60 Watts
Special Features
• Universal input
• Less than 1U high
• 2" x 4" footprint
• Remote sense
• Overload and short circuit protection
• Adjustable Output Voltage
• High efficiency
• High MTBF
• Built in EMI filter (CISPR 22 Class B)
• LED power good indicator
• Input power <74 watts
• Complies with EN61000-3-2
• UL Class I approved
• UL Class II available, consult factory
Total Power: 55 - 60 Watts Input Voltage: 90 - 264 VAC
127 - 300VDC
# of Outputs: Single
Electrical Specifications
Safety
Input
Input range
90 - 264 VAC (wide range) 127 - 300VDC
Frequency 47-440 Hz
Inrush current <60A peak @ 230VAC, cold start @ 25°C
Input power <74 Watts
Efficiency 80% - 85% typical at full load
EMI/RFI
FCC Class B conducted; CISPR22 Class B conducted; EN55022
Class B conducted; VDE0878PT3 Class B conducted. Safety ground leakage current
275 uA @ 50/60 Hz, 264 VAC input
Output
Maximum power 60W for convection (LPS52, 55W)
Adjustment range ±20% minimum Hold-up time
10/20 ms 115/230 VAC Input line Overload protection
Short circuit protection on all outputs. Case overload protect-
ed @ 110-160% of normal rating Overvoltage protection
30-50% above nominal output
Remote sense Compensates for 0.5 V lead drop max. Will operate without
remote sense connected. Reverse connection protected.
UL UL 60601-1 CSA CSA-C22.2 No. 601.1-M90 VDE EN60601-1 CE LVD & EMC
RoHS
Page 2
Embedded Power for Business-Critical Continuity
Rev. 02.05.07
LPS50-M Series
2of 3
Mechanical Drawing
1.30"
[33.0]
1.72"
[43.8]
3.73" [94.7]
4.00"
[101.6]
0.16" [4.0]
2.00"
[50.8]
R22
SK1
TH
1
C1
F2
L1
F1
C
2
C N 1
C3
C5
L3
DB1
C32
C24
C30
C
1
7
C9
C18
Q6
T1
D4
R1
LED1
D2
T2
R
2
6
C22
SK2
C27
R
3A
R3
Q5
L2
VR1
DIP
T3.15A 2.5A
250VAC
2005
250VAC
T3.15A
+
GRN/
YEL
~~
B
A
HTSK_SEC
C4
2.5A
1
TP1
J
I
J3
F
H
J2
E
G
J1
D
TP2
J4
Mounting Hole Ø0.16"[4.0] 4 Places
GND
3
1
M1
04272000202X-JA
6
1
VR1
Output Voltage
Adjust Pot
M2
Operating temperature:
0° to 50°C ambient derate each output as 2.5% per degree from 50° to 70°C. -20°C start up
Storage temperature: -40°C to +85°C Electromagnetic susceptibility:
designed to meetEN61000-4;
-2, -3, -4, -5, -6, -8, -11 Level 3
Humidity: Operating; non-condensing 10% to 95% RH
Vibration: IEC68-2-6 to the levels of IEC721-3-2
MTBF demonstrated >550,000 hours at full load and 25°C ambient conditions
Environmental Specifications
Page 3
Rev. 02.05.07
LPS50-M Series
3of 3
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2007 Emerson Electric Co.
Embedded Power for Business-Critical Continuity
Emerson Network Power.
The global leader in enabling business-critical continuity.
EmersonNetworkPower. com
AC Power
Connectivity
DC Power
Embedded Power
Inbound Power Integrated Cabinet Solutions Outside Plant
Precision Cooling
Site Monitoring and Services
Astec
5810 Van Allen Way Carlsbad, CA 92008 USA Telephone: +1 760 930 4600 Facsimile: +1 760 930 0698
Waterfront Business Park Merry Hill, Dudley West Midlands, DY5 1LX United Kingdom Telephone: +44 (0) 1384 842 211 Facsimile: +44 (0) 1384 843 355
13-15, Shing Wan Road Tai Wai, Shatin, N. T. Hong Kong Telephone: +852 2699 2868 Facsimile: +852 2699 1770
For global contact, visit:
www.astecpower.com technicalsupport@astec.com
While every precaution has been taken to ensure accuracy and completeness in this literature, Emerson Network Power assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Ordering Information
MMooddeell
NNuummbbeerr
OOuuttppuutt
VVoollttaaggee
MMiinniimmuumm
LLooaadd
MMaaxxiimmuumm LLooaadd wwiitthh CCoonnvveeccttiioonn CCoooolliinngg
PPeeaakk LLooaadd RReegguullaattiioonn22
RRiippppllee
PP//PP ((PPAARRDD))33
LPS52-M 5V 0A 11A 12A ±2% 50mV
LPS53-M 12V 0A 5A 5.4A ±2% 120mV
LPS54-M 15V 0A 4A 4.4A ±2% 150mV
LPS55-M 24V 0A 2.5A 2.75A ±2% 240mV
LPS58-M 48V 0A 1.25A 1.35A ±2% 480mV
1. Peak current lasting <15 seconds with a maximum 10% duty cycle.
2. At 25°C including initial tolerance, line voltage, load currents and output voltages adjusted to factory settings.
3. Peak-to-peak with 20 MHz bandwidth and 10 μF (tantalum capacitor) in parallel with a 0.1 μF capacitor at rated line voltage and load ranges.
4. (T) Indicates Terminal Block option for input and output (instead of Molex type).
Connector LPS52-M LPS53-M LPS54-M LPS55-M LPS58-M
SK1-1 Line Line Line Line Line SK1-3 Neutral Neutral Neutral Neutral Neutral
SK2-1 +5 V +12 V +15V +24V +48 SK2-2 +5 V +12 V +15V +24V +48 SK2-3 Common Common Common Common Common SK2-4 Common Common Common Common Common SK2-5 -Sense -Sense -Sense -Sense -Sense SK2-6 +Sense +Sense +Sense +Sense +Sense
Mating Connectors (Not required for T models)
AC Input: Molex 09-50-8031 (USA)
09-91-0300 (UK) PINS: 08-52-0113
DC Outputs: Molex 09-50-8061 (USA)
09-91-0600 (UK) PINS: 08-52-0113
Astec Connector Kit #70-841-006, includes all of the above
Notes:
1. Specifications subject to change without notice.
2. All dimensions in inches (mm), tolerance is ±.02" (±0.5mm)
3. Mounting holes M1 and M2 should be grounded for EMI purposes.
4. Mounting hole M1 is safety ground connection.
5. Specifications are for convection rating at factory settings at 115 VAC
input, 25°C unless otherwise stated.
6. Warranty: 2 year
7. Weight: .41lbs/.18kg
Pin Assignments