Emerson Fisher 249, Fisher 249P, Fisher 249VS, Fisher 249W, Fisher 2500 Data Sheet

...
Level Instruments
D103219X012
Fisherr Level Instruments
FISHER 2100E
ELECTRIC LEVEL SWITCH
Product Bulletin
11.2:Level
February 2015
W8418‐1
FISHER L2 PNEUMATIC
LEVEL CONTROLLER
W8678
FIELDVUE DLC3010 DIGITAL LEVEL
CONTROLLER IN COMBINATION WITH
A FISHER 249W SENSOR
n FIELDVUE™ Digital Level Instruments—
Microprocessor‐based, communicating digital level transmitter for liquid level, specific gravity (density), and liquid level interface. Using HART F
OUNDATION™ fieldbus communications protocol,
R
or
the DLC3010/DLC3020f digital level controller gives easy access to information critical to process operation. Available in combination with a 249 sensor to meet mounting requirements.
n Fisher 2100E electric switch and 2100 on-off
pneumatic switch— Sense high or low liquid levels.
Typically, these switches electrically or pneumatically operate safety shutdown systems for field processing equipment in oil and gas industry applications
FISHER L2e ELECTRIC
LEVEL CONTROLLER
n Liquid Level Controllers— Displacer type sensors
used to detect liquid level or interface of two liquids of different specific gravities. The L2e electric level controller, in conjunction with the Fisher easy-Drive™ actuator, can provide a fully electric level control loop; the L2 pneumatic level controller offers snap-acting, throttling control, while the on-off/direct acting L2sj controller features a low-bleed relay to help to conserve natural gas to reduce emissions.
n Pneumatic Liquid Level Instruments— Proportional
control mode. The 2500 controller/transmitter receives the change in fluid level or fluid‐to‐fluid interface level from the change in buoyant force the fluid exerts on the sensor displacer. Available in combination with a 249 sensor to meet mounting requirements.
www.Fisher.com
Product Bulletin
11.2:Level February 2015
Level Instruments
D103219X012
FIELDVUE Digital Level Instruments
FIELDVUE DLC3010 digital level controllers (figures 1 and 3) are loop‐powered instruments. In conjunction with a 249 sensor, they measure changes in liquid level, the level of an interface between two liquids, or liquid specific gravity (density). The DLC3020f is a fieldbus‐powered instrument that measures liquid level or interface between two liquids. A level, density, or interface level change in the measured fluid causes a change in the displacer position.
This change is transferred to the torque tube assembly and to the digital level controller lever assembly. The rotary motion moves a magnet attached to the lever assembly, changing the magnetic field that is sensed by the Hall‐effect sensor. In the DLC3010, the sensor converts the magnetic field signal to a varying electronic signal, which is converted to a 4‐20 mA output signal. In the DLC3020f, the sensor converts the changing magnetic field to a digital signal, which is ambient temperature compensated, linearized, and sent to the electronics assembly.
Standard or Custom Configuration... the DLC3010 digital level controller in combination with a 249W sensor enables users to install digital level transmitters to a variety of industry standard or custom process vessel connections. The sensor consists of a wafer body, torque tube assembly and displacer and is rated for CL150, 300, and 600. The wafer body mounts between NPS 3 or 4 raised face flanges. Custom configurations are also available to meet your specific application requirements. Refer to the DLC3010/DLC3020f specifications in tables 1, 2, 3, and 9, and the 249 specifications in tables 4, 5, 6, 7, 8, and 9 for product line capabilities and options.
Figure 1. Fisher DLC3010 Digital Level Controller in Combination with a 249W Sensor —Installed in a Typical Customer‐Supplied Cage
475 FIELD COMMUNICATOR
W8678
Figure 2. AMS Suite: Intelligent Device Manager Configuration Screen
HART/AMS Compliant... The DLC3010 uses HART
protocol to interface with the Field Communicator (see figure 1) for field interface operations. Advanced user‐interface capabilities are enabled by AMS Suite: Intelligent Device Manager.
F
OUNDATION fieldbus/AMS Compliant... The DLC3020f
uses F
OUNDATION fieldbus protocol to interface with the
Field Communicator (see figure 1) for field interface operations. Advanced user‐interface capabilities are enabled by AMS Suite: Intelligent Device Manager (see figure 2).
