Endress+Hauser NMS80 Specifications

TI01248G/00/EN/04.18 71411297 2018-07-13
Products
Solutions Services
Technical Information
Proservo NMS80
Tank Gauging
Application
Proservo NMS8x Series intelligent tank gauges are designed for high accuracy liquid level measurement in storage and process applications. They fulfill the exacting demands of tank inventory management, inventory control, custody transfer, loss control, total cost saving, and safe operation.
Typical areas of application
• Precise level, interface, and density measurement of oil (fuels), petrochemical, chemical, and alcohol
Your benefits
• SIL2 certified (Min, Max, Continuous level)
• SIL3 (in preparation)
• Measures liquid level to an accuracy of +/- 0.4 mm (0.016 in)
• Measurement of up to two interface levels and density of up to three liquid phases
• Liquid density profiling of up to 50 points throughout the tank or upper layer, configurable.
• Wetted parts are completely separated from the electronic circuit
• Tank top mounting with 3” flange
• Wide range of output signals including V1, Modbus RS 485, and HART protocol
• Material and pressure rating of the wetted parts can be selected.
• Suitable for atmospheric and high pressure applications up to 6 bar/600 kPa/ 87 psi
• Integration of e.g. temperature, water level, pressure, overfill prevention sensor
• Direct connection of spot or average temperature sensor
• Robust IP66/68, NEMA Type 4x/6P enclosure
• Operation and display in a wide variety of local languages
• Easy commissioning, maintenance, and diagnostics via FieldCare

Table of contents

Proservo NMS80
Document information ....................... 3
Symbols .................................... 3
Function and system design ................... 5
Measuring principle ............................ 5
Integration of tank sensors ....................... 6
Measuring system ............................ 15
Input/output .............................. 16
Level measurement ........................... 16
HART Ex ia/IS active input ...................... 17
I/O modules ................................ 18
Power supply ............................. 24
Terminal assignment .......................... 24
Sources for gauge commands ..................... 24
Supply voltage .............................. 26
Cable entries ............................... 27
Cable specification ............................ 27
Overvoltage protection ......................... 27
Performance characteristics .................. 28
Reference operating conditions ................... 28
Measured value resolution ...................... 28
Maximum measured error ....................... 28
Hysteresis ................................. 29
Repeatability ............................... 29
Linearity .................................. 29
Long-term drift .............................. 29
Influence of ambient temperature ................. 29
Influence of medium temperature .................. 29
Influence of medium pressure .................... 29
Effect of gas phase ............................ 29
Installation ............................... 30
Requirements ............................... 30
Environment .............................. 37
Ambient temperature range ..................... 37
Classification of environmental conditions according to
DIN EN 60721-3-4 ........................... 37
Storage temperature .......................... 37
Humidity .................................. 37
Degree of protection .......................... 37
Electromagnetic compatibility (EMC) ............... 37
Mechanical construction .................... 41
Dimensions ................................ 41
Weight ................................... 41
Materials .................................. 42
Operability ............................... 43
Operating concept ............................ 43
Operating options ............................ 43
Local operation .............................. 43
Remote operation ............................ 44
Operation via service interface .................... 44
Certificates and approvals ................... 45
CE mark ................................... 45
RCM-Tick marking ............................ 45
Ex approval ................................ 45
Single seal according to ANSI/ISA 12.27.01 ........... 45
Functional Safety (SIL) ......................... 45
WHG ..................................... 45
Weight & Measure approval ..................... 45
Non-ionizing radiation protection .................. 45
CRN approval ............................... 45
Test, certificate .............................. 46
Other standards and guidelines ................... 46
Ordering information ....................... 47
Ordering information .......................... 47
Marking .................................. 47
Shipping condition ............................ 47
Application packages ....................... 48
Advanced tank measurement methods .............. 48
Accessories ............................... 51
Device-specific accessories ...................... 51
Communication-specific accessories ................ 54
Service-specific accessories ...................... 54
System components ........................... 54
Documentation ............................ 55
Technical Information (TI) ...................... 55
Brief Operating Instructions (KA) .................. 55
Operating Instructions (BA) ..................... 55
Description of Device Parameters (GP) ............... 55
Safety instructions (XA) ........................ 56
Process .................................. 38
Process temperature range ...................... 38
Process pressure range ......................... 38
Medium density ............................. 38
Medium density difference for interface measurement .... 39
Viscosity .................................. 39
Registered trademarks ...................... 57
Custody transfer approval ................... 40
2 Endress+Hauser
Proservo NMS80
DANGER
WARNING
CAUTION
NOTICE
A

Document information

Symbols Safety symbols

Symbol Meaning
Electrical symbols
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in personal injury.
Symbol Meaning
Direct current
Alternating current
Direct current and alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential equalization line or a star grounding system depending on national or company codes of practice.
Symbols for certain types of information
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
Reference to page
Reference to graphic
Visual inspection
Endress+Hauser 3
Symbols in graphics
1.
-
.
Symbol Meaning
1, 2, 3 ... Item numbers
, 2., 3.… Series of steps
A, B, C, ... Views
A-A, B-B, C-C, ... Sections
Symbols at the device
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables.
Proservo NMS80
Hazardous area
Indicates a hazardous area.
Safe area (non-hazardous area)
Indicates the non-hazardous area.
4 Endress+Hauser
Proservo NMS80
CPU
1
2
3
4
4
5
6
7
8
AB
C

Function and system design

Measuring principle

NMS8x is an intelligent tank gauge for measuring liquid levels with high precision. The system is based on the principle of gauging displacement.
A small displacer is accurately positioned in a liquid medium using a stepping motor. The displacer is then suspended on a measuring wire which is wound onto a finely grooved wire drum. NMS8x counts the rotations of the wire drum and to calculate the traveling distance of the wire and obtain the liquid level change.
The drum is driven via coupling magnets that are completely separated by the drum housing. Outer magnets are connected to the wire drum, with inner magnets connected to the drive motor. As the inner magnets turn, their magnetic attraction causes the outer magnets to turn, as well, causing the entire drum assembly to turn. The weight of the displacer on the wire creates torque on the outer magnets generating change of magnetic flux. These changes generated in the drum assembly are detected by a unique electromagnetic transducer on the inner magnets. The transducer transmits the weigh signal to a CPU using a non contact principle (patented). The drive motor is actuated to keep the weigh signal constant at set value defined by the operating command.
When the displacer is lowered and touches a liquid, the weight of the displacer is reduced by liquid buoyancy force, which is measured by a temperature-compensated magnetic transducer. As a result, the torque in the magnetic coupling changes, and this is measured by six hall sensors. A signal indicating the weight of the displacer is sent to the motor control circuit. As the liquid levels rise and fall, the displacer position is adjusted by the drive motor. The rotation of the wire drum is continuously evaluated to determine the level value using a magnetic rotary encoder. In addition to gauging the level, NMS8x can measure the interfaces between up to three liquid phases, and the tank bottom, as well as spot and profile densities.
 1 Operating principle
A Displacer position data B Weight data 1 Encoder 2 Motor 3 Rotary transformer 4 Shafts 5 Gears 6 Wire drum 7 Measuring wire 8 Displacer
Endress+Hauser 5
A0026724
Proservo NMS80
3
4
4
3
2
2
1
1
HART
A
B
HART
HART
4...20mA

