Emerson A6312 Quick Start Manual

Quick Start Guide
MHM-97448
NC: 6540-90025
Rev.: 1.032
CSI 6500 Machinery Health™Monitor
A6312, Dual Channel Speed/ Key Monitor
835 Innovation Drive
Knoxville, TN 37932 USA
T 1(865) 675-2400
F 1(865) 218-1401
www.EmersonProcess.com
©2010, Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has
been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available on request.We reserve the right to modify or
improve the designs or specifications of our products at any time without notice.
All rights reserved. Machinery Health is a mark of one of the Emerson Process Management group of
companies. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are
the property of their respective owners.
GB
Explanation of symbols
!
If this symbol is printed on a device, according to IEC 61010 it means that the documentation of the device must be completely read and understood before installation and commissioning of the device. All safetyrelated instructions of this document must be observed. These safetyrelated instructions are marked by the “STOP” symbol in this document.
If this symbol is printed on a device, according to IEC 61010 it means that this device must be operated with DC voltage.
i
This symbol identifies text that contains important information.
!
Not following instructions identified with this symbol can result in functional issues and incorrect measurements without damaging the machine.
STOP
Safety and warning instructions are identified with this symbol. Failure to observe these instructions can result in material damage or
personal injury.
D
Symbolerklärung
!
Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010 aus, das es zur Installation und Inbetriebnahme des Gerätes zwingend erforderlich ist, die Dokumentation des Gerätes vollständig gelesen und verstanden zu haben. Sicherheitsrelevante Hinweise in dieser Dokumentation sind unweigerlich zu beachten und im weiteren Verlauf dieser Dokumentation durch das “STOP” Symbol (siehe unten) gekennzeichnet.
Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010 aus, dass es mit Gleichspannung betrieben wird.
i
Dieses Symbol kennzeichnet Textstellen, die wichtige Informationen enthalten.
!
Hinweise, die bei Nichtbeachtung zu Funktionsstörungen und Fehlmessungen führen, ohne das Gerät zu beschädigen, sind mit diesem Symbol gekennzeichnet.
STOP
Sicherheits- und Warnhinweise sind mit diesem Symbol gekennzeichnet. Die Nichtbeachtung solcher Hinweise kann zu Sachbeschädigungen oder
Personenschäden führen.
Product Service Centers
America
Emerson Process Management 835 Innovation Drive Knoxville, TN 37932 Tel: 8656752110 Fax: 865−218−1401
Brazil
Emerson Process Management Ltd. Av Hollingsworth 325 Sorocaba, SP BRAZIL 18087−000 Phone: 55 15 2383788 Fax: 55 15 22823300
Europe, Middle East, Africa
Emerson Process Management div. ESAD MHM Repair Center Piestanska 1202/44 915 28 Nove Mesto nad Vahom Slowakia Tel: +421/32/7700 538 Fax: +421/32/7700 884
Asia
Emerson Process Management / Asia Pacific Private Ltd.
3904 Room Central Plaza 18 Harbour Road Wan−Chai Hong Kong Tel: 852−2802−9223 Fax: 852−2802−8227
Incoming goods inspection
Check the content of the shipment to ensure that it is complete; visibly inspect the goods to determine if the device may possibly have been damaged during transport. The following parts are included in the scope of delivery and must be contained in the shipment.
1. A6312
2. Product information
If the contents are incomplete, or if any defects are observed, a complaint must be filed with the carrier immediately. Moreover, the responsible Emerson sales organization must be informed to enable repair or replacement of the device. Repairs or calibration that may be required, are only possible at the Emerson factory.
In this case, a nondetachable tag with customer name, defect observed and version of the A6910 configuration software must be attached to the device.
Repair and maintenance
During operation, monitors do not require any mainte­nance.
Repair or calibration of monitors is only possible at Emerson.
i
The additional PCB (controller board) is calibrated with the main board and must not be replaced.
If work with the opened device onsite is unavoidable, this should only be performed by a specialist who is familiar with the associated hazards.
STOP
Capacitors in the device can still be energized, even if the device has been disconnected from all power sources.
If repair or recalibration of a monitor is required, it must be sent to Emerson. Attach a non−detachable tag to the monitor with customer name, defect observed and version of the A6910 configuration software.
Guidelines for Returning Equipment to the Product Service Center
If repair or calibration of a monitor is required, it must be sent to Emerson. Occasionally, concerns with CSI technology hardware could arise. Should this happen, customers under warranty or a current support agreement are entitled to no−charge repairs.
Follow the checklist below to minimize return time and ensure proper processing of your equipment. Before returning any equipment to a Product Support Center, please review this information:
1. Obtain a Return Materials Authorization (RMA) number and the address of the appropriate Product Service Center by calling 865.675.4274*.
Listen to the options for receiving an RMA. You will be routed to support personnel who will document your concern and give you an RMA number if you are under support or warranty. If your hardware is not under support or warranty, you must have a Purchase Order for the amount of the repair service before you can receive an RMA number. Pricing for your repair can be obtained from support personnel or by calling your local sales representative. Once you have your purchase order, call 865.675.4274* for an RMA.
2. Once you have received your RMA, send your hardware to the appropriate product service center. Your hardware package should include:
G RMA Number (plus Purchase Order if
applicable)
G Description of the hardware
problem
G Return shipping address including a
phone number (No P.O. boxes).
G Any special request regarding the
return shipment.
G A list of the model numbers of each
item(s) being returned, along with the serial number.
G Your name, address, telephone
number and email address.
G Company Name.
A form for completing this information has been provided.
Make a copy of the form, complete all lines, and return a copy in each return shipment.
Out of warranty? Need to get under support? Get a customized quote for bringing all your CSI technologies under a support agreement: Phone: 865.675.2400*, ext. 2130 Fax: 865.218.1478* Email: mhm.supportagreement@emersonproces s.com
*Customers outside the Americas and Canada: please refer to the list of service centers and contact the service center near you.
All rights are strictly reserved
Reproduction or divulgation in any form whatsoever is not permitted without written authority from the copyright owner.
RMA Required Information
RMA number issued by Product Service Center:
For all items beingreturned, please list Model / Serial Number:
Are you under warranty or a current support agreement (circle one)?
Yes No
If you answered no, what is your purchase order number?
Company Name:
Contact Name:
Contact Address:
Contact Phone:
Contact Fax:
Contact Email:
Please describe the problem you are experiencing:
If we are to send the return shipment to someone other than the Contact Name/Address above, please provide that address here, including Contact Name and Phone Number:
Are there any special instructions regarding the return?
Please provide invoice address (if a purchase order was required):
Support customers your instrument is shipped back to you the same way that it is sent to our service center. For example, if you ship via ground transportation, it is shipped back via ground.
Page/Seite 7
Product Information / Produktinformation
A6312
1
GB
Rotational Speed Monitor 8......................
1.1 Scope of Delivery 8...........................................
1.2 CSA Certification 9...........................................
1.3 CSA Conditions of acceptability 9............................
1.4 Advice for Installation 9.......................................
1.5 Installation and Mounting 9...................................
1.6 Technical data 11..............................................
1.6.1 Signal conditioning 11.......................................................
1.6.2 Channel monitoring 13......................................................
1.6.3 Function outputs and alarms 15..............................................
1.6.4 Communication interfaces 16.................................................
1.6.5 Power supply 17............................................................
1.6.6 Environmental conditions 18.................................................
1.6.7 Mechanical structure 18.....................................................
2
D
Drehzahl / KeyMonitor 19.......................
