, telephone line
input voltage/current, battery level and battery charger operation.
Outputs include one supplementary NAC (Notification Appliance Circuit), two programmable Form-C relays and 12
VDC resettable special application power. The 41 1UDAC interfaces with the public switched telephone network and
is compatible with most central station receivers. A total of fifteen popular communications formats are supported,
including the industry standard Ademco Contact ID. The communicator also contains a unique DACT option that
eliminates 'dialer runaway'. It restricts the transmission of any intermittent nuisance fault to 10 attempts in a 24 hour
period.
Accessories include the Fire-Watch 411 Series DACT Programmer (Model PRO-411) as well as the PK-411UD
Windows
®
95 based remote site programming software. The 411UDAC is supplied with a compact metal cabinet.
The digital communicator can be programmed or interrogated off-site via the public switched telephone network.
Any IBM compatible personal computer with Windows
®
3.1 or greater, with a 1200 baud Hayes® compatible modem
and Upload/Download software P/N PK-411UD, may serve as a service terminal.
1.1Product Features
FIGURE 1-1:411UDAC Digital Communicator
• Four input/channels - three fixed Style B (Class B) and
one Style A (Class A) or Style B (Class B)
• One Style Y (Class B) NAC (supplementary application)
• Dual telephone lines
FIGURE 1-2:DP-2 Dress Panel
Dual telephone line voltage detect
Alternating phone lines for 24 hour test messages
• 12 VDC operation
• 1.6 amps total system power
• Alarm Verification
• Signal Silence Inhibit
• Autosilence
• Trouble Reminder
• Trouble Resound - troubles will resound the buzzer every 24
hours at midnight until the trouble is cleared
• Optional DP-2 Dress Panel (required for Canadian
applications)
DP411A.CDR
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D9
Product Features
• Industry first 20-digit central station and service terminal telephone numbers
• NAC coding per ANSI S-3.41 (Temporal Coding)
• Surface mount technology
• Separate external keypad and display
provides means of programming 411UDAC in program mode
provides means of testing input/output circuits (including telephone connections) in Troubleshoot Mode
• Compact in size 14.5" (36.83 cm) high X 12.5" (31.75 cm) wide X 2.875" (7.303 cm) deep metal cabinet
• Communicates vital status of monitored control panel (Slave Mode):
fire alarm
host control panel trouble
fire supervisory
AC (mains) power loss (programmable)
other
• Communicates vital status of 411UDAC:
digital communicator troubles
telephone Line 1 and 2 voltage fault
Primary Central Station number communication fault
Secondary Central Station number communication fault
system off-normal (local Program Mode entered)
24 Hour normal test
24 Hour abnormal test (24 hour test message with previou sl y repo rted alarm or trouble still active)
• Individual LEDs for:
AC Power
System Trouble
Input Active
Supervisory
Communication Fail
Battery Trouble
Earth Fault
• Local piezo sounder with separate and distinct sounds for the various conditions
Maximum Charging Circuit: Normal flat charge - 13.7V @ 0.6 amps
Maximum Charger Capacity: 14 Amp Hour battery
Supervised, nonpower-limited
Channels/Inputs - TB2 Terminals 1 through 10
Programmable Channels 1 through 4
Power-limited circuitry
Fully supervised (monitored for opens, shorts and earth fault)
Normal Operating Voltage: 12.0 VDC (ripple = 100 mV maximum)
End-of-Line Resistor: 2.2K ohms, ½ watt (P/N 27070 UL listed)
Operation for each channel:
• Channel/Input 1, Style B (Class B) 2-wire smoke detector input and Channel/Input 3, Style B (Class B) 2-wire
smoke detectors or waterflows or Style D (Class A) waterflow input:
Note: Connecting 2-wire detectors on Channel/Input 3 requires NFPA Style B (Class B) only.
Alarm Current: 11 mA
Short Circuit Current: 24 mA maximum
Maximum Detector Current in Standby: 2 mA
Maximum Loop Resistance: 30 ohms
Detector Loop Current is sufficient to ensure operation of a minimum of one alarmed detector per
zone
Standby Current: 5.17 mA (including End-of-Line Resistor)
• Channel/Input 2 and Channel/Input 4 - Style B (Class B) contact closure input:
Short Circuit Current: 4.46 mA maximum
Maximum Loop Resistance: 100 ohms
Standby Current: 2.66 mA
Refer to Device Compatibility Document for listed compatible devices
The 411UDAC Notification Appliance Circuit may only be used to supplement host panel NACs
Style Y (Class B) power-limited and supervised circuit (monitored for opens, shorts and earth fault)
Maximum voltage drop in wiring: 2.0 VDC
Operating voltage nominal 13.8 VDC
Current for all external devices: 1.0 amp
End-of-line resistor: 2.2K ohms, ½ watt (P/N 27070)
Refer to Device Compatibility Document for listed compatible devices
12 VDC Resettable Special Application Power - TB4 Terminals 3(+) and 4(-)
Operating voltage nominal 12 voltsMaximum ripple voltage: 10 mV
RMS
Up to 200 mA is available for powering 4-wire smoke detectors
Power-limited and supervised circuitry. Recommended maximum standby current is 50 mA
Notes:
1. For power supply and battery calculations, refer to Chapter 6
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D11
Circuits
1.3Circuits
The 411UDAC circuit board utilizes surface mount technology and contains a MicroController Unit (MCU), dual
modular phone line jacks, piezo sounder, two sockets for optional programmable relays and connectors for input, output and power wiring. A piezo silence switch and reset switch are provided on the membrane panel which plugs into
connector J7 on the main circuit board.
1.3.1 Channels/Inputs
Four input channels are provided on the 411UDAC. The 411UDAC can be used to monitor a host FACP (Fire
Alarm Control Panel) in Slave Mode or as a stand-alone FAC (Fire Alarm Communicator). Each input can be
programmed to monitor the following conditions:
• fire alarm activation
• 2-wire smoke (channels 1 & 3 only)
• pull station
• normally open contact device
• waterflow
• trouble activation
• fire supervisory activation
1.3.2 Notification Appliance Circuit
One Style B NAC (Notification Appliance Circuit) requiring a 2.2K ohm End-of-Line resistor. This NAC can
only be used to supplement host panel NACs.
1.3.3 Output Circuits
• Modular jacks are used to interface the primary and secondary phone lines to the public telephone network.
Phone lines are fully supervised at all times (if communication is enabled).
• 12 volt resettable special application power output (200 mA)
• 12 volt battery charge r will charge up to 14 AH batteries
1.3.4 Auxi liary Rela ys
Two dry Form-C relays (P/N: 411RK), with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30
VAC (resistive), are installed on the main circuit board. Each relay is programmable for:
Alarm
Fire supervisory - latching
Fire supervisory - autoresettable
Host panel trouble
DACT trouble
Total communications failure
1.3.5 Earth Ground
12
Connect a separate earth ground wire to ground stud in backbox for transient protection (refer to Figure 2-4 on
page 21 for location of stud).
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Controls and Indicators
1.4Controls and Indicators
FIGURE 1-3:411UDAC Controls and Indicators
411ACDSP.CDR
Front Panel Switch
• Reset Switch - to reset 411UDAC circuits
• Acknowledge/System Silence Switch
press once to acknowledge alarm or trouble (silence local 411UDAC piezo sounder and change all
flashing LEDs to steady on)
press a second time and hold for minimum of two seconds to perform a System Signal Silence (silence
Notification Appliance Circuit)
411UDAC Piezo Sounder
• The 411UDAC piezo sounder is used to locally annunciate DACT alarms and troubles. DACT troubles
include input channel open circuit, NAC fault, phone line 1 or 2 voltage fault, phone number 1 or 2
communication fault and total communication failure. Separate and distinct sounds are provided for the
following conditions:
alarm - steady On
trouble - 1 second On and 1 second Off
supervisory - ½ second On and ½ second Off
Front Panel Indicator
• AC Power - green LED
• Input Active - green LED
• Communication Fail - yellow LED
• System Trouble - yellow LED
• Supervisory - yellow LED
• Battery Trouble - yellow LED
Circuit Board Indicator
• Earth Fault - yellow LED (indicates zero impedance between panel and earth ground)
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D13
Components and Accessories
1.5Components and Accessories
Main Circuit Board
The main circuit board contains the system’s MCU (microcontroller unit), power supply, other primary
components and wiring interface connectors. The main circuit board is shipped in the same carton as the cabinet
but is not mounted in the cabinet. The circuit board should be installed only after the cabinet is mounted to the
wall and the area is clean and free of potential contaminants.
Cabinet
The cabinet is red and measures 14.5" (36.83 cm) high X 12.5" (31.75 cm) wide X 2.875" (7.303 cm) deep. It
provides space for up to two 7 Amp Hour batteries which must be ordered separately. A dress panel, which
mounts inside the cabinet, is also available. A supplied bezel must be installed in the door opening.
Dress Panel
An optional dress panel (P/N: DP-2) is available (required for Canadian installations). The dress panel restricts
access to the system wiring while allowing access to the membrane switch panel. See Figure 1-2 on page 9.
Transformer Assembly
One transformer is shipped in the same carton as the cabinet and main circuit board but not mounted in the
cabinet. The transformer should be installed before the cabinet is mounted to the wall.
Fire•Watch 411 Series DACT Programmer (Model PRO-411)
The PRO-411 is an optional DACT programmer which can be used to troubleshoot and program the 411UDAC,
as well as access the various modes of operation. The PRO-411 must be ordered separately.
PK-411UD Upload/Download Software Kit
The optional PK-411UD Kit consists of the PK-411UD Upload/Download software on 3½” disk and the
PK-411UD Program Manual. The PK-411UD enables a user to program the 411UDAC off site via the public
®
switched telephone network using any personal computer with Windows
1200 baud Hayes
®
compatible modem.
3.1 or greater or Windows® 95 and a
1.6Digital Communicator Operation
The 411UDAC has been designed to be compatible with a wide variety of fire alarm, nonfire and combination control
panels (Slave Mode operation). Numerous formats are also available for communication to a central station. Two
modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 and PH2 for the Primary and Secondary phone lines. The digital communicator provides the following functions:
• Line Seizure- takes control phone lines, disconnecting any premise phones which may be using the same lines
• Off/On-Hook - perform on and off-hook status to phone lines
• Listen for dial tone - 440 hertz tone typical in most networks
• Dialing the Central Station(s) phone number - default is Touch-Tone®, programmable to rotary
• Discern proper Central Station 'ACK' and 'Kiss-off' tone(s)
• Transmit data to the Central Station(s)
• Verify data has been accepted by the Central Station(s)
• Hang-up and release phone lines
• Communicate in a variety of formats (Refer to Table 4-1, “Format Selection Addresses ( 20 and 50) Programming,” on page 56).
14
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Panel Configuration
1.7Panel Configuration
The 411UDAC can be configured, through programming, for the following modes of operation:
• Stand-alone Mode With Communicator Enabled - the 411UDAC functions as a latching digital alarm communicator in which all input circuit activations latch (except those programmed as autoresettable) and are
restored only by pressing the local reset switch. The onboard communicator will attempt to transmit events to
a Central Station
• Slave Mode With Communicator Enabled - the 411UDAC functions as a nonlatching slave to a host control
panel and the onboard digital alarm communicator will attempt to transmit events to a Central Station
• Slave Mode With Communicator Disabled - the 411UDAC functions only as a nonlatching slave to a host
control panel. The digital alarm communicator will not transmit to a Central Station
1.8Operational Modes
1.8.1 Normal Mode
Normal Mode is the standard mode of operation in which the 411UDAC monitors the channel/input circuits as well
as telephone line voltage and other internal circuits. In addition to locally annunciating system trouble, active channel/input and communication fail, the onboard communicator transmits system status information to UL listed central
station receivers if programmed to do so. Transmitted data includes fire alarm, fire alarm trouble, supervisory alarm
and AC loss information. Specific digital communicator troubles are also transmitted.
1.8.2 Real Time Clock Mode
Real Time Clock Mode allows the user to change the digital alarm communicator’s internal 24 hour clock. Connecting an external Programmer allows access to the various Modes of operation. While the 411UDAC is in Real Time
Clock Mode, it does not monitor channel inputs.
1.8.3 Program Mode
Program Mode is used to change the programmed functions of the 411UDAC. While the 411UDAC is in Program
Mode, it does not monitor channel inputs. In addition, some program items will be locked, which will prevent editing
while the communicator is active (dialing, transmitting, etc.).
1.8.4 Troubleshoot Mode
Troubleshoot Mode may be used to sample and display status for all channel/input circuits, Notification Appliance
Circuit, AC power, battery, charger and 12 volt resettable power. In addition, Troubleshoot Mode may be used for
testing the telephone line interconnect wiring. Connection from the 411UDAC’s modular jacks, through the RJ31X
jacks and into the telephone network may be easily checked. In this mode, the Programmer keypad acts similar to a
telephone touchpad. While the 411UDAC is in Troubleshoot Mode, it does not monitor channel inputs.
1.8.5 Default Mode
Default Mode may be used to return all 411UDAC programming back to the factory default settings and to reset the
Real-Time Clock to ‘00:01’ midnight. See “Default Mode” on page 53.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D15
Telephone Requirements and Warnings
1.9Telephone Requirements and Warnings
1.9.1 Telephone Circuitry - PH1 & PH2
AC Ringer Equivalence Number (REN) = 1.2B
DC Ringer Equivalence Number (REN) = 0.0B
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all
areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN
for the calling area.
1.9.2 Digital Alarm Communicator:
Before connecting the 411UDAC to the public switched telephone network, the installation of two RJ31X jacks is
necessary. The following information is provided if required by the local telephone company:
Manufacturer:Fire•Lite Alarms Inc./Notifier
One Fire-Lite Place
Northford, CT 06472
Product Model Number: 411UDAC
FCC Registration Number: OAAUSA-25431-AL-E
AC Ringer Equivalence: 1.2B
DC Ringer Equivalence: 0.0B
Note: FCC ID label is located on the inside cover.
Important! The DACT must not
be used to dial a phone number that is call-forwarded per requirements of UL 864
9th Edition.