Integration of tank sensors

In addition to measuring the level, interfaces, tank bottom, and density, the device can also be used to integrate of tank sensors into tank inventory systems. All measured and calculated values can be displayed on the built-in display. They can be transferred to an inventory control system via a field communication protocol.
A0026722
 2 Measuring system
A HART multidrop mode B HART and analog mode 1 Pressure transmitter 2 Average temperature transmitter (NMT53x) 3 Proservo NMS8x 4 Field protocol transmits data to an inventory control system
Typical values measured by the sensors are:
• Level
• Spot temperature
• Average temperature
• Water level
• Pressure
• Secondary level value (for critical applications)
Major applications
The number of measuring functions and output options, as well as the compact design, enables NMS8x to be installed in a wide range of applications at minimal cost.
Petroleum industry
From oil production to storage at an oil depot, there exists an extensive need to measure and manage a wide variety of products. Remote tank gauging by NMS8x combined with an inventory management system is an ideal way to measure and manage tank contents.
Chemical industry
A wide choice of options for the wetted parts ensures chemical compatibility and long product life.
Power plant
Fuel oil levels are major applications where precise measurement is required to ensure safe operation.
6 Endress+Hauser
Proservo NMS80
B
2
3
4
5
6
1
4
5
6
A
1
3
3
4
5
C
6
1
Typical tank installation
 3 Typical tank installation
A Fixed roof tank B High pressure tank C Floating roof tank with stilling well 1 NMS8x 2 Ball valve 3 Measuring wire 4 Displacer 5 Stilling well 6 Prothermo NMT53x
A0026725
When installing NMS8x to a floating roof tank, be sure to use a stilling well to protect the measuring wire. Otherwise the wire may break due to an external shock.
Application
NMS8x is primarily a highly accurate level measurement gauging instrument with the added ability to measure density. The following level measurements are supported: liquid surface level and interface level(s) between different liquids, as well as finding tank floor or datum plate. The
Endress+Hauser 7
Proservo NMS80
2
1
3
7
6
5
4
following density measurements are supported: single-point (spot measurements), as well as profile measurements of all liquid(s) in a tank.
The choice of the most suitable displacer depends on the liquid conditions and measurement functions. These can be classified as follows:
• Single measurement value only, e.g. level, interface, or density
• Multiple measurement application, e.g. level, interface, and density
Measurement terminology
 4 NMS8x with standard level, I/F x 2, Tank bottom and spot density x 3 measurement
1 Upper density 2 Middle density 3 Lower density 4 Tank bottom 5 Lower I/F 6 Upper I/F 7 Level
8 Endress+Hauser
A0026727
Proservo NMS80
4
3
1
BA
2
5
C
6
A0026728
 5 Density Profile measurement
A Tank profile: density profiling throughout tank B Interface profile: density profiling withing upper phase C Manual profile: density profiling from a specific position to level 1 Level 2 Manual profile level 3 Upper phase (oil) 4 Middle phase (emulsion) 5 Lower phase (water) 6 Tank bottom
Endress+Hauser 9
Proservo NMS80
Displacer selection guide
A wide variety of displacers are available to suit different application. Proper displacer selection ensures optimal performance and longevity. The following guidelines will assist you in selecting the most suitable displacer for your application.
Displacer types
The following NMS8x displacers are available.
30 mm (1.18 in) 50 mm (1.97 in) 70 mm (2.76 in) 110 mm (4.33 in)
316L/PTFE 316L/Alloy C/PTFE 316L 316L
A0026731 A0026732
A0026729
A0026730
10 Endress+Hauser
Proservo NMS80
A
Ø30(1.18)
a
B
86 (3.39)
Ø30(1.18)
3.6 (0.14)
121 (4.76)
165.5 (6.52)
64 (2.52)
153.6 (6.05)
185.6 (7.31)
9.5 (0.37)
a
Displacer dimensions
A0029579
A ⌀30 mm (1.18 in) 316L cylindrical displacer B ⌀30 mm (1.18 in) PTFE cylindrical displacer a Immersion point
Item
Weight (g) 261 250
Volume (ml) 84.3 118
Balance volume (ml) 41.7 59
⌀30 mm (1.18 in) 316L
cylindrical displacer
⌀30 mm (1.18 in) PTFE
cylindrical displacer
The weight, volume, and balance volume are individually determined by each displacer and also might vary depending on the values stated above.
Endress+Hauser 11
Proservo NMS80
A
B
C
Ø50.8 (2)
a
45 (1.77)
85 (3.35)
129 (5.08)
2.5 (0.09)
Ø50.8 (2)
a
45 (1.77)
2.5 (0.09)
85 (3.35)
Ø50 (1.97)
a
35 (1.38)
82.7 (3.26)
46.7 (1.84)
11.5 (0.45)
11.5 (0.45)
129 (5.08)
A ⌀50 mm (1.97 in) 316L cylindrical displacer B ⌀50 mm (1.97 in) AlloyC cylindrical displacer C ⌀50 mm (1.97 in) PTFE cylindrical displacer a Immersion point
Item
Weight (g) 253 253 250
Volume (ml) 143 143 118
Balance volume (ml) 70.7 70.7 59
⌀50 mm (1.97 in) 316L
cylindrical displacer
The weight, volume, and balance volume are individually determined by each displacer and also
⌀50 mm (1.97 in) AlloyC
cylindrical displacer
⌀50 mm (1.97 in) PTFE
cylindrical displacer
might vary depending on the values stated above.
A0029580
12 Endress+Hauser
Proservo NMS80
A
B
46.6 (1.83)
1 (0.03)
90 (3.54)
Ø70(2.76)
a
a
67 (2.64)
26 (1.02)
2 (0.07)
10 (0.39)
Ø110 (4.33)
A0029582
A ⌀70 mm (2.76 in) 316L conical displacer B ⌀110 mm (4.33 in) 316L conical displacer a Immersion point
Item ⌀70 mm (2.76 in) 316L conical displacer ⌀110 mm (4.33 in) 316L conical displacer
Weight (g) 245 223
Volume (ml) 124 108
Balance volume (ml) 52.8 36.3
The weight, volume, and balance volume are individually determined by each displacer and also might vary depending on the values stated above.
Recommended displacer by application
Application Product level Interface level Density
Viscous liquid 50 mm (1.97 in) PTFE Not Recommended Not Recommended
Crude oil 50 mm (1.97 in) 316L
50 mm (1.97 in) PTFE
Black oil 50 mm (1.97 in) 316L 50 mm (1.97 in) 316L 50 mm (1.97 in) 316L
White oil 70 mm (2.76 in) 316L 70 mm (2.76 in) 316L 70 mm (2.76 in) 316L
Liquefied gas, LPG/LNG 70 mm (2.76 in) 316L 70 mm (2.76 in) 316L 70 mm (2.76 in) 316L
Corrosive liquid
50 mm (1.97 in) Alloy C 50 mm (1.97 in) PTFE
50 mm (1.97 in) 316L 50 mm (1.97 in) PTFE
50 mm (1.97 in) Alloy C 50 mm (1.97 in) PTFE
50 mm (1.97 in) 316L 50 mm (1.97 in) PTFE
50 mm (1.97 in) Alloy C 50 mm (1.97 in) PTFE
Product level
In general, larger diameter displacers have better accuracy under similar conditions.
Interface level(s)
Cylindrical-shaped displacers, with rounded top and bottom, reduce resistance while moving through liquid(s). This provides smoother movement and faster interface measurements compared to flat­faced displacers, particularly in density profile measurements that span the full tank height.
In order to move a displacer down through liquids, the displacer density (weight divided by volume) must be higher than the liquid density.
Tank bottom and datum plate level
Endress+Hauser 13
70 mm (2.76 in) and 50 mm (1.97 in) displacers reduce resistance while moving through liquids. This provides smoother movement and faster interface measurements.
Proservo NMS80
Density
Since the density is the calculated result of two measurements, a displacer with higher volume will usually yield the most accurate density measurement. In most cases we recommend our 50 mm (1.97 in) diameter displacer for density measurement.
For non-viscous applications (e.g. white oil, LPG/LNG), the 70 mm (2.76 in) displacer also works very well.
Level and density
When an application calls for equal emphasis on measuring both level and density, the 50 mm (1.97 in) and the 70 mm (2.76 in) diameter displacers will give the best all-around performance.
Custody transfer
The 50 mm (1.97 in) displacer or larger is the choice for requirements per NMi.
The 110 mm (4.33 in), conical 316L displacer is the choice for requirements per PTB.
Material compatibility
Displacers are available in three different standard materials. Material compatibility should be confirmed to ensure safe operation and optimal NMS8x performance.
316L
Stainless steel is a highly versatile industrial material that provides good compatibility with a wide range of chemicals, including most white and black oils.
Alloy C
This high-performance material is harder than 316L, and provides excellent resistance to many of the harshest corrosive chemical applications.
PTFE
One of the most well-known and versatile polymer materials, this high-performance material has one of the lowest friction coefficients. It provides excellent performance in viscous/sticky liquids, and also has excellent chemical resistance to a wide range of corrosives.
Process connection size
The process connection defines the tank process entry, and may affect the displacer size. The standard NMS8x process connections start at 3”/DN80 and fit most tank gauging applications. Accordingly, most applications can be covered with one of the 50mm or 70mm displacer options. Smaller diameter displacers are available when the process connection is smaller.
When the 110 mm (4.33 in) diameter custody transfer approval (PTB) displacer is selected, a separate calibration and maintenance chamber is recommended between the NMS8x and tank process connection.
14 Endress+Hauser
Proservo NMS80
NXA820
NXA820
NXA820
NXA820
8
9
10
12
7
1
2
23 3 5 2 3
4 6
8
13
11
15
14

