Emerson A6312 Quick Start Manual

Quick Start Guide
MHM-97448
NC: 6540-90025
Rev.: 1.032
CSI 6500 Machinery Health™Monitor
A6312, Dual Channel Speed/ Key Monitor
835 Innovation Drive
Knoxville, TN 37932 USA
T 1(865) 675-2400
F 1(865) 218-1401
www.EmersonProcess.com
©2010, Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has
been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available on request.We reserve the right to modify or
improve the designs or specifications of our products at any time without notice.
All rights reserved. Machinery Health is a mark of one of the Emerson Process Management group of
companies. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are
the property of their respective owners.
GB
Explanation of symbols
!
If this symbol is printed on a device, according to IEC 61010 it means that the documentation of the device must be completely read and understood before installation and commissioning of the device. All safetyrelated instructions of this document must be observed. These safetyrelated instructions are marked by the “STOP” symbol in this document.
If this symbol is printed on a device, according to IEC 61010 it means that this device must be operated with DC voltage.
i
This symbol identifies text that contains important information.
!
Not following instructions identified with this symbol can result in functional issues and incorrect measurements without damaging the machine.
STOP
Safety and warning instructions are identified with this symbol. Failure to observe these instructions can result in material damage or
personal injury.
D
Symbolerklärung
!
Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010 aus, das es zur Installation und Inbetriebnahme des Gerätes zwingend erforderlich ist, die Dokumentation des Gerätes vollständig gelesen und verstanden zu haben. Sicherheitsrelevante Hinweise in dieser Dokumentation sind unweigerlich zu beachten und im weiteren Verlauf dieser Dokumentation durch das “STOP” Symbol (siehe unten) gekennzeichnet.
Ist dieses Symbol auf einem Gerät angebracht, so sagt dies nach IEC 61010 aus, dass es mit Gleichspannung betrieben wird.
i
Dieses Symbol kennzeichnet Textstellen, die wichtige Informationen enthalten.
!
Hinweise, die bei Nichtbeachtung zu Funktionsstörungen und Fehlmessungen führen, ohne das Gerät zu beschädigen, sind mit diesem Symbol gekennzeichnet.
STOP
Sicherheits- und Warnhinweise sind mit diesem Symbol gekennzeichnet. Die Nichtbeachtung solcher Hinweise kann zu Sachbeschädigungen oder
Personenschäden führen.
Product Service Centers
America
Emerson Process Management 835 Innovation Drive Knoxville, TN 37932 Tel: 8656752110 Fax: 865−218−1401
Brazil
Emerson Process Management Ltd. Av Hollingsworth 325 Sorocaba, SP BRAZIL 18087−000 Phone: 55 15 2383788 Fax: 55 15 22823300
Europe, Middle East, Africa
Emerson Process Management div. ESAD MHM Repair Center Piestanska 1202/44 915 28 Nove Mesto nad Vahom Slowakia Tel: +421/32/7700 538 Fax: +421/32/7700 884
Asia
Emerson Process Management / Asia Pacific Private Ltd.
3904 Room Central Plaza 18 Harbour Road Wan−Chai Hong Kong Tel: 852−2802−9223 Fax: 852−2802−8227
Incoming goods inspection
Check the content of the shipment to ensure that it is complete; visibly inspect the goods to determine if the device may possibly have been damaged during transport. The following parts are included in the scope of delivery and must be contained in the shipment.
1. A6312
2. Product information
If the contents are incomplete, or if any defects are observed, a complaint must be filed with the carrier immediately. Moreover, the responsible Emerson sales organization must be informed to enable repair or replacement of the device. Repairs or calibration that may be required, are only possible at the Emerson factory.
In this case, a nondetachable tag with customer name, defect observed and version of the A6910 configuration software must be attached to the device.
Repair and maintenance
During operation, monitors do not require any mainte­nance.
Repair or calibration of monitors is only possible at Emerson.
i
The additional PCB (controller board) is calibrated with the main board and must not be replaced.
If work with the opened device onsite is unavoidable, this should only be performed by a specialist who is familiar with the associated hazards.
STOP
Capacitors in the device can still be energized, even if the device has been disconnected from all power sources.
If repair or recalibration of a monitor is required, it must be sent to Emerson. Attach a non−detachable tag to the monitor with customer name, defect observed and version of the A6910 configuration software.
