Emerson Fisher 2503, Fisher 2500 Instruction Manual

Instruction Manual
D200124X012
2500 and 2503 Controllers/Transmitters
June 2017
Fisher™ 2500 and 2503 Controllers and Transmitters
Contents
Introduction 2.................................
Scope of Manual 2.............................
Description 2.................................
Educational Services 2.........................
Installation
Sensor Assembly 6............................
Uncrating 6..................................
Controller/Transmitter Orientation 7.............
Mounting Caged Sensor 8......................
Mounting Cageless Sensor 10...................
Side‐Mounted Sensor 10....................
Top‐Mounted Sensor 12....................
Supply and Output Pressure Connection 12........
Supply Pressure 12.........................
Controller/Transmitter Output Connection 13..
Vent Assembly 13.............................
Prestartup Checks 14...........................
2500 Controller or 2500T Transmitter 17..........
2500S Controller 18...........................
2503 Controller 18............................
Adjustments 19...............................
Control Action 19..........................
Level Adjustment (Controllers Only) 19........
Zero Adjustment (Transmitters Only) 20.......
Proportional Band Adjustment
(Except Transmitters and 2503
Controllers) 20..........................
Specific Gravity Adjustment
(Transmitters Only) 20...................
Calibration
Precalibration Requirements 20.................
Wet Calibration 20.........................
Dry Calibration 21.........................
Controller/Transmitter and Torque Tube Arm
Disassembly 21.........................
Determining the Amount of
Suspended Weight 21....................
Calibration Procedure 22.......................
2500 Controller and 2500T Transmitter 23.....
2500S and 2503 Controllers 25..............
Startup
2500 Controller 27............................
2500T Transmitter 27..........................
2500S Controller 27...........................
2503 Controller 27............................
Figure 1. Fisher 2500 or 2503 Controller/Transmitter on 249 Caged Sensor
5....................................
2500 OR 2503 CONTROLLER/ TRANSMITTER
249 SENSOR
W8334
Principle of Operation 27........................
2500 Controller or 2500T Transmitter 28..........
20...................................
Proportional Valve 28..........................
2500S Controller 28...........................
2503 Controller 29............................
Maintenance 30................................
Troubleshooting 31............................
Removing Controller/Transmitter from Sensor 32..
Changing Mounting Methods 33.................
Installing Controller/Transmitter on Sensor 34.....
Replacing the Bourdon Tube 35..................
Changing Action 35............................
Relay Deadband Testing (2500 Controller
27......................................
or 2500T Transmitter Only) 36................
Replacing the Proportional Valve 37..............
Changing Relay 37.............................
Parts Ordering 37...............................
Parts List 38...................................
www.Fisher.com
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
Introduction
Scope of Manual
This manual provides installation, operating, calibration, maintenance, and parts ordering information for 2500 and 2503 pneumatic controllers and transmitters used in combination with 249 displacer sensors.
Note
This manual does not include installation or maintenance procedures for the supply pressure regulator, sensor, or other devices. For that information, refer to the appropriate instruction manual for the other device.
Do not install, operate, or maintain a 2500 or 2503 pneumatic controller/transmitter without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or
property damage, it is important to carefully read, understand, and follow all contents of this quick start guide, including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson
sales office or Local Business Partner before proceeding.
Description
These instruments control or transmit the fluid level, the level of interface between two fluids, or the density (specific gravity). Each unit consists of a 249 displacer‐type fluid level sensor and a 2500 or 2503 pneumatic controller or transmitter. Figure 1 shows a typical controller‐sensor combination.
Specifications
Refer to table 1 for specifications.
Educational Services
For information on available courses for 2500 or 2503 controller/transmitter as well as a variety of other products, contact:
Emerson Automation Solutions Educational Services - Registration Phone: 1-641-754-3771 or 1-800-338-8158 E-mail: education@emerson.com emerson.com/fishervalvetraining
2
Instruction Manual
D200124X012
Table 1. Specifications
2500 and 2503 Controllers/Transmitters
June 2017
Available Configurations
(1)
2500—Proportional‐only controller 2500C—Proportional‐only controller with indicator
(see figure 10)
2500R—Reverse acting proportional‐only controller 2500S—Differential gap (snap acting) controller. See
changing controller action procedure and figure 15
2500T—Transmitter 2503—Differential gap controller without
proportional valve; for applications requiring very little adjustment
Input Signal
Fluid Level or Fluid‐to‐Fluid Interface Level: From 0 to 100% of displacer length—standard lengths for all sensors are 356 mm or 812 mm (14 inches or 32 inches). Other lengths available depending on sensor construction.
