Pad Condition ........................................................................................................................................... 1-2
Using an Existing Pad ............................................................................................................................... 1-3
Front Installation ....................................................................................................................................... 1-4
Aligning the Chain .................................................................................................................................... 1-9
Connecting the Battery and Turning DC Power ON .............................................................................. 1-10
Programming the Initial Setup Menu ...................................................................................................... 1-11
Establishing the OPEN & CLOSE Limits ............................................................................................... 1-12
Installing the Target Magnet ................................................................................................................... 1-13
Front Installation .............................................................................................................................. 1-14
Installing the Extended Battery Backup Kit .............................................................................................. 2-12
Chapter 3: Display and Menu Options
I
NITIAL SETUP
Turning Both Power Switches On ............................................................................................................. 3-2
Using the Smart DC Controller Buttons In Menu Mode ........................................................................... 3-3
R
UN MODE
Understanding Gate Status Displays .......................................................................................................... 3-4
Using the Smart DC Controller Buttons in RUN Mode ............................................................................ 3-5
Viewing Operator Status Displays .............................................................................................................. 3-6
U
SER MENU
Adjusting the Close Timer ......................................................................................................................... 3-8
Setting the Time and Date ......................................................................................................................... 3-9
Setting AC Power Loss Gate Function ..................................................................................................... 3-10
Adjusting the Display Contrast ................................................................................................................ 3-11
I
NSTALLER MENU
Resetting the OPEN and CLOSE Limits ................................................................................................. 3-16
4SlideSmart DC Installation and Reference ManualRevision D
Intelligent Features: Smart DC Controlle rTM
Introducing SlideSmart DC
Thank you for purchasing our premium SlideSmart DC™ slide gate operator. At HySecurity® Gate, Inc., we pride
ourselves on quality. Our new line of electromechanical gate operators include a number of unparalleled user benefits:
Robust - An especially low flex, corrosion resistant, steel chassis combines with an attractive, key-locked, fade
resistant, roto-molded cover. The components on the Smart DC Controller
which shield them from power surges and lightning strikes.
Power - The Smart DC Controller provides variable speed control to a powerful, continuous duty 24V DC
motor which drives the gearbox. The electronics, motor and gear box are rated to operate in temperatures that
range from -13°F to 158°F (-25°C to 70°C). SlideSmart DC 15 is rated for gates up to 40 feet long and 1,500
pounds (12m and 682kg). SlideSmart DC 10F is rate for gates up to 40ft and 1,000lbs. (12m and 454kg).
Solar options are available for both models.
Finesse - A variable rate of gate acceleration and deceleration, dependent upon gate weight and length, assures
very smooth handling.
™
are protected by opto-isolators
UPS backup and Solar ready - Two 12V, 8 amp hour (Ah) batteries will provide a fully functional gate operator
(up to 4000ft/1219m of gate travel) when AC power is unavailable. Four user-selectable UPS modes are
available. 12VDC and 24VDC are available to power accessory controls. An optional base extension is available
that provides space for the optional 50Ah batteries which support solar applications or usage during extended
power outages.
I
NTELLIGENT
Menus and User relays - The Smart DC Controller has 46 menu items to allow installer configuration of gate
function and two user relays, which can be configured for 22 different functions.
Independent adjustment for open and close gate speeds - An easy-to-use menu on the Smart DC Controller
allows the installer to vary the open and close speed settings.
Intelligent Inherent Entrapment Sensor (IES) - Any impediment to gate travel is sensed by the system, stopping
gate movement per UL 325 Safety Standards. The intelligent system monitors gate power then adapts the IES
to trip at an adjustable threshold above normal power.
Improved Liquid Crystal Display (LCD) - A 32-character LCD provides increased readability for programming
and troubleshooting.
USB communications port - A direct connect provides accessibility to download system diagnostics and upload
system configurations using the Smart Touch Analyze and Retrieve Tool (START) software.
F
EATURES
: S
MART
DC C
ONTROLLER
TM
START software and diagnostics - With START software loaded on a laptop computer, you can get the latest
software upgrade and have an invaluable troubleshooting tool for all HySecurity operators. To download this
free software, visit the HySecurity website at www.hysecurity.com.
Revision DIntroducing SlideSmart DCIntro-3
Technical Support
T
ECHNICAL
For technical support, call your installer or authorized HySecurity distributor. Obtain the serial number of your
operator before calling. Refer to SlideSmart Components on the front page. For the name of a distributor near
you, call HySecurity at 800-321-9947.
