Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure you thoroughly understand the contents before
installing, using, or maintaining this product.
Within the United States, Rosemount Inc. has two toll-free assistance numbers:
Customer Central
Technical support, quoting, and order-related questions.
1-800-999-9307 (7:00 am to 7:00 pm CST)
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of the United States, contact your local Emerson Process Management
representative.
The products described in this document are NOT designed for nuclear-qualified
applications. Using non-nuclear qualified products in applications that require
nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson
Process Management Sales Representative.
This manual provides installation, configuration, troubleshooting, and other procedures for the
use of the Rosemount 8600D Vortex Flowmeter. Specifications and other important
information are also included.
Section 2: Installation
Contains mechanical and electrical installation instructions.
Section 1: Introduction
January 2013
Section 3: Configuration
Contains information on entering and verifying basic configuration parameters.
Section 4: Operation
Contains information on advanced configuration parameters and functions that can aid in
maintaining the 8600D.
Section 5: Troubleshooting
Provides troubleshooting techniques, diagnostic information, and transmitter verification
procedures.
Appendix A: Reference data
Provides reference and specification data.
Appendix B: Approval Information
Provides specific information for approval codes.
Appendix C: Electronics verification
Introduction
Provides a short procedure for verification of electronic output to assist in meeting the quality
standards for ISO 9000 certified manufacturing processes.
Figure 1-1: Rosemount 8600D HART™ Menu Tree
Provides command tree, and Fast Key Sequence tables for the Field Communicator when used in
conjunction with the Rosemount 8600D.
1
Section 1: Introduction
January 2013
1.2Safety messages
Procedures and instructions in this manual may require special precautions to ensure the safety
of the personnel performing the operations. Refer to the safety messages, listed at the
beginning of each section, before performing any operations.
1.3System description
The Rosemount 8600D Vortex Flowmeter consists of a meter body and transmitter and
measures volumetric flow rate by detecting the vortices created by a fluid passing by the
shedder bar.
The meter body is installed in-line with process piping. A sensor is located at the end of the
shedder bar and creates an alternating sine wave due to the passing vortices. The transmitter
measures the frequency of the sine waves and converts it into a flowrate.
This manual is designed to assist in the installation and operation of the Rosemount 8600D
Vor tex Flowmeter.
Reference Manual
00809-0100-4860, Rev BC
This product is intended to be used as a flowmeter for liquid, gas, or
steam applications. Any use other than for which it was intended may
result in serious injury or death.
This section provides installation instructions for the Rosemount 8600D Vortex Flowmeter.
Dimensional drawings for each Rosemount 8600D variation and mounting configuration are
included in the Appendix on page 107.
The options available for the Rosemount 8600D flowmeter are also described in this section.
The numbers in parentheses refer to the codes used to order each option.
Section 2: Installation
January 2013
2.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the safety
of the personnel performing the operations. Please refer to the following safety messages
before performing any operation in this section.
Explosions could result in death or serious injury:
Do not remove the transmitter cover in explosive atmospheres when the circuit is
alive.
Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Both transmitter covers must be fully engaged to meet explosion-proof requirements.
Failure to follow these installation guidelines could result in death or serious injury:
Make sure only qualified personnel perform the installation.
Installation
3
Section 2: Installation
Is
Configuration
OK?
Mount
Flowmeter
Wire
Flowmeter
Power
Flowmeter
DONE
Mount
Conduit
START HERE
FIELD
INSTALL
CONFIGURE
Tag
Process Config
• Transmitter Mode
•Process Fluid
•Fixed Process Temp.
•Dens/Dens Ratio
-Density Ratio
(Std. or Normal
Volumetric Flow Units
Only)
-Fixed Process Density
(Mass Flow Units Only)
No
Bench
Commissioning?
Review
Configuration
Yes
No
Yes
Did you
Configure on
Bench?
No
Yes
Configure if
Necessary
Go to
Review
Configuration
A
A
A
Go to
B
Go to
B
Reference
K-Factor
Mating Pipe ID
Variable Mapping
Flange Type
PV Unit
Range Values
PV Damping
Auto Adjust Filter
Using
LCD?
Yes
Configure
Local
Display
Using Pulse
Output
No
Using
Tot al iz er
Meter
Installed
Configure
Pulse
Output
Yes
No
Configure
Totalizer
Yes
No
Yes
No
DONE
January 2013
Figure 2-1. Installation Flowchart
Reference Manual
00809-0100-4860, Rev BC
4
Installation
Reference Manual
00809-0100-4860, Rev BC
2.2Commissioning
Commission the Rosemount 8600D before putting it into operation. This ensures proper
configuration and operation of the meter. It also enables you to check hardware settings, test
the flowmeter electronics, verify flowmeter configuration data, and check output variables. Any
problems can be corrected – or configuration settings changed – before going out into the
installation environment. To commission on the bench, connect the Field Communicator or
Asset Management Solutions
loop in accordance with the specifications for your communicator.
2.2.1General considerations
Before you install a flowmeter in any application, you must consider flowmeter sizing (the line
size) and location. Choose the correct flowmeter size for an application to increase rangeability
and minimize pressure drop and cavitation. Proper location of the flowmeter can ensure a clean
and accurate signal. Follow the installation instructions carefully to reduce start-up delays, ease
maintenance, and ensure optimum performance.
2.2.2Flowmeter sizing
™
(AMS) software (or other communications device) to the signal
Section 2: Installation
January 2013
Correct meter sizing is important for flowmeter performance. The Rosemount 8600D is capable
of processing signals from flow applications within the limitations described in Appendix A:
Reference data. Full scale is continuously adjustable within these ranges.
To determine the correct flowmeter size for an application, process conditions must be within
the stated requirements for Reynolds number and velocity. See Appendix A: Reference data for
sizing data.
Contact your local Rosemount Inc. sales representative to obtain a copy of Instrument Toolkit
which contains a sizing module for the Rosemount 8600D Vortex flowmeter. The vortex sizing
module will calculate valid flowmeter sizes based on user-supplied application information.
2.2.3Flowmeter orientation
Design process piping so the meter body will remain full, with no entrapped air. Allow enough
straight pipe both upstream and downstream of the meter body to ensure a nonskewed,
symmetrical profile. Install valves downstream of the meter when possible.
Vertical installation
Vertical installation allows upward process liquid flow and is generally preferred. Upward flow
ensures that the meter body always remains full and that any solids in the fluid are evenly
distributed.
®
Installation
The vortex meter can be mounted in the vertical down position when measuring gas or steam
flows. This type of application should be strongly discouraged for liquid flows, although it can
be done with proper piping design.
Note
To ensure that the meter body remains full, avoid downward vertical
liquid flows where back pressure is inadequate.
5
Section 2: Installation
The meter body installed with the
electronics to the side of the pipe.
(PREFERRED ORIENTATION)
The meter body installed with the
electronics below the pipe.
(ACCEPTABLE ORIENTATION)
January 2013
Horizontal installation
For horizontal installation, the preferred orientation is to have the electronics installed to the
side of the pipe. In liquid applications, this ensures any entrapped air or solids do not strike the
shedding bar and disrupt the shedding frequency. In gas or steam applications, this ensures that
any entrained liquid (such as condensate) or solids do not strike the shedder bar and disrupt the
shedding frequency.
High-Temperature installations
Install the meter body so the electronics are positioned to the side of the pipe or below the pipe
as shown in Figure 2-2. Insulation may be required around the pipe to maintain an electronics
temperature below 185 °F (85 °C).
Figure 2-2. Examples of High-Temperature Installations
Reference Manual
00809-0100-4860, Rev BC
6
Steam installations
For steam applications, avoid installations such as the one shown in Figure 2-3. Such
installations may cause a water-hammer condition at start-up due to trapped condensate. The
high force from the water hammer can over stress the sensing mechanism and cause permanent
damage to the sensor.
Figure 2-3. Avoid This Type of Installation for Steam Applications
Installation
Reference Manual
NOTE: The MTA option can be purchased for an integral
temperature measurement and mass flow temperature
compensation for saturated steam only.
4 Downstream
6 Downstream
TP
00809-0100-4860, Rev BC
Section 2: Installation
January 2013
Upstream/Downstream piping
The vortex meter may be installed with a minimum of ten diameters (D) of straight pipe length
upstream and five diameters (D) of straight pipe length downstream.
Rated accuracy is based on the number of pipe diameter from an upstream disturbance. No
K-factor correction is required if the meter is installed with 35 D upstream and 5 D downstream.
The value of the K-factor may shift up to 0.5% when the upstream straight pipe length is
between 10D and 35D. Please see Technical Data Sheet (00816-0100-3250) on Installation
Effects for optional K-factor corrections. This effect can be corrected for using the Installation
Effect Correction Factor (See page 52).
Pressure and temperature transmitter location
When using pressure and temperature transmitters in conjunction with the Rosemount 8600D
for compensated mass flows, install the transmitter(s) downstream of the Vortex Flowmeter.
See Figure 2-4.
Figure 2-4. Pressure and Temperature Transmitter Location
2.2.4Wetted material selection
2.2.5Environmental considerations
Installation
Ensure that the process fluid is compatible with the meter body wetted materials when
specifying the Rosemount 8600D. Corrosion will shorten the life of the meter body. Consult
recognized sources of corrosion data or contact your Rosemount Sales Representative for more
information.
