FAAC 450 MPS User Manual

Page 1
100% papel reciclado
ist umweltfreundlich
100% Altpapier
450 MPS
450 MPS
pour la nature
papier recyclé 100%
for nature
recycled paper 100%
per la natura
M
R
E
E
T
C
A
Z
I
E
N
D
UNI EN ISO 9001-085
A
C
I
F
A
I
T
C
R
E
A
T
carta riciclata 100%
Page 2
ENGLISH
IMPOR TANT NOTICE FOR THE INSTALLER
GENERAL SAFETY REGULATIONS
1) WARNING! FAAC strongly recommends to follow these instructions literally for the safety of persons. Improper
installation or misuse of the product will cause very serious damages to persons.
2) Packaging material (plastic, polystyrene etc.) is a potential hazard and must be kept out of reach of children. Read the instructions carefully before installing the product.
3)
4) Keep these instructions for future reference.
5) This product has been designed and manufactured only for the use stated in this manual. Any other use not expressly set forth will affect the reliability of the product and/or could be source of hazard.
6) FAAC S.p.A. cannot be held responsible for any damage caused by improper use or different from the use for which the automation system is destined to.
7) Do not use this device in areas subject to explosion: the presence of flammable gas or fumes is a serious hazard.
8) Mechanical constructive elements must comply with UNI8612, CEN pr EN 12604 and CEN pr EN 12605 standards. Countries outside the EC shall follow the regulations above besides their national normative references in order to
offer the utmost safety.
9) FAAC cannot be held responsible for failure to observe technical standards in the construction of gates and doors, or for any deformation of the gates which may occur during use.
10) Installation must comply with UNI8612, CEN pr EN 12453 and CEN pr EN 12635. The degree of safety of the automation must be C+E.
11) Before carrying out any operations, turn off the system’s main switch.
12) An omnipower switch shall be provided for the installation with an opening distance of the contacts of 3 mm or more. Alternatively, use a 6A thermomagnetic breaker with multi-pole switching.
13) Ensure that there is a differential switch up-line of the electrical system, with a trip threshold of 0.03A.
14) Check that the earthing plant is in perfect condition and connect it to the metallic parts. Also earth the yellow/green wire of the operator.
15) The automation is fitted with an anti-crush safety system that is a torque control device. In any case, further safety devices shall be installed.
16) The safety devices (e.g. photocells, safety edges, etc.) protect areas wherethere is a mechanical movement hazard, e.g. crushing, entrapment and shearing.
17) Each installation must be fitted with at least one flashing light (e.g. FAAC LAMP, MINILAMP etc.) as well as a warning plate suitably fixed to the gate, besides the safety devices as per point 16. above.
18) FAAC cannot be held responsible regarding safety and correct functioning of the automation in the event that parts other than FAAC original parts are used.
19) Use only FAAC original spare parts for maintenance operations.
20) Do not carry out any modifications to automation components.
21) The installer must supply all information regarding manual operation of the system in the event of an emergency and provide the end-user with the leaflet attached to the product.
22) Keep out of persons when the product is in operation.
23) Keep out of reach of children the remote radio controls and any control devices. The automation could be operated unintentionally.
24) The end-user must avoid any attempt to repair or adjust the automation personally. These operations must be carried out exclusively by qualified personnel.
25) What is not explicitly stated in these instructions is not permitted.
