Emko ESM-9920 User guide

ESM-9920 96 x 96 1/4 DIN
Temperature Controller with Universal Input
- 4 digits process(PV) and 4 digits process set value(SV) display
- Universal process input (TC, RTD )
- Configurable ON/OFF, P, PI, PD and PID control forms
- Adaptation of PID Coefficients to the system with Self-Tune operation (Step Response Tuning)
- Programmable Heating or Cooling Functions for Control Output
- Alarm Functions for Alarm Output
ESM-9920 96x96 1/4 DIN Temperature Controller
Instruction Manual. ENG ESM-9920 02 V00 03/06
ABOUT INSTRUCTION MANUAL
Instruction manual of ESM-9920 Temperature Controller consists of two main sections. Explanation of these sections are below. Also, there are other sections which include order information and technical specifications of the device. All titles and page numbers in instruction manual are in “CONTENTS” section. User can reach to any title with section number.
Installation:
In this section, physical dimensions of the device, panel mounting, electrical wiring, physical and electrical installation of the device to the system are explained.
Operation
parameters are explained.
physical and electrical mounting or using the device.
c
and Parameters:
In this section user interface of the device, accessing to the parameters, description of the
Also in these sections, there are warnings to prevent serious injury while doing the
Explanation of the symbols which are used in these sections are given below.
This symbol is used for safety warnings. User must pay attention to these warnings.
This symbol is used to determine the dangerous situations as a result of an electric shock. User must pay attention to these warnings definitely.
a
This symbol is used to determine the important notes about functions and usage of
i
the device.
2
CONTENTS
1.PREFACE............................................................................................................................................
1.1 GENERAL SPECIFICATIONS
1.2 ORDERING INFORMATION
1.3 WARRANTY
1.4 MAINTENANCE
2.INSTALLATION....................................................................................................................................
2.1 GENERAL DESCRIPTION
2.2 DIMENSIONS
2.3 PANEL CUT-OUT
2.4 ENVIRONMENTAL RATINGS
2.5 PANEL MOUNTING
2.6 INSTALLATION FIXING CLAMP
2.7 REMOVING FROM THE PANEL
3.ELECTRIAL WIRINGS.........................................................................................................................
3.1 TERMINAL LAYOUT AND CONNECTION INSTRUCTIONS
3.2 ELECTRICAL WIRING DIAGRAM
3.3 VIEW OF THE DEVICE LABEL
3.4 SUPPLY VOLTAGE INPUT CONNECTION OF THE DEVICE
3.5 PROCESS INPUT CONNECTION
3.5.1 TC (THERMOCOUPLE) CONNECTION
3.5.2 RTD CONNECTION
3.6 GALVANIC ISOLATION TEST VALUES OF ESM-9920 TEMPERATURE CONTROLLER
4.OUTPUT CONNECTION FORMS IN ESM-9920 TEMPERATURE CONTROLLER......................
4.1 PROCESS OUTPUT ( RELAY ) CONNECTION
4.2 PROCESS OUTPUT ( SSR DRIVER ) CONNECTION
4.3 ALARM OUTPUT ( RELAY ) CONNECTION
Page 5
Page 8
Page 13
Page 19
5.FRONT PANEL DEFINITION AND ACCESSING TO THE MENUS....................................................
5.1 FRONT PANEL DEFINITION
5.2 RUN THE DEVICE AND
5.3 ADJUSTMENT OF PROCESS SET VALUES
5.4 ADJUSTMENT OF ALARM SET VALUES
6.PARAMETERS.....................................................................................................................................
6.1 PARAMEER LIST
6.2 PROGRAMMING SECTION EASY ACCESS
6.3 ENTERING TO THE PROGRAMMING SECTION AND PROCESS MENU
6.4 CONTROL MENU
6.5 ALARM MENU
6.6 PROTECTION MENU
7.GENERAL INFORMATION..................................................................................................................
7.1 TUNE OPERATION
7.2 ALARM TYPES
8.FAILURE MESSAGES IN ESM-9920 TEMPERATURE CONTROLLER............................................
9.SPECIFICATIONS................................................................................................................................
OBSERVATION OF SOFTWARE REVISION ON THE DISPLAYS
Page 21
Page 24
Page 38
Page 43
Page 44
3
EU DECLARATION OF CONFORMITY
Manufacturer Company Name : Emko Elektronik A.S.
Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye
The manufacturer hereby declares that the product conforms to the following standards and conditions.
Product Name : Temperature Controller
Model Number : ESM-9920
Type Number : ESM-9920
Product Category : Electrical equipment for measurement, control and laboratory use
Conforms to the following directives :
73 / 23 / EEC The Low Voltage Directive as amended by 93 / 68 / EEC
89 / 336 / EEC The Electromagnetic Compatibility Directive
Has been designed and manufactured according to the following specifications
EN 61000-6-4:2001 EMC Generic Emission Standard for the Industrial Environment
EN 61000-6-2:2001 EMC Generic Immunity Standard for the Industrial Environment
EN 61010-1:2001 Safety Requirements for electrical equipment for measurement, control and laboratory use
4
1.Preface
ESM-9920 series temperature controllers are designed for measuring and controlling a process value. They can be used in many applications with their universal process input, control outputs and selectable alarm functions.