Fluid Density: From 0 to 100% of displacement force change obtained with given displacer volume. Standard volume for displacers are listed in table 2.
Output Signal
2500 Controller and 2500T Transmitter: 0.2 to 1 bar (3 to 15 psig) or 0.4 to 2 bar (6 to 30 psig)
2500S and 2503 Differential Gap Controllers: 0 bar (0 psig) when switched off and full supply [1.4 or 2.4 bar (20 or 35 psig) nominal depending on controller output pressure range] when switched on.
Area Ratio of Relay Diaphragms
3:1
Supply Pressure Data
See table 3
(2)
Supply Medium
Air or Natural Gas Supply medium must be clean, dry, and noncorrosive
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized
(continued)
Per ISO 8573-1
Maximum particle density size: Class 7 Oil content: Class 3 Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Maximum Supply Pressure
(2,3)
3 bar (45 psig) to the controller or transmitter. If controller or transmitter is equipped with an integrally mounted 67CFR filter/regulator, typical supply pressure to the regulator is from 2.5 bar (35 psig) to 17 bar (250 psig), maximum. For supply pressures to the filter/regulator, refer to the appropriate regulator instruction manual.
Steady‐State Air Consumption
2500 Controllers and Transmitters (2500, 2500C, 2500R, 2500S, and 2500T): See table 3
2503 Controller: Vents only when relay is exhausting
Proportional Band Adjustment (Proportional‐Only Controllers)
Full output pressure change adjustable over 10 to 100% of displacer length
(4)
Differential Gap Adjustment (Differential Gap Controllers)
2500S Controller: Full output pressure change adjustable from 20 to 100% of displacer length.
(4)
2503 Controller: Full output pressure change adjustable over approximately 25 to 40% of displacer
(4)
length
Span Adjustment (2500T Transmitter)
Full output pressure change adjustable from 20 to 100% of displacer length
(4)
Set Point (controllers only) or Zero (transmitters only) Adjustment
For proportional‐only controllers or transmitters, level adjustment positions the set point or zero for the fluid level, interface level, or displacer force change (density) within the displacer length. For differential gap controllers, level adjustment simultaneously positions both ends of the gap within the displacer length.
3
2500 and 2503 Controllers/Transmitters
June 2017
Table 1. Specifications (Continued)
Instruction Manual
D200124X012
Performance
Independent Linearity (transmitters only): 1% of output pressure change for 100% span. Hysteresis: 0.6% of output pressure change at 100% proportional band, differential gap, or span
Typical Ambient Temperature Operating Influence
Output pressure changes 1.5% per 10_C (50_F) change in temperature at 100% proportional band when using a standard wall torque tube with 249 sensors
Repeatability: 0.2% of displacer length or displacement force change
Deadband (except differential gap controllers
(5)
):
0.05% of proportional band or span Typical Frequency Response: 4 Hz and 90 degree phase shift at 100% proportional band with output
Hazardous Area Classification
2500 and 2503 controllers/transmitters comply with the requirements of ATEX Group II Category 2 Gas
and Dust piped to typical instrument bellows using 6.1 meters (20 feet) of 1/4‐inch tubing
Ambient Operating Temperature Limits
For ambient temperature ranges and guidelines for use of the optional heat insulator assembly, see figure
(3)
Supply and Output Connections
1/4 NPT internal
2. Relay temperature limits are:
Standard Construction: ‐40 to 71_C (‐40 to 160_F) High‐Temperature Construction: ‐18 to 104_C
(0 to 220_F)
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. Controllers are field adjustable between direct or reverse action. The letter R in the type number indicates that the controller/transmitter shipped from the factory set for reverse action (see chang ing controller action procedures). The letter C in the type number indicates that a pointer is attached to the torque tube shaft providing visual monitoring of torque tube motion.
2. Control and stability may be impaired if the maximum pressures are exceeded.
3. The pressure/temperature limits in this document, and any applicable standard or code limitation should not be exceeded.
4. These statements apply only to units sized to produce a full output change for a 100% level change at the maximum proportional band dial setting.
