Pouring the Concrete ................................................................................................................................ 1-2
Using an Existing Pad ............................................................................................................................... 1-4
Installing the Extended Battery Backup Kit .............................................................................................. 2-13
Chapter 3: Display and Menu Options
I
NITIAL SETUP
Turning Both Power Switches On ............................................................................................................. 3-2
Using the Smart DC Controller Buttons In Menu Mode ........................................................................... 3-3
Configuring the Setup Menu ..................................................................................................................... 3-4
R
UN MODE
Understanding Gate Status Displays .......................................................................................................... 3-5
Using the Smart DC Controller Buttons In RUN Mode ........................................................................... 3-6
Viewing Operator Status Displays .............................................................................................................. 3-7
U
SER MENU
Adjusting the Close Timer ......................................................................................................................... 3-9
Setting the Time and Date ....................................................................................................................... 3-10
Setting AC Power Loss Gate Function ..................................................................................................... 3-11
Adjusting the Display Contrast ................................................................................................................ 3-12
I
NSTALLER MENU
Adjusting the Gate Speed ......................................................................................................................... 3-17
Adjusting the IES Sensitivity .................................................................................................................... 3-18
4SwingSmart - Installation, Operation and Maintenence ManualRevision E
Intelligent Features: Smart DC ControllerTM
Introducing SwingSmart DC
Thank you for purchasing our premium SwingSmart DC™ 20 swing gate operator. At HySecurity® Gate, Inc.,
we pride ourselves on quality and a number of unparalleled user benefits:
Robust - An especially strong twin channel steel chassis and adjustable taper clutch greatly improves the ability
for SwingSmart to resist damage from vehicle hits on the gate. The components on the Smart DC Controller
are protected by opto-isolators which shield them from power surges and lightning strikes.
Power - A variable speed control board supplies a powerful, continuous 24V DC motor which drives a 600:1
gearbox providing variable speeds. The electronics, motor and gear box are rated to operate in very broad
temperatures that range from -13°F to 158°F (-25°C to 70°C). SwingSmart DC is rated for gates up to 20 feet
long and 1,300 pounds.
Finesse - A variable rate of gate acceleration and deceleration, dependent upon gate weight and length, assures
very smooth handling.
Adaptable - The design incorporates left and right gate arms to assure aesthetic functionality. An articulating
arm is an available option which also provides adaptability to a variety of site situations.
UPS backup and Solar ready - Two 12V, 8 amp hour (Ah) batteries will provide a fully functional gate operator
(up to 300 gate cycles) when AC power is unavailable. Four user-selectable UPS modes are available. 12VDC
and 24VDC are available to power access controls. The unit’s design also incorporates space for optional 50Ah
batteries to support solar applications or usage during extended power outages.
I
NTELLIGENT
Automatic adjustment and synchronization of bi-parting gates - The Smart DC Controller automatically
adjusts the gate speed to synchronize the left and right gates so that they reach the open and close positions at
the same time. Independent leaf delay adjustment for bi-parting gates is selectable in ½ second increments.
Menus and User relays - The Smart DC Controller has 48 menu items to allow installer configuration of gate
function and two user relays, which can be configured for 22 different functions.
Independent adjustment for open and close gate speeds - An easy-to-use menu on the Smart DC Controller
allows the installer to vary the open and close speed settings in a range between 10 and 15 seconds.
Intelligent Inherent Entrapment Sensor (IES) - Any impediment to gate travel is sensed by the system, stopping
gate movement per UL 325 Safety Standards. The intelligent system monitors gate power then adapts the IES
to trip at an adjustable threshold above normal power.
Improved Liquid Crystal Display (LCD) - A 32-character LCD provides increased readability for programming
and troubleshooting.
F
EATURES
: S
MART
DC C
ONTROLLER
TM
USB communications port - A direct connect provides accessibility to download system diagnostics and upload
system configurations using the Smart Touch Analyze and Retrieve Tool (S.T.A.R.T.) software.
S.T.A.R.T. software and diagnostics - With S.T.A.R.T. software loaded on a laptop computer, you have an
invaluable management tool for all HySecurity operators. To download this free software, visit the HySecurity
website at www.hysecurity.com.
Intro-2SwingSmart DC Installation and Refer ence Manual Revision E
Technical Support
T
ECHNICAL
For technical support, call your installer or authorized HySecurity distributor. Obtain the serial number of your
operator before calling. Refer to SwingSmart Components on the front page. For the name of a distributor near
to your locale, call HySecurity at 800-321-9947.