9
Page 3
ENGLISH
DESCRIPTION AND TECHNICAL SPECIFICATIONS
LAYOUT AND ELECTRICAL WIRING
Table 1: 450 MPS Control unit technical specifications
Power supply 230 V(+6%-10%) - 50 Hz Absorbed power 10 W Max. motor load 800 W Max. accessories load 0,5 A Max. electric lock load 12 VA Temperature range -20 °C +55 °C Fuses N. 4 (see fig.1) Operations logics Automatic / Semi-automatic / Safety / Dead-man
Automatic timer/ button / Step-by-step semi-automatic
Opening/closing time Adjustable by trimmer (from 0-120 s) Pause time Adjustable by trimmer (from 0-240 s) Closing leaf delay time Adjustable by trimmer (from 0 -28 s) Opening leaf delay time 2.5 s (Can be disabled through bridge) Thrust force Adjustable by trimmer Terminal block inputs Open/Open single leaf/Stop/Opening safeties/Closing
Terminal block outputs Flashing light - motors - 24 Vdc accessories power
Quick connector Decoding cards - RP 433 SL/DS Microswitch programmable functions Operating logics - Reversing stroke for
J1
supply - 24 Vdc warning light power supply -
J2
safeties/ mains power +earth
12 Vac electric lock power supply
electric lock - Closing safeties logics
F1
J3
F4
F2
l
F3
OPENING
e
LEAF DELAY DISABLE
i
DL4
DL5
J2 J3J1
NL
a b c
j
m k
f
FAILSAFE ON-OFF
DL2
DL3
g
d
h
n
o
DL1
Fig. 1
1
2
N
230 V
3
L
50 Hz
4
6
5
OP COM CL CL COM OP
LAMP MOTOR 1 MOTOR 2
BLU
M1
C1
98
7
10
BLU
M2
C2
11
N.B.: The capacitors are provided with the operators.
Caution: Before touching the electronic unit (connections,
programming, maintenance) always switch off the power supply.
a J1 terminal block (fig. 2)
: Earth connection N. : power supply 230 V~ ( Neutre ) L. : power supply 230 V~ ( Phase)
N.B.: For correct operation the card must be connected to the
system’s earth. Install a suitable differential magneto-thermal circuit-breaker upstream of the system.
b J2 terminal block (fig. 2)
LAMP.: flashing light output ( 230 V ~) MOTOR 1 Open /Common/ Close: Motor 1 connection
Can be used in one-leaf application. (
leaf closing delay)
MOTOR 2 Close /Common/ Open: Motor 2 connection
Not to be used in one-leaf application.
N.B. To check the operation of the equipment at the test
bench, a load must be connected on the MOTOR 1 input.
c J3 terminal block: low voltage (fig. 2) used to connect all
accessories (see table 2).
12
13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
+ —
OP — CL NC —
30 Vcc FSW STOP
B — A — + —
OPEN
STOP
IND.
OPEN TOT.
FSWTX W.LIGHT LOCK
FSW TX
+ —
24 Vdc
3 W
For the safety and fail-safe devices, see the “Safety devices” section.
Fig. 2
Warning: the max. accessory load is 500 mA. To calculate
absorption values, refer to table 2.
Safety devices
These are all devices (photocells, safety edges, magnetic coils, etc.) with an N.C. (normally closed) contact which activate if an obstacle obstructs the area protected by the
Opening, closing or opening/closing photocells
A
A
A
B
B
30 Vdc
– accessories power supply negative + accessories power supply positive (+ 30 Vdc)
10
Closing photocells
Opening
photocells
Fig. 3
Page 4
ENGLISH
1 2
5
4
3
1
2
RX CL TX CL
1 2
5
4
3
1
2
RX OPTX OP
14
15
2423
16
12
13
30Vcc
OP — CL
FSW
+ —
FSWTX
+ —
safety devices and stop the movement of the gate leaves (fig. 3). The 450 MPS card has an additional FAIL-SAFE device which serves to check that the N.C. contact on the photocell receiver is working efficiently before any operation (Can be disabled through bridge Fig. 1 ref.15) . N.B.: If the Opening safety devices are engaged when the gate is closed, they prevent the leaves from opening. If the Closing safety devices are engaged when the gate is open, they prevent the leaves from closing.
OP. - Opening safety device contact (N.C.): in the A-S-E-EP-AD
logics, during the opening phase the safety devices stop the movement of the gate leaves; when they are disengaged the opening movement recommences. They do not engage during closure. In the B, C and B/C logics, they interrupt movement during the opening cycle. They do not engage during the closing cycle.
N.B.: If opening safety devices are not connected, jumper inputs OP and FSW TX (Fig. 4).
