Fisher™ 2500 and 2503 Controllers and Transmitters
Contents
Introduction2.................................
Scope of Manual2.............................
Description2.................................
Specifications2...............................
Educational Services2.........................
Installation
Sensor Assembly6............................
Uncrating6..................................
Controller/Transmitter Orientation7.............
Mounting Caged Sensor8......................
Mounting Cageless Sensor10...................
Side‐Mounted Sensor10....................
Top‐Mounted Sensor12....................
Supply and Output Pressure Connection12........
Supply Pressure12.........................
Controller/Transmitter Output Connection13..
Vent Assembly13.............................
Prestartup Checks14...........................
2500 Controller or 2500T Transmitter17..........
2500S Controller18...........................
2503 Controller18............................
Adjustments19...............................
Control Action19..........................
Level Adjustment (Controllers Only)19........
Zero Adjustment (Transmitters Only)20.......
Proportional Band Adjustment
(Except Transmitters and 2503
Controllers)20..........................
Specific Gravity Adjustment
(Transmitters Only)20...................
Calibration
Precalibration Requirements20.................
Wet Calibration20.........................
Dry Calibration21.........................
Controller/Transmitter and Torque Tube Arm
Disassembly21.........................
Determining the Amount of
Suspended Weight21....................
Calibration Procedure22.......................
2500 Controller and 2500T Transmitter23.....
2500S and 2503 Controllers25..............
Startup
2500 Controller27............................
2500T Transmitter27..........................
2500S Controller27...........................
2503 Controller27............................
Figure 1. Fisher 2500 or 2503 Controller/Transmitter
on 249 Caged Sensor
5....................................
2500 OR 2503
CONTROLLER/
TRANSMITTER
249 SENSOR
W8334
Principle of Operation27........................
2500 Controller or 2500T Transmitter28..........
20...................................
Proportional Valve28..........................
2500S Controller28...........................
2503 Controller29............................
Maintenance30................................
Troubleshooting31............................
Removing Controller/Transmitter from Sensor32..
Changing Mounting Methods33.................
Installing Controller/Transmitter on Sensor34.....
Replacing the Bourdon Tube35..................
Changing Action35............................
Relay Deadband Testing (2500 Controller
27......................................
or 2500T Transmitter Only)36................
Replacing the Proportional Valve37..............
Changing Relay37.............................
Parts Ordering37...............................
Parts List38...................................
www.Fisher.com
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
Introduction
Scope of Manual
This manual provides installation, operating, calibration, maintenance, and parts ordering information for 2500 and
2503 pneumatic controllers and transmitters used in combination with 249 displacer sensors.
Note
This manual does not include installation or maintenance procedures for the supply pressure regulator, sensor, or other devices.
For that information, refer to the appropriate instruction manual for the other device.
Do not install, operate, or maintain a 2500 or 2503 pneumatic controller/transmitter without being fully trained and
qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or
property damage, it is important to carefully read, understand, and follow all contents of this quick start guide,
including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson
sales office or Local Business Partner before proceeding.
Description
These instruments control or transmit the fluid level, the level of interface between two fluids, or the density (specific
gravity). Each unit consists of a 249 displacer‐type fluid level sensor and a 2500 or 2503 pneumatic controller or
transmitter. Figure 1 shows a typical controller‐sensor combination.
Specifications
Refer to table 1 for specifications.
Educational Services
For information on available courses for 2500 or 2503 controller/transmitter as well as a variety of other products,
contact:
2500—Proportional‐only controller
2500C—Proportional‐only controller with indicator
(see figure 10)
2500R—Reverse acting proportional‐only controller
2500S—Differential gap (snap acting) controller. See
changing controller action procedure and figure 15
2500T—Transmitter
2503—Differential gap controller without
proportional valve; for applications requiring very
little adjustment
Input Signal
Fluid Level or Fluid‐to‐Fluid Interface Level: From 0 to
100% of displacer length—standard lengths for all
sensors are 356 mm or 812 mm
(14 inches or 32 inches). Other lengths available
depending on sensor construction.
Fluid Density: From 0 to 100% of displacement force
change obtained with given displacer volume.
Standard volume for displacers are listed in table 2.
Output Signal
2500 Controller and 2500T Transmitter: 0.2 to 1 bar
(3 to 15 psig) or 0.4 to 2 bar (6 to 30 psig)
2500S and 2503 Differential Gap Controllers: 0 bar (0
psig) when switched off and full supply [1.4 or 2.4 bar
(20 or 35 psig) nominal depending on controller
output pressure range] when switched on.