2.1 Lieferumfang 19...............................................
2.2 CSA Zertifizierung 20..........................................
2.3 CSA Akzeptanzkriterien 20....................................
2.4 Hinweis zur Installation 21......................................
2.5 Installation und Montage 21....................................
2.6 Technische Daten 23...........................................
2.6.1 Signalkonditionierung 23.....................................................
2.6.2 Kanalüberwachung 25.......................................................
2.6.3 Funktionsausgänge und Alarme 27............................................
2.6.4 Kommunikationsschnittstellen 28.............................................
2.6.5 Spannungsversorgung 29....................................................
2.6.6 Umgebungsbedingungen 30..................................................
2.6.7 Mechanischer Aufbau 30....................................................
3 Connection Diagrams and Figures /
Anschlusspläne und Abbildungen 31....................
4 PI Revision List 36.....................................
Page 8
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1
GB
ROTATIONAL SPEED MONITOR
!
This product Information contains general information about the dual channel speed/ key monitor types A6312/06 & A6312/08. If not stated otherwise, all information denoted by A6312 is valid for both types, listed before.
The twochannel rotational speed monitor A6312 is a module of the A6000 machine monitoring system. The microprocessor controlled monitor is used in conjunction with two eddy current measuring chains or halleffect sensors (e.g. PR 9376) and in combination with triggering wheels to measure and conditioning of shaft speeds and rotational reference marks (keypulses).
Both channels may be used separately used to measure:
2 speeds from 2 shafts
2 keypulses from 2 shafts each with a triggermark (with phase relation)
Both channels may also be used in combination with each other:
to detect the direction of rotation of one shaft
to detect a difference between two shaft speeds
i
In this product information the mounting and electrical connection of the monitor is described.
For secure use of the monitor, observe the direction for use “Rotational Speed Monitor A6312” (order number: 611090025). You can find this direction on the configuration software CD as pdfdata file. Amongst others, it contains useful informations for configuration and use of the A6312.
To ensure the safe operation of the monitor and to permit setting of all functions, it is indispensable to use only the latest versions of configuration software (version 2.05 or newer) and operating manual.
The use of old operating manuals or configuration programs out of date may lead to malfunctions or limitations of the measuring functions.
1.1 Scope of Delivery
The following parts are included in the scope of delivery and must be contained in the shipment:
Rotational Speed Monitor A6312
This product information
Accessories (not included in delivery):
MMS ParaKit (order no.: 9510−00027)
If the contents are incomplete or if is there any damage, so directly complain at the bearer. The competent epro−sales agency must be also informed, to enable repair or replacement for the monitor. Repair or calibration of this instrument may only be done at epro.
Page 9
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1.2 CSA Certification
STOP
For valid CSA certification, all devices (IMR 6000/xx and A6000 modules) must be marked with the respective CSA lable.
If no CSA lable is available on the respective device, this device is not CSA certified!
The respective CSA lable looks as shown in the following picture.
1.3 CSA Conditions of acceptability
This device must be supplied with safety low voltage SELV LPS (C22.2 609501) 24V. The voltage required for operation must be drawn from a separate power supply.
The IMR system should be placed in a suitable fire enclosure.
The IMR system is evaluated for an ambient of 0°C to 45°C.
Adequate ventilation space has to be provided so that heat does not build up. The ventilation space must be at least 1 RU (1
3/4
inch) in all directions. If the ambient temperature of the rack
rises above 45 °C, cool this instrument with a forced air fan, cooler, or similar.
When mounting several IMR units above each other in one cabinet, install cooling fan racks in between instead of the ventilation space. The necessary specifications for cooling fan racks result from the environmental and sitting criterions of the cabinet and thus cannot be defined generally.
1.4 Advice for Installation
STOP
According to the IEC 61010 directive, permanently installed systems must be equipped with a power disconnect device (e.g. a switch or circuit−breaker according to IEC609471 and IEC609473). When using an IMR rack, in compliance with this directive, such a switch or breaker must be implemented into the cabinet installation and easily accessible for the user. Furthermore, each disconnect devices must be labeled in accordance to the associated system.
1.5 Installation and Mounting
A prepared 3U slot in a 19” rack, or other Intermas−compatible enclosure, is required for mounting the A6312 monitor. The slot must be fitted with a 48−pin plug connector (DIN 41612, design F 48 M). The pin assignment is listed in the following table.
Page 10
Product Information / Produktinformation
A6312
Rotational Speed Monitor
d b z
2
UN+ (+24V) U (0V/Common) UB+ (+24V, redundant)
2
4
A (RS 485) GND (BP, Common, RS 485) B (RS 485)
4
6
Supply2+ (sensor) Supply1 (sensor) Supply1+ (sensor)
6
8
AIN2 (Input) Supply2 (sensor) AIN1 (Input)
8
10
AIN2+ (Input) GND AIN1+ (Input)
10
12
PU1 (24Vpull up pulse1) GND NC
(MMS6310)
/ Test1
(MMS6312)
12
14
Pulse1C (collector) Pulse1E (emitter) Pulse1TTL
14
16
Pulse2C (collector) Pulse2E (emitter) Pulse2TTL
16
18
PU 2(24Vpull up pulse2) I1 (current output common) I1+ (current output CH1)
18
20
Reset peak value 1 I2 (current output common) I2+ (current output CH2)
20
22
NC
(MMS6310)
/ Test2
(MMS6312)
GND ES (external lock)
22
24
SCA (oper. principle GW2) GND SCD (oper. principle GW1)
24
26
GW1DC (danger1 collector) GW1AC (alert1 collector) CC1C (ch. clear1 collector)
26
28
GW1−D−E (danger1 emitter) GW1−A−E (alert1 emitter) CC1E (ch. clear1 emitter)
28
30
GW2DC (danger2 collector) GW2AC (alert2 collector) CC2C (ch. clear2 collector)
30
32
GW2−D−E (danger2 emitter) GW2−A−E (alert2 emitter) CC2E (ch. clear2 emitter)
32
Jumper RS 485
RS 485 bus operation requires an electrical terminator on the first and last bus device.
This is done with plugin jumpers, that are on the controller board. The figure shows the position of the jumpers.
To activate the bus terminator and to place lines “A” and “B” on the references, plug the jumpers as shown in Fig. b). Fig. a) shows the jumper position for deactivated bus termination and open references (delivery status).
Plugin jumper 12 closed: Bus line “B” via pulldown resistor on ground
Plugin jumper 34 closed: 120 Ω Resistor between “A” and “B”
Plugin jumper 56 closed: Bus line “A” via pullup resistor on +5 V
Page 11
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1
35
2
46
1
35
2
46
a)
b)
i
For troublefree operation of the RS 485 bus, the lines “A” and “B” in one monitor must be connected on their references (+5 V, ground), this is only possible if the bus terminator jumper is also set in this monitor.
Installation
3. Check the slot wiring prior to installing the monitor.
4. Push the A6312 monitor into the prepared slot and press it with light pressure into the plug
connector.
5. Hand tighten the two anchoring screws on the front panel to secure the monitor
Any other information, e. g. shielding and grounding, configuration of the monitor, etc., can be found in the direction for use “Rotational Speed Monitor A6312”, order number: 6110−90025.
1.6 Technical data
Only information with tolerances and limit values are considered as binding data. Data without tolerances or error limits are provided as information only. We reserve the right to make technical changes – particularly to the software.
All of the following information applies uniformly for channel 1 and channel 2, if not otherwise specified.