1.9.3 Telephone Company Rights and Warnings:
The telephone company, under certain circumstances, may temporarily discontinue services and/or make changes in
its facilities, services, equipment or procedures which may affect the operation of this digital communicator. However, the telephone company is required to give advance notice of such changes or interruptions. If the digital communicator causes harm to the telephone network, the telephone company reserves the right to temporarily
discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In
such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems
and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the digital communicator activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The digital communicator must be connected to the public switched telephone network upstream of any private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to
the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
16
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Telephone Requirements and Warnings
1.9.4 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
“NOTICE: The Industry Canada (IC) label identifies certified equipment. This certification means that the equip-
ment meets certain telecommunications network protective, operational and safety requirements as prescribed in the
appropriate Terminal Equipment Technical Requirements document(s). The Department does not guarantee the
equipment will operate to the user’s satisfaction.”
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not prevent degradation of service in some
situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the
supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the
telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone
lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly
important in rural areas.
CAUTION
Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection
authority, or electrician.
“The Ringer Equivalence Number
(REN) assigned to each terminal device provides an indication of the maximum
number of terminals allowed to be connected to a telephone interface. The termination of an interface may consist of
any combination of devices subject only to the requirement that the sum of the REN of all devices does not exceed 5.”
Representative: NOTIFIER/FIRE•LITE, CANADA
10 Whitmore Rd.
Woodbridge, Ontario L4L 7Z4
IC Certificate Number:
Ringer Equivalence Number (REN): 0.4B
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D17
Installation
CHAPTER 2Installation
2.1Mounting Options
The cabinet may be either semi-flush or surface mounted. The door is removable during the installation period by
opening and lifting it off the hinges. The cabinet mounts using two key slots and two additional 0.25" diameter holes
located in the backbox. The keyslots are located at the top of the backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry, vibration-free area
where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily
install and maintain the panel. Locate the top of the cabinet approximately five feet above the floor with the hinge
mounting on the left. Determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience. Select the appropri ate knock out(s) and pull the required conductors into
the box. Note that there are no knockouts on the left (hinged) side of the cabinet. All wiring should be in accordance
with the National and/or Local codes for fire alarm systems.
2.2Mounting
Backbox Mounting
FIGURE 2-1:Transformer Mounting
• Open the door and lift the door off the pin hinges
• Mark and predrill holes for the top two keyhole mount-
ing bolts using the dimensions shown in Figure 2-2 on
page 19
Top of backbox
Ground
Stud
• Install two upper fasteners in the wall with the screw
heads protruding
• Using the upper 'keyholes', temporarily mount the
backbox over the two screws
• Mark the lower two holes, remove the backbox from
Transformer
flange
Transformer
mounting stud
the wall and drill the lower two holes in the wall
• Before mounting the backbox to the wall, install the
supplied transformer in the backbox by sliding the bottom transformer flange into the lower transformer
Transformer
mounting slot
mounting slot. Position the hole in the top transformer
flange over the transformer mounting stud. Refer to
Figure 2-1 for the location of the slot and stud
• Secure the transformer with the supplied nut and
attached washer
• Mount the backbox to the keyhole mounting bolts, install and tighten the remain ing fasteners
Main Circuit Board Mounting
• When the location is clean and free of construction dust or other contaminants, install the main PC board by
installing the four supplied standoffs on the four main circuit board mounting studs located in the backbox.
Refer to Figure 2-2, “Cabinet Dimensions and Knockout Locations,” on page 19
• Position the main circuit board’s four corner mounting holes over the four standoffs just installed. Be certain
to observe the proper ESD (Electro Static Discharge) precautions to prevent damage to the static sensitive
circuits. This includes, but is not limited to, use of a wrist strap
• Secure the main circuit board to the standoffs with the four supplied screws and attached washers
• Plug the transformer connector into the main circuit board connector J4. The connector is keyed and can only
be plugged-in one way. Refer to Figure 2-4 on page 21 and Figure 2-13 on page 30 for transformer connector
location and AC power connections
• When wiring is completed, install the door on the backbox pin hinges and the window bezel in the door
411XFRMT.CDR
18
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Mounting
FIGURE 2-2:Cabinet Dimensions and Knockout Locations
1.125“
(2.858 cm)
Knockouts
0.875“
(2.223 cm)
1.1“ (2.794 cm)
1.25“
(3.175 cm)
4.12“ (10.47 cm)
(7.62 cm)
3.0“
Double
Transformer
Mounting
Slot
Single
Transformer
Mounting
Slot
6.12“ (15.55 cm)
Transformer
Mounting
Stud
8.12“ (20.63 cm)
10.12“ (25.75 cm)
12.5“ (31.75 cm)
6.5“ (16.51 cm)
Ground
Stud
Main Circuit Board
Mounting Studs
2.875“
(7.303 cm)
14.5“
(36.83 cm)
Top (back)
Top (front)
1.25“
(3.175 cm)
(8.255 cm)
(4.445 cm)
(8.89 cm)
3.25“
1.75“
3.5“
TR-3-R Trim Ring
16.625" (42.228 cm)
12.625"
(32.068 cm)
14.625“ (37.148 cm)
5024JRBB.CDR
17.625"
(44.768 cm)
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D19
Mounting
FIGURE 2-3:411UDAC Backbox
Door=14.714“ (37.374 cm)
Backbox=14.5“ (36.83 cm)
Top
Door=12.714“ (32.294 cm)
Backbox=12.5“ (31.75 cm)
Depth=2.875“ (7.303 cm)
Depth=3“
(7.62 cm)
Bottom
Right Side
411ACABB.CDR
20
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Operating Power
2.3Operating Power
CAUTION: Several different sources of power can be connected to the 411UDAC. Disconnect all sources of power
!
before servicing this unit. The communicator and associated equipment may be damaged by removing and/or inserting modules or cables with power applied.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the 411UDAC cabinet. The primary power source is 120 VAC, 60 Hz, 0.3
amps. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB3 of the main
circuit board. As per the National Electric Code, use 14 AWG (2.00 mm
tion. No other equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent
protection and may not contain any power disconnect devices. A separate earth ground connection must be made to
ensure proper panel operation and lightning and transient protection. Connect the earth ground wire [minimum 14
2
AWG (2 .00 mm
) to the earth ground stud in the cabinet. Do not use conduit for the earth ground connection since
the does not provide reliable protection.
FIGURE 2-4:Operating Power Connections
Connect Earth Ground
Wire to earth ground stud
2
) or heavier gauge wire with 600V insula-
Earth
Neutral
Hot
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D21
Black
12 VDC Battery
Red
411AINBX.CDR
Operating Power
Secondary Power Source (batteries)
Observe polarity while connecting the battery. When installing one 12 volt battery for up to 7 Amp Hour applications, connect the supplied battery cable (P/N 75516) by sliding the connector attached to the long red wire onto the
positive (+) battery terminal and the connector attached to the long black wire onto the negative (-) battery terminal.
Tie-wrap or tape the two unused short wires to the long wires.
When installing two 12 volt, 7 Amp Hour batteries (in parallel) for up to 14 Amp Hour applications (60 hour
standby), follow the same procedure as described for one battery except connect the unused short wires to the second
battery. Slide the connector attached to the short red wire onto the positive (+) terminal of the second battery and the
connector attached to the short black wire onto the negative (-) battery terminal of the second battery.
When the panel is ready to have power applied, connect the battery cable plug to connector J3 on the 411UDAC main
circuit board. The battery charger is current-limited and capable of recharging sealed lead acid type batteries. The
charger shuts off when the system is in alarm. Refer to the battery calculations table to determine the correct battery
rating.
CAUTION! Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy
fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek
immediate medical attention.
FIGURE 2-5:Battery Cable Connections
Connect to J3 on 411UDAC
main circuit board
Connect to J3 on 41 1UDAC
main circuit board
Red Wire
Red Wire
Unused wire - tie-wrap or
tape to long wires
One 12 Volt Battery - Up to 7 Amp Hour Applications
Black Wire
Black Wire
Negative (-)
Terminal
Unused wire - tie-wrap or
tape to long wires
Negative (-) Terminal
Positive (+) Terminal
411BATT.CDR
Negative (-)
Terminal
22
Positive (+)
Terminal
411BATT2.CDR
Two 12 Volt Batteries - Up to 14 Amp Hour Applications
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Input Channels
2.4Input Channels
The 411UDAC has four channel inputs. Channel/input field wiring is supervised for opens (trouble), shorts (alarm)
and ground faults (zero ohms impedance between panel and earth ground) by the 411UDAC. All conditions are visually and audibly annunciated and, if programmed, communicated to a Central Station.
Each channel is a Style B (Class B) Initiating Device Circuit with the exception of channel/input 3 which can be configured for Style B or Style D (Class A). All inputs can be connected to normally-open contact type devices. In addition, inputs 1 and 3 can be connected to conventional 2-wire smoke detectors. Refer to Figure 2-6, “Wiring Initiating
Device Circuits,” on page 24 for information on wiring Style B and Style D circuits.
The channel/inputs may be programmed as shown below:
• 2-wire smoke detector (inputs 1 & 3 only)
• Pull station
• Normally-open contact device
• Host panel trouble
• Supervisory
• Supervisory autoresettable
A maximum of five waterflow devices may be used on any circuit programmed as a waterflow zone per NFPA 72.
• Waterflow silenceable
• Waterflow nonsilenceable
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone. This is not recommended, however, since specific and detailed reports will not be possible (particularly critical
when using Contact ID format). For example, the report of general fire alarm versus pull station fire alarm or smoke
detector fire alarm could not be distinguished.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D23
Input Channels
The factory default programming for each channel is as follows:
Channel 1 - fire alarm (2-wire smoke)
Channel 2 - pull station
Channel 3 - fire alarm (2-wire smoke)
Channel 4 - pull station
The following illustration shows Channel 1 connected to 2-wire smoke detectors, Channel 2 connected to manual pull
stations, Channel 3 connected to 2-wire smoke detectors and Channel 4 connected to waterflow devices. In this
example, the factory default programming for Channel 4 must be changed from pull station to waterflow device.
FIGURE 2-6:Wiring Initiating Device Circuits
Zone 1/Channel 1
Zone 2/Channel 2
Zone 3/Channel 3
Zone 4/Channel 4
411UDAC Main Circuit Board
2-Wire Smoke
Detectors
(Class B)
Manual Pull
Stations
(Class B)
2-Wire Smoke
Detectors
(Class A)
Waterflow
Devices
(Class B)
24
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Input Channels
FIGURE 2-7:Typical Addressable FACP Connection to 411UDAC
Note: The addressable monitor module
input, which is being used to monitor th e
411UDAC Relay Output programmed for
DACT Trouble (requires optional 41 1RK
Relay Kit), must be programmed as
'DACT Trouble' at the FACP. The
411UDAC must be programmed as a
Slave Communicator (programming
address 64 set to ‘2’)
411UDAC Relay 2 Output (DACT Trouble)
Channel 2/Zone 2
Program the 411UDAC as follows:
Channel 1 - Normally Open Contact Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory
End-of-Line Resistor
supplied with
Monitor Module
2.2K
EOL
411UDAC
Channel 1/Zone 1
Channel 3/Zone 3
2.2K EOL Channel 4
Supervisory Relay
Alarm Relay
*If the SLC device does not
match the one in this figure,
refer to the SLC manual wiring
conversion charts for legacy
and newer versions of the
modules.
Monitor Circuit Input
Addressable FACP
(must be UL-listed for
Central Station Service
and Remote Signaling
Service)
Trouble Relay
Monitor
UL listed
2.2K EOLs
P/N 27070
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D25
Module*
SLC Loop
9200411A.CDR
Output Circuits
2.5Output Circuits
Notification Appliance Circuit
The 411UDAC provides one Style Y (Class B) NAC (Notification Appliance Circuit). The NAC is supervised
and power-limited and is capable of 1.0 amp of current. Refer to the Device Compatibility Document for a listing
of compatible notification appliances.
Note:
1. The 411UDAC can only be used to supplement host panel NACs.
2. Do not connect strobes to the 411UDAC Notification Appliance Circuit.
Style Y (Class B) Notification Appliance Circuit
(supervised and power-limited).
2.2K ohms, ½ watt P/N 27070
Note: Notification Appliance Circuit
polarity shown in alarm state
Dummy Load NAC circuit with 2.2K ohm, ½ watt
End-of-Line resistor if not being used.
TB4
+
+
+
B+
NAC
Polarized Bell
Polarized Horn
Polarized Horn
+B--
+12V POWER
411ANAC.CDR
26
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Output Circuits
Relay Programming:
The relays are programmable for activation on fire alarm, host panel trouble, fire supervisory, total communication failure and DACT. Refer to “DACT Programming” on page 36. Addresses ‘85 - 88’ are used for programming relay functions and enable.
FIGURE 2-9:Programmable Relay
Note: Relay connections may be power-limited or nonpower-limited, provided that 0.25" spacing is
maintained between conductors of power-limited and nonpower-limited circuits.
Relays automatically change to energized
condition when programmed for Trouble.
RELAY 1RELA Y 2
TB1
NONONCNCCC
Relay 1 - Shown Programmed for Alarm,
Supervisory, or any other function except
DACT Trouble and Host Panel Trouble
(relay contacts shown in deenergized
condition with power applied to 411UDAC)
Relay 2 - Shown Programmed for DACT
Trouble or Host Panel Trouble (relay contacts shown in energized condition with
power applied to 411UDAC)
411ARELE.CDR
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D27
Telephone Circuits
2.6Telephone Circuits
Provision to connect two independent telephone lines is available via two telephone jacks labeled PH1 (Primary)
and PH2 (Secondary). Telephone line control/command is possible via double line seizure as well as usage of an
RJ31X style interconnection. (RJ31X jacks must be ordered separately).
CAUTION: It is critical that the 411UDAC be located as the first device on the incoming telephone circuit to
properly function.
FIGURE 2-11:Wiring Phone Jacks
Green Wire
Tip
Red Wire
Ring
(Primary Lines)
Incoming Telco
Phone Lines
Ring
To Premises Phone
Tip
Tip
Ring
(Secondary Lines)
Incoming Telco
Phone Lines
Green Wire
Red Wire
To Premises Phone
Ring
Tip
411UDAC
Note: Shorting bars
inside RJ31X Jack
removed during
male plug insertion
7 foot Cable (MCBL-7)
Not supplied - Order
Separately
(2 required)
Secondary Phone Line PH2
Primary Phone Line PH1
Male Plug
Connectors
Female
Connectors
411AJAK.CDR
28
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Optional Programmer
2.7Optional Programmer
The Fire-Watch 411 Series DACT Programmer (Model PRO-411) is used to:
switch between the digit a l alarm communicator's five Modes of operation
set the digital alarm communicator's 24 hour internal clock in Real-Time Clock Mode
program the 411UDAC digital alarm communicator in Program Mode
test the status of input and output circuits (including telephone lines) in Troubleshoot Mode
return all digital alarm communicator programming to the factory default settings in Default Mode
To use the PRO-411 Programmer:
1. Remove all power from the 411UDAC
2. Unlock and open the 411UDAC door
3. Connect the Programmer cable to connector J2 located in the lower right corner of the 411UDAC. Note that
the key on the connector must align with the slot in the J2 connector
4. Reapply power to the 411UDAC
5. Operate the Programmer by pressing the MODE key. Enter the appropriate four digit code and then press the
[ENTER/STORE] key.