Note
For accurate results perform a Positive Material Identification (PMI) test on a machined surface.
Avoid excessive heat and vibration to ensure maximum flowmeter life. Typical problem areas
include high-vibration lines with integrally mounted electronics, warm-climate installations in
direct sunlight, and outdoor installations in cold climates.
7
Section 2: Installation
January 2013
Although the signal conditioning functions reduce susceptibility to extraneous noise, some
environments are more suitable than others. Avoid placing the flowmeter or its wiring close to
devices that produce high intensity electromagnetic and electrostatic fields. Such devices include
electric welding equipment, large electric motors and transformers, and communication
transmitters.
2.3Hazardous locations
The Rosemount 8600D has an explosion-proof housing and circuitry suitable for intrinsically
safe and non-incendive operation. Individual transmitters are clearly marked with a tag
indicating the certifications they carry.
2.4Hardware configuration
The hardware jumpers on the Rosemount 8600D enable you to set the alarm and security. (See
Figure 2-5.) To access the jumpers, remove the electronics housing cover from the electronics
end of the Rosemount 8600D. If your Rosemount 8600D includes an LCD option, the alarm and
security jumpers are found on the face of the LCD indicator. (See Figure 2-6 on page 10.)
Reference Manual
00809-0100-4860, Rev BC
Note
If you will be changing configuration variables frequently, it may be
useful to leave the security lockout jumper in the OFF position to
avoid exposing the flowmeter electronics to the plant environment.
Set these jumpers during the commissioning stage to avoid exposing the electronics to the
plant environment.
Figure 2-5. Alarm and Security Jumpers
8
Installation
Reference Manual
00809-0100-4860, Rev BC
Alarm
As part of normal operations, the Rosemount 8600D continuously runs a self-diagnostic
routine. If the routine detects an internal failure in the electronics, flowmeter output is driven to
a low or high alarm level, depending on the position of the failure mode jumper.
The failure mode jumper is labeled ALARM and is set at the factory per the CDS (Configuration
Data Sheet); the default setting is HI.
Security
You can protect the configuration data with the security lockout jumper. With the security
lockout jumper ON, any configuration changes attempted on the electronics are disallowed.
You can still access and review any of the operating parameters and scroll through the available
changes, but no actual changes will be permitted. The security lockout jumper is labeled
SECURITY and is set at the factory per the CDS; the default setting is OFF.
2.4.1Failure mode vs. saturation output values
Section 2: Installation
January 2013
The failure mode alarm output levels differ from the output values that occur when the
operating flow is outside the range points. When the operating flow is outside the range points,
the analog output continues to track the operating flow until reaching the saturation value
listed below; the output does not exceed the listed saturation value regardless of the operating
flow. For example, with standard alarm and saturation levels and flows outside the 4—20 mA
range points, the output saturates at 3.9 mA or 20.8 mA. When the transmitter diagnostics
detect a failure, the analog output is set to a specific alarm value that differs from the saturation
value to allow for proper troubleshooting.
.
Table 2-1. Analog Output: Standard Alarm Values vs. Saturation Values
Level4—20 mA Saturation Value4—20 mA Alarm Value
Low 3.9 mA< 3.75 mA
High20.8 mA 21.75 mA
.
Table 2-2. Analog Output: NAMUR-Compliant Alarm Values vs. Saturation Values
Level4—20 mA Saturation Value4—20 mA Alarm Value
Low 3.8 mA< 3.6 mA
High20.5 mA 22.6 mA
Installation
9
Section 2: Installation
ALARM
LO
HI
OFF
ON
SECURITY
January 2013
2.4.2LCD indicator option
If your electronics are equipped with the LCD indicator (Option M5), the ALARM and SECURITY
jumpers are located on the face of the indicator as shown in Figure 2-6.
Figure 2-6. LCD Indicator Alarm and Security Jumpers
Reference Manual
00809-0100-4860, Rev BC
10
Installation
Reference Manual
00809-0100-4860, Rev BC
2.5Meter body installation tasks
The installation tasks include detailed mechanical and electrical
installation procedures.
2.5.1Handling
Handle all parts carefully to prevent damage. Whenever possible, transport the system to the
installation site in the original shipping containers. Keep the shipping plugs in the conduit
connections until you are ready to connect and seal them.
Note
Do not lift the flowmeter by the transmitter. Lift the meter by the meter body. Lifting supports
can be tied around the meter body as illustrated below if necessary.
Section 2: Installation
January 2013
2.5.2Flow direction
Mount the meter body so the FORWARD end of the flow arrow, shown on the meter body,
points in the direction of the flow in the pipe.
2.5.3Gaskets
The Rosemount 8600D requires flange gaskets supplied by the user, and sensor gaskets
supplied with the meter. Be sure to select gasket material that is compatible with the process
fluid and pressure ratings of the specific installation.
Note
Ensure that the inside diameter of the flange gasket is larger than the inside
diameter of the flowmeter and adjacent piping. If gasket material extends into the flow stream,
it will disturb the flow and cause inaccurate measurements.
Installation
11
Section 2: Installation
Gaskets
(Supplied by Customer)
Flow
Installation Bolts and Nuts
(Supplied by Customer)
January 2013
2.5.4Flange bolts
Install the Rosemount 8600D Flowmeter between two conventional pipe flanges, as shown in
Figure 2-7 on page 12.
Figure 2-7. Flanged-Style Flowmeter Installation
Reference Manual
00809-0100-4860, Rev BC
12
Installation
Reference Manual
1
3
4
2
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
10
11
12
00809-0100-4860, Rev BC
2.5.5Flanged-style flowmeter mounting
Physical mounting of a flanged-style flowmeter is similar to installing a typical section of pipe.
Conventional tools, equipment, and accessories (such as bolts and gaskets) are required.
Tighten the nuts following the sequence shown in Figure 2-8.
Note
The required bolt load for sealing the gasket joint is affected by several factors, including operating
pressure and gasket material, width, and condition. A number of factors also affect the actual bolt
load resulting from a measured torque, including condition of bolt threads, friction between the nut
head and the flange, and parallelism of the flanges. Due to these application-dependent factors, the
required torque for each application may be different. Follow the guidelines outlined in the ASME
Pressure Vessel Code (Section VIII, Division 2) for proper bolt tightening. Make sure the flowmeter is
centered between flanges of the same nominal size as the flowmeter.
Figure 2-8. Flange Bolt Torquing Sequence
Section 2: Installation
January 2013
2.5.6Flowmeter grounding
Grounding is not required in typical vortex applications; however, a proper ground will eliminate
possible noise pickup by the electronics. Grounding straps may be used to ensure that the
meter is grounded to the process piping. If you are using the transient protection option (T1),
grounding straps are required to provide a proper low impedance ground.
Note
Properly ground flow meter body and transmitter per the local code.
Installation
To use grounding straps, secure one end of the grounding strap to the bolt extending from the
side of the meter body and attach the other end of each grounding strap to a suitable ground.
13
Section 2: Installation
January 2013
2.6Electronics considerations
Both integral and remote mounted electronics require input power at the electronics. For
remote mount installations, mount the electronics
against a flat surface or on a pipe that is up to two inches (50 mm) in diameter.
Remote mounting hardware includes an L bracket that is stainless steel and one stainless steel
u-bolt. See Appendix A: Reference data, “Dimensional drawings” on page 107 for dimensional
information.
2.6.1High-Temperature installations
Install the meter body so the electronics are positioned to the side of or
below the pipe as shown in Figure 2-2 on page 6. Insulation may be required around the pipe to
maintain an ambient transmitter temperature below 185 °F (85 °C) or the more restrictive
temperature ratings marked on hazardous locations tags.
2.6.2Conduit connections
Reference Manual
00809-0100-4860, Rev BC
The electronics housing has two ports for 1/2–14 NPT or M201.5 conduit connections. Unless
marked otherwise conduit entries in the housing are
conventional manner in accordance with local or plant electrical codes. Be sure to properly seal
unused ports to prevent moisture or other contamination from entering the terminal block
compartment of the electronics housing. Additional conduit entry types are available via
adapters.
Note
In some applications it may be necessary to install conduit seals and arrange for conduits to
drain to prevent moisture from entering the wiring compartment.
2.6.3High-Point installation
Prevent condensation in any conduit from flowing into the housing by mounting the flowmeter
at a high point in the conduit run. If the flowmeter is mounted at a low point in the conduit run,
the terminal compartment could fill with fluid.
If the conduit originates above the flowmeter, route conduit below the flowmeter before entry.
In some cases a drain seal may need to be installed.
1
/2 NPT. These connections are made in a
14
Installation
Reference Manual
Conduit Line
Conduit Line
00809-0100-4860, Rev BC
Section 2: Installation
January 2013
Figure 2-9. Proper Conduit Installation with Rosemount 8600D
2.6.4Cable gland
If you are using cable glands instead of conduit, follow the cable gland manufacturer’s instructions
for preparation and make the connections in a conventional manner in accordance with local or plant
electrical codes. Be sure to properly seal unused ports to prevent moisture or other contamination
from entering the terminal block compartment of the electronics housing.