1.6.1 Signal conditioning
Two separate signal inputs for channel 1 and channel 2 with uncoupled signal conditioning.
Measured value inputs
Differential voltage amplification inputs, nonreactive, opencircuit and shortcircuit proof.
Channel 1 z8: SENS1−A−;z10: SENS1−B+
Channel 2 d8: SENS2−A−;d10: SENS2−B+
Input nominal range 0... 27,3 V DC
Limit range 0 ... 30 V DC
Input resistance > 100 kΩ
Page 12
Product Information / Produktinformation
A6312
Rotational Speed Monitor
Signal conditioning
Sensor signal outputs Front sockets SMB, decoupled, opencircuit and
shortcircuit proof, nonreactive.
Channel 1 SENS 1 SMB Ch1
Channel 2 SENS 2 SMB Ch2
Signal output 0 ... 4,1 V; signal = 0,15 x sensor input signal
Precision ±1 % of f.s.d.
Frequency range 0 ... 16 kHz (3 dB) ±20 %
Per. load resistance > 100 kΩ
Internal resistance 10 kΩ
Dynamic outputs
TTL – Outputs The processed input signals are output as TTL signals
Pulse 1 TTL / Pulse 2 TTL z14 / z16 open−circuit and short−circuit proof,
nonreactive
Nominal range 0...5 V pp
Frequency range 0.....20 kHz
permissible load >100 kΩ
Source impedance 10 kΩ
Key pulse outputs Potential free output for pulses 1 x per revolution
Pulse 1UC /Pulse2UC d12 / d18 supply for pulse output
Max. voltage +24 V at UC +48 V DC at collector
Pulse 1C / Pulse 1−E d14 / b14 collector – emitter line pulse 1
Pulse 2C / Pulse 2−E d16 / b16 collector – emitter line pulse 2
Max. current CE conducting 100 mA
Pulse duration 1 ms ±20 %
At measuring mode “Speed”, the pulse duration is synchronous to the tooth.
Output load (maximum number of modules to be connected)
15, at Uc +24 V, f < 50 Hz, T < 30°C
Page 13
Product Information / Produktinformation
A6312
Rotational Speed Monitor
Signal conditioning for characteristical value
The input signals are scaled before processing. The characteritical value is proportional to the speed, i.e. the input frequency divided by the number of theeth of the pulse wheel configured with the configuration software.
Range adjustment determined during configuration
Maximum measuring range limited by the max. signal frequency of 20 kHz
Maximum speed 65535 rpm with 18 teeth,
max. signal frequency = 20 kHz
Maximum number of teeth 255
Current output characteristical value
The calculation of the characteristical value and its evaluation depends on the function determined during configuration.
Current output 1 I1+ / I1 z18 (+) / b18 () galvanically isolated
Current output 2 I2+ / I2 z20 (+) / b20 () galvanically isolated
Nominal range 0...20 mA or 4...20 mA, depending on configuration
Life zero mode in the 4...20 mA mode the output con be set to 0 mA
in case of a fault. This function is activated during configuration.
Accuracy / resolution ±1 % of f.s.d. / 16 bit
Permissible load 500 Ω
1.6.2 Channel monitoring
Monitoring function Constant monitoring
Sensor signals GOOD range (configuration dependent)
System voltages Voltage − OK
μP function (watchdog) WD − OK
External disable signal ES
Status channel monitoring
Channel status = no error (OK) if (voltage_OK = yes)
AND (WD_OK = yes) AND (Sensor signal in the GOOD range) AND (ES = no)
Channel status = error If the previous condition is not satisfied
Page 14
Product Information / Produktinformation
A6312
Rotational Speed Monitor
Visualization
Green LED on the front panel
Channel status = no error (OK) Continuous light
Channel status = error Dark
Gap error Flashing light (flashing rate 0,2s)
configuration error / watchdog Flashing light (flashing rate 1s)
Channel Clear outputs
Optodecoupled collector/emitter segments
Channel Clear channel 1, C1C / C1E z26 (collector) / z28 (emitter)
Channel Clear channel 2, C2C / C2E z30 (collector) / z32 (emitter)
Ext. disabled or status = error CE disabled, max. perm. voltage: 48 V
Not ext. disabled and status = OK CE conducting, max. perm. current: 100 mA
Binary inputs
Signal level LOW: 0 ... +3 V, HIGH: +13 ... +48 V
External locking
z22 for locking the function / alarm outputs e.g. for service works etc.
Disable / locking input LOW = disable of channel supervision and alarm
output
Enable / unlocking input HIGH or open = channel supervision and alarm
output is enabled
Reset Latch
d20 for resetting the latch function of the function output
Reset input LOW
no Reset input HIGH or open
Test channel 1 / channel 2
z12 / d22 internal test value activation
Test operation input LOW
Normal operation input HIGH or open
Page 15
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1.6.3 Function outputs and alarms
Two function outputs per channel with separate configuration for functions and alarm limits. Function and switching characteristics are configured separately.
Limit settings
During configuration freely selectable depending on the relevant function. With functions rotational direction and standstill no alarm limits.
Adjustment range 0 ... 100 % of the configured measuring range
Resolution 0,1 % of full scale.,
1 rpm in speed range 0...12000 rpm
Hysteresis freely selectable
Reaction time
Delay time between calculation of characteristical value and reaction of the limit output (only valid for output function limit).
average reaction time 2 ms
Alarm blocking
Blocking if (supply or watchdog not ok) ODER
(Ex. locking = lock) ODER (channel status = not ok*)
No blocking if condition above are not met
* During configuration it can be defined whether or not blocking of the alarm outputs shall be controlled by the channel supervision.
Alarm visualization
By means of two yellow LEDs for channel 1 and channel 2.
No limit exceeded or alarms blocked LED off
Limit eceeded or function „true” LED switched on (steady light)
Page 16
Product Information / Produktinformation
A6312
Rotational Speed Monitor
Function outputs
Opto decoupled collector / emitter lines
Out 11 C / Out 11 E d26 (collektor) / d28 (emitter)
Out 12 C / Out 12 E b26 (collektor) / b28 (emitter)
Out 21 C / Out 21 E d30 (collektor) / d32 (emitter)
Out 22 C / Out 22 E b30 (collektor) / b32 (emitter)
Maximum values for alarm outputs CE off: max. voltage UCE = 48 V
CE conducting: max. current ICE = 100 mA
active state of function outputs conducting in the open circuit mode
switched of in the closed circuit mode
Open circuit / closed circuit mode
Selectable by means of external signal inversion at binary inputs d24 and z24, only for the function outputs Out 1−1 and Out 2−1.
Outputs Out 12 and Out 22 are invariably fixed to open circuit mode
Switch over Out 11 d24 = HIGH / open open circuit mode
d24 = LOW closed circuit mode
Switch over Out 21 z24 = HIGH / open open circuit mode
z24 = LOW closed circuit mode
Switching level LOW: 0 ... +3 V
HIGH: 13 ... 48 V
Input resistance >10 kΩ
1.6.4 Communication interfaces
RS 232 interface
Front socket for connecting a laptop / computer for configuration and visualization purposes
Round plug connector on the front side
Mini DIN socket type TM 0508A/6 for parameterization cable (included in the operating kit)
RS 485 interface
d4, z4 bus interface for communication with an MMS 68xx epro analysis and diagnostic system and the configuration software.
Page 17
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1.6.5 Power supply
The system supply voltages with their grounds, the signal inputs and supervision inputs / outputs are galvanically isolated from each other.