Measuring system

• From single tank level measurement to the largest oil refinery applications, Endress+Hauser tank gauging devices are an integral part of tank farm management solutions. A wide variety of data output protocols are available for seamless integration into many commonly used systems.
• A primary example is Tankvision from Endress+Hauser. Tankvision is a scalable system offering local tank management for multiple loops via Modbus or V1 protocols. Accumulated data is available to DCS and other plant management systems via a Host Link.
A0027700
 6 Integration of tank gauging devices into an inventory management system (typical example)
1 Proservo NMS8x 2 Pressure transmitter (e.g. Cerabar) 3 Temperature transmitter (e.g. Prothermo) 4 Tankside Monitor NRF81 5 Micropilot S FMR5xx 6 Micropilot NMR8x 7 Field protocol (e.g. Modbus, V1) 8 Tankvision Tank Scanner NXA820 9 Ethernet 10 Ethernet switch 11 Internet Browser 12 Tankvision Data Concentrator NXA821 13 Tankvision Host Link NXA822 14 Modbus 15 DCS or PLC
Endress+Hauser 15

Input/output

Level measurement Measured variable

Proservo is primarily a highly accurate level measurement gauging instrument, with the added ability to measure interfaces and densities. The following level measurements are supported: liquid surface level and interface level(s) between different liquids, as well as finding tank bottom or datum plate. The following density measurements are supported: single-point (called “spot” measurements), as well as profile measurements of all liquid(s) in a tank.
Measuring range
• Level and interface: Max.36 m (118 ft)(longer range is possible as special product)
• Density: 0.430 to 2.000 g/cm The level and interface measuring range depends on the measuring wire and material compatibility
to measured medium. Measuring wires are available in three different standard materials. Material compatibility should be confirmed to ensure safe operation and optimal measuring performance.
Measuring range Material
28 m (93.33 ft), 36 m (120 ft) 316L
16 m (53.33 ft) PFA > 316L
22 m (73.33 ft) AlloyC276
Proservo NMS80
3
16 Endress+Hauser
Proservo NMS80
D
E
G
F
C
B
A
1
1
1
1
1 3
2
3
2
2 4
1
HR
CDI
WP
on
SIM
22334
4
112233445566778
8
POWER
i
E
1
1
2
CDI
D
C
1 2 3 4
1 2 3 4

HART Ex ia/IS active input

A0027364
 7 HART Ex ia/IS active input
E1 HART + E2 HART -
The device has a HART Ex ia/IS active input. Additional features are provided if the following Endress+Hauser devices are connected:
Prothermo NMT
The measured level is transmitted to the Prothermo. Prothermo uses this level to calculate the average temperature of the product.
Technical data
Transmitter power supply voltage 23.0 V - 380 Ω ⋅ I
load
Maximum load 500 Ω including signal line
Maximum current of all connected devices 24 mA
The HART Ex ia/IS active input is available by default. It needs not to be chosen explicitly when ordering a device.
Endress+Hauser 17

I/O modules Overview

E
G
F
1
1
1
1 3
2
2
2 4
HR
CDI
WP
on
SIM
POWER
i
D
C
B
A
1122334
4
112233445566778
8
D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
22334
4
112233445566778
8
i
G
1
3
2
POWER
NMx8x - XX xx xxxxxx ...
040
NMx8x - xx XX xxxxxx ...
050
 8 Position of the I/O modules in the terminal compartment
The terminal compartment contains up to four I/O modules, depending on the order code.
• Modules with four terminals can be in any of these slots.
• Modules with eight terminals can be in slot B or C. The exact assignment of the modules to the slots is dependent on the device version. For a
detailed description refer to the Operating Instructions of the device in question. The following restrictions apply when selecting the modules:
• The device may contain a maximum of four I/O modules.
• A maximum of two I/O modules with 8 terminals is possible.
Proservo NMS80
A0027363
Ordering feature 040: "Primary Output"
Option Number of I/O modules Type of I/O module Number of terminals Technical data
A1 1 Modbus RS485 4 →  19
B1 1 V1 4 →  20
E1 1 4-20mA HART Ex d/XP 8 →  21
H1 1 4-20mA HART Ex i/IS 8 →  21
Ordering feature 050: "Secondary IO Analogue"
Option Number of I/O
modules
A1 1 1 x "Ex d/XP 4-20mA HART + RTD input" 1 x 8 →  21
A2 2 2 x "Ex d/XP 4-20mA HART + RTD input" 2 x 8 →  21
B1 1 1 x "Ex i/IS 4-20mA HART+ RTD input" 1 x 8 →  21
B2 2 2 x "Ex i/IS 4-20mA HART+ RTD input" 2 x 8 →  21
C2 2 1 x "Ex i/IS 4-20mA HART + RTD input"
X0 0 none 0 -
Type of I/O module Number of terminals Technical data
2 x 8 →  21
1 x "Ex d/XP 4-20mA HART + RTD input"
18 Endress+Hauser
Proservo NMS80
NMx8x - xx xx XXxxxx ...
060
Ordering feature 060: "Secondary IO Digital Exd"
Option Number of I/O modules Type of I/O module Number of terminals Technical data
A1 1 1 x "2x relay + 2x discrete I/O" 1 x 4 →  23
A2 2 2 x "2x relay + 2x discrete I/O" 2 x 4 →  23
A3 3 3 x "2x relay + 2x discrete I/O" 3 x 4 →  23
B1 1 1x "Modbus RS485" 1 x 4 →  19
B2 2 1x "Modbus RS485"
1 x "2x relay + 2x discrete I/O"
B3 3 1x "Modbus RS485"
2 x "2x relay + 2x discrete I/O"
X0 0 none 0 -
2 x 4 →  19
→  23
3 x 4 →  19
→  23
"Modbus RS485": Technical data
No. of units Maximum 15 instruments per loop
Baud rate Selectable:
• 600 bit/s
• 1 200 bit/s
• 2 400 bit/s
• 4 800 bit/s
• 9 600 bit/s
• 19 200 bit/s
Parity Selectable:
• Odd
• Even
• None
Cable Three-wire cable with screening. The screening must be connected inside the housing.
Termination resistors To be set as required in specific environments
Topology • Serial bus
• Tree structure
Transmission distance Maximum 1 200 m (3 900 ft) including limbs or branches;
branches under 3 m (9.8 ft) are negligible
Instrument address Each transmitter has an individual bus address configured in the software of the
transmitter.
Isolation Bus inputs are electrically isolated from the other electronics.
Error on alarm Error message classified according to NAMUR NE 107
Endress+Hauser 19
Proservo NMS80
"V1": Technical data
No. of units Maximum 10 instruments per loop
Baud rate 3 300 bit/s
Parity Selectable:
• Odd
• Even
• None
Cable • Two-wire twisted pair; screening recommended
• Two-wire unscreened
Termination resistors Not required
Topology • Serial bus
• Tree structure
Transmission distance Maximum 6 000 m (19 700 ft)
Instrument address Each transmitter has an individual bus address configured in the software of the
transmitter.
Isolation Serial communication circuit isolated from other circuits
Error on alarm Error message classified according to NAMUR NE 107
20 Endress+Hauser
Proservo NMS80
"4-20mA HART" I/O module (Ex d/XP or Ex i/IS): Technical data
General data
No. of units Max. 6 instruments per loop
Baud rate 1 200 bit/s
Cable Two-wire, twisted pair screened cable;
Core cross section: 0.2 to 2.5 mm2 (24 to 13 AWG)
Topology • Serial bus
• Tree structure
Transmission distance Maximum 1 200 m (3 900 ft)
Instrument address Each transmitter on a signal loop has an individual bus address. This is defined within
the transmitter software and / or auxiliary configuration environment such as host system or Field Communicator 475.
Isolation Bus inputs are electrically isolated from the other electronics
Input data
Input operating modes • 4..20mA input (1 external device)
• HART master+4..20mA input (1 external device)
• HART master (up to 6 external devices)
Internal load (to ground) 400 Ω
Measuring range 0 to 26 mA
Accuracy ±15 µA (after linearization and calibration)
Connection of a Prothermo NMT The measured level is transmitted to the Prothermo. Prothermo uses this
level to calculate the average temperature of the product.
Connection of a RTD temperature probe
2-, 3- or 4-wire connection
Output data
Output operating modes • 4..20mA output
• HART slave +4..20mA output
Output current 3 to 24 mA
Accuracy ±15 µA (after linearization and calibration)
Error on alarm HART error message classified according to NAMUR NE 107
Endress+Hauser 21
Data for passive usage (input or output)
D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
22334
4
112233445566778
8
i
G
1
3
2
POWER
-
+
!
E
G
F
1
1
1 3
2
2 4
HR
CDI
WP
on
SIM
i
D
C
B
A
1122334
4
112233445566778
8
G
1
3
2
POWER
D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
22334
4
112233445566778
8
i
G
1
3
2
POWER
-
+
E
G
F
1
1
1 3
2
2 4
HR
CDI
WP
on
SIM
i
D
C
B
A
1122334
4
112233445566778
8
G
1
3
2
POWER
 9 Passive input or output: Use terminals 1 and 2
Minimum terminal voltage 10.4 V
Maximum terminal voltage 29 V
Proservo NMS80
A0033030
1)
1)
1) Observing these values is mandatory in order to ensure correct measured value information.
Data for active usage (input or output)
 10 Active input or output: Use terminals 2 and 3
Transmitter power supply voltage (Ex d/XP)
Transmitter power supply voltage (Ex i/IS)
Output load max. 500 Ω including signal line
18.5 V - 360 Ω ⋅ I
20.0 V - 360 Ω ⋅ I
load
load
1)
A0033031
22 Endress+Hauser
1) Observing this value is mandatory in order to ensure correct measured value information.
Proservo NMS80
"Digital I/O module": Technical data
Output
Relay switching power for resistive load • 30 VDC @ 2 A
• 250 VDC @ 0.1 A
• 250 VAC @ 2 A
Relay type normally open;
can be set to "normally closed" by a software option
Input
Maximum pick-up voltage • 250 V
Minimum pick-up voltage • 25 V
• 250 V
• 5 V
DC
AC
DC
AC
Current consumption at maximum voltage • ≤ 1 mA (DC)
• ≤ 2 mA (AC)
1) In case of a power supply failure, the switching state is always "open", irrespectiv of the selected software option.
1)
Endress+Hauser 23