Some application fields which they are used are below:
Application Fields Application
Glass PID Process Control Plastic Petro-Chemistry Textile Automative Machine production industries
1.1 General Specifications
ESM-9920
Standard
Supply Voltage Input
Process Input
Standard
Process Out
Standard
Alarm Out
230 V V (±15%) , 50/60Hz
Optional Supply Voltage Input
115 V V (±15%) , 50/60Hz 24 V V (±15%) , 50/60Hz
12 V W (±15%) , 50/60Hz
Universal Process Input TC, RTD
Control Output
Alarm Output
Heating-Cooling Function ON/OFF, PID Operation
5
1.2 Ordering Information
A BC D E FG HI
ESM-9920 (96x96 1/4DIN)
Supply VoltageA
24V V ( ± 15% ) 50/60Hz
3
115V V ( ± 15% ) 50/60Hz
4
230V V ( ± 15% ) 50/60Hz
5
12V W ( ± 15% ) 50/60Hz
6
Customer
9
Input Type
BC
23
J ,Fe CuNi IEC584.1(ITS90) K ,NiCr Ni IEC584.1(ITS90)
25
R ,Pt13%Rh Pt IEC584.1(ITS90)
27
S ,Pt10%Rh Pt IEC584.1(ITS90)
28
T ,Cu CuNi IEC584.1(ITS90)
29
PT 100 , IEC751(ITS90)
39
PT 100 , IEC751(ITS90)
40
E
Process Output
1
Relay Output ( resistive load 5A@250V V , 1 NO + 1NC )
2
SSR Driver Output (Maximum 20mA@ 18V Z)
0 00
-199.9°C,650.0°C
/
Scale(°C) Scale(°F)
-200°C,900°C
-200°C,1300°C
0°C,1700°C
0°C,1700°C
-200°C,400°C
-200°C,650°C
U
V W Z/
/
0 0 0 001
/
-328°F,1652°F
-328°F,2372°F
32°F,3092°F
32°F,3092°F
-328°F,752°F
-328°F,1202°F
-199,9°F,999.9°F
All order information of E S M - 9 9 2 0 Te m p e r a t u r e Controller are given on the table at left. User may form appropriate d e vi ce co nf ig u r a t i o n fr om information and codes that at the table and convert it to the ordering codes.
Firstly, supply voltage then other specifications must be determined. Please fill the order code blanks according to your needs.
Please contact us, if your needs are out of the standards.
FG
Alarm Output
01
Relay Output ( resistive load 5A@250V V , 1 NO + 1NC)
V Þ Vac, Z Þ Vdc
c
Þ Vdc or Vac can be applied.W
6
1.3 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely.
1.4 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case.
7
2.Installation
Before beginning installation of this product, please read the instruction manual and warnings below carefully.
c
In package ,
- One piece unit
- Two pieces mounting clamp
- One piece instruction manual
A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power switch or a fuse. Use power switch and fuse as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During the equipment is putted in hole on the metal panel while mechanical installation some metal burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s mounting clamp. Do not do the montage of the device with inappropriate mounting clamp. Be sure that device will not fall while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction manual.
8
2.1 General Description
Mounting Clamps
Front Panel IP65 protection NEMA 4X
2.2 Dimensions
°C
°F
PSPO
AO
PSET
AS
P
Panel surface (maximum thickness 15mm / 0.59 inch)
Maximum 15mm / 0.59 inch
ASET
96mm / 3.78 inch
Temperature Controller
ESM-9920
96mm / 3.78 inch
12 ± 1 mm / 0.47 inch
84 mm / 3.31 inch
9
2.3 Panel Cut-Out
129 mm/5,08 inch (min)
129 mm/5,08 inch (min)
92mm / 3.62 inch
92mm / 3.62 inch
10
2.4 Environmental Ratings
Operating Conditions
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000m.
Forbidden Conditions: Corrosive atmosphere
c
Explosive atmosphere Home applications (The unit is only for industrial applications)
2.5 Panel Mounting
1
1-Before mounting the device in your panel, make sure that the cut­out is of the right size.
2-Check front panel gasket position
3-Insert the device through the cut-out. If the mounting clamps are on the unit, put out them before inserting the unit to the panel.
c
3
2
During installation into a metal panel, care should be taken to avoid injury from metal burrs which might be present. The equipment can loosen from vibration and become dislodged if installation parts are not properly tightened. These precautions for the safety of the person who does the panel mounting.
11
2.6 Installation Fixing Clamp
c
1
2
Montage of the unit to a system must be done with it’s own fixing clamps. Do not do the montage of the device with inappropriate fixing clamps. Be sure that device will not fall while doing the montage.
The unit is designed for panel mounting.
1-Insert the unit in the panel cut­out from the front side.
2- Insert the mounting clamps to the holes that located top and bottom sides of device and screw up the fixing screws until the unit completely immobile within the panel
2.7 Removing from the Panel
Before starting to remove the unit from panel, power off the unit and the related system.
c
2
1
1-Loosen the screws.
2-Pull mounting clamps from top and bottom fixing sockets.
3-Pull the unit through the front side of the panel
3
12
3.Electrical Wirings
You must ensure that the device is correctly configured for your application. Incorrect configuration could result in damage to the process being controlled, and/or personal injury. It is your responsibility, as the installer, to ensure that
c c
the configuration is correct. Parameters of the device has factory default values. These parameters must be set according to the system’s needs.
Only qualified personnel and technicians should work on this equipment. This equipment contains internal circuits with voltage dangerous to human life. There is severe danger for human life in the case of unauthorized intervention.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure.
c
Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented.
c
3.1 Terminal Layout and Connection Instructions
aa
Max. 2.5mm / 0.098 inch
Wire Size:
14AWG/1mm²
Solid /Stranded
Screw driver 0.8x3mm
Torque 0.5 Nm
13
3.2 Elekctrical Wiring Diagram
Electrical wiring of the device must be the same as ‘Electrical Wiring Diagram’ below to prevent damage to the process being controlled and personnel injury.
c
P/N : ESM-9920
c
PT 100
ı
TC
1 2 3 156 7 8 9 10 11
Temperature Sensor
Input
(TC or PT-100)
Optional SSR Output (It must be determined in order.)
CAT II
Y
+
Not-1 (+)(-)
Process Output
Relay or
PROCESS OUT
5A@250VV
NO C NC
ALARM OUT
5A@250V V
NO C NC
14
aa
Alarm Output Relay
L
N
Supply Voltage Input
230V V ( ± 15% ) 50/60Hz - 3VA 115V V ( ± 15% ) 50/60Hz - 3VA
24V V ( ± 15% ) 50/60Hz - 3VA 12V W ( ± 15% ) 50/60Hz - 3VA
(It must be determined in order.)