Supply voltage inputs Two redundant, diode decoupled inputs for nominal
+24 V with common 0 V reference
Voltage input UB+ / UN+ d2 / z2
Common reference 0 V U b2
Permissible voltage range 19 ... 31.2Vdc (IEC 654−2 class DC 4)
CSA: 24Vdc; SELV LPS
Power consumption Max. 6 W, at 24 V max. 250 mA
The monitor system voltages, and thus the 0 V / common connections for the measurement and monitoring inputs and outputs, are galvanically separated.
Monitor system voltage
The module system voltages required for the internal supply are permanently checked on low voltage. If ”Low voltage” is detected, an error message will be given.
Sensor supply
For both channels of the module
Separation Decoupled and galvanically separated from the
supply voltage, can be operated in parallel with other monitors, open
circuit and short circuit proof, non−reactive
Sensor supply channel 1 Sup.Ch1+ / Sup.Ch1− b6/z6
Sensor supply channel 2 Sup.Ch2+ / Sup.Ch2− b8/d6
Supply voltage 26,75 V DC; Tolerance ±2 %
Residual ripple < 20 mVss (at nominal current 20 mA)
Max. current 35 mA
Max. shortcircuit current 0 mA I short−circuit 5 mA;
Opencircuit and shortcircuit proof
Page 18
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1.6.6 Environmental conditions
Application class KTF in accordance with DIN 40040
Ambient temperature
Reference temperature +25 °C
Nominal use range 0...+45°C (CSA requirement and recommended range)
max. range −10°C ... +65°C (not CSA conform)
Operating altitude up to 2000m above sea level
Storage, transport temperature 30 ... +85 °C
Relative humidity 95 % non condensing
Vibration In accordance with IEC68 – 2 Part 6
Amplitude 0.15 mm at 10 ... 55 Hz
Acceleration 19.6 mm/s2 at 55 ... 150 Hz
Shock In accordance with IEC68 – 2 Part 29
Peak acceleration value 98 m/s
2
Nominal duration of shock 15 ms
Enclosure protection class IP 00, open design in accordance with DIN 40050
EMC immunity In accordance with EN 50 0811 / EN 50 082−2
satisfied
Allowed degree of pollution Category 2 (According to IEC 61010−1)
Enviromental Area Indoor use only
1.6.7 Mechanical structure
PCB Euro format (100 mm x 160 mm) in accordance with
DIN 41494
Width A6312/06: 6HP (approximately 30 mm)
A6312/08: 8HP (approximately 40 mm)
Plug connector DIN 41612, form F 48 M
Front element
2 LEDs green Channel Clear channel 1 / 2
4 LEDs yellow Pulse channels 1 / 2
4 SMB socket connectors For sensor channel 1 / 2
TTLPulse channel 1 / 2
1 mini DIN round socket connector RS 232 for connecting a laptop / computer (for
configuration and visualization purposes)
Weight Approximately 320 g without packaging
approximately 450 g with standard packaging
Seite 19
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
2
D
DREHZAHL / KEYMONITOR
!
Diese Produktinformation enthält Informationen zu den zweikanal Drehzahl−/ Key Monitortypen A6312/08 & A6312/06. Falls nicht seperat aufgeführt sind alle, im weiteren Verlauf dieser Dokumentation mit A6312 bezeichneten Informationen für beide, zuvor genannten, Typen gültig.
Der zweikanalige Key−Monitor A6312 ist eine Baugruppe des A6000 Maschinenüberwa- chungssystems. Der mikrocontrollergesteuerte Monitor dient in Verbindung mit zwei Wirbel­strommessketten oder Feldplattenaufnehmer (z. B. PR 9376) der Messung und Aufbereitung von Wellendrehzahlen oder Drehbezugssignalen (Key−Signalen) an Turbinen aller Art, Kompressoren, Lüftern, Getrieben usw.
Die beiden Kanäle des Monitors arbeiten unabhängig voneinander. Mittels Konfiguration können folgende Messungen eingestellt werden:
Drehzahlmessung an zwei Wellen.
KeyMessung an zwei Wellen.
Durch Kombination der beiden Kanäle können folgende Messungen eingestellt werden:
Drehrichtungserkennung an einer Welle.
Berechnung der Drehzahldifferenz zweier Wellen.
Die Messsignale werden pro Kanal über einen Open−Kollektor−Ausgang, TTL−Impuls− Ausgang und Stromausgang zur Verfügung gestellt.
i
In dieser Produktinformation wird die Montage und der elektrische Anschluss des Monitors beschrieben.
Für den sicheren Betrieb des Monitors muss die Gebrauchsanleitung “Drehzahl / KeyMonitor A6312” (Bestellnr. 610090025) unbedingt beachtet werden. Die Gebrauchsanleitung befindet sich im pdf−Format auf der CD mit der Konfigurationssoftware. Sie enthält unter anderem Informationen zur Konfiguration und Bedienung des A6312.
Um den sicheren Betrieb des Monitors zu gewährleisten und um alle Funktionen des Gerätes einstellen zu können ist es erforderlich, die jeweils aktuellsten Versionen von Konfigurationssoftware (ab Version 2.05) und Gebrauchsanleitung zu verwenden.
Die Verwendung älterer Konfigurationsprogramme oder Gebrauchs anleitungen kann Funktionseinschränkungen oder Fehlfunktionen zur Folge haben.
2.1 Lieferumfang
Folgende Teile gehören zum Lieferumfang und müssen in der Sendung enthalten sein:
Drehzahl / KeyMonitor A6312
diese Produktinformation
Seite 20
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
Zubehör (nicht im Lieferumfang enthalten):
MMS ParaKit (Best.Nr. 951000027)
Sollte der Inhalt unvollständig sein oder irgend welche Defekte vorliegen, so muss beim Überbringer sofort reklamiert werden. Außerdem muss die zuständige epro Verkaufsstelle verständigt werden, um Reparatur oder Ersatz des Gerätes zu ermöglichen. Eventuell erforder­liche Reparaturen oder Kalibrierung von A6000 Monitoren sind nur im epro−Werk möglich.
2.2 CSA Zertifizierung
STOP
Zur gültigen CSA Zertifizierung müssen alle Geräte (IMR 6000/xx und A6000) mit einem entsprechenden CSA Label versehen worden sein.
Für den Fall das kein CSA Lable auf dem Gerät angebracht wurde ist dieses Gerät nicht CSA zugelassen!
Das entspechende CSA Label sieht wie nachfolgend dargestellt aus.
2.3 CSA Akzeptanzkriterien
Dieses Gerät muss mit Schutzkleinspannung SELV LPS (C22.2 609501) 24V betrieben werden. Diese Betriebsspannung muss von einem seperaten Speisegerät bezogen werden.
Das IMR System sollte in einem zweckmäßigen Feuerschutzgehäuse installiert werden.
Das IMR System ist bewertet für einen Umgebungstemperaturbereich von 0°C bis 45°C.
Es muss angemessener Zirkulationsfreiraum vorgesehen werden damit sich keine Hitze aufstauen kann. Der Zirkulationsfreiraum muss mindestens 1 HE (1
3/4
inch) in allen Richtungen betragen. Für den Fall das die Umgebungstemperatur des Racks über 45°C steigt müssen die gerätschaften mit einem festen Lüfter, einer Kühlvorrichtung etc. auf den entsprechend zugelassenen Temperaturbereich heruntergekühlt werden.