Application examples
The following are the commonly used connection arrangements (enable fail -safe):
No safety device connected One pneumatic edge connected as closing safety device and
15
14
OP — CL
FSW
16
+ —
FSWTX
2423
The purpose of the opening safety devices is to safeguard the zone behind the gate leaves (A, fig. 3).
CL. - Closing safety device contact (N.C.): in the A-S-E-EP-AD
logics, during the closing phase the safety devices reverse the direction of movement of the gate leaves, or they stop the movement of the leaves then reverse direction when they are disengaged (see microswitch SW4 settings). They do not engage during the opening cycle. In B, C and B/C logics, they interrupt movement during the closing cycle. They do not engage during the opening cycle.
N.B.: If closing safety devices are not connected, jumper inputs OP and FSWTX (fig. 4).
The purpose of the closing safety devices is to safeguard the zone in which the leaves move during the closing cycle (B, fig. 3). If the Fail-Safe function is not used, see cabling at page 4 for connections of photocells.
one connected as opening safety device
15
14
OP — CL
FSW
16
+ —
FSWTX
2423
1 pair of closing photocells connected 1 pair of opening photocells connected
15
16
14
13
12
+ —
OP — CL
30Vcc
FSW
1
2 3
4 5
RX TX
1 pair of opening photocells and 1 pair of closing
photocells connected
15
16
14
13
12
+ —
30Vcc
OP — CL
FSW
1
2 3
4 5
RX CL TX CL
+ —
FSWTX
1 2
+ —
FSWTX
1 2
2423
Fig. 4
2423
12
+ —
30Vcc
Fig. 6
13
15
16
14
OP — CL
FSW
1
2 3
4 5
RX TX
+ —
FSWTX
1 2
2423
Fig. 5
Fig. 7
1 pair of closing photocells and 1 pair of opening/closing
photocells connected
1 2
Important: for further information on the operation of the safety devices, see table 3.
1
2 3
4
5
RX OPTX OP
Fig. 8
Fig. 9
11
Page 5
ENGLISH
Application examples
The following are the commonly used connection arrangements (disable fail -safe)
No safety device connected
15
16
14
OP — CL
FSW
+ —
FSWTX
1 pair of closing photocells connected
15
16
14
13
12
+ —
30Vcc
OP — CL
FSW
1
2 3
4 5
RX TX
+ —
FSWTX
1
2
2423
2423
Fig. 4/A
Fig. 6/A
One pneumatic edge connected as closing safety device and
one connected as opening safety device
15
14
OP — CL
FSW
16
+ —
FSWTX
2423
Fig. 5/A
1 pair of opening photocells connected
12
+ —
30Vcc
13
15
16
14
OP — CL
FSW
1
2 3
4 5
RX TX
+ —
FSWTX
1
2
2423
Fig. 7/A
Two pair of closure photocells connected
15
16
14
13
12
+ —
30Vcc
OP — CL
FSW
1
2 3
4 5
1 2
RX TX
TX
1 2
RX
+ —
FSWTX
5 4
3 2
1
1 pair of closing photocells and 1 pair of opening/closing
photocells connected
2423
12
+ —
30Vcc
13
15
14
OP — CL
FSW
1
2 3
4
5
16
RX TX
1
2
TX
Fig. 8/A
RX
+ —
FSWTX
1 2
5 4
3 2
1
2423
Fig. 9/A
12
Page 6
ENGLISH
STOP
– Common ( - ) N.C. - STOP contact: all devices (such as pushbuttons)
which by opening a contact stop gate movement. To install several safety stop devices, connect the N.C. contacts in series.
N.B. If the STOP devices are not connected, jumper STOP and - inputs.
B - SINGLE LEAF OPENING (N.O.): all devices (e.g. pushbutton)
which, by closing a contact activates opening and/or closing of the leaf driven by motor 1.
– Common ( - )
A - TWO-LEAF OPENING (N.O.): all devices (pushbuttons ,
photocells, detectors, etc.) which assures opening/closing of both leaves by closing a contact. To install several control devices, connect the N.O. contacts in parallel.