For information about HySecurity training for installers, maintenance personnel and end-users, refer to the
company website at www.hysecurity.com or call 800-321-9947.
S
UPPORT
Revision EIntroducing SwingSmart DCIntro-3
Installer's Check List
I
NSTALLER'S
C
HECK
L
IST
The following list provides a high level overview of the tasks involved in installing the SwingSmart DC gate
operator. Take a moment to review the list and check off the items as you complete the install.
?
Site Prep - concrete pad location/dimensions/distance from gate, conduits and vehicle detector loops
properly installed, gate bracket and linkage arm mounting considerations.
?
Make sure gate installation complies with ASTM F2200 Specification for Automated Vehicular Gate
Construction and UL325 Safety Standards. Install supplied WARNING signs on both sides of the gate.
?
Check for compliance with local codes, site conditions, and NEC standards.
?
Install operator on concrete pad using four ½ - 13 x 3.5 inch long concrete wedge anchors.
?
Temporarily attach gate bracket and linkage arm(s).
?
Adjust open and close limit switches through manual operation of the gate.
?
Complete gate arm installation (weld or drill and bolt).
?
Cut the excess off the over extension stop (angle iron) on the SwingSmart arm.
?
Hand-tighten the taper clamp to obtain a tight clutch setting.
?
Install the earth ground and AC wiring connections for AC power.
?
Connect battery wire to switch.
?
Complete Initial Setup Menu programming.
?
Review the connections on the Smart DC Controller.
?
Install Master/Slave operator connections, if the site is a bi-parting gate system.
?
Attach accessory devices.
?
Configure the User and Installer Menu options. Program applicable settings dependent on accessory
devices installed.
?
Set the Close Timer (in the User Menu), if necessary.
?
Check the Smart DC Controller software version. If needed, upload the latest version from
www.hysecurity.com. See Smart Touch Analyze and Retrieve Tool (S.T.A.R.T.).
?
Give a copy of the operator instructions to the end user. Show the end user how to:
•Remove the operator covers. Turn the power off and on.
•Turn the DC power switch off, which disengages the motor.
•Loosen the taper clamp and manually push the gate(s) open & close.
Note: Remember to re-tighten the taper clamp before turning the DC power switch back on and
replacing the covers.
•Test the red Emergency Stop Button located on the side of the control box. It can be accessed through a
hole in the cover. See illustration on page S-8.
?
Take photographs of the completed installation site and save them in your business files.
Intro-4SwingSmart DC Installation and Refer ence Manual Revision E
Important Safety Instructions
WARNING
!
Safety Requirements
Automatic gate operators provide user convenience and security. However, because these machines can produce
high levels of force, it is imperative that gate operator system designers, installers and end users be aware of
potential hazards associated with improperly designed, installed, or maintained systems. The gate operator is
only one component of the total gate operating system. It is the joint responsibility of the architect, site
designer, purchaser, installer and end user to verify that the total system is appropriately configured for its
intended use. Additionally, certain municipalities have established licensing, codes or regulations that regulate
automated gate system design and installation. Consult local government agencies for up-to-date rules and
regulations prior to gate system design or installation.
I
MPORTANT
A moving gate can cause serious injury or death. S.T.A.R.T. the gate operator only when the
gate’s travel path is clear.
S
AFETY INSTRUCTIONS
Hazards, associated with automatic gates, can be reduced with proper site design, installation, and use.
Installers, maintenance crews, and owners/users must read and follow the
manual and review all the literature that accompanies the product. It is important that only qualified installer’s
handle the installation of the SwingSmart gate operator. A “qualified” installer has one of the following:
•A minimum of three years experience installing similar equipment.
•Proof of attending a HySecurity Technical Training seminar within the past three years.
•Significant manufacturer endorsements of technical aptitude in gate operator installation and operation.
Underwriter Laboratories (UL) and the American Society for Testing and Materials (ASTM) are responsible for
current safety standards and regulations regarding gate operators and automated gates. To pass UL certification,
all aspects of gate installation must comply with the appropriate safety standards. For the most up-to-date,
ASTM F2200 Gate and Fence Standards, refer to www.astm.org. For UL 325 Safety Standard, refer to
www.ul.com.
Important Safety Instructions
Safety Standards - Installer's Responsibility
•Study the entire contents of this manual prior to installing, operating, or maintaining the SwingSmart gate
operator. Taking extra time to align the gate operator and verify a fully functional installation will reduce
maintenance, guarantee longest system life, and ensure customer satisfaction.