2.6.5Grounding the transmitter case
The transmitter case should always be grounded in accordance with national and local electrical
codes. The most effective transmitter case grounding method is direct connection to earth
ground with minimal impedance. Methods for grounding the transmitter case include:
Internal Ground Connection: The Internal Ground Connection screw is inside the
FIELD TERMINALS side of the electronics housing. This screw is identified by a ground
symbol (), and is standard on all Rosemount 8600D transmitters.
External Ground Assembly: This assembly is included with the optional transient
protection terminal block (Option Code T1). The External Ground Assembly can also be
ordered with the transmitter (Option Code V5) and is automatically included with
certain hazardous area approvals.
Note
Grounding the transmitter case using the threaded conduit connection may not provide a
sufficient ground. The transient protection terminal block (Option Code T1) does not provide
transient protection unless the transmitter case is properly grounded. See “Transient Terminal
Block” on page 27 for transient terminal block grounding. Use the above guidelines to ground
the transmitter case. Do not run the transient protection ground wire with signal wiring as the
ground wire may carry excessive current if a lightning strike occurs.
Installation
15
Section 2: Installation
8600
V
ps
R
loop
V
terminals
January 2013
2.6.6Wiring procedure
The signal terminals are located in a compartment of the electronics housing separate from the
flowmeter electronics. Connections for a HART-based communicator and a current test
connection are above the signal terminals. Figure 2-10 illustrates the power supply load
limitations for the flowmeter.
Note
A power disconnect is required to remove power from the transmitter for maintenance,
removal, and replacement.
Power supply
Power Supply Specifications:
Typical installations use a 22 Vdc – 28 Vdc power supply. The dc power supply should provide
clean power with less than 2% ripple. Refer to Figure 2-10 as a quick reference.
Loop resistance specification:
Reference Manual
00809-0100-4860, Rev BC
If HART communication is required, a minimum resistance of 250 dc is required between the
power supply and the transmitter. *Note: See the loop load calculation section to determine the
maximum allowable loop resistance as a function of power supply voltage.
Typical single loop wiring diagram:
*Loop Load Calculation: R
loop(max)
= (Vps – 10.8) / 0.024
Where:
R
R
V
10.8 = minimum terminal voltage “V
0.024 = maximum transmitter current in Adc
loop(min)
loop(max)
ps
= 250 . Required for HART communication.
= The maximum value the loop load resistor can be.
= Power Supply Voltage
terminals
” in Vdc.
16
Installation
Reference Manual
00809-0100-4860, Rev BC
Section 2: Installation
January 2013
Figure 2-10. Power Supply Load Limitations
Note
R
loop(max)
in the equation above refers to the total loop load resistance. Technically, the total
loop load resistance is the sum of the loop load resistor, signal wiring resistance, and if
applicable, any intrinsic safety barriers. In a typical installation, the loop load resistor will largely
determine the total loop resistance. In some installations, depending on signal wire gauge and
signal wire length, and/or any IS barriers, the additional resistance may need to be accounted
for.
To minimize noise pickup on the 4-20 mA signal and any digital communications signal:
Twisted pair wiring is recommended.
Shielded signal wire is preferred.
For high EMI/RFI environments, shielded signal wire is required.
To ensure proper operation, wiring should be:
24 AWG or larger.
Less than 5000 ft. (1500 m) in length.
Ohms per 1,000 ft (305 m) at 68 °F (20 °C)
Gage Number A.W.G.
142.525
164.016
186.385
2010.15
2216.14
2425.67
Equivalent
Installation
17
Section 2: Installation
January 2013
Note
If a Smart Wireless THUM™ Adapter is being used with the Rosemount 8600 flowmeter to
exchange information via the WirelessHART protocol, an additional 2.5 Vdc is dropped in the
connected loop. This is because the THUM is wired in series with the transmitter. Please use the
following formula to calculate the maximum loop load resistor.
Reference Manual
00809-0100-4860, Rev BC
Loop Load Calculation: R
loop(max)
= (Vps – 10.8 – 2.5) / 0.024
Where:
R
V
10.8 = minimum terminal voltage “V
2.5 = Maximum voltage drop across the THUM wireless adapter.
0.024 = maximum transmitter current in Adc.
loop(max)
ps
= The maximum value the loop load resistor can be.
= Power Supply Voltage.
terminals
” in Vdc.
Analog output
The flowmeter provides a 4–20 mA dc isolated current output, linear
with the flow rate.
To make connections, remove the FIELD TERMINALS side cover of the electronics housing. All
power to the electronics is supplied over the 4–20 mA signal wiring. Connect the wires as shown
in Figure 2-13 on page 21.
18
Installation
Reference Manual
50% Duty Cycle
00809-0100-4860, Rev BC
Section 2: Installation
Pulse output
Note
Remember when using the pulse output, all power to the electronics
is still supplied over the 4–20 mA signal wiring.
The flowmeter provides an isolated transistor switch-closure frequency output signal
proportional to flow, as shown in Figure 2-11. The
frequency limits are as follows:
Maximum Frequency = 10000 Hz
Minimum Frequency = 0.0000035 Hz (1 pulse/79 hours)
Duty Cycle = 50%
External Supply Voltage (V
Load Resistance (R
Max Switching Current = 75 mA >= V
Switch Closure: Transistor, open collector
Open contact < 50
Close contact < 20
): 100 to 100 k
L
A leakage
): 5 to 30 Vdc
s
S/RL
January 2013
The output may drive an externally powered electromechanical or electronic totalizer, or may
serve as a direct input to a control element.
To connect the wires, remove the FIELD TERMINALS side cover
of the electronics housing. Connect the wires as shown in Figure 2-14 on page 21.
Figure 2-11. Example: The pulse output will maintain a 50 percent duty cycle for all
frequencies.
Installation
19
Section 2: Installation
Housing
Ground
Screw
Captive
Screws
Transient Terminal
Block Ground Tab
January 2013
Note
When using pulse output, be sure to follow these precautions:
Shielded twisted pair is required when the pulse output and 4–20 mA output are run in
Do not connect the powered signal wiring to the test terminals. Power could damage
Do not run signal wiring in conduit or open trays with power wiring or near heavy
If the flowmeter is protected by the optional transient protector, you must provide a
Figure 2-12. The Transient Terminal Block
Reference Manual
00809-0100-4860, Rev BC
the same conduit or cable trays. Shielded wire will also reduce false triggering caused
by noise pickup. Wiring should be 24 AWG or larger and not exceed 5,000 ft. (1500 m).
the test diode in the test connection.
electrical equipment. If needed, ground signal wiring at any one point on the signal
loop, such as the negative terminal of the power supply. The electronics housing is
grounded to the meter body.
high-current ground connection from the electronics housing to earth ground. Also,
tighten the ground screw in the bottom center of the terminal block to provide a good
ground connection.
20
Plug and seal all unused conduit connections on the electronics housing to avoid
moisture accumulation in the terminal side
of the housing.
If the connections are not sealed, mount the flowmeter with the conduit entry
positioned downward for drainage. Install wiring with a drip loop, making sure the
bottom of the drip loop is lower than the conduit connections or the electronics
housing.
Installation
Reference Manual
+
-
R
L
250
Tes t Am mete r
RL 250
+
Tes t
Ammeter
+
–
-
Pulse
Counter
00809-0100-4860, Rev BC
Figure 2-13. 4-20 mA Wiring
Section 2: Installation
January 2013
Figure 2-14. 4–20 mA and Pulse Wiring with Electronic Totalizer/ Counter
2.6.7Remote electronics
If you order one of the remote electronics options (options R10, R20, R30, R33, R50, or RXX),
the flowmeter assembly will be shipped in two parts:
Installation
1.The meter body with an adapter installed in the bracket and an interconnecting coaxial
cable attached to it.
2.The electronics housing installed on a mounting bracket.
21
Section 2: Installation
NOTE
Consult factory for SST installation
Ground
Connection
Housing Adapter
Housing Adapter Screws
Electronics Housing
Coaxial
Cable Nut
Housing
Base Screw
1
/2 NPT Conduit Adapter or Cable Gland
(Supplied by Customer)
Coaxial Cable
Meter Adapter
Union
Wash er
Sensor Cable Nut
Meter Body
Nut
Bracket
½ NPT Conduit Adapter or Cable
Gland (Supplied by Customer)
January 2013
Mounting
Mount the meter body in the process flow line as described earlier in this section. Mount the
bracket and electronics housing in the desired location. The housing can be repositioned on the
bracket to facilitate field wiring and conduit routing.
Cable connections
Refer to Figure 2-15 and the following instructions to connect the loose end of the coaxial cable
to the electronics housing. (See “Remote electronics procedure” on page 83 if connecting/dis-
connecting the meter adapter to the meter body.)
Figure 2-15. Remote Electronics Installation
Reference Manual
00809-0100-4860, Rev BC
22
Installation
Reference Manual
00809-0100-4860, Rev BC
Section 2: Installation
January 2013
1.If you plan to run the coaxial cable in conduit, carefully cut the conduit to the desired
length to provide for proper assembly
at the housing. A junction box may be placed in the conduit run to provide a space for
extra coaxial cable length.
2.Slide the conduit adapter or cable gland over the loose end of the coaxial cable and
fasten it to the adapter on the meter body bracket.
