When you see these Safety Symbols and Signal Words on the following pages, they
will alert you to the possibility of serious injury or death if you do not comply with
the warnings that accompany them. The hazard may come from something
mechanical or from electric shock. Read the warnings carefully.
When you see this Signal Word on the following pages, it will alert you to the
possibility of damage to your gate and/or the gate operator if you do not comply
with the cautionary statements that accompany it. Read them carefully.
IMPORTANT NOTE
• BEFORE attempting to install, operate or maintain the operator, you must read
and fully understand this manual and follow all safety instructions.
• DO NOT attempt repair or service of your gate operator unless you are an
A vehicular gate operator (or system) intended for use in a home of one-to four
single family dwellings, or a garage or parking area associated therewith.
CLASS II – COMMERCIAL/GENERAL ACCESS VEHICULAR
GATE OPERATOR
A vehicular gate operator (or system) intended for use in a commercial location or
building such as a multi-family housing unit (five or more single family units) hotel,
garage, retail store or other building servicing the general public.
CLASS III – INDUSTRIAL/LIMITED ACCESS VEHICULAR
GATE OPERATOR
A vehicular gate operator (or system) intended for use in a industrial location or
building such as a factory or loading dock area or other location not intended to
service the general public.
CLASS IV– RESTRICTED ACCESS VEHICULAR GATE
OPERATOR
A vehicular gate operator (or system) intended for use in a guarded industrial
location or building such as an airport security area or other restricted access
locations not servicing the general public, in which unauthorized access is prevented
via supervision by security personnel.
UL325 ENTRAPMENT PROTECTION REQUIREMENTS
This chart illustrates the entrapment protection requirements for the UL325 classes.
I
II
III
IV
GATE OPERATOR ENTRAPMENT PROTECTION
UL325 ClassificationSwing Gate Operator
Primary TypeSecondary Type
CLASS I-CLASS IVAB1 or B2
In order to complete a proper installation you must satisfy the entrapment
protection chart shown. That means that the installation must have one primary
means of entrapment protection and one independent secondary means of
entrapment protection. Both primary and secondary entrapment protection
methods must be designed, arranged or configured to protect against entrapments
in both the open and close directions of gate travel.
For Example: For a gate system that is installed on a single-family residence
(UL325 Class I) you must provide the following: As your primary type of
entrapment protection you must provide
• Type A - Inherent (built into the operator) entrapment sensing and at least
one of the following as your secondary entrapment protection:
• Type B1 - Non-contact sensors such as photoelectric sensors,
• Type B2 - Contact sensors such as gate edges
NOTE: UL requires that all installations must have warning signs placed in plain view
on both sides of the gate to warn pedestrians of the dangers of motorized gate
systems.
2
Page 5
SAFETY
SAFETY INSTALLATION INFORMATION
1. Vehicular gate systems provide convenience and security. Gate systems are
comprised of many component parts. The gate operator is only one component.
Each gate system is specifically designed for an individual application.
2. Gate operating system designers, installers and users must take into account the
possible hazards associated with each individual application. Improperly designed,
installed or maintained systems can create risks for the user as well as the
bystander. Gate systems design and installation must reduce public exposure to
potential hazards.
3. A gate operator can create high levels of force in its function as a component part
of a gate system. Therefore, safety features must be incorporated into every
design. Specific safety features include:
• Gate Edges • Guards for Exposed Rollers
• Photoelectric Sensors • Screen Mesh
• Vertical Posts • Instructional and Precautionary Signage
4. Install the gate operator only when:
a. The operator is appropriate for the construction and the usage class of the gate.
b. All openings of a horizontal slide gate are guarded or screened from the
bottom of the gate to a minimum of 4 feet (1.2 m) above the ground to
prevent a 2-1/4 inches (6 cm) diameter sphere from passing through the
openings anywhere in the gate, and in that portion of the adjacent fence that
the gate covers in the open position.
SAFETY INSTALLATION INFORMATION
8. Controls intended for user activation must be located at least 6 feet (1.8 m)
away from any moving part of the gate and where the user is prevented from
reaching over, under, around or through the gate to operate the controls.
Outdoor or easily accessible controls shall have a security feature to prevent
unauthorized use.
9. The Stop and/or Reset (if provided separately) must be located in the line-ofsight of the gate. Activation of the reset control shall not cause the operator to
start.
10. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of
the gate where easily visible.
c. All exposed pinch points are eliminated or guarded, and guarding is supplied
for exposed rollers.
5. The operator is intended for installation only on gates used for vehicles.
Pedestrians must be supplied with a separate access opening. The pedestrian
access opening shall be designed to promote pedestrian usage. Locate the gate
such that persons will not come in contact with the vehicular gate during the
entire path of travel of the vehicular gate.
6. The gate must be installed in a location so that enough clearance is supplied
between the gate and adjacent structures when opening and closing to reduce the
risk of entrapment. Swinging gates shall not open into public access areas.
7. The gate must be properly installed and work freely in both directions prior to the
installation of the gate operator.
11. For a gate operator utilizing a non-contact sensor:
a. Reference owner’s manual regarding placement of non-contact sensor for
each type of application.
b. Care shall be exercised to reduce the risk of nuisance tripping, such as when a
vehicle trips the sensor while the gate is still moving.
c. One or more non-contact sensors shall be located where the risk of
entrapment or obstruction exists, such as the perimeter reachable by a moving
gate or barrier.
12. For a gate operator utilizing a contact sensor such as an edge sensor:
a. One or more contact sensors shall be located where the risk of entrapment or
obstruction exists, such as at the leading edge, trailing edge and post
mounted both inside and outside of a vehicular horizontal slide gate.
b. One or more contact sensors shall be located at the bottom edge of a
vehicular vertical lift gate.
c. A hard wired contact sensor shall be located and its wiring arranged so the
communication between the sensor and the gate operator is not subject to
mechanical damage.
d. A wireless contact sensor such as the one that transmits radio frequency (RF)
signals to the gate operator for entrapment protection functions shall be
located where the transmission of the signals are not obstructed or impeded
by building structures, natural landscaping or similar obstruction. A wireless
contact sensor shall function under the intended end-use conditions.
e. One or more contact sensors shall be located on the inside and outside leading
edge of a swing gate. Additionally, if the bottom edge of a swing gate is
greater than 6 inches (152 mm) above the ground at any point in its arc of
travel, one or more contact sensors shall be located on the bottom edge.
f. One or more contact sensors shall be located at the bottom edge of a vertical
barrier (arm).
3
Page 6
SAFETY
GATE CONSTRUCTION INFORMATION
GATE CONSTRUCTION INFORMATION
Vehicular gates should be installed in accordance with ASTM F2200: Standard Specification for Automated Vehicular Gate Construction. For a copy, contact ASTM directly at
610-832-9585 or www.astm.org.
1. GENERAL REQUIREMENTS
1.1 Gates shall be constructed in accordance with the provisions given for the
appropriate gate type listed, refer to ASTM F2200 for additional gate types.
1.2 Gates shall be designed, constructed and installed to not fall over more than
45 degrees from the vertical plane, when a gate is detached from the
supporting hardware.
1.3 Gates shall have smooth bottom edges, with vertical bottom edged
protrusions not exceeding 0.50 inches (12.7 mm) when other than the
exceptions listed in ASTM F2200.
1.4 The minimum height for barbed tape shall not be less than 8 feet (2.44 m)
above grade and for barbed wire shall not be less than 6 feet (1.83 m)
above grade.
1.5 An existing gate latch shall be disabled when a manually operated gate is
retrofitted with a powered gate operator.
1.6 A gate latch shall not be installed on an automatically operated gate.
1.7 Protrusions shall not be permitted on any gate, refer to ASTM F2200 for
Exceptions.
1.8 Gates shall be designed, constructed and installed such that their movement
shall not be initiated by gravity when an automatic operator is disconnected.
1.9 A pedestrian gate shall not be incorporated into a vehicular gate panel or
that portion of the adjacent fence that the gate covers in the open position.
2. SPECIFIC APPLICATIONS
2.1 Any non-automated gate that is to be automated shall be upgraded to
conform to the provisions of this specification.
2.2 This specification shall not apply to gates generally used for pedestrian
access and to vehicular gates not to be automated.
2.3 Any existing automated gate, when the operator requires replacement, shall
be upgraded to conform to the provisions of this specification in effect at
that time.
3. VEHICULAR HORIZONTAL SLIDE GATES
3.1 The following provisions shall apply to Class I, Class II and Class III vehicular
horizontal slide gates:
3.1.1 All weight bearing exposed rollers 8 feet (2.44 m), or less, above grade
shall be guarded or covered.
3.1.2 All openings located between 48 inches (1.22 m) and 72 inches (1.83 m)
above grade shall be designed, guarded or screened to prevent a 4 inch
(102 mm) diameter sphere from passing through the openings anywhere in
the gate, and in that portion of the adjacent fence that covers in the open
position.
3.1.3 A gap, measured in the horizontal plane parallel to the roadway, between a
fixed stationary object nearest the roadway, (such as a gate support post)
and the gate frame when the gate is in either the fully open position or the
fully closed position, shall not exceed 2 1/4 inches (57 mm), refer to ASTM
F2200 for Exception.
3.1.4 Positive stops shall be required to limit travel to the designed fully open and
fully closed positions. These stops shall be installed at either the top of the
gate, or at the bottom of the gate where such stops shall horizontally or
vertically project no more than is required to perform their intended
function.
3.1.5 All gates shall be designed with sufficient lateral stability to assure that the
gate will enter a receiver guide, refer to ASTM F2200 for panel types.
3.2 The following provisions shall apply to Class IV vehicular horizontal slide
gates:
3.2.1 All weight bearing exposed rollers 8 feet (2.44 m), or less, above grade
shall be guarded or covered.
3.2.2 Positive stops shall be required to limit travel to the designed fully open and
fully closed positions. These stops shall be installed at either the top of the
gate, or at the bottom of the gate where such stops shall horizontally or
vertically project no more than is required to perform their intended
function.
4. VEHICULAR HORIZONTAL SWING GATES
4.1 The following provisions shall apply to Class 1, Class II and Class III vehicular
horizontal swing gates:
4.1.1 Gates shall be designed, constructed and installed so as not to create an
entrapment area between the gate and the supporting structure or other
fixed object when the gate moves toward the fully open position, subject to
the provisions in the 4.1.1.1 and 4.1.1.2.
4.1.1.1 The width of an object (such as a wall, pillar or column) covered by a swing
gate when in the open position shall not exceed 4 inches (102 mm),
measured from the centerline of the pivot point of the gate, refer to ASTM
F2200 for exception.
4.1.1.2 Except for the zone specified in Section 4.1.1.1, the distance between a
fixed object such as a wall, pillar or column, and a swing gate when in the
open position shall not be less than 16 inches (406 mm), refer to ASTM
F2200 for exception.
4.2 Class IV vehicular horizontal swing gates shall be designed, constructed and
installed in accordance with security related parameters specific to the
application in question.
4
Page 7
SAFETY
REQUIRED ENTRAPMENT PROTECTION DEVICES
REQUIRED ENTRAPMENT PROTECTION DEVICES
To prevent SERIOUS INJURY or DEATH from a moving gate:
• Entrapment protection devices MUST be installed to protect anyone who may
come near a moving gate.
• Locate entrapment protection devices to protect in BOTH the open and close
gate cycles.
An entrapment zone is every location or point of contact where a person can become entrapped between a moving gate and a stationary object. All gate operator systems
REQUIRE two independent entrapment protection systems for each entrapment zone. This operator contains an inherent (internal) entrapment protection system (the primary
entrapment protection system) and REQUIRES the addition of an external entrapment protection system (non-contact photoelectric sensor or contact safety edge sensor) for
EACH entrapment zone.
Your application may contain one or many entrapment zones. Property owners are obligated to test entrapment protection devices monthly.
CONTACT SENSORS (EDGE SENSORS)
If the electrically activated edge sensor comes in contact with an obstruction while the gate is moving, the gate will stop and reverse. The gate will not be able to travel in that
direction until the obstruction is cleared. Use edge sensor models G65MG0204, G65MGR020, or G65MGS020.
3 Edge Contact Sensor
• Locate entrapment protection devices to protect between moving gate and
RIGID objects, such as posts or walls.
Edge Sensor for Open CycleEdge Sensor for Close Cycle
!