Note that it is not possible to switch from Normal Mode to any other mode if any of the four Channels is programmed
for fire alarm or fire supervisory and is active, that is, in alarm (shorted).
FIGURE 2-11:Programmer Connection to 411UDAC
NOTE: The Fire•Watch 411 Series DACT Programmer
must be removed when not in use.
411UDAC
Programmer
Cable attached
to Programmer
J2 connector
411A-PRO.CDR
- +
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D29
UL Power-limited Wiring Requirements
2.8UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any nonpower-limited circuit wiring. Furthermore, all power-limited
and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A
typical wiring diagram for the 411UDAC is shown below.
FIGURE 2-12:Typical UL Power-limited Wiring Diagram
Note: Relay connections may be power-limited or nonpowerlimited, provided that 0.25" spacing is maintained between
conductors of power-limited and nonpower-limited circuits.
Nonpower-limited Circuits
Power-limited Circuits
30
411AULPW.CDR
AC Power
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Modes of Operation
CHAPTER 3Modes of Operation
The 411UDAC has five operational modes:
• Normal Mode
• Real Time Clock Mode
• Program Mode
• Troubleshoot Mode
• Default Mode
The operational mode for the 411UDAC is Normal Mode. The operator is able to switch between any modes of operation provided no alarm events are active in the system. It should be noted that the unit will not respond to input activations while in any mode except Normal Mode.
Access to any other Mode requires connection of the PRO-411 DACT Programmer which consists of a keypad and
display. Refer to Figure 3-1, “Programmer Keypad,” on page 32.
Note that if the 411UDAC is configured to operate as a Slave Communicator, it will attempt to transmit all panel status to a Central Station. If set to operate in the Test Communicator configuration, the 411UDAC will function as a
local slave panel only without transmitting panel status to a Central Station.
3.1Normal Mode
Normal Mode is the standard (default) mode of operation for the 411UDAC. The unit continuously monitors the status of the four input channels as well as the status of the onboard digital communicator. If no activity is detected on
the four input channels (no shorts or opens) and the 411UDAC is operating free of internal troubles, the unit will display the following conditions:
All LEDs are off except the AC Power LED
NAC output is off
Onboard piezo sound er is off
The relays are in their normal deactivated state
Communicator is not transmitting to the Central Station
The 411UDAC transmits system status reports to a central station, if programmed to do so, via the public switched
telephone network. T wo supervised telephone line connections are made to interface the digital communicator to the
telephone lines. Both telephone lines are supervised by the 411UDAC for proper voltage.
The 411UDAC is capable of line seizure on both the primary and secondary telephone line interfaces. Any time the
digital communicator detects the necessity to call the Central Station, line seizure will disconnect any local premises
phones sharing the same telephone line. Sharing of phone lines, for fire systems, must be approved by the Local
Authority Having Jurisdiction. All transmissions to the Central Station will be sent over the Primary phone line. In
the event of a noisy or faulty phone line, transmissions will be sent over the backup Secondary phone line.
Transmission options exist to:
• send reports to the secondary phone number as backup only
• send reports to both the primary and secondary phone numbers
• send reports to the first available central station phone number
If 10 total attempts to communicate are unsuccessful, the 411UDAC will turn on the Communication Fail LED.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D31
Normal Mode
The 411UDAC meets NFPA 72 requirements for Remote Station Protective Signaling Service and Central Station
Signaling Service reporting requirements for: (a) the type of signal, (b) condition and (c) location of the reporting
premises. See “Central Station Communications” on page 55, for additional information.
The 411UDAC can be switched from Normal Mode to any other Mode, provided no channel programmed for fire
alarm or fire supervisory is active, that is, in alarm (shorted). The PRO-411 DACT Programmer, for use with the
Fire•Watch 411 Series, must be connected to the 411UDAC in order to change from mode to mode.
3.1.1 Programmer Key Functions
FIGURE 3-1:Programmer Keypad
PR411KEY.CDR
Select operating mode
Increment memory address
Address entry keys are 0 to 9
Data entry keys are 0 to 9 and A to F
Decrement memory address
One press = first memory address
Two presses = type any address
Save data, go to next address
MODE KEY
Pressing the MODE key followed by a valid 4-digit numerical code and the [ENTER/STORE] key selects one of
the five modes of operation. To enter Normal Mode from any other mode, press the MODE key followed by
6676 and then [ENTER/STORE].
6676 spells NORM on a Touch-Tone® phone.
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key . Note that as
information is entered into the 411UDAC, the digits will scroll across the Programmer display from right to left.
___6
__66
_667
6676
A pause of up to 10 seconds between each number is allowed while entering the code.
32
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Normal Mode
LAMP TEST KEY
Pressing the Lamp Test key on the Programmer , while the digital communicator is in Normal Mode, will cause the
front panel LEDs and all segments of the four 7-segment display on the 411UDAC to light. A Lamp Test can only
be performed in Normal Mode. The Lamp Test key can also be used in Troubleshoot Mode to view the 12 volt
resettable power value.
1st EVENT KEY
This key, along with the UP and DOWN arrow keys, are used only in Program Mode. Press the 1st EVENT key
at any time to display the first program memory address and its content. The following may be displayed on the
Programmer:
00_F
(address)
(data)
If the 1st EVENT key is pressed a second time, the following will be displayed on the Programmer display:
0.
Digit to be programmed
The contents of any address can be viewed by entering the digits of the desired address. For example, to view the
contents of address 86, press the '8' key on the keypad. '8' will appear as the first digit in the display, a blank will
appear in the position of the second digit and the decimal point will move one position to the right, indicating that
the next digit can now be entered.
8_.
Digit to be programmed
Press the '6' key on the keypad. '6' will appear as the second digit on the display and the decimal point will move
one position to the right. Press the [ENTER/STORE] to view the contents of address 86.
86_.
DOWN ARROW
Use the DOWN arrow key to decrement the memory address and view its content.
UP ARROW
Use the UP arrow key to increment the memory address and view its content.
[ENTER/STORE]
Stores entry into nonvolatile E
2
memory located on the 411UDAC printed circuit board, then increments to the
next higher address.
3.1.2 Programmer Display
Four 7-segment red LED characters provide visual display of information in the various modes of operation.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D33
Real Time Clock Mode
3.2Real Time Clock Mode
Real Time Clock Mode is entered by pressing the MODE key followed by the 4-digit entry code 2525 and pressing
the [ENTER/STORE] key.
2525 spells CLCK on a Touch-Tone
®
phone.
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key . Note that as
information is entered into the 411UDAC, the digits will scroll across the Programmer display from right to left.
___2
__25
_252
2525
A pause of up to 10 seconds between each number is allowed while entering the code. After pressing the [ENTER/
STORE] key, the 411UDAC will be in Real Time Clock Mode. A maximum of 10 minutes idle time is allowed at
this point before beginning program entries and between each key stroke, otherwise, the 411UDAC will return to
Normal Mode. Note that the time is not stored until the fourth and final digit is selected and the [ENTER/STORE]
key is pressed. If the 411UDAC returns to Normal Mode prior to entering the fourth digit, no changes will be stored
and the original time is retained.
On entering Real Time Clock Mode, 0.001 will appear on the Programmer display:
0.001
Digit to be programmed
The time is displayed in military time. Note the position of the decimal point in the display. This indicates that the
first digit to be programmed is the one to the left of the decimal point. To program the first hour digit, press the corresponding number on the Programmer keypad and then press the [ENTER/STORE] key. For example, to program
2:00 PM (1400 in military time), press '1' on the keypad and th en the [ENTER/STORE] key. The number '1' will
appear as the far left digit and the decimal point will move one position to the right indicating that the second digit
from the left is now ready for programming.
10.01
Digit to be programmed
Enter the second hour digit (4 in this example) and press the [ENTER/STORE] key. The number '4' will appear as
the digit second from the left and the decimal point will move one position to the right indicating that the third digit
from the left is now ready for programming.
140.1
Digit to be programmed
Enter the first minute digit (0 in this example) and press the [ENTER/STORE] key. The number '0' will appear as
the digit third from the left and the decimal point will move one position to the right indicating that the fourth digit
from the left is now ready for programming.
1400.
Digit to be programmed
34
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
Enter the second minute digit (0 in this example) and press the [ENTER/STORE] key . The number '0' will appear as
the digit fourth from the left. Following the entry of the fourth and final digit, the operating mo de will immediately
switch to Normal Mode, indicating that programming of the time is now comp leted.
T o exit Real Time Clock Mode before completing clock programm ing, pr ess the MODE key, followed by the 4-digit
code for an alternate mode and then the [ENTER/STORE] key. During Real T ime Clock Mode, if no key is pressed
within 10 minutes, the 411UDAC will revert to Normal Mode.
Note that upon power-up, the internal clock starts running at 00:01 midnight. It must be changed so that the
411UDAC can accurately call in test signals to the Central Station. Upon power loss or on entering Default Mode,
the clock reverts to 00:01 midnight and must be reset.
3.3Program Mode
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must
be limited to specific values or not used at all as indicated below:
Program feature
or option
Trouble Call LimitN
Permitted in
UL 864? (Y/N)
Possible settings
Program Address 96 = 0 (factory default): unlimited
calling to Central Station for any trouble condition
Program Address 96 = 1: limits call for each unique
trouble to 10 within a 24 hour period
Settings permitted
in UL 864
Program Address 96
= 0 for unlimited
Central Station
trouble calls
All programming selections made during Program Mode are stored in nonvolatile Electrically-Erasable Programmable Read-only Memory (EEPROM). This ensures that the 411UDAC will retain all entries made in Programming
Mode even if power is removed.
The user must program the primary and secondary phone numbers, account nu mbers, 24-hour test report times and
verify event codes for each Central Station account. The 411UDAC is shipped with the program options/features
already factory programmed. Alternative options/features may be programmed if desired. If all factory default settings are acceptable, programming is complete.
Program Mode is entered by pressing the MODE key followed by the 4-digit program mode entry code 7764 and
pressing the [ENTER/STORE] key.
7764 spells PROG on a Touch-Tone
If an incorrect key is entered, reenter the proper 4-digit code before
®
phone.
pressing the [ENTER/STORE] key . Note that as
information is entered into the 411UDAC, the digits will scroll across the Programmer display from right to left.
___7
__77
_776
7764
A pause of up to 10 seconds between each number is allowed while entering the code. After pressing the [ENTER/
STORE] key, the 411UDAC will be in Program Mode. A maximum of 10 minutes idle time is allowed at this point
before beginning program entries and between each key stroke, otherwise, the unit will return to Normal Mode. All
entries made prior to the 10 minute time-out are valid and are stored.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D35
Program Mode
A
Once in Program Mode, the 411UDAC will:
Light the DACT Trouble LED
Activate Relay if programmed for DACT trouble
Ignore all other keys other than those mentioned in this section
Display 00_F on the Programmer display
Continue to communicate any events not previously acknowledged at a central station prio r to entering
Programming Mode
Communicate an 'Off Normal' event to the Central Station
Turn off piezo
While in Program Mode, the first three locations on the left of the Programmer display represent the memory address
and the last location (farthest right) represents the contents of the memory address. The first address displayed is
shown below:
00_F
(address)
(data)
Certain program items will be locked from editing if the communicator is active (dialing, transmitting, etc.). These
programming locations are ‘00-19’ Primary Central Station Phone Number, ‘20’ Primary Central Station Communications Format, ‘21-24’ Primary Central Station Account Code, ‘30-49’ Secondary Central Station Phone Number,
‘50’ Secondary Central Station Communications Format, ‘51-54’ Secondary Central Station Account Code, ‘61’
Central Station Backup Reporting and ‘145-end’ Event Codes.
To unlock these locations, either wait until the com mun icato r stops transmitting or disable the communicator via
address location 64 by changing the content of this address to ‘0.’
When desired changes have been completed, exit Programming Mode by pressing the MODE key, followed by the
4-digit code for an alternate mode and then the [ENTER/STORE] key. During Program Mode, if no key is pressed
within 10 minutes, the unit will revert to Normal Mode.
The Programmer cable should not be removed from the 411UDAC unless the unit is in Normal Mode. If the Programmer cable is removed while the 411UDAC is in a Mode other than Normal Mode, the communicator will automatically revert to Normal Mode following a 10 minute
Troubleshoot Mode when the cable is removed, the 411UDAC will revert to Normal Mode following a 20 minute
time-out period. Note that if the Programmer is in
time-out period.
3.3.1 DACT Programming
Primary Central Station Phone Number (00 - 19)
The first twenty addresses (00 - 19) are factory set to 'F' (00_F to 19_F). Programming is done as follows:
If your phone number is 484-7161, press 4.
The display will read 00_4.
Press [ENTER/STORE] to save the entry to memory and increment to the next address 01_F.
Enter the remaining numbers in their respective addresses as shown below:
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as
dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
36
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must remain in all unused phone number addresses)
If the first digit of the Primary Central Station Phone Number remains ‘F’ and the digital communicator is enabled for
transmission to a Central Station, a primary phone number fault will be generated. The phone number must begin
with a digit other than ‘F.’
New FCC regulations allow extra digits to the CIC (Carrier ID Code), to identify the long distance carrier. The
expanded phone number field of 20 digits facilitates this function. Simply enter the digits required by the telephone
company if desired.
Primary Central Station Number Communication Format (20)
One location is needed to select the Communication Format to the primary phone number. Address 20 is used for
this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
Consult the Central Station for proper Format selection. For any Format chosen, all event codes are automatically programmed by the 41 1UDAC. Refer to Table 3-2, “4+2 Standar d and 4+2 Expr ess Formats - Primary,” on
page 40, Table 3-3, “All 3+1, 4+1 and 4+2 Expanded Formats - Primary,” on page 41 and Table 3-1, “Ademco
Contact ID Format - Primary,” on page 39.