For information about HySecurity training for installers, maintenance personnel and end users, refer to the
company website at www.hysecurity.com or call 800-321-9947.
S
UPPORT
Intro-4SlideSmart DC Installation and Reference Manual Revision D
Installer's Check List
I
NSTALLER'S
C
HECK
L
IST
The following list provides a high level overview of the tasks involved in installing the SlideSmart DC gate
operator. Take a moment to review the list and check off the items as you complete the install.
?
Site Prep - concrete pad location/dimensions, distance from gate, chain height, and mounting
considerations: post or base extension, front or rear installation.
?
Make sure gate installation complies with ASTM F2200 Standard Specification for Automated Vehicular
Gate Construction. And, install the supplied WARNING sign on both sides of the gate.
?
Check for compliance with local codes, site conditions, and NEC standards.
?
Install operator - (on concrete pad use four ½ - 13 x 3.5in long concrete wedge anchors.)
?
Attach chain end bracket to gate at proper height.
?
Attach chain to end brackets and feed under SlideSmart idlers and over chain sprocket.
?
Tighten chain using tensioning bolts.
?
Verify chain is level with idlers and parallel to operator and gate.
?
Connect red wire to DC Power Switch.
?
Turn DC Power ON.
?
Complete Initial Setup Menu programming.
?
Install the target magnet and make sure it is in line with and passes by the target sensor so it can be
recognized by the software programming.
?
Connect AC Power.
?
Connect all accessory devices.
?
Set the Close Timer (through the User Menu).
?
Set gate speed, if applicable (through Installer Menu). Refer to START (Smart Touch Analyze and Retrieve
Tool) in the Reference section.
?
Set IES sensitivity, if needed (through Installer Menu).
?
Check the Smart DC Controller software version. If needed, upload the latest version from
www.hysecurity.com. See Smart Touch Analyze and Retrieve Tool.
?
Program changes through the Installer Menu depending on the accessory devices that you have installed.
?
Give a copy of the operator instructions to the end user. Show the end user how to:
•Remove the operator cover. Turn the power off and on to demonstrate learn limits after DC/AC cycles.
•Turn the DC power switch off, which disengages the motor, and manually push the gate.
•Test the red Emergency Stop Button located on the side of the control box. It can be accessed through a
hole in the cover. See illustration on page S-8.
?
Take photographs of the completed installation site and save it in your business files.
Revision DIntroducing SlideSmart DCIntro-5
Installer's Check List
Intro-6SlideSmart DC Installation and Reference Manual Revision D
Important Safety Instructions
WARNING
!
Safety Requirements
Automatic gate operators provide user convenience and security. However, because these machines can produce
high levels of force, it is imperative that gate operator system designers, installers and end users be aware of
potential hazards associated with improperly designed, installed, or maintained systems. The gate operator is
only one component of the total gate operating system. It is the joint responsibility of the architect, site
designer, purchaser, installer and end user to verify that the total system is appropriately configured for its
intended use. Additionally, certain municipalities have established licensing, codes or regulations that regulate
automated gate system design and installation. Consult local government agencies for up-to-date rules and
regulations prior to gate system design or installation.
I
MPORTANT
A moving gate can cause serious injury or death. Start the gate operator only when the gate’s
travel path is clear.
S
AFETY INSTRUCTIONS
Hazards, associated with automatic gates, can be reduced with proper site design, installation, and use.
Installers, maintenance crew, and owners/users must read and follow the Important Safety Instructions in this
manual and review all the literature that accompanies the product. It is important that only qualified installers
handle the installation of the SlideSmart gate operator. A “qualified” installer has one of the following:
•A minimum of three years experience installing similar equipment.
•Proof of attending a HySecurity Technical Training seminar within the past three years.
•Significant manufacturer endorsements of technical aptitude in gate operator installation and operation.
Underwriter Laboratories (UL) and the American Society for Testing and Materials (ASTM) are responsible for
current safety standards and regulations regarding gate operators and automated gates. All aspects of gate
installation must comply with the appropriate safety standard. For the most up-to-date ASTM F2200 Gate and
Fence Standards, refer to www.astm.org. For UL 325 Safety Standard, refer to www.ul.com.