NON-CONTACT SENSORS
If the photoelectric sensor beam gets blocked while the gate is moving, the gate will stop and reverse. The gate will not be able to travel in that direction until the obstruction
is cleared. It is best to use monitored photoelectric sensors, model CPS-UN4. If a monitored photoelectric sensor is not working or loses power or the beam is blocked, then ALL
gate operation in that direction will stop. Unmonitored photoelectric sensor models AOMRON and RETROAB are also acceptable.
Safety Non-Contact Sensor
Sensor for Close Cycle
Sensor for Open Cycle
!
!
5
Page 8
SAFETY
IMPORTANT SAFETY INFORMATION
INSTALLATION
IMPORTANT SAFETY INFORMATION
To prevent SERIOUS INJURY or DEATH from a moving gate:
• Pinch points must be guarded at all times. Install enclosed-style gate tracks and
roller guards.
• Place screen mesh 4 feet (1.2 m) high on the gate to prevent access through
openings anywhere the gate may travel.
• Mount controls at least 6 feet (1.8 m) from the gate or ANY moving part of the
gate.
• Install Warning signs on EACH side of gate in PLAIN VIEW. Permanently secure
each Warning sign in a suitable manner using fastening holes.
• This operator is intended for vehicular use only. To prevent INJURY to
pedestrians, a separate pedestrian access should be supplied, visible from the
gate. Locate the pedestrian access where there is not a chance of INJURY at
any point during full movement of the gate.
• Contact sensors MUST be located at the leading and trailing edges, and post
mounted both inside and outside a horizontal swing gate. Non-contact sensors
such as photo eyes MUST be mounted across the gate opening and operate
during BOTH the open and close cycles.
• To AVOID damaging gas, power or other underground utility lines, contact
underground utility locating companies BEFORE digging more than 18 inches
(46 cm) deep.
• Entrapment protection devices MUST be installed to protect anyone who may
come near a moving gate.
• Locate entrapment protection devices to protect in BOTH the open and close
gate cycles.
• Locate entrapment protection devices to protect between moving gate and
RIGID objects, such as posts or walls.
• Too much force on gate will interfere with proper operation of safety reversal
system.
• NEVER increase force beyond minimum amount required to move gate.
• NEVER use force adjustments to compensate for a binding or sticking gate.
• If one control (force or travel limits) is adjusted, the other control may also
need adjustment.
• After ANY adjustments are made, the safety reversal system MUST be tested.
Gate MUST reverse on contact with a rigid object.
• DO NOT touch the heater when switch is on, heater may be hot.
• ALWAYS wear protective gloves and eye protection when changing the battery
or working around the battery compartment.
WIRING
To reduce the risk of SEVERE INJURY or DEATH:
• ANY maintenance to the operator or in the area near the operator MUST NOT
be performed until disconnecting the electrical power (AC or solar and battery)
and locking-out the power via the operator power switch. Upon completion of
maintenance the area MUST be cleared and secured, at that time the unit may
be returned to service.
• Disconnect power at the fuse box BEFORE proceeding. Operator MUST be
properly grounded and connected in accordance with national and local
electrical codes. NOTE: The operator should be on a separate fused line of
adequate capacity.
ADJUSTMENT
To reduce the risk of SEVERE INJURY or DEATH:
• Without a properly installed safety reversal system, persons (particularly small
children) could be SERIOUSLY INJURED or KILLED by a moving gate.
• Too much force on gate will interfere with proper operation of safety reversal
system.
• NEVER increase force beyond minimum amount required to move gate.
• NEVER use force adjustments to compensate for a binding or sticking gate.
• ALL electrical connections MUST be made by a qualified individual.
• DO NOT install ANY wiring or attempt to run the operator without consulting
the wiring diagram. We recommend that you install an edge sensor BEFORE
proceeding with the control station installation.
• ALL power wiring should be on a dedicated circuit and well protected. The
location of the power disconnect should be visible and clearly labeled.
• ALL power and control wiring MUST be run in separate conduit.
• If one control (force or travel limits) is adjusted, the other control may also
need adjustment.
• After ANY adjustments are made, the safety reversal system MUST be tested.
Gate MUST reverse on contact with a rigid object.
• Keep clear of moving arm while setting limits.
6
Page 9
SAFETY
IMPORTANT SAFETY INFORMATION
ADDITIONAL FEATURES
To prevent SERIOUS INJURY or DEATH from a moving gate:
• Entrapment protection devices MUST be installed to protect anyone who may
come near a moving gate.
• Locate entrapment protection devices to protect in BOTH the open and close
gate cycles.
MAINTENANCE AND OPERATION
To reduce the risk of SEVERE INJURY or DEATH:
• READ AND FOLLOW ALL INSTRUCTIONS.
• ANY maintenance to the operator or in the area near the operator MUST NOT
be performed until disconnecting the electrical power (AC or solar and battery)
and locking-out the power via the operator power switch. Upon completion of
maintenance the area MUST be cleared and secured, at that time the unit may
be returned to service.
• Disconnect power at the fuse box BEFORE proceeding. Operator MUST be
properly grounded and connected in accordance with national and local
electrical codes. NOTE: The operator should be on a separate fused line of
adequate capacity.
• NEVER let children operate or play with gate controls. Keep the remote control
away from children.
• ALWAYS keep people and objects away from the gate. NO ONE SHOULD CROSS
THE PATH OF THE MOVING GATE.
IMPORTANT SAFETY INFORMATION
• Locate entrapment protection devices to protect between moving gate and
RIGID objects, such as posts or walls.
• Test the gate operator monthly. The gate MUST reverse on contact with a rigid
object or reverse when an object activates the non-contact sensors. After
adjusting the force or the limit of travel, retest the gate operator. Failure to
adjust and retest the gate operator properly can increase the risk of INJURY or
DEATH.
• Use the manual disconnect release ONLY when the gate is not moving.
• KEEP GATES PROPERLY MAINTAINED. Read the owner’s manual. Have a
qualified service person make repairs to gate hardware.
• ALL maintenance MUST be performed by a LiftMaster professional.
• Activate gate ONLY when it can be seen clearly, is properly adjusted and there
are no obstructions to gate travel.
• To reduce the risk of FIRE or INJURY to persons use ONLY LiftMaster part
29-NP712 for replacement batteries.
• SAVE THESE INSTRUCTIONS.
• ALWAYS wear protective gloves and eye protection when changing the battery
or working around the battery compartment.
TROUBLESHOOTING
To protect against fire and electrocution:
• DISCONNECT power (AC or solar and battery) BEFORE installing or servicing
operator.
For continued protection against fire:
• Replace ONLY with fuse of same type and rating.
7
Page 10
INTRODUCTION
OPERATOR SPECIFICATIONS
This model is intended for use in vehicular swing gate applications:
Check the national and local building codes BEFORE installation.
GATECONDUIT & CONCRETE PAD
Gate must be constructed and installed according to ASTM F2200 standards (refer
to page 4). Gate must fit specifications of operator (refer to specifications).
Conduit must be UL approved for low and high voltage. Consider the operator
placement BEFORE installing the pad or post.
Concrete Pads
10
Page 13
SITE PREPARATION
SAFETY
Entrapment protection devices are required to protect against any entrapment or
safety conditions encountered in your gate application (refer to page 5 for more
details). Install warning signs on both sides of the gate.
!
!
Warning Signs
Entrapment Danger
VEHICLE LOOPS
The vehicle loops allow the gate to stay open when vehicles are obstructing the
gate path. Suggested for vehicles 14 feet (4.27 m) or longer. Vehicle loops are
not required but are recommended.
SAFETY
STANDARD INSTALLATION
(Inside Property)
The illustration is an example of a standard installation.
COMPACT INSTALLATION
EARTH GROUND ROD
Proper grounding gives an electrical
charge, such as from an electrical
static discharge or a near lightning
strike, a path from which to
dissipate its energy safely into the
earth. Without this path, the intense
energy generated by lightning could
be directed towards the gate
operator. Although nothing can
absorb the tremendous power of a
direct lightning strike, proper
grounding can protect the gate
operator in most cases.
(Inside Property)
Check national
and local codes
for proper depth
(Inside Property)
The illustration is an example of a compact installation. If the operator arm
will hit an obstruction when the gate is in the open position follow the
directions for Compact Installation.
UPHILL DRIVEWAY INSTALLATION
(Side View)
(Outside Property)
The illustration is an example of an uphill driveway installation. If installing
the operator on a hill, a special swivel arm and hinges are required (not
provided).
11
Page 14
INSTALLATION
STANDARD INSTALLATION ONLY
STANDARD INSTALLATION ONLY
For compact installation start on page 14.
DETERMINE LOCATION FOR CONCRETE PAD AND
OPERATOR
DO NOT run the operator until instructed.
Below is a recommended guide for positioning the concrete pad:
Measure 1/4 the length of the gate from the gate hinge center. This is A.
1
Subtract 14 inches from A to get B, the distance from the center of the output
2
shaft to the center of the gate hinge.
Open the gate 90°. The distance from the gate to the center of the output
3
shaft must be a minimum of 9 inches.
1/41/41/4
6.5”
CONDUIT LOCATIONMOUNTING FOOTPRINT
5.5”
1”
4.5”
4”
1.5”
(Conduit)
10”
15”
24”
1
A
3”
28”
20”
(Pad)
(cover mounting distance)
TOP VIEW OF OPERATOR AND GATE
Gate Hinge
90°
minimum
of 9”
13.6”
12.2”
6.1”
2.49”
14”
14.82”
2
B
CONCRETE PAD AND OPERATOR ATTACHMENT
Check the national and local building codes before installation. NOTE: When lifting
the operator use the handle to avoid damaging the operator.
Install the electrical conduit.
1
Pour a concrete pad (reinforced concrete is recommended). The concrete pad
2
should be 6 inches above the ground and deeper than the frost line. Ensure
the pad is tall enough to avoid possible flooding.
Secure the operator to the concrete pad with appropriate fasteners.
3
NOTE: An alternative to a concrete pad is to post mount the operator (refer to
accessories).
Below the frost line.
2
Check all national
and local codes.
Post Mount
6” Above Ground
28”
1
3
Output Shaft28”
24”
3
4 Concrete Anchors
1/2” x 3 1/2”
24”
12
Page 15
INSTALLATION
STANDARD INSTALLATION ONLY
POSITION THE GATE BRACKET
NOTE: It may be necessary to attach horizontal reinforcement to the gate before
attaching the gate bracket.
Position the operator arm onto the output shaft so that the pin slides into the
1
slot.
Measure 1/4 the length of the gate from the hinge center.
2
Make sure the operator arm is level and tack weld the gate bracket in this
3
position. Use the set screws on the arm to temporarily hold the arm in place
while determining the correct measurements.
1/4 of gate length
2
STANDARD INSTALLATION ONLY
Gate Hinge
Center
1
Slot
3
Tack weld
ADJUST THE OPERATOR ARM LENGTH
NOTE: The length of the arm can be adjusted if necessary. If adjusting the length,
ensure that both sections of the arm are adjusted proportionally. Use the set screws
on the arm to temporarily hold the arm in place while determining the correct
measurements.
Close the gate and measure the distance of the operator arm from the gate
1
bracket to the output shaft center. This distance is E.
Open the gate 90° (do not allow arms to scissor when open). Measure both
2
sections of the arm (D and C). The arm lengths are correct as long as C+D=E
(arm should be perpendicular to the gate in the open position as shown).
Set Screws
1
TOP VIEW - OPEN GATE
Gate Open
90°
TOP VIEW - CLOSED GATE
Output Shaft
2
Output Shaft
Pin
Set Screws
E
Output Shaft
Proceed to PAGE 16.
C
Set Screws
D
13
Page 16
INSTALLATION
COMPACT INSTALLATION ONLY
COMPACT INSTALLATION ONLY
DETERMINE LOCATION FOR CONCRETE PAD AND
OPERATOR
DO NOT run the operator until instructed.
Refer to the illustration to determine the measurements and location of the
concrete pad.
NOTE: When lifting the operator use the handle to avoid damaging the operator.
CONCRETE PAD AND OPERATOR ATTACHMENT
Check the national and local building codes before installation.
Gate Hinge Center
Gate Open 90°
Handle
TOP VIEW OF OPERATOR AND GATE
26-1/2”
9”
24”
Post Mount
Output Shaft Center
28”
Install the electrical conduit.
1
Pour a concrete pad (reinforced concrete is recommended). The concrete
2
pad should be 6 inches above the ground and deeper than the frost line.