Area Ratio of Relay Diaphragms
3:1
Supply Pressure Data
See table 3
(2)
Supply Medium
Air or Natural Gas
Supply medium must be clean, dry, and noncorrosive
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized
(continued)
Per ISO 8573-1
Maximum particle density size: Class 7
Oil content: Class 3
Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Maximum Supply Pressure
(2,3)
3 bar (45 psig) to the controller or transmitter. If
controller or transmitter is equipped with an
integrally mounted 67CFR filter/regulator, typical
supply pressure to the regulator is from 2.5 bar (35
psig) to 17 bar (250 psig), maximum. For supply
pressures to the filter/regulator, refer to the
appropriate regulator instruction manual.
Steady‐State Air Consumption
2500 Controllers and Transmitters (2500, 2500C,
2500R, 2500S, and 2500T): See table 3
2503 Controller: Vents only when relay is exhausting
Proportional Band Adjustment (Proportional‐Only
Controllers)
Full output pressure change adjustable over 10 to
100% of displacer length
(4)
Differential Gap Adjustment (Differential Gap
Controllers)
2500S Controller: Full output pressure change
adjustable from 20 to 100% of displacer length.
(4)
2503 Controller: Full output pressure change
adjustable over approximately 25 to 40% of displacer
(4)
length
Span Adjustment (2500T Transmitter)
Full output pressure change adjustable from 20 to
100% of displacer length
(4)
Set Point (controllers only) or Zero (transmitters
only) Adjustment
For proportional‐only controllers or transmitters,
level adjustment positions the set point or zero for
the fluid level, interface level, or displacer force
change (density) within the displacer length.
For differential gap controllers, level adjustment
simultaneously positions both ends of the gap within
the displacer length.
3
2500 and 2503 Controllers/Transmitters
June 2017
Table 1. Specifications (Continued)
Instruction Manual
D200124X012
Performance
Independent Linearity (transmitters only): 1% of
output pressure change for 100% span.
Hysteresis: 0.6% of output pressure change at 100%
proportional band, differential gap, or span
Typical Ambient Temperature Operating Influence
Output pressure changes 1.5% per 10_C (50_F)
change in temperature at 100% proportional band
when using a standard wall torque tube with 249
sensors
Repeatability: 0.2% of displacer length or
displacement force change
Deadband (except differential gap controllers
(5)
):
0.05% of proportional band or span
Typical Frequency Response: 4 Hz and 90 degree
phase shift at 100% proportional band with output
Hazardous Area Classification
2500 and 2503 controllers/transmitters comply with
the requirements of ATEX Group II Category 2 Gas
and Dust
piped to typical instrument bellows using 6.1 meters
(20 feet) of 1/4‐inch tubing
Ambient Operating Temperature Limits
For ambient temperature ranges and guidelines for
use of the optional heat insulator assembly, see figure
(3)
Supply and Output Connections
1/4 NPT internal
2. Relay temperature limits are:
Standard Construction: ‐40 to 71_C (‐40 to 160_F)
High‐Temperature Construction: ‐18 to 104_C
(0 to 220_F)
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. Controllers are field adjustable between direct or reverse action. The letter R in the type number indicates that the controller/transmitter shipped from the factory set for reverse action (see chang
ing controller action procedures). The letter C in the type number indicates that a pointer is attached to the torque tube shaft providing visual monitoring of torque tube motion.
2. Control and stability may be impaired if the maximum pressures are exceeded.
3. The pressure/temperature limits in this document, and any applicable standard or code limitation should not be exceeded.
4. These statements apply only to units sized to produce a full output change for a 100% level change at the maximum proportional band dial setting.
5. Adjusting the span of the differential gap controller is equivalent to adjusting the deadband.
Maximum Working Pressure (sensors only)
Refer to the appropriate sensor instruction manual
1. For 249W, with standard 812 mm (32‐inch) displacer.
2. For 249W, with standard 356 mm (14‐inch) displacer.
3. With standard 305 mm (12‐inch) flange‐face‐to‐displacer centerline dimension only.
Standard Volume
Liters
1.6
1.0
1.9
(3)
1.3
Table 3. Supply Pressure Data
STANDARD SUPPLY AND
OUTPUT SIGNAL RANGE
0.2 to 1 bar (3 to 15 psig)0 to 30 psig1.4204.2 scfh
0.4 to 2 bar (6 to 30 psig)0 to 60 psig2.4357 scfh
1. Consult your Emerson Automation Solutions sales office about gauges in other units.
2. Control and stability may be impaired if this pressure is exceeded.
3. At zero or maximum proportional band or specific gravity setting.
4. At setting in middle of proportional band or specific gravity range.
5. If air consumption is desired in normal m
4
OUTPUT
PRESSURE GAUGE
INDICATIONS
3
/hr at 0_C and 1.01325 bar, multiply scfh by 0.0258.