•Verify the gate operator usage class for the site. Refer to
for gate classifications. Install SwingSmart only when the gate operator class is correct for the site, size, and
type of gate.
•Install an automatic operator only on gates that comply with ASTM F2200 Gate and Fence Standards.
Screen or enclose openings in the gate per UL 325 Safety Standards.
Identifying Gate Operator Category and Usage Class
in this
Revision ESafety RequirementsS-1
Important Safety Instructions
NOTE
•Before attaching the operator to the gate, move the gate in both directions. Make sure it is level and moves
freely. A gate that swings easily reduces strain on operator components. Gravity should play no part in the
opening or closing of the gate.
•Make sure there is a separate walk-through entrance nearby. Make certain a clear pedestrian path is
designated and signs direct pedestrians to the walk-through gate. The automated gate entry is for vehicle
use only. No one should cross the path of a moving gate.
•Install the gate operator on the secure (non-public) side of the gate. Note that swing gates cannot open into
public areas. Locate controls (OPEN, STOP, CLOSE) where a user will have a clear view of the gate.
•Mount access control devices beyond reach of the gate. The control devices that operate the gate must be:
•Located in a clear line of sight to the gate.
•Mounted beyond 6 feet of the gate to prevent users from touching or accessing the gate while operating
the controls. People attempting to access the controls by reaching through or around the gate can be
seriously injured or killed by the moving gate.
•Incorporate a security feature to prevent unauthorized use.
•The gate operator must be properly grounded and the incoming power voltage must match the voltage
label on the junction box.
•Install enough external entrapment protection sensors so that pedestrians are protected from entrapment in
both directions of the gate travel and all hazard areas and possible pinch points are fully protected. Review
the information found in
•Install the supplied WARNING signs on the inside and outside of the gate so they are clearly visible from
both sides of the gate. Installing the signs is a requirement for UL 325 compliance.
•Locate controls (Open, Close, Stop/Reset) where a user will have a clear view of the gate. Refer to the
Emergency Stop Button
OPEN terminal.
•Connect radio and other remote access (non-resetting controls) to the RADIO OPTIONS terminals.
•Open and close the gate to confirm that it was properly installed and to ensure reduced risk of entrapment.
Verify the clearance between the gate and adjacent structures per UL 325 Safety Standards. Have a
qualified technician test the gate monthly.
•When you complete the installation, show the end user how to:
•Remove the operator covers and turn the power off and on.
•Turn the DC power switch off, which disengages the motor.
•Loosen the taper clamp and manually push the gate(s) open & close.
Secondary Entrapment Protection Sensors
. Connect radio and other remote access (non-resetting controls) to the REMOTE
.
Note: Remember to re-tighten the taper clamp before turning the DC power switch back on and
replacing the covers.
•Test the red Emergency Stop Button located on the side of the control box. It can be accessed through a
hole in the cover.
Gate operator instructions must be given to the owner per UL 325 Safety Standards.
S-2SwingSmart DC Installation and Refer ence Manual Revision E
Important Safety Instructions
WARNING
!
CAUTION
Safety Standards - Owner/User Responsibility
A moving gate can cause serious injury or death. Automatic gate operators move gates with high
force. Make sure gates and gate operators are installed to reduce the risks of entrapment. Verify
your gate and gate operator comply with UL 325 Safety Standards and ASTM F2200 Gate and
Fence Standards. Ask for a copy of the gate operator’s product literature and review it. You are
responsible for educating all gate system users about proper use of the automated gate system.
Failure to adjust and test the gate operator on a regularly maintained schedule can increase the risk
of injury or death.
•Automatic gates are for vehicular use only; provide and maintain walkways and signs to direct pedestrians
to a separate walk-through entrance.
•An automatic gate can S.T.A.R.T. at any time without warning; always keep people away from the gate
area.
•Never let children operate or play with gate controls. Keep all remote controls, especially radio
transmitters, away from children. Do not allow children to play on or around the gate, gate area, or gate
operators.
•Learn how to turn the power on and off. Learn how to manually release the gate.
Before attempting a manual release, make sure the gate is not moving.
•WARNING signs supplied with the gate operator must remain installed and clearly visible on both sides of
the gate. The signs are required to maintain UL 325 compliance.