Werden mehrere 19” Rahmen übereinander in einem Schaltschrank installiert so sollten anstelle des Zirkulationsfreiraum entsprechende 1HE Lüftereinschübe installiert werden. Da die notwendigen Spezifikationen derartiger Lüfter aus den Umgebungs und Standortbedingungen des Schaltschrankes resultieren können keine generellen Lüfterspezifikationen festgelegt werden.
Seite 21
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
2.4 Hinweis zur Installation
STOP
Gemäß der IEC 61010 Richtlinie müssen fest installierte Systeme mit einer Trenneinrichtung (ggf. einem Schalter und/ oder einem Leitungsschutz schalter nach IEC60947−1 und IEC60947−3) zum unterbrechen der Spannungsversorgung ausgestattet sein. Bei Verwendung eines IMR Systems kann dies, unter Beachtung dieser Richtlinie, durch einen Schalter oder Leistungsschalter erfolgen.
Dazu muss sich dieser in der Gebäude bzw. Schaltschrankinstallation befinden, in unmittelbarer Nähe zum System implementiert sein und für den Anwender leicht zugänglich sein.
Des weiteren muss jede derartige Trenneinrichtung entsprechend dem zugehörigen System gekennzeichnet bzw. beschriftet sein.
2.5 Installation und Montage
Für die Montage des A6312 Monitors wird ein vorbereiteter Steckplatz in einem 19“ Baugruppenträger mit 3 HE oder ein anderes IntermasKompatibles Gehäuse benötigt. Der Steckplatz muss mit einem 48poligen Steckverbinder (DIN 41612, Bauform F 48 M) ausgestattet sein. Die PinBelegung ist in der nachfolgenden Tabelle aufgeführt.
d b z
2
UN+ (+24V) U (0V/Common) UB+ (+24V, redundant)
2
4
A (RS 485) GND (BP, Common, RS 485) B (RS 485)
4
6
Supply2+ (sensor) Supply1 (sensor) Supply1+ (sensor)
6
8
AIN2 (Input) Supply2 (sensor) AIN1 (Input)
8
10
AIN2+ (Input) GND AIN1+ (Input)
10
12
PU1 (24Vpull up pulse1) GND NC
(MMS6310)
/Test1
(MMS6312)
12
14
Pulse1C (collector) Pulse1E (emitter) Pulse1TTL
14
16
Pulse2C (collector) Pulse2E (emitter) Pulse2TTL
16
18
PU 2(24Vpull up pulse2) I1 (current output common) I1+ (current output CH1)
18
20
Reset peak value 1 I2 (current output common) I2+ (current output CH2)
20
22
NC
(MMS6310)
/ Test2
(MMS6312)
GND ES (external lock)
22
24
SCA (oper. principle GW2) GND SCD (oper. principle GW1)
24
26
GW1DC (danger1 collector) GW1AC (alert1 collector) CC1C (ch. clear1 collector)
26
28
GW1−D−E (danger1 emitter) GW1−A−E (alert1 emitter) CC1E (ch. clear1 emitter)
28
30
GW2DC (danger2 collector) GW2AC (alert2 collector) CC2C (ch. clear2 collector)
30
32
GW2−D−E (danger2 emitter) GW2−A−E (alert2 emitter) CC2E (ch. clear2 emitter)
32
Seite 22
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
Jumper für RS 485
Der Betrieb des RS 485 Busses erfordert einen elektrischen Abschluss jeweils am ersten und letzten Gerät des Busses. Dies geschieht mit Steckbrücken, die sich auf dem Kontrollerboard befinden. Das Bild zeigt die Position der Jumper.
Um den BusAbschluss zu aktivieren und die Leitungen “A” und “B” auf die Bezüge zu legen, stecken Sie die Jumper wie in Bild b) gezeigt. Das Bild a) zeigt die Jumperposition für einen deaktivierten BusAbschluss und offene Bezüge (Auslieferungszustand).
Steckbrücke 12 geschlossen: Busleitung “B” über Pulldown Widerstand an Masse
Steckbrücke 34 geschlossen: 120 Ω Widerstand zwischen “A” und “B”
Steckbrücke 56 geschlossen: Busleitung “A” über Pullup Widerstand an +5 V
135
2
46
135
2
46
a)
b)
i
Für einen störungsfreien Betrieb des RS 485 Busses müssen die Leitungen “A” und “B” in einem Monitor auf ihre Bezüge (+5 V; Masse) gelegt werden, dies ist nur möglich wenn in diesem Monitor auch der BusabschlussJumper gesetzt ist
MonitorEinbau
1. Überprüfen Sie vor Einbau des Monitors die Steckplatzverdrahtung.
2. Schieben Sie den A6312 Monitor in den vorbereiteten Steckplatz und drücken Sie ihn mit
leichtem Druck in den Steckverbinder.
3. Zur Sicherung des Monitors ziehen Sie die beiden Befestigungsschrauben auf der Front-
platte leicht handfest an.
Alle weiteren Informationen, wie z. B. Schirmung und Erdung, Konfiguration des Monitors, usw., finden Sie in der Gebrauchsanleitung “Drehzahl / Key−Monitor A6312”, Bestellnr. 610090025.
Seite 23
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
2.6 Technische Daten
Nur Angaben mit Toleranzen oder Grenzwerten sind verbindliche Daten. Daten ohne Toleranzen bzw. ohne Fehlergrenzen sind informative Daten. Technische Änderungen – vor allem der Software – bleiben vorbehalten.
Alle folgenden Angaben gelten, sofern nicht anders angeben, für Kanal 1 und Kanal 2 gleicher­maßen.
2.6.1 Signalkonditionierung
Zwei separate Signaleingänge für Kanal 1 und Kanal 2 mit voneinander entkoppelter Signalkonditionierung.
Messwerteingänge
Differenzspannungsverstärkereingänge, rückwirkungsfrei, leerlauf und kurzschlussfest.
Kanal 1 z8: SENS1−A−;z10: SENS1−B+
Kanal 2 d8: SENS2−A−;d10: SENS2−B+
Eingangsnennbereich 0...27,3 V DC
Grenzbereich 0...30 V DC
Eingangswiderstand > 100 kΩ
Signalkonditionierung
Sensorsignalausgänge Frontbuchsen SMB, entkoppelt, leerlauf und
kurzschlussfest, rückwirkungsfrei
Kanal 1 SENS 1 SMBBuchse für Kanal 1
Kanal 2 SENS 2 SMBBuchse für Kanal 2
Signalausgang 0...4,1 V; Signal = 0,15 x Sensoreingangssignal
Genauigkeit ±1 % vom Endwert
Frequenzbereich 0...16 kHz (−3dB) ±20 %
Zul. Belastungswiderstand >100 kΩ
Innenwiderstand 10 kΩ
Seite 24
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
Dynamische Ausgänge
TTLAusgänge Die aufbereiteten Eingangsimpulse werden mit
TTLPegel ausgegeben.
Pulse 1 TTL / Pulse 2 TTL z14 / z16 leerlauf− und kurzschlussfest, rückwir-
kungsfrei
Nennbereich 0...5 V ss
Frequenzbereich 0 Hz...20 kHz
Zul. Belastungswiderstand >100 kΩ
Innenwiderstand 10 kΩ
Key Impuls Ausgänge Potentialfreier Ausgang für Impulse 1 x pro
Umdrehung
Pulse 1 – UC / Pulse 2 UC d12 / d18 Speisung für Impulsausgang
Max. Spannung +24 V an UC, +48 V an Kollektor
Pulse 1C / Pulse 2−E d14 / b14 Kollektor−Emitterstrecke Impuls 1
Pulse 2C / Pulse 2−E d16 / b16 Kollektor−Emitterstrecke Impuls 2
Max. Strom bei CE leitend 100 mA
Impulsbreite 1 ms ±20 %
Bei Messart „Drehzahl” ist die Impulsbreite Zahnsyn­chron.