5. Adjusting the span of the differential gap controller is equivalent to adjusting the deadband.
Maximum Working Pressure (sensors only)
Refer to the appropriate sensor instruction manual
Table 2. Standard Displacer Volumes
Sensor
249, 249B, 249BF, 249BP, 249K, 249P, 249W 249C, 249CP, 249W 249L 249VS
1. For 249W, with standard 812 mm (32‐inch) displacer.
2. For 249W, with standard 356 mm (14‐inch) displacer.
3. With standard 305 mm (12‐inch) flange‐face‐to‐displacer centerline dimension only.
Standard Volume
Liters
1.6
1.0
1.9
(3)
1.3
Table 3. Supply Pressure Data
STANDARD SUPPLY AND
OUTPUT SIGNAL RANGE
0.2 to 1 bar (3 to 15 psig) 0 to 30 psig 1.4 20 4.2 scfh
0.4 to 2 bar (6 to 30 psig) 0 to 60 psig 2.4 35 7 scfh
1. Consult your Emerson Automation Solutions sales office about gauges in other units.
2. Control and stability may be impaired if this pressure is exceeded.
3. At zero or maximum proportional band or specific gravity setting.
4. At setting in middle of proportional band or specific gravity range.
5. If air consumption is desired in normal m
4
OUTPUT
PRESSURE GAUGE
INDICATIONS
3
/hr at 0_C and 1.01325 bar, multiply scfh by 0.0258.
(1)
NORMAL OPERATING
SUPPLY PRESSURE
Bar Psig Minimum
(2)
AIR CONSUMPTION AT
NORMAL OPERATING
SUPPLY PRESSURE
(3)
(5)
(5)
Maximum
27 scfh
42 scfh
Standard Volume
Cubic Inches
(1)
100
(2)
60
120
(3)
80
(4)
(5)
(5)
SUPPLY PRESSURE
3 bar (45 psig)
3 bar (45 psig)
MAXIMUM
Instruction Manual
PROCESS TEMPERATURE ( C)
D200124X012
Figure 2. Guidelines for Use of Optional Heat Insulator Assembly
2500 and 2503 Controllers/Transmitters
June 2017
AMBIENT TEMPERATURE (_C)
01020
10
18
1100
_
800
HEAT INSULATOR
30 40 50 60 70
REQUIRED
400
0
20
40
PROCESS TEMPERATURE ( F)
NO INSULATOR NECESSARY
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS TEMPERATURE, ICE FORMATION MAY CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
0 20 40 60 80 100 120 140 160
AMBIENT TEMPERATURE (_F)
STANDARD CONTROLLER OR TRANSMITTER
NOTE: FOR APPLICATIONS BELOW -29_C (-20_F), BE SURE THE SENSOR MATERIALS OF CONSTRUCTION ARE APPROPRIATE FOR THE SERVICE TEMPERATURE.
CV6190-E B1413‐3
TOO HOT
71
593 500
_
_
400 300
200 100
18
29
40
PROCESS TEMPERATURE ( C)
PROCESS TEMPERATURE ( F)
AMBIENT TEMPERATURE (_C)
0
10 20
30 40 50 60 70
1100
800
400
18
10
HEAT INSULATOR REQUIRED
NO INSULATOR NECESSARY
0
USE INSULATOR (CAUTION! IF AMBIENT DEWPOINT IS ABOVE PROCESS TEMPERATURE, ICE FORMATION MAY CAUSE INSTRUMENT MALFUNCTION AND REDUCE INSULATOR EFFECTIVENESS.)
20 0 20 40 60 80 100 120 140 200
AMBIENT TEMPERATURE (_F)
HIGH‐TEMPERATURE CONTROLLER OR TRANSMITTER
80 90
180160
thank
Table 4. Displacer and Torque Tube Materials
Part Standard Material Other Materials
Displacer 304 Stainless Steel 316 Stainless Steel, N10276, N04400, Plastic, and Special Alloys
Displacer Stem, Driver Bearing, Displacer Rod and Driver
Torque Tube N05500
1. N05500 is not recommended for spring applications above 232_C (450_F). Contact your Emerson sales office or application engineer if temperatures exceeding this limit are required.
316 Stainless Steel N10276, N04400, other Austenitic Stainless Steels, and Special Alloys
(1)
316 Stainless Steel, N06600, N10276
100
TOO HOT
105
220
593 500 400 300 200 100 0
_
Installation
2500 and 2503 controller/transmitters work in combination with 249 displacer‐type sensors. The factory attaches the controller/transmitter to the sensor, unless it is ordered separately.
If using natural gas as the pneumatic supply medium, natural gas will be used in the pressure connections of the unit to any connected equipment. The unit will vent natural gas into the surrounding atmosphere.
WARNING
Always wear protective clothing, gloves, and eyewear when performing any installation operations to avoid personal injury.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this instruction manual.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
5
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
WARNING
Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of the following: Remote venting of the unit, re‐evaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any ignition sources. For information on remote venting of this controller refer to page 13.
Sensor Assembly
Table 2 lists sensors recommended for use with controller/transmitters. Table 4 contains displacer and torque tube materials. For sensor installation and maintenance, refer to the appropriate sensor instruction manual.