•Never disable the Warn Before Operate buzzer and NEVER disconnect or cut its wires. The buzzer
provides an alert that the gate is about to move and it must be functional in the event of entrapment
regardless of UL 325 gate usage class. Disabling the warning buzzer may increase the risk or extent of
injury if entrapment occurs.
•Test the gate operator monthly. Specifically, test the primary Inherent Entrapment Sensor (IES) and
secondary entrapment protection sensors. The gate must reverse its direction of travel upon contact with a
rigid object and/or stop, when an object activates the non-contact sensors. After adjusting the force or the
limit of travel, retest the gate operator. Failure to adjust and test the gate operator on a regularly maintained
schedule can increase the risk of injury or death.
•Have a professional gate installer routinely test the entire gate operator and entrapment protection sensors.
Have a qualified service person make repairs to gate hardware to keep the gate running smoothly.
Revision ESafety RequirementsS-3
Important Safety Instructions
CAUTION
!
Hazardous Materials and Proper Disposal
SwingSmart uses sealed, state-of-the-art Absorbed Glass Mat (AGM) batteries and highly recommends
replacing used batteries with new AGM-type batteries.
The batteries used with the SwingSmart gate operator contain materials that are considered hazardous to the environment. Proper disposal of the battery is required by federal law. Refer to
federal guidelines found in
To reduce the risk of fire or injury to persons:
•Observe the polarity between the batteries and charging circuit.
•Never mix battery sizes, types, or brands. HySecurity strongly recommends that only sealed AGM style
batteries be used.
•Exercise care in handling batteries. Be aware that the metal found in rings, bracelets, and keys can conduct
electricity, short the batteries, and cause potential injury.
•Do not open or mutilate the batteries. Battery cells contain corrosive materials which may cause burns and
other injuries. The material within batteries is toxic.
•Always dispose of batteries properly. Do NOT place batteries in fire. The battery cells may explode. Follow
federal guidelines for proper disposal of hazardous waste.
•Replace batteries according to the instructions found in
Hazardous Waste Regulations
.
DC Battery Replacement
.
S-4SwingSmart DC Installation and Refer ence Manual Revision E
Secondary Entrapment Protection Sensors
CAUTION
!
S
ECONDARY
SwingSmart is equipped with a primary, Type A, inherent entrapment sensor (IES). UL 325 Safety Standard
compliance requires installation of secondary entrapment protection sensors, the number of which, depends on
the entrapment hazards that exist at each particular installation.
To comply with UL 325, the following external sensors may be used:
•Contact sensors, such as edge sensors
•Non-contact sensors, such as photoelectric eyes
The site designer or installer can choose either photoelectric eyes or edge sensors or use these devices in
combination. Whatever devices are used, protection in both the opening and closing directions of gate travel
must be provided.
The UL 325 Safety Standard for automatic swinging gates specifically requires that edge sensors or
photoelectric eyes or a combination of both devices be installed to protect against pedestrian entrapment in
BOTH directions of the gate travel and where an entrapment hazard exists.
E
NTRAPMENT
P
ROTECTION
S
ENSORS
PHOTOELECTRIC EYES:
obstruction exists, such as the perimeter reachable by a moving gate.
A photoelectric eye or contact sensor is also required to protect against possible entrapment if
the gate opens to a position less than 16 inches (40.6cm) from any object, such as a post or wall.
EDGE SENSORS:
gate where the risk of entrapment or obstruction exists. If the bottom edge of the swing gate is situated more
than 6-inches (152 mm) above ground level at any point in its arc of travel, one or more contact sensors must
be located on the bottom edge, as well.
SENSOR SECURITY:
between the sensor and gate is not subjected to mechanical damage.
SENSOR FUNCTION and COMMUNICATION:
must be located so its signal is not impeded by building structures or other obstructions. All sensors must be
installed so that they function as intended for the end-use conditions.
UL 325 LISTING:
Components” under UL 325 in order to be deemed acceptable for use in a gate operator. Study the
Safety Instructions
Locate edge sensors and/or photoelectric sensors accordingly.
Be certain that a sufficient number of sensors are used so that pedestrians are protected from entrapment in
both directions of the gate travel and all hazard areas are fully protected. Refer to the UL website at
www.ul.com for the most up-to-date list of gate operator safety standards (UL 325). Refer to www.astm.org for
a complete list of ASTM F2200 Gate and Fence Standards.
One or more edge sensors shall be located on the inner and outer leading edge of a swing
The edge sensors and photo electric eyes must be tested and labeled as “Recognized
and consider your specific installation to determine where the greatest entrapment risks exist.