Ensure the pad is tall enough to avoid possible flooding.
Secure the operator to the concrete pad with appropriate fasteners.
3
NOTE: An alternative to a concrete pad is to post mount the operator (refer to
accessories).
CONDUIT LOCATIONMOUNTING FOOTPRINT
5.5”
1”
6.5”
1.5”
4.5”
4”
(Conduit)
10”
3”
28”
20”
13.6”
12.2”
6.1”
2.49”
14”
3
4 Concrete Anchors
1/2” x 3 1/2”
1
28”
24”
2
6” Above Ground
Below the frost line.
Check all national
and local codes.
15”
24”
(Pad)
14.82”
(cover mounting distance)
14
Page 17
INSTALLATION
COMPACT INSTALLATION ONLY
SHORTEN THE OPERATOR ARM
For a compact installation the operator arm will have to be shortened.
COMPACT INSTALLATION ONLY
Take the operator arm apart and remove the inner sleeves from the outer
1
tubing.
Cut the outer tubing of the operator arm sections to the lengths shown.
2
Put the arm back together and adjust the arm to the measurements as
3
shown. Use the set screws on the arm to temporarily hold the arm in place
while determining the correct measurements.
POSITION THE GATE BRACKET
NOTE: It may be necessary to attach horizontal reinforcement to the gate before
attaching the gate bracket. Use the set screws on the arm to temporarily hold the
arm in place while determining the correct measurements.
2
3
1
CUTCUT
10”22”4”
CUT
23”
long arm section
short arm section
20”4”
Set Screws
25-1/2”
Position the operator arm onto the output shaft so that the pin slides into
1
the slot.
Measure 33 inches from the gate hinge center.
2
Make sure the operator arm is level and tack weld the gate bracket in this
3
position.
2
3
Tack weld
Set Screws
33”
Gate Hinge
Center
1
Slot
Output Shaft
Pin
15
Page 18
INSTALLATION
INSTALLATION CONTINUED...
WELD THE OPERATOR ARM
Once the operator arm measurements are verified:
Weld the gate bracket to the gate.
1
Weld the short arm section.
2
Weld the long arm section.
3
Remove the set screws from the arm.
4
NOTE: Completely weld around the outer tubing and bracket.
INSTALLATION CONTINUED...
1
3
2
SECURE THE OPERATOR ARM TO THE OUTPUT SHAFT
Adjust the nuts on the operator arm so the operator arm fits snug on the
1
output shaft yet still allows enough room to swivel (the handle must be in a
90° position).
Tighten the handle by pushing it down. Test to make sure the operator arm
2
does not slip on the output shaft.
REMOVE THE PINS FROM THE VENT PLUGS
Remove the pin from the vent plug on both the top and bottom gear boxes.
1
Top Gear Box
Bottom Gear Box
1
2
Pin
Vent Plug
16
Page 19
WIRING
ALARM
RESET
WIRE THE ENTRAPMENT PROTECTION DEVICES + EARTH GROUND ROD
WIRE THE ENTRAPMENT PROTECTION DEVICES
Entrapment protection devices are required. Refer to page 5 for more information regarding application.
To prevent SERIOUS INJURY or DEATH from a moving gate:
• Entrapment protection devices MUST be installed to protect anyone who may
come near a moving gate.
• Locate entrapment protection devices to protect in BOTH the open and close
gate cycles.
Connect the entrapment protection device to the EYES EDGE terminal on the
1
control board:
• Close Photoelectric Sensor Entrapment Protection: Connect wires from the
photoelectric sensors to the Inputs on the CLOSE EYES/INTERRUPT terminal.
• Close Edge Entrapment Protection: Connect wires from the entrapment
protection device to the Inputs on the CLOSE EDGE terminal.
• Open Entrapment Protection: Connect wires from the entrapment protection
device to the Inputs on the OPEN EYES/EDGE terminal.
NOTE: Refer to the “Accessory Features on the Control Board” section on page 31.
• Locate entrapment protection devices to protect between moving gate and
RIGID objects, such as posts or walls.
1
TO ERASE LEARNED MONITORED PHOTOELECTRIC
SENSORS
Remove the photoelectric sensor wires from the terminal block.
1
Press the SET OPEN and SET CLOSE buttons simultaneously until the SET OPEN
2
and SET CLOSE LEDs turn on.
Press both SET OPEN and SET CLOSE buttons again to turn off the SET OPEN
3
and SET CLOSE LEDs.
NOTE: For dual gate applications repeat the steps above on the other operator.
EARTH GROUND ROD
Use the proper earth ground rod for your local area. The ground wiremust be a
single, whole piece of wire. Never splice two wires for the ground wire. If you should
cut the ground wire too short, break it, or destroy its integrity, replace it with a single
wire length.
Install the earth ground rod within 3 feet of the operator.
1
To Operator
Check national and local
codes for proper depth
Run wire from the earth ground rod to the operator.
2
NOTE: If the operator is not grounded properly the range of the remote controls will
be reduced.
17
Page 20
WIRING
POWER WIRING
POWER WIRING
This operator can be wired for either 120 Vac or 240 Vac or a solar
panel (not provided). Follow the directions according to your application.
For dual gate applications, power will have to be connected to each
operator. Main power supply and control wiring MUST be run in
separate conduits.
The AC Power switch on the operator will turn the incoming 120/240 Vac power ON
or OFF. The operator's AC Power switch ONLY turns off AC power to the control board
and DOES NOT turn off battery power.
If using the 240 Vac option a heater cannot be used. The accessory outlet is disabled
and cannot be used with the 240 Vac option.
Remove the outlet housing from the electrical box by removing the
1
screws (2).
Pull the outlet housing out and locate the power wiring connector on the
2
EMI board.
Unplug the power wiring connector from the 120 Vac socket (factory default
3
location) and plug it into the 240 Vac socket.
Replace the outlet housing by securing with the screws. The operator is now
4
set for 240 Vac operation.
AC Power Switch
Outlet Housing
240 Vac Socket
Power Wiring Connector
(120 Vac Socket, factory default)
EMI Board
18
Page 21
WIRING
POWER WIRING CONTINUED...
120 VAC AND 240 VAC
Turn off the AC power from the main power source circuit breaker.
1
Run the AC power wires to the operator.
2
Remove the junction box cover.
3
Connect the green wire to the earth ground rod and AC ground using a wire
4
nut. NOTE: The earth ground rod can be grounded to the chassis.
POWER WIRING
Connect the white wire to NEUTRAL using a wire nut.
5
Connect the black wire to HOT using a wire nut.
6
Replace the junction box cover. Ensure the wires are not pinched.
7
SOLAR PANEL(S)
NOT PROVIDED. SEE ACCESSORIES.
For solar applications DO NOT use the expansion board and the wireless dual gate feature. These features will substantially decrease the cycle rate
and standby time of the operator. The solar panel(s) must be located in an open area clear of obstructions and shading for the entire day. The gate operator is not
supported in northern climates where temperatures reach below -4˚F. This is due to cold weather and a reduced number of hours of sunlight during the winter months. Cycle
rate may vary from solar chart for areas that reach below 32˚F. Solar panels should be cleaned on a regular basis for best performance to ensure proper operation. For solar
applications, a minimum of two 10W solar panels in series and two 7AH batteries are recommended. For Zone 3 cold weather sites, two 33AH batteries are recommended. We
recommend LiftMaster low power draw accessories to minimize power draw, refer to accessory page.
Remove the outlet housing from the chassis by removing the screws (2).
1
Remove the electrical box from the chassis by removing the 4 corner screws.
2
Locate the red and black wires connected to the J15 plug labeled DC POWER
3
on the control board. Unplug the wires from the bridge rectifier located on
the back of the electrical box.
Junction Box Cover
NUMBER OF CYCLES PER DAY (SOLAR)
Swing Gate
Installation (12 ft.
800 lb. gate)
CONFIGURATIONZONE 1
(6 Hrs
sunlight/day)
ZONE 2
(4 Hrs
Sunlight/day)
ZONE 3
(2 Hrs
Sunlight/day)
Connect the red (+) wire from the J15 plug to the red wire from the
4
solar panel.
Connect the black (-) wire from the J15 plug to the black wire from the
5
solar panel.
Reassemble the operator.
6
Black Wire
Red Wire
Bridge Rectifier
(back of Electrical Box)
Outlet Housing
J15 Plug
20W SOLAR PANEL
NOTE: 20W would be two 10W
(12V) panels in series.
There are two options for dual gate communication: wired or wireless. Follow the directions according to your application. Do not use
wired and wireless communication simultaneously. Wired dual gate applications will have a longer battery standby time than wireless applications.
WIRED DUAL GATES
Before digging, contact local underground utility locating companies. Use PVC conduit to prevent damage to cables.
Trench across driveway to bury the extension cable.
1
Connect the wires from the extension cable to the Comm Link terminals
2
on the primary gate operator control board.
Route the extension cable to the secondary gate operator's control
3
board.
Connect the wires from the extension cable to the Comm Link terminals
4
on the secondary control board (Comm Link A to Comm Link A and
Comm Link B to Comm Link B).
DUAL GATE WIRE TYPE (STRANDED COPPER WIRE)
22AWG up to 200 feet (61 m)18AWG - 200-1000 feet
(61-305 m)
Wire must be rated at 30 Volt minimum
DUAL GATES ONLY
Comm Link Data A
Comm Link Data B
2
Property
Inside
1
Outside
!
Property
!
Comm Link Data A
Comm Link Data B
4
3
20
Page 23
WIRING
WIRELESS DUAL GATES
Turn on power to the operator.
TO ACTIVATE THE WIRELESS FEATURE:
Choose an operator to be the network primary operator. All wireless
1
accessories will need to be programmed to the primary operator.
Press and release the LEARN RADIO button on the primary operator. The
2
green XMITTER LED will light.
Press and release the LEARN RADIO button again on the primary
3
operator. The NETWORK LED will light.
Press and release the OPEN test button to assign this operator as
4
network primary.
DUAL GATES ONLY
DUAL GATES ONLY
Press and release the LEARN RADIO button on the second operator. The
5
green XMITTER LED will light.
Press and release the LEARN RADIO button again on the second
6
operator. The NETWORK LED will light.
Press and release the CLOSE test button to assign this operator as
7
network second.
Both operators will beep and the NETWORK LEDs will turn off indicating
programming is successful.
TO DEACTIVATE THE WIRELESS FEATURE:
Press and release the LEARN RADIO button on either operator. The
1
green XMITTER LED will light.
Press and release the LEARN RADIO button again on the same operator.
2
The yellow NETWORK LED will light.
Press and hold the LEARN RADIO button for 5 seconds. The yellow
3
NETWORK LED will blink (operator will beep) then turn off indicating
successful deactivation.
Repeat the steps for the other operator.
ALARM
RESET
21
Page 24
WIRING
BIPART DELAY/SYNCHRONIZED CLOSE
The LOCK/BIPART DELAY switch is used only with dual gate applications and
serves two functions:
• BIPART DELAY
SWING GATE APPLICATIONS: The BIPART DELAY is used in applications
where a mag-lock, solenoid lock, or decorative overlay would require one
gate to close before the other. The operator with the LOCK/BIPART DELAY
switch ON will delay from the close limit when opening and be the first to
close from the open limit.
SLIDE GATE APPLICATIONS: Not applicable, set to OFF.
• SYNCHRONIZED CLOSE
The BIPART DELAY is also used in applications where one gate travels a
longer distance than the other. To synchronize the closing of the gates, set
the LOCK/BIPART DELAY switch to ON for both operators.
DUAL GATES ONLY
DUAL GATES ONLY + CONNECT BATTERIES
ALARM
RESET
CONNECT BATTERIES
7AH BATTERIES
The batteries are charged in the circuit by the integrated transformer. The batteries
are for battery backup or solar installation.
Turn OFF AC power to the operator.
1
Unplug the J15 plug labeled BATT on the control board by squeezing the plug
2
and pulling it from the control board.
Connect a jumper between the positive (+) terminal of one battery to the
3
negative terminal (-) of the other battery.
Connect the red wire from the J15 plug to the positive (+) terminal of the
4
battery.
Connect the black wire from the J15 plug to the negative (-) terminal of the
5
battery.
Plug the J15 plug back into the control board. This will power up the control
6
board.
J15 Plug
Red Wire
Jumper Black Wire
Turn ON AC power to the operator.
7
Turn ON the AC power switch on the operator.