Terminal assignment

D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
22334
4
112233445566778
8
i
G
1
3
2
POWER
D
E
F
C
B
A
1
1
1
1 3
2
2 4
1
HR
CDI
WP
on
SIM
22334
4
112233445566778
8
i
G
1
3
2
POWER
G1 N G3 L
AC 85...264 V
Proservo NMS80

Power supply

A0026905
 11 Terminal compartment (typical example) and ground terminals
Terminal area Module
Up to four I/O modules, depending on the order code
A/B/C/D (slots for I/O modules)
• Modules with four terminals can be in any of these slots.
• Modules with eight terminals can be in slot B or C.
The exact assignment of the modules to the slots is dependent on the device version.
For a detailed description refer to the Operating Instructions of the device in question.
E HART Ex i/IS interface
• E1: H+
• E2: H-
F Remote display
• F1: VCC (connect to terminal 81 of the remote display)
• F2: Signal B (connect to terminal 84 of the remote display)
• F3: Signal A (connec t to terminal 83 of the remote display)
• F4: Gnd (connect to terminal 82 of the remote display)
Power consumption: 28.8 VA
Power supply: 85 to 264 V
G
• G1: N
1)
AC
• G2: not connected
• G3: L
Protective ground connection (M4 screw)
A0018339
1) Maximum power varies depending on the configuration of the modules. As the value of 28.8 VA shows maximum apparent power, select the applicable cables accordingly. The actual consumed effective power is 12 w.

Sources for gauge commands

Gauge commands can be sent via various sources.
• Displays or CDI (e.g. FieldCare)
• Digital input (e.g. switch)
• Fieldbus (Modbus, V1, HART)
The last received gauge command via any sources will be executed as usual.
During calibration, gauge commands are not accepted from any sources.
24 Endress+Hauser
Proservo NMS80
X X X
X X
X X
X
X
mm
INST
LIFT
STOP OFF
NXA820
1
2
3
A0029538
1 Display operation 2 Digital input (e.g. switch) 3 Tankvision
Gauge command priorities
The priority of the gauge command for NMS8x is very simple. The last received gauge command via any sources will be executed to take of the former gauge command. However the priority varies depending on the devices. When replacing the device with the NMS8x, check the priorities shown below.
NOTICE
Undesired gauge command will be executed.
If the setting is not changed, an undesired gauge command will be executed (e.g. Level command via Fieldbus would overwrite Stop command for maintenance.).
If the system has been automatically or semi-automatically programmed for operation,
maintenance or other purposes, the setting should be changed corresponding to use.
Proservo NMS8x
By display From digital input From Fieldbus
Command Priority Command Priority Command Priority
Level 1 Level 1 Level 1
Interface 1 Interface 1 Interface 1
Tank bottom 1 Tank bottom 1 Tank bottom 1
Spot density 1 Spot density 1 Spot density 1
Profile density 1 Profile density 1 Profile density 1
Up 1 Up 1 Up 1
Stop 1 Stop 1 Stop 1
Endress+Hauser 25
Proservo NMS80
Proservo NMS5/NMS7
By display From NRF560 From digital input From Fieldbus
Command Priority Command Priority Command Priority Command Priority
Level 4 Level 4 Level 4 Level 4
Interface 2 Interface 3 Interface 1 Interface 4
Tank bottom 2 Tank bottom 3 N/A N/A Tank bottom 4
Spot density 2 Spot density 3 N/A N/A Spot density 4
Profile density 2 Profile density 3 N/A N/A Profile density 4
Up 2 Up 3 Up 1 Up 4
Stop 2 Stop 3 Stop 1 Stop 4
Servo level gauge TGM5
By display From NRF560 From DRM9700 From digital input From Fieldbus
Command Priority Command Priority Command Priority Command Priority Command Priority
Level 4 Level 4 Level 4 Level 4 Level 4
Interface 2 Interface 3 N/A N/A N/A N/A Interface 4
Tank bottom
Spot density 2 Spot density 3 N/A N/A N/A N/A Spot density 4
Profile density
Up 2 Up 3 Up 1 Up 1 Up 4
Stop 2 Stop 3 N/A N/A Stop 1 Stop 4
2 Tank
bottom
2 Profile
density
3 N/A N/A N/A N/A Tank
bottom
3 N/A N/A N/A N/A Profile
density
4
4

Supply voltage

Servo level gauge TGM4000
By display From DRM9700 From digital input From Fieldbus
Command Priority Command Priority Command Priority Command Priority
Level 4 Level 4 Level 4 Level 4
Interface 2 Interface 1 N/A N/A Interface 4
Tank bottom 2 N/A N/A N/A N/A Tank bottom 4
Spot density 2 N/A N/A N/A N/A Spot density 4
Profile density 2 N/A N/A N/A N/A Profile density 4
Up 2 Up 1 Up 1 Up 4
Stop 2 Stop N/A Stop 1 Stop 4
85 to 264 VAC, 50/60 Hz, 28.8 VA
1)
1) maximum value; actual value depending on modules installed. 28.8 VA includes the nominal power and the cabling specification has to meet this value. On the other hand, the effective power consumption is 12 W.
26 Endress+Hauser
Proservo NMS80

Cable entries

Ordering feature 090 "Electrical Connection"
A 7 x thread M20
B 7 x thread M25
C 7 x thread G1/2
D 7 x thread G3/4
E 7 x thread NPT1/2
F 7 x thread NPT3/4
1) Position 13 of the order code, e.g. NMx8x-xxxxxxxxxxxxA...
For the following devices with TIIS Ex d approval, cable glands are attached to the device (see position 1 and 2 of the order code). These cable glands must be used. Proservo NMS80-TC...

Cable specification Terminals

Terminal Wire cross section
Signal and power supply
• Spring terminals (NMx8x-xx1...)
• Screw terminals (NMx8x-xx2...)
Ground terminal in the terminal compartment max. 2.5 mm2 (13 AWG)
Ground terminal at the housing max. 4 mm2 (11 AWG)
1)
Cable entries (with blind plugs)
0.2 to 2.5 mm2 (24 to 13 AWG)

Overvoltage protection

Power supply line
Standard device cable is sufficient for the power line.
HART communication line
• Standard device cable is sufficient if only the analog signal is used.
• Shielded cable is recommended if using the HART protocol. Observe the grounding concept of the plant.
Modbus communication line
• Observe the cable conditions from the TIA-485-A, Telecommunications Industry Association.
• Additional conditions: Use shielded cable.
V1 communication line
• Two wire (twisted pair) screened or un-screened cable
• Resistance in one cable: ≤ 120 Ω
• Capacitance between lines: ≤ 0.3 µF
On the communication and power lines; according to IEC 60060-1 /DIN 60079-14:
10 kA, 8/20 μs, 10 pulses according to IEC 60060-1 / DIN 60079-14
Endress+Hauser 27