(1)
NORMAL OPERATING
SUPPLY PRESSURE
BarPsigMinimum
(2)
AIR CONSUMPTION AT
NORMAL OPERATING
SUPPLY PRESSURE
(3)
(5)
(5)
Maximum
27 scfh
42 scfh
Standard Volume
Cubic Inches
(1)
100
(2)
60
120
(3)
80
(4)
(5)
(5)
SUPPLY PRESSURE
3 bar (45 psig)
3 bar (45 psig)
MAXIMUM
Instruction Manual
PROCESS TEMPERATURE ( C)
D200124X012
Figure 2. Guidelines for Use of Optional Heat Insulator Assembly
2500 and 2503 Controllers/Transmitters
June 2017
AMBIENT TEMPERATURE (_C)
01020
−10
−18
1100
_
800
HEAT INSULATOR
3040506070
REQUIRED
400
0
−20
−40
PROCESS TEMPERATURE ( F)
NO INSULATOR NECESSARY
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE
PROCESS TEMPERATURE, ICE FORMATION MAY CAUSE INSTRUMENT
MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
020406080100120140160
AMBIENT TEMPERATURE (_F)
STANDARD CONTROLLER OR TRANSMITTER
NOTE:
FOR APPLICATIONS BELOW -29_C (-20_F), BE SURE THE SENSOR MATERIALS OF CONSTRUCTION
ARE APPROPRIATE FOR THE SERVICE TEMPERATURE.
CV6190-E
B1413‐3
TOO
HOT
71
593
500
_
_
400
300
200
100
−18
−29
−40
PROCESS TEMPERATURE ( C)
PROCESS TEMPERATURE ( F)
AMBIENT TEMPERATURE (_C)
0
1020
3040506070
1100
800
400
−18
−10
HEAT INSULATOR
REQUIRED
NO INSULATOR NECESSARY
0
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS
TEMPERATURE, ICE FORMATION MAY CAUSE INSTRUMENT MALFUNCTION AND
REDUCE INSULATOR EFFECTIVENESS.)
−20
020406080100 120 140200
AMBIENT TEMPERATURE (_F)
HIGH‐TEMPERATURE CONTROLLER OR TRANSMITTER
8090
180160
thank
Table 4. Displacer and Torque Tube Materials
PartStandard MaterialOther Materials
Displacer304 Stainless Steel316 Stainless Steel, N10276, N04400, Plastic, and Special Alloys
Displacer Stem, Driver Bearing,
Displacer Rod and Driver
Torque TubeN05500
1. N05500 is not recommended for spring applications above 232_C (450_F). Contact your Emerson sales office or application engineer if temperatures exceeding this limit are required.
316 Stainless SteelN10276, N04400, other Austenitic Stainless Steels, and Special Alloys
(1)
316 Stainless Steel, N06600, N10276
100
TOO
HOT
105
220
593
500
400
300
200
100
0
_
Installation
2500 and 2503 controller/transmitters work in combination with 249 displacer‐type sensors. The factory attaches the
controller/transmitter to the sensor, unless it is ordered separately.
If using natural gas as the pneumatic supply medium, natural gas will be used in the pressure connections of the unit
to any connected equipment. The unit will vent natural gas into the surrounding atmosphere.
WARNING
Always wear protective clothing, gloves, and eyewear when performing any installation operations to avoid personal
injury.
Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this
instruction manual.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed
by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
5
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
WARNING
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and
preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of the following:
Remote venting of the unit, re‐evaluating the hazardous area classification, ensuring adequate ventilation, and the
removal of any ignition sources. For information on remote venting of this controller refer to page 13.
Sensor Assembly
Table 2 lists sensors recommended for use with controller/transmitters. Table 4 contains displacer and torque tube
materials. For sensor installation and maintenance, refer to the appropriate sensor instruction manual.
WARNING
When replacing the sensor assembly, the displacer may retain process fluid or pressure. Personal injury or property
damage may occur due to sudden release of the pressure. Contact with hazardous fluid, fire, or explosion can be caused by
puncturing, heating, or repairing a displacer retaining process pressure or fluid. This danger may not be readily apparent
when disassembling the sensor assembly or removing the displacer. Before disassembling the sensor or removing the
displacer, observe the more specific warning provided in the sensor instruction manual.