3.If using conduit, route the coaxial cable through the conduit.
4.Place a conduit adapter or cable gland over the end of the
coaxial cable.
5.Remove the housing adapter from the electronics housing.
6.Slide the housing adapter over the coaxial cable.
7.Remove one of the four housing base screws.
8.Attach the coaxial cable ground wire to the housing via the housing base ground screw.
9.Attach and securely tighten the coaxial cable nut to the connection on the electronics
housing.
10.Align the housing adapter with the housing and attach
with two screws.
11.Tighten the conduit adapter or cable gland to the
housing adapter.
Caution
To prevent moisture from entering the coaxial cable connections, install the interconnecting
coaxial cable in a single dedicated conduit run or use sealed cable glands at both ends of the
cable.
2.6.8Calibration
Rosemount 8600D Flowmeters are wet-calibrated at the factory and need no further calibration
during installation. The calibration factor (K-factor) is indicated on each meter body and is
entered into the electronics. Verification can be accomplished with a Field Communicator
or AMS.
2.7Software configuration
Installation
To complete the installation of the Rosemount 8600D Vortex Flowmeter, configure the
software to meet the requirements of your application. If the flowmeter was pre-configured at
the factory, it may be ready to install. If not, refer to Section 3: Configuration.
LCD indicator
The LCD indicator (option M5) provides local indication of the output and abbreviated
diagnostic messages governing operation of the flowmeter. The indicator is located on the
electronics side of the flowmeter electronics. An extended cover is required to accommodate
23
Section 2: Installation
Electronics Board
January 2013
the indicator. Figure 2-16 shows the flowmeter fitted with the LCD indicator and extended
cover.
Figure 2-16. Rosemount 8600D with Optional Indicator
Reference Manual
00809-0100-4860, Rev BC
The indicator features an eight-character (and five alphanumeric) liquid crystal display that
gives a direct reading of the digital signal from the microprocessor. During normal operation,
the display can be configured to alternate between the following readings:
1.Primary variable in engineering units
2.Percent of range
3.Totalized flow
4.4–20 mA electrical current output
5.Shedding Frequency
6.Electronics Temperature
7.Pulse Output Frequency
8.Process Temperature
(MTA Option Only)
9.Mass Flow
10.Volume Flow
11.Velocity Flow
24
12.Calculated Process Density
(MTA Option Only)
Installation
Reference Manual
00809-0100-4860, Rev BC
Section 2: Installation
January 2013
Figure 2-17 shows the indicator display with all segments lit.
Figure 2-17. Optional Liquid Crystal Display
A HART-based communicator can be used to change the engineering units of the parameters
displayed on the indicator. (SeeSection 4: Operation for more information).
2.7.1Installing the indicator
For flowmeters ordered with the LCD indicator, the indicator is shipped installed. When
purchased separately from the Rosemount 8600D, you must install the indicator using a small
instrument screwdriver and the indicator kit (part number 8600-5640). The indicator kit
includes:
One LCD indicator assembly
One extended cover with o-ring installed
One connector
Two mounting screws
Two jum per s
Referring to Figure 2-16, use the following steps to install the
LCD indicator:
1.If the flowmeter is installed in a loop, secure the loop and disconnect the power.
2.Remove the flowmeter cover on the electronics side.
Installation
25
Section 2: Installation
January 2013
Note
The circuit board is electrostatically sensitive. Be sure to observe handling precautions for
static-sensitive components.
3.Insert the mounting screws into the LCD indicator.
4.Remove the two jumpers on the circuit board that coincide with the Alarm and the
5.Insert the connector into the Alarm / Security junction.
6.Gently slide the LCD indicator onto the connector and tighten
7.Insert jumpers into ALARM and SECURITY positions on the face of the LCD indicator.
8.Attach the extended cover and tighten at least one-third turn past o-ring contact.
Note
The indicator may be installed in 90-degree increments for easy viewing. Mounting screws may
need to be installed in the alternative holes based on LCD orientation. One of the four
connectors on the back of the indicator assembly must be positioned to fit into the ten-pin
connector on the electronic board stack.
Reference Manual
00809-0100-4860, Rev BC
Security settings.
the screws into place.
Note the following LCD temperature limits:
Operating:–4 to 185 °F(–20 to 85 °C)
Storage:–50 to 185 °F (–46 to 85 °C)
2.8Transient protection
The optional transient terminal block prevents damage to the flowmeter from transients
induced by lightning, welding, heavy electrical equipment, or switch gears. The transient
protection electronics are located in the terminal block.
The transient terminal block meets the following specifications:
IEEE C62.41 - 2002 Category B.
3 kA crest (8 X 20
6 kV crest (1.2 X 50
6 kV/0.5 kA (0.5
Note
The ground screw inside the terminal housing must be tightened for the proper operation of the
transient protection. Also, a high-current ground connection to earth is required.
s)
s)
s, 100 kHz, ring wave)
26
Installation
Reference Manual
Transient Terminal
Block Ground Tab
Captive Screws
Housing Ground
Screw
00809-0100-4860, Rev BC
2.8.1Installing the Transient Protector
For flowmeters ordered with the transient protector option (T1), the protector is shipped
installed. When purchased separately from the Rosemount 8600D, you must install the
protector on a Rosemount 8600D flowmeter using a small instrument screwdriver, a pliers, and
the transient protection kit.
The transient protection kit includes the following:
One transient protection terminal block assembly
Three captive screws
Use the following steps to install the transient protector:
1.If the flowmeter is installed in a loop, secure the loop and disconnect power.
2.Remove the field terminal side flowmeter cover.
3.Remove the captive screws.
4.Remove the housing ground screw.
Section 2: Installation
January 2013
5.Use pliers to pull the terminal block out of the housing.
6.Inspect the connector pins for straightness.
7.Place the new terminal block in position and carefully press it into place. The terminal
block may have to be moved back and forth to get the connector pins started into the
sockets.
Review the flowmeter configuration parameters set at the factory to ensure accuracy and
compatibility with your particular application of the flowmeter. Once you have activated the
Review function, scroll through the data list to check each variable in the configuration data list.
The last step of start-up and commissioning is to check the flowmeter output to ensure that the
flowmeter is operating properly. Rosemount 8600D digital process variables include: primary
variable, primary variable as a percent of range, analog output, vortex shedding rate, pulse
frequency, mass flow, volumetric flow, velocity flow, totalizer, electronics temperature,
calculated process density, cold junction temperature, and process temperature.
Section 3: Configuration
January 2013
3.2Process variables
Field Comm.1, 1
The process variables for the Rosemount 8600D provide the flowmeter output. When
commissioning a flowmeter, review each process variable, its function and output, and take
corrective action if necessary before using the flowmeter in a process application.
3.2.1Primary Variable (PV)
Field Comm.1, 1, 1
PV – The measured value of the variable mapped to the primary variable. This can be either
Process Temperature (MTA option only) or Flow. Flow variables are available as mass, volume, or
velocity. When bench commissioning, the flow values for each variable should be zero and the
temperature value should be the ambient temperature.
If the units for the flow or temperature variables are not correct, refer to “View other variables”
on page 30. Use the Process Variable Units function to select the units for your application.
Configuration
29
Section 3: Configuration
January 2013
3.2.2PV% of range
Field Comm.1, 1, 2
Percent of Range — The primary variable as a percentage of range provides a gauge as to where
the current measurement of the meter is within the configured range of the meter. For example,
the range may be defined as 0 gal/min to 20 gal/min. If the current flow is 10 gal/min, the
percent of range is 50 percent.
3.2.3Analog output
Field Comm.1, 1, 3
Analog Output — The analog output variable provides the analog value for the primary variable.
The analog output refers to the industry standard output in the 4–20 mA range. Check the
analog output value against the actual loop reading given by a multi-meter. If it does not match,
a 4–20 mA trim is required. See D/A Trim (Digital-to-Analog Trim).
3.2.4View other variables
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 1, 4
View Other Variables — Allows for the viewing and configuration of other variables such as flow
units, totalizer operation, and pulse output.
Volume flow
Field Comm.1, 1, 4, 1, 1
Allows the user to view the current volumetric flow value.
Volume flow units
Field Comm.1, 1, 4, 1, 2
Allows the user to select the volumetric flow units from the available list.