Event Codes - Setting Entries
The Format selected in address 20 will cause the 411UDAC to automatically program addresses 145 - 228 with the
factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior to altering the event code settings. An entry of all zeros for any event code will cause the communicator to NOT
transmit the
report. Transmission of reports to either or both Central Station phone numbers may be disabled.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D37
Program Mode
Upon accessing the first event code address (address 145) shown in Table 3-2 , the following may be displayed on the
Programmer 7-Segment Display, if the corresponding Format was selected in address 20.
1451
(address)
(data)
The first three locations on the left of the Programmer displ ay represent the memory address 145 of the Format previously selected in address 20. The last location 1 (farthest right) represents the contents of memory address 145
(which is the first digit of the event code).
The following T ables list the data which is automatically programmed for each Format that can be selected in address
20. The addresses shown in each Table contain the Setting data which is automatically programmed by the
411UDAC. To change the value, key in the new digit and then press the [ENTER/STORE] key to save the new
value. Use the Up and Down Arrow keys to increment to the next address or decrement to the previous address.
38
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
Ademco Contact ID Format Primary Central Station Event Codes
If 'E' is entered for address 20, the following data is automatically programmed for the Primary Central Station
phone number event codes. Enter '000' for the Setting to disable the report to the Central Station. The Channel #
is not programmable.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D39
Program Mode
4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes
If ‘1, A or C’ is entered for address 20, the following data is automatically programmed for the Primary Central
Station phone number event codes. Enter '00' for the Setting to disable the report to the Central Station.
TABLE 3-2: 4+2 Standard and 4+2 Express Formats - Primary
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
All 3+1, 4+1 and 4+2 Expanded Formats Primary Central Station Event Codes
If ‘0, 2, 3, 4, 5, 6, 7, 8 ,9, B or D’ is entered for address 20, the following data is automatically programmed for the
Primary Central Station phone number event codes. Enter '0' for the Setting to disable the report to the Central
Station.
TABLE 3-3: All 3+1, 4+1 and 4+2 Expanded Formats - Primary
AddressDescriptionSetting
145Primary # Input Channel 1 Active Event Code1
146Primary # Input Channel 2 Active Event Code1
147Primary # Input Channel 3 Active Event Code1
148Primary # Input Channel 4 Active Event Code1
149Primary # Input Channel 1 Fault Event CodeF
150Primary # Input Channel 2 Fault Event CodeF
151Primary # Input Channel 3 Fault Event CodeF
152Primary # Input Channel 4 Fault Event CodeF
153Primary # AC Power Fault Event Code9
154Primary # Earth Fault Event Code6
155Primary # Low Battery Fault Event Code6
156Primary # No Battery Fault Event Code6
157Primary # Phone Line 1 Voltage Fault Event Code6
158Primary # Phone Line 2 Voltage Fault Event Code6
159Primary # NAC Fault Event Code6
160Primary # Charger Fault Event Code4
161Primary # Phone Number 1 Communication Fault Event Code6
162Primary # Phone Number 2 Communication Fault Event Code6
163Primary # System Off Normal Fault Code6
164Primary # Input Channel 1 Active Restore CodeE
165Primary # Input Channel 2 Active Restore CodeE
166Primary # Input Channel 3 Active Restore CodeE
167Primary # Input Channel 4 Active Restore CodeE
168Primary # Input Channel 1 Fault Restore CodeD
169Primary # Input Channel 2 Fault Restore CodeD
170Primary # Input Channel 3 Fault Restore CodeD
171Primary # Input Channel 4 Fault Restore CodeD
172Primary # AC Voltage Fault Restore Code9
173Primary # Earth Fault Restore CodeA
174Primary # Low Battery Fault Restore CodeA
175Primary # No Battery Fault Restore CodeA
176Primary # Phone Line 1 Voltage Fault Restore CodeA
177Primary # Phone Line 2 Voltage Fault Restore CodeA
178Primary # NAC Fault Restore CodeA
179Primary # Charger Fault Restore Code
180Primary # Phone Number 1 Communication Fault Restore CodeA
181Primary # Phone Number 2 Communication FAult Restore CodeA
182Primary # System Off Normal Restore CodeA
183Primary # System Test Message9
184Primary # System Abnormal Test Message
185Primary # Upload/Download Request Code7
186Primary # Upload Successful Code7
187Primary # Download Successful Code7
188Primary # Upload/Download Failed Code7
F
1
1
Note: For Formats ‘B’ and ‘D’, this address is defaulted to ‘9’ instead of ‘F.’
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D41
Program Mode
Primary Central Station Number Account Code (21 - 24)
The four locations at addresses 21 - 24 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits
entered must match the format selection. If programming '2, 3, 4 or 5' into address 20, enter three digits (one digit
each in locations 21, 22 and 23 - location 24 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into
address 20, enter four digits (one each in locations 21, 22, 23 and 24).
Primary Central Station Number 24 Hour Test Time (25 - 28)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four
locations, from addresses 25 - 28. The default is 00:00 (12:00 midnight). The limits for each location are as follows (do not use values of A - F as entries).
25: enter 0, 1 or 2
26: enter 0 - 9
27: enter 0 - 5
28: enter 0 - 9
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (29)
The test report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If other te st rep ort times are needed, enter 1 = 12 hour,
2 = 8 hour or 3 = 6 hour.
Secondary Central Station Phone Number (30 - 49)
Addresses 30 - 49 are factory set to 'F' (30_F to 49_F). Programming is typically done as follows:
If your phone number is 484-7161, press 4.
The display will read 30_4.
Press [ENTER/STORE] to save the entry to memory and increment to the next address 31_F.
Enter the remaining numbers in their respective addresses as shown below:
Valid entries for both the primary and secondary phone numbers are 0 to 9 and A to F with the numeric digits as
dialed numbers and the hexadecimal digits representing the following functions:
• A = * on a Touch-Tone phone keypad
• B = # on a Touch-Tone phone keypad
• C = look for secondary dial tone for up to two seconds (then dial anyway)
• D = three second pause
• E = five second pause
• F = end of phone number (Note: F must remain in all unused phone number addresses)
If the first digit of the Secondary Central Station Phone Number remains ‘F’ and the digital communicator is enabled
for transmission to a Central Station, a secondary phone number fault will be generated. The phone number must
begin with a digit other than ‘F.’
42
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
Secondary Central Station Number Communication Format (50)
One location is needed to select the Communication Format to the secondary phone number. Address 50 is used
for this purpose. The factory default setting for this address is 'E', which is Contact ID Format. You may enter '0'
through 'D' in place of the default, then press [ENTER/STORE]. Choose from the list of formats below:
The Format selected in address 50 will cause the 411UDAC to automatically program addresses 229 - 312 with the
factory default settings. Any of the Event Code settings may be altered. Consult your Central Station prior to altering the event code settings. An entry of all zeros for any event code will cause the communicator to NOT
transmit the
report. Transmission of reports to either or both Central Station phone numbers may be disabled.
Refer to “Central Station Communications” on page 55 for information on Format reporting.
Upon accessing the first event code address which is 229 (Refer to Table 3-5, “4+2 Standard and 4+2 Express Formats - Secondary,” on page 45), the following may be displayed on the Programmer’s 7-Segment Display, if the corresponding Format was selected in address 50.
2291
(address)
(data)
The first three locations on the left of the Programmer’s display represent the memory address 229. The last location
1 (farthest right) represents the contents of memory address 229 which is the first digit of the event code.
The following Tables list the data which is automatically programmed for each Format that can be selected in address
50. The addresses shown in each Table contain the event code Setting data which is automatically programmed by
the 411UDAC. To change the value, key in the new digits and then press the [ENTER/STORE] key to save the new
value. Use the Up and Down Arrow keys to increment to the next address or decrement to the previous address.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D43
Program Mode
Ademco Contact ID Format Secondary Central Station Event Codes
If ‘E’ is entered for address 50, the following data is automatically programmed for the Secondary Central Station
phone number event codes. Enter '000' for the Setting to disable the report to the Central Station.
TABLE 3-4: Ademco Contact ID Format - Secondary
Channel/
AddressDescriptionSetting
233 - 235Secondary # Input Channel 1 Active Event Code111001
236 - 238Secondary # Input Channel 2 Active Event Code115002
239 - 241Secondary # Input Channel 3 Active Event Code111003
242 - 244Secondary # Input Channel 4 Active Event Code115004
245 - 247Secondary # Input Channel 1 Fault Event Code380001
248 - 250Secondary # Input Channel 2 Fault Event Code380002
251 - 253Secondary # Input Channel 3 Fault Event Code380003
254 - 256Secondary # Input Channel 4 Fault Event Code380004
257 - 259Secondary # AC Voltage Fault Event Code301000
260 - 262Secondary # Earth Fault Event Code310000
263 - 265Secondary # Low Battery Fault Event Code302000
266 - 268Secondary # No Battery Fault Event Code311000
269 - 271Secondary # Phone Line 1 Voltage Fault Event Code351000
272 - 274Secondary # Phone Line 2 Voltage Fault Event Code352000
275 - 277Secondary # NAC Fault Event Code321000
278 - 280Secondary # Charger Fault Event Code300000
281 - 283Secondary # Phone Number 1 Communication Fault Event Code354001
284 - 286Secondary # Phone Number 2 Communication Fault Event Code354002
287 - 289Secondary # System Off Normal Fault Event Code308000
290 - 292Secondary # System Test Message602000
293 - 295Secondary # System Abnormal Te st Message608000
296 - 298Secondary # Upload/Download Request Code411000
299 - 301Secondary # Upload Successful Code416000
302 - 304Secondary # Download Successful Code412000
305 - 307Secondary # Upload/Download Failed Code413000
Input #
44
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
4+2 Standard and 4+2 Express Formats Secondary Central Station Event Codes
If 1, A or C is entered for address 50, the following data is automatically programmed for the Secondary Central Station phone number event codes. Enter '00' for the Setting to disable the report to the Central Station.
TABLE 3-5: 4+2 Standard and 4+2 Express Formats - Secondary
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D45
Program Mode
All 3+1, 4+1 and 4+2 Expanded Formats Secondary Central Station Event Codes
If 0, 2, 3, 4, 5, 6, 7, 8 ,9, B or D is entered for address 50, the following data is automatically programmed for the
Secondary Central Station phone number event codes. Enter '0' for the Setting to disable the report to the Central
Station.
TABLE 3-6: Al l 3+1, 4+ 1 and 4+2 Expanded Fo rmats - Secondary
AddressDescriptionSetting
233Secondary # Input Channel 1 Active Event Code1
234Secondary # Input Channel 2 Active Event Code1
235Secondary # Input Channel 3 Active Event Code1
236Secondary # Input Channel 4 Active Event Code1
237Secondary # Input Channel 1 Fault Event CodeF
238Secondary # Input Channel 2 Fault Event CodeF
239Secondary # Input Channel 3 Fault Event CodeF
240Secondary # Input Channel 4 Fault Event CodeF
241Secondary # AC Power Fault Event Code9
242Secondary # Earth Fault Event Code6
243Secondary # Low Battery Fault Event Code6
244Secondary # No Battery Fault Event Code6
245Secondary # Phone Line 1 Voltage Fault Event Code6
246Secondary # Phone Line 2 Voltage Fault Event Code6
247Secondary # NAC Fault Event Code6
248Secondary # Charger Fault Event Code4
249Secondary # Phone Number 1 Communication Fault Event Code6
250Secondary # Phone Number 2 Communication Fault Event Code6
251Secondary # System Off Normal Fault Code6
252Secondary # Input Channel 1 Active Restore CodeE
253Secondary # Input Channel 2 Active Restore CodeE
254Secondary # Input Channel 3 Active Restore CodeE
255Secondary # Input Channel 4 Active Restore CodeE
256Secondary # Input Channel 1 Fault Restore CodeD
257Secondary # Input Channel 2 Fault Restore CodeD
258Secondary # Input Channel 3 Fault Restore CodeD
259Secondary # Input Channel 4 Fault Restore CodeD
260Secondary # AC Voltage Fault Restore Code9
261Secondary # Earth Fault Restore CodeA
262Secondary # Low Battery Fault Restore CodeA
263Secondary # No Battery Fault Restore CodeA
264Secondary # Phone Line 1 Voltage Fault Restore CodeA
265Secondary # Phone Line 2 Voltage Fault Restore CodeA
266Secondary # NAC Fault Restore CodeA
267Secondary # Charger Fault Restore Code5
268Secondary # Phone Number 1 Communication Fault Restore CodeA
269Secondary # Phone Number 2 Communication FAult Restore CodeA
270Secondary # System Off Normal Restore CodeA
271Secondary # System Test Message9
272Secondary # System Abnormal Test Message
273Secondary # Upload/Download Request Code7
274Secondary # Upload Successful Code7
275Secondary # Download Successful Code7
276Secondary # Upload/Download Failed Code7
F
1
46
1
Note: For Formats ‘B’ and ‘D’, this address is defaulted to ‘9’ instead of ‘F.’
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
Secondary Central Station Number Account Code (51 - 54)
The four locations at addresses 51 - 54 default to all '0's. Valid entries are 0 - 9 and A - F. The number of digits
entered must match the format selection. If programming '2, 3, 4 or 5' into address 50, enter three digits (one digit
each in locations 51, 52 and 53 - location 54 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into
address 50, enter four digits (one each in locations 51, 52, 53 and 54).
Secondary Central Station Number 24 Hour Test Time (55 - 58)
Use military time when entering the 24 hour 'test' time. The 24 hour test report to phone number 1 takes up four
locations, from addresses 55 - 58. The default is 00:00 (12:00 midnight). The limits for each location are as follows (do not use values of A - F as entries):
55: enter 0, 1 or 2
56: enter 0 - 9
57: enter 0 - 5
58: enter 0 - 9
Secondary Central Station Number 24/12/8/6 Hour Test Time Interval (59)
The test report sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If other test report times are needed, enter 1 = 12 hour,
2 = 8 hour or 3 = 6 hour.
AC Loss Reporting Delay (60)
Enter a digit of 0 - 9 or A - F corresponding to the number of hours to be delayed in reporting the loss of AC
power. The factory default is '2' for 2 hours. The valid entries are '0' = no delay; '1' = 1 hours; '2' = 2 hours;
'3' = 6 hours; '4' = 7 hours; '5' = 8 hours; '6' = 9 hours; '7' = 10 hours; '8' = 11 hours; '9' = 12 hours; 'A' = 13 hours;
'B' = 14 hours; 'C' = 15 hours; 'D' = 16 hours; 'E' = 17 hours; 'F' = 18 hours.