Uncrating
Unless ordered separately, the controller/transmitter is attached to the sensor when shipped. Carefully uncrate the
assembly.
CAUTION
Sensors used for interface or density control may be so large and heavy that the torque tube cannot fully support their
weight in air. On the 249VS, a travel stop is used to prevent damage. Do not remove this travel stop assembly without first
removing the displacer from the displacer rod. Refer to the appropriate instruction manual for 249 cageless sensors.
Note
Caged sensors have rods and blocks installed at each end of the displacers to protect the displacers in shipping. Remove these
parts before you install the sensor to allow the displacer to function properly.
Caged sensors come with the displacer installed in the cage. If a tubular gauge glass is ordered with the sensor, the
gauge glass is crated separately and must be installed at the site. A damping plate is installed in the lower screwed or
flanged connection (see figure 3) to provide more stable operation. Be certain that the cage equalizing connections
and the damping plate are not plugged by foreign material.
6
Instruction Manual
D200124X012
Figure 3. Damping Plate Location
W2141-1B
2500 and 2503 Controllers/Transmitters
June 2017
DISPLACER
CAGE
SCREWED
CONNECTION
DAMPING PLATE
W0144-1
FLANGED
CONNECTION
A cageless sensor comes with its displacer separated from the sensor assembly. Displacers longer than 813 mm (32
inches) come in a separate crate. Shorter displacers come in the same crate as the sensor, but are not attached to their
displacer rods. Inspect the displacer to ensure it is not dented. A dent may reduce the pressure rating of the displacer.
If a displacer is dented, replace it.
Controller/Transmitter Orientation
The controller/transmitter attaches to the sensor in one of the mounting positions shown in figure 4. Right‐hand
mounting is with the controller or transmitter case to the right of the displacer when you look at the front of the case;
left‐hand mounting is with the case to the left of the displacer. The mounting position can be changed in the field.
Changing this mounting position changes the control action from direct to reverse, or vice versa.
All caged sensors have a rotatable head. That is, the controller/transmitter may be positioned at any of eight alternate
positions around the cage as indicated by the numbers 1 through 8 in figure 4. To rotate the head, remove the head
flange bolts and nuts and position the head as desired.
7
2500 and 2503 Controllers/Transmitters
June 2017
Figure 4. Cage Head Mounting Positions
Instruction Manual
D200124X012
RIGHT‐HAND MOUNTING
1 67CFR FILTER/REGULATOR.
AH9150-A
A2613-2
LEFT‐HAND MOUNTING
Mounting Caged Sensor
Note
Install the cage so that it is plumb; the displacer must not touch the cage wall. If the displacer touches the cage wall, the unit will
transmit an erroneous output signal.
Note
If the controller/transmitter is not mounted on the sensor, refer to the Installing Controller/Transmitter on Sensor procedures in
the Maintenance section. This section also provides instructions for adding a heat insulator to a unit.
Cage connections normally are either NPS 1‐1/2 or 2, screwed or flanged. Figure 5 shows the combinations. With
flanged connections, use standard gaskets or other flat‐sheet gaskets compatible with the process fluid. Spiral‐wound
gaskets without compression‐controlling centering rings cannot be used for flange connections.
8
Instruction Manual
D200124X012
Figure 5. Cage Connection Styles
2500 and 2503 Controllers/Transmitters
June 2017
STYLE 1: TOP
AND BOTTOM
SCREWED: S1
FLANGED: F1
A1271-2
STYLE 2: TOP
AND LOWER SIDE
SCREWED: S2
FLANGED: F2
STYLE 3: UPPER
AND LOWER SIDE
SCREWED: S3
FLANGED: F3
STYLE 4: UPPER
SIDE AND BOTTOM
SCREWED: S4
FLANGED: F4
As shown in figure 6, mount the cage by running equalizing lines between the cage connections and the vessel. A
shutoff or hand valve with a 1‐1/2 inch diameter or larger port should be installed in each of the equalizing lines. Also
install a drain between the cage and shutoff or hand valve whenever the bottom cage line has a fluid‐trapping low
point.
Figure 6. Caged Sensor Mounting
CENTER OF LIQUID
OR INTERFACE LEVEL
DF5379‐A
A1883‐2
EQUALIZING LINE
SHUTOFF
VALVES
DRAIN VALVE
EQUALIZING LINE
9
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
On fluid or interface level applications, position the sensor so that the center line on the cage (see figure 6) is as close
as possible to the center of the fluid level or interface level range being measured. Also consider installing a gauge
glass on the vessel, or on the sensor cage (if the cage is tapped for a gauge).