WARNING
When replacing the sensor assembly, the displacer may retain process fluid or pressure. Personal injury or property damage may occur due to sudden release of the pressure. Contact with hazardous fluid, fire, or explosion can be caused by puncturing, heating, or repairing a displacer retaining process pressure or fluid. This danger may not be readily apparent when disassembling the sensor assembly or removing the displacer. Before disassembling the sensor or removing the displacer, observe the more specific warning provided in the sensor instruction manual.
Uncrating
Unless ordered separately, the controller/transmitter is attached to the sensor when shipped. Carefully uncrate the assembly.
CAUTION
Sensors used for interface or density control may be so large and heavy that the torque tube cannot fully support their weight in air. On the 249VS, a travel stop is used to prevent damage. Do not remove this travel stop assembly without first removing the displacer from the displacer rod. Refer to the appropriate instruction manual for 249 cageless sensors.
Note
Caged sensors have rods and blocks installed at each end of the displacers to protect the displacers in shipping. Remove these parts before you install the sensor to allow the displacer to function properly.
Caged sensors come with the displacer installed in the cage. If a tubular gauge glass is ordered with the sensor, the gauge glass is crated separately and must be installed at the site. A damping plate is installed in the lower screwed or flanged connection (see figure 3) to provide more stable operation. Be certain that the cage equalizing connections and the damping plate are not plugged by foreign material.
6
Instruction Manual
D200124X012
Figure 3. Damping Plate Location
W2141-1B
2500 and 2503 Controllers/Transmitters
June 2017
DISPLACER
CAGE
SCREWED CONNECTION
DAMPING PLATE
W0144-1
FLANGED CONNECTION
A cageless sensor comes with its displacer separated from the sensor assembly. Displacers longer than 813 mm (32 inches) come in a separate crate. Shorter displacers come in the same crate as the sensor, but are not attached to their displacer rods. Inspect the displacer to ensure it is not dented. A dent may reduce the pressure rating of the displacer. If a displacer is dented, replace it.
Controller/Transmitter Orientation
The controller/transmitter attaches to the sensor in one of the mounting positions shown in figure 4. Right‐hand mounting is with the controller or transmitter case to the right of the displacer when you look at the front of the case; left‐hand mounting is with the case to the left of the displacer. The mounting position can be changed in the field. Changing this mounting position changes the control action from direct to reverse, or vice versa.
All caged sensors have a rotatable head. That is, the controller/transmitter may be positioned at any of eight alternate positions around the cage as indicated by the numbers 1 through 8 in figure 4. To rotate the head, remove the head flange bolts and nuts and position the head as desired.
7
2500 and 2503 Controllers/Transmitters
June 2017
Figure 4. Cage Head Mounting Positions
Instruction Manual
D200124X012
RIGHT‐HAND MOUNTING
1 67CFR FILTER/REGULATOR.
AH9150-A A2613-2
LEFT‐HAND MOUNTING
Mounting Caged Sensor
Note
Install the cage so that it is plumb; the displacer must not touch the cage wall. If the displacer touches the cage wall, the unit will transmit an erroneous output signal.
Note
If the controller/transmitter is not mounted on the sensor, refer to the Installing Controller/Transmitter on Sensor procedures in the Maintenance section. This section also provides instructions for adding a heat insulator to a unit.
Cage connections normally are either NPS 1‐1/2 or 2, screwed or flanged. Figure 5 shows the combinations. With flanged connections, use standard gaskets or other flat‐sheet gaskets compatible with the process fluid. Spiral‐wound gaskets without compression‐controlling centering rings cannot be used for flange connections.
8
Instruction Manual
D200124X012
Figure 5. Cage Connection Styles
2500 and 2503 Controllers/Transmitters
June 2017
STYLE 1: TOP AND BOTTOM
SCREWED: S1 FLANGED: F1
A1271-2
STYLE 2: TOP AND LOWER SIDE
SCREWED: S2 FLANGED: F2
STYLE 3: UPPER AND LOWER SIDE
SCREWED: S3 FLANGED: F3
STYLE 4: UPPER SIDE AND BOTTOM
SCREWED: S4 FLANGED: F4
As shown in figure 6, mount the cage by running equalizing lines between the cage connections and the vessel. A shutoff or hand valve with a 1‐1/2 inch diameter or larger port should be installed in each of the equalizing lines. Also install a drain between the cage and shutoff or hand valve whenever the bottom cage line has a fluid‐trapping low point.