FSWTX
+ – Photocell transmitter power supply (FailSafe) To use the Fail-Safe function, power supplies to the photocell transmitters must be connected.
W.LIGHT
+– Warning lamp power supply 24 Vdc 3 W max.
For correct operation of the system, power (see table 2).
LOCK
12 Vac electric lock power supply.
do not exceed stated
d J4 quick connector for decoder SL/DS - MINIDEC SL/DS - RP
433 SL/DS cards (figs. 10-11-12-13)
e TORQUE trimmer: thrust adjusting trimmer (anti-crushing
safety system).
f PAUSE trimmer: pause time adjusting trimmer (A/S/AD
logics). Pause time is adjustable from 0 to 240 seconds.
g OP/CL trimmer: Opening/Closing time adjusting trimmer
Time is adjustable from 0 to 120 seconds.
h LEAF DELAY trimmer: closing leaf delay adjusting trimmer.
Leaf delay time is adjustable from 0 to 28 seconds.
N.B.:
1) If the opening/closing time is less than the set delay
time, the delayed leaf closes at the end of the closing time.
2) In one-leaf application, set the leaf delay time to
minimum
i Programming microswitches j Fuse F1 5x20 5 A/250 V rapid (motor power supply)
k Fuse F2 5x20 800 mA/250 V delayed (accessories power
supply)
l Fuse F3 5x20 1.6 A/250 V delayed (electric power supply) m Fuse F4 5x20 250 mA/250 V delayed (transformer power
supply)
n Bridge to enable/disable the Fail-Safe (Fig. 14).
o Bridge to enable/disable the wing opening
delay(Fig. 14).
Table 2 - Current drawn by accessories
ACCESSORY CURRENT DRAWN
PLUS 40 SL 30 mA PLUS 433 E 20 mA
MINIDEC SL / DS 6 mA
DECODER SL / DS 20 mA / 55 mA
RP 433 SL / DS 12 mA / 6 mA
DIGICARD 15 mA
METAL DIGIKEY 15 mA
FOTOSWITCH 90 mA
DETECTOR F4 / PS6 50 mA
PHOTOBEAM 50 mA
WARNING LIGHT 150 mA
PLUS 433 E
450 MPS
DECODER
MINIDEC SL/DS
Fig. 10
N.B. Use a dedicated decoder for other accessory types.
SL
Fig. 11
Fig. 12
13
Fig. 13
Page 7
ENGLISH
4) Switch on the power.
5) Send an OPEN signal to input A (fig. 2) and check that the
If the gate closes, invert the motor wires on the control unit (brown and black wires).
FAIL-SAFE LEAF DELAY
Disable
Enable
DisableEnable
Fig. 14
Opening/closing times are set by the OP/CL trimmer on the control unit (fig. 1 - ref.7). To reduce operation time, adjust the trimmer anticlockwise To increase operation time, adjust the trimmer clockwise. Maximum operation time is 120 seconds. For 90° opening the approximate opening/closing time is 18
1. PROGRAMMING THE MICROSWITCHES
Automation programming is carried out by the microswitches (fig. 1 - ref. 9) as shown in the diagram below.
Fig. 15
12345
seconds. For optimal system efficiency set the opening/closing time so that the electric motor remains activated for a few seconds after the leaf has reached the mechanical travel stop.
In the case of overlapping leaves, it is possible to delay closing of the leaf driven by motor M1 (see fig. 2) to ensure correct closure of the gate. Set the delay by the LEAF DELAY trimmer on the 450 MPS control
SW2
OPERATING LOGICS
A
S E
EP
B
C
B/C
AD
SW1 OFF
ON
OFF
ON ON
OFF
OFF
OFF OFF
ON ON ON
OFF
ON OFF
1.1. OPERATION LOGICS
SW3 OFF
OFF OFF OFF
ON ON
ON ONON
REVERSING STROKE FOR
ELECTRIC LOCK
NOT ACTIVATED
ACTIVATED
SAFETIES ON CLOSING
INVERTS MOVEMENT IMMEDIATELY
STOPS AND INVERTS MOVEMENT ON DISENGAGEMENT
SW5 OFF
ON
SW4
OFF
ON
unit (fig. 1 - ref. 8). To reduce delay time, adjust the trimmer anticlockwise. To increase delay time, adjust the trimmer clockwise. Maximum delay time is 28 seconds. If the operation time is shorter, the delay time is reduced automatically.