8
22
Page 25
WIRING
CONNECT BATTERIES
33AH BATTERIES
The batteries are charged in the circuit by the integrated transformer. The batteries
are for battery backup or solar installation. The 33AH application requires the 33AH
battery harness (Model K94-36596) and an additional battery tray (Model K10-
36183) to allow more space in the enclosure. The heater option cannot be used with
the 33AH battery application.
Remove the outlet housing from the chassis by removing the screws (2).
1
Remove the electrical box from the chassis by removing the 4 corner
2
screws.
Disconnect the red (+) and black (-) wires going from the bridge rectifier to
3
the J15 plug labeled DC POWER on the control board.
Connect the red (+) and black (-) wires from the new 33AH harness to the
4
bridge rectifier.
Reassemble the operator.
5
Connect a jumper between the positive (+) terminal of one battery to the
6
negative (-) terminal of the other battery.
(back of Electrical Box)
+
-
Bridge Rectifier
CONNECT BATTERIES
Outlet Housing
J15 Plug
-
Connect the red wire from the J15 plug to the positive (+) terminal of the
7
battery.
Connect the black wire from the J15 plug to the negative (-) terminal of the
8
battery.
Turn ON AC power to the operator.
9
Turn ON the AC power switch on the operator.
10
Plug the J15 plug back into the control board.
11
Black (-)
Red (+)
Red (+)
33AH Batteries
Black (-)
23
Page 26
OPEN limit
CLOSE limit
!
SET OPEN
SET CLOSE
OFF
PRESS &
RELEASE
TO BEGIN
MOVE
GATE
5
INPUT POWER
PRESS &
RELEASE
TO BEGIN
SETUP
LIMIT
TO BEGIN
PRESS &RELEASETO BEGIN
ADJUSTMENT
LIMIT AND FORCE ADJUSTMENT
To reduce the risk of SEVERE INJURY or DEATH:
• Without a properly installed safety reversal system, persons (particularly small
children) could be SERIOUSLY INJURED or KILLED by a moving gate.
• Too much force on gate will interfere with proper operation of safety reversal
system.
• NEVER increase force beyond minimum amount required to move gate.
• NEVER use force adjustments to compensate for a binding or sticking gate.
LIMIT AND FORCE ADJUSTMENT
• If one control (force or travel limits) is adjusted, the other control may also
need adjustment.
• After ANY adjustments are made, the safety reversal system MUST be tested.
Gate MUST reverse on contact with a rigid object.
• Keep clear of moving arm while setting limits.
INTRODUCTION
Your operator is designed with electronic controls to make travel limit and force
adjustments easy. The adjustments allow you to program where the gate will stop in
the open and close position. The electronic controls sense the amount of force
required to open and close the gate. The force is adjusted automatically when you
program the limits but should be fine tuned using the REVERSAL FORCE dial on the
control board (refer to Fine Tune the Force section) to compensate for environmental
changes.
The limits can be set using the control board (below) or a remote control (refer to
Limit Setup with a Remote Control in the Additional Features section). Setting the
limits with a remote control requires a 3-button remote control programmed to
OPEN, CLOSE, and STOP.
INITIAL LIMITS AND FORCE ADJUSTMENT
For dual gate applications the limits will have to be set for each
operator. The gate MUST be attached to the operator before setting the
limits and force.
Press and release the SET OPEN and SET CLOSE buttons simultaneously to
1
enter limit setting mode.
Press and hold one of the MOVE GATE buttons to move the gate to the open or
2
close limit.
LIMIT SETUP LEDS
SET OPEN
LED
BLINKINGBLINKINGNORMAL MODELimits are not set.
OFFOFFNORMAL MODELimits are set.
BLINKINGBLINKINGLIMIT SETTING MODELimits are not set.
BLINKINGONLIMIT SETTING MODEOpen limit is not set.
ONBLINKINGLIMIT SETTING MODEClose limit is not set.
ONONLIMIT SETTING MODELimits are set.
SET CLOSE
LED
OPERATOR MODEEXPLANATION
2
1
3
Press and release the SET CLOSE or SET OPEN button depending on which
3
limit is being set.
Press and hold one of the MOVE GATE button to move the gate to the other
4
limit.
Press and release the SET CLOSE or SET OPEN button depending on which
5
limit is being set.
Cycle the gate open and close. This automatically sets the force.
6
When limits are set properly the operator will automatically exit limit setting mode.
24
6
ALARM
RESET
4
5
Page 27
ALARM
RESET
60
180
MIN
MAX
BATT LOW
NETWORK
OPEN
CLOSE
STOP
XMITTER
NETWORK
!
OPEN limit
CLOSE limit
!
ADJUSTMENT
SETOPEN
SET CLOSE
OFF
BIPART
DELAY
PRESS &RELEASETO BEGIN
FINE TUNE THE FORCE
The FORCE DIAL on the control board is used for fine tuning the force in cases where
wind or environmental changes may affect the gate travel.
Based on the length and weight of the gate it may be necessary to make additional
force adjustments. The force setting should be high enough that the gate will not
reverse by itself nor cause nuisance interruptions, but low enough to prevent serious
injury to a person. The force setting is the same for both the open and close gate
directions.
Open and close the gate with the TEST BUTTONS.
1
If the gate stops or reverses before reaching the fully open or closed position,
2
increase the force by turning the force control slightly clockwise.
Perform the “Obstruction Test” after every force setting adjustment
3
(see below).
ADJUST THE LIMITS
If the limits have already been set the operator will exit the limit setting mode after
resetting each limit. Each limit is set separately by following steps 1-3 of the Initial
Limit and Force Adjustment section.
LIMIT AND FORCE ADJUSTMENT + OBSTRUCTION TEST
1
2
ERASE LIMITS
To erase the limits, press and hold the SET OPEN and SET CLOSE buttons
1
simultaneously (5 seconds) until both the SET OPEN and SET CLOSE LEDs blink
rapidly and the operator beeps.
Release the buttons and the SET OPEN and SET CLOSE LEDs will blink slowly
2
indicating the limits will need to be set.
OBSTRUCTION TEST
The operator is equipped with an automatic obstruction sensing feature. If the gate
encounters an obstruction during motion, the operator will automatically reverse
direction of the gate for a short time and then stop the gate. After any adjustments
are made, test the operator:
Open and close the gate with the TEST BUTTONS, ensuring that the gate is
1
stopping at the proper open and close limit positions.
Place a solid object between the open gate and a rigid structure. Ensure that
2
the gate, the solid object, and the rigid structure can withstand the forces
generated during this obstruction test.
Run the gate in the close direction. The gate should stop and reverse upon
3
contact with the solid object. If the gate does not reverse off the solid object,
reduce the force setting by turning the force control slightly counter-clockwise.
The gate should have enough force to reach both the open and close limits,
but MUST reverse after contact with a solid object.
Repeat the test for the open direction.
4
25
1
ALARM
RESET
2
ALARM
RESET
3
Page 28
PROGRAMMING
REMOTE CONTROLS + ERASE ALL CODES
REMOTE CONTROLS
A total of 50 Security✚ 2.0™ remote controls and 2 keyless entries (1 PIN for each keyless entry) can be programmed to the operator. NOTE: When the memory is full the
operator will exit programming mode and the remote control/keyless entry will not be programmed. The memory will need to be erased before programming any additional
remote controls/keyless entries. If installing an 86LM to extend the range of the remote controls DO NOT bend the antenna.
TO ADD OR REPROGRAM A REMOTE CONTROL
(NOT PROVIDED)
Press and release the LEARN RADIO button (operator will beep and green
1
XMITTER LED will light).
Press the remote control button for the desired function. The operator will
2
automatically exit learn mode (operator will beep and green XMITTER LED
will go out) if programming is successful.
This programming step will program a single button as an open, close, and stop. To
program additional Security✚ 2.0™ remote controls, repeat the steps until all the
remote controls are programmed.
PROGRAM OPEN ONLY ON A 1-BUTTON REMOTE
CONTROL
Press and release the LEARN RADIO button (operator will beep and green
1
XMITTER LED will light).
Press the OPEN button.
2
Press the remote control button. The operator will automatically exit learn
3
mode (operator will beep and green XMITTER LED will go out) if programming
is successful.
To program additional Security✚ 2.0™ remote controls, repeat the steps until all the
remote controls are programmed.
1
1
2
ALARM
RESET
2
ALARM
RESET
3
PROGRAM OPEN, STOP, AND CLOSE ON A 3-BUTTON
REMOTE CONTROL
Press and release the LEARN RADIO button (operator will beep and green
1
XMITTER LED will light).
Press the OPEN, CLOSE, or STOP button for the desired function.
2
Press the remote control button for the desired function. The operator will
3
automatically exit learn mode (operator will beep and green XMITTER LED
will go out) if programming is successful.
To program additional buttons or Security✚ 2.0™ remote controls, repeat the steps
until all the buttons or remote controls are programmed.
ERASE ALL CODES
Press and release the LEARN RADIO button (operator will beep and green
1
XMITTER LED will light).
Press and hold the LEARN RADIO button again until the green XMITTER LED
2
goes out (approximately 6 seconds). All remote control codes are now erased.
NOTICE: To comply with FCC and/or Industry Canada (IC) rules, adjustment or modifications of this transceiver are prohibited. THERE ARE
NO USER SERVICEABLE PARTS.
This device complies with Part 15 of the FCC rules and IC RSS-210. Operation is subject to the following two conditions: (1) this device may
not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired
operation.
1
ALARM
RESET
AVIS : Les règles de la FCC et/ou d’Industrie Canada (IC) interdisent tout ajustement ou toute modification de ce récepteur. IL N’EXISTE
AUCUNE PIÈCE SUSCEPTIBLE D’ÊTRE ENTRETENUE PAR L’UTILISATEUR.
Cet appareil est conforme aux dispositions de la partie 15 du règlement de la FCC et de la norme IC RSS-210. Son utilisation est assujettie
aux deux conditions suivantes : (1) ce dispositif ne peut causer des interférences nuisibles, et (2) ce dispositif doit accepter toute
interférence reçue, y compris une interférence pouvant causer un fonctionnement non souhaité.
26
2
3
Page 29
FINISH INSTALLATION
INSTALL THE COVER
INSTALL THE COVER
The operator cover consists of two pieces: a rear cover and a front cover. The front cover can easily be removed to access the electrical box. To access the reset switch slide the
access door up. The front cover and access door can be locked with the key.
TO INSTALL THE COVER
Remove the operator arm from the output shaft by releasing the handle.
1
Align the tabs on the rear cover with the slots on the chassis and place the
2
cover over the operator.
Secure both sides of the rear cover to the chassis with two 5/16-18 hex bolts
3
and washers.
Reattach the operator arm to the output shaft (making sure the pin fits into
4
the slot) and secure by pushing the handle down.
5/16-18
Hex Bolts
and Washers
5/16-18
Screw
Place the operator arm cover over the operator arm and secure.
5
Align the front cover with the back cover, making sure the grooves line up.
6
Secure the front cover to the chassis with two 5/16-18 hex bolts and washers.
7
Secure the front cover to the rear cover using the 5/16-18 screw.
8
TO LOCK THE ACCESS DOOR
From the factory the access door for the reset switch will not be locked. To lock the
access door follow the steps below:
Tabs on Rear Cover
Slots on Chassis
Groove on Front Cover
Access Door
Lock Tab
Locate the lock tab on the back of the front cover and remove the screw
1
securing the tab to the cover.
Turn the tab 180 degrees, then secure with the screw. The access door can
Press the reset switch to RESET/DISCONNECT. Release the handle on the operator arm
to allow the gate to be opened and closed manually. On a dual gate application the
handle must be released on both operators. To resume normal function tighten the
handle by pushing it down.
RESET SWITCH
The reset switch is located on the front of the operator and serves several functions.
Toggling the reset switch will stop a moving gate during a normal open/close cycle,
like a stop button. The operator does not need to be reset after doing this. The reset
switch will disable the gate in the present position and will energize the solenoid lock
for two minutes and disable the maglock for two minutes.
OPERATOR ALARM
If a contact sensor detects an obstruction twice consecutively the alarm will sound
(up to 5 minutes) and the operator will need to be reset. If a command is given
after the initial 5 minutes the operator will beep.
When the inherent force of the operator (RPM/current sensor) detects the
following (twice consecutively) the alarm will sound (up to 5 minutes) and the
operator will need to be reset:
A. The operator arm or gate is incorrectly installed.
B. The gate does not meet specifications.
C. Gate hinges are too tight or broken and the gate is not moving freely.
D. The gate is moving and a car pushes the gate.
E. A foreign object is on the gate frame while the gate is moving.
F. The gate hits the driveway or curb and gets stuck or bent in an awkward
position.