Note: UL requires a minimum of 2 hours delay.
Backup Reporting (61)
Leaving address 61 at '0' means that reports will be transmitted to the secondary Central Station phone number
only if attempts to communicate to the primary Central Station phone number are unsuccessful. Programming a
'1' causes all reports to be transmitted to both the primary and secondary Central Station phone numbers. Programming a '2' causes reports to go to the first available receiver.
!
CAUTION: Do not alter this entry while the digital communicator is active.
Reserved for Future Use (62)
DACT Trouble Reminder (63)
The factory default entry of '0' in address location 63 disables the trouble reminder feature. Selecting '1' for location 63 will cause a reminding beep (after the Silence switch is pressed) every 15 seconds for active alarms and
every two minutes during a DACT trouble condition. The beeps from the onboard piezo sounder will occur until
the alarm or DACT fault is cleared. The piezo sounder will begin beeping at a rate of one second On and one
second Off after 24 hours unless the DACT fault has been cleared.
Operational Mode Selection (64)
The factory default setting is ‘0’ for latching inputs and the onboard communicator disabled. This prevents the
unit from transmitting status information to the Central Station(s).
TABLE 3-7: 411UDAC Operational Modes
Address 64 Setting411UDAC Operational Mode411UDAC Function
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D47
Program Mode
Input Channel 1 Function Selection (65)
1
Factory default for Channel 1 is '0' for activation on fire alarm (2-wire smoke). Enter '1' for pull station; '2' for
normally open contact device; '3' for host panel trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
Input Channel 2 Function Selection (66)
1
Factory default for Channel 2 is '1' for pull station. Enter '2' for normally open contact device; '3' for host panel
trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
Note that '0' is not a valid entry.
Input Channel 3 Function Selection (67)
1
Factory default for Channel 3 is '0' for activation on fire alarm (2-wire smoke). Enter '1' for pull station; '2' for
normally open contact device; '3' for host panel trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
Input Channel 4 Function Selection (68)
1
Factory default for Channel 4 is '1' for pull station. Enter '2' for normally open contact device; '3' for host panel
trouble; '4' for fire supervisory; '5' for fire supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
Note that '0' is not a valid entry.
Input Channel 1 Delay Timer (69 - 71)
2
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 1 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not
be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, t he delay timer will als o delay activ ation of
the relay , piezo sounder and LEDs.
Input Channel 2 Delay Timer (72 - 74)
2
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 2 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not
be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, t he delay timer will als o delay activ ation of
the relay , piezo sounder and LEDs.
Input Channel 3 Delay Timer (75 - 77)
2
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 3 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not
be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, t he delay timer will als o delay activ ation of
the relay , piezo sounder and LEDs.
1. Changing the input function will automatically change the correspond ing Primary and Secondary event codes to reflect the new
input function. The Communication Format should be programmed first, followed by the Input Channel Function. See
“Events and Default Event Codes” on page 80.
2. This timer does not delay LED or Output Relay activation and is not used for channels programmed as AC Loss circuits.
48
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
Input Channel 4 Delay Timer (78 - 80)
1
The Delay Timer is used to delay digital communicator transmission to a Central Station when the Input Channel
is activated. Input Channel 4 Delay Timer is factory set to '000' seconds for no delay. The timer may be programmed for a delay of from 0 to 179 seconds. Inputs programmed for fire alarm, pull station, host control panel
trouble and fire supervisory, must not
be delayed. A delay, therefore, cannot be selected for inputs programmed
for these fire applications. If the input is set for a waterflow function, the delay timer will also delay activation of
the relay, piezo sounder and LEDs.
Touchtone/Rotary Select for Primary Phone (81)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the primary phone line. Select '1'
for rotary dialing.
Make/Break Ratio for Primary Phone (82)
This address is used only if a '1' has been programmed for address 81. The Make/Break ratio is factory set to '0'
which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (83)
A '0' programmed in this address by the factory, triggers Touchtone dialing over the secondary phone line. Select
'1' for rotary dialing.
Make/Break Ratio for Secondary Phone (84)
This address is used only if a '1' has been programmed for address 83. The Make/Break ratio is factory set to '0'
which is 67/33 ratio, but may be changed to '1' which is 62/38 ratio.
Output Relay #1 Enable (85)
The factory default setting for Output Relay #1 is '0' for disabled. Enter '1' to enable the relay.
Output Relay #1 Function Selections (86)
The Output Relay can be programmed to activate for any one of six conditions. The factory default for address 86
is '0' for activation on fire alarm. Program a '1' for host panel trouble; '2' for DACT trouble; '3' for latching fire
supervisory; '4' for autoresettable fire supervisory; '8' for total communication failure.
Output Relay #2 Enable (87)
The factory default setting for Output Relay #2 is '0' for disabled. Enter '1' to enable the relay.
Output Relay #2 Function Selections (88)
Output Relay #2 can be programmed to activate for any one of six conditions. The factory default for address 88
is '2' for activation on DACT trouble. Program a '0' for activation on fire alarm; '1' for host panel trouble; '3' for
latching fire supervisory; '4' for autoresettable fire supervisory; '8' for total communication fail ure.
Reserved for Future Use (89)
Leave default setting of '0'
Reserved for Future Use (90)
Leave default setting of '0'
1. This timer does not delay LED or Output Relay activation and is not used for channels programmed as AC Loss circuits.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D49
Program Mode
Alarm Verification Enable (91)
Alarm verification works only on zones programmed as 2-wire smoke detector zones (i.e. zones 1 and 3). After
detecting an alarm, the panel removes power from two-wire smoke zones for 6 seconds, resetting all 2-wire smoke
detectors. Power is reapplied and a 12 second retard period allows detectors to stabilize. During the retard/reset
period of 18 seconds, subsequent alarms by the same initiating zone are ignored. An alarm detected on any other
2-wire detector zone during the retard period will cause immediate verified alarms. A subsequent alarm on the
initiating zone occurring within the confirmation time will cause a verified alarm. Note: Mixing devices on zones
designated as 2-wire smoke zones is not recommended. The communicator will not transmit a signal to the Central Station signifying that alarm verification is in progress.
During the alarm verification period, access to other modes of operation is prevented.
FIGURE 3-2:Verification Timing Diagram
0 Sec.
Detector Alarm Verification
Detector Zone Goes Into Alarm
Different Detector Zone Alarm
6 Sec.
RESET RETARD
Alarm IgnoredPanel Processes Alarm if Same Detector Zone is Still in Alarm
18 Sec.
18
ALARM VERIFICATION PERIOD
60 SECOND CONFIRMATION TIME
Panel Immediately Processes Alarm
Factory Default is no verification which is an entry of '0'. Entering '1' enables verification. Alarm Verification is
ignored if the 411UDAC is configured for nonlatching Slave Communicator operation or Test Mode.
Note: consult local Authority Having Jurisdiction (AHJ) prior to altering this address.
Setting address 92 to '1' prevents the silencing or resetting of the Notification Appliance Circuit for one minute
following an alarm. The factory default setting is '0' for no silence inhibit.
Autosilence Notification Appliance Circuit (93)
The Notification Appliance Circuit may be autosilenced after a programmed time interval between 5 and 30
minutes. Enter '1' for 5 minute autosilence; '2' for 10 minutes; '3' for 15 minutes; '4' for 20 minutes; '5' for 25
minutes; '6' for 30 minutes. The factory default is '0' for no autosilence.
78 Sec.
Restoral Method (94)
Note: Restoral Method refers to the communication of Restoral Events to a Central Station. It has no effect on the
actual input circuit restoral itself.
• Typical Restoral Method - ‘0’ entry programs the panel to transmit each input circuit restoral, as it occurs, to
the Central Station. In Slave Mode, this means that as soon as an input restores, the communicator will
immediately transmit the Restoral Event to the Central Station. In Stand-alone Mode, the restoral of inputs
programmed as Autoresettable Supervisory will also cause the communicator to transmit a Restoral Event
immediately. All other input types in Stand-alone Mode are latching and their restoral will not communicate a
Restoral Event until the Reset Switch is pressed.
• Conditional Restoral Method #1 - ‘1’ entry programs the panel to transmit each input circuit restoral, as it
occurs, to the Central Station. In Slave Mode, this means that as soon as an input restores, the communicator
will immediately transmit the Restoral Event to the Central Station. In Stand-alone Mode, the restoral of
inputs programmed as Autoresettable Supervisory will also cause the communicator to transmit a Restoral
Event immediately. All other input types in Stand-alone Mode are latching and the communication of their
Restoral Events are dependent upon an after-reset condition.
50
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Program Mode
The input circuit must be physically clear of an input short upon completion of the reset period. If, and only if,
the input circuit is normal (clear of an input short) after the reset period will the communicator transmit a
Restoral Event to the Central Station. If the input circuit remains active after the reset period, no transmission
will take place.
• Conditional Restoral Method #2 - ‘2’ entry programs the panel to transmit each input circuit restoral if, and
only if, all input circuits are normal (clear of an input short). In Slave Mode, this means that as soon as all
input circuits are restored, the communicator will transmit the Restoral Event(s) to the Central Station. In
Stand-alone Mode, the restoral of inputs programmed as either Autoresettable Supervisory will cause the
communicator to transmit a Restoral Event if, and only if, all input circuits are normal
1
. All other input types
in Stand-alone Mode are latching and the communication of their Restoral Events are dependent upon an
after-reset condition. If, and only if, all input circuits are normal (clear of an input short) after the reset period
will the communicator transmit a Restoral Event(s) to the Central Station. If any input circuit remains active
after the reset period, no transmission will take place, even if other input circuits are truly restored.
T able 3-8 describes the events that would take place after the reset period, according to each unique Communicator Restoral Method. It is assumed that an input circuit is active before reset.
TABLE 3-8: Restoral Methods
Input Circuit
After ResetTypical Restoral Method
All local annunciation of the
active event stops. The short is
rediscovered after reset period
and local annunciation begins
SHORTED
again.
1
The panel communicates:
1. A Restoral Event
2. An Active Event
2
Conditional Restoral
Method #1
All local annunciation of the
active event stops. The short is
rediscovered after reset period
and local annunciation begins
1
again.
The panel communicates
nothing because this input is
still in an active state after
reset.
Conditional Restoral
Method #2
All local annunciation of the
active event stops. The short is
rediscovered after reset period
and local annunciation begins
1
again.
The panel communicates
nothing because an input (can
be any input) is still in an
active state after reset.
All local annunciation of the
active event stops. The circuit
is found to be in a normal state.
If, and only if, all
input circuits
are found to be in a normal
state will the panel
communicate:
1. A Restoral Event
NOT SHORTED
All local annunciation of the
active event stops. The circuit
is found to be in a normal state.
The panel communicates:
1. A Restoral Event
All local annunciation of the
active event stops. The circuit
is found to be in a normal state.
The panel communicates:
1. A Restoral Event
Otherwise, the panel will
communicate nothing.
Table Notes:
1. Local annunciation is dependent upon input circuit function. Inputs programmed as wa terflow devices will not annunciate until the
waterflow retard period has expired. Inputs programmed as 2-wire smoke devices, with the Alarm Verification feature enabled, will
not annunciate until the alarm is verified.
2. Inputs programmed with a delay will not communicate the Active Event until the delay period has expired.
Coding, Notification Appliance Circuit (95)
Coding of the Notification Appliance Circuit is selectable as ‘0’ for no coding (steady) or ‘1’ for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off). Factory default is ‘0’ for no
coding (steady). Note that this NAC should only be used to supplement host panel NACs.
1. Latching input circuits will never restore in Stand-alon e Mode until the Reset Switch is pressed. If both an Autoresettable input
circuit and a Latching input circuit are activated and subsequently cleared, only the Autoresettable input circuit will restore, but
no transmission will occur to the Central Station since there is still an input circuit active (the Latching input circuit).
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D51
Factory default setting of '0' in address 96, allows the digital communicator to call the Central Station each time
any DACT trouble and any active Channel programmed for host panel trouble is detected by the 411UDAC. Programming a '1' in this address enables the Trouble Call Limit feature, which limits the number of 411UDAC and
Input Channel Trouble calls to the Central Station to 10 calls for each unique trouble event within a 24 hour
period. Separate limit counters keep track of each unique type of trouble (e.g. open input channel). To clear the
limit counters, disable and then enable this location. Note that the number of phone line (communicati on) faults
called to the Central Station are not limited by this feature. No subsequent restoral message is sent to the Central
Station(s) for a particular trouble whose limit of 10 calls has been reached. Local DACT annunciation will still
track the particular trouble and restoral.
Panel Identification Number (97 - 100)
The Panel Identification Number is a 4-digit code (valid digits are 0 to F) that is used to identify the installed
panel. It is important to program this 4-digit code at the jobsite the first time that downloading is performed so
that the called Service Terminal can identify the panel. The Factory default is '0000'. (Future Use).
Service Terminal 1 Phone Number (101 - 120)
Addresses 100 - 119 are reserved for the Service Terminal Number 1 phone number. Factory default is all 'F's.
Valid entries are 0 - 9 plus A, B, C, D and E. Use 'F' to designate the end of the phone number. See “Remote Site
Upload/Download” on page 61 for additional information.
Ring Count on Primary Phone Line (121 - 122)
Use this address to designate the number of rings allowed on the primary phone line prior to answering an incoming call from the Service Terminal. Factory default is '3' meaning the communicator will not answer an incoming
call until 3 rings are detected. This entry may be programmed up to a maximum of '25' rings. A setting of '00'
prevents the communicator from answering incoming calls.
FAX/Answer Machine, Primary Phone Line (123)
This entry is used when the primary phone line is being shared with a FAX, answering machine or other device.
Factory default is '0' for no sharing of the primary phone line. An entry of '1' indicates that another device is sharing the primary phone line. The communicator will wait for three consecutive calls from the Service Terminal
spaced 30 seconds apart, before responding. Sharing of phone lines requires the prior approval of the AHJ
(Authority Having Jurisdiction).
Service Terminal 2 Phone Number (124 - 143)
Addresses 123 - 142 are reserved for the Service Terminal Number 2 phone number. Factory default is all 'F's.
Valid entries are 0 - 9 plus A, B, C, D and E. Use 'F' to designate the end of the phone number. See “Remote Site
Upload/Download” on page 61 for additional information.