Guidelines for Returning Equipment to the Product Service Center
If repair or calibration of a monitor is required, it must be sent to Emerson. Occasionally, concerns with CSI technology hardware could arise. Should this happen, customers under warranty or a current support agreement are entitled to no−charge repairs.
Follow the checklist below to minimize return time and ensure proper processing of your equipment. Before returning any equipment to a Product Support Center, please review this information:
1. Obtain a Return Materials Authorization (RMA) number and the address of the appropriate Product Service Center by calling 865.675.4274*.
Listen to the options for receiving an RMA. You will be routed to support personnel who will document your concern and give you an RMA number if you are under support or warranty. If your hardware is not under support or warranty, you must have a Purchase Order for the amount of the repair service before you can receive an RMA number. Pricing for your repair can be obtained from support personnel or by calling your local sales representative. Once you have your purchase order, call 865.675.4274* for an RMA.
2. Once you have received your RMA, send your hardware to the appropriate product service center. Your hardware package should include:
G RMA Number (plus Purchase Order if
applicable)
G Description of the hardware
problem
G Return shipping address including a
phone number (No P.O. boxes).
G Any special request regarding the
return shipment.
G A list of the model numbers of each
item(s) being returned, along with the serial number.
G Your name, address, telephone
number and email address.
G Company Name.
A form for completing this information has been provided.
Make a copy of the form, complete all lines, and return a copy in each return shipment.
Out of warranty? Need to get under support? Get a customized quote for bringing all your CSI technologies under a support agreement: Phone: 865.675.2400*, ext. 2130 Fax: 865.218.1478* Email: mhm.supportagreement@emersonproces s.com
*Customers outside the Americas and Canada: please refer to the list of service centers and contact the service center near you.
All rights are strictly reserved
Reproduction or divulgation in any form whatsoever is not permitted without written authority from the copyright owner.
RMA Required Information
RMA number issued by Product Service Center:
For all items beingreturned, please list Model / Serial Number:
Are you under warranty or a current support agreement (circle one)?
Yes No
If you answered no, what is your purchase order number?
Company Name:
Contact Name:
Contact Address:
Contact Phone:
Contact Fax:
Contact Email:
Please describe the problem you are experiencing:
If we are to send the return shipment to someone other than the Contact Name/Address above, please provide that address here, including Contact Name and Phone Number:
Are there any special instructions regarding the return?
Please provide invoice address (if a purchase order was required):
Support customers your instrument is shipped back to you the same way that it is sent to our service center. For example, if you ship via ground transportation, it is shipped back via ground.
Page/Seite 7
Product Information / Produktinformation
A6312
1
GB
Rotational Speed Monitor 8......................
1.1 Scope of Delivery 8...........................................
1.2 CSA Certification 9...........................................
1.3 CSA Conditions of acceptability 9............................
1.4 Advice for Installation 9.......................................
1.5 Installation and Mounting 9...................................
1.6 Technical data 11..............................................
1.6.1 Signal conditioning 11.......................................................
1.6.2 Channel monitoring 13......................................................
1.6.3 Function outputs and alarms 15..............................................
1.6.4 Communication interfaces 16.................................................
1.6.5 Power supply 17............................................................
1.6.6 Environmental conditions 18.................................................
1.6.7 Mechanical structure 18.....................................................
2
D
Drehzahl / KeyMonitor 19.......................
2.1 Lieferumfang 19...............................................
2.2 CSA Zertifizierung 20..........................................
2.3 CSA Akzeptanzkriterien 20....................................
2.4 Hinweis zur Installation 21......................................
2.5 Installation und Montage 21....................................
2.6 Technische Daten 23...........................................
2.6.1 Signalkonditionierung 23.....................................................
2.6.2 Kanalüberwachung 25.......................................................
2.6.3 Funktionsausgänge und Alarme 27............................................
2.6.4 Kommunikationsschnittstellen 28.............................................
2.6.5 Spannungsversorgung 29....................................................
2.6.6 Umgebungsbedingungen 30..................................................
2.6.7 Mechanischer Aufbau 30....................................................
3 Connection Diagrams and Figures /
Anschlusspläne und Abbildungen 31....................
4 PI Revision List 36.....................................
Page 8
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1
GB
ROTATIONAL SPEED MONITOR
!