Safety Standards - Installer's Responsibility
•Study the entire contents of this manual prior to installing, operating, or maintaining the SlideSmart gate
operator. Taking extra time to align the gate operator and verify a fully functional installation will reduce
maintenance, guarantee longest system life, and ensure customer satisfaction.
•Verify the gate operator usage class for the site. Refer to
in this manual. Install SlideSmart only when the gate operator class is correct for the site and type of gate.
•Install an automatic operator only on gates that comply with ASTM F2200 Gate and Fence Standards.
Screen or enclose openings in the gate per UL 325 Safety Standards.
→
All horizontal slide gates must guard or screen openings from the gate’s base support to a minimum
height of 6 feet (183cm) above the ground. The screen mesh must prevent a sphere of 2¼-inches
(57mm) in diameter from passing through an opening in the gate or the adjacent fence that is covered
in the gate’s open position.
Identifying Gate Operator Category and Usage Class
Revision DSafety RequirementsS-1
Important Safety Instructions
NOTE
→
Physical stops exist in the gate construction to prevent over-travel in both directions and guard posts
prevent the gate from falling in the event of a roller failure.
•Before attaching the operator to the gate, slide the gate in both directions. Make sure it is level and moves
freely. A gate that slides easily reduces strain on operator components. Gravity should play no part in the
opening or closing of the gate.
•In the case of hydraulic operators, never over-tighten a clutch or pressure relief valve to compensate for a
stiff or damaged gate.
•Make sure all exposed pinch points, rollers and wheels are guarded.
•To reduce the risk of entrapment throughout the entire travel path, make sure the gate is installed in a
location so enough clearance is supplied between the gate and adjacent structures when opening or closing.
Minimize the parallel gap between the gate and the fence.
•Make sure a separate walk-through entrance is nearby. Make certain a clear pedestrian path is designated
and signs direct pedestrians to the walk-through gate. The automated gate entry is for vehicle use only. No
one should cross the path of a moving gate.
•Install the gate operator on the secure (non-public) side of the gate. Locate controls (Open, Close, Stop/
Reset) where a user will have a clear view of the gate.
•Mount access control devices beyond reach of the gate. The control devices that operate the gate must be:
•Located in a clear line of sight to the gate.
•Mounted beyond 6 feet (183cm) of the gate, to prevent users from touching or accessing the gate
while operating the controls. People attempting to access the controls by reaching through or around
the gate can be seriously injured or killed by the moving gate.
•Incorporate a security feature to prevent unauthorized use.
•The gate operator must be properly grounded and the incoming power voltage must match the voltage
label on the junction box.
•Install enough external entrapment protection sensors so that pedestrians are protected from entrapment in
both directions of the gate travel and all hazard areas and possible pinch points are fully protected. Review
the information found in
•Install the supplied WARNING signs on the inside and outside of the gate so they are clearly visible from
both sides of the gate. Installing the signs is a requirement for UL 325 compliance.
•Connect radio and other remote access (non-resetting controls) to the RADIO OPTIONS terminals.
•Open and close the gate to confirm that it was properly installed and to ensure reduced risk of entrapment.
Verify the clearance between the gate and adjacent structures per UL 325 Safety Standards. Have a
qualified gate technician test the gate monthly.
•When you complete the installation, show the end user how to:
→
Remove the cover. Turn the power off and on to demonstrate relearn limits after DC/AC cycles.
→
Turn the DC power switch off, which disengages the motor, and manually push the gate.
→
Use the Emergency Stop Button located on the side of the control box. It can be accessed through a
hole in the cover.
Gate operator instructions must be given to the owner per UL 325 Safety Standards.
Secondary Entrapment Protection Sensors
.
S-2SlideSmart DC Installation and Reference Manual Revision D
Important Safety Instructions
WARNING
!
CAUTION
Safety Standards - Owner/User Responsibility
A moving gate can cause serious injury or death. Automatic gate operators move gates with high
force. Make sure gates and gate operators are installed to reduce the risks of entrapment. Verify
your gate and gate operator comply with UL 325 Safety Standards and ASTM F2200 Gate and
Fence Standards. Ask for a copy of the gate operator’s product literature and review it. You are
responsible for educating all gate system users about proper use of the automated gate system.
•Automatic gates are for vehicular use only; provide and maintain walkways and signs to direct pedestrians
to a separate walk-through entrance.