Upload/Download Reports Sent to Secondary Central Station Phone #, Backup or Always (144)
Leaving address 144 programmed to the factory default setting of '0' means that reports for request for 'upload/
download' and 'failed upload/download' will be sent to the secondary Central Station phone number only if
attempts to the primary Central Station phone number are unsuccessful. Programming a '1' causes all reports to be
transmitted to both primary and secondary phone numbers. Programming a '2' causes reports to be sent to the first
available receiver.
!
CAUTION: Do not alter entry while the communicator is active.
Programming Event Code Settings (145 - 312)
Event Code Settings, corresponding to the Formats selected for the Primary Central Station phone number in
address 20 and the Secondary Central Station phone number in address 50, are automatically set to factory default
values. Refer to Table 3-2, “4+2 Standard and 4+2 Express Formats - Primary,” on page 40, Table 3-3, “All 3+1,
4+1 and 4+2 Expanded Formats - Primary,” on page 41 and Ta ble 3-1, “Ademco Contact ID Format - Primary,”
on page 39 for format designated by address 20. Refer to Table 3-5, “4+2 Standard and 4+2 Express Formats Secondary,” on page 45, Table 3-6, “All 3+1, 4+1 and 4+2 Expanded Formats - Secondary,” on page 46 and Table
3-4, “Ademco Contact ID Format - Secondary,” on page 44 for format designated by address 50. The Event Code
Settings can be altered. Consult your Central Station prior to changing the event code settings.
52
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Default Mode
3.4Default Mode
To return all program entries, including the upload/ download secret password and time, to their factory original settings, perform the following steps only when the system is idle (i.e. the communicator is not active) and there are no
active fire alarms or fire supervisories in the system:
Press the MODE key followed by the 4-digit code 3337 and press the [ENTER/STORE] key.
3337 spells DEFP (DEFault Programming) on a Touch-Tone
If an incorrect key is entered, reenter the proper 4-digit code before
pressing the [ENTER/STORE] key. Within
®
phone.
five seconds, repeat this entry by again pressing the MODE key followed by the 4-digit code 3337 and pressing
the [ENTER/STORE] key. The display will read 3337 while the E
2
nonvolatile memory (storage area for all programming options) is being reprogrammed with the original default settings. When reprogramming is complete,
the display will be blank.
3.5Troubleshoot Mode
In this mode, system voltages may be displayed on the 4-character display of the PRO-411. An internal voltmeter
measures the voltage present at the channel/inputs, AC power input, battery terminal leads, Notification Appliance
Circuit and resettable 24 volt power. A lack of keyboard activity for a period of 20 minutes will cause the panel to
return to Normal Mode.
T o access the T roubleshoot Mode, press the MODE key followed by the digits 8768 and then the [ENTER/STORE]
key.
8768 spells TROU on a Touch-Tone
®
phone.
Once in this mode, the 411UDAC will continue to communicate any events not yet acknowledged at a central station
prior
to entering Troubleshoot Mode. The UP arrow, DOWN arrow and 1st EVENT keys do not function in this
mode.
All status displays in Troubleshoot Mode are shown in real-time, which means the display will update automatically
as the status changes. The one exception is the battery voltage which requires pressing the [ENTER/STORE] key to
update the display.
Channel/Inputs
Pressing 1 through 4 followed by the [ENTER/STORE] key on the PRO-411 displays the input status of the
selected channel. Listed below are the status display and corresponding nominal threshold voltages, as measured
across B+ and B-, for each zone:
Channel #Normal w/E.O.L.ShortedOpen Circuit
1 through 4 (status)nAF
1 and 3 (voltage)11.5V0V12.0V
2 and 4 (voltage)5.0V0V12.0V
Where n = normal, A = active and F = fault (or open).
AC Line
Pressing A followed by the [ENTER/STORE] key will display the AC input voltage as shown below. The following lists the AC line voltage range. The AC Power LED will turn off and the trouble LED will turn on when
the AC line voltage drops below the Low Line threshold.
AC Line VoltageLow LineNormalHigh Line
102 VAC115 VAC132 VAC
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D53
Troubleshoot Mode
Battery
Pressing B followed by the [ENTER/STORE] key will display the battery voltage. Note that the battery voltage
display does not automatically update with a change in battery voltage. The [ENTER/STORE] key must be
pressed each time a display update is desired. Shown below are the critical battery threshold conditions:
Battery VoltageNormalLow BatteryNo Battery
13.7 VDC10.4 VDC8.0 VDC
Battery Charger
Pressing 0 followed by the [ENTER/STORE] key will display the battery charger voltage.
Charger VoltageAverage Low Voltage High Voltage
13.8 VDC 12.1 VDC 14.6 VDC
12 Volt Resettable Power
Pressing the Lamp Test switch will display the Resettable Power voltage.
Notification Appliance Circuit
Pressing 8 followed by the [ENTER/STORE] key will display the status of the Notification Appliance Circuit.
Listed below are the status display and corresponding nominal threshold voltages for the NAC measured across
B+ and B-:
NACNormal w/E.O.L.ShortedOpen Circuit
statusnSO
voltage-1.0V0V-5.5V
Where n = normal, S = shorted and O = open.
Telephone Line Testing
Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/STORE] causes seizure of the
Primary phone line. After a delay of three seconds, the 411UDAC goes off-hook to acquire a dial tone.
The Programmer keypad may be used as a telephone touchpad for number dialing. Once the first digit is pressed, the
display will move the C or D character one position to the left, while placing the digit to be dialed on the farthest right
display position. Continue to press the phone numbers to be dialed. Successive depressions of the [ENTER/STORE] key hangs up and picks up the phone (places the phone on or off the hook).
The secondary phone line may be tested by pressing the E key for touchtone dialing or the F key for rotary dialing
and then following the same procedure used for the primary phone line. A handset may be temporarily connected
across transformer T1 of the 411UDAC as indicated in Figure 3-3. The handset, when connected across T1, may be
used only as an amplifier/speaker or telephone with the keypad used for number dialing.
FIGURE 3-3:Handset/Speaker Connection
411UDABD.CDR
54
Both Primary and Secondary Lines
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Central Station Communications
CHAPTER 4Central S tation Communications
The 411UDAC transmits system status reports to Central Stations via the public switched telephone network. Two
supervised telephone line connections are made to interface the communicator to the telephone lines. Two 7-foot
telephone cords P/N MCBL-7 may be used for this purpose (not supplied - order separately).
The digital communicator supervises both telephone lines for proper voltage. A delay of two minutes will occur
before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound, the yellow Trouble LED will turn on, the optional trouble relay will activate if programmed for DACT
trouble and the trouble condition will be reported to a central station over the remaining good ph one line.
The digital communicator comes with line seizure capability provided for both the primary and secondary telephone
line interfaces. Any time that the DACT needs to make a call to a central station, line seizure will disconnect any
local premises phones sharing the same telephone line. All transmissions to central stations will be sent over the Primary Central Station phone line. In the event of noisy phone lines, transmissions will be sent over the backup Secondary phone line.
T wo phone numbers must be programmed, the Primary Central Station phone number and the Secondary Central Station phone number. There are three options for transmission to the Central Station:
• All reports are always sent to the Primary Central Station phone number with the Secondary Central Station
number for emergency backup purposes only
• All reports are sent to both Central Station phone numbers
• Reports are sent to the first available Central Station phone number only
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D55
Central Station Communications
The digital communicator is capable of reporting detailed messages depending upon the Format in use. Table 4-1
shows the data reporting structure for each of the pulsed formats as well as the Ademco Express Formats. Ademco
Express Formats allow a typical data message to be transmitted to the Central Station in under 5 seconds. Pulsed formats typically require 15 to 20 seconds in comparison. Table 4-2 defines each letter code used in Table 4-1 . See
“Ademco Contact ID Format Event Code Description” on page 59 for a description of the data reporting structure for
Ademco Contact ID Format.
TABLE 4-1: Format Selection Addresses ( 20 and 50) Programming
Format #
0, 2, 4, 6, 8
Report
3+1/4+1/Standard
4+1 Express
Fire AlarmSSS(S) FA
Fire Alarm RestoreSSS(S) RF A
Channel/Input Trouble
(Channel/Input Open)
Channel/Input Trouble
Restore
SSS(S) TZ
SSS(S) RTZ
System TroubleSSS(S) TS
System Trouble RestoreSSS(S) RTS
AC LossSSS(S) P
AC Loss RestoreSSS(S) RP
Fire Supervisory ConditionSSS(S) V
Fire Supervisory Condition
Restore
SSS(S) RV
Format #
3, 5, 7, 9
3+1/4+1/Expanded
SSS(S) FA
FAFAFA(FA) 2
SSS(S) RFA
RF ARFARFA (RFA) 2
SSS(S) TZ
TZTZTZ(TZ) Z
SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSS(S) TS
TSTSTS(TS) Y
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSS(S) P
PPP(P) Z
SSS(S) RP
RPRPRP(RP) Z
SSS(S) V
VVV(V) Z
SSS(S) RV
RVRVR(RV) Z
Format #
1, A, C
4+2/Standard 4+2
Express
4+2/Expanded
SSSS FAFA2SSSS FAZ
SSSS RFARFA2SSSS RFAZ
SSSS TZTZ2SSSS TZZ
SSSS RTZRTZ2SSSS RTZZ
SSSS TSTS2SSSS TSY
SSSS RTSRTS2SSSS RTSY
SSSS PP2SSSS PP2
SSSS RPRP2SSSS RPRP2
SSSS VV2SSSS VZ
SSSS RVRV2SSSS RVZ
Test ReportSSS(S) XSSS(S) XSSSS XX2SSSS XX2
Up or DownloadSSS(S) UDSSS(S) UDSSS UDUD2SSS UDUD2
Format #
B, D
56
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Central Station Communications
TABLE 4-2: Format Selection Address Explanation
Where:
SSS or SSSS= Subscriber ID
FA= Fire Alarm (1st digit)
FA2= Fire Alarm (2nd digit)
Z= Channel/Input Number
RFA= Fire Alarm Restore (1st digit)
RFA2= Fire Alarm Restore (2nd digit)
TZ= Zone Trouble (1st digit)
TZ2= Zone Trouble (2nd digit)
RTZ= Zone Trouble Restore (1st digit)
RTZ2= Zone Trouble Restore (2nd digit)
TS= System Trouble (1st digit)
TS2= System Trouble (2nd digit)
RTS= System Trouble Restore (1st digit)
RTS2= System Trouble Restore (2nd digit)
P= AC Loss (1st digit)
P2= AC Loss (2nd digit)
RP= AC Loss Restore (1st digit)
RP2= AC Loss Restore (2nd digit)
V= Fire Supervisory Condition (1st digi t)
V2= Fire Supervisory Condition (2nd digit)
RV= Fire Supervisory Condition Restore (1st digit)
RV2= Fire Supervisory Condition Restore (2nd digit)
X= Test Report (1st digit)
X2= Test Report (2nd digit)
Y= Trouble corresponding to the following:
1 = Not Used
2 = Not Used
3 = Not Used
4 = Telco Primary Line Fault
5 = Telco Secondary Line Fault
6 = Not Used
7 = Not Used
8 = Not Used
9 = Not Used
A = Communication Failure Primary Number
B = Communication Failure Secondary Number
C = Not Used
D = Not Used
E = Not Used
F = System Off Normal
UD= Upload/Download (1st digit)
UD2= Upload/Download (2nd digit)
Note that for Expanded Reporting, the digital communicator automatical ly add s th e digit corresponding to the
Channel/Input number, and the second digit corresponding to any system trouble conditi on. Only the first digit
shown in Table 3-3 and Table 3-6 is programmable.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D57
Central Station Communications
4.0.1 Transmittal Priorities
The digital communicator transmits highest priority events first. Events in terms of priority are listed below in
descending order:
1. Fire Alarm (highest priority level)
2. Fire Supervisory
3. System Troubles
Host Panel Trouble (active input programmed for trouble)
AC Fail (after delay)
Channel/Input faults
T elephone line fault
Communication trouble
System Off Normal
4. Restoral Reports
Fire Alarm
Fire Supervisory
Host Panel Trouble
AC
Channel/Input fault
T elephone line
Communication
System Off Normal
5. System Test
6. Upload/Download events (lowest priority)
58
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Central Station Communications
4.0.2 Ademco Contact ID Format Event Code Description
This section describes the various Event Codes and their messages which are available for the Ademco Contact ID
Format. The reporting structure for the Ademco Contact ID Format is as follows:
SSSS 18 QXYZ GG CCC
Where:
SSSS= Four digit Subscriber ID Account Code (addresses 21 - 24 and 51 - 54)
18= Identifies transmission as Contact ID to the receiver at the Central Station
Q= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ= Event code (shown in Tables)
GG= Group number
CCC= Channel/Input number
Notes:
1. 18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
alarm and trouble report.
2. Q, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
R
for New Restore.
3. GG Group Number is fixed at '00' and cannot be changed.
4. CCC Channel/Input Number is transmitted as '001' for Channel/Input 1, '002' for Channel/Input 2, '003' for
Channel/Input 3, '004' for Channel/Input 4.
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the
Ademco Contact ID Reporting Structure follows:
(1) With version 3.9 software.
(2) With 685-8 Line Card with Rev. 4.4d software.
(3) With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software.
(4) With 124077V2.00 Receiver and 126047 Line Card Rev. M.
(5) With V.7301 Receiver S/W.
(6) With 01.01.03 Receiver S/W and Line Card 01.01.03.
(7) Surgard System III software version 1.6.
(8) Surgard MLR-2 software version 1.86.
(9) With DSP4016 and V1.6 Line Card.
(10) With 124060V206B and 124063 Line Card Rev. B
IMPORTANT! It is the installer’s responsibility to ensure that the Digital Alarm Communicator/Transmitter is compatible with the Central Station Receiver, utilized by the monitoring service, prior to installation. The Compatibility
Table provides a list of compatible r eceivers and associated software versions for the receivers. Changes in the hardware and/or software by the receiver manufacturers may affect the receiver compatibility with the DACT. After completing the installation, communication between the DACT and Central Station Receiver must be tested and verified.
60
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Remote Site Upload/Download
CHAPTER 5Remote Site Upload/Download
The 411UDAC may be programmed off site via the public switched telephone network. Any personal computer with
Windows
ware P/N PK-411UD, may serve as a Service Terminal. For details on the remote site upload/download software
package, refer to the PK-411UD Manual. The Upload/Download software allows the following:
!