Performance characteristics

Proservo NMS80

Reference operating conditions

Measured value resolution

Maximum measured error

According to OIML R85
Level and interface ≤ 0.1 mm (0.004 in)
Density
Level ±0.4 mm (±0.016 in) Reference condition
Interface ±2 mm (±0.08 in) Reference condition
Tank bottom ±2 mm (±0.08 in) Reference condition
Density ±0.003 g/cm
≤ 0.001 g/cm
3
Accuracy of NMi approved calibration rig at Endress +Hauser Yamanashi according to the combination of the order code is as per the table below.
• Standard displacer 70 mm (2.76 in)
• Density difference 0.2 g/cm3 or more (min. detectable density difference for interface measurement is 0.1 g/cm
• Max. performance selected in feat.150
• Standard displacer 70 mm (2.76 in)
• Flat datum plate or flat tank bottom
• Max. performance selected in feat.150
3
Reference condition
• Standard displacer 50 mm (1.97 in) or 70 mm (2.76 in)
• On-site density calibration (offset)
• Max. performance selected in feat.150
3
The following values are valid for a level measurement distance up to 40 m (133.33 ft).
Displacer (ordering feature 120)
1AC, 2AC, 3AC,
4AC, 5AC
⌀50 mm (1.97 in)
Accuracy
±1 mm
(±0.04 in)
±1 mm
(±0.04 in)
±1 mm
(±0.04 in)
±0.6 mm
(±0.024 in)
±1 mm
(±0.04 in)
1BE, 4AE 1BJ
⌀70 mm (2.76 in)
±1 mm
(±0.04 in)
±1 mm
(±0.04 in)
±1 mm
(±0.04 in)
±0.4 mm
(±0.016 in)
±1 mm
(±0.04 in)
Ordering
feature 150
ICR Standard version, w/o
ICW Standard version, 3-point
ICX Standard version, 5-point
NTA Maximum performance,
NTC Custody transfer type
Weight and measure
approval
calibration certificate
calibration certificate
calibration certificate
NMi type approval acc. OIML R85, API 3.1B, ISO 4622, factory calibration certificate
approval acc. NMi OIML R85, API 3.1B, ISO4622, factory calibration certificate
1AA, 2AA
⌀30 mm (1.18 in)
±2.5 mm (±0.1 in)
±2.5 mm (±0.1 in)
±2.5 mm (±0.1 in)
N/A
N/A
⌀110 mm
(4.33 in)
±1 mm
(±0.04 in)
±1 mm
(±0.04 in)
±1 mm
(±0.04 in)
±0.4 mm
(±0.016 in)
±1 mm
(±0.04 in)
28 Endress+Hauser
Proservo NMS80
Ordering
feature 150
PTA Maximum performance,
PTC Custody transfer type
Weight and measure
approval
PTB type approval factory calibration certificate
approval per PTB, factory calibration certificate
1AA, 2AA
⌀30 mm (1.18 in)
N/A
N/A
Displacer (ordering feature 120)
1AC, 2AC, 3AC,
4AC, 5AC
⌀50 mm
(1.97 in)
±0.6 mm
(±0.024 in)
±1 mm
(±0.04 in)
1BE, 4AE 1BJ
⌀70 mm (2.76 in)
Accuracy
±0.4 mm
(±0.016 in)
±1 mm
(±0.04 in)
⌀110 mm
(4.33 in)
±0.4 mm
(±0.016 in)
±1 mm
(±0.04 in)

Hysteresis

Repeatability

Linearity

Long-term drift

Influence of ambient temperature

Influence of medium temperature

Influence of medium pressure

Effect of gas phase

Within the specified accuracy (+/- 1 mm (0.039 in)) according to OIML R85 (2008)
It can be reduced by non hysteresis measurement mode.
0.1 mm (0.004 in)
Within maximum measured error
Within the specified error of measurement
Within the specified accuracy according to OIML R85 (2008)
None (Displacer principle is not influenced by medium temperature.)
No influence of medium pressure to the measuring principle.
No effect of gas phase to the measuring principle.
Endress+Hauser 29

Installation

Requirements Type of tanks

Depending on the type of tank and application, different installation procedures are recommended for NMS8x.
Type of tanks Without guide system With stilling well With guide wires
Fixed roof tank
Floating roof tank
Proservo NMS80
Covered floating roof tank
Pressurized or bullet tank
Tank with agitator or heavy turbulence
• A stilling well is required in a floating roof tank and a covered floating roof tank.
• Guide wires cannot be installed in a floating roof tank. When the measuring wire is exposed to free space, it may break due to an external shock.
• Installing guide wires is not allowed in pressurized tanks because the wires would prevent closing the valve for replacing the wire, wire drum, or displacer. NMS8x installation position is important for applications without the guide wire system in order to prevent the measuring wire from being broken (refer to Operating Instructions for details ).
30 Endress+Hauser
Proservo NMS80
L
1
L
2
L
1
L
2
A
B
L
3
L
3
D
2
D
1
d
r
D
1
d
D
2
p (L )x
Mounting with a stilling well
The stilling well diameter that is required to protect the measuring wire without disturbing its operation varies depending on the tank height. The stilling well could either be of constant diameter, or narrower at its upper part and wider at its lower part. The following figure shows two examples of the latter case, namely a concentric stilling well and an asymmetric stilling well.
A0029577
 12 Mounting with concentric stilling well
A Front view B Side view L1Length from the center of the calibration window to the upper part of the stilling well
L2Length from the center of the calibration window to the bottom of the stilling well L3Length from the center of the calibration window to the bottom of the flange D1Diameter of upper part of stilling well D2Diameter of stilling well d Diameter of displacer
p
Longitudinal wire position from the center of the flange (Lx) r Radial direction offset
Endress+Hauser 31
Proservo NMS80
L
1
L
2
L
1
L
2
A
B
L
3
L
3
D
2
D
1
d
r
D
1
d
D
2
p (L )x
A0029576
 13 Mounting with asymmetric stilling well
A Front view B Side view L1Length from the center of the calibration window to the upper part of the stilling well
L2Length from the center of the calibration window to the bottom of the stilling well L3Length from the center of the calibration window to the bottom of the flange D1Diameter of upper part of stilling well D2Diameter of stilling well d Diameter of displacer
p
Longitudinal wire position from the center of the flange
r Radial direction offset
(Lx)
• L3: length from center of the calibration window to the bottom of the flange (77 mm (3.03 in) + flange thickness). For JIS 10K 150A RF, the flange thickness is 22 mm (0.87 in).
• When using an asymmetric stilling well, take into account the lateral shift of the displacer and follow the NMS8x mounting direction as shown in the figure.
• To calculate the required stilling well diameters, the formula below should be used. The following tables contain the necessary parameters in order to calculate the dimensions of the stilling well. Be sure to have appropriate dimensions of the stilling well according to each dimension in the table.
• The radial direction offset (r) is required for only the 47 m (154.20 ft) and 55 m (180.45 ft) wire drum. For all other drums, the offset is 0 mm/in.
32 Endress+Hauser
Proservo NMS80
Feature: 110 Description
(Measuring range; Wire;
Diameter)
G1
H1
Feature: 120 Description
1AA 316L; 30 mm (1.18 in) cylindrical 30 mm (1.18 in)
1AC 316L; 50 mm (1.97 in) cylindrical 50 mm (1.97 in)
1BE 316L; 70 mm (2.76 in) conical 70 mm (2.76 in)
1BJ 316L;110 mm (4.33 in) conical 110 mm (4.33 in)
2AA PTFE; 30 mm (1.18 in) cylindrical 30 mm (1.18 in)
2AC PTFE; 50 mm (1.97 in) cylindrical 50 mm (1.97 in)
3AC AlloyC276; 50 mm (1.97 in)
4AC 316L polished; 50 mm (1.97 in)
4AE 316L polished; 70 mm (2.76 in)
5AC PTFE; 50 mm (1.97 in) cylindrical,
47 m (154.20 ft); 316L;
0.15 mm (0.00591 in)
55 m (180.45 ft); 316L
0.15 mm (0.00591 in)
(Displacer material; Type)
cylindrical
cylindrical
conical
hygienic white
NMS80 NMS81 NMS83 r
6 mm (0.24 in)
6 mm (0.24 in)
NMS80 NMS81 NMS83 d
50 mm (1.97 in)
50 mm (1.97 in)
70 mm (2.76 in)
50 mm (1.97 in)
Parameter Description
d Diameter of displacer
p(Lx) Longitudinal wire position from the center of the flange
The value can be determined by using following graph.
r Radial direction offset
s Safety factor recommended: 5 mm (0.197 in)
The following graph shows the lateral shift of the displacer depending on the measured distance for the different wire drums.
Endress+Hauser 33
Proservo NMS80
L , L (mm) ( )
1 2
in
p (Lx) (mm) ( )in
-1.4 -1.3 -1.2 -1.1 -1.0 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
0 2000 4000 6000 8000
10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000 32000 34000 36000 38000 40000 42000 44000 46000 48000 50000 52000 54000 56000
-36 -32 -28 -24 -20 -16 -12 -8 -4 0 4 8
a
d
e
c
b
f
 14 Lateral shift of displacer according to measurement range
a 16 m (A3) (NMS80/NMS81/NMS83) b 22 m (C2) (NMS80/NMS81/NMS83) c 28 m (D1) (NMS80/NMS81) d 36 m (F1) (NMS80/NMS81) e 47 m (G1) (NMS81) f 55 m(H1) (NMS81)
Upper diameter of stilling well
The dimension of D1 has to be the largest value of the dimensions D1a, D1b , D1c, and D1d according to the following formula.
34 Endress+Hauser
D1 Dimension
(Example)
>68.1 mm
(2.68 in)
D
Dimension
1x
Example Parameter
68.1 mm (2.68 in)
65.6 mm (2.58 in)
D
1a
D
1b
Description Formula
D1 dimension when the displacer is at the center of the calibration window
D1 dimension when the displacer is at the upper part of the stilling well
= 2 x ( |p (0)|+ d/2 + s)
= 2 x (|p (L1)|+ d/2 + s)
A0027997
Proservo NMS80
D1 Dimension
(Example)
D
Dimension
1x
Example Parameter
50.9 mm (2.00 in)
D
1c
D
1d
Description Formula
D1 dimension when the displacer is at the bottom of the stilling well
D1 dimension when the radial direction offset is considered. This calculation is used only with the 47 m (154.20 ft) wire drum (G1 in Feature110) and 55 m (180.45 ft) (H1 in feature
110)
= 2 x ( |p (L2)|+ s)
= 2 x (d/2 + r + s)
Example: L1 = 1 000 mm, L2 = 20 000 mm, d = 50 mm, s = 5.0, 28 m drum
Lower diameter of stilling well
The dimension of D2 has to be the larger value of the dimensions D1 and D2b .
See the table below.
Concentric pipe
D2 Dimension
(Example)
>100.9 mm
(3.97 in)
D2x Dimension
Example Parameter
68.1 mm (2.68 in)
100.9 mm (3.97 in)
D
1
D
2b
Description Formula
Calculated D1 value
D2 dimension when the displacer is in L2 length
= 2 x (|p (L2)| + d/2 + s)
Example: L2 = 20 000 mm, d = 50 mm, s = 5.0, 28 m drum
Asymmetric pipe
D2 Dimension
(Example)
>84.5 mm
(3.33 in)
D2x Dimension
Example Parameter
68.1 mm (2.68 in)
84.5 mm (3.33 in)
D
1
D
2b
Description Formula
Calculated D1 value
D2 dimension that the displacer can pass through (nth groove)
= |p (L2)| + d/2 + s + D1/2
Example: L2 = 20 000 mm, d = 50 mm, s = 5.0, 28 m drum
Recommendations for NMS8x mounting with a stilling well
Follow the recommendations for mounting NMS8x with a stilling well.
• Keep the pipe connection welds smooth.
• When drilling holes into the pipe, keep the interior surface of the holes clear of metal chips and burrs.
• Coat or paint the interior surface of the pipe to prevent corrosion.
• Keep the pipe as vertical as possible. Check using a plumb bob.
• Install the asymmetric pipe under the valve and align the centers of the NMS8x and the valve.
• Set the center of the lower part of the asymmetric pipe in the direction of the lateral motion.
• Observe the recommendations as per API MPMS chapter 3.1B.
• Confirm grounding between NMS8x and the tank nozzle.
Endress+Hauser 35
Mounting with guide wires
2
1
3
7
4
8
12
13
9
10 11
5
6
100 (3 .94)
B
D
A
C
It is also possible to guide the displacer with guide wires to prevent swinging.
Proservo NMS80
A0026819
 15 Guide wire; dimensions mm (in)
No. Description
A Calibration chamber
B Spring and sleeve
C Guide wire sleeve
D Crimp tool
1 NMS8x
2 Reducer plate
3 Spring, SUS304
4 Sleeve, SUS316
5 Calibration chamber for maintenance
6 Tank
7 Measuring wire
8 Guide wire, SUS316
9 Displacer
10 Anchor hook plate, SUS304
11 Welding point
12 Wire ring, SUS316L
13 Flange
36 Endress+Hauser
Proservo NMS80