Figure 6. Caged Sensor Mounting
CENTER OF LIQUID OR INTERFACE LEVEL
DF5379‐A A1883‐2
EQUALIZING LINE
SHUTOFF VALVES
DRAIN VALVE
EQUALIZING LINE
9
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
On fluid or interface level applications, position the sensor so that the center line on the cage (see figure 6) is as close as possible to the center of the fluid level or interface level range being measured. Also consider installing a gauge glass on the vessel, or on the sensor cage (if the cage is tapped for a gauge).
Mounting Cageless Sensor
Note
If a stillwell is used, install it plumb so that the displacer does not touch the wall of the stillwell. If the displacer touches the wall, the unit will transmit an erroneous output signal.
Since the displacer hangs inside the vessel, provide a stillwell around the displacer if the fluid is in a state of continuous agitation to avoid excessive turbulence around the displacer.
Note
Displacers used in an interface level application must be completely submerged during operation. If displacers aren't completely submerged, they will not calibrate or perform properly. To obtain the desired controller or transmitter sensitivity may require using either a thin‐wall torque tube, an oversized displacer, or both.
Note
If the controller/transmitter is not mounted on the sensor, refer to the Installing Controller/Transmitter on Sensor procedures in the Maintenance section. This section also provides instructions for adding a heat insulator to a unit.
Attach a cageless sensor to a flanged connection on the vessel as shown in figure 7. For interface or fluid level applications, install a gauge glass on the vessel.
Side‐Mounted Sensor
If a stillwell is required (see figure 7), attach the displacer to the displacer rod from inside the vessel.
Connect the displacer as shown in figure 8, locking the assembly with the cotter spring provided. If a stillwell is not required, attach the displacer rod before mounting the sensor on the vessel. Then, you can swing the displacer out horizontally for insertion into the vessel. However, once the sensor is installed and the displacer drops to a vertical position, the displacer may not be capable of being withdrawn for servicing later. Be sure there is another access to the displacer to permit swinging it to a horizontal position or to permit disconnecting it from the displacer rod.
If an extension is used between the displacer spud and the displacer stem end piece, make sure the nuts are tight at each end of the displacer stem extension. Install and tighten suitable bolting or cap screws in the flanged connection to complete the installation.
10
Instruction Manual
D200124X012
Figure 7. Cageless Sensor Mounting
2500 and 2503 Controllers/Transmitters
June 2017
TOP MOUNTED
SIDE MOUNTED
W9517‐1
SIDE VIEW (SHOWING STILLWELL)
Figure 8. Displacer and Displacer Rod Connections
COTTER SPRING
DISPLACER ROD
DISPLACER
STEM EXTENSION
LOCKING NUTS
DISPLACER SPUD
CF5380‐A A3893
SIDE VIEW (WITHOUT STILLWELL)
COTTER SPRING
W9357
249VS
DISPLACER SPUD
W0228‐1A
DISPLACER ROD
ALL OTHER TYPES
11
2500 and 2503 Controllers/Transmitters
June 2017
Instruction Manual
D200124X012
Top‐Mounted Sensor
CAUTION
If inserting the displacer into the vessel before attaching to the displacer rod, provide a means of supporting the displacer to prevent it from dropping into the vessel and suffering damage.
Figure 7 shows an example of a top‐mounted cageless sensor. You may attach the displacer to the displacer rod before installing the sensor on the vessel. If the displacer diameter is small enough, you may install a long or sectionalized displacer through the sensor head access hole after the sensor is installed on the vessel. Connect the displacer as shown in figure 8, locking the assembly with the cotter springs provided. If a stem extension is used between the displacer spud and the stem end piece, make sure the nuts are tight at each end of the stem. Install and tighten suitable cap screws in the flanged connection to complete the installation.
A special travel stop may be provided on top‐mounted sensors to aid in servicing of the sensor. This option prevents dropping the displacer and stem when the displacer rod is disconnected.
Supply and Output Pressure Connections
WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure, do not install any system component where service conditions could exceed the limits given in this manual. Use pressure‐relieving devices as required by government or accepted industry codes and good engineering practices.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
Figure 9 shows dimensions, locations, and connections for controller/transmitter installation. All pressure connections to the controller/transmitter are 1/4 NPT internal.
Supply Pressure
WARNING
Personal injury or property damage may occur from an uncontrolled process if the supply medium is not clean, dry, oil‐free air, or noncorrosive gas. While use and regular maintenance of a filter that removes particles larger than 40 micrometers in diameter will suffice in most applications, check with an Emerson Automation Solutions field office and industry instrument air quality standards for use with corrosive air or if you are unsure about the proper amount or method of air filtration or filter maintenance.
Supply pressure medium must be clean, dry, and noncorrosive and meet the requirements of ISA Standard 7.0.01 or ISO 8573-1. A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5
12
Loading...
+ 28 hidden pages