Note-1: SSR Driver OutputMax 20mA@18V Z for
Temperature measurement input is in CAT II class.
ii
14
3.3 View of the Device Label
Label for PT-100 (-19.9 ; + 99.9 ) Scaled device
o o
C C
a
c
Y
CAT II
P/N : ESM - 9920
230 VV 15%±
Pt-100
TC
1
2 3
PROSES-OUT
5A@250VV
76 8
ALARM-OUT
5A@250VV
9
10 11
50/60 Hz - 3VA
L
NCNO CNCNO C
N
14
15
15
3.4 Supply Voltage Input Connection of the Device
Connection of Supply Voltage
Input
Y
N L
a
14
15
External
Fuse
(1 A V T)
Power
Supply
Switch
c
Supply Voltage
230 V V (± 15%) 50/60 Hz or 115 V V (± 15%) 50/60 Hz or
24 V V (± 15%) 50/60 Hz
Connection of Supply Voltage
Input
Y
N L
a
14
15
Note-1
External Fuse
(12V V : 1 A V T)
(12V Z : 1 A Z T)
Power Supply Switch
c
Supply Voltage
12 V W (± 15%) 50/60 Hz
Note-1: “L” is (+) , “N” is (-) for 12VZ supply voltage
Make sure that the power supply voltage is the same indicated on the instrument.
c c c c
Switch on the power supply only after that all the electrical connections have been completed.
Supply voltage range must be determined in order. Device is produced different for low and high voltage. While installing the unit, supply voltage range must be controlled and appropriate supply voltage must be applied to the unit. Controlling prevents damages in unit and system and possible accidents as a result of incorrect supply voltage.
There is no power supply switch or fuse on the device. So the user must put power supply switch and a fuse to the supply voltage input. In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument. Power supply switch and fuse must be put to a place where user can reach easily.
Power supply switch must be two poled for seperating phase and neutral. On/Off condition of power supply switch is very important in electrical connection. On/Off condition of power supply switch must be signed for preventing the wrong connection.
c
External fuse must be on phase connection in Vsupply input. External fuse must be on (+) line connection in Zsupply input.
16
3.5 Process Input Connection
3.5.1 TC (Thermocouple) Connection
TC
1 2 3
Always use compensation wire corresponding to the thermocouple used. If
i
ii
present, the shield must be connected to a proper ground.
Input resistance is greater than 10M W.
Connect the wires with the polarity as shown in the figure at left.
3.5.2 RTD Connection
Pt-100
Note 1
Pt-100
Note 2
1 12 23 3
3-wire Pt-100 connection (with line compensation)
(Max. Line impedance is 10 W)
Note 1 : In 3-wire system, use always cables of the same diameter (min 1mm²) Always use wires of the same gauge and type whether a 2-wire or 3-wire system.
Note 2 : Install a jumper between terminals 2 and 3 when using a 2-wire RTD. Note 3 : If the distance is longer than 10 meters, use 3-wire system
2-wire Pt-100 connection (without line compensation)
ii
Input resistance is greater than 10M W.
17
3.6 Galvanic Isolation Test Values of ESM-9920 Temperature Controller
2000V V ( For ESM-9920.1.....)
500V V ( For ESM-9920.2.....)
Supply Voltage
14
15
Ground
1
2000V V
2000V V
2000V V
2000V V
Process Output
(Relay)
Process Output
(SSR Driver)
Alarm Output (Relay)
Analog
Inputs
10
11
6
7
8
7
8
9
2
3
2000V V
2000V V
18
4. Output Connection Forms in ESM-9920 Temperature Controller
4.1 Process Output ( Relay ) Connection
L N
Device
c
C
5A V T Fuse
7
NC
8
Last Control Element
(Contactor)
NO
6
c
Fuse
Load
Fuses must be selected according to the application.
4.2 Process Output ( SSR Driver ) Connection
Device
Last Control
Element
(SSR)
7
8
15-18 V Z Max. 20mA
L N
c
Fuse
Load
c
Fuses must be selected according to the application.
19
4.3 Alarm Output ( Relay ) Connection
Device
C
10
NC
11
NO
9
L N
5A V T Fuse
Last Control Element
(Contactor)
c
Fuse
Load
c
Fuses must be selected according to the application.
20
5. Front Panel Definition and Accessing to the Menus
5.1 Front Panel Definition
LED indication of °C:Centigrade Unit
LED indication of °F Fahrenheit Unit
Process Output Status Led
Alarm Output Status
°C
°F
PO
PS
Led
AO
AS
PS , Process Set Value LED AS , Alarm Set
PSET
P
ASET
Value LED
Temperature Controller
Displays Process Value (PV) and Parameter
Displays Set Value, Parameter
Please refer to Section 6.1
for detailed information;
Section 6.1 (Process and
Alarm Set Parameters)
This button is used to access
to the process set value. If it
is pressed for 5 seconds
continuously programming
section is entered.
Note-1
This button is used to
decrase the parameter
values, access to the
program menus
ESM-9920
This button is used to
access to the alarm set
value and use as OK
button.
Note-1
This button is used to
increase the parameter
values and access to
the program menus
Note-1: If increment or decrement button is pressed for 5 seconds continuously, increment and decrement number become 10, if increment or decrement button is pressed for 10 seconds continuously, increment and decrement number become 100.
21
5.2 Run the Device and Observation of Software Version on the Displays
When the power is applied to the device all led indicators and display segments are momentarily illuminated for testing. Software revision number of the controller on the bottom display is momentarily illuminated.
°C
°F
PS
AS
P
Temperature Controller
“ rU” Þ Revision
PO
AO
PSET
When power on, display of the indicator is like below:
°C
°F
PO
AO
PSET
PS
AS
P
Temperature Controller
ASET
°C
°F
PO
AO
PSET
PS
AS
P
Temperature Controller
ASET
ESM-9920
ASET
Revision number
°C
°F
PO
AO
PSET
PS
AS
P
Temperature Controller
ASET
ESM-9920
First segments of top and
bottom displays are tested
°C
°F
PO
AO
PSET
PS
AS
P
Temperature Controller
ASET
ESM-9920
Fourth segments of top
and bottom displays are
tested.