When A or S logics are selected, the leaf momentary stop time can be set using the PAUSE trimmer (fig. 1 ref. 6). Turn the trimmer clockwise to increase the time. Turn the trimmer anticlockwise to reduce the time. The maximum pause time is 240 sec.
There are seven operating logics available: A: “AUTOMATIC ” E : “SEMI-AUTOMATIC”
S : “SAFETY” EP : “SEMI-AUTOMATIC STEP-BY-STEP” B : “DEAD-MAN BUTTON” C : “DEAD-MAN BUTTON” B/C : “DEAD-MAN BUTTON” AD :“AUTOMATIC TIMER”
Operation of the different logics is described in tables 3/a-b-c-d-e-f-g-h.
1.2. REVERSING STROKE FOR ELECTRIC LOCK
This function is to be activated only if the electric lock is installed.
1.3. SAFETIES ON CLOSING
This function serves to select the operating mode for the closing safeties:
- OFF: immediate reverse of movement during gate closure
- ON: movement is stopped during closing and reversed on opening when the safety is disengaged.
The 450 MPS control unit has been designed for use on both electromechanical and hydraulic operators. When the 450 MPS card is used on electromechanical operators, the torque control device must be set by turning the TORQUE trimmer (fig. 1 ref. 5). To reduce torque, adjust the trimmer anticlockwise. To increase torque, adjust the trimmer clockwise. In any event, FAAC advises not to exceed a torque of 15 Kg measured on the outer edge of the leaf. To ensure precise torque adjustment use a linear dynamometer. When the 450 MPS card is used on hydraulic operators, the torque control device must be set to the maximum value by turning the TORQUE trimmer clockwise. This device is already present inside the operator hydraulic circuit (BY-PASS valves).
2. START-UP
1) Program the 450 MPS electronic control unit according to
specific requirements as shown in fig. 14.
2) Check led status as shown in table.
LED functions
LEDS ON OFF DL 1 (OPEN INPUT A) Command active Command not active DL 2 (OPEN INPUT B) Command active Command not active DL 3 (STOP) Command not active Command active DL 4 (FTSW OPEN) Safeties disengaged Safeties engaged DL 5 (FTSW CLOSE) Safeties disengaged Safeties engaged
N.B.: the bold text indicates led status with gate idle.
2.1. DIRECTION OF ROTATION
1) Switch off the power.
2) Manually move the gate to halfway.
3) Lock the operators.
leaf opens.
2.2. OPERATION TIME ADJUSTMENT
2.3. CLOSING LEAF DELAY ADJUSTMENT
2.4. SETTING PAUSE TIME
2.5. ANTI-CRUSHING SYSTEM ADJUSTMENT
14
Page 8
ENGLISH
on
W.L.
OPENING/CLOSING SAFETIESCLOSING SAFETIESOPENING SAFETIES
on
flashing light
continues to open
No effect (OPEN inhibited)
Stops opening and, when disengaged,
Stops closing and, when disengaged, opens
No effect off
No effect
Freezes pause until disengagement (*1) (OPEN inhibited)
See paragraph 1.3
on
on
W.L.
No effect (OPEN inhibited)
OPENING/CLOSING SAFETIESCLOSING SAFETIESOPENING SAFETIES
No effect (OPEN inhibited)
No effect off
Freezes pause until disengagement (*1) (OPEN inhibited)
on
on
flashing light
continues to open
Stops opening and, when disengaged,
Stops closing and, when disengaged, opens
No effect (OPEN inhibited)
No effect
on
W.L.