•An automatic gate can start at any time without warning; always keep people away from the gate area.
•Never let children operate or play with gate controls. Keep all remote controls, especially radio
transmitters, away from children. Do not allow children to play on or around the gate, gate area, or gate
operators.
•Learn how to turn the power on and off. Learn how to manually release the gate.
Before attempting a manual release, make sure the gate is not moving.
•WARNING signs supplied with the gate operator must remain installed and clearly visible on both sides of
the gate. The signs are required to maintain UL 325 compliance.
•Do not physically disable the warning buzzer and NEVER disconnect or cut its wires. The buzzer is
required to function in the event of entrapment, regardless of UL 325 gate usage class. It provides an alert
that the gate is about to move. Disabling the warning buzzer may increase the risk or extent of injury if
entrapment occurs.
•Test the gate operator monthly. Specifically, test the primary Inherent Entrapment Sensor (IES) and
secondary entrapment protection sensors. The gate must reverse its direction of travel upon contact with a
rigid object and/or stop when an object activates the non-contact sensors. After adjusting the force or the
limit of travel, retest the gate operator. Failure to adjust and test the gate operator on a regularly maintained
schedule can increase the risk of injury or death.
•Have a professional gate installer routinely test the entire gate operator and entrapment protection sensors.
Have a qualified service person make repairs to gate hardware to keep the gate running smoothly.
Revision DSafety RequirementsS-3
Important Safety Instructions
CAUTION
!
Hazardous Materials and Proper Disposal
SlideSmart uses sealed, state-of-the-art Absorbed Glass Mat (AGM) batteries and highly recommends replacing
used batteries with new AGM-type batteries.
The batteries used with the SlideSmart gate operator contain materials that are considered hazardous to the environment. Proper disposal of the battery is required by federal law. Refer to
federal guidelines found in
To reduce the risk of fire or injury to persons:
•Observe the polarity between the batteries and charging circuit.
•Never mix battery sizes, types, or brands. The charging circuit on HySecurity DC operators is designed for
AGM-type batteries, not lead acid-type batteries. HySecurity strongly recommends that only sealed AGM
style batteries be used.
•Exercise care in handling batteries. Be aware that the metal found in rings, bracelets, and keys can conduct
electricity, short the batteries, and cause potential injury.
•Do not open or mutilate the batteries. Battery cells contain corrosive materials which may cause burns and
other injuries. The material within batteries is toxic.
•Always dispose of batteries properly. Do NOT place batteries in fire. The battery cells may explode. Follow
federal guidelines for proper disposal of hazardous waste.
•Replace batteries according to the instructions found in DC Battery Replacement.
Hazardous Waste Regulations
.
S-4SlideSmart DC Installation and Reference Manual Revision D
Secondary Entrapment Protection Sensors
CAUTION
!
S
ECONDARY
SlideSmart is equipped with a primary, Type A, inherent entrapment sensor (IES). UL 325 Safety Standard
compliance requires installation of secondary entrapment protection sensors, the number of which, depends on
the entrapment hazards that exist at each particular installation.
To comply with UL 325, the following external sensors may be used:
•Contact sensors, such as edge sensors
•Non-contact sensors, such as photoelectric eyes
The site designer or installer can choose either photoelectric eyes or edge sensors or use these devices in
combination. Whatever devices are used, protection in both the opening and closing directions of gate travel
must be provided.
The UL 325 Safety Standard for automatic sliding gates specifically requires that edge sensors or photoelectric
eyes or a combination of both devices be installed to protect against pedestrian entrapment in BOTH
directions of the gate travel and where an entrapment hazard exists.
E
NTRAPMENT
P
ROTECTION
S
ENSORS
PHOTOELECTRIC EYES:
obstruction exists, such as the perimeter reachable by a moving gate.
A photoelectric eye or contact sensor is also required to protect against possible entrapment if
the gate opens to a position less than 16 inches from any object, such as a post or wall.
EDGE SENSORS:
where the risk of entrapment or obstruction exists. One or more contact sensors (edge sensors) shall be located
at the leading edge, trailing edge, and post-mounted, both inside and outside of a sliding gate.
SENSOR SECURITY:
between the sensor and gate is not subjected to mechanical damage.
SENSOR FUNCTION and COMMUNICATION:
must be located so its signal is not impeded by building structures or other obstructions. All sensors must be
installed so that they function as intended for the end-use conditions.