Ausgangslast (maximale Anzahl anzuschließender Monitore)
15, bei Uc = +24V, f 50 Hz, T 30°C
Signalkonditionierung für Kenngröße
Die Eingangssignale werden vor der Verarbeitung im Prozessor standardisiert. Die Kenngröße (Drehzahl) ist proportional zur Eingangsimplusfrequenz geteilt durch die eingestellte Anzahl der Polradzähne.
Bereichseinstellung wird bei der Konfiguration bestimmt
maximaler Messbereich Begrenzt durch die max. Eingangsfrequenz 20 kHz
maximaler Drehzahlwert 65535 UpM (durch 20 kHz begrenzt auf max. 18
Zähne)
maximale Anzahl Polradzähne 255
UpM
60s
* AnzahlZähne x 20000
1 s
bei z.B. 60 Zähnen max. 20000 UpM
Seite 25
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
StromausgängeKenngröße
Die Kenngrößenbildung und Bewertung ist abhängig von den bei der Konfiguration bestimmten Funktionen.
Stromausgang 1 (I1+ / I1) z18 / b18 (galvanisch getrennt)
Stromausgang 2 (I2+ / I2) z20 / b20 (galvanisch getrennt)
Nennbereich 0 ... 20 mA oder 4 ... 20 mA,
abhängig von der Konfiguration
Life zeroBetrieb Im 4 ... 20 mA Betrieb kann mittels der Konfiguration
bestimmt werden, dass der Ausgang bei Erkennung einer Störung auf 0 mA gesetzt wird.
Genauigkeit / Auflösung ±1 % vom Messbereichsendwert / 16 Bit
Zul. Belastungswiderstand max. 500 Ω
2.6.2 Kanalüberwachung
Überwachungsfunktion ständige Überwachung
Sensorsignale GUTBereich (konfigurationsabhängig)
Systemspannungen Spannung OK
μP Funktion (watchdog) WD – OK
Konfiguration & Parametrierung K&P – OK
externes Sperrsignal Ext. Lock
Status Kanalüberwachung
Kanalstatus = kein Fehler (OK) wenn ( Spannung_OK = Ja )
UND (WD_OK = Ja) UND ( K&P_OK = Ja ) UND ( Sensorsignal im GUT−Bereich )
UND (Extern Sperren = Nein)
Kanalstatus = Fehler falls die vorherige Bedingung nicht erfüllt ist
Interne Wirkung Im Fehlerfall wirkt die Kanalüberwachung auf die
Kenngröße und die Grenzwertbildung nur wenn die Unterdrückung in der Konfiguration aktiviert worden ist.
Seite 26
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
Visualisierung
Grüne LED auf der Frontplatte
Kanalstatus = kein Fehler (OK) Dauerlicht
Kanalstatus = Fehler Dunkel
GapFehler Blinklicht 0,2 s Takt
Parametrierfehler / Watchdog Blinklicht 1 s Takt
Ausgänge Channel Clear
optoentkoppelte Kollektor/EmitterStrecken
Channel Clear Kanal 1, C1C / C1E z26 (Kollektor) / z28 (Emitter)
Channel Clear Kanal 2, C2C / C2E z30 (Kollektor) / z32 (Emitter)
Ext. gesperrt oder Status = Fehler CE gesperrt, max. zul. Spannung: 48 V
nicht ext. gesperrt und Status = OK CE leitend, max. zul. Strom: 100 mA
Binäreingänge
Signalpegel LOW: 0 ... +3 V, HIGH: +13 ... +48 V
Eingang extern Sperren ES
z22 zum Sperren der Grenzwertalarme, z.B. bei Wartungsarbeiten etc.
Funktion Sperren Eingang LOW = Sperren der Kanalüberwachung und
der Grenzwertbildung
Freigabe Eingang HIGH oder unbeschaltet = kein Sperren der
Kanalüberwachung und der Grenzwertüberwachung
Reset Latch
d20 zum Zurücksetzen der Selbsthaltung der Funktionsausgänge, der gespeicherten DrehzahlSpitzenwerte und Drehrichtungsreset
Reset Eingang LOW
kein Reset Eingang HIGH oder unbeschaltet
Test Kanal 1 / Kanal 2
z12 / d22 aktivieren des intern generierten Prüfwerts
Testbetrieb Eingang LOW
Normalbetrieb Eingang HIGH oder unbeschaltet
Seite 27
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
2.6.3 Funktionsausgänge und Alarme
Zwei Funktionsausgänge pro Kanal mit separater Funktions bzw. Grenzwerteinstellung. Die Funktion wird in der Konfiguration bestimmt, somit auch die Schaltcharakteristik.
Grenzwerteinstellung
Durch Parametrierung, abhängig von der zugeordneten Funktion. Bei den Funktionen Drehrichtung und Stillstand keine Grenzwerte.
Einstellbereich 0 ... 100 % des parametrierten Messbereichs
Auflösung 0,1 % bezogen auf den Messbereichsendwert,
1 UpM bei Drehzahlen bis 12000 UpM
Hysterese parametrierbar
Reaktionszeit
Verzögerungszeit zwischen Kenngößenbildung und Grenzwertalarm (nur für KanalGrenz wertfunktion)
mittlere Reaktionszeit 2 ms
Blockierung der Ausgänge
Blockierung Wenn (Spannung oder Watchdog nicht ok) ODER
(Ex. Sperren = sperren) ODER (Kanalstatus = nicht ok*)
keine Blockierung wenn obige Bedingung nicht erfüllt ist
* Nur wenn in der Konfiguration die Grenzwertunterdrückung aktiviert ist.
Visualisierung des Ausgangsstatus
Durch je eine gelbe LED.
Ausgang nicht aktiviert, in Grund­stellung (keine Grenzwertüber­schreitung) oder Ausgänge blockiert.
LED aus
Ausgang aktiviert (Grenzwertver­letzung, Funktion „wahr”)
LED hat Dauerlicht
Seite 28
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
Funktionsausgänge
Optoentkoppelte KollektorEmitterSchalter
Out 11 C / Out 11 E d26 (Kollektor) / d28 (Emitter)
Out 12 C / Out 12 E b26 (Kollektor) / b28 (Emitter)
Out 21 C / Out 21 E d30 (Kollektor) / d32 (Emitter)
Out 22 C / Out 22 E b30 (Kollektor) / b32 (Emitter)
Maximalwerte für Alarmausgänge CE gesperrt: max. zulässig UCE = 48 V
CE leitend: max. zulässig ICE = 100 mA
Funktionsausgänge aktiv leitend im Arbeitsstrombetrieb
gesperrt im Ruhestrombetrieb
Arbeitsstrom und Rubestrombetrieb
Durch externe Beschaltung der Eingänge d24 und z24, Wählbar für die Funktionsausgänge Out 11 und Out 21.
Out 12 und Out 22 sind immer im Arbeitsstrombetrieb.