No effect (OPEN inhibited)
OPENING/CLOSING SAFETIESCLOSING SAFETIESOPENING SAFETIES
No effect (OPEN inhibited)
No effect off
on
flashing light
Stops opening and, when disengaged,
Stops closing and, when disengaged, opens
No effect
See paragraph 1.3
on
continues to open
on
W.L.
No effect (OPEN inhibited)
OPENING/CLOSING SAFETIESCLOSING SAFETIESOPENING SAFETIES
No effect (OPEN inhibited)
No effect off
on
flashing light
continues to open
Stops opening and, when disengaged,
Stops closing and, when disengaged, opensSee paragraph 1.3
No effect
on
No effect (OPEN inhibited)
PULSES
No effect
No effect (OPEN inhibited)
Stops opening and, when disengaged, closes
No effect (OPEN inhibited)
STOP
Stops
OPEN-B
after pause time
Recloses leaf immediately
Opens single leaf and re-closes
No effect
OPEN-A
Opens leaves and
recloses after pause time
Reopens leaves immediately Reopens leaf immediately
Recloses leaves immediately
No effect
PULSES
No effect
No effect (OPEN inhibited)
STOP
No effect (OPEN inhibited)
OPEN-B
Opens single leaf and
recloses after pause time
Recloses leaf immediately
Closes the leaf/leaves
OPEN-A
Opens leaves and
recloses after pause time
Recloses leaves immediately
No effect
No effect (OPEN inhibited) See paragraph 1.3
Stops opening and, when disengaged, closes
Stops
No effect (OPEN inhibited)
PULSES
No effect
No effect (OPEN inhibited)
No effect (OPEN inhibited)
STOP
Stops
OPEN-B
Opens single leaf
Recloses leaf immediately
Closes the leaf/leaves
Reopens leaves immediately Reopens leaf immediately
Recloses leaves immediately
OPEN-A
Reopens leaf immediately
Opens leaves
Recloses leaves immediately Recloses leaf immediately
Reopens leaves immediately
No effect No effect (OPEN inhibited)
Stops opening and, when disengaged, closes
PULSES
STOP
No effect
Stops opening and, when disengaged, closes
No effect (OPEN inhibited)
Stops
OPEN-B
Stops
Closes the leaf/leaves No effect (OPEN inhibited)
Recloses leaf/leaves immediately
OPEN-A
Opens leaves Opens single leaf
Stops
Stops
No effect (if the gate must open, inhibits OPEN) No effect (if gate must close, inhibits OPEN)
No effect (OPEN inhibited)
Inverts the direction
GATE STATUS
LOGICS "A"
Table 3/a
CLOSING
CLOSED
OPEN on PAUSE
STOPPED
OPENING
GATE STATUS
LOGICS "S"
Table 3/b
CLOSED
CLOSING
OPEN on PAUSE
STOPPED
OPENING
Table 3/c
15
CLOSED
GATE STATUS
LOGICS "E"
OPEN
CLOSING
STOPPED
OPENING
GATE STATUS
LOGICS "EP"
Table 3/d
OPEN
CLOSED
OPENING
CLOSING
STOPPED
Page 9
ENGLISH
on
off
W.L.
on
No effect
No effect
(OPEN A/B inhibited)
(OPEN A/B inhibited)
flashing light
Interrupts operation
(OPEN-A/B inhibited)
on
No effect
Interrupts operation
(OPEN-A/B inhibited)
OPENING/CLOSING SAFETIES
No effect
No effect
(OPEN-B inhibited)
(OPEN-B inhibited)
CLOSING SAFETIESOPENING SAFETIES
Interrupts operation
(OPEN-B inhibited)
No effect
No effect
off
W.L.
No effect
(OPEN A/B inhibited)
(OPEN A/B inhibited)
OPENING/CLOSING SAFETIES
(OPEN-B inhibited)
No effect
(OPEN-B inhibited)
CLOSING SAFETIESOPENING SAFETIES
on
No effect
(OPEN A/B inhibited)
No effect
(OPEN-B inhibited)
on
flashing light
Interrupts operation
Interrupts operation
(OPEN-A/B inhibited)
(OPEN-A/B inhibited)
No effect
(OPEN-B inhibited)
Interrupts operation
on
No effect
(OPEN A/B inhibited)
W.L.