Volumetric UnitLCD DisplayField Communicator
U.S. Gallons per secondGAL/Sgal/s
U.S. Gallons per minuteGAL/Mgal/m
U.S. Gallons per hourGAL/Hgal/h
U.S. Gallons per dayGAL/Dgal/d
Actual Cubic Feet per secondACFSACFS
Actual Cubic Feet per minuteACFMACFM
Actual Cubic Feet per hourACFHACFH
Actual Cubic Feet per dayACFDACFD
Standard Cubic Feet per
minute
Standard Cubic Feet per hourSCFH
Barrels per secondBBL/Sbbl/s
Barrels per minuteBBL/Mbbl/min
Barrels per hourBBL/Hbbl/h
SCFM
30
Configuration
Reference Manual
00809-0100-4860, Rev BC
Barrels per dayBBL/Dbbl/d
Imperial Gallons per secondIGAL/SImpgal/s
Imperial Gallons per minuteIGAL/MImpgal/min
Imperial Gallons per hourIGAL/HImpgal/h
Imperial Gallons per dayIGAL/DImpgal/d
Liters per secondL/SL/s
Liters per minuteL/MINL/min
Liters per hourL/HL/h
Liters per dayL/DL/D
Actual Cubic Meters per
second
Actual Cubic Meters per
minute
Actual Cubic Meters per hourACMHACMH
Actual Cubic Meters per dayACMDACMD
Million Actual Cubic Meters per
day
Normal Cubic Meters per
minute
Normal Cubic Meters per hourNCMH
Normal Cubic Meters per dayNCMD
ACMSACMS
ACMMACMM
MACMDMACMD
NCMM
Section 3: Configuration
January 2013
Standard/Normal flow units
StdCuft/min
SCFH
NCMM
NmlCum/h
NCMD
Note
When configuring Standard or Normal Flow units to the volumetric flow, a density ratio must be
provided. See the Density/Density Ratio on page 39.
Special units
Field Comm.1, 1, 4, 1, 3
Special Units allows you to create flow rate units that are not among the standard options. They
can be volumetric only. Configuration of a special unit involves entry of these values: base
volume unit, base time unit, user defined unit and conversion number. Suppose you want the
Configuration
31
Section 3: Configuration
January 2013
Rosemount 8600D to display flow in barrels per minute instead of gallons per minute, and one
barrel is equal to 31.0 gallons.
Base volume unit: gal
Base time unit: min
User defined unit: br
Conversion number:
See the specific variables listed below for more information on setting special units.
Base volume unit
Field Comm.1, 1, 4, 1, 3, 1
Base Volume Unit is the unit from which the conversion is made. You must select one of the Field
Communicator defined unit options:
Gallons (gal)
Liters (L)
Imperial gallons (Impgal)
Cubic meters (Cum)
Barrels (bbl) where 1 bbl=42 gal
1
/31.0
Reference Manual
00809-0100-4860, Rev BC
Cubic Feet (Cuft)
Base time unit
Field Comm.1, 1, 4, 1, 3, 2
Base Time Unit provides the time unit from which to calculate the special units. For example, if
your special units is a volume per minute, select minutes. Choose from the following units:
Seconds (s)
Minutes (min)
Hours (h)
Days (d)
User defined unit
Field Comm.1, 1, 4, 1, 3, 3
User Defined Unit is a format variable that provides a record of the flow units to which you are
converting. The LCD on the Rosemount 8600D will display the actual units you define. The Field
Communicator will simply display “SPCL.” There are four characters available to store the new
units designation.
Conversion number
Field Comm.1, 1, 4, 1, 3, 4
32
Conversion Number is used to relate base units to special units. For a straight conversion of
volume units from one to another, the conversion number is the number of base units in the
new unit.
Configuration
Reference Manual
00809-0100-4860, Rev BC
For example, if you are converting from gallons to barrels and there are 31 gallons in a barrel,
the conversion factor is 31. The conversion equation is as follows (where barrels is the new
volume unit):
1 gallon = 0.032258 bbl.
Mass flow
Allows the user to view the current mass flow value and units. Also allows the user to configure
the mass flow units.
Mass flow
Displays the current mass flow value and units.
Mass units
Section 3: Configuration
January 2013
Field Comm.1, 1, 4, 2
Field Comm.1, 1, 4, 2, 1
Field Comm.1, 1, 4, 2, 2
Allows the user to select the mass flow units from the available list. (1 STon = 2000 lb; 1 MetTon
= 1000 kg)
If you select a Mass Units option, you must enter process density in your configuration. See the
Density/Density Ratio section on page 39.
Velocity flow
Field Comm.1, 1, 4, 3
Allows the user to view the current velocity flow value and units. Also allows the user to
configure the velocity flow units.
Configuration
33
Section 3: Configuration
January 2013
Velocity flow
Field Comm.1, 1, 4, 3, 1
Displays the current velocity flow value and units.
Velocity units
Field Comm.1, 1, 4, 3, 2
Allows the user to select the velocity units from the available list.
ft/s
m/s
Velocity measured base
Field Comm.1, 1, 4, 3, 3
Velocity Measured Base will determine if the velocity measurement is based on the mating pipe
ID or the meter body ID.
Reference Manual
00809-0100-4860, Rev BC
Tota li ze r
Field Comm.1, 1, 4, 4
To ta li ze r — Totalizer tallies the total amount of liquid or gas that has passed through the
flowmeter since the totalizer was last reset.
It enables you to change the settings of the totalizer.
Total
Field Comm.1, 1, 4, 4, 1
To ta l — Provides the output reading of the totalizer. Its value is the amount of liquid or gas that
has passed through the flowmeter since the totalizer was last reset.
Start
Field Comm.1, 1, 4, 4, 2
Start — Starts the totalizer counting from its current value.
Stop
Field Comm.1, 1, 4, 4, 3
Stop — Interrupts the totalizer count until it is restarted again. This feature is often used during
pipe cleaning or other maintenance operations.
34
Reset
Field Comm.1, 1, 4, 4, 4
Reset — Returns the totalizer value to zero. If the totalizer was running, it will continue to run
starting at zero.
Configuration
Reference Manual
00809-0100-4860, Rev BC
Totalizer config
Totalizer Conf ig — Used to configure the flow parameter (volume, mass, velocity) that will be
totalled.
Note
The totalizer value is saved in the non-volatile memory of the electronics every three seconds.
Should power to the transmitter be interrupted, the totalizer value will start at the last saved
value when the power is re-applied.
Note
Changes that affect the density, density ratio, or compensated K-Factor will affect the totalizer
value being calculated. These changes will not cause the existing totalizer value to be
recalculated.
Pulse frequency
Section 3: Configuration
January 2013
Field Comm.1, 1, 4, 4, 5
Field Comm.1, 1, 4, 5
Allows users to view the pulse output frequency value. To configure the pulse output, refer to
the section on pulse output found on page 54.
Vortex frequency
Field Comm.1, 1, 4, 6
Allows users to view the shedding frequency directly off of the sensor.
Electronics temperature
Field Comm.1, 1, 4, 7
Allows users to view the electronics temperature value and units. Also allows the user to
configure the units for the electronics temperature.
Electronics temperature
Field Comm.1, 1, 4, 7, 1
Displays the current electronics temperature value and units.
Electronics temperature unit
Configuration
Field Comm.1, 1, 4, 7, 2
Allows the user to select the units for electronics temperature from the available list.
deg C
deg F
deg R
Kelvin
35
Section 3: Configuration
January 2013
Calculated process density
Field Comm.1, 1, 4, 8
Allows users to view the calculated process density value when the vortex is configured for
temperature compensated steam applications. Also allows the user to configure the calculated
density units.
Process density
Field Comm.1, 1, 4, 8, 1
Displays the current calculated process density value.
Density units
Field Comm.1, 1, 4, 8, 2
Allows the user to configure the units for the calculated process density from the available list.
g/Cucm (cm3)
Reference Manual
00809-0100-4860, Rev BC
g/L
kg/Cum (m3)
lb/Cuft (ft3)
lb/Cuin (in3)
Process temperature
Field Comm.1, 1, 4, 9
Allows users to view the process temperature value when the vortex transmitter has the
temperature sensor option. Also allows the user to configure the process temperature units.
Process temperature
Field Comm.1, 1, 4, 9, 1
Displays the current process temperature value.
Process temperature units
Field Comm.1, 1, 4, 9, 2
Allows the user to configure the units for the process temperature from the available list.
36
deg C
deg F
deg R
Kelvin
Configuration
Reference Manual
00809-0100-4860, Rev BC
T/C failure mode
Allows the user to configure the temperature sensor failure mode. In the event that the
thermocouple sensor fails, the vortex can go either into an alarm output mode, or continue to
operate normally using the Fixed Process Temperature value. See Fixed Process Temperature
page 38. This mode is only relevant with the MTA option.
Note
If the Primary Variable is set to Process Temperature and there is an error, the output will always
go to alarm and this setting will be ignored.
Cold Junction (CJ) temperature
Allows users to view the thermocouple cold junction temperature value when the vortex has the
temperature sensor option. Also allows the user to configure the CJ temperature units.
Section 3: Configuration
January 2013
Field Comm.1, 1, 4, 9, 3
Field Comm.1, 1, 4, Scroll to bottom of list
CJ temperature
Field Comm.1, 1, 4, -, 1
Displays the current thermocouple cold junction temperature value.
CJ temperature units
Field Comm.1, 1, 4, -, 2
Allows the user to configure the units for the thermocouple cold junction temperature from the
available list.
deg C
deg F
deg R
Kelvin
3.2.5Basic setup
Field Comm.1, 3
The Rosemount 8600D must be configured for certain basic variables in order to be operational. In
most cases, all of these variables are pre-configured at the factory. Configuration may be required if
your Rosemount 8600D is not configured or if the configuration variables need revision.
Configuration
37
Section 3: Configuration
January 2013
3.2.6Tag
Field Comm.1, 3, 1
Tag is the quickest way to identify and distinguish between flowmeters. Flowmeters can be
tagged according to the requirements of your application. The tag may be up to eight
characters long.