Environment

Ambient temperature range

Classification of environmental conditions according to DIN EN 60721-3-4

Storage temperature

Humidity

Degree of protection

Electromagnetic compatibility (EMC)

Device –40 to +60 °C (–40 to +140 °F)
Display module –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside this
temperature range.
4K5, 4K6, 4B1, 4M7, 4Z2, 4Z3, 4Z8
–50 to +80 °C (–58 to +176 °F)
≤ 95 %
• IP68/66 according to DIN EN 60529
• Type 6P/4x according to NEMA 250
• Transient emissions according to DIN EN 61326, class B
• Interference resistance according to DIN EN 61326, Appendix A (Industry use) and NAMUR recommendation NE21
Endress+Hauser 37

Process

1
2
3
4
5
6
Proservo NMS80

Process temperature range

–200 to +200 °C (–328 to 392 °F)
If the specification of the tank application exceeds the range above, a special displacer can be ordered.
Process sealing
A1 HNBR –30 to 150 °C (–22 to 302 °F)
B1 FKM, GLT –40 to 150 °C (–40 to 302 °F)
C1 CR Chloropren –30 to 80 °C (–22 to 176 °F)
D1 PTFE (Wire drum FKM) –100 to 150 °C (–148 to 302 °F)
E1 VMQ silicone –40 to 200 °C (–40 to 392 °F)
A temperature difference exists between the liquid in the tank and the NMS8x on the tank nozzle due to the distance from each other. Also, the process sealing temperature of NMS8x does not show the temperature for the liquid temperature. The process sealing temperature shows the temperature of the gas that reaches inside the housing of the NMS8x. In most cases, the gas temperature is the same as the ambient temperature. If there are any temperature differences between the process sealing and the gas, install a pipe or chamber between the NMS8x and the tank nozzle to adjust the temeparature or cover the tank with a heat insulting material to control the temperature.
 16 Process sealing
1 Chamber or pipe for adjusting temperature 2 Heat insulting material 3 Measuring wire 4 Displacer 5 Tank wall 6 High or low temperature liquid

Process pressure range

Medium density

Housing type Process pressure range
Aluminum 0 to 6 bar (600 Kpa/87 psi)
0.430 to 2.000 g/cm3 (27 to 125 lb/ft3)
38 Endress+Hauser
A0028848
Proservo NMS80

Medium density difference for interface measurement

Viscosity

0.1 g/cm3 (6.24 lb/ft3)
0 to 5 000 mPa s
Endress+Hauser 39

Custody transfer approval

Proservo NMS80
Ordering feature 150 "Accuracy, Weight + Measure Approval"
ICR Standard version (±1 mm), without calibration certificate
ICW Standard version (±1 mm), 3-point calibration certificate
ICX Standard version (±1 mm), 5-point calibration certificate
LTA Maximum performance (±0.4 mm), type approval according to LNE, OIML R85, API
LTC Custody transfer (±1 mm) type approval according to NMi, OIML R85, API 3.1B,
NTA Maximum performance (±0.4 mm), type approval according to NMi, OIML R85, API
NTC Custody transfer (±1 mm) type approval according to NMi, OIML R85, API 3.1B,
PTA Maximum performance (±0.4 mm), PTB type approval, factory calibration certificate
PTC Custody transfer (±1 mm) type approval per PTB, factory calibration certificate
1) Position 25 to 27 in the order code (e.g. NMS8x-xxxxxxxxxxxxxxxxxxxxxxxxICR...)
Accuracy properties
1)
3.1B, ISO4622, factory calibration certificate
ISO4622, factory calibration certificate
3.1B, ISO4622, factory calibration certificate
ISO4622, factory calibration certificate
• Depending on the displacer (ordering feature 120) some of these versions will not be available.
• Proservo NMS8x that are certified for Custody Transfer applications are calibrated on a certified production rig. The production rig reference standard is a laser tracker with an absolute accuracy of ±0.010 mm and a resolution of 0.0002 mm. Calibration is performed at 10 equally-spaced measuring points over the full measuring range (up to 40 m (131 ft)). Additionally, hysteresis is checked at three points.
• The Maximum Permissible Error (MPE) is 0.4 mm (0.016 in) for maximum performance models, and ±1 mm (±0.04 in) for custody transfer models. The resultant factory calibration certificate is included in the scope of delivery along with the respective type approval certificate.
40 Endress+Hauser
Proservo NMS80
368 (14.49)
307 (12.09)
208.5 (8.21)
60.5
(2.38)
292.3 (11.51)
316.3 (12.45)
227.5 (8.96)
48 (1.89)
215.8 (8.5)
100.3 (3.95)
101.3 (3.99)
55 (2.17)
135 (5.31)
215.8 (8.5)
208.5 (8.21)
22
(0.87)