If there is an unexpected situation while opening the device, power off the
c
device and inform a qualified personnel.
ESM-9920
Second segments of top
and bottom displays are
tested.
°C
°F
PO
AO
PSET
PS
AS
P
Temperature Controller
ASET
ESM-9920
Revision number is shown.
All leds are energised.
ESM-9920
Third segments of top and
bottom displays are tested.
°C
°F
PO
AO
PSET
PS
AS
P
Temperature Controller
ASET
ESM-9920
Main operation screen is
shown
22
5.3 Adjustment of Process SET Values
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
When PSET button is pressed, PS
led starts to blink, the information to
indicate which set is shown is on top
display, process set value is shown
on bottom display.
Press PSET button to exit without
saving the process set value.
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
°C
°F
PO
AO
PSET
P
PS
AS
Process Set Screen
ASET
Change the process set
value with increment and
decrement buttons.
Press ASET/OK button for saving process set value.
°C
°F
PS
PO
AS
AO
Operation Screen
Value, can be adjusted from process set low limit to process
PSET
P
ASET
set high limit .
°C
°F
PO
AO
PSET
P
PS
AS
ASET
5.4 Adjustment of Alarm SET Values
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
When ASET button is pressed, AS
led starts to blink, the information to
indicate which set is shown is on top
display, alarm set value is shown on
bottom display.
Operation Screen
value can be adjusted from alarm set low limit to alarm set high limit .
°C
°F
PO
AO
PSET
P
PS
AS
Alarm Set Screen
ASET
Change alarm set value
with increment and
decrement buttons.
°C
°F
PS
PO
AS
AO
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Press PSET
button to exit
without
saving the
alarm set
value.
Press ASET/OK button for saving process set value.
PSET
P
ASET
23
6. Parameters
6.1 Parameter List
Process menu title
Process input type selection ( Default Value = J Type (FE.C.n) )
J type (Fe,Cu,Ni) Thermocouple, or -200°C,900°C -328°F,1652°F
K type (Ni,Cr,Ni) Thermocouple , -200°C,1300°C or -328°F,2372°F
R type (Pt13%RhPt) Thermocouple , 0°C,1700°C or 32°F,3092°F
S type (Pt10%RhPt) Thermocouple, 0°C,1700°C or 32°F,3092°F
T type (Cu,Cu,Ni) Thermocouple , -200°C,400°C or -328°F,752°F
Pt - 100 , -200°C,650°C or -328°F,1202°F
Pt - 100 , -199.9°C,650.0°C or -199.9°F,999.9°F
Unit Selection ( Default Value = °C )
Unit is °C
Unit is °F
Process Set Low Limit. Minimum process set value is defined with this parameter. It changes according to process input type and scale. ( Default Value = -200 )
Process Set High Limit. Maximum process set value is defined with this parameter. It changes according to process input type and scale. ( Default Value = 900 )
Display offset for process value. It can be adjusted from -10% of scale (PuPL-PLoL) to 10% of scale (PuPL-PLoL). It is added to the process display value. ( Default
Value = 0 )
Control menu title
Process Type selection ( Default Value = Heat )
Process type is heating
Process type is cooling
Process Control Type selection ( Default Value = on.oF )
Process Control form is ON/OFF
Process Control form is PID
Tune parameter ( Default Value = no ) This parameter can be observed if Cnts parameter is Pıd
Self - Tune (Step Response Tuning) does not run. (Please refer to Section 7.1 for Tune Operation)
Self - Tune runs (Step Response Tuning) .
24
Proportional Band . It can be adjusted from 1% to 100%.( Default Value = 10 ) If process control type selection CntS = Pıd, then this parameter can be observed
Integral Time. It can be adjusted from 0 to 3600 secs. If process control type selection CntS = Pıd, then this parameter can be observed
( Default Value = 100 )
Derivative Time. It can be adjusted from 0.0 to 999.9 secs. If process control type selection CntS = Pıd, then this parameter can be observed
( Default Value = 25.0 )
Output Control period. It can be adjusted from 1 to 150 seconds. If process control type selection CntS = Pıd, then this parameter can be observed
( Default Value = 10 )
Hysteresis value. If Process Control Type selection CntS = on.oF, then this parameter can be observed. It can be adjusted from 0% of defined scale ( PuPL- PLoL ) to 50% of defined scale ( PuPL- PLoL ).( Default Value = 0 )
Alarm menu title
Alarm Hysteresis value. It can be adjusted from 0% of defined scale ( AuPL- ALoL ) to 50% of defined scale ( AuPL- ALoL ). ( Default Value = 0 )
Alarm Type selection ( Default Value = PHıA (Process High Alarm) )
Process High Alarm
Process Low Alarm
Deviation High Alarm
Deviation Low Alarm
Deviation Band Alarm
Deviation Range Alarm
Alarm Set Value Low Limit. Minimum value of the alarm set value is defined in this parameter. It can be adjusted from process set value low limit parameter to alarm set high limit parameter. It changes according to process input type and scale.
( Default Value = 0 )
Alarm Set High Limit. Maximum value of the alarm set value is defined in this parameter. It can be adjusted from alarm set low limit parameter to process set high limit parameter. It changes according to process input type and scale.
( Default Value = 500 )
Alarm on delay time. It can be adjusted from 0 to 9999 seconds. ( Default Value = 0 )
Alarm off delay time. It can be adjusted from 0 to 9998 seconds. When it is higher than 9998, “LtCH” is shown and alarm latching output is selected. To make the alarm latching output passive, decrement button must be pressed in main operation screen
( Default Value = 0 )
Protection menu title
Password for accessing to the programming section. It can be adjusted from 0 to
9999. ( Default Value = 0 )
25
6.2 Easy Access Diagram of Programming Section
Main Operation
Screen
°C
°F
PS
PO
AO
PSET
AS
P
PO
AO
PSET
For entering to the
programming section, press
PSET/P button for 5
seconds.
°C
°F
PS
AS
P
After 5secs
°C
°F
PS
PO
AS
AO
Password entering
screen is shown when
ASET/OK Button is
pressed.