2
Level Instruments
D103219X012
Product Bulletin
11.2:Level
February 2015
Simplified Setup and Calibration... With the electronic Device Setup, digital level controller startup is straightforward and fast. Level and temperature alarms, specific gravity tables, calibration trim, and trending are readily configurable. DLC3010/DLC3020f digital level controllers also support re‐ranging without a fluid reference.
Responsive to Small Process Change... Accurate, high‐gain analog‐to‐digital conversion enables measurement of small changes in the process variable. In addition, an input filter and output damping may be adjusted by the user to attenuate noise from mechanical disturbance or liquid turbulence at the displacer.
Easy Maintenance... Field wiring connections are in a compartment separated from the electronics. This helps to protect the electronics from any moisture brought into the housing by the field wiring. This also eases installation and maintenance. The digital level controller does not have to be removed to facilitate troubleshooting or service. However, if it is necessary to remove the digital level controller for in‐shop maintenance and calibration, field wiring does not need to be disconnected.
Figure 3. FIELDVUE DLC3020f Digital Level Controller
W6102‐1
Note
Mountings for Masoneilan, Yamatake and Foxboro/Eckhardt sensors are available. Contact your Emerson Process Management sales office for mounting kit information.
Table 1. FIELDVUE DLC3010 General Specifications
Controller Selections
Input Signal
Output Signal
Supply 12‐30 VDC; the instrument has reverse‐polarity protection
Ambient Relative Humidity 0 to 95% non‐condensing
Approximate Weight (Controller) 2.7 kg (6 pounds)
Option Heat insulator
Electrical Housing NEMA 4X, CSA Enclosure, IP66
Hazardous Area Classification
1. Also refer to tables 4, 5, 6, and 7.
2. Other Certifications/Classifications available. Contact your Emerson Process Management Sales office for additional information.
For use with 249 caged and
(1)
uncaged displacer sensors
Level, Interface or Density: Rotary motion of the torque tube shaft proportional to changes in liquid lever, interface level, or density that change the buoyancy of the displacer. Process Temperature: Interface for 2‐ or 3‐wire 100 ohm platinum RTD for sensing process temperature, or optional user‐entered target temperature to permit compensating for changes in specific gravity
Analog 4‐20 mA DC direct (increasing input increases output) or reverse action Digital HART 1200 baud FSK (frequency shift keyed)
CSA—Intrinsically Safe, Explosion-proof, Division 2, Dust Ignition-proof
(2)
FM—Intrinsically Safe, Explosion-proof, Non-incendive, Dust Ignition-proof ATEX—Intrinsically Safe, Type n, Flameproof IECEx—Intrinsically Safe, Type n, Flameproof
DLC3010
3
Product Bulletin
11.2:Level February 2015
Table 2. FIELDVUE DLC3020f General Specifications
Controller Selections
Device Inputs
Digital Communication Protocol Foundation fieldbus registered device (ITK 5)
Supply 9 to 32 volts DC, 17.7 mA DC; instrument is not polarity sensitive
Ambient Relative Humidity 0 to 95% non‐condensing
Approximate Weight (Controller) 2.7 kg (6 pounds)
Option Heat insulator
Electrical Housing Type 4X, NEMA 4X, IP66
Hazardous Area Classification
1. Also refer to tables 4, 5, 6, and 7.
2. Other Certifications/Classifications available. Contact your Emerson Process Management Sales office for additional information.