This product Information contains general information about the dual channel speed/ key monitor types A6312/06 & A6312/08. If not stated otherwise, all information denoted by A6312 is valid for both types, listed before.
The twochannel rotational speed monitor A6312 is a module of the A6000 machine monitoring system. The microprocessor controlled monitor is used in conjunction with two eddy current measuring chains or halleffect sensors (e.g. PR 9376) and in combination with triggering wheels to measure and conditioning of shaft speeds and rotational reference marks (keypulses).
Both channels may be used separately used to measure:
2 speeds from 2 shafts
2 keypulses from 2 shafts each with a triggermark (with phase relation)
Both channels may also be used in combination with each other:
to detect the direction of rotation of one shaft
to detect a difference between two shaft speeds
i
In this product information the mounting and electrical connection of the monitor is described.
For secure use of the monitor, observe the direction for use “Rotational Speed Monitor A6312” (order number: 611090025). You can find this direction on the configuration software CD as pdfdata file. Amongst others, it contains useful informations for configuration and use of the A6312.
To ensure the safe operation of the monitor and to permit setting of all functions, it is indispensable to use only the latest versions of configuration software (version 2.05 or newer) and operating manual.
The use of old operating manuals or configuration programs out of date may lead to malfunctions or limitations of the measuring functions.
1.1 Scope of Delivery
The following parts are included in the scope of delivery and must be contained in the shipment:
Rotational Speed Monitor A6312
This product information
Accessories (not included in delivery):
MMS ParaKit (order no.: 9510−00027)
If the contents are incomplete or if is there any damage, so directly complain at the bearer. The competent epro−sales agency must be also informed, to enable repair or replacement for the monitor. Repair or calibration of this instrument may only be done at epro.
Page 9
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1.2 CSA Certification
STOP
For valid CSA certification, all devices (IMR 6000/xx and A6000 modules) must be marked with the respective CSA lable.
If no CSA lable is available on the respective device, this device is not CSA certified!
The respective CSA lable looks as shown in the following picture.
1.3 CSA Conditions of acceptability
This device must be supplied with safety low voltage SELV LPS (C22.2 609501) 24V. The voltage required for operation must be drawn from a separate power supply.
The IMR system should be placed in a suitable fire enclosure.
The IMR system is evaluated for an ambient of 0°C to 45°C.
Adequate ventilation space has to be provided so that heat does not build up. The ventilation space must be at least 1 RU (1
3/4
inch) in all directions. If the ambient temperature of the rack
rises above 45 °C, cool this instrument with a forced air fan, cooler, or similar.
When mounting several IMR units above each other in one cabinet, install cooling fan racks in between instead of the ventilation space. The necessary specifications for cooling fan racks result from the environmental and sitting criterions of the cabinet and thus cannot be defined generally.
1.4 Advice for Installation
STOP
According to the IEC 61010 directive, permanently installed systems must be equipped with a power disconnect device (e.g. a switch or circuit−breaker according to IEC609471 and IEC609473). When using an IMR rack, in compliance with this directive, such a switch or breaker must be implemented into the cabinet installation and easily accessible for the user. Furthermore, each disconnect devices must be labeled in accordance to the associated system.
1.5 Installation and Mounting
A prepared 3U slot in a 19” rack, or other Intermas−compatible enclosure, is required for mounting the A6312 monitor. The slot must be fitted with a 48−pin plug connector (DIN 41612, design F 48 M). The pin assignment is listed in the following table.
Page 10
Product Information / Produktinformation
A6312
Rotational Speed Monitor
d b z
2
UN+ (+24V) U (0V/Common) UB+ (+24V, redundant)
2
4
A (RS 485) GND (BP, Common, RS 485) B (RS 485)
4
6
Supply2+ (sensor) Supply1 (sensor) Supply1+ (sensor)
6
8
AIN2 (Input) Supply2 (sensor) AIN1 (Input)
8
10
AIN2+ (Input) GND AIN1+ (Input)
10
12
PU1 (24Vpull up pulse1) GND NC
(MMS6310)
/ Test1
(MMS6312)
12
14
Pulse1C (collector) Pulse1E (emitter) Pulse1TTL
14
16
Pulse2C (collector) Pulse2E (emitter) Pulse2TTL
16
18
PU 2(24Vpull up pulse2) I1 (current output common) I1+ (current output CH1)
18
20
Reset peak value 1 I2 (current output common) I2+ (current output CH2)
20
22
NC
(MMS6310)
/ Test2
(MMS6312)
GND ES (external lock)
22
24
SCA (oper. principle GW2) GND SCD (oper. principle GW1)
24
26
GW1DC (danger1 collector) GW1AC (alert1 collector) CC1C (ch. clear1 collector)
26
28
GW1−D−E (danger1 emitter) GW1−A−E (alert1 emitter) CC1E (ch. clear1 emitter)
28
30
GW2DC (danger2 collector) GW2AC (alert2 collector) CC2C (ch. clear2 collector)
30
32
GW2−D−E (danger2 emitter) GW2−A−E (alert2 emitter) CC2E (ch. clear2 emitter)
32
Jumper RS 485
RS 485 bus operation requires an electrical terminator on the first and last bus device.