Remove any obstructions. Press the reset button to shut off the alarm and reset
the operator. After the operator is reset, normal functions will resume.
The operator alarm will beep 3 times with a command if the battery is low.
Manual Disconnect
Handle
A
C
NORMAL OPERATION
RESET/DISCONNECT
!
B
!
D
!
!
REMOTE CONTROL
Once the remote control has been programmed the operator will operate as follows:
When gate is in the closed position, activation of the remote control button will open
the gate. During the open cycle another activation of the remote control will stop the
gate and the next activation of the remote control will close the gate.
When the gate is in the open position, activation of the remote control button will
close the gate. If the remote control is activated while the gate is closing, the gate will
stop and the next activation will open the gate.
HEATER (IF APPLICABLE)
The operator may have a heater installed, depending on the model purchased. The
heater must be powered by 120 Vac ONLY. If the heater switch is left in the “ON”
position, the heater will turn on and off automatically when needed.
28
E
!
F
!
Heater (if applicable)
120 Vac ONLY
Page 31
ADDITIONAL FEATURES
GATE OPERATOR SETUP EXAMPLES
GATE OPERATOR SETUP EXAMPLES
The following are example setups for the gate operator. Your specific site requirements may be different. Always setup the operator system to the site requirements, including
all necessary secondary entrapment protection systems.
RESIDENTIAL SMALL
RESIDENTIAL LARGE: A residential community (more than four homes) having one or more gated entrances/exits, allowing vehicle access trumps security concerns
COMMERCIAL: Business site where security (gate closed) is important
INDUSTRIAL: Large business site where security is required
: One to four residential homes sharing a gated entrance/exit, allowing vehicle access trumps security concerns
Setting
Quick Close switch setting
AC Fail Open switch setting
Low Battery switch setting
Anti-Tail switch setting
Bipart Delay switch setting
Aux Relay Out – Open
Limit Switch
Aux Relay Out – Close
Limit Switch
Aux Relay Out – Gate
Motion
Aux Relay Out –
Pre-Motion Delay
(Expansion Board Inputs)
Attach alert signal (audible or
visual alert system)
Attach alert signal (audible or
visual alert system)
Attach visual alert to know when
system is charging batteries (i.e.
not running on batteries)
Attach alert signal (audible or
visual alert system) to indicate if
gate is manually tampered with by
being pushed off of close limit
Use during servicing only to
determine operator cycles
Suggested use if outside
temperature remain below
0°F (-20°C).
29
Page 32
ADDITIONAL FEATURES
CONTROL BOARD OVERVIEW
CONTROL BOARD OVERVIEW
SET OPEN ButtonThe SET OPEN button sets the OPEN limit. See Adjust Limits section.
SET CLOSE ButtonThe SET CLOSE button sets the CLOSE limit. See Adjust Limits section.
MOVE GATE ButtonThe MOVE GATE buttons will either open or close the gate when the operator is in Limit setting mode. See Adjust Limits section.
BIPART DELAY Switch
LEARN Button
TIMER-TO-CLOSE dial
REVERSAL FORCE dial
TEST BUTTONS
STATUS LEDs
The LOCK/BIPART DELAY switch is used only for dual gates. See Bipart Delay section.
The LEARN RADIO button is for programming remote controls and the network.
The TIMER-TO-CLOSE (TTC) dial can be set to automatically close the gate after a specified time period. The TTC is factory set to OFF. If the
TTC is set to the OFF position, then the gate will remain open until the operator receives another command from a control. Rotate the
TIMER-TO-CLOSE dial to the desired setting. The range is 0 to 180 seconds, 0 seconds is OFF.
NOTE: Any radio command, single button control, or CLOSE command on the control board prior to the TTC expiring will close the gate.
The TTC is reset by any signals from the open controls, loops, close edges, and close photoelectric sensors (IR’s).
The REVERSAL FORCE dial adjusts the force. See Force Adjustment section.
The TEST BUTTONS will operate the gate (OPEN, STOP and CLOSE).
The STATUS LEDs are diagnostic codes for the operator. See Status LED Chart in the Troubleshooting section.
Open
Close
Stop
Com
Fire Dept
Com
Exit
Com
Shadow
Com
Close Eyes
Interrupt
Close Edge (+)
Close Edge (-)
Open Eyes/Edge (+)
Open Eyes/Edge (-)
Comm Link Data A
Comm Link Data B
Lock N.C. (Maglock)
Com
Lock N.O. (Solenoid)
Com (-)
AccPower +24 Vdc
Com (-)
AccPower +24 Vdc
A
3 Button
B
Station
C
Fire Dept.
D
Exit Loop
E
Shadow Loop
F
Close Eyes/
Interrupt Loop
G
Close Edge
H
Open Eyes/Edge
I
Comm Link
J
Mag and
K
Solenoid Lock
L
Acc. Power
Switched ON with gate motion. Always ON with
M
expansion board connected. Switches Off to save
battery power if expansion board disconnected.
N
Always ON
30
RESET
ALARM
Page 33
ADDITIONAL FEATURES
ACCESSORY FEATURES ON CONTROL BOARD
ACCESSORY FEATURES ON CONTROL BOARD
A
B
C
D
E
F
G
H
I
J
K
L
M
N
Open Input (& common)
(3-Button Control Station, 4 terminals
total)
Close Input (& common)
(3-Button Control Station, 4 terminals
total)
Stop Input (& common)
(3-Button Control Station, 4 terminals
total)
Fire Dept Open Input
(2 terminals)
Exit Loop Input
(2 terminals)
Shadow Loop Input
(2 terminals)
CLOSE EYES/Interrupt Loop Input
(2 terminals)
Close Edge
(2 terminals)
Open Eyes/Edge
(2 terminals)
Comm Link
(2 terminals)
Lock Outputs: Maglock
(2 terminals, N.C. and COM)
Solenoid Lock & Common(2 terminals, N.O. and COM)
Accessory Power Out
Switched, (2 terminals)
Accessory Power Out
Un-switched, (2 terminals)
Open command - opens a closed gate.
Hard open (maintained switch overrides external safeties and resets alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Opens a closing gate and holds open an open gate (within line-of-sight).
Close command - closes an open gate.
Hard close (maintained switch overrides external safeties and resets alarm condition within line-of-sight)
Stop command - stops a moving gate.
Hard stop (maintained switch overrides Open and Close commands and resets alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Overrides Open and Close commands (within line-of-sight).
Acts as hard open.
Maintained input overrides (ignores) external safeties (photoelectric sensor and edge), pauses Timer-to-Close
momentary input logic as single button control and safeties remain active, re-enables Timer-to-Close.
Open command - opens a closed gate.
Soft open (maintained switch does not override external safeties and does not reset alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Opens a closing gate and holds open an open gate.
Loop detector connection when loop is positioned under gate.
- Holds open gate at open limit
- Disregarded at CLOSE limit and during gate motion
- Pauses Timer-to-Close at OPEN limit
CLOSE EYES/Interrupt Loop detector connection when loop is along the side of the gate.
- Holds open gate at open limit
- Stops and reverses a closing gate to open limit
- Pauses Timer-to-Close at OPEN limit
Close Direction Photoelectric Sensors, IR, or Infra-red detector wired to CLOSE EYES Input, disregarded during gate
opening.
Pulsed Photoelectric Sensors = monitored device putting out a pulse train when unblocked.
Photoelectric Sensors, IR, Infra-red detector, contact opens fully with obstruction.
Close Direction Edge Sensor to Close Safety Input, disregarded during gate opening
Open Direction Photoelectric Sensors, IR, Infra-red detector wired or Edge Sensor to Close Entrapments Input,
disregarded during gate closing,
Pulsed Photoelectric Sensors = monitored device putting out a pulse train when unblocked.
Photoelectric Sensors, IR, Infra-red detector, edge sensor = normally open contact, contact reverses for 2 seconds
with obstruction.
Commercial Link (two wires) - connects two operators together (primary-secondary wired connection)
Relay contact output, Normally - closed (N.C.) output for maglocks
Relay activates prior to motor activation and during motor run. Relay is off when motor is off.
Normally - open (N.O.) output for solenoid locks
Relay activates prior to motor activation and during motor run. Relay is off when motor is off.
24 Vdc voltage out to power accessories, will turn off when gate is not in motion to save battery power
Always on if Expansion Board is connected.
24 Vdc voltage out to power accessories, always ON
31
Page 34
ADDITIONAL FEATURES
EXPANSION BOARD OVERVIEW
EXPANSION BOARD OVERVIEW
To AVOID damaging the circuit board, relays or accessories, DO NOT connect more than 42 Vdc (32 Vac) to the AUX relay contact terminal blocks.
QUICK CLOSE Switch
OFF: No change to the gate's normal operation.
ON: When CLOSE EYES/Interrupt loop is deactivated it causes an opening or a stopped gate to close (ignores the Timer-to-Close).
AC FAIL OPEN/BATT Switch
OPEN: Loss of AC power will cause gate to immediately OPEN and remain OPEN until AC power is restored (enabling the Timer-to-Close).
BATT: With loss of AC power, gate will remain in present position and operator is powered from batteries.
LOW BATT/EXIT LOOP FAIL
Switch
• When AC power is OFF and battery voltage is low the gate will latch at a limit until AC power is restored or batteries voltage increases.
• Option select switch set to OPEN forces gate to latch at the OPEN limit if it is at the OPEN limit or on next open command until AC power is
restored or battery voltage increases.
• Option select switch set to CLOSE forces gate to latch at CLOSE limit if at CLOSE limit or on next CLOSE command until AC power restored or
battery voltage increases.
• Constant pressure on a hard command input overrides to open or close the gate.
• Low battery detect point = 22 V
• When set to OPEN, if the EXIT plug-in loop detector detects a fault, then the gate will open and remain open until fault is cleared. When set to
CLOSE, then plug-in EXIT loop detector faults are ignored (EXIT loop is faulted and inoperative).
ANTI-TAIL OPEN/CLOSE
SELECTION switch
AUX RELAY switches
AUX RELAY
SETTING
SWITCH
SETTINGS
OFF: When CLOSE EYES/Interrupt loop is activated it causes a closing gate to stop and reverse.
ON: When CLOSE EYES/Interrupt loop is activated it causes a closing gate to pause. Once the vehicle is clear the gate will continue to close.
Set the AUX RELAY switches as needed to obtain the desired function:
123
Off (no feature
OFF OFF OFF
Relay always off. Use this Aux Relay setting to conserve
selected)
Open Limit
OFF OFF ON
Energizes at open limit. Use with SAMS (Sequenced Access Management
Switch
Close Limit
OFF ON OFF
Energizes when not at close limit. Connect “Gate Close/Secure” indicator
Switch
Gate Motion
Pre-Motion
Delay
Power
OFF ON ON
ON OFF OFF
ON ON OFF
Energizes when motor is on (gate in motion). Connect “Gate In Motion”
Energizes 3 seconds before gate motion and remains energized during gate
motion. Connect “Gate In Motion” indicator (e.g. warning light or sounder).
Energizes when AC power or solar power is present. There is approximately
a 10-12 second delay before relay cutoff, after AC shutdown.
Tamper
Cycle Quantity
ON OFF ON
ON ON ON
Energizes if gate is manually tampered with by being pushed off of close
The OPEN, CLOSE, and STOP LEDs will blink out the cycle count
Feedback*
CYCLE COUNT
* First, note the current Aux Relay switch positions. To
determine the actual cycles that the gate operator has
run (in thousands), set all three Aux Relay switches to
the ON setting for Aux Relay 1. The Expansion Board’s
OPEN, CLOSE, and STOP LEDs will blink out the cycle
count, with OPEN LED blinking 1000’s, CLOSE LED blink
10,000’s, STOP LED blinking 100,000’s, and
simultaneously all three LED’s blink 1,000,000’s (e.g.
Open blinks 3 times, Close blinks 6 times, and Stop
blinks once. Cycle count is 163,000.). Cycle count
displayed is between 1,000 and 9,999,000 cycles.
After servicing, set Aux Relay switches back to their
appropriate positions. Cycle count cannot be reset or
changed. If under 1,000 cycles the Open, Close, and
Stop LEDs will turn on for 10 seconds, then turn off.