No effect
OPENING/CLOSING SAFETIES
No effect
(OPEN-B inhibited)
CLOSING SAFETIES
Interrupts operation
on
off
flashing light
No effect
(OPEN A/B inhibited)
(OPEN A/B inhibited)
(OPEN-B inhibited)
Interrupts operation
(OPEN-A/B inhibited)
(OPEN-B inhibited)
Interrupts operation
(OPEN-B inhibited)
Interrupts operation
on
Interrupts operation
(OPEN-A/B inhibited)
W.L.
No effect (OPEN inhibited)
OPENING/CLOSING SAFETIESCLOSING SAFETIESOPENING SAFETIES
No effect
No effect off
on
on
flashing light
Stops closing and, when disengaged, opens
Freezes pause until disengagement (*1) (OPEN inhibited)
See paragraph 1.3
on
continues to open
Stops opening and, when disengaged,
No effect (OPEN inhibited)
No effect
PULSES
STOP
No effect
No effect
(OPEN-A inhibited)
No effect
(OPEN A/B inhibited)
OPEN-B
Closes the leaf/leaves
OPEN-A
Opens the leaf/leaves
No effect
(OPEN-A inhibited)
Stops
No effect
(OPEN A/B inhibited)
No effect
Closes the leaf/leaves
No effect
Opens the leaf/leaves
No effect
(OPEN-A inhibited)
(OPEN-A inhibited)
Interrupts operation
No effect
(OPEN A/B inhibited)
No effect
Closes leaves or 1 leaf
No effect
Opens leaves or 1 leaf
No effect
No effect
No effect
(OPEN-A inhibited)
(OPEN-A inhibited)
No effect
(OPEN-A inhibited)
(OPEN-A inhibited)
Interrupts operation
HOLD-TO-RUN CONTROLS
OPENING PULSE/HOLD TO RUN CONTROL
STOP
No effect
(OPEN A/B inhibited)
OPEN-B
Closes the leaf/leaves
OPEN-A
Opens the leaf/leaves
Stops
No effect
(OPEN A/B inhibited)
No effect
Closes the leaf/leaves
No effect
Opens the leaf/leaves
No effect
(OPEN A/B inhibited)
No effect
Closes leaves or 1 leaf
No effect
Opens leaves or 1 leaf
No effect
(OPEN-A inhibited)
OPENING SAFETIES
STOP
No effect
(OPEN A/B inhibited)
OPEN-B
Closes the leaf/leaves
OPEN-A
Opens the leaf/leaves
No effect
No effect
(OPEN-A inhibited)
No effect
(OPEN A/B inhibited)
No effect
Closes the leaf/leaves
No effect
Opens the leaf/leaves
PULSES
(OPEN-A inhibited)
Interrupts operation
Stops
No effect
No effect
No effect
No effect (OPEN inhibited)
No effect (OPEN inhibited)
STOP
OPEN-B
OPEN-A
pause time
after pause time
Opens single leaf and re-closes
It controls the re-counting of the
pause time
Opens leaves and
recloses after pause time
It controls the re-counting of the
No effect
Stops opening and, when disengaged, closes
Stops
No effect (OPEN inhibited)
Closes the leaf/leaves
If held, it remains in pause (timer function).
Reopens leaves immediately Reopens leaf immediately
GATE STATUS
LOGICS "B"
Table 3/e
CLOSED
OPEN
CLOSING
OPENING
STOPPED
Table 3/f
CLOSED
GATE STATUS
LOGICS "B/C"
OPEN
CLOSING
OPENING
16
STOPPED
Table 3/g
CLOSED
GATE STATUS
LOGICS "C"
OPEN
CLOSING
OPENING
GATE STATUS
LOGICS "AD"
Table 3/h
CLOSED
OPEN on PAUSE
STOPPED
CLOSING
OPENING
(*1) If residual pause time is less than 5 seconds on safety disengagement, the gate closes after 5 seconds.