®
3.1 or greater or Windows® 95, with a 1200 Baud Hayes compatible modem and Upload/Download soft-
• Download of the entire program
• Upload of the entire program
• Upload current status, system voltages or time
• Real-time upload of current status or system voltages
• Download new time
CAUTION: Changes to program entries occur as a result of the downloading process. After successful downloading, make certain to perform the following steps:
1. Manually view programmed entries and compare to intended program data.
2. Test all affected system operations.
3. Immediately correct any problems found.
5.1General
Any time that the digital communicator is contacted, a secret code (factory default 0000) is verified between the digital communicator and the Service Terminal. Changing the Secret Code may only be accomplished at the Service
T erminal and subsequently loaded into the panel. Future upload or download requests cause verification of the Secret
Code by the communicator before processing of data is allowed. If the Secret Code is not verified, the communicator
will terminate the request immediately.
In order to contact the communicator, the following must be true:
The digital communicato r may be in any mod e of operatio n inclu ding Normal, Program, Real Time
Clock, Troubleshoot or Lamp Test. Downloading is not possible if the communicator is active during
Central Station communications or while testing the phone lines while in Troubleshoot Mode.
There cannot be any active communications ongoing with a Central Station receiver.
All active events must be successfully 'kissed-off' by the Central Station(s). The digital communicator
must be in a standby state with no new information waiting to be transmitted to a Central Station.
Two basic communication mechanisms are supported as follows:
• Contact with callback - The Service Terminal calls the digital communicato r. The communicator answers the
call, confirms the calling party then hangs-up. The Service Terminal then waits for a callback from the communicator. After the digital communicator calls the Central Station and successfully reports that a request has
been received, the communicator calls the Service Terminal back. Upon secret code verification, data transfers occur. When the data transfers are completed and the Service Terminal disconnects from the communicator, the digital communicator calls the Central Station back to confirm either successful or unsuccessful
results.
• Contact with callback disabled - The Service Terminal calls the communicator. No hang-up sequence occurs.
Data transfers proceed.
Note that Callback enable/disable is controlled by the master user at the Service Terminal on a per call basis.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D61
General
With program address location 64 set to '1' in Program Mode, anytime a contact with callback is initiated, the communicator will first either contact the primary Central Station or contact both the primary and secondary Central Stations or contact the first available Central Station phone number to report a 'request for upload/download' message
(depending upon the program entry in address location 137). Once the request is 'kissed-off' by the Central Station(s), the communicator will then call the appropriate Service Terminal and begin the downloading process.
With program address location 64 set to '1' in Program Mode, anytime a contact with callback disabled is initiated,
the communicator and the Service T erminal will communicate and transfer data without first contacting a Central Station. When the data transfers are completed and the communicator disconnects from the Service Terminal, the communicator will call the Central Station and report one of the following:
• Upload/download request received
• Upload and/or download successful
• Upload/download failed
T o prevent the 'request for upload/download' message(s) from being reported to the Central Station(s), make certain
to set address 64 to ‘0’ or ‘3’ or disable all upload/download reports back to both Central Stations. Refer to Table 32 on page 40 through Table 3-4, “Ademco Contact ID Format - Secondary,” on page 44 for additional information.
Unlike most competitive products, during the downloading process, the input monitoring and 411UDAC supervision
remain active. Should an input activation or system trouble occur, the communicator immediately terminates downloading, processes the trouble or alarm locally and transmits the information to the Central Station(s).
5.1.1 Security Features
Remote site upload and download with the 411UDAC have been carefully designed to include key security features
to ensure proper functionality. The key features are listed and explained below.
Secret Code Verification
A secret code is stored in the communicator by a Service Terminal to prevent unauthorized access. The secret
code is created at the Service Terminal by a Master user and cannot be viewed or changed by anyone other than a
Master user. Viewing of the secret code is prohibited at the communicator. Prior to allowing an upload or download of data, the communicator will verify the secret code transmitted by the Service Terminal.
Time-out at 411UDAC
Upon answering an incoming call on the primary Central Station phone line, the communicator will listen for a
modem connection signal. If this signal is not received within 30 seconds, the communicator will disconnect the
call. Upon successful connection (i.e. secret code verified and callback complete if applicable), if no communication occurs within two minutes, the communicator will disconnect the call.
Callback to Service Terminal
Any time that the communicator is remotely requested to allow an upload or download with callback, it will confirm the source of the incoming call, hang-up and call the calling party (Service Terminal phone number) back.
Error Checking
As each block of data is received by the communicator, it is checked for accuracy. If an error is detected, the
block is retransmitted until correct, up to a maximum of four times. If the Secret Code is not verified and four
errors occur, the call is disconnected and the report that the upload/download was not successful is called to the
Central Station(s).
62
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Downloading to the Communicator
Central Station Acknowledge
There is an option whereby the communicator will report to one or both Central Stations that a request for uploading or downloading has been received prior to processing the call. This is called the 'callback' option. If the Central Station(s) does not acknowledge receipt of this request, uploading or downloading is prohibited. If
acknowledged by the Central Station(s), another message is transmitted informing the Central Station(s) that:
• downloading was successful
• uploading was successful
• uploading/downloading was not successful
Data Protection/Integrity
Programming data is completely verified for accuracy prior to reprogramming of the 411UDAC EEPROM.
Incomplete or corrupted data packets are ignored or retried.
5.2Downloading to the Communicator
Before initiating the download procedure, make certain that the communicator is in the standby state.
Once an incoming call is accepted/answered by the communicator, the 411UDAC will:
1. Establish basic modem connection
2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If callback is requested, perform steps 4
through 10; if no callback is requested, perform steps 9 and 10 only
4. Verify product type
5. Identify the Service Terminal location
6. Hang-up/disconnect call
7. Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
this message is accepted, the communicator will proceed to the next step
8. Return call to the Service Terminal
9. Verify secret code
10. Verify Product type
11. Begin downloading
12. Upon completion of download, call the Central Station(s) back and report a successful download or failed
upload/download status (if programmed to do so).
5.3Uploading From the Communicator
Items that may be uploaded from the communicator to a Service Terminal are:
• All or portions of programmed data plus the real time clock
• Troubleshoot system voltages in real-time or as a 'snapshot'
• Current system status in real-time continuous or as a 'snapshot'
Uploading is possible at any time provided the following conditions are true:
The communicator may be in any mode of operation. Uploading is not possible if the communicator is
active or while testing the phone lines while in Troubleshoot Mode.
There cannot be any active communications ongoing with a Central Station receiver.
All active events must be successfully 'kissed-off' by the Central Station(s). The communicator must be
in a standby state with no new information waiting to be transmitted to a Central Station.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D63
Simultaneous Data Transfers
Once an incoming call is accepted/answered by the communicator, the 411UDAC will:
1. Establish basic modem connection
2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If callback is requested, perform steps 4
through 10; if no callback is requested, perform steps 9 and 10 only
4. Verify product type
5. Identify the Service Terminal location
6. Hang-up/disconnect call
7. Call the Central Station(s) and transmit a request for upload/download message (if programmed to do so). If
this message is accepted, the communicator will proceed to the next step
8. Return call to the Service Terminal
9. Verify secret code
10. Verify product type
11. Begin downloading
12. Upon completion of download, call the Central Station(s) back and report a successful download or failed
upload/download status (if programmed to do so).
Unlike most competitive products, during the uploading process, the 411UDAC fire protection remains active.
Should a system trouble or alarm condition occur, the communicator immediately terminates uploading and processes the trouble or alarm locally and transmits the information to the Central Station(s).
5.4Simultaneous Data Transfers
Uploading and downloading may take place on a single telephone call. Control and selection of the data transaction
is coordinated at the Service Terminal. This eliminates multiple phone calls, allows instant verification of downloaded data files and simplifies the overall process.
64
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Battery Calculations
CHAPTER 6Battery Calculations
Use the Total Standby and Alarm Load Currents calculated in Table 6-2, “Load in Standby ,” on page 66, and Table 63, “Load in Alarm,” on page 66, for the following battery calculations.
TABLE 6-1: Battery Calculations
Standby Load
Current in amps
(from Table 6-2 )
[ ]
Alarm Load
Current in amps
(from Table 6-3 )
[ ]
X
X
Required Standby Time in Hours
(24 or 60 Hours)
[ ]
Required Alarm Time in Hours
(i.e. 5 min. = 0.084 Hours)
[ ]
=__________
=__________
Add Standby and Alarm Load for Required Ampere Hour Battery__________
Multiplying by derating factor of 1.2X1.2
Total Ampere Hour Battery
1. Select a battery with an Amp Hour rating greater than that calculated in Table 6-1 .
1
=__________
NFPA 72 for Central Station and Proprietary Protected Premises systems require 24 hours of standby
NFPA 72 for Auxiliary and Remote Station systems require 60 hours of standby (14 Amp Hours)
2. Two 12 VDC, 7 Amp Hour batteries, wired in parallel, can be located in the backbox to provide 14 Amp
Hours of backup (refer to Figure 2-5 on page 22 for battery cable connections)
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D65
411UDAC Power Supply
6.1411UDAC Power Supply
The 411UDAC provides filtered power for operating the digital communicator, external devices and the battery
charger. The power for operating external devices is limited. Use Table 6-2 (standby or nonalarm) and Table 6-3
(alarm) to determine if external loading is within the capabilities of the power supply.
TABLE 6-2: Loa d in Standby
Current
Device Type# of Devices
(amps)
Main Circuit Board1X0.143=0.143
2-wire Detector Heads[ ]X[ ]=
4-wire Detector Heads[ ]X[ ]=
Power Supervision Relays
Additional Current Draw
from 12 VDC Resettable
1
[ ]X[ ]=
X=
Sum Column for Standby Load=amps
Notes:
1. Refer to the Device Compatibility Document for compatible listed power supervision relays.
2. Refer to Device Compatibility Document for 2-wire and 4-wire smoke detector standby current.
TABLE 6-3: Loa d in Alarm
Total Current
(amps)
Device Type# of Devices
Current
(amps)
Total Current
Main Circuit Board1X0.330=0.330
4-wire Detector Heads[ ]X[ ]=
Power Supervision Relay
Notification Appliances
Additional Current Draw
from 12 VDC Resettable
1
2
3
[ ]X0.025=
[ ]X[ ]=
[ ]X[ ]=
Sum Column for Alarm Load=amps
Notes:
1. Use compatible listed power supervision relay only. Refer to the Device Compatibility Document
2. Refer to the Device Compatibility Document for 4-wire smoke detector current
3. Maximum available current for notification appliances is 1.0 amp
4. Maximum available current from resettable output is 0.200 amps
5. Total system current cannot exceed 1.6 amps
6. For Remote Station applications, total standby current must not exceed 193 mA
(amps)
66
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Programming Sheets
Appendix APr ogramming Sheets
A.1Digital Communicator Options Program Sheets
--To enter Programming Mode, press the MODE key, 7764 and then the [ENTER/STORE] key.
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to r epresent the end of number.
Secondary Central Station Communication Format: Valid entries are 0 to 9 and A to F.
50
515253
555657
Secondary Number Test Time Interval. Enter '0' for 24-hour; '1' for 12-hour; '2' for 8-hour; '3' for 6-hour.
59
AC Loss Reporting Delay. Enter '0' for no delay; '1' for 1 hours; '2' for 2 hours; '3' for 6 hours; '4' for 7 hours;
60
'5' for 8 hours; '6' for 9 hours; '7' for 10 hours; '8' for 11 hours; '9' for 12 hours; 'A' for 13 hours; 'B' for 14 hours; 'C' for
15 hours; 'D' for 16 hours; 'E' for 17 hours; 'F' for 18 hours.
Backup Reporting. Enter '0' to report to Secondary phone number as backup only; '1' to report to both Primary
61
and Secondary phone number for all reports/messages; '2' reports go to first available receiver.
Reserved for Future Use.
62
DACT Trouble Reminder. Enter '0' to disable; '1' to enable.
63
Operational Mode Selection. Enter '0' for stand-alone/communicator disabled; '1' for stand-alone/communica-
64
tor enabled; '2' for slave/communicator enabled; '3' for slave/communicator disabled. Default setting is '0'.
Input Channel 1 Function Selection. Enter '0' for fire alarm; '1' for pull statio n; '2' for normally open contact;
65
'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.
Input Channel 2 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel
66
trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
Input Channel 3 Function Selection. Enter '0' for fire alarm; '1' for pull statio n; '2' for normally open contact;
67
'3' for host panel trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for
waterflow nonsilenceable.
Input Channel 4 Function Selection. Enter '1' for pull station; '2' for normally open contact; '3' for host panel
68
trouble; '4' for supervisory; '5' for supervisory autoresettable; '6' for waterflow silenceable; '7' for waterflow nonsilenceable.
6970
Does not delay Input Channels programmed for fire functions.
7273
Does not delay Input Channels programmed for fire functions.
71
74
Secondary Central Station Account Code: Valid entries are 0 to 9 and A to F.
54
Secondary Central Station 24-hour Test Time: Use military time (i.e. 1400 for 2:00 PM).
58
Input Channel 1 Delay Timer . Enter 0 - 179 seconds delay . Factory default is '000' for no delay .
Input Channel 2 Delay Timer . Enter 0 - 179 seconds delay . Factory default is '000' for no delay .
19
49
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D67
Programming Sheets
7576
Does not delay Input Channels programmed for fire functions.
7879
Does not delay Input Channels programmed for fire functions.
Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
81
Make/Break Ratio for Primary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
82
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
83
Make/Break Ratio for Secondary Phone. Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
84
Output Relay #1 enable. Enter '1' to enable Relay #1; '0' to disable relay.
85
Output Relay #1 Function. Enter '0' for relay to activate on alarm; '1' host panel trouble; '2' DACT trouble; '3'
86
for latching fire supervisory; '4' for autoresettable fire supervisory; '7' (future use); '8' for total communication failure.
Output Relay #2 enable. Enter '1' to enable Relay #2; '0' to disable relay.
87
Output Relay #2 Function. Enter '0' for relay to activate on fire alarm; '1' host panel trouble; '2' for DACT
88
trouble; '3' for latching fire supervisory; '4' for autoresettable fire supervisory; '7' (future use); '8' total communication
failure.
Reserved for future use. Leave default setting of ‘0.’
89
Reserved for future use. Leave default setting of ‘0.’