AUX RELAY 1AUX RELAY 2
battery power.
System, jointly with barrier gate)
(e.g. light).
indicator (e.g. warning light or sounder).
limit. Connect alert (e.g. light or sounder).
See below.
EXIT
INTERRUPT
SHADOW
Shadow Loop
Interrupt Loop
Exit Loop
F
G
32
Relay always off. Use this Aux Relay setting to conserve battery power.
Energizes when at open limit. Use with SAMS (Sequenced Access
Management System, jointly with barrier gate)
Energizes when not at close limit. Connect “Gate Not Closed/Secure”
indicator (e.g. light).
Energizes when motor is on (gate in motion). Connect “Gate In Motion”
indicator (e.g. warning light or sounder).
Not used.
Energizes when on battery power. There is approximately a 10-12
second delay before relay cutoff, after AC shutdown.
Energizes if gate is manually tampered with by being pushed off of close
limit. Connect alert (e.g. light or sounder).
Not used.
D
A
B
C
Single
Button
Control
Station
3-Button
Control
Station
1
SBC
Com
Open
Close
Stop
Com
AUX Relay 1 N.O.
E
H
AUX Relay 1 N.C.
Com
AUX Relay 2 N.O.
AUX Relay 2 N.C.
Com
I
Page 35
ADDITIONAL FEATURES
ACCESSORY FEATURES ON EXPANSION BOARD
ACCESSORY FEATURES ON EXPANSION BOARD
A
B
C
D
E
F
G
H
I
Open Input (& common)
(3-Button Control Station,
4 terminals total)
Close Input (& common)
(3-Button Control Station,
4 terminals total)
Open command - opens a closed gate.
Soft close (maintained switch does not override external safeties and does not reset alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Opens a closing gate and holds open an open gate.
Close command - closes an open gate.
Soft close (maintained switch does not override external safeties and does not reset alarm condition)
Stop command - stops a moving gate.
Hard stop (maintained switch overrides Open and Close commands and resets alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Overrides an Open or Close command.
Gate command sequence - Open, Stop, Close, Stop, ...
Soft open (maintained switch does not override external safeties and does not reset alarm condition)
Loop wire connection for plug-in loop detector when loop is inside secured area near gate.
Open command - opens a closed gate.
Soft open (maintained switch does not override external safeties and does not reset alarm condition)
If maintained, pauses Timer-to-Close at OPEN limit.
Opens a closing gate and holds open an open gate.
Loop wire connection for plug-in loop detector when loop is along side gate.
- Holds open gate at open
- Disregarded at Close limit and during gate motion
- Pauses Timer-to-Close at Open Limit
Loop wire connection for plug-in loop detector when loop is positioned under gate.
- Holds open gate at open
- Stops and reverses a closing gate
- Pauses Timer-to-Close at Open LimitNormally - open and normally - closed relay contacts to control external devices,
Function of relay contact activation determined by AUX Relay #1 option switch settings. (For connection of Class
2, low voltage (<32 V), DC or AC, max 5 Amps, power sources only)
Normally-open and normally-closed relay contacts to control external devices,
Function of relay contact activation determined by AUX Relay #2 option switch settings. (For connection of Class
2, low voltage (<32 V), DC or AC, max 5 Amps, power sources only)
AUX RELAY WIRING EXAMPLE
N.C.
Aux Relay
COM
N.O.
Class 2 Power Source
(32 V max, 5 A max)
+
—
Warning Light
SAMS WIRING WITH RELAYS NOT ENERGIZED
Main Board
Dipswitch settings for AUX Relay 1:
1-OFF, 2-OFF, 3-ON
33
Expansion Board
EXIT
INTERRUPT
SHADOW
ALARM
RESET
1
AUX Relay 1
Exit Input
Shadow Input
Barrier Arm Operator
C
Auxiliary
Command
NO
Access Device
Page 36
ADDITIONAL FEATURES
SET OPEN
SET CLOSE
OFF
BIPART
DELAY
PRESS &RELEASE
TO BEGIN
LIMIT SETUP WITH A REMOTE CONTROL
To set the limits using a remote control, first you will need a 3-button remote control
that has been programmed for OPEN, CLOSE, and STOP. Refer to the Programming
section.
INITIAL LIMITS AND FORCE ADJUSTMENT
For dual gate applications the limits will have to be set for each
operator. The gate MUST be attached to the operator before setting the
limits and force.
Ensure the gate is closed.
Press the SET OPEN and SET CLOSE buttons simultaneously to enter limit
1
setting mode.
Press and hold the OPEN or CLOSE button on the remote control until the gate
2
reaches the desired open position. The gate can be jogged back and forth
using the OPEN and CLOSE buttons on the remote control.
Once the gate is in the desired open position, press and release the STOP
3
button on the remote control.
Press and release the OPEN button on the remote control again to set the
4
open limit.
LIMIT SETUP WITH A REMOTE CONTROL
To reduce the risk of injury keep clear of moving arm while setting limits.
ALARM
RESET
3-Button Remote Control programmed for OPEN, CLOSE, and STOP
Press and hold the CLOSE or OPEN button on the remote control until the gate
5
reaches the desired close position. The gate can be jogged back and forth
using the OPEN and CLOSE buttons on the remote control.
Once the gate is in the desired close position, press and release the STOP
6
button on the remote control.
Press and release the CLOSE button on the remote control again to set the
7
close limit.
Cycle the gate open and close. This automatically sets the force.
8
When limits are set properly the operator will automatically exit limit setting mode.
ADJUST THE LIMITS
If the limits have already been set the operator will exit the limit setting mode after resetting each limit.
Set the Close Limit Only
Press the SET OPEN and SET CLOSE buttons simultaneously to enter limit
1
setting mode.
Press and hold the CLOSE button on the remote control until the gate reaches
2
the desired close position. The gate can be jogged back and forth using the
OPEN and CLOSE buttons on the remote control.
Set the Open Limit Only
Press the SET OPEN and SET CLOSE buttons simultaneously to enter limit
1
setting mode.
Press and hold the OPEN button on the remote control until the gate reaches
2
the desired open position. The gate can be jogged back and forth using the
OPEN and CLOSE buttons on the remote control.
Once the gate is in the desired close position, press and release the STOP
3
button on the remote control.
Press and release the CLOSE button on the remote control again to set the
4
close limit.
When the close limit is set properly the operator will automatically exit limit setting
mode.
Once the gate is in the desired open position, press and release the STOP
3
button on the remote control.
Press and release the OPEN button on the remote control again to set the
4
open limit.
When the open limit is set properly the operator will automatically exit limit setting
mode.
34
Page 37
MAINTENANCE
MAINTENANCE CHART + BATTERIES
MAINTENANCE CHART
Disconnect all power (AC, solar, battery) to the operator before servicing. The operator's AC Power switch ONLY turns off AC power to the control board and
DOES NOT turn off battery power. ALWAYS disconnect the batteries to service the operator.
DESCRIPTIONTASKCHECK AT LEAST ONCE EVERY
MONTH6 MONTHS3 YEARS
Entrapment Protection DevicesCheck and test for proper operationX
Warning SignsMake sure they are presentX
Manual DisconnectCheck and test for proper operationX
Sprockets and ChainsCheck for excessive slack and lubricateX
GateInspect for wear or damageX
AccessoriesCheck all for proper operationX
ElectricalInspect all wire connectionsX
Chassis Mounting BoltsCheck for tightnessX
OperatorInspect for wear or damageX
BatteriesReplaceX
NOTES:
• Severe or high cycle usage will require more frequent maintenance checks.
• It is suggested that while at the site voltage readings be taken at the operator.
Using a digital voltmeter, verify that the incoming voltage to the operator it is
within ten percent of the operator’s rating.
BATTERIES
Batteries will degrade over time depending on temperature and usage. For best
performance, the batteries should be replaced every 3 years. Use only LiftMaster
part 29-NP712 for replacement batteries. The operator comes with two 7AH
batteries. Two 33AH (A12330SGLPK) with additional battery tray (K10-36183) may
be used in place of the 7AH batteries.
The batteries contain lead and need to be disposed of properly. Batteries do not
perform well in extremely cold temperatures.
NOTE: If your application includes a heater, two 33AH will not fit into the operator
enclosure.
The operator alarm will beep 3 times with a command if the battery is low.
35
Page 38
TROUBLESHOOTING
CONTROL BOARD LEDS
CONTROL BOARD LEDS
The control board is equipped with many LEDs that have a variety of functions. The control board LEDs indicate the status of the operator, assist with programming, and
diagnose potential problems with the operator.
STATUS LEDS
LIMIT SETUP LEDS
GREEN XMITTER LED
DIAGNOSTIC CODES LEDS
INPUT LEDS
LIMIT SETUP LEDS
SET OPEN
LED
BLINKINGBLINKINGNORMAL MODELimits are not set.
OFFOFFNORMAL MODELimits are set.
BLINKINGBLINKINGLIMIT SETTING MODELimits are not set.
BLINKINGONLIMIT SETTING MODEOpen limit is not set.
ONBLINKINGLIMIT SETTING MODEClose limit is not set.
ONONLIMIT SETTING MODELimits are set.
SET CLOSE
LED
OPERATOR MODEEXPLANATION
RESET
ALARM
GREEN XMITTER LED
XMITTER LEDEXPLANATION
OFFNo remote control activity, normal operation.
ONProgramming mode active.
FASTRecognized remote control signal.
FASTERUnrecognized remote control signal.
FASTESTRemote controls are being erased.
36
Page 39
TROUBLESHOOTING
CONTROL BOARD LEDS
CONTROL BOARD LEDS
DIAGNOSTIC CODES LEDS
YELLOW DIAGNOSTIC LED
# BLINKSMEANINGCORRECTION
1 BLINK
2 BLINKS
Low Power Mode(not an error)
ID resistor failureCheck ID resistor wiring, clear limit
settings and reset limits
3 BLINKS
5 BLINKS
Exceeded Maximum
Run Timer
Check gate travel, if necessary adjust
force setting
RPM (obstruction) Check for obstruction, if necessary
adjust force setting
6 BLINKS
Current (obstruction) Check for obstruction, if necessary
adjust force setting
7 BLINKS
Position failure Check gate travel, clear limit settings
and reset limits
12 BLINKS
Loop Error
One of the loops is in error. Refer to the
loop detector to determine the error.
STATUS LEDS
INPUT POWEROFFOFF state
ONAC charger or Solar power available
BATT
CHARGING
TIMEROFFThe timer is disabled
GATE MOVINGOFFThe gate is stopped
BATT LOWOFFNo battery error
ACC PWR OVLD OFFOFF state
OFFNot charging
ONTrickle charge
FAST BLINKHigh current charge
FASTER BLINKOver voltage error
ONThe timer is enabled
MEDIUM BLINKThe timer is running
FAST BLINKThe timer is paused
FASTER BLINKThe timer is cancelled
ONThe gate is opening or closingFASTEST BLINKThe operator is in E2
ONBattery low error
MEDIUM BLINKBattery critically low error
FAST BLINKBattery disconnected error
FASTEST BLINKCharging, extreme temperature, or over
voltage error
ONAccessory overload protector opened
RED DIAGNOSTIC LED
# BLINKSMEANINGCORRECTION
2 BLINKS
Current SenseMotor control circuit fault, replace
control board
3 BLINKS
FET Failure Motor control circuit fault, replace
control board
4 BLINKS
5 BLINKS
RAM FailureMemory failure, replace control board
Flash Memory
Memory failure, replace control board
Failure
6 BLINKS
7 BLINKS
EEPROM FailureMemory failure, replace control boardWatchdog FailureController failure, replace control
board
8 BLINKSBrownoutCheck power harness or line voltage
9 BLINKSFailControl Board failure
10-14 BLINKS Software FailureCycle power to the control board. If
continues replace control board.
INPUT LEDS
OPEN INPUTOFFInput inactive
ONInput active
BLINKInput active on other operator
CLOSE INPUTOFFInput inactive
ONInput active
BLINKInput active on other operator
STOP INPUTOFFInput inactive
ONInput active
BLINKInput active on other operator
FIRE DEPT
INPUT
OPEN SAFETY
INPUT
CLOSE SAFETY
INPUT
OFFInput inactive
ONInput active
BLINKInput active on other operator
OFFInput inactive
ONInput active
BLINKInput active on other operator
OFFInput inactive
ONInput active
BLINKInput active on other operator
37
Page 40
TROUBLESHOOTING
FAULTPOSSIBLE CAUSESCORRECTIONS
Operator does not
run and diagnostic
LED not on.