Umschaltung Out 1−1 d24 = HIGH / unbeschaltet → Arbeitsstrom
d24 = LOW Ruhestrombetrieb
Umschaltung Out 2−1 z24 = HIGH / unbeschaltet → Arbeitsstrom
z24 = LOW Ruhestrombetrieb
Schaltpegel LOW: 0 ... +3 V
HIGH: 13 ... 48 V
Eingangswiderstand >10 kΩ
2.6.4 Kommunikationsschnittstellen
Schnittstelle RS232
Frontbuchse zum Anschluss eines Rechners zwecks Konfiguration und Visualisierung
Rundsteckverbinder auf Frontseite MiniDIN–Buchse Typ TM 0508A/6 für
Parametrierkabel (Bestellnr. 5700−00003, im Operating Kit enthalten)
Schnittstelle RS485
d4, z4 Busschnittstelle für Kommunikation mit dem epro−Analyse− und Diagnosesystem MMS 6850 und für die Konfiguration.
Seite 29
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
2.6.5 Spannungsversorgung
Die Monitorsystemspannungen und somit auch die 0 V / commonAnschlüsse für die Mess und Überwachungsein− und −ausgänge sind voneinander galvanisch getrennt.
Versorgungsspannungseingänge zwei redundante, diodenentkoppelte Eingänge für
nominal +24 V mit gemeinsamen 0 V Bezug
Spannungseingang UB+ / UN+ d2 / z2
Gemeinsamer Bezug, 0 V U b2
Zul. Spannungsbereich 19 ... 31,2 Vdc (IEC 654−2 Klasse DC 4)
CSA: 24Vdc; SELV LPS
Leistungsaufnahme max 6W, bei 24 V max. 250 mA
Monitorsystemspannung
Die für die interne Versorgung benötigten MonitorSystemspannungen werden ständig auf Unterspannung überwacht. Bei Erkennung einer Unterspannung wird eine Fehlermeldung generiert.
Sensorspeisung
für beide Kanäle des Monitors
Trennung Entkoppelt und zu den übrigen Systemspannungen
und zur Versorgungsspannung galvanisch getrennt, mit anderen Monitoren parallel rückwirkungsfrei
betreibbar, leerlauf und kurzschlussfest.
Sensorspeisung Kanal 1 Sup.Ch1 + /Sup.Ch1− z6 / b6
Sensorspeisung Kanal 2 Sup.Ch2 + /Sup.Ch2− d6 / b8
Speisespannung 26,75 V DC; Toleranz ±2 %
Restwelligkeit < 20 mVss (bei Nennstrom 20 mA)
max. Strom 35 mA
max. Kurzschlussstrom 0 mA ≤ Ikurzschl. ≤ 5 mA;
leerlauf und kurzschlussfest
Seite 30
Product Information / Produktinformation
A6312
Drehzahl / KeyMonitor
2.6.6 Umgebungsbedingungen
Anwendungsklasse KTF nach DIN 40040
Umgebungstemperatur
Bezugstemperatur +25 °C
Nenngebrauchsbereich 0...+45°C (CSA Anforderung und empfohlener Bereich)
max. Bereich −10°C ... +65°C (nicht CSA konform)
Betriebshöhe bis zu 2000m über NN
Lagerungs, Transporttemperatur −30... +85 °C
Relative Feuchte 95 % ohne Betauung
Schwingung nach IEC−68 − 2 Teil 6
Weg 0,15 mm bei 10...55 Hz
Beschleunigung 19,6 mm/s2 bei 55...150 Hz
Schock nach IEC−68 − 2 Teil 29
Beschleunigungsspitzenwert 98 m/s
2
Nominelle Schockdauer 16 ms
Gehäuseschutzart IP 00, offene Bauweise nach DIN 40050
EMVFestigkeit nach EN 50 0811 / EN 50 0822 erfüllt
Zulässiger Verschmutzungsgrad Kategorie 2 (nach IEC 61010−1)
Betriebsumgebung Gebrauch ausschließlich in geschlossenen Räumen
2.6.7 Mechanischer Aufbau
Leiterplatte EuroFormat (100 mm x 160 mm) nach DIN 41494
Breite A6312/06 6 TE (ca. 30 mm )
A6312/08 8 TE (ca. 40mm)
Steckverbinder DIN 41612, Bauform F 48 M
Frontelemente
2 LEDs Grün Channel Clear Kanal 1 / 2
4 LEDs Gelb Messart „Key”: Impulszustand Kanal 1 / 2
Messart „Drehzahl”: Zustand der Funktionsausgänge
4 SMB Steckbuchsen für Sensorsignal Kanal 1 / 2 und
TTLImpulse Pulse 1 / 2
1 MiniDIN Rundsteckbuchse für RS 232 zum Anschluss eines Laptops (zwecks
Konfiguration und Parametrierung)
Gewicht ca. 320 g (ohne Verpackung)
ca. 450 g (mit Standardverpackung)
Page/Seite 31
Product Information / Produktinformation
A6312
Connection Diagrams and Figures / Anschlusspläne und Abbildungen
3 CONNECTION DIAGRAMS AND FIGURES /
ANSCHLUSSPLÄNE UND ABBILDUNGEN
U
U
GND
UN+
U
UB+
Extern lock
Sens 1+
Sens 1
Sens 1−A−NEG
Sens 1−B−POS
SensC
ABC1C
C1E
C2C
C2E
Pulse2 TTL
24 V Pull up Pullse1
GND
CC
2
Sens 2+
Sens 2
Sens 2−A−NEG
Sens 2−B−POS
Sensor signal 1
Out −1
Out −2
Reset
RS232
Front socket
GND
GND
Controller
d14
b14
J1
RS
232
d4
z4
J2
RS
485
z26
z28
z30
z32
d12
b12
b24
b22
z2b2d2
z12
d22
d20
z6
b6
U
U
z8
z10
b10
d8
d10
Sensor signal 2
d6
b8
U
U
d6
b8
GND
b4
HardwareStart
Automatic measurement
Pulse 1
Pulse 2
1
12
12
Puls 1 Collector
Puls 1 Emitter
24 V Pull up Pulse2
d16
b16
d18
Pulse2 Collector
Pulse 2 Emitter
Pulse1 TTL
z14
z16
Pulse generation
Pulse generation
MUX
z22
Test Channel 1
Test Channel 2
Out 11 K
Out 11 E
Out 12 K
Out 12 E
b26
b28
d26
d28
Out 21 K
Out 21 E
Out 22 K
Out 22 E
b30
b32
d30
d32
D
A
U
I
Pulse2 TTL
Pullse1 TTL
z14
z16
Pulse2 TTL
Pullse1 TTL
z14
z16
D
A
U
I
Block diagram / Blockschaltbild A6312
Page/Seite 32
Product Information / Produktinformation
A6312
Connection Diagrams and Figures / Anschlusspläne und Abbildungen
A6312
Speed / KeyMonitor
+24V /2
0V (24V)
+24V /1
d2
b2
z2
UB+UN+
U
A
B
BP
d4b4z4
Pull up
P1E
P1C
ES
GND
z22
d20
z32
z30
z28
z26
CHANNEL
CLEAR 1
CHANNEL
CLEAR 2
RESET
P1TTL
P2TTL
z14
z16
GND
b24
C1C
C1E
C2C
C2E
0V
+24V
RS485 Bus
Reset
Ex. lock
Puls 1C collector
Puls 1 TTLsignal
Puls 2 TTLsignal
24V
OUT
CON 0xx
z8
z10
b10
z6
b6
d8
d10
d6
b8
Sens1+
Sens1
Sens2+
Sens2
PR 642x
SensC
Sens1ANEG
Sens1BPOS
Sens2ANEG
Sens2BPOS
Signal groundProtective earth
b22
Cabinet
Field
24V
OUT
CON 0xx
PR 642x
to
protective earth
d12
d14
b14
Puls 1E emitter
+24 V Pull up Pulse 1
Pull up
P2E
P2C Puls 2C collector
d18
d16
b16
Puls 2E emitter
+24 V Pull up Pulse 2
d22
z12
Test channel 1
Test channel 2
I1+
I2+
z18
z20
I1
b18
Current output 1
Current output 2
I2
b20
Out 11 inv.