UL 325 LISTING:
Components” under UL 325 in order to be deemed acceptable for use in a gate operator. Study the
Safety Instructions
Locate edge sensors and/or photoelectric sensors accordingly. Be certain that a sufficient number of sensors are
used so that pedestrians are protected from entrapment in both directions of the gate travel and all hazard areas
are fully protected. Refer to the UL website at www.ul.com for the most up-to-date list of gate operator safety
standards (UL 325). Refer to www.astm.org for a complete list of ASTM F2200 Gate and Fence Standards.
One or more edge sensors shall be located on the leading and trailing edges of a slide gate
The edge sensors and photo electric eyes must be tested and labeled as “Recognized
and consider your specific installation to determine where the greatest entrapment risks exist.
One or more photoelectric eyes shall be located where the risk of entrapment or
A hard-wired sensor shall be located and its wiring arranged so that communication
A sensor that transmits its signal to the gate operator
Important
Revision DSafety RequirementsS-5
Secondary Entrapment Protection Sensors
Identifying Gate Operator Category and Usage Class
The SlideSmart operator, according to UL 325 Safety Standards, falls in the Slide Gate and Vertical Barrier
Arm category for gate operators. Its usage class is determined by the area that the vehicular gate services.
Four different vehicular usage classes are defined by UL 325:
Class I
Class I: Intended for use in a location of one to four single family dwellings or a
parking area associated with one to four single family dwellings.
Class II
Class III
Class IV
Class II: Intended for use in a commercial location or building such as a multifamily housing units (five or more single family units) hotels, garages, retail stores
or other buildings servicing the general public.
Class III: Intended for use in an industrial location or building such as
factories or loading docks or other locations not intended to service the
general public.
Class IV: Intended for use in guarded industrial locations or buildings such
as an airport security area or other restricted access location, not servicing
the general public, in which access is monitored by security personnel or via
closed circuitry.
S-6SlideSmart DC Installation and Reference Manual Revision D
Secondary Entrapment Protection Sensors
NOTE
CAUTION
Choosing Secondary Entrapment Protection
The site designer or installer must determine which secondary entrapment sensor devices will be installed with
the SlideSmart operator to meet UL compliance. The type of entrapment sensor device systems are described
below. For a complete listing of the requirements, see UL 325 Safety Standards.
SlideSmart is equipped with a primary, Type A, inherent entrapment sensor (IES) that complies
with UL 325. Any impediment to gate travel causes the gate to stop and reverse.
Usage ClassPrimary Type DeviceSecondary Type Device
Class I, II, IIIAB1, B2, C, or D
Class IVAB1, B2, C, D, or E
To comply with UL 325, refer to the chart and take the following steps:
1) Select the Usage Class according to the gate’s locale and purpose.
2) The required UL 325 primary Type A sensor is an integral part of the SlideSmart system.
3) Based on the gate’s usage class, choose Secondary Type Devices: B1, B2, C, D, or E.
•To comply using B1 - install non-contact sensors (photoelectric sensor or the equivalent).
•To comply using B2 - install contact sensors (edge sensor device or the equivalent).
•To comply using a Type D device requires a CONSTANT HOLD push-button station. This CONSTANT
HOLD push-button station must be the only device that opens and closes the gate. It can only be used where
the gate and push button station will be monitored by personnel 24 hours a day in full view of the gate area.
An automatic closing device (such as a timer, loop sensor, or similar device) must not be employed. A Warning
placard stating, “WARNING - Moving Gate has the Potential of Inflicting Injury or Death - Do Not Start the
Gate Unless the Path is Clear” must be placed adjacent to the gate operator controls.
While compliance is possible with Type C, which is a low force limiting clutch, the SlideSmart
operator does not utilize a clutch, therefore this option is not available.
Similar compliance issues exist with a Type E device (audio warn before operate alarm). A Type
E device is permitted as a means of secondary entrapment protection by UL 325 in Class IV
applications, but it is not recommended by HySecurity because a buzzer warns, but cannot
protect against possible entrapment. HySecurity highly recommends, even for Class IV use, that
secondary entrapment protection (edge or photo-eye sensor) devices be installed to detect
possible entrapment.