Mounting Cageless Sensor
Note
If a stillwell is used, install it plumb so that the displacer does not touch the wall of the stillwell. If the displacer touches the wall,
the unit will transmit an erroneous output signal.
Since the displacer hangs inside the vessel, provide a stillwell around the displacer if the fluid is in a state of continuous
agitation to avoid excessive turbulence around the displacer.
Note
Displacers used in an interface level application must be completely submerged during operation. If displacers aren't completely
submerged, they will not calibrate or perform properly. To obtain the desired controller or transmitter sensitivity may require
using either a thin‐wall torque tube, an oversized displacer, or both.
Note
If the controller/transmitter is not mounted on the sensor, refer to the Installing Controller/Transmitter on Sensor procedures in
the Maintenance section. This section also provides instructions for adding a heat insulator to a unit.
Attach a cageless sensor to a flanged connection on the vessel as shown in figure 7. For interface or fluid level
applications, install a gauge glass on the vessel.
Side‐Mounted Sensor
If a stillwell is required (see figure 7), attach the displacer to the displacer rod from inside the vessel.
Connect the displacer as shown in figure 8, locking the assembly with the cotter spring provided. If a stillwell is not
required, attach the displacer rod before mounting the sensor on the vessel. Then, you can swing the displacer out
horizontally for insertion into the vessel. However, once the sensor is installed and the displacer drops to a vertical
position, the displacer may not be capable of being withdrawn for servicing later. Be sure there is another access to the
displacer to permit swinging it to a horizontal position or to permit disconnecting it from the displacer rod.
If an extension is used between the displacer spud and the displacer stem end piece, make sure the nuts are tight at
each end of the displacer stem extension. Install and tighten suitable bolting or cap screws in the flanged connection
to complete the installation.
10
Instruction Manual
D200124X012
Figure 7. Cageless Sensor Mounting
2500 and 2503 Controllers/Transmitters
June 2017
TOP MOUNTED
SIDE MOUNTED
W9517‐1
SIDE VIEW (SHOWING STILLWELL)
Figure 8. Displacer and Displacer Rod Connections
COTTER SPRING
DISPLACER ROD
DISPLACER
STEM EXTENSION
LOCKING NUTS
DISPLACER
SPUD
CF5380‐A
A3893
SIDE VIEW (WITHOUT STILLWELL)
COTTER SPRING
W9357
249VS
DISPLACER SPUD
W0228‐1A
DISPLACER ROD
ALL OTHER TYPES
11
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
Top‐Mounted Sensor
CAUTION
If inserting the displacer into the vessel before attaching to the displacer rod, provide a means of supporting the displacer
to prevent it from dropping into the vessel and suffering damage.
Figure 7 shows an example of a top‐mounted cageless sensor. You may attach the displacer to the displacer rod before
installing the sensor on the vessel. If the displacer diameter is small enough, you may install a long or sectionalized
displacer through the sensor head access hole after the sensor is installed on the vessel. Connect the displacer as
shown in figure 8, locking the assembly with the cotter springs provided. If a stem extension is used between the
displacer spud and the stem end piece, make sure the nuts are tight at each end of the stem. Install and tighten
suitable cap screws in the flanged connection to complete the installation.
A special travel stop may be provided on top‐mounted sensors to aid in servicing of the sensor. This option prevents
dropping the displacer and stem when the displacer rod is disconnected.
Supply and Output Pressure Connections
WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure, do not install any system
component where service conditions could exceed the limits given in this manual. Use pressure‐relieving devices as
required by government or accepted industry codes and good engineering practices.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed
by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
Figure 9 shows dimensions, locations, and connections for controller/transmitter installation. All pressure connections
to the controller/transmitter are 1/4 NPT internal.
Supply Pressure
WARNING
Personal injury or property damage may occur from an uncontrolled process if the supply medium is not clean, dry, oil‐free
air, or noncorrosive gas. While use and regular maintenance of a filter that removes particles larger than 40 micrometers in
diameter will suffice in most applications, check with an Emerson Automation Solutions field office and industry
instrument air quality standards for use with corrosive air or if you are unsure about the proper amount or method of air
filtration or filter maintenance.
Supply pressure medium must be clean, dry, and noncorrosive and meet the requirements of ISA Standard 7.0.01 or
ISO 8573-1. A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5
12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.