This is done with plugin jumpers, that are on the controller board. The figure shows the position of the jumpers.
To activate the bus terminator and to place lines “A” and “B” on the references, plug the jumpers as shown in Fig. b). Fig. a) shows the jumper position for deactivated bus termination and open references (delivery status).
Plugin jumper 12 closed: Bus line “B” via pulldown resistor on ground
Plugin jumper 34 closed: 120 Ω Resistor between “A” and “B”
Plugin jumper 56 closed: Bus line “A” via pullup resistor on +5 V
Page 11
Product Information / Produktinformation
A6312
Rotational Speed Monitor
1
35
2
46
1
35
2
46
a)
b)
i
For troublefree operation of the RS 485 bus, the lines “A” and “B” in one monitor must be connected on their references (+5 V, ground), this is only possible if the bus terminator jumper is also set in this monitor.
Installation
3. Check the slot wiring prior to installing the monitor.
4. Push the A6312 monitor into the prepared slot and press it with light pressure into the plug
connector.
5. Hand tighten the two anchoring screws on the front panel to secure the monitor
Any other information, e. g. shielding and grounding, configuration of the monitor, etc., can be found in the direction for use “Rotational Speed Monitor A6312”, order number: 6110−90025.
1.6 Technical data
Only information with tolerances and limit values are considered as binding data. Data without tolerances or error limits are provided as information only. We reserve the right to make technical changes – particularly to the software.
All of the following information applies uniformly for channel 1 and channel 2, if not otherwise specified.
1.6.1 Signal conditioning
Two separate signal inputs for channel 1 and channel 2 with uncoupled signal conditioning.
Measured value inputs
Differential voltage amplification inputs, nonreactive, opencircuit and shortcircuit proof.
Channel 1 z8: SENS1−A−;z10: SENS1−B+
Channel 2 d8: SENS2−A−;d10: SENS2−B+
Input nominal range 0... 27,3 V DC
Limit range 0 ... 30 V DC
Input resistance > 100 kΩ
Page 12
Product Information / Produktinformation
A6312
Rotational Speed Monitor
Signal conditioning
Sensor signal outputs Front sockets SMB, decoupled, opencircuit and
shortcircuit proof, nonreactive.
Channel 1 SENS 1 SMB Ch1
Channel 2 SENS 2 SMB Ch2
Signal output 0 ... 4,1 V; signal = 0,15 x sensor input signal
Precision ±1 % of f.s.d.
Frequency range 0 ... 16 kHz (3 dB) ±20 %
Per. load resistance > 100 kΩ
Internal resistance 10 kΩ
Dynamic outputs
TTL – Outputs The processed input signals are output as TTL signals
Pulse 1 TTL / Pulse 2 TTL z14 / z16 open−circuit and short−circuit proof,
nonreactive
Nominal range 0...5 V pp
Frequency range 0.....20 kHz
permissible load >100 kΩ
Source impedance 10 kΩ
Key pulse outputs Potential free output for pulses 1 x per revolution
Pulse 1UC /Pulse2UC d12 / d18 supply for pulse output
Max. voltage +24 V at UC +48 V DC at collector
Pulse 1C / Pulse 1−E d14 / b14 collector – emitter line pulse 1
Pulse 2C / Pulse 2−E d16 / b16 collector – emitter line pulse 2
Max. current CE conducting 100 mA
Pulse duration 1 ms ±20 %
At measuring mode “Speed”, the pulse duration is synchronous to the tooth.
Output load (maximum number of modules to be connected)
15, at Uc +24 V, f < 50 Hz, T < 30°C