3.2.7Process config
Field Comm.1, 3, 2
The flowmeter can be used for liquid or gas/steam applications, but it must be configured
specifically for the application. If the flowmeter is not configured for the proper process,
readings will be inaccurate. Select the appropriate Process configuration parameters for your
application:
Transmitter mode
Field Comm.1, 3, 2, 1
Reference Manual
00809-0100-4860, Rev BC
For units with an integral temperature sensor, the temperature sensor can be activated here.
Without Temperature
Sensor
With Temperature Sensor
Process fluid
Field Comm.1, 3, 2, 2
Select the fluid type: either Liquid, Gas/Steam, Tcomp Sat Steam. Tcomp Sat Steam requires the
MTA Option and provides a temperature compensated mass flow output for saturated steam.
Fixed process temperature
Field Comm.1, 3, 2, 3
Process Temperature is needed for the electronics to compensate for thermal expansion of the
flowmeter as the process temperature differs from the reference temperature. Process
temperature is the temperature of the liquid or gas in the line during flowmeter operation.
Fixed process temperature may also be used as a back-up temperature value in the event of a
temperature sensor failure if the MTA option is installed.
Note
The Fixed Process Temperature may also be changed under Calculate Density Ratio.
When configuring a meter for mass flow units, a density value needs to be entered. When
configuring a meter for Standard and Normal Volumetric flow units a density ratio will be
required.
Density ratio
Configure the Density Ratio in one of two ways:
1.Enter Density Ratio to convert from actual flow rate to standard flow rate.
2.Enter the process and base conditions. (The Rosemount 8600D electronics will then
Note
Be careful to calculate and enter the correct conversion factor. Standard flow is calculated with
the conversion factor you enter. Any error in the factor entered will result in an error in the
standard flow measurement. If pressure and temperature changes over time, use actual
volumetric flow units. The Rosemount 8600D does not compensate for changing temperature
and pressure.
Section 3: Configuration
January 2013
Field Comm.1, 3, 2, 4
Field Comm.1, 3, 2, 4, 1
calculate the density ratio for you).
Note
Changing the base process conditions will modify the density ratio. Likewise a change to the
density ratio will lead to a change in the base process pressure (Pf).
Density ratio
Field Comm.1, 3, 2, 4, 1, 1
Density Ratio is used to convert actual volumetric flow to standard volumetric flow rates based
on the following equations:
Calculate density ratio
Field Comm.1, 3, 2, 4, 1, 2
Calculate Density Ratio will calculate the density ratio (shown above) based on user entered
process and base conditions.
Tf = absolute temperature at actual (flowing) conditions in degrees Rankine or Kelvin. (The
transmitter will convert from degrees Fahrenheit or degrees Celsius to degrees Rankine or Kelvin
respectively.)
= absolute pressure at actual (flowing) conditions psia or KPa absolute. (The transmitter will
P
f
convert from psi, bar, kg/sqcm, kpa, or mpa to psi or kpa for calculation. Note that pressure
values must be absolute.)
Z
= compressibility at actual (flowing) conditions (dimensionless)
f
Base conditions
Field Comm.1, 3, 2, 4, 1, 2, 2
Tb = absolute temperature at standard (base) conditions degrees Rankine or Kelvin. (The transmitter
will convert from degrees Fahrenheit or degrees Celsius to degrees Rankine or Kelvin respectively.)
Reference Manual
00809-0100-4860, Rev BC
P
= absolute pressure at standard (base) conditions psia or KPa absolute. (The transmitter will
b
convert from psi, bar, kg/sqcm, kpa, or mpa to psi or kpa for calculation. Note that pressure values
must be absolute.)
Z
= compressibility at standard (base) conditions (dimensionless)
b
Example
Configure the Rosemount 8600D to display flow in standard cubic feet per minute (SCFM).
(Fluid is hydrogen flowing at conditions of 170 °F and 100 psia.) Assume base conditions of 59 °F
and 14.696 psia.)
Fixed process density
Field Comm.1, 3, 2, 4, 2
Process Density is required only if you have designated mass units for your flow rate units. You
will first be prompted for density units. It is required for the conversion from volumetric units to
mass units. For example, if you have set flow units to kg/sec rather than gal/sec, a density is
required to convert the measured volumetric flow into the desired mass flow. The Fixed Process
Density must be entered even in temperature compensated Saturated Steam applications as
this value is used to determine flow sensor limits in Mass Flow Units.
40
Note
If mass units are chosen, you must enter the density of your process fluid into the software. Be
careful to enter the correct density. The mass flow rate is calculated using this user-entered
density, and any error in this number will cause error in the mass flow measurement. If fluid
density is changing over time, it is recommended that volumetric flow units be used.
Configuration
Reference Manual
00809-0100-4860, Rev BC
3.2.8Reference K-factor
Field Comm.1, 3, 3
The reference K-factor is a factory calibration number relating the flow through the meter to the
shedding frequency measured by the electronics. Every 8600 meter manufactured by Emerson
is run through a water calibration to determine this value.
3.2.9Flange type
Field Comm.1, 3, 4
Flange Type enables you to specify the type of flange on the flowmeter for later reference. This
variable is preset at the factory but can be changed if necessary.
ANSI 150
ANSI 300
PN16
PN40
Section 3: Configuration
January 2013
Spcl
3.2.10Mating pipe ID (Inside Diameter)
Field Comm.1, 3, 5
The Pipe ID (Inside Diameter) of the pipe adjacent to the flowmeter can cause entrance effects
that may alter flowmeter readings. You must specify the exact inside diameter of the pipe to
correct for these effects. Enter the appropriate value for this variable.
Pipe ID values for schedule 10, 40, and 80 piping are given in Ta b le 3 - 1 . If the piping in your
application is not one of these, you may need to contact the manufacturer for exact Pipe ID.
f
Table 3-1. Pipe IDs for Schedule 10, 40, and 80 Piping
Allows the user to select which Variables the 8600D will output.
Configuration
41
Section 3: Configuration
January 2013
Primary Variable (PV)
Field Comm.1, 3, 6, 1
Selections for this Variable are Mass Flow, Volumetric Flow, Velocity Flow, and Process
Temperature. The Primary Variable is the variable mapped to the analog output.
Secondary Variable (SV)
Field Comm.1, 3, 6, 2
Selections for this Variable include all Variables that can be mapped to PV, and also Vortex
Frequency, Pulse Output Frequency, Totalizer Value, Calculated Process Density, Electronics
Temperature, and Cold Junction (CJ) Temperature.
Tertiary Variable (TV)
Field Comm.1, 3, 6, 3
Selections for this Variable are identical to those of the Secondary Variable.
Reference Manual
00809-0100-4860, Rev BC
Quaternary Variable (4V)
Field Comm.1, 3, 6, 4
Selections for this Variable are identical to those of the Secondary Variable.
3.2.12PV units
Field Comm.1, 3, 7
Selections for this include all units available for the selection of PV. This will set the units for the
flow rate or process temperature.
3.2.13Range values
Field Comm.1, 3, 8
Range Values enables you to maximize resolution of analog output. The meter is most accurate
when operated within the expected flow ranges for your application. Setting the range to the
limits of expected readings will maximize flowmeter performance.
The range of expected readings is defined by the Lower Range Value (LRV) and Upper Range
Value (URV). Set the LRV and URV within the limits of flowmeter operation as defined by the line
size and process material for your application. Values set outside that range will not be
accepted.
42
Primary Variable Upper Range Value (PV URV)
Field Comm.1, 3, 8, 1
This is the 20 mA set point for the meter.
Configuration
Reference Manual
00809-0100-4860, Rev BC
Primary Variable Lower Range Value (PV LRV)
Field Comm.1, 3, 8, 2
This is the 4 mA set point for the meter, and is typically set to 0 when the PV is a Flow Variable.
3.2.14PV damping
Field Comm.1, 3, 9
Damping changes the response time of the flowmeter to smooth variations in output readings
caused by rapid changes in input. Damping is applied to the Analog Output, Primary Variable,
Percent of Range, and Vortex Frequency. This will not affect the Pulse Output, Total, or other
Digital Information.
The default damping value is 2.0 seconds. This can be reset to any value between 0.2 to 255
seconds when PV is a flow variable or 0.4 to 32 seconds when PV is Process Temperature.
Determine the appropriate damping setting based on the necessary response time, signal
stability, and other requirements of the loop dynamics in your system.
Section 3: Configuration
January 2013
Note
If the vortex shedding frequency is slower than the damping value selected, no damping is
applied.
3.2.15Auto adjust filter
Field Comm.1,3, Scroll to
Bottom
The Auto Adjust Filter is a function that can be used to optimize the range of the flowmeter
based on the density of the fluid. The electronics uses process density to calculate the minimum
measurable flow rate, while retaining at least a 4:1 signal to the trigger level ratio. This function
will also reset all of the filters to optimize the flowmeter performance over the new range. If the
configuration of the device has changed, this method should be executed to ensure the signal
processing parameters are set to their optimum settings. For a stronger signal select a density
value that is lower than the actual flowing density.