One or more photoelectric eyes shall be located where the risk of entrapment or
A hard-wired sensor shall be located and its wiring arranged so that communication
A sensor that transmits its signal to the gate operator
Important
Revision ESafety RequirementsS-5
Secondary Entrapment Protection Sensors
Identifying Gate Operator Category and Usage Class
The SwingSmart operator, according to UL 325 Safety Standards, falls in the Swing Gate and Vertical Barrier
Arm category for gate operators. It’s usage class is determined by the area that the vehicular gate services.
Four different vehicular usage classes are defined by UL 325:
Class I
Class I: Intended for use in a location of one to four single family dwellings or a
parking area associated with one to four single family dwellings.
Class II
Class III
Class IV
Class II: Intended for use in a commercial location or building such as a multifamily housing units (five or more single family units) hotels, garages, retail stores
or other buildings servicing the general public.
Class III: Intended for use in an industrial location or building such as
factories or loading docks or other locations not intended to service the
general public.
Class IV: Intended for use in guarded industrial locations or buildings such
as an airport security area or other restricted access location, not servicing
the general public, in which access is monitored by security personnel or via
closed circuitry.
S-6SwingSmart DC Installation and Refer ence Manual Revision E
Secondary Entrapment Protection Sensors
NOTE
CAUTION
Choosing Secondary Entrapment Protection
The site designer or installer must determine which secondary entrapment sensor devices will be installed with
the SwingSmart operator to meet UL compliance. The type of entrapment sensor device systems are described
below. For a complete listing of the requirements, see UL 325 Safety Standards.
SwingSmart is equipped with a primary, Type A, inherent entrapment sensor (IES) that complies with UL 325. Any impediment to gate travel causes the gate to stop and reverse.
Usage ClassPrimary Type DeviceSecondary Type Device
Class I, II, IIIAB1, B2, C, or D
Class IVAB1, B2, C, D, or E
To comply with UL 325, refer to the chart and take the following steps:
1. Select the Usage Class according to the gate’s locale and purpose.
2. The required UL 325 primary Type A sensor is an integral part of the SwingSmart system.
3. Based on the gate’s usage class, choose Secondary Type Devices: B1, B2, C, D, or E.
•To comply using B1 - install non-contact sensors (photoelectric sensor or the equivalent).
•To comply using B2 - install contact sensors (edge sensor device or the equivalent).
•To comply using a Type D device requires a CONSTANT HOLD push-button station. This CONSTANT
HOLD push-button station must be the only device that opens and closes the gate. It can only be used where
the gate and push button station will be monitored by personnel 24 hours a day in full view of the gate area.
An automatic closing device (such as a timer, loop sensor, or similar device) must not be employed. A Warning
placard stating, “WARNING - Moving Gate has the Potential of Inflicting Injury or Death - Do Not
S.T.A.R.T. the Gate Unless the Path is Clear” must be placed adjacent to the gate operator controls.
While compliance is possible with Type C, which is a low force limiting clutch, the SwingSmart
operator develops more gate actuation force than is permitted under the UL 325 Safety Standards and, therefore, its clutch cannot be considered an entrapment protection device.
Similar compliance issues exist with a Type E device (audio warn before operate alarm). A Type
E device is permitted as a means of secondary entrapment protection by UL 325 in Class IV
applications, but it is not recommended by HySecurity because a buzzer warns, but cannot
protect against possible entrapment. HySecurity highly recommends, even for Class IV use, that
secondary entrapment protection (edge or photo-eye sensor) devices be installed to detect
possible entrapment.
Revision ESafety RequirementsS-7
Emergency St op Button
Red
Emergency
Stop button
E
MERGENCY
An emergency stop button that is accessible from the
outside of the operator is a requirement for compliance
with UL325 Safety Standards. The red emergency stop
button on the SwingSmart operator is located inside a hole
cutout on the cover.
Pressing the emergency stop button while the gate is
opening or closing disables the automatic close timer and
stops gate travel. The gate travel remains stopped until the
operator receives any open or close signal.
Make sure all users of the gate know where the emergency
stop button is located.
A screwdriver or hex key can be used to press lightly on the
switch to activate it.
S
TOP
B
UTTON
E
MERGENCY
Make sure to teach all users how to turn off electric power and how to move the gate manually. SwingSmart
allows a gate to be pushed manually when the taper clamp is loosened. It is recommended that you turn off DC
power which disengages the motor allowing you to easily move the gate.