ASET
Password Entering Screen
°C
°F
PS
PO
AS
AO
Enter the password with increment or decrement
buttons.
°C
°F
PS
PO
AS
AO
ASET
Press ASET/OK button for entering to the menus.
°C
°F
PS
PO
AS
AO
Process menu
ASET
Process Input type selection
°C
°F
PS
PO
AS
AO
ASET
Unit selection
°C
°F
PS
PO
AS
AO
ASET
Process Set Low
Limit
°C
°F
PS
PO
AS
AO
ASET
Process Set High
Limit
°C
°F
PS
PO
AS
AO
ASET
°C
°F
PS
PO
AS
AO
Control menu
ASET
Process Type Selection
°C
°F
PS
PO
AS
AO
ASET
°C
°F
PS
PO
AS
AO
ASET
Process Control Type Selection
°C
°F
PS
PO
AS
AO
Hysteresis
Value
°C
°F
PS
PO
AS
AO
ASET
ASET
°C
°F
PS
PO
AS
AO
Tune
parameter
°C
°F
PS
PO
AS
AO
ASET
ASET
Proportional
Band
°C
°F
PS
PO
AS
AO
ASET
°C
°F
PS
PO
AS
AO
Alarm menu
ASET
Alarm Hysteresis
Value
°C
°F
PS
PO
AS
AO
ASET
Alarm Type selection
°C
°F
PS
PO
AS
AO
ASET
Alarm Low
Limit
°C
°F
PS
PO
AS
AO
ASET
Alarm High
Limit
°C
°F
PS
PO
AS
AO
ASET
°C
°F
PS
PO
AS
AO
Protection Menu
ASET
Programming Section
Entering Password
°C
°F
PS
PO
AS
AO
ASET
Process
Offset Value
°C
°F
PS
PO
AS
AO
ASET
Integral
Time
°C
°F
PS
PO
AS
AO
ASET
Derivative
Time
°C
°F
PS
PO
AS
AO
ASET
Control Period
°C
°F
PS
PO
AS
AO
ASET
Alarm On
Time
°C
°F
PS
PO
AS
AO
Alarm OFF
Time
°C
°F
PS
PO
AS
AO
ASET
ASET
26
6.3 Entering to the Programming Section and Process Menu
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
Press PSET/P button for 5
seconds for entering
programming section
Press ASET/OK button for accessing to the password entering screen.
°C
°F
PO
AO
PSET
P
PS
AS
If password for
entering to the
programming
ASET
Enter the password
with increment or
decrement buttons.
section is
defined,
password
entering
screen is
shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
When 5secs is expired,
programming section
entering screen is shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Press ASET/OK button for entering to the menus.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Programming
Section Entering
Screen
When screen is shown,
parameters can be observed by pressing ASET/OK button
without entering the
password. But no changes
can be done with the
parameters. Please refer to
Section 6.6 (Protection Menu)
for detailed information
Protection Menu
°C
°F
PS
PO
AS
AO
PSET
P
Former menu can be accessed by pressing left arrow button.
ASET
Process Menu
°C
°F
PS
PO
AS
AO
PSET
P
Control Menu
°C
°F
PS
PO
AS
AO
ASET
PSET
P
Following menu can be access by pressing right arrow button.
Press ASET/OK button for
accessing to the Process
Menu.
ASET
27
°C
°F
PO
AO
PSET
P
Process Input Type Selection
Process Input Type can be changed into any of the type which are listed
PS
AS
below with increment and decrement buttons.
: J type (Fe,Cu,Ni)Thermocouple, or : K type (Ni,Cr,Ni)Thermocouple , : R type (Pt13%RhPt) Thermocouple,
ASET
: S type (Pt10%RhPt) Thermocouple, : T type (Cu,Cu,Ni)Thermocouple , : Pt - 100 , : Pt - 100 ,
-200°C,650°C or -328°F,1202°F
-199.9°C,650.0°C or -199.9°F,999.9°F
-200°C,900°C -328°F,1652°F
-200°C,1300°C or -328°F,2372°F 0°C,1700°C or 32°F,3092°F 0°C,1700°C or 32°F,3092°F
-200°C,400°C or -328°F,752°F
Press ASET/OK button for saving the changes and accessing to the following parameter.
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
PSET
P
Unit selection
PS
AS
Unit can be selected or by increment and decrement buttons.
Press ASET/OK button for saving the changes and accessing to the
ASET
following parameter.
Process Set Value Low Limit
PS
AS
Minimum value of the process set value can be adjusted with this parameter. It can be adjusted from process input type minimum value to process high limit parameter value. It changes according to the process input type and scale.
ASET
Press ASET/OK button for saving the changes and accessing to the following parameter.
°C
°F
PO
AO
PSET
P
Process Set Value High Limit
PS
AS
Maximum value of the process set value can be adjusted with this parameter. It can be adjusted from process low limit parameter to process input type maximum value. It changes according to the process input type and scale.
ASET
Press ASET/OK button for saving the changes and accessing to the following parameter.
28
°C
°F
PO
AO
PSET
P
Process Value Display Offset
It can be adjusted -10% of scale (PuPL-PLoL) to 10% scale (PuPL-PLoL).
PS
AS
Defined value is added to the process display value.
Press ASET/OK button for saving the changes and accessing to the
ASET
following parameter.
Operation Screen
°C
°F
PS
PO
AS
AO
PSET
ASET
P
Press PSET/P for exiting
menu list and turn to operation
screen.
Process Menu
°C
°F
PS
PO
AS
AO
PSET
P
Following menu can be access by pressing right arrow button.
ASET
Control Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
29
6.4 Control Menu
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
Press PSET/P button for 5
seconds for entering
programming section
Press ASET/OK button for accessing to the password entering screen.
°C
°F
PO
AO
PSET
P
PS
AS
If password for
entering to the
programming
ASET
Enter the password
with increment or
decrement buttons.
section is
defined,
password
entering
screen is
shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
When 5secs is expired,
programming section
entering screen is shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Press ASET/OK button for entering to the menus.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Programming
Section
Entering
Screen
When screen is shown,
parameters can be observed by pressing ASET/OK button
without entering the
password. But no changes
can be done with the
parameters. Please refer to
Section 6.6 (Protection Menu)
for detailed information
Protection Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Former menu can be accessed by pressing left arrow button.