Revision DSafety RequirementsS-7
Emergency St op Button
NOTE
Red
Emergency Stop
E
MERGENCY
An emergency stop button that is accessible from the
outside of the operator is a requirement for compliance
with UL 325 Safety Standards. The red emergency stop
button is located inside a hole cutout on the SlideSmart
cover.
Pressing the emergency stop button while the gate is
opening or closing disables the automatic close timer and
stops gate travel. The gate travel remains stopped until the
operator receives an open or close signal.
Make sure all users of the gate know where the emergency
stop button is located.
A screwdriver or hex key can be used to press lightly on the
switch to activate it.
S
TOP
B
UTTON
E
MERGENCY
Make sure and teach all users how to turn off electric power and how to move the gate manually. SlideSmart
allows a gate to be pushed manually when the operator’s DC power is turned off. (
AC power off to manually push the gate.
When you turn DC power off, the following occurs:
•The motor disengages which makes it easier to push the gate open (or close)
•The GATE NO LOAD (FAULT 4) appears on the display
•The position sensor is active and established limits are remembered
To turn DC power on, take the following steps:
If you turn OFF both power switches (AC and DC) and manually move the gate, the operator
will search for the target to re-establish its limits. When you turn AC & DC power back ON,
the operator will cycle the gate and search for the target magnet (its “home” position).
An operator with the DC power switch ON and the AC power switch OFF still functions normally, but “NO AC” flashes in the display. If you “push” the gate, it will push back because the
position sensor is active and the motor is engaged.
R
ELEASE
) See NOTE.
1. Make sure the gate is not moving.
2. Flip the DC power switch on.
3. Clear any faults by pressing STOP or RESET.
You DO NOT need to turn
S-8SlideSmart DC Installation and Reference Manual Revision D
Wind Load Factors & Site Prep
CAUTION
!
W
IND
Wind load is always a factor when considering the appropriate gate for a particular site. Solid gate panels
produce a larger wind load than gates with slats or open decorative features. If you are installing a gate operator
in high wind areas, the gate design will affect the load on the gate operator. Because wind force acts the same as
an obstruction, it is important that gates be designed to present a relatively low surface area for the wind to
push on the gate panel.
If the gate is heavy and near the weight capacity of what the gate operator can handle (see specifications for
SlideSmartDC on the back cover), make sure it has an open design that allows wind to flow through it. A solid
or semi-solid gate design under certain wind load conditions may cause damage to the gate operator and is not
covered by the HySecurity Limited Warranty.
Several factors play into the calculations of the wind load on a gate panel. To find out the maximum wind
speed in areas around the United States, search for US government wind speed maps on the internet. If you
don’t know how to calculate for wind load, ask a mechanical engineer or site architect for assistance prior to
installing the gate operator and gate panels.
SlideSmartDC incorporates a primary Type-A inherent entrapment sensor (IES) into its design per UL 325
Safety Standards. (More information about adjusting the adaptive IES software can be found in this manual
under, Adjusting the IES Sensitivity.) When the IES trips, it sends a signal to the gate operator to stop and
reverse direction. This feature may be falsely triggered in excessively windy conditions because the wind itself,
acting over the surface area of the gate panel, can provide the necessary force to trigger the IES.
L
OAD
F
ACTORS
& S
ITE
P
REP
Do not adjust IES sensitivity to accommodate for inappropriately designed gate panels. Loss of
IES sensitivity increases mechanical wear on the gate hardware and the gate operator. It may
also pose a safety hazard. Compensating for wind loads by adjusting the IES may set the IES
sensitivity to a level which, when encountering an obstruction, ignores the obstruction and fails
to reverse direction. For more information, refer to Adjusting the IES Sensitivity.
Revision DSafety RequirementsS-9
Safety Noti ce s
DANGER
!
WARNING
!
CAUTION
!
CAUTION
Attention
- Take Note -
- Danger -
Keep Away
Entrapment
Zone
Possible
Pinch Point
S
AFETY
The following four levels of safety notices are used where applicable within this manual; each notice contains
information specific to the situation.
N
OTICES
Indicates death or serious injury
Indicates death or serious injury
Indicates mild or moderate injury
Indicates damage to equipment
C
OMMON INDUSTRIAL
The following international safety symbols may appear on the product or in its literature. The symbols are used
to alert you to potential personal injury hazards. Obey all safety messages that follow these symbols to avoid
possible injury or death.
will
occur if the hazardous situation is not avoided.
could
occur if the hazardous situation is not avoided.
could
occur if the hazardous situation is not avoided.
is probable
if the hazardous situation in not avoided.