Control board
powers up, but
motor does not run.
Relay clicks with
command, but motor
does not turn on.
Arm moves, but
cannot set correct
limits.
Gate does not fully
open or fully close
when setting limits.
Operator does not
respond to a wired
control/command
(example: Open,
Close, SBC, etc.)
Operator does not
respond to a
wireless control or
transmitter
a) No power to control board
b) Open fuse
c) If on battery power only, low or dead batteries
d) Defective control board
a) Check DIAGNOSTIC LEDs
b) Reset button is stuck
c) Stop button active
d) If on battery power only, low or dead batteries
e) Open or Close input active
f) Entrapment Protection Device active
g) Vehicle loop detector or probe active
h) Defective control board
a) Arm jammed or not connected
b) Defective motor or motor wires
c) Defective control board
a) Arm does not extend or retract enough during
travel
b) Arm is interfering with mounting bracket
c) Gate is too difficult to move
a) Arm does not extend or retract enough during
travel
b) Arm is interfering with mounting bracket
c) Gate is too difficult to move
a) Check DIAGNOSTIC LEDs
b) Check Open and Close command input LEDs
c) Stop button is active
d) Reset button is stuck
e) If on battery power only, low or dead batteries
f) Entrapment Protection Device active
g) Vehicle loop detector or vehicle probe active
h) Defective control board
a) Check DIAGNOSTIC LEDs
b) Check XMITTER LED when wireless control is
active
c) Stop button is active
d) Reset button is stuck
e) Poor radio reception
f) Defectivecontrol board
a) Check AC and battery power
b) Check fuses
c) Charge batteries by AC or solar power or replace batteries
d) Replace defective control board
a) Use Diagnostic code to identify issue
b) Check Reset button
c) Check Stop button is not “stuck on”
d) Charges batteries by AC or solar power or replace batteries
e) Check all Open and Close inputs for a “stuck on” input
f) Check all Entrapment Protection Device inputs for a “stuck on” sensor
g) Check all vehicle detector inputs for a “stuck on” detector
h) Replace defective control board
a) Disconnect the arm from the operator and ensure arm moves freely
Inspect motor and motor wires for open wire, shorted wires, damage, etc. Else, replace
b)
motor.
c) Replace defective control board.a) Disconnect the arm from the operator and ensure arm moves freely
b) Examine the hinge point where the arm mounts to the gate post. Make sure that the arm
housing does not hit or interfere with the gate post or mounting bracket. Correct as
necessary.
c) Disconnect arm from gate and move gate manually. Gate must move easily and freely
through its entire range, limit-to-limit. Repair gate as needed.
a) Disconnect the arm from the operator and ensure arm moves freely
b) Examine the hinge point where the arm mounts to the gate post. Make sure that the arm
housing does not hit or interfere with the gate post or mounting bracket. Correct as
necessary.
c)Disconnect arm from gate and move gate manually. Gate must move easily and freely
through its entire range, limit-to-limit. Repair gate as needed.
a) Use Diagnostic code to identify issue
b) Check all Open and Close inputs for a “stuck on” input
c) Check Stop button is not “stuck on”
d) Check Reset button
e) Charges batteries by AC or solar power or replace batteries
f) Check all Entrapment Protection Device inputs for a “stuck on” sensor
g) Check all vehicle detector inputs for a “stuck on” detector
h) Replace defective control board
a) Use Diagnostic code to identify issue
b) Activate wireless control and check XMITTER LED is on. Re-learn wireless control/
transmitter to control board. Replace wireless control as needed.
c) Check Stop button is not “stuck on”
d) Check Reset button
e) Check if similar wired control operates correctly. Check if wireless controls works properly
when within a few feet of operator. Check operator’s antenna and antenna wire. Check
other wireless controls or devices.
f) Replace defective control board
TROUBLESHOOTING CHART
38
Page 41
TROUBLESHOOTING
FAULTPOSSIBLE CAUSESCORRECTIONS
Gate stops during
travel and reverses
immediately.
Gate opens, but will
not close.
Gate closes, but will
not open.
Gate does not close
from Timer-to-Close.
Vehicle Exit loop
activation does not
cause gate to open.
CLOSE EYES/
Interrupt loop does
not cause gate to
stop and reverse.
Vehicle Shadow loop
does not keep gate
at open limit.
a) Check DIAGNOSTIC LEDs
b) Inherent force obstruction detection
E xternal Entrapment Protection Device
c)
activation
d) Control (Open, Close) becoming active
e) Vehicle loop detector active
f) Low battery voltage
a) Check DIAGNOSTIC LEDs
b) Open control active
c) Close Entrapment Protection Device active
d) Vehicle loop detector active
e) Loss of AC power with AC FAIL set to OPEN
f) Low battery with LOW BATT set to OPEN
g) Fire Dept input active
a) Check DIAGNOSTIC LEDs
b) Open Entrapment Protection Device active
c) Vehicle loop detector active
d) Low battery with LOW BATT option set to
CLOSE
a) Timer-to-Close not set
b) Open control active
c) Close Entrapment Protection Device active
d) Vehicle loop detector active
e) Loss of AC power with AC FAIL set to OPEN
f) Low battery with LOW BATT option set to OPEN
g) Fire Dept input active
a) Check DIAGNOSTIC LEDs
b) Exit vehicle detector setup incorrectly
c) Defective Exit loop detector or loop wire
d) Low battery with LOW BATT option set to
CLOSE
a) Check DIAGNOSTIC LEDsb) Vehicle detector setup incorrectly
c) Defective vehicle loop detector or loop wire
a) Check DIAGNOSTIC LEDs
b) Vehicle detector setup incorrectly
c) Defective vehicle loop detector or loop wire
a) Use Diagnostic code to identify issue
Check for obstruction in gate’s path or travel. Disconnect arm from gate and move gate
b)
manually. Gate must move easily and freely through its entire range, limit-to-limit.
Remove obstruction or repair gate as needed.
c) Check all Entrapment Protection Device inputs for an active sensor
d) Check all Open and Close inputs for an active input
e) Check all vehicle detector inputs for an active detector
f) Battery voltage must be 22.0 Vdc or higher. Charge batteries by AC or solar power or
replace batteries
a) Use Diagnostic code to identify issue
b) Check all Open inputs for an active input
c) Check all Entrapment Protection Device inputs for an active sensor
d) Check all vehicle detector inputs for an active detector
e) Check AC power and AC Fail option setting
f) Battery voltage must be 22.0 Vdc or higher. Charge batteries by AC or solar power or
replace batteries
g) Check Fire Dept input
a) Use Diagnostic code to identify issue
b) Check all Entrapment Protection Device inputs for an active sensor
c) Check all vehicle detector inputs for an active detector
d) Check if AC power is available. If no AC power, then running on batteries and battery
voltage must be 22.0 Vdc or higher. Charge batteries by AC or solar power or replace
batteries
a) Check Timer-to-Close (TTC) setting
b) Check all Open inputs for an active input
c) Check all Entrapment Protection Device inputs for an active sensor
d)Check all vehicle detector inputs for an active detector
e) Check AC power and AC Fail option setting
f) Check if AC power is available. If no AC power, then running on batteries and battery
voltage must be 22.0 Vdc or higher. Charge batteries by AC or solar power or replace
batteries.
g) Check Fire Dept input
a) Use Diagnostic code to identify issue.
b) Review Exit loop detector settings. Adjust settings as needed.
c) Check Exit loop wire. Replace defective Exit loop detector.
d) Check if AC power is available. If no AC power, then running on batteries and battery
voltage must be 22.0 Vdc or higher. Charge batteries by AC or solar power or replace
batteries.
a) Use Diagnostic code to identify issue. Check Anti-Tail gate switch.
b) Review Interrupt loop detector settings. Adjust settings as needed
c) Check Interrupt loop wire. Replace defective Interrupt loop detector
a) Use Diagnostic code to identify issue
b) Review Shadow loop detector settings. Adjust settings as needed
c) Check Shadow loop wire. Replace defective Shadow loop detector
TROUBLESHOOTING CHART
39
Page 42
TROUBLESHOOTING
FAULTPOSSIBLE CAUSESCORRECTIONS
Obstruction in gates
path does not cause
gate to stop and
reverse
Photoelectric sensor
does not stop or
reverse gate.
Edge Sensor does
not stop or reverse
gate.
Alarm sounds for 5
minutes or alarm
sounds with a
command.
Alarm beeps three
times with a
command.
On dual-gate
system, one gate is
not commanding the
other.
On dual-gate
system, incorrect
gate opens first or
closes first.
Expansion board
function not
controlling gate.
Maglock not
working correctly.
a) Force setting too higha) Adjust force setting. Retest that obstruction in gate’s path causes gate to stop and
reverse direction.
a) Incorrect photoelectric sensor wiring
b) Defective photoelectric sensor
a) Incorrect edge sensor wiring
b) Defective edge sensor
a) Double entrapment occurreda) Check for cause of entrapment (obstruction) detection and correct. Press the reset button
a) Low battery with loss of AC/solar powera) Check if AC power is available. If no AC power, then running on batteries and battery
a) Defective or incorrect Operator-to-Operator
wiring
b) Incorrect Operator-to-Operator wireless
learning
a) Incorrect Bipart switch settinga) Change setting of both operator’s Bipart switch settings. One operator should have Bipart
a) Defective main board to expansion board
wiring
b) Incorrect input wiring to expansion board
c) Defective expansion board or defective main
board
a) Maglock wired incorrectlya) Check that Maglock is wired to N.O. and COM terminals. Check that Maglock has power
a)
Check photoelectric sensor wiring. Retest that obstructingphotoelectric sensor causes
moving gate to stop, and may reverse direction. Check Anti-Tail gate switch.
b) Replace defective photoelectric sensor. Retest that obstructing photoelectric sensor causes
moving gate to stop, and may reverse direction.
Check edge sensor wiring. Retest that activating edge sensor causes moving gate to stop
a)
and reverse direction.
b) Replace defective edge sensor. Retest that activating edge sensor causes moving gate to
stop and reverse direction.
to shut off alarm and reset the operator.
voltage must be 22.0 Vdc or higher. Charge batteries by AC or solar power or replace
batteries
a) Check operator-to-operator wiring.
b) Relearn the wireless network of one operator to the other operator.
switch ON (operator that opens first) and the other operator should have Bipart switch
OFF (operator that opens second)
a) Check main board to expansion board wiring. If required, replace wire cable.
b) Check wiring to all inputs on expansion board.
c) Replace defective expansion board or defective main board
(do not power maglock from control board accessory power terminals). If shorting lock’s
NO and COM wires does not activate Maglock, then replace Maglock or Maglock wiring
TROUBLESHOOTING CHART
Solenoid lock not
working correctly.
Switched (SW)
Accessory power
remaining on.
Accessories
connected to Switch
(SW) Accessory
power not working
correctly, turning
off, or resetting.
a) Solenoid wired incorrectlya)
Main control board is not going to low power
a)
mode.
a)
Main control board is going to low power
mode.
a) Photoelectric sensor inputs may be active.
a) With expansion board disconnected and running on batteries (no AC power or solar
Check that Solenoid is wired to N.C. and COM terminals. Check that Solenoid has power
(do not power solenoid from control board accessory power terminals). If shorting lock’s
NC and COM wires does not activate Solenoid, then replace Solenoid lock or Solenoid
wiring
power available), main board will go into low power mode. Move accessory power to
Accy Power ON terminals (+, -). Connect expansion board to prevent low power mode.
40
Page 43
TROUBLESHOOTING
FAULTPOSSIBLE CAUSESCORRECTIONS
Accessories
connected to
Accessory power
not working
correctly, turning
off, or resetting.
Quick Close not
working correctly.
Anti-Tailgating not
working correctly.
AUX Relay not
working correctly.
a) Accessory power protector active
b) Defective control board
a) Quick Close setting incorrect
b)
CLOSE EYES/Interrupt loop detector or loop
wire defective
c) Defective Expansion board
a) Anti-Tail setting incorrect
b) CLOSE EYES/Interrupt loop detector or loop
wire defective
c) Defective Expansion board
a) AUX Relay setting incorrect
b) AUX Relay wiring incorrect
c) Defective Expansion board
a) Disconnect all accessory powered devices and measure accessory power voltage (should
be 23 – 30 Vdc). If voltage is correct, connect accessories one at a time, measuring
accessory voltage after every new connection.
b) Replace defective control board
a) Check that Quick Close setting is ON
b) Check operation of CLOSE EYES/Interrupt Loop detector
c) Replace defective Expansion board
a) Check that Anti-Tail setting is ON
b) Check operation of CLOSE EYES/Interrupt Loop detector
c) Replace defective Expansion board
a) Check AUX Relay switches settings
b) Check that wiring is connected to either N.O. and COM or to N.C. and COM.
c) Set AUX Relay to another setting and test. Replace defective expansion board.