N.B.: Effects of other active impulse inputs are shown in brackets
Page 10
Le descrizioni e le illustrazioni del presente manuale non sono impegnative. La FAAC si riserva il diritto, lasciando inalterate le caratteristiche essenziali dell’apparecchiatura, di apportare in qualunque momento e senza impegnarsi ad aggiornare la presente pubblicazione, le modifiche che essa ritiene convenienti per miglioramenti tecnici o per qualsiasi altra esigenza di carattere costruttivo o commerciale.
The descriptions and illustrations contained in the present manual are not binding. FAAC reserves the right, whilst leaving the main features of the equipments unaltered, to undertake any modifications it holds necessary for either technical or commercial reasons, at any time and without revising the present publication.
Les descriptions et les illustrations du présent manuel sont fournies à titre indicatif. FAAC se réserve le droit d’apporter à tout moment les modifications qu’elle jugera utiles sur ce produit tout en conservant les caractéristiques essentielles, sans devoir pour autant mettre à jour cette publication.
Die Beschreibungen und Abbildungen in vorliegendem Handbuch sind unverbindlich. FAAC behält sich das Recht vor, ohne die wesentlichen Eigenschaften dieses Gerätes zu verändern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorliegenden Anleitungen, technisch bzw. konstruktiv/kommerziell bedingte Verbesserungen vorzunehmen.
Las descripciones y las ilustraciones de este manual no comportan compromiso alguno. FAAC se reserva el derecho, dejando inmutadas las características esenciales de los aparatos, de aportar, en cualquier momento y sin comprometerse a poner al día la presente publicación, todas las modificaciones que considere oportunas para el perfeccionamiento técnico o para cualquier otro tipo de exigencia de carácter constructivo o comercial.
para la naturaleza
100% papel reciclado
ist umweltfreundlich
100% Altpapier
FAAC per la natura
La presente istruzione è realizzata al 100% in carta riciclata.
Non disperdete nell'ambiente gli imballaggi dei componenti dell'automazione bensì selezionate i vari materiali (es. cartone, polistirolo) secondo prescrizioni locali per lo smaltimento rifiuti e le norme vigenti.
FAAC for the environment
The present manual is produced in 100% recycled paper
Respect the environment. Dispose of each type of product packaging material (card, polystyrene) in accordance with the provisions for waste disposal as specified in the country of installation.
FAAC der Umwelt zuliebe
Vorliegende Anleitungen sind auf 100% Altpapier gedruckt.
Verpackungsstoffe der Antriebskomponenten (z.B. Pappe, Styropor) nach den einschlägigen Normen der Abfallwirtschaft sortenrein sammeln.
FAAC écologique
La présente notice a été réalisée 100% avec du papier recyclé.
Ne pas jeter dans la nature les emballages des composants de l’automatisme, mais sélectionner les différents matériaux (ex.: carton, polystyrène) selon la législation locale pour l’élimination des déchets et les normes en vigueur.
FAAC por la naturaleza.
El presente manual de instrucciones se ha realizado, al 100%, en papel reciclado.
Los materiales utilizados para el embalaje de las distintas partes del sistema automático (cartón, poliestireno) no deben tirarse al medio ambiente, sino seleccionarse conforme a las prescripciones locales y las normas vigentes para el desecho de residuos sólidos.
FAAC S.p.A.
Via Benini, 1 40069 Zola Predosa (BO) - ITALIA Tel.: 051/6172411 - Tlx.: 521087 Fax: 051/758518
pour la nature
papier recyclé 100%
for nature
recycled paper 100%
Timbro del Rivenditore:/Distributor’s Stamp:/Timbre de l’Agent:/ Fachhändlerstempel:/Sello del Revendedor:
per la natura
732260 - Rev. D - 11000 - 697 - M
carta riciclata 100%
Loading...