When you turn DC power off, the following occurs:
•The motor disengages which keeps it from running should any relay or open/close leaf functions be set.
•The GATE NO LOAD (FAULT 4) may appear on the display.
To manually open the gate(s), take the following steps:
1. Remove the covers and turn off.
2. Extend the taper handle and loosen the clamp by turning the handle counter-clockwise. Refer to
Figure 1-16 on page 1-15.
3. Swing the gate(s) open or close.
To return SwingSmart to automatic operation, take the following steps:
1. Make sure the gate(s) is not moving.
2. Tighten the taper clamp until no slippage occurs when you simulate a gate strike. Refer to
Clamp
on page 1-15.
R
ELEASE
Setting the Taper
3. Flip the DC power switch ON.
4. Clear any faults by pressing STOP or RESET.
S-8SwingSmart DC Installation and Refer ence Manual Revision E
Wind Load Factors & Site Prep
CAUTION
!
W
IND
Wind load is always a factor when considering the appropriate gate for a particular site. Solid gate panels
produce a larger wind load than gates with slats or open decorative features. If you are installing a gate operator
in high wind areas, the gate design will affect the load on the gate operator. Because wind force acts the same as
an obstruction, it is important that gates be designed to present a relatively low surface area for the wind to
push on the gate panel.
If the gate is heavy and near the weight capacity of what the gate operator can handle (see specifications for
SwingSmartDC on the back cover), make sure it has an open design that allows wind to flow through it. A
solid or semi-solid gate design under certain wind load conditions may cause damage to the gate operator and
is not covered by the HySecurity Limited Warranty.
Several factors play into the calculations of the wind load on a gate panel. To find out the maximum wind
speed in areas around the United States, search for US government wind speed maps on the internet. If you
don’t know how to calculate for wind load, ask a mechanical engineer or site architect for assistance prior to
installing the gate operator and gate panels.
SwingSmartDC incorporates a primary Type-A inherent entrapment sensor (IES) into its design per UL 325
Safety Standards. (More information about adjusting the adapative IES software can be found in this manual
under,
reverse direction. This feature may be falsely triggered in excessively windy conditions because the wind itself,
acting over the surface area of the gate panel, can provide the necessary force to trigger the IES.
L
OAD
Adjusting the IES Sensitivity
F
ACTORS
& S
.) When the IES trips, it sends a signal to the gate operator to stop and
ITE
P
REP
Do not adjust IES sensitivity to accommodate for inappropriately designed gate panels. Loss of
IES sensitivity increases mechanical wear on the gate hardware and the gate operator. It may
also pose a safety hazard. Compensating for wind loads by adjusting the IES may set the IES
sensitivity to a level which, when encountering an obstruction, ignores the obstruction and fails
to reverse direction. For more information, refer to
Adjusting the IES Sensitivity
.
Revision ESafety RequirementsS-9
Safety Noti ce s
DANGER
!
WARNING
!
CAUTION
!
CAUTION
Attention
- Take Note -
- Danger -
Keep Away
Entrapment
Zone
Possible
Pinch Point
S
AFETY
The following four levels of safety notices are used where applicable within this manual; each notice contains
information specific to the situation.
N
OTICES
Indicates death or serious injury
Indicates death or serious injury
Indicates mild or moderate injury
Indicates damage to equipment
C
OMMON INDUSTRIAL
The following international safety symbols may appear on the product or in its literature. The symbols are used
to alert you to potential personal injury hazards. Obey all safety messages that follow these symbols to avoid
possible injury or death.
will
occur if the hazardous situation is not avoided.
could
occur if the hazardous situation is not avoided.
could
occur if the hazardous situation is not avoided.
is probable
if the hazardous situation in not avoided.
S
YMBOLS
S-10SwingSmart DC Installation and Reference Manual Revision E
S
Secure Side
Public Side
C
L
Pedestrian gate
Make sure a separate walkthrough entrance is available and
its pedestrian path is clearly
designated.
Edge sensors
detectors
In-ground vehicle loop
Reflector for
photo eye
Photo eye
Keypad or Card Reader
Mount access control devices
at least 6ft (1.8m) beyond gate.
Earth ground
Attach WARNING Signs
Be sure to place the
WARNING signs on both
sides of the gate. For your records, take a
photograph of the completed installaon site.
WARNING
Wind Load Factors
Design gate panels to
accommodate for wind loads.