Dimensions

Mechanical construction

Weight

The thickness of the flange (22 mm (0.87 in)) shows the specification of the 10K 150A RF aluminium flange JIS B2220.
• Approx. 15 kg (33.0 lb) with NPS 3" Cl. 150, DN80PN10/16, 10K80A flange
• Approx. 20 kg (44.1 lb) with NPS 6" Cl. 150 flange
• Approx. 24 kg (52.9 lb) with NPS 8" Cl. 150 flange The weights vary depending on the selected options.
A0029578
Endress+Hauser 41

Materials Material of housing

1
2
3
Feature Option Housing descriptions
070 AB Transmitter + process Alu, coated
Materials of measuring wire
Feature Option Wire descriptions
110 A3 16 m (53.33 ft); PFA >316L; 0.4 mm (0.016 in)
110 C2 22 m (73.33 ft); AlloyC276; 0.2 mm (0.008 in)
110 D1 28 m (93.33 ft); 316L; 0.15 mm (0.006 in)
110 F1 36 m (120 ft); 316L; 0.15 mm (0.006 in)
110 G1 47 m (154.20 ft); 316L; 0.15 mm (0.006 in)
Material of process connection (flange)
Feature Option Descriptions of process connection (flange)
140 AFA NPS 3" Cl.150 RF, Aluminium flange ASME B16.5
140 AHA NPS 6" Cl.150 RF, Aluminium flange ASME B16.5
140 GSA DN80 PN10/16 B1, Aluminium flange EN1092-1
140 PFA 10K 80A RF, Aluminium flange JIS B2220
140 PHA 10K 150A RF, Aluminium flange JIS B2220
140 P5A 10K 80A FF, Aluminium flange JIS B2220
140 QFA 80A 150lbs RF, Aluminium flange JPI 7S-15
Proservo NMS80
A0029583
1 Housing 2 Flange 3 Measuring wire
42 Endress+Hauser
Proservo NMS80
1
E

Operability

Operating concept

Operating options

Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Operating languages
• English
• German
• Japanese Feature 500 of the product structure determines which of these languages is preset on delivery.
Quick and safe commissioning
• Guided menus ("Make-it-run" wizards) for applications
• Menu guidance with brief explanations of the individual parameter functions
Reliable operation
Standardized operation at the device and in the operating tools
Efficient diagnostics increase measurement reliability
• Remedy information is integrated in plain text
• Diverse simulation options
• Local display; operation via the local display is possible without opening the device.
• Tank Gauging system
• Plant Asset Management tool (e.g. FieldCare); connected via
– HART – Service port (CDI)

Local operation

 17 NMS80 Display
1 Display
Display elements
• 4-line display
• White background lighting; switches to red in event of device errors
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
Operating elements
• External operation via touch control; 3 optical keys:
, ,
• Operating elements also accessible in various hazardous areas
A0029584
Endress+Hauser 43

Remote operation

NXA820
5
6
4
1 2 3
7
CDI
1
2
Proservo NMS80
A0025621
 18 Remote operation of Tank Gauging devices
1 Proservo NMS8x 2 Tankside Monitor NRF81 3 Micropilot NMR8x 4 Field protocol (e.g. Modbus, V1) 5 Tankvision Tank Scanner NXA820 6 Ethernet 7 Computer with operating tool (e.g. FieldCare)

Operation via service interface

A0030161
 19 Operation via service interface
1 Service interface (CDI = Endress+Hauser Common Data Interface) 2 Commubox FXA291 3 Computer with "FieldCare" operating tool and "CDI Communication FXA291" COM DTM
44 Endress+Hauser
Proservo NMS80

Certificates and approvals

Currently available certificates and approvals can be called up via the product configurator.

CE mark

RCM-Tick marking

Ex approval

Single seal according to ANSI/ISA 12.27.01

The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
The supplied product or measuring system meets the ACMA (Australian Communications and Media Authority) requirements for network integrity, interoperability, performance characteristics as well as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0029561
The devices are certified for use in hazardous areas and the relevant safety instructions are provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on the nameplate.
The separate documentation "Safety Instructions" (XA) containing all the relevant explosion protection data is available from your Endress+Hauser Sales Center.
The devices have been designed according to ANSI/ISA 12.27.01 as single seal devices, allowing the user to waive the use and save the cost of installing external secondary process seals in the conduit as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1 (CEC) These instruments comply with the North-American installation practice and provide a very safe and cost­saving installation for pressurized applications with hazardous fluids.
Further information can be found in the Safety Instructions (XA) of the relevant devices.

Functional Safety (SIL)

WHG

Weight & Measure approval

Non-ionizing radiation protection

CRN approval

Use for level monitoring (MIN, MAX, range) up to SIL 2 according to IEC 61508:2010.
For details refer to the "Functional Safety Manual": SD01920G (NMS80, NMS81, NMS83)
in preparation
• OIML R85 (2008)
• NMi
• PTB
• PAC
• LNE
• WELMEC
• GOST (in preparation) The device has a sealable locking switch according to the Weight & Measure requirements. This
switch locks all software parameters related to the measurement. The switching status is indicated on the display and via the communication protocol.
According to guideline 2004/40/EG-ICNIRP Guidelines EN50371
Some device versions have a CRN approval. Devices are CRN approved if the folowing two conditions are met:
• The CRN approval is selected (Product structure: Feature 590 "Additional Approval", option LD
"CRN")
• The device has a CRN approved process connection according to the following table:
Endress+Hauser 45
Proservo NMS80
Feature 140: Process Connection Meaning
AFA NPS 3" Cl.150 RF, aluminium flange ASME B16.5
AHA NPS 6" Cl.150 RF, aluminium flange ASME B16.5
AJA NPS 8" Cl.150 RF, aluminium flange ASME B16.5
• Process connections without CRN approval are not included in this table.
• CRN approved devices are marked with the registration number OF18152.5C on the nameplate.

Test, certificate

Other standards and guidelines

Ordering feature 580 "Test, Certificate" Designation
KE Pressure test, internal procedure, inspection certificate
KS Welding documentation, wetted/pressurized seams
Industry standards
• Directive 2002/95/EC: "Restriction of Hazardous Substances Directive" (RoHS)
• Directive 2004/22/EC: "Measuring Instruments Directive" (MID)
• IEC61508: "Functional Safety of Electrical/Electronic/Programmable Electronic Safety-related Systems" (SIL)
• NACE MR 0175, NACE MR 0103: "Sulfide stress cracking resistant metallic materials for oilfield equipment"
• API Recommended Practice 2350: "Overfill Protection for Storage Tanks in Petroleum Facilities"
• API MPMS: "Manual of Petroleum Measurement Standards"
• EN 1127: "Explosive atmospehres - Explosion prevention and protection"
• IEC 60079: "Equipment protection"
• EN 1092: "Flanges and their joints"
• EN 13463: "Non-electrical equipment for use in potentially explosive atmospheres"
• TIA-485-A: "Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems "
• IEC61511: "Functional safety - Safety instrumented systems for the process industry sector"
• IEEE 754: "Standard for Binary Floating-Point Arithmetic for microprocessor systems "
• ISO4266: "Petroleum and liquid petroleum products - measurement of level and temperature in storage tanks by automatic methods"
• ISO6578: "Refrigerated hydrocarbon liquids - Static measurement - Calculation procedure"
• ISO 11223: "Petroleum and liquid petroleum products - Determination of volume, density and mass of the contents of verical cylindrical tanks by Hybrid Tank Measurement Systems"
• ISO15169: "Petroleum and liquid petroleum products - Direct static measurement - Measurement of content of vertical storage tanks by hydrostatic tank gauging"
• JIS K2250: "Petroleum Measurement Tables"
• JIS B 8273: "Bolted flange for pressure vessels"
• G.I.I.G.N.L.: "LNG Custody transfer handbook"
• NAMUR NE043: "Standardization of the Signal Level for the Failure Information of Digital Transmitters"
• NAMUR NE107: "Self-Monitoring and Diagnosis of Field Devices"
• PTBA-A-4.2: "Volume measuring devices for liquids in a stationary condition - Storage containers and their measuring devices"ur
Metrological standards
• OIML R85 (2008) "Requirements for ambient temperature low –25 °C (–13 °F) and ambient temperature high +55 °C (+131 °F)
• "Mess- und Eichverordnung" (Calibration regulations for the Federal Republic of Germany)
• Directive 2004/22/EC of the European Parliament and of the Council of 31 March 2004 on measuring instruments
46 Endress+Hauser
Proservo NMS80