Process Menu
°C
°F
PS
PO
AS
AO
PSET
P
Control Menu
°C
°F
PS
PO
AS
AO
ASET
PSET
P
Following menu can be access by pressing right arrow button.
Press ASET/OK button for
accessing to the Process
Menu.
ASET
30
°C
°F
Process Type Selection
PSET
°C
°F
PSET
°C
°F
PSET
°C
°F
PSPO
AS
AO
P
Process Type Selection can be selected or with increment and decrement buttons.
Press ASET/OK button for saving the parameter and accessing to the next
ASET
parameter.
Process Control Type Selection
°C
°F
Process Control Type can be
PSPO
AS
AO
selected or with increment and decrement buttons.
PSPO
AS
AO
Press ASET/OK button for saving the parameter
ASET
P
Press ASET/OK button for saving the parameter and
PSET
P
accessing to the next
ASET
and accessing t o t h e n e x t parameter.
parameter.
Hysteresis Value
°C
°F
P ro c es s C o nt r ol T yp e
PSPO
AS
AO
selection.If = ,then thi s para mete r c an be
PSPO
AS
AO
observed.It can be adjsuted from 0% of full scale (PuPL-
ASET
P
PLoL) to 50% of full scale
PSET
P
(PuPL-PLoL) with increment and decrement buttons.
If Process Control Type selection = , parameter is saved and
PSPO
AS
AO
exit from control menu by p r e s s i n g A S E T / O K
Pr ess ASE T/O K button for saving the p a r a m e t e r a n d accessing to the next parameter.
Tune Parameter
Tune operation can be started and stopped with increment
ASET
and decrement buttons. If Process Control Type
= T h e n t h i s parameter can be observed.
button.
PSET
P
ASET
Control Menu
Proportional band can be adjusted from 1% to 100% with increment and decrement buttons. If Process
Control Type selection = , then this parameter can be observed. For example ; If = 1000°C, = 0°C and = 50. Proportional Band = ( - ) * /100 Proportional Band = ( 1000 - 0 ) * 50 /100 = 500 °C
°C
°F
PSET
P
Proportional Band
PSPO
AS
AO
ASET
Press ASET/OK button for saving the parameter and accessing t o t h e n e x t parameter.
31
°C
°F
PO
AO
PSET
P
Integral Time
It can be adjusted from 0 to 3600 seconds with increment and decrement
PS
AS
buttons.If Process Control Type selection = , then this parameter
can be observed.
Press ASET/OK button to save the value and access to the next
ASET
parameter.
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
PSET
P
Derivative Time
It can be adjusted from 0.0 to 999.9 seconds.
PS
AS
If Process Control Type selection = , then this parameter can be observed.
Press ASET/OK button for saving the parameter and accessing to the next
ASET
parameter.
Output Control Period
It can be adjusted from 1 to 150 with increment and decrement buttons.
PS
AS
If Process Control Type selection = , then this parameter can be observed.
OUTPUT : ON
ASET
Relay Output : Output period must be short for
stable process control. Relay must not be used in short output periods because of limited life of their relay contact (number of open/close
OUTPUT
PERIOD
OUTPUT
PERIOD
P r e s s A S E T / O K button for saving the p a r a m e t e r a n d accessing to the next
events). Relay output must be used as control output in values near to 30 seconds or greater than this value. SSR Output : If short output period is needed in a system (approximately 1-2 seconds) SSR driver output module as last control
parameter.
Process Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Former menu can be accessed by pressing left-arrow button.
Press PSET/P button to exit from menu list and
Control Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Next menu can be accessed by pressing right-arrow button.
turn to the operation screen.
Alarm Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
32
6.5 Alarm Menu
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
Press PSET/P button for 5
seconds for entering
programming section
Press ASET/OK button for accessing to the password entering screen.
°C
°F
PO
AO
PSET
P
PS
AS
If password for
entering to the
programming
ASET
Enter the password
with increment or
decrement buttons.
section is
defined,
password
entering
screen is
shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
When 5secs is expired,
programming section
entering screen is shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Press ASET/OK button for entering to the menus.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Programming
Section
Entering
Screen
When screen is shown,
parameters can be observed by pressing ASET/OK button
without entering the
password. But no changes
can be done with the
parameters. Please refer to
Section 6.6 (Protection Menu)
for detailed information
Protection Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Former menu can be accessed by pressing left arrow button.
Process Menu
°C
°F
PS
PO
AS
AO
PSET
P
Control Menu
°C
°F
PS
PO
AS
AO
ASET
PSET
P
Following menu can be access by pressing right arrow button.
Press ASET/OK button for
accessing to the Process
Menu.
ASET
33
°C
°F
PS
PO
AS
AO
Alarm Menu
PSET
P
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
PSET
P
ASET
Press ASET/OK button to access to the alarm menu.
Alarm Hysteresis value
PS
AS
It can be adjusted from 0% of ( AuPL- ALoL ) to 50% of ( AuPL- ALoL ).
Press ASET/OK button for saving the changes and accessing to the
ASET
following parameter.
Alarm Type Selection
PS
AS
It can be adjusted to the values listed below:
: Process High Alarm : Process Low Alarm
ASET
: Deviation High Alarm : Deviation Low Alarm : Deviation Band Alarm : Deviation Range Alarm Please refer to Section 7.2 Alarm Types for detailed information
°C
°F
PO
AO
PSET
P
Press ASET/OK button for saving the changes and accessing to the following parameter.
Alarm Set Low Limit Value
PS
AS
Minimum value of the alarm set is defined with this parameter. It changes according to the process type and scale. It can be adjusted from process set value low limit parameter to alarm set high limit parameter value.
ASET
Press ASET/OK button for saving the changes and accessing to the following parameter.