90
Alarm verification. Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
91
Silence inhibit. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC for one minute.
92
Autosilence. Enter '0' for no autosilence; '1' for 5 minute autosilence; '2' for 10 minutes; '3' for 15 minutes; '4'
93
for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
Restoral method. Enter '0' for Typical restoral method; '1' for Conditional Restoral Method #1; '2' for
94
Conditional Restoral Method #2.
Coding, Notification Appliance Circuit. Enter ‘0’ for no coding (steady); ‘1’ for Temporal coding.
95
Trouble Call Limit - Dialer Runaway Prevention Feature. Enter a '0' to disable this feature; '1' to enable Trou-
96
ble Call Limit. Factory default is '0' for disabled.
A - E. 'F' designates the end of the phone number.
121122
are 00 to 25 (00 = no answer). Factory default is 03.
'F' designates the end of the phone number.
Station Phone Number on backup only; '1' for Upload/Download reports to always go to the Secondary; '2' for
Upload/Download reports to go to the first available Central Station phone number.
FAX/Answer Machine, Primary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.
Addresses 30 to 49 store the Secondary Central Station phone number. Enter 'F' to represent the end of number.
E
Secondary Central Station Communication Format. 'E' for Ademco Contact ID Format.
50
0 0 0 0
515253
0 0 0 0
555657
0
Secondary Number Test Time Interval. '0' for 24 hours.
59
2
AC Loss Reporting Delay. '2' for 2 hour delay.
60
0
Backup Reporting. '0' to report to Secondary Central Station phone number as backup only.
61
0
Reserved for Future Use.
62
0
Trouble Reminder. '0' disables Trouble Reminder.
63
0
Operational Mode Select. '0' enables stand-alone mode, disables communication to Central Station.
64
0
Input Channel 1 Function Selection. '0' for fire alarm.
65
1
Input Channel 2 Function Selection. '1' for pull station alarm.
66
0
Input Channel 3 Function Selection. '0' for fire alarm.
67
1
Input Channel 4 Function Selection. '1' for pull station alarm.
68
0 0 0
6970
0 0 0
7273
0 0 0
7576
0 0 0
7879
0
Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.
81
0
Make/Break Ratio for Primary Phone. '0' for 67/33 ratio.
82
71
74
77
80
Primary Central Station Account Code.
24
Primary Central Station 24-hour Test Time. '0000' = 12:00 midnight.
28
Secondary Central Station Account Code.
54
Secondary Central Station 24-hour Test T ime: '0000' = 12:00 midnight.
58
Input Channel 1 Delay Timer. '000' for no delay. Does not delay fire functions.
Input Channel 2 Delay Timer. '000' for no delay. Does not delay fire functions.
Input Channel 3 Delay Timer. '000' for no delay. Does not delay fire functions.
Input Channel 4 Delay Timer. '000' for no delay. Does not delay fire functions.
19
49
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D69
Programming Sheets
0
Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing.
83
0
Make/Break Ratio for Secondary Phone. '0' for 67/33 ratio.
84
0
Output Relay #1 Enable. '0' to disable relay.
85
0
Output Relay #1 Function Selection. '0' for activation on fire alarm (2-wire smoke).
86
0
Output Relay #2 Enable. '0' to disable relay.
87
2
Output Relay #2 Function Selection. '2’ for activation on DACT trouble.
88
0
Reserved for future use. Leave default setting of ‘0.’
89
0
Reserved for future use. Leave default setting of ‘0.’
90
0
Alarm Verification. '0' to disable.
91
0
Silence Inhibit. '0' to disable.
92
0
Autosilence. '0' to disable.
93
0
Restoral Method. '0' for Typical restoral.
94
0
Coding, Notification Appliance Circuit. '0' for no coding.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D75
Ademco Contact ID Format Event Code Description
Appendix CAdemco Contact ID Format Event
Code Description
EVENT CODE CLASSIFICA TIONS
100
ALARMS
Medical
Fire
Panic
Burglary
General
24 Hour
200
SUPERVISORY
Fire
300
TROUBLES
System
Sounder/Relay
System Peripheral
Communication
Protective Loop
Sensor
400
OPEN/CLOSE
REMOTE ACCESS
Open/Close
Remote Access
Access Control
500
DISABLES/
BYPASSES
System
Sounder/Relay
System Peripheral
Communication
EVENTMESSAGE
Medical Alarms - 100
100 MedicalEMERG - Personal Emergency - #
101 Pendant transmitterEMERG - Personal Emergency - #
102 Fail to report inEMERG - Fail to Check-in - #
24 Hour Non-Burglary - 150 and 160
150 24-Hour Non-BurgALARM - 24-Hr. Non-Burg - #
151 Gas detectedALARM - Gas Detected - #
152 RefrigerationALARM - Refrigeration - #
153 Loss of heatALARM - Heating System - #
154 Water leakageALARM - Eater Leakage - #
155 Foil breakALARM - Foil Break - #
156 Day trouble ALARM - Day Zone - #
157 Low bottled gas levelALARM - Low Gas Level - #
158 High tempALARM - High Temperature - #
159 Low tempALARM - Low Temperature - #
161 Loss of air flowALARM - Air Flow - #
Fire Supervisory - 200 and 210
200 Fire supervisorySUPER. - Fire Supervisory - #
201 Low water pressureSUPER. - Low Water Pressure - #
202 Lox CO2SUPER. - Low CO2
203 Gate valve sensorSUPER. - Gate Valve - #
204 Low water levelSUPER. - Low Water Level - #
205 Pump activatedSUPER. - Pump Activation - #
206 Pump failureSUPER. - Pump Failure - #
System Troubles - 300 and 310
300 System troubleTROUBLE - System Trouble
301 AC lossTROUBLE - AC Power
302 Low system batteryTROUBLE - System Low Battery
303 RAM checksum badTROUBLE - Bad RAM Checksum (Restore not applicable)
304 ROM checksum badTROUBLE - Bad ROM Checksum (Restore not applicable)
305 System resetTROUBLE - System Reset (Restore not applicable)
306 Panel program changedTROUBLE - Programming Changed (Restore not applicable)
307 Self-test failureTROUBLE - Self Test Failure
308 System shutdownTROUBLE - System Shutdown
309 Battery test failureTROUBLE - Battery Test Failure
310 Ground faultTROUBLE - Ground Fault - #
311 No batteryTROUBLE - No Battery
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D77
Ademco Contact ID Format Event Code Description
EVENTMESSAGE
System Peripheral Troubles - 330 and 340
330 System peripheralTROUBLE - Sys. Peripheral - #
331 Polling loop openTROUBLE - Polling Loop Open
332 Polling loop shortTROUBLE - Polling Loop Short
333 Expansion module failureTROUBLE - Exp. Module Fail - #
334 Repeater failureTROUBLE - Repeater Failure - #
335 Local printer paper outTROUBLE - Printer Paper Out
336 Local printer failureTROUBLE - Local Printer
Communication Troubles - 350 and 360
350 CommunicationT ROUBLE - Communication Trouble
351 Telco 1 faultT ROUBLE - Phone Line #1
352 Telco 2 faultT ROUBLE - Phone Line #2
353 Long range radio xmitter faultTROUBLE - Radio Transmitter
354 Fail to communicateTROUBLE - Fail to Communicate
355 Loss of radio supervisionTROU BLE - Radio Supervision
356 Loss of central pollingTROUBLE - Central Radio Polli ng
Open/Close - 400
400 Open/CloseOPENINGCLOSING
401 Open/Close by userOPENING - User #CLOSING - User #
402 Group Open/CloseOPENING - Group User #CLOSING - Group User #
403 Automatic Open/CloseOPENING - AutomaticCLOSING - Automatic
404 Late Open/CloseOPENING - LateCLOSING - Late
405 Deferred Open/CloseOpenin g not usedCl osing not used
406 CancelOPENING - CancelClosing not used
407 Remote arm/disarmOPENING - RemoteCLOSING - Remote
408 Quick armOpening not applicableCLOSING - Quick arm
409 Keyswitch Open/CloseOPENING - KeyswitchCLOSING - Keyswitch
Remote Access - 410
411 Callback request madeREMOTE - Callback RequestedRestore not applicable
412 Success - download/accessREMOTE - Successful AccessRestore not applicable
413 Unsuccessful accessREMOTE - Unsuccessful AccessRestore not applicable
414 System shutdownREMOTE - System Shutdown
415 Dialer shutdownREMOTE - Dialer Shutdown
416 Success - upload/accessREMOTE - Successful AccessRestore not applicable
78
Access Control - 420
421 Access deniedACCESS - Access Denied - User #Restore not used
422 Access report by userACCESS - Access Gained - User #Restore not used
System Disables - 500 and 510
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Communication Disables - 550 and 560
551 Dialer disabledDISABLE - Dialer Disable
552 Radio transmitter disabledDISABLE - Radio Disable
Bypasses - 570
570 Zone bypassBYPASS - Zone Bypass - #
571 Fire bypassBYPASS - Fire Bypass - #
572 24-Hour zone bypassBYPASS - 24-Hour Bypass - #
573 Burglar bypassBYPASS - Burg. Bypass - #
574 Group bypassBYPASS - Group Bypass - #
Test Misc. - 600
601 Manual trigger testTEST - Manually TriggeredRestore not applicable
602 Periodic test reportTEST - PeriodicRestore not applicable
603 Periodic RF transmissionTEST - Periodic RadioRestore not applicable
604 Fire testTEST - Fire TestRestore not used
605 Status report to followSTATUS - Status Follows Restore not applicable
606 Listen-in to followLIST EN - Li sten-in ActiveRestore not applicable
607 Walk test modeTEST - Walk Tes t Mo de
608 System abnormal testTEST - System Abnormal Test
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D79
Events and Default Event Codes
Appendix DEvents and Default Event Codes
Note: The character ‘x’ in the following table refers to the input circuit number (1 - 4).
411UDAC EventsFormat Grou p 1Format Group 2Ademco Contact ID
Input Circuit FaultFxDxFD38000x
AC Fault929399301000
Earth Fault61A16A310000
Low Battery Fault62A26A302000
No Battery Fault63A36A311000
Phone Line 1 Fault64A46A351000
Phone Line 2 Fault65A56A352000
NAC Fault66A66A321000
Phone Number 1 Fault6AAA6A354001
Phone Number 2 Fault6BAB6A354002
System Off Normal Fault6FAF6A308000
Special EventsActiveRestoreActiveRestore
System Test Message99-9-602000
System Abnormal Test Message91-F-608000
Upload/Download Request71-7-411000
Upload Successful72-7-416000
Download Successful73-7-412000
Upload/Download Failed74-7-412000
4+1 Ademco Express Standard, DTMF1400/2300 Hz ACK
3+1 Standard 1800 Hz Carrier2300 Hz ACK
3+1 Standard 1900 Hz Carrier1400 Hz ACK
4+1 Standard 1800 Hz Carrier2300 Hz ACK
4+1 Standard 1900 Hz Carrier1400 Hz ACK
Note that although all Expanded Mode formats communicate two digits per event, only the first digit is
programmable. The second digit cannot be changed.
80
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Operational Modes
Appendix EOperational Modes
CODEACTIVITYNOTES
6676 (NORM)Returns to normal operationFire protection is on.
2525 (CLCK)Enters Real-Time Clock Mode
7764 (PROG)Enters Program Mode
3337 (DEFP)
Returns digital communicator to factory
default program settings
8768 (TROU)Allows display of status for all circuitsFire protection is off during Troubleshoot Mode.
Allows programming of digital communicator.
Program digital communicator time.
Fire protection is off.
Fire protection is off.
Fire protection is off during Default Mode.
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D81
Canadian Applications
Appendix FCanadian Applications
This section illustrates the connection of the 411UDAC Digital Alarm Communicator/Transmitter (DACT) to an
FACP for Canadian Applications. The following conditions must be adhered to in order to compl y wit h Ca nadian
requirements.
1. Only one FACP can be connected to the 411UDAC DACT.
2. Phone lines must exit the building in separate directions.
3. The 411UDAC DACT relay #1 must be enabled [refer to “Output Relay #1 Enable (85)” on page 49] and must
be programmed to activate on DACT trouble [refer to “Output Relay #1 Function Selections (86)” on page
49].
4. The Auxiliary Trouble Input wiring from the 411UDAC DACT must be in conduit and in the same room as
the FACP and DACT.
-24 VDC nonresettable power from FACP
411UDAC
2.2K ELRs P/N 27070
Relay Output (DACT
Trouble) from 411UDAC
Channel 4 (2.2k ELR)
FACP ATrouble Relay
FACP Supv. Relay
FACP Alarm Relay
82
FACP
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D83
Notes
84 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Notes
411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D85
Notes
86 411UDAC Document #51073 Rev. D 12/09/2008 P/N 51073:D
Limited Warranty
Honeywell International Inc. warrants products manufactured by it
to be free from defects in materials and workmanship for eighteen
(18) months from the date of manufacture, under normal use and
service. Products are date stamped at time of manufa cture. The sole
and exclusive obligation of Honeywell International Inc. is to repair
or replace, at its option, free of charge for parts and labor, any part
that is defective in materials or workmanship under normal use and
service. All returns for credit are subject to inspection and testing at
the factory before actual determination is made to allow credit.
Honeywell International Inc. does not warrant products not
manufactured by it, but assigns to the purchaser any warranty
extended by the manufacturer of such products. This warranty is void
if the product is altered or repaired by anyone other than Honeywell
International Inc. or as expressly authorized by Honeywell
International Inc. in writing, or is serviced by anyone other than
Honeywell International Inc. or its authorized distributors. This
warranty is also void if there is a failure to maintain the products and
systems in which they operate in a proper and workable manner. In
case of defect, secure a Return Material Authorization form from our
Return Authorization Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products. Honeywell
International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases
provide the protection for which they are installed or intended. Buyer
acknowledges that Honeywell International Inc., is not an insurer
and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS
BEYOND THE DESCRIPTION ON THE F ACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC.
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY,
DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF
THE USE OF, OR INABILITY TO USE HONEYWELL
INTERNATIONAL INC.’S PRODUCTS. FURTHERMORE,
HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE
COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL
OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by Honeywell International Inc. No increase or
alteration, written or verbal, of the obligation of this warranty is
authorized.
Warn-HL-05-2007.fm
World Headquarters
1 Firelite Place
Northford, CT 06472-1653 USA
203-484-7161
fax 203-484-7118
www.firelite.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.