S
YMBOLS
S-10SlideSmart DC Installation and Reference Manual Revision D
S
Secure Side
Public Side
Le Hand Gate
opening
g
Pedestrian gate
To comply with ASTM F2200, a screened wire mesh
Maximum 2¼” (57mm) width
between vertical bars
Target magnet on chain
Photo eye (entrapment protection shown in four locations)
Physical stop - weld stops at both ends of V track
Earth ground
Edge sensor
Edge sensor on
V track
Photo eye
Physical
stop
Make sure a separate walkthrough entrance is available and its pedestrian
path is clearly
designated.
Attach WARNING Signs
Be sure to place the
WARNING signs on both
sides of the gate. For your records, take a
photograph of the completed installaon site.
WARNING
Mount access control
beyond gate.
devices at least 6ft
Keypad or Card Reader
on trailing
edge
leading edge
extends to the top of the gate or to a minimum
height of 6 ft. (183cm) if a 2¼” (57mm) or larger
gap exists between the vertical bars.
ITE
O
VERVIEW
& P
Site Overview & Planning
Installation
Chapter 1
LANNING
SlideSmart DC 15SlideSmart DC 10F
Duty cycle: continuousDuty cycle: continuous
Power, single phase: Switch selectablePower, single phase: Switch selectable
Note:For SlideSmart DC Solar operators, refer to www.hysecurity.com
Revision DInstallation1-1
Figure 1-1.
Site Overview & Planning
19" minimum
(48.3cm)
Area
cut out
for
conduit
6.9 x 12"
(17.5 x 30.5cm)
21"
(53.3cm)
10.5"
(26.7cm)
1.6"
(4.1cm)
6.4"
(16.3cm)
10.38"
(26.4cm)
Figure 1-2.
Chain
#40 Roller
Slotted holes (4x) for
concrete anchors:
½ - 13 x 3½"
Concrete
pad
Gate
Figure 1-3.
Pad Condition
1. Follow the local building codes to
identify the frost line and determine
the required depth of the concrete pad.
HySecurity recommends a minimum
16-inch depth with a minimum 2-inch
extension above ground level. Refer to
Figure 1-2 and Figure 1-3.
2. Before pouring the pad, consider
conduit placement so it fits within the
confines of the 6.9 x 12-inch cutout in
the SlideSmart base as shown in
Figure 1-2. Run separate conduits for:
•high voltage wiring (115-230V
supply power) including
equipment ground
•low voltage wiring (12V and 24V
accessory power)
•vehicle loop control wiring
•master/slave connections
•earth ground (NEC/NFPA)
3. Extend conduit height 2-inches (5cm) above the pad (4-inches (9cm) above ground level). Make sure the
concrete forms are square with the gate and the pad is level. The operator footprint, with covers, is
approximately an 18-inch square (4.7cm). See Figure 1-2 for the minimum pad dimensions.
SlideSmart DC
operator
Conduit runs
2" (5cm) above
concrete pad
Minimum pad
height is 2" (5cm)
above grade level.
Grade level
Vehicle loop
control wires
Extra conduit
(Master/Slave power)
(Conduit may be shared with low voltage wires)
Low
voltage/Communicaon wires
Ground
wire & rod
Chain
3 max.
(91.4cm)
Ground
lug
Consult local
codes for
proper depth
1-2SlideSmart Installation and Reference Manual Revision D
In many applications, SlideSmart may be a replacement
operator for an existing gate system.
Make sure the pad is level and inspect the pad for:
•Compliance with local building codes.
•Appropriate distance from the gate. See Figure 1-4.
•Appropriate dimensions (See Figure 1-2) for
SlideSmart installation.
•Durability.
To use an existing pad, take the following steps:
1. Remove any existing equipment from the pad.
2. Measure the pad to ensure it is sized properly for
SlideSmart.
3. Check the mounting hole locations and re-drill, if
necessary.
4. Follow the steps in
Concrete Pad Mount
.
7¾"
(19.7cm)
Site Overview & Planning
Side View
Consider positioning the operator so existing conduit enters the cutout in the SlideSmart base
plate. Cutting small holes in the plastic base plate and cover for pre-existing conduit is
permissible. Two 0.875-inch (22mm) diameter holes for running conduit are also provided on
both sides of the chassis. See Figure 1-5.