Configuration
43
Section 3: Configuration
1. Device
Setup
2. PV
3. AO
4. LRV
5. URV
1. Process
Variables
2. Diagnostics
and Service
3. Basic Setup
4. Detailed
Setup
5. Review
1. PV
2. PV % Range
3. Analog Output
4. View Other
Variables
1. Volumetric Flow
2. Mass Flow
3. Velocity Flow
4. Totalizer
5. Pulse Frequency
6. Vortex Frequency
7. Electronics Temp
8. Calc Proc Density
9. Process Temp
- CJ Tem
p
erature
1. Volume Flow
2. Units
3. Special Units
1. Base Volume Unit
2. Base Time Unit
3. User Defined Unit
4. Conversion Number
1. Mass Flow
2. Mass Flow Unit
1. Total
2. Start
3. Stop
4. Reset
5. Totalizer Config
1. Electr Temp
2. Elec Temp Units
1. Test/Status
2. Loop Test
3. Pulse Output Test
4. Flow Simulation
5. D/A Trim
6. Scaled D/A Trim
7. Shed Fre
q
at URV
1. View Status
2. Config Status
3. Density Test Calc
4. Min/Max Temps
5. Self Test
6. Reset Xmt
r
1. PV
2. Shedding Frequency
3. Configure Flow Simulation
4. Enable Normal Flow
5. Mode
1. Tag
2. Process Config
3. Reference K Factor
4. Flange Type
5. Mating Pipe ID
6. Variable Mapping
7. PV Unit
8. Range Values
9. PV Damping
-Auto Ad
j
ust Filte
r
1. Transmitter Mode
2. Process Fluid
3. Fixed Process Temp
4. Density / Dens Ratio
1. Density Ratio
2. Fixed Process
Density
1. Density Ratio
2. Calc Density Ratio
1. PV is
2. SV is
3. TV is
4. QV is
1. URV
2. LRV
3. PV Min Span
4. USL
5. LSL
1. Operating Conditions
2. Base Conditions
3. Exit
1.Characterize Meter
2. Configure Outputs
3. Signal Processing
4. Device Information
1. K Factor
2. Mating Pipe ID
3. Flange Type
4. Wetted Material
5. Meter Body #
6. Installation Effects
1. Reference K Factor
2. Compensated K Factor
1.Anlg Output
2. Pulse Output
3.HART Output
4. Local Display
1. Range Values
2. Loop Test
3. Alarm Jumper
4. D/A Trim
5. Alarm Level Select
6. Alarm/Sat Levels
7. Scaled D/A Trim
8. Recall Factor
y
Trim
1. Vel. Flow
2. Vel. Flow Unit
3. Velocity Meas Base
1. High Alarm
2. High Saturation
3. Low Saturation
4. Low Alarm
1. Pulse Output
2. Pulse Output Test
1. Off
2. Direct (Shedding)
3. Scaled Volume
4. Scaled Velocity
5. Scaled Mass
1. Poll Address
2. # of Req Preams
3. Num Resp Preams
4. Burst Mode
5. Burst Option
6. Burst Xmtr Vars
1.Xmtr Var, Slot 1
2.Xmtr Var, Slot 2
3.Xmtr Var, Slot 3
4.Xmtr Var, Slot 4
1. Optimize Flow Range
2. Manual Filter Adjust
3. Filter Restore
4. Damping
5. LFC Response
1. Manufacturer
2. Tag
3. Descriptor
4. Message
5. Date
6. Write Protect
8. Revision Numbers
7. Transmitter Options
1. PV
2. LFC
3. Sig/Tr
4. Auto Adjust
Filter
1. PV
2. Sig/Tr
3. Low Flow Cutoff
4. Low Pass Filter
5. Trigger Level
1. Universal Rev
2. Transmitter Rev
3. Software Rev
4. Hardware Rev
5. Final Assembly #
6. Device ID
7. Board Serial #
1. Proc
Density
2. Density
Units
1. Proc Temp
2. Proc Temp
Units
3. T/C Failure
Mode
1. URV
2. LRV
3. PV Min Span
4. USL
5. LSL
1. CJ Temp
2. CJ Temp Units
1. Min Electr Temp
2. Max Electr Temp
1. PV Damping
2. Flow Damping
3. Temperature Damping
January 2013
Figure 3-1. Field Communicator Menu Tree for the Rosemount 8600D
This section contains information for advanced configuration parameters and diagnostics.
The software configuration settings for the Rosemount 8600D can be accessed through a
HART-based communicator or through a control system. The software functions for the Field
Communicator are described in detail in this section of the manual. It provides an overview and
summary of communicator functions. For more complete instructions, see the communicator
manual.
Before operating the Rosemount 8600D in an actual installation, you should review all of the
factory set configuration data to ensure that they reflect the current application.
Section 4: Operation
January 2013
4.1Diagnostics/service
Field Comm.1, 2
Use the following functions to verify that the flowmeter is functioning properly, or when you
suspect component failure or a problem with loop performance, or when instructed to do so as
part of a troubleshooting procedure. Initiate each test with the Field Communicator or other
HART-based communications device.
4.1.1Test/status
Field Comm.1, 2, 1
Under Test/Status choose from View Status or Self Test.
View status
Field Comm.1, 2, 1, 1
Allows you to view any error messages that may have occurred.
Configuration status
Field Comm.1, 2, 1, 2
Operation
Configuration status allows you to check the validity of the transmitter configuration.
47
Section 4: Operation
January 2013
Density test calc
Allows for the test of the density calculation for saturated steam. The vortex meter will calculate
the associated steam density at a user entered temperature value. Process Fluid must be set to
Tcomp Sat Steam in order to run this test.
Min/Max electronics temperatures
Allows the user to view the minimum and maximum temperatures that the electronics have
been exposed to.
Min electronics temp
Displays the lowest temperature that the electronics have been exposed to.
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 2, 1, 3
Field Comm.1, 2, 1, 4
Field Comm.1, 2, 1, 4, 1
Max electronics temp
Field Comm.1, 2, 1, 4, 2
Displays the highest temperature that the electronics have been exposed to.
Self test
Field Comm.1, 2, 1, 5
Although the Rosemount 8600D performs continuous self-diagnostics, you can initiate an
immediate diagnostic to check for possible electronics failure.
Self Test checks proper communications with the transmitter and provides diagnostic
capabilities for transmitter problems. Follow on-screen instructions if problems are detected, or
check the appropriate appendix for error messages relating to your transmitter.
Reset transmitter
Field Comm.1, 2, 1, 6
Restarts the transmitter - same as cycling power.
4.1.2Loop test
Field Comm.1, 2, 2
48
Loop Test verifies the output of the flowmeter, the integrity of the loop, and the operation of any
recorders or similar devices. Conduct the loop test after the flowmeter is installed in the field.
If the meter is located in a loop with a control system, the loop will have to be set to manual
control before the loop test is performed.
Loop Test allows the device to be set to any output between the Low Alarm and High Alarm.
Operation
Reference Manual
00809-0100-4860, Rev BC
4.1.3Pulse output test
Field Comm.1, 2, 3
Pulse Output Test is a fixed frequency mode test that checks the integrity of the pulse loop. It
tests that all connections are good and that the pulse output is running on the loop.
4.1.4Flow simulation
Field Comm.1, 2, 4
Flow Simulation enables you to check the electronics functionality. This can be verified with
either the Flow Simulation Internal or Flow Simulation External method. PV must be Volume
Flow, Velocity Flow, or Mass Flow before Flow Simulation can be used.
PV
Field Comm.1, 2, 4, 1
Shows the flow value in current engineering units for the flow simulation.
Section 4: Operation
January 2013
Shedding frequency
Field Comm.1, 2, 4, 2
Shows the shedding frequency for the flow simulation.
Configure flow simulation
Field Comm.1, 2, 4, 3
Allows you to configure your flow simulation (internal or external).
Simulate flow internal
Field Comm.1, 2, 4, 3, 1
When licensed, the simulate flow internal function will automatically electronically disconnect
the sensor and enable you to configure the internal flow simulation (fixed or varying).
Fixed flow
Field Comm.1, 2, 4, 3, 1, 1
The fixed flow simulation signal can be entered in either a percent of range or flow rate in current
engineering units. This simulation locks the Vortex in to the specific flow rate entered.
Operation
Varying flow
Field Comm.1, 2, 4, 3, 1, 2
The minimum and maximum flowrate can be entered in either percent of range or as a flow rate
in current engineering units. The ramp time can be entered in seconds from a minimum of 0.6
seconds to a maximum of 34951 seconds. This simulation causes the Vortex meter to
continuously ramp from the minimum entered rate to the maximum entered rate and back over
the ramp time.
49
Section 4: Operation
January 2013
Simulate flow external
Simulate flow external allows you to disconnect the sensor electronically so an external
frequency source can be used to test and verify the electronics.
Enable normal flow
Enable normal flow allows you to exit the flow simulation mode (internal or external) and return
to normal operation mode. Enabled Normal Flow must be activated after any simulation is run.
Failure to enable normal flow will leave the Vortex in simulation mode.
Mode
Mode allows you to view which flow simulation mode you are in:
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 2, 4, 3, 2
Field Comm.1, 2, 4, 4
Field Comm.1, 2, 4, 5
Internal (flow simulation – internal)
Snsr Offln (flow simulation – external)
Norm Flow (normal flow operation)
4.1.5D/A trim
Field Comm.1, 2, 5
D/A Trim (Digital-to-Analog Trim) enables you to check and trim the analog output in a single
function. If the analog output is trimmed, it will be scaled proportionally through the range of
the output.