TROUBLESHOOTING CHART
41
Page 44
DIAGRAM
WIRING DIAGRAMS
NON SOLAR
To protect against fire and electrocution:
• DISCONNECT power and battery BEFORE installing or servicing operator.
Field Wiring
Edge
Photoelectric Sensors
Interrrupt
Antenna
CONTROL BOARD
N.C.
Photoelectric Sensors
Primary/Secondary link
to other gate operator
Shielded Twisted
Yellow
Ground the shield of the cable to the
chassis ground of each operator.
Blue
Black
Red
Pair Cable
ALARM
For continued protection against fire:
• Replace ONLY with fuse of same type and rating.
Field Wiring
N.C.
1
EXPANSION BOARD
APS Encoder
Piezo Alarm
Red
Black
White
RESET
White
Purple
Resistor
Identication
Black
Stop/Reset
Run
To Pin 1
To Pin 2
Red
Reset Switch
1/2 HP 24 Vdc Motor
Ferrite EMI Filters
Field Wiring
Wire Loop
EXIT
INTERRUPT
SHADOW
Wire Loop
Wire Loop
Field Wiring
Coaxial Antenna Cable
+
--+
Black
Red
Black
Red
Red
12V 7AH Battery
12V 7AH Battery
Black
Black
Accessory
Power
Outlets
White
Gray
Install male insulated faston connectors on solar panel leads.
Plug them into the female faston connectors that were
connected to the bridge rectier.
-
+
-
-
Bridge Rectier
Orange
Orange
Transformer 375 VA, 24V, 120V
Blue
Purple
Brown
NOTE: The accessory outlet is disabled and
cannot be used with the 240 Vac option.
Two 12V Solar Panels in Series
Butt Splice
Solenoid Lock
(Optional)
COM
N.C.
N.O.
LOCK
(not provided)
N.C.
COM
LOCK
Maglock
(Optional)
N.O.
(not provided)
Switch/5A Breaker
Black
Red
EMI FILTER/SURGE PROTECTION BOARD
Heater
L
L
N
N
GND
GND
Input Power Connection
29C
42
Page 45
ACCESSORIES
ENTRAPMENT PROTECTION DEVICES
MISCELLANEOUS
PHOTOELECTRIC SENSORS (NON-CONTACT)
The photoelectric sensors are designed to detect an obstacle in the
path of the electronic beam and stop the operator. Includes
mounting brackets.
Sensing edges can detect an obstacle upon contact and stop the
operator.
Models G65MG0204, G65MG0205, G65MGR205, and
G65MGS205
SENSING EDGE CHANNEL
Mounting channel for all MG020 type edges.
Model G65ME120C5
REMOTE CONTROLS
Chamberlain offers a variety of LiftMaster remote controls to satisfy your application needs.
Single-button to 4-button, visor or key chain. The following remote controls are compatible
with operators manufactured by Chamberlain after 1993. Contact your authorized LiftMaster
dealer for additional details and options.
3-BUTTON REMOTE CONTROL
The 3-button remote control can be programmed to control the
operator. Includes visor clip.
Model 893MAX
3-BUTTON MINI-REMOTE CONTROL
The 3-button remote control can be programmed to control the
operator. Includes key ring and fastening strip.
Model 890MAX
KEYLESS ENTRY
Enables homeowner to operate gate operator from outside by
entering a 4-digit code on a specially designed keypad.
Model 877MAX
MISCELLANEOUS
POST-MOUNTING PLATE
For post-mounting model CSW24V commercial swing operator
(also CSW200 commercial swing operator). Posts not included.
Model MPEL
REMOTE ANTENNA EXTENSION KIT
The remote antenna extension kit allows the antenna to be
remotely installed.
Model 86LM
HEATER
Keeps operator, gearbox and batteries at suitable temperature
when outside temperature is below 0°F for extended periods of
time.
Models GHTRKITRSW (for Swing operator, includes bracket for
optimal heater location) and G6518CSW (Swing replacement
heater only)
PLUG-IN LOOP DETECTOR
Conveniently plugs into existing control board.
Model LOOPDETLM
LOOP DETECTOR
Low power loop detectors.
Model LD7LP
VEHICLE SENSING PROBE
The vehicle sensing probe is buried in the ground and can detect a
car as it approaches and will then open the gate.
Model CP3
SOLAR PANEL KIT - 10 WATT
This kit is to replace or add a solar panel to the operator
application. Up to three solar panels can be connected to the
operator.
Model SOLPNL10W12V (requires 2 minimum)
BATTERY FOR GATE ACCESS SYSTEMS
Gate access system batteries replace or upgrade the gate operator
batteries.
Model 29-NP712 (standard 7 AMP-Hour Battery or two 7 AMPHour battery service kit K74-30762, 12 Vdc, to replace original
batteries provided with operator, reuse existing harnesses)
Model A12330SGLPK (upgrade 33 AMP-Hour Battery, 12 Vdc,
includes 33AH harness. Ideal for solar applications and extended
battery backup. Two required.)
Two identical 12 Vdc batteries are required for each gate
operator. Do not mix 7AH and 33AH batteries within a gate
operator.
Model K10-36183 (battery tray for use with 33AH batteries)
SOLENOID GATE LOCK
The automatic gate lock is a solenoid-driven lock that
automatically unlocks when the gate is open and locks when the
gate is closed. Can be mounted onto a gate or post. Can be
released in case of emergency.
Models GC824 (115 Vac) and GC824-12 (12/24 Vac/dc)
WIRELESS ACCESS CONTROL RECEIVER
Access control receiver for up to 450 remote controls.
Model STAR450-315
MAGNETIC GATE LOCK
Outdoor magnetic lock, transformer, junction box, mounting plate
and hardware. Not for use with Solar Applications. Must be
powered separately.
Model MG1300
43
Page 46
REPAIR PARTS
INDIVIDUAL PARTS
ITEM PART NUMBER DESCRIPTION
1 K13-36117 Cludge Cover
2 K77-36538 Operator Cover with labels, keys, and lock
assembly
3 K73-36109 Chassis
4 K76-34644 APS Encoder with cable
5 K19-50038 #50 Drive Chain and Master Link
6 K32-35814 Gear Reducer (bottom)
7 K15-50B18LKGH Gear Reducer Sprocket with set screws and
and APS sprocket roll pin
9 K32-34655-1 Gear Box (top)
10 K10-36395 Battery Tray
11 29-NP712 Battery, 7AH, 12 Vdc
12 K204C0211 Toroid Transformer
13 K1A6408 APE Assembly with plastic tray, RPM board
with mounting hardware
14 K52C0481 Bridge Rectifier
15 K1D6597-1CC Main Board with heat sink
16 K1D6686CC Expansion Board
17 K76-34728 EMI Board with 120V receptacles and AC
power switch
18 K77-36541 Antenna
19 K76-36398 Motor, 1/2 HP, 24 Vdc
20 K77-36542 Electrical Box with junction box
21 K180A0357 Reset Switch
22 K94-35152 Alarm with harness
23 K75-36260 Lock and Keys
24 Q118 Keys
25 K13-34729 Dust Guard
26 Q061 Output Shaft Cludge Arm Clamp and Release
Handle
27 Q059 Output Arm
28 Q060 Release Handle
29 Q104 Standard Arm Assembly
NOT SHOWN
K94-36540 Wiring Harness with ID resistor assembly
K94-36250 Battery Harness (for 7AH batteries)
Q103 Swivel Arm AssemblyK80-36544 Vent Plug (for top gear box)K80-36545 Vent Plug (for bottom gear box)30 Amp Fuses
K74-30762 Two 7AH batteriesK94-36596 Battery Harness (for 33AH batteries)
44
Page 47
REPAIR PARTS
1
28
9
12
7
5
6
19
26
27
8
29
1011
3
22
20
4
14
18
13
21
15
17
16
25
2
23
24
45
Page 48
WARRANTY
7 YEAR RESIDENTIAL / 5 YEAR COMMERCIAL CSW24V™ AND CSW24VH™ LIMITED WARRANTY
The Chamberlain Group, Inc. (“Seller”) warrants to the first purchaser of this product, for the structure in which this product is originally installed, that it is free from defect in
materials and/or workmanship for a period of 7 year residential/ 5 year commercial from the date of purchase [and that the CSW24V™ and CSW24VH™ are free from
defect in materials and/or workmanship for a period of 7 year residential/ 5 year commercial from the date of purchase]. The proper operation of this product is dependent
on your compliance with the instructions regarding installation, operation, maintenance and testing. Failure to comply strictly with those instructions will void this limited
warranty in its entirety.
If, during the limited warranty period, this product appears to contain a defect covered by this limited warranty, call 1-800-528-2806, toll free, before dismantling this
product. Then send this product, pre-paid and insured, to our service center for warranty repair. You will be advised of shipping instructions when you call. Please include a
brief description of the problem and a dated proof-of-purchase receipt with any product returned for warranty repair. Products returned to Seller for warranty repair, which
upon receipt by Seller are confirmed to be defective and covered by this limited warranty, will be repaired or replaced (at Seller’s sole option) at no cost to you and returned
pre-paid. Defective parts will be repaired or replaced with new or factory-rebuilt parts at Seller’s sole option.
ALL IMPLIED WARRANTIES FOR THE PRODUCT, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO THE 7 YEAR RESIDENTIAL/
5 YEAR COMMERCIAL LIMITED WARRANTY PERIOD SET FORTH ABOVE [EXCEPT THE IMPLIED WARRANTIES WITH RESPECT
TO THE CSW24V™ AND CSW24VH™, WHICH ARE LIMITED IN DURATION TO THE 7 YEAR RESIDENTIAL/ 5 YEAR
COMMERCIAL LIMITED WARRANTY PERIOD FOR THE CSW24V™ AND CSW24VH™], AND NO IMPLIED WARRANTIES WILL
EXIST OR APPLY AFTER SUCH PERIOD. Some states do not allow limitations on how long an implied warranty lasts,
so the above limitation may not apply to you. THIS LIMITED WARRANTY DOES NOT COVER NON-DEFECT DAMAGE,
DAMAGE CAUSED BY IMPROPER INSTALLATION, OPERATION OR CARE (INCLUDING, BUT NOT LIMITED TO ABUSE, MISUSE,
FAILURE TO PROVIDE REASONABLE AND NECESSARY MAINTENANCE, UNAUTHORIZED REPAIRS OR ANY ALTERATIONS TO
THIS PRODUCT), LABOR CHARGES FOR REINSTALLING A REPAIRED OR REPLACED UNIT, OR REPLACEMENT OF BATTERIES.
THIS LIMITED WARRANTY DOES NOT COVER ANY PROBLEMS WITH, OR RELATING TO, THE GATE OR GATE HARDWARE,
INCLUDING BUT NOT LIMITED TO THE GATE SPRINGS, GATE ROLLERS, GATE ALIGNMENT OR HINGES. THIS LIMITED
WARRANTY ALSO DOES NOT COVER ANY PROBLEMS CAUSED BY INTERFERENCE. ANY SERVICE CALL THAT DETERMINES
THE PROBLEM HAS BEEN CAUSED BY ANY OF THESE ITEMS COULD RESULT IN A FEE TO YOU.
UNDER NO CIRCUMSTANCES SHALL SELLER BE LIABLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES ARISING
IN CONNECTION WITH USE, OR INABILITY TO USE, THISPRODUCT. IN NO EVENT SHALL SELLER’S LIABILITY FOR BREACH
OF WARRANTY, BREACH OF CONTRACT, NEGLIGENCE OR STRICT LIABILITY EXCEED THE COST OF THE PRODUCT COVERED
HEREBY. NO PERSON IS AUTHORIZED TO ASSUME FOR US ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OF THIS
PRODUCT.
Some states do not allow the exclusion or limitation of consequential, incidental or special damages, so the above limitation or exclusion may not apply to you. This limited
warranty gives you specific legal rights, and you may also have other rights which vary from state to state.