Revision DInstallation1-3
Site Overview & Planning
Secure Side
Public Side
ublic Side
Note:Several different ways to mount the SlideSmart operator exist. A few are shown here.
For more detailed drawings, refer to the Installation Configurations in the Appendix.
Base extension mountPost mounted
Post mounted with base extension
Chain bracket (2x)
Chain
Physical stop (2x)
Figure 1-6.
Optional
50Ah
batteries
Chain
Front Installation
The most common and cost efficient type of installation is the front installation.
P
1-4SlideSmart Installation and Reference Manual Revision D
Site Overview & Planning
Le Hand Gate
opening
Idler Post
Posion post to maintain a minimum
distance of 1 foot (31 cm) from the end
of the gate when gate is fully closed.
End of the gate
tdl
Po
oosi
8"
5"
OPEN
OPEN
View shows how to feed chain over
sprocket and idler wheel for a
Sprocket
Chain
Idler wheel
Ta rge t
magnet
Figure 1-7.
Target magnet position between idler wheel and sprocket when gate is fully closed.
rear installation.
Chain & bracket position:
8" (20cm) and 5" (13cm)
Rear Installation
A rear installation requires additional idler wheels and gate brackets, but it provides aesthetics as the chain is
not visible along the gate.
te
s
er
p
on
Chain to Gate
Ideal distance = 3¾" (9.5cm)
Min. distance = 2½" (6.4cm)
Chain
height
8"
(20.3cm)
7¾"
(19.7cm)
Gate
Lengthen the chain
access slot by cung
the cover on the
chain side only.
17½"
(44.5cm)
Concrete pad
Side View
Revision DInstallation1-5
Unpacking the Operator
Service Outlet
115VAC, 15A
Cover
Base plate
Figure 1-8.
U
NPACKING THE
O
PERATOR
Lock
Prepare the gate operator for installation. See Figure 1-8.
1. Open the top of the box and remove packing materials.
2. Cut open the box to access the operator.
3. Lift the cover up and off the base of the operator. DO NOT lift the cover by its lock.
1-6SlideSmart Installation and Reference Manual Revision D
Install the operator, by taking the following steps:
1. Place the operator on the pad to best suit the conduit as
shown in Figure 1-2. Use the operator as a template and
center it on the pad. The chain path must be parallel
with the gate.
2. Assess any limitations in the chain path such as gate
support posts. Adjust the operator’s location as required.
Mark the mounting locations based on gate, operator,
and chain requirements. Mark the drill point at the
center of the slot to allow for adjustments.
See Figure 1-4 and Figure 1-9.
3. Remove the operator from the concrete pad and drill the
holes for the concrete anchors. See
Tip
.
4. Mount the operator with four ½ - 13 x 3½-inch
concrete anchors as shown in Figure 1-10.
Revision DInstallation1-7
Appendix.
5. For additional types of mounting options, refer to the
Tip: To keep pinpoint accuracy while drilling
the mounting holes in the concrete, use a
3/16-inch bit to pilot the holes and then move
to a ½-inch drill bit.
Gate Bracket and Chain Installation
Secure Side
Public Side
Sid
e
Chain bracket
Trai ling edge
Eye bolt
Connector link
7¾"
(19.7cm)
Leading edge view
1. Secure the gate to prevent movement.
2. Measure for proper chain alignment BEFORE welding the brackets to the gate. Make sure the chain will
run horizontal to the ground and parallel with the gate.
3. Weld the chain bracket in two places: leading edge and trailing edge. You may need to cut the length of
the bracket to achieve proper chain alignment. Gusset plates are provided and can be welded to the
bracket for added support.
4. Attach the eye bolts to the brackets, and then attach the connector link between the chain and eye bolt.
5. Feed the chain around the idler wheels and over the sprocket (See Figure 1-12) and attach the chain to
the bracket on the opposite end of the gate. Make sure the chain is horizontal to the ground and parallel
to the gate.
6. Adjust the nuts on the eye bolt to tighten the chain (minimize sag, but avoid overtightening). Chain sag
should not exceed 3 inches (76mm) from its anchor point.
view
G
ATE
B
RACKET AND
C
HAIN INSTALLATION
1-8SlideSmart Installation and Reference Manual Revision D
Figure 1-11.
Loading...
+ 118 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.