34
°C
°F
PS
PO
AS
AO
Alarm Set High Limit Value
Maximum value of alarm set is defined with this parameter. It can be adjusted from alarm set low limit parameter to process set high limit parameter . It changes according to process input type and scale.
PSET
P
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
PSET
P
ASET
Press ASET/OK button for saving the changes and accessing to the following parameter.
Alarm On Delay Time
PS
AS
It can be adjusted from 0 to 999 seconds with increment and decrement buttons.
Alarm
ASET
Status
Alarm
Output
OFF
Delay
On
Delay
Press ASET/OK button for saving the changes and accessing to the following parameter.
Alarm OFF Delay Time
PS
AS
It can be adjusted from 0 to 9998 seconds. When it is higher than 9998, Is shown and alarm latching output is selected. To make the alarm latching output passive, decrement button must be pressed in main operation screen
Press ASET/OK button for saving the changes and accessing to the
ASET
following parameter.
Control Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Former menu can be accessed by pressing left arrow button.
Press PSET/P for exiting menu list and turn to
Alarm Menu
°C
°F
PS
PO
AS
AO
PSET
P
Following menu can be access by pressing right arrow button.
operation screen.
ASET
Protection Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Press ASET/OK button for
accessing to the Process
Menu.
35
6.6 Protection Menu
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
Press PSET/P button for 5
seconds for entering
programming section
Press ASET/OK button for accessing to the password entering screen.
°C
°F
PO
AO
PSET
P
PS
AS
If password for
entering to the
programming
ASET
Enter the password
with increment or
decrement buttons.
section is
defined,
password
entering
screen is
shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
When 5secs is expired,
programming section
entering screen is shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Press ASET/OK button for entering to the menus.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Programming
Section
Entering
Screen
When screen is shown,
parameters can be observed by pressing ASET/OK button
without entering the
password. But no changes
can be done with the
parameters. Please refer to
Section 6.6 (Protection Menu)
for detailed information
Protection Menu
°C
°F
PS
PO
AS
AO
PSET
P
Press ASET/OK
button for
accessing to the
protection
menu.
Process Menu
°C
°F
PS
PO
AS
AO
ASET
PSET
P
Former menu can be accessed by pressing left arrow button.
Control Menu
°C
°F
PS
PO
AS
AO
ASET
PSET
P
Following menu can be accessed by pressing right arrow button.
ASET
36
°C
°F
PS
PO
AS
AO
PSET
P
Press ASET/OK
button for saving
the parameter and exiting from protection menu
parameters.
Programming Section Entering Password
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is 0, programming section is accessed without entering the password.
If it is different from 0, in programming section entering password;
ASET
1- If user enters the password incorrect:
Device turns to main operation screen without being able to see the parameters 2- If user press the ASET/OK button without entering the password for entering to the programming section (observation of the parameters): All menus and parameters except protection menu ( ) can be observed but they can not be changed. (Please refer to Section 8. Failure Messages in ESM-9920 Temperature Controller(4))
Alarm Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Former menu can be accessed by pressing left arrow button.
Protection Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Following menu can be access by pressing right arrow button.
Press PSET/P for exiting
menu list and turn to
operation screen.
Operation Screen
°C
°F
Process Menu
°C
°F
PS
PO
AS
AO
PSET
P
ASET
PO
AO
PSET
P
PS
AS
ASET
37
7. General Information
7.1 Tune Operation
Esm-XX20 devices use Self Tune (Step Response Tuning) method to automatically determine PID parameters.
Starting the Tune operation by the user
! Enter to the programming section ! Select the parameter in menu, and turn to main operation screen. ! Observe that is blinking in set display
°C
°F
PO
AO
PSET
P
PS
AS
Operation Screen
ASET
Press PSET/P button for 5
seconds for entering
programming section
Press ASET/OK button for accessing to the password entering screen.
°C
°F
PO
AO
PSET
P
PS
AS
If password for
entering to the
programming
ASET
Enter the password
with increment or
decrement buttons.
section is
defined,
password
entering
screen is
shown.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
When 5secs is expired,
programming section
entering screen is shown.
°C
°F
PO
AO
PSET
P
PS
AS
ASET
When screen is shown,
Section 6.6 (Protection Menu)
Press ASET/OK button for entering to the menus.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Programming
Section
Entering
Screen
parameters can be observed by pressing ASET/OK button
without entering the
password. But no changes
can be done with the
parameters. Please refer to
for detailed information
Following menu can be accessed by pressing right arrow button.
Process Menu
°C
°F
PS
PO
AS
AO
PSET
P
Control Menu
°C
°F
PS
PO
AS
AO
ASET
PSET
P
Press ASET/OK button for
accessing to the Control Menu
ASET
38
Process Control Type Selection
°C
°F
PO
AO
PSET
P
PS
AS
Process Type Selection
ASET
Press ASET/OK button for saving the parameter and ac ce s si ng to t he n ex t parameter.
°C
°F
PO
AO
PSET
P
PS
AS
Tune Parameter
ASET
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Change Process Control
Type as with increment
button.
°C
°F
PS
PO
AS
AO
PSET
P
ASET
°C
°F
PS
PO
AS
AO
PSET
P
ASET
P r e s s A S E T / O K button for saving the p a r a m e t e r a n d accessing to the next parameter.
Proportional Band
°C
°F
PS
PO
AS
AO
PSET
P
ASET
Press PSET/P
Change Tune Parameter as
With increment button.
Press ASET/OK button for
saving the parameter.
button to exit from
the parameters
section and turn
to main operation
screen.
°C
°F
PS
PO
AS
AO
°C
°F
PS
PO
AS
AO
Operation Screen
“Tune” and PSET value is shown on the main operation screen following one another.
PSET
P
ASET
PSET
P
ASET
Press PSET/P button to turn to the
main operation screen.
If Self Tune operation is finished without any problem, device saves new PID parameters to memory and runs. It changes parameter to
Canceling Self Tune operation :
1- If sensor breaks ; 2- If Self Tune operation can not be completed in 8 hours ; 3- While heating Self Tune operation is running, if process value becomes greater than Set value 4- While cooling Self Tune operation is running, if process value becomes lower than Set value ; 5- While cooling Self Tune operation is running, if user changes process set value ;
Self Tune operation is canceled
. Then device continues to run with former PID parameters
without changing PID parameters.