For use with 249 caged and
(1)
uncaged displacer sensors
(2)
DLC3020f
Level Sensor Input: Rotary motion of the torque tube shaft proportional to buoyant force of the displacer caused by changes in liquid level or interface level. Process Temperature: Interface for 2‐ or 3‐wire 100 ohm platinum RTD for sensing process temperature; AO Block - Foundation fieldbus temperature transmitter; Manual - compensation values entered manually in the device
CSA—Intrinsically Safe, Explosion-proof, Division 2, Dust Ignition-proof FM—Intrinsically Safe, Explosion-proof, Non-incendive, Dust Ignition-proof ATEX—Intrinsically Safe, Type n, Flameproof IECEx—Intrinsically Safe, Type n, Flameproof
Level Instruments
D103219X012
Table 3. FIELDVUE DLC3010/DLC3020f Performance
Performance Criteria
Independent Linearity
DLC3010 DLC3020f
$0.25% of output span $0.1% of output span $0.8% of output span $0.5% of output span
(1)
Stand‐Alone
(2)
DLC3010 w/ NPS 3 249W,
Using a14‐inch Displacer
DLC3010 w/ All Other
249 Sensors
Hysteresis < 0.2% of output span < 0.50% of output span - - - - - -
Repeatability
$0.1% of full scale output
Dead Band < 0.05% of input span
< 0.10% of output span
$ 0.10% (RH9.2% to 90%)
$0.5% of output span $0.3% of output span
- - - - - -
Hysteresis and Dead Band - - - - - - < 1.0% of output span < 1.0% of output span
Accuracy - - -
Fluid Level or Fluid
Process Sensor Range (Input Signal)
Allowable Specific Gravity (Standard)
Interface Level
Fluid Density (DLC3010)
Fluid Level or Fluid Interface Level
Fluid Density (DLC3010)
Fluid Level or Fluid
Zero Adjustment
Interface Level
Fluid Density (DLC3010)
1. At full design span, reference conditions.
2. To lever assembly rotation inputs.
3. The torque tube and the displacer must be properly sized for the application in order for 0 to 100% of displacer length to be available.
4. With a nominal 4.4 degrees torque tube shaft rotation for a 0 to 100 percent change in liquid level (specific gravity=1), the digital level controller can be adjusted to provide full output for an input range of 5% of nominal input span. This equates to a minimum differential specific gravity of 0.05 with standard volume displacers. Operating at 5% proportional band will degrade accuracy by a factor of 20. Using a thin wall torque tube, or doubling the displacer volume will each roughly double the effective proportional band. When proportional band of the system drops below 50%, changing displacer or torque tube should be considered if high accuracy is a requirement.
From 0 to 100 percent of displacer length or 813 mm (32 inches); other lengths available depending on sensor construction
From 10 to 100 percent of displacement force change obtained with given displacer volume—standard volumes are 1016 cm
3
(62 in3) for 249C and 249CP sensors and 1622 or 1360 cm3 (99 or 83 in3) for most other sensors;
other volumes available depending upon sensor construction
Specific gravity range, 0.05 to 1.10; Minimum differential specific gravity 0.05
Specific gravity range, 0.1 to 1.10; Minimum change in specific gravity 0.05
Continuously adjustable to position span of less than 100 percent anywhere within displacer length, and report the value in engineering units with any desired bias.
Continuously adjustable to position span of less than 90 percent anywhere within 10 to 100 percent of displacement force change obtained with given displacer volume.
$0.15%
(3)
—standard lengths for all sensors are 356 mm (14 inches)
- - - - - -
(4)
(4)
4
Level Instruments
D103219X012
Product Bulletin
11.2:Level
February 2015
Figure 4. Fisher 2100E Electric Liquid Level Switch
APPROXIMATE SWITCHING POINT
LOCATION OF OPTIONAL SIGHT WINDOW
Figure 5. Fisher 2100 Pneumatic Liquid Level Switch
W9954-1
Fisher 2100 Liquid Level Switches
Typically, 2100E and 2100 switches electrically or pneumatically operate safety shutdown systems for field processing equipment in oil and gas industry applications
Switch construction comes in a left‐hand as well as a right‐hand mounting version. The explosion‐proof, hermetically sealed 2100E switch is offered as both a factory mounting and as an electric switch retrofit to the proven 2100 switch.
With the 2100E switch rising liquid level exerts a buoyant force on the torque tube that either activates or deactivates an electrical SPDT or DPDT switch
depending on the switching action desired. Falling liquid level deactivates or activates the same switch depending on the action desired.
When the 2100 switch is in the normal position with the flapper against the nozzle, output pressure cannot bleed off and remains the same as full supply pressure. Rising liquid level exerts a buoyant force on the displacer, producing a torque on the torque tube. When the torque transmitted by the torque tube exceeds the torque exerted on the flapper by the magnet, the flapper snaps away from the nozzle, allowing output pressure to bleed through the nozzle faster than supply pressure can enter through the bleed orifice. The reduced pressure in the output signal line activates the shutdown or alarm system. When the liquid level lowers, the falling displacer forces the flapper into the field of the magnet, letting the magnet snap the flapper against the nozzle and causing output pressure to build to full supply pressure.
5