ITE
O
VERVIEW
& P
Site Overview & Planning
Installation
Chapter 1
LANNING
SwingSmart DC 20SwingSmart DCS 20 Solar
Duty cycle: continuousDuty cycle: continuous
Power, single phase: Switch selectableSolar-powered
230 volts, 1.5 amps, 50/60 Hertzpanels and a minimum of 5 solar hours/day.
Motor: ½ hpMotor: ½ hp
DC Batteries: Two 8Ah (50Ah optional)DC Batteries: Two 8Ah (50Ah optional)
Gate time to open/close: Gate time to open/close:
Approximately 10 to 15 secondsApproximately 10 to 15 seconds
1. Follow the local building codes to
identify the frost line and determine
the required depth of the concrete pad.
HySecurity recommends a minimum
16-inch (40.6cm) depth with a
minimum 2-inch (51cm) extension
above ground level. Refer to Figure 1-2
and Figure 1-3.
2. Before pouring the pad, consider
conduit placement so it fits within the
confines of the cutout in the
SwingSmart base plate as shown in
Figure 1-3. Run separate conduits for:
•high voltage wiring (115-230V
supply power) including
equipment ground
•low voltage wiring (12V and 24V
accessory power) including:
•vehicle loop control wiring
•master/slave connections
•earth ground (NEC/NFPA)
1-2SwingSmart DC Installation and Refer ence Manual Revision E
Pad Condition
NOTE
CAUTION
2.5"
7.6"
2.8"
1.8"
1.5"
3.5"
6" x 7"
(15.2cm x 17.7cm)
(8.9cm)
(3.8cm)
(4.6cm)
(19.3cm)
22" Cover
(56cm)
6.3cm
7.1cm
20" Cover
(50.8cm)
10.5" (26.7cm)
23" (58.4cm)
21" (53.3cm)
12" (30.5cm)
14" (35.6cm)
5.3"
5.7" (14.5cm)
minimum
10.5"
(13.4cm)
minimum
minimum
26.7cm
Pad Depth: 16" minimum
2" minimum
(51mm)
(41cm)
Output Shaft Center
Drill 4 holes for ½" x 3 ½" concrete anchors
6" x 7" conduit
area
Output
Shaft
Center
Cover area
Chassis base
14.5 x 16"
36.8 x 40.6cm
Conduit
area
Figure 1-3.
SwingSmart provides a 6 x 7-inch (15.2 x 17.7cm) cutout in its chassis base for conduit.
Refer to Figure 1-3. The design also provides a 9.6-inch (24.4cm) height between the control
box and chassis base for pulling and placement of wires.
3. Extend conduit height 2-inches (51mm) above the pad (4-inches/102mm above ground level). Make
sure the concrete forms are square with the gate and the pad is level. Refer to Figure 1-3 for minimum
pad dimensions.
Be sure to restrict conduit to the 6 x 7-inch (15.2 x 17.7cm) cutout in the chassis base if you
plan to use the extended battery backup kit. The area designed for the optional dual 50Ah batteries may be obstructed if conduit is routed elsewhere. Refer to
Backup Kit
.
Installing the Extended Battery
Revision EInstallation1-3
Pad Condition
CAUTION
Using an Existing Pad
In many applications, SwingSmart may be a replacement operator for an existing gate system. Make sure the
pad is level and inspect the pad for:
•Compliance with local building codes.
•Appropriate distance from the gate. Refer to Figure 1-3.
•Appropriate dimensions for SwingSmart installation.
•Durability.
To use an existing pad, take the following steps:
1. Remove any existing equipment from the pad.
2. Measure the pad to ensure it is sized properly for SwingSmart.
3. Mark the center shaft location.
4. Follow the steps in
Consider positioning the operator so existing conduit exits through the cutout in the SwingSmart base plate. Cutting small holes in the base plate for pre-existing conduit is permissible,
but not recommended because it can impair the strength of the chassis and void the Limited
Warra nty.
Mounting the Operator
.
1-4SwingSmart DC Installation and Refer ence Manual Revision E
U
NOTE
1
2
3
5
6
4
Front cover
Rear cover
NPACKING THE
O
PERATOR
Unpacking the Operator
Figure 1-4.
Prepare the gate operator for installation. See Figure 1-4.
1. Remove the top cap by unscrewing the knob.
2. Unfasten the side cover latches.
3. Remove the front cover.
4. Use a Phillips-head screwdriver to remove the two screws that secure the top of the rear cover. Set the
screws aside.