39
If power is off while operation continues, PID parameters and parameter are not changed. When power is off and then on, device starts to complete the operation.
Self Tune
Self Tune
If heating function and PID control form is selected for the system; If set value is greater than process value, process output becomes active till to the Temperature+[(Set - Temperature) / 2] value. When process value reaches to this value, process output reduces to 0% and it calculates the PID coefficients.
Process
Value
Process Set Value ( )
TunE
Start
Value
Process
Output
% 100
PID coefficients are determined
and system becomes stable
Start Value + [ ( Set - Start Value) ]
2
Time
If cooling function and PID control form is selected for the system; If set value is less than process value, process output becomes active till to the Temperature - [( Set - Temperature) / 2] value. When process value reaches to this value, process output is reduced to 0% and it starts to calculate PID coefficients.
Process
Value
tunE
Start
Value
Start Value - [ ( Set - Start Value) ]
PID coefficient are
determined
2
Process Set Value ( )
Time
Process
Output
% 100
For starting Tune ( Step Response Tuning ) operation :
i
1- Control form must be P,PI,PD or PID. 2- For heating tune, Process Value must be 5% of full scale lower than process set
value For cooling tune, process value must be 5% of full scale higher than process set value. 3- If Process Set Value is changed while Tune operation continues, tune operation is canceled.
40
7.2 Alarm Types
Alarm types which are explained in Section 6.5 Alarm Types Selection parameter are explained below:
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
PSET
P
Process High Alarm
PS
AS
ASET
Alarm
Output
ON
OFF
Process Value
Process Low Alarm
PS
AS
ASET
Alarm
Output
ON
OFF
Process Value
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
PSET
P
Deviation High Alarm
PS
AS
ASET
Alarm
Output
( + )
ON
OFF
Process Value
Deviation Low Alarm
PS
AS
ASET
Alarm
Output
( - )
ON
OFF
Process Value
41
°C
°F
PO
AO
PSET
P
Deviation Band Alarm
PS
AS
ASET
Alarm
Output
( + ) ( - )
ON
OFF
Process Value
°C
°F
PO
AO
PSET
P
Deviation Range Alarm
PS
AS
ASET
Alarm
Output
( + ) ( - )
ON
OFF
Process Value
42
8. Failure Messages in ESM-9920 Temperature Controller
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
PSET
P
°C
°F
PO
AO
1- Sensor failure in analog inputs. Sensor connection is wrong or there is no
sensor connection.
PS
AS
ASET
2- If value that is read from the analog input is lower
than process set low limit parameter , value on
PS
AS
ASET
the top display starts to blink like on the picture.
For this example in menu = ; = ; = and
°C
°F
PO
AO
PSET
P
PS
AS
ASET
=
Please refer to Section 6.3 for detailed
i
3- If value that is read from the analog input is higher
information about the parameter
°C
°F
than process set high limit parameter value ,
PS
AS
value on the top display starts to blink like on the picture.
PS
PO
AS
AO
PSET
P
ASET
For this example in menu = ; = ; = and
PSET
P
ASET
=
Please refer to Section 6.3 for detailed
i
°C
°F
4- If programming section entering password is different from “0” and user
information about the parameter
accesses to the parameter by ASET/OK button without entering the
PS
PO
AS
AO
password and wants to change a parameter, the warning message is shown on the bottom display as shown on the left. Device does not allow to do any changes without entering the password correctly.
PSET
P
°C
°F
PS
PO
AS
AO
PSET ASET
P
ASET
ASET
5- If user does not do anything for 120 seconds while
device is on programming section, device turns to operation screen.
°C
°F
PO
AO
PSET
P
PS
AS
°C
°F
PO
AO
PSET
P
6- In programming section, when Tune operation is selected , if warning
which is shown on the left blinks in operation screen for 10 seconds, it
PS
AS
ASET
means that start conditions is not okay for Tune operation.
43
9. Specifications
Device Type : Temperature Controller Housing&Mounting : 96mm x 96mm x 96mm 1/4 DIN 43700 plastic housing
for panel mounting. Panel cut-out is 92x92mm.
Protection Class : NEMA 4X (IP65 at front, IP20 at rear). Weight : Approximately 0.34 Kg. Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters
with none condensing humidity.
Storage/Operating Temperature : -40 C to +85 C / 0 C to +50 C
o o o o
Storage/Operating Humidity : 90 % max. (None condensing) Installation : Fixed installation Overvoltage Category : II Pollution Degree : II, office or workplace, none conductive pollution Operating Conditions : Continuous
Supply Voltage and Power : 230 V V (±15%) 50/60 Hz. 3VA
115 V V (±15%) 50/60 Hz. 3VA 24 V V (±15%) 50/60 Hz. 3VA 12 V V (±15%) 50/60 Hz. 3VA 12 V Z (±15%) 3W
Process Inputs : Universal input TC, RTD Thermocouple input types : Selectable by parameters
J ,K ,R ,S ,T (IEC584.1)(ITS90)
Thermoresistance input type : PT 100 (IEC751) (ITS90) Accuracy : ± 0,25% of full scale for Thermocouple and
Thermoresistance
Cold Junction Compensation : Automatically ± 0.1°C/1°C. Line Compensation : Maximum 10 .
W
Sensor Break Protection : Upscale Sampling Cycle : 3 samples per second Input Filter : 1.0 second Control Forms : Programmable ON / OFF, P, PI, PD or PID.
Relay Outputs : 2 pieces.Resistive load 5A@250V V (Programmable
control or alarm output) (Electrical Life : 100.000 Operation (Full Load))
Optional SSR Driver Output : Max 20mA@18V Z Process Display : 19 mm Red 4 digits LED display
Set Display : 10.8 mm Green 4 digits LED display LED Indicators : PS ( Process Set value), AS ( Alarm Set value ),
PO ( Process Output ) , AO ( Alarm Output ) °C ve °F unit leds