Ordering information

Ordering information

Marking

Shipping condition

Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com -> Click "Corporate"
-> Select your country -> Click "Products" -> Select the product using the filters and search field -> Open product page -> The "Configure" button to the right of the product image opens the Product Configurator.
• From your Endress+Hauser Sales Center: www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Option of ordering feature 895 "Marking"
Z1 Tagging (TAG)
Z2 Bus address
Optionally, the device can be ordered with a specific tagging and/or bus address according to the table above. When the respective option is selected, the tag or bus address must be defined in an additional specification.
To enable turnkey operation and commission, NMS8x is shipped in all-in-one condition except for the following specifications.
• 47 m (154.20 ft) measuring range
• 55 m (180.45 ft) measuring range
• 110 mm (4.33 in) displacer
• NPS8 in flange
• Cleaned from oil+grease option
Meaning
Endress+Hauser 47

Application packages

1
2
2
3 1
Proservo NMS80

Advanced tank measurement methods

The device software provides the following tank measurement methods:
• Direct level measurement →  48
• Hybrid tank measurement system (HTMS) →  49
• Hydrostatic tank shell correction (HyTD) →  50
• Thermal tank shell correction (CTSh) →  50
Direct level measurement
If no advanced tank measurement methods have been selected, level and temperature are measured directly.
Direct level measurement modes
Measuring mode Installation example Measured variables Calculated variables
Level only
1 NMS8x 2 To inventory management system
Level + temperature
Level None
A0026820
• Level
• Temperature (point or average)
None
A0026829
1 NMS8x 2 To inventory management system 3 Temperature transmitter (point or average)
48 Endress+Hauser
Proservo NMS80
2
3
D1
1
2
3
4 1
D3
HTMS measuring modes
Measuring mode Installation example Measured variables Calculated variables
HTMS + P1
This mode should be used in atmospheric (i.e.
non-pressurized) tanks
HTMS + P1 + P3
This mode should be used in non- atmospheric
(i.e. pressurized) tanks
Hybrid tank measurement system (HTMS)
HTMS uses level and pressure measurements to calculate the contents of the tank and (optionally) the density of the medium.
• Level
• Bottom pressure (at position D1)
A0026830
1 NMS8x 2 To inventory management system 3 Pressure transmitter (bottom)
• Level
• Bottom pressure (at position D1)
• Top pressure (at position D3)
Density of the medium
Density of the medium
A0026831
1 NMS8x 2 To inventory management system 3 Pressure transmitter (bottom) 4 Pressure transmitter (top)
Endress+Hauser 49
Proservo NMS80
Δx
Hydrostatic tank shell correction (HyTD)
The hydrostatic tank shell correction can be used to compensate for vertical movement of the Gauge Reference Height due to bulging of the tank shell caused by the hydrostatic pressure exerted by the liquid stored in the tank. The compensation is based on a linear approximation obtained from manual hand dips at several levels distributed over the full range of the tank.
A0026832
 20 Movement Δx of the tank reference height due to the bulging of the tank shell caused by hydrostatic
pressure
Thermal tank shell correction (CTSh)
The thermal tank shell correction can be used to compensate for vertical movement of the Gauge Reference Height due to temperature effects on the tank shell or stilling well. The calculation is based on the thermal expansion coefficients of steel and on insulation factors for both the dry and wetted part of the tank shell.
• This correction is recommended for any tank gauge operating at conditions deviating considerably from the conditions during calibration and for extremely high tanks. For refrigerated, cryogenic and heated applications this correction is highly recommended.
• Wire length can also be corrected with the parameters related to CTSh.
50 Endress+Hauser
Proservo NMS80
32.5 (1.28)
319 (12.6)
471.6 (18.6)

Accessories

Device-specific accessories Weather protection cover

 21 Weather protection cover; dimensions: mm (in)
Materials
Part Material
Protection cover and mounting brackets 316L (1.4404)
Screws and washers A4
• The weather protection cover can be ordered together with the device: Ordering feature 620 "Accessory Enclosed", option PA "Weather Protection Cover")
• It can also be ordered as an accessory: Order code: 71305035 (for NMS8x)
A0029585
Endress+Hauser 51
Proservo NMS80
Calibration chamber
A calibration chamber is recommended for use with tank level gauges in order to allow maintenance (removing the 70 mm (2.76 in) displacer or larger), while the tank is in service. Contact your Endress +Hauser Sales Center if necessary.
Ball valve
Ball valves are recommended for use with tank level gauges in order to allow maintenance such as removing displacers while tank is in service. Contact your Endress+Hauser Sales Center if necessary.
Control switch
A control switch is used for field mounted tank gauges. This provides additional gauge operation contact switching in order to control the gauge’s operation, such as hoisting up the displacer. Contact your Endress+Hauser Sales Center if necessary.
Relief valve and pressure gauge
A relief valve is used to release pressure inside the housing of NMS8x before maintenance.
 22 Relief valve
A pressure gauge is used to check process pressure inside the housing.
 23 Pressure gauge
A0028881
A0028882
52 Endress+Hauser
Proservo NMS80
1
1
2
A0030102
 24 Mounting position of relief valve and pressure gauge
1 Pressure gauge 2 Relief valve
Cleaning nozzle and gas purging nozzle
A cleaning nozzle used for washing inside housing is especially recommended for F&B or alcohol applications.
A gas purging nozzle used for purging gas inside the housing is especially recommended for a nitrogen blanket for petrochemical or chemical applications.
A0030103
 25 Holes for cleaning nozzle and gas purging nozzle
1 Cleaning nozzle 2 Gas purging nozzle
Endress+Hauser 53
Proservo NMS80

Communication-specific accessories

Service-specific accessories

Accessory Description
WirelessHART Adapter SWA70
Accessory Description
Commubox FXA195 HART
Accessory Description
Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser
Accessory Description
FieldCare Endress+Hauser's FDT-based Plant Asset Management tool.
Connects field devices to a WirelessHART network. The WirelessHART adapter can be mounted directly at a HART device and is easly integrated into an existing HART network. It ensures safe data transmission and can be operated in parallel with other wireless networks.
For details refer to Operating Instructions BA00061S
For intrinsically safe HART communication with FieldCare via the USB interface.
For details refer to Technical Information TI00404F
Common Data Interface) to the USB interface of a computer.
For details refer to Technical Information TI00405C
Helps to configure and maintain all field devices of your plant. By supplying status information it also supports the diagnosis of the devices.
For details refer to Operating Instructions BA00027S and BA00059S.

System components

Accessory Description
RIA15 Compact process display unit with very low voltage drop for universal use to display
4 to 20 mA/HART signals
For details refer to Technical Information TI01043K.
Tankvision
• Tank Scanner NXA820
• Data Concentrator NXA821
• Host Link NXA822
Inventory Management System with completely integrated software for operation via standard web browser
For details refer to Technical Information TI00419G.
54 Endress+Hauser
Proservo NMS80

Documentation

Technical Information (TI)

Brief Operating Instructions (KA)

Operating Instructions (BA)

Description of Device Parameters (GP)

The Technical Information contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
Device Technical Information
Proservo NMS80 TI01248G
The Brief Operating Instructions contain all the essential information from incoming acceptance to initial commissioning.
Device Brief Operating Instructions
Proservo NMS80 KA01200G
The Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
It also contains a detailed explanation of each individual parameter in the operating menu (except the Expert menu). The description is aimed at those who work with the device over the entire life cycle and perform specific configurations.
Device Operating Instructions
Proservo NMS80 BA01456G
The Description of Device Parameters provides a detailed explanation of each individual parameter in the 2nd part of the operating menu: the Expert menu. It contains all the device parameters and allows direct access to the parameters by entering a specific code. The description is aimed at those who work with the device over the entire life cycle and perform specific configurations.
Device Description of Device Parameters
Proservo NMS80 GP01074G
Endress+Hauser 55
Proservo NMS80

Safety instructions (XA)

Ordering feature 010 "Approval" Meaning XA
BC ATEX II 1/2G Ex db [ia Ga] IIC T6 Ga/Gb XA01495G
FD FM C/US XP-AIS Cl.I Div.1 Gr.BCD T6
AEx db [ia Ga] IIC T6 Ga/Gb
GC EAC Ga/Gb Ex db [ia Ga] IIC T6...T1 X XA01711G
IC IEC Ex db [ia Ga] IIC T6 Ga/Gb XA01495G
1)
KC
MC INMETRO Ex d[ia] IIC T6 Ga/Gb XA01705G
NC NEPSI Ex d[ia] IIC T6 Ga/Gb XA01704G
TC TIIS Ex d[ia] IIC T4 Ga/Gb XA01600G
1) KC approval is covered with IEC Ex approval.
KC Ex d[ia] IIC T6 Ga/Gb XA01495G
XA01496G
56 Endress+Hauser
Proservo NMS80