d24
Out 11 in quiescent current
Out 21 inv.
z24
Out 21 in quiescent current
d32
d30
b32
b30
Out 2−1
Out 2−2
C1C
C1E
C2C
C2E
d28
d26
b28
b26
Out 1−1
Out 1−2
C1C
C1E
C2C
C2E
Connection diagram eddy current measuring chains Anschlussdiagramm Wirbelstrommessketten
Page/Seite 33
Product Information / Produktinformation
A6312
Connection Diagrams and Figures / Anschlusspläne und Abbildungen
A6312
Speed / KeyMonitor
+24V /2
0V (24V)
+24V /1
d2
b2
z2
UB+
UN+U
A
B
BP
d4b4z4
Pull up
P1E
P1C
ES
GND
z22
d20
z32
z30
z28
z26
CHANNEL
CLEAR 1
CHANNEL
CLEAR 2
RESET
P1TTL
P2TTL
z14
z16
GND
b24
C1C
C1E
C2C
C2E
0V
+24V
RS485 Bus
Reset
Ex. lock
Puls 1C collector
Puls 1 TTLsignal
Puls 2 TTLsignal
Sens1+
Sens1
Sens2+
Sens2
SensC
Sens1ANEG
Sens1BPOS
Sens2ANEG
Sens2BPOS
d12
d14
b14
Puls 1E emitter
+24 V Pull up Pulse 1
Pull up
P2E
P2C
Puls 2C collector
d18
d16
b16
Puls 2E emitter
+24 V Pull up Pulse 2
d22
z12
Test channel 1
Test channel 2
I1+
I2+
z18
z20
I1
b18
Current output 1
Current output 2
I2
b20
Out 11 inv.
d24
Out 11 in quiescent current
Out 21 inv.
z24
Out 21 in quiescent current
d32
d30
b32
b30
Out 2−1
Out 2−2
C1C
C1E
C2C
C2E
d28
d26
b28
b26
Out 1−1
Out 1−2
C1C
C1E
C2C
C2E
+VS (blue)
OUT (white)
PR 9376
z8
z10
b10
z6
b6
d8
d10
d6
b8
Signal ground
Protective earth
b22
CabinetField
to
protective earth
VS (screen)
connectionbox
+VS (blue)
OUT (white)
PR 9376
VS (screen)
connectionbox
Connection diagram PR 9378 Anschlussdiagramm PR 9376
Page/Seite 34
Product Information / Produktinformation
A6312
Connection Diagrams and Figures / Anschlusspläne und Abbildungen
2
6
4
8
10
12
14
16
18
20
22
24
26
28
30
32
2
6
4
8
10
12
14
16
18
20
22
24
26
28
30
32
db z d b
UB+ (+24V) U− (0V/Common) UN+ (+24V redundant)
Sens2+ (sensor supply ) Sens1−(sensor supply) Sens1+ (sensor supply)
Sens2−A−NEG (input) Sens2− (sensor supply) Sens1−A−NEG (input)
Sens2−B−POS (input)
Sens−C (GND/Common) Sens1−B−POS (input)
A (RS 485) BP (Common) RS 485 B (RS 485)
24 V Pull up pulse 1 GND
Test channel 1
Puls1−C collector
I1 0/4...20mA channel 1
Puls1−TTL
Puls2−C collector Puls2−E emitter Puls2−TTL
24 V Pull up pulse 2 I1+ 0/4...20mA channel 1
Reset Spitzenwert I2 0/4...20mA channel 2 I2+ 0/4...20mA channel 2
GND Common ES alarm stop
Switch over Out 11 GND Common Switch over Out 2−1
Out 12 collector
Out 22 collector
Out 11 collector
Out 21 collector
C1−C CC1 collector
C2−C CC2 collector
Out 12 emitter
Out 22 emitter
Out 11 emitter
Out 21 emitter
C1−E CC1 emitter
C2−E CC2 emitter
Puls1E emitter
Test channel 2
Pin allocation Steckerbelegung
Page/Seite 35
Product Information / Produktinformation
A6312
Connection Diagrams and Figures / Anschlusspläne und Abbildungen
All dimensions in mm
Alle Abmessungen in mm
30.1 / 40.1
6TE / 8TE
128.4
3 HE
2.5
17
173.5
1
00
160
27
2.5
Dimensions A6312 Abmessungen A6312
Page/Seite 36
Product Information / Produktinformation
A6312
PI Revision List
4 PI REVISION LIST
Version Date Changes Chapter
1.000 02.04.2011 Initial Version (based on PI MMS6312 Rev: 18.04.2007)
1.010 17.05.2011 Additional Information (CSA relevant) all
1.020 17.05.2011 Change of front cover design
1.030 17.05.2011 Re brand from MMS6740 to A6740 all
1.031 23.05.2011 Change of front cover subtitle
1.032 25.02.2013 Change of service address Europe
EG-Konformitätserklärung
EC-Declaration of Conformity
Wir (We): epro GmbH, Jöbkesweg 3, 48599 Gronau
erklären in alleiniger Verantwortung, dass das Produkt:
declare under the exclusive liability that the product:
Produktbezeichnung (Product designation): System A6000 Produktbeschreibung (Product description): Modul zur Auswertung von dynamischen und
statischen Messwerten. Module for evaluation of dynamic and static
measuring values
Artikelnummer (Product codes): 919900XXX CEKennzeichnung entsprechend der EU Richtlinie/ CE identification corresponds to EU directive:
98/336 / EWG (EMV) geändert/ modified 97/236 ; EWG 92/31 / EWG; 93/68 / EWG.
auf das sich diese Erklärung bezieht, mit der/den folgenden Norm(en) oder normativen Doku­menten übereinstimmt:
which is subject of this declaration, is in conformity with the following standards or normative documents:
Bestimmungen der Richtlinie
Terms of the directive
Titel und/oder Nr.
Title and/or no.
Fachgrundnorm Störaussendung, Industriebereich
Engineering standard interference emission, industrial applications
Fachgrundnorm Störfestigkeit, Industriebereich
Engineering standard interference immunity, industrial applications
DIN EN 55011 + A1 + A2 DIN EN 61326 + A1 + A2 + A3 einschliesslich / including: DIN EN 61000−4−2 + A1 + A2 DIN EN 61000−4−3 + A1 DIN EN 61000−4−4 DIN EN 61000−4−5 + A1 DIN EN 61000−4−6 + A1
Wir weisen darauf hin, dass
die Konformität und damit die Betriebserlaubnis erlischt, wenn dieses Erzeugnis ohne unsere ausdrückliche Genehmigung geändert wird.
NichtFachleute die Gegebenheiten des Einsatzgebietes und die daraus resultierenden Anforderungen vor der Inbetriebnahme prüfen lassen sollen.
We point out that
the conformity and thus the approval for the operation lapses, if the product is modified without our explicit permission (without consultation with us).
Non specialists should let check the conditions of the operational area and the requirements resulting thereof before installation.
Gronau, 04.05.2011
Ort und Datum Geschäftsbereichsleiter Leiter Qualitätsmanagement
Place and date Divisional director Head of quality management
Certif_MMS_06_Rev_02