5. Remove the two wing nuts that secure the rear cover to the base plate and set the rear cover aside. Set the
wing nuts aside.
Do not lose the Phillips-head screws or wing nuts as they are used to secure the rear cover when
the installation is complete.
6. Remove the four lag bolts and separate the operator from the shipping boards.
Revision EInstallation1-5
Mounting the Operator
Photo Eye
Photo Eye
For short gates up to 10 feet (3m):
If X = 10.5",
Set Y dimension at 14, 18, or 20".
(35.6, 45.7, or 50.8cm)
For medium gates up to 13 feet (3.9m):
If X = 12",
Set Y dimension at 22, 24, or 28".
(55.9, 61, or 71cm)
For long gates up to 20 feet (6.1m):
If X = 15",
Set Y dimension at 30, 35, or 40".
(76, 89, or 102cm)
Hinge Center
Output Shaft Center
X
Y
Potential entrapment area.
Minimum 16
"
(40.6cm) clearance
required. If less than 16
"
, install a
photo-eye or edge sensor.
Figure 1-6.
Concrete
anchor
Fasteners
Concrete
anchors
Base plate
Concrete
pad
M
OUNTING THE
O
PERATOR
Install the operator, by taking the following steps:
1. Assess any limitations in the surrounding area such as
curbs, walls, or bushes.
2. Before placing the operator on the pad, measure and
mark the output shaft center on the concrete pad by
selecting the X and Y dimensions. Refer to Figure 1-3
and Figure 1-5.
3. Set the operator base on the concrete pad and use it as a
template. Position the operator base so the center mark
on the pad aligns with the small hole in the base plate.
Mark the fastener and conduit cutouts. Remove the
operator from the concrete pad and drill the holes for
the concrete anchors.
4. Mount the operator with four ½ x 3½-inch concrete
anchors as shown in Figure 1-6.
1-6SwingSmart DC Installation and Refer ence Manual Revision E
Figure 1-5.
G
CAUTION
!
Short Gate Installation:
For gates up to 10 feet (3 meters)
X
Y
Xg
14"23.5"
10.5"
18"27.5"
Medium Gate Installation:
For gates up to 13 feet (4 meters)
Long Gate Installation:
For gates up to 20 feet (6 meters)
Custom Gate Installation:
X
Y
Xg
X + Y - 1
36cm
27cm
60cm
46cm
70cm
20"29.5"
51cm
75cm
X
Y
Xg
22"33"
12"
24"35"
56cm
31cm
84cm
61cm
89cm
28"39"
71cm
99cm
X
Y
Xg
30"44"
15"
35"49"
76cm
38cm
112 cm
89cm
124cm
40"54"
101cm
137cm
Operator Center
Photo eye
Horizontal
cross member
Hinge Center
X
Y
Xg
ATE
B
RACKET AND
L
INKAGE
Installing the Gate Bracket
Gate Bracket and Linkage Arms
A
RMS
1. Secure the gate to prevent movement.
2. Determine the proper position of the gate bracket. Use the chart for reference.
3. Measure and position the gate bracket so it is level with the arm on the operator. Clamp the gate bracket to
Revision EInstallation1-7
Figure 1-7.
If vertical bars make up the gate design, be sure to install a horizontal cross member to provide
the necessary support to the gate arm. Do not mount the bracket to a small number of vertical
pickets. Pickets will bend in the event of a gate strike.
Hint
: Determine if you have a short, medium, or long gate. If the X and Y dimensions in the chart are the
same as your install, set the gate bracket at the Xg dimension. If your install does not fit to the chart specs,
use the Custom Gate Installation formula to determine the proper gate bracket placement.
the horizontal cross member.
Gate Bracket and Linkage Arms
NOTE
2
1
4
3
Taper handle
Stub arm
Attaching the Stub Arms
Figure 1-8.
1. Attach the swivel eye bolt to the gate bracket using the fasteners provided.
2. Remove the fasteners from the taper clamp assembly.
3. Align the stub arm and secure it to the taper clamp assembly using the fasteners removed in step 2.
4. Pull the taper handle to lengthen it. Adjust the handle so the ball detent fits into its cutout and secures the
handle length. Turn the handle counterclockwise to loosen the taper clamp. Figure 1-8.
Do not retighten the taper clamp. It needs to remain loose for manual gate adjustments.
1-8SwingSmart DC Installation and Refer ence Manual Revision E
Loading...
+ 106 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.