To trim the digital-to-analog output, initiate the D/A Trim function and connect an ammeter to
the loop to measure the actual analog output of the meter. Follow the on-screen functions to
complete the task.
4.1.6Scaled D/A trim
Field Comm.1, 2, 6
Scaled D/A Trim enables you to calibrate the flowmeter analog output using a different scale
than the standard 4-20 mA output scale. Non-scaled D/A Trimming (described above), is
typically performed using an ammeter where calibration values are entered in units of
milliamperes. Both non-scaled D/A trimming and scaled D/A trimming allow you to trim the
4-20mA output to approximately ±5% of the nominal 4mA end point and ±3% of the nominal
20mA end point. Scaled D/A Trimming allows you to trim the flowmeter using a scale that may
be more convenient based upon your method of measurement.
50
For example, it may be more convenient for you to make current measurements by direct
voltage readings across the loop resistor. If your loop resistor is 500 Ohms, and you want to
calibrate the meter using voltage measurements made across this resistor, you could rescale
(select CHANGE on the 375) your trim points from 4-20 mA to 4-20 mA x 500 ohm or 2-10 Vdc.
Operation
Reference Manual
00809-0100-4860, Rev BC
Once your scaled trim points have been entered as 2 and 10, you can now calibrate your
flowmeter by entering voltage measurements directly from the voltmeter.
4.1.7Shed freq at URV
Field Comm.1, 2, 7
Shed Freq at URV function gives the shedding frequency corresponding to your URV (URV =
Upper Range Value). If the PV is Process Temperature, the Shedding Frequency at URV
represents the shedding frequency of the Volumetric Flow URV. This can be set by assigning
Volumetric Flow to PV and setting range values.
4.2Advanced functionality
The Rosemount 8600D enables you to configure the flowmeter for a wider range of applications
and special situations. These functions are grouped as follows under Detailed Set-Up:
Section 4: Operation
January 2013
4.3Detailed set-up
Field Comm.1, 4
Characterize Meter
Configure Outputs
Signal Processing
Device Information
4.3.1Characterize meter
Field Comm.1, 4, 1
The Meter Body variables provide configuration data that are unique to your Rosemount 8600D.
The settings of these variables can affect the compensated K-factor on which the primary
variable is based. This data is provided during factory configuration and should not be changed
unless the physical make-up of your Rosemount 8600D is changed.
K-factor
Field Comm.1, 4, 1, 1
The Field Communicator provides information on Reference and Compensated K-factor values.
The Reference K-factor is factory set according to the actual K-factor for your application. It
should only be changed if you replace parts of the flowmeter. Contact your Rosemount
representative for details.
Operation
The Compensated K-factor is based on the reference K-factor as compensated for the given
process temperature, wetted materials, body number, and pipe ID. Compensated K-factor is an
informational variable that is calculated by the electronics of your flowmeter.
51
Section 4: Operation
January 2013
Mating pipe I.D.
The inside diameter of the pipe adjacent to the flow meter can cause entrance effects that may
alter flowmeter readings. The exact inside diameter of the pipe must be specified to correct for
these effects. Enter the appropriate value for this variable.
Mating Pipe ID values for schedule 10, 40, 80, and 160 piping are given in Table 3-1 on page 41.
If the piping in your application is not one of these, you may need to contact the manufacturer
for exact Pipe ID.
Flange type
Flange Type enables you to specify the type of flange on the flowmeter for later reference. This
variable is preset at the factory but can be changed if necessary.
ANSI 150
ANSI 300
PN16
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 4, 1, 2
Field Comm.1, 4, 1, 3
PN40
Spcl
Wetted material
Field Comm.1, 4, 1, 4
Wetted Material is a factory set configuration variable that reflects the construction of your
flowmeter.
316 SST
Spcl
Meter body number
Field Comm.1, 4, 1, 5
Meter Body Number is a factory set configuration variable that stores the body number of your
particular flowmeter and the type of construction. The meter body number is found to the right
of the body number on the meter body tag, which is attached to the bracket of the meter body.
The format of this variable is a number followed by an alpha character. The number designates
the body number.
Installation effect
52
Field Comm.1, 4, 1, 6
Installation Effect enables you to compensate the flowmeter for installation effects caused by
less than ideal straight run piping. See reference graphs located in Technical Data Sheet
00816-0100-3250 for the percent of K-factor shift based on entrance effects of upstream
disturbances. This value is entered as a percentage of the range of -1.5% to +1.5%.
Operation
Reference Manual
00809-0100-4860, Rev BC
4.3.2Configure outputs
Field Comm.1, 4, 2
The Rosemount 8600D is digitally adjusted at the factory using precision equipment to ensure
accuracy. You should be able to install and operate the flowmeter without a D/A Trim.
Analog output
Field Comm.1, 4, 2, 1
For maximum accuracy, calibrate the analog output and, if necessary, trim for your system loop.
The D/A Trim procedure alters the conversion of the digital signal into an analog 4–20 mA
output.
Range values
Field Comm.1, 4, 2, 1, 1
Range Values enables you to maximize resolution of analog output. The meter is most accurate
when operated within the expected flow ranges for your application. Setting the range to the
limits of expected readings will maximize flowmeter performance.
Section 4: Operation
January 2013
The range of expected readings is defined by the Lower Range Value (LRV) and Upper Range
Value (URV). Set the LRV and URV within the limits of flowmeter operation as defined by the line
size and process material for your application. Values set outside that range will not be
accepted.
Loop test
Field Comm.1, 4, 2, 1, 2
Loop Test verifies the output of the flowmeter, the integrity of the loop, and the operation of any
recorders or similar devices. Conduct the loop test after the flowmeter is installed in the field. If
the meter is located in a loop with a control system, the loop will have to be set to manual
control before the loop test is performed.
Loop Test allows the device to be set to any output between the Low Alarm and High Alarm.
Alarm jumper
Field Comm.1, 4, 2, 1, 3
Alarm Jumper lets you verify the alarm jumper setting.
D/A trim (Digital-to-Analog trim)
Field Comm.1, 4, 2, 1, 4
Digital-to-Analog Trim enables you to check and trim the analog output in a single function. If
the analog output is trimmed, it will be scaled proportionally through the range of the output.
To trim the digital-to-analog output, initiate the D/A Trim function and connect an ammeter to
the loop to measure the actual analog output of the meter. Follow the on-screen functions to
complete the task.
Operation
53
Section 4: Operation
January 2013
Alarm level select
Select the Alarm level of the transmitter. Either Rosemount standard or NAMUR compliant.
Alarm / sat levels
Displays Alarm and Saturation mA output levels.
Note
Alarm and Saturation levels can be found in the specifications section.
Scaled D/A trim
Scaled D/A Trim enables you to calibrate the flowmeter analog output using a different scale
than the standard 4-20 mA output scale. Non-scaled D/A Trimming (described above), is
typically performed using an ammeter where calibration values are entered in units of
milliamperes. Both non-scaled D/A trimming and scaled D/A trimming allow you to trim the
4-20mA output to approximately ±5% of the nominal 4mA end point and ±3% of the nominal
20mA end point. Scaled D/A Trimming allows you to trim the flowmeter using a scale that may
be more convenient based upon your method of measurement.
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 4, 2, 1, 5
Field Comm.1, 4, 2, 1, 6
Field Comm.1, 4, 2, 1, 7
For example, it may be more convenient for you to make current measurements by direct
voltage readings across the loop resistor. If your loop resistor is 500 Ohms, and you want to
calibrate the meter using voltage measurements made across this resistor, you could rescale
your trim points from 4-20mA to 4-20mA x 500 ohm or 2-10 Vdc. Once your scaled trim points
have been entered as 2 and 10, you can now calibrate your flowmeter by entering voltage
measurements directly from the voltmeter.
Recall factory Trim
Field Comm.1, 4, 2, 1, 8
Recall Factory Trim enables you to return to the original factory trim values.
Pulse output
Field Comm.1, 4, 2, 2
Pulse Output enables you to configure the Pulse Output.
Note
The Field Communicator will allow configuration of the pulse features even if the pulse option
(Option P) was not ordered.
54
Operation
Reference Manual
00809-0100-4860, Rev BC
Pulse output
The Rosemount 8600D comes with an optional pulse output option (P). This enables the
flowmeter to output the pulse rate to an external control system, totalizer, or other device. If the
flowmeter was ordered with the pulse mode option, it may be configured for either pulse
scaling (based on rate or unit) or shedding frequency output. There are four methods for
configuring the pulse output:
Off
Direct (Shedding Frequency)
Scaled Volume
Scaled Velocity
Scaled Mass
Direct (shedding frequency)
Section 4: Operation
January 2013
Field Comm.1, 4, 2, 2, 1
Field Comm.1, 4, 2, 2, 1, 2
This mode provides the vortex shedding frequency as output. In this mode, the software does
not compensate the K-factor for effects such as thermal expansion or differing mating pipe
inside diameters. Scaled pulse mode must be used to compensate the K-factor for thermal
expansion and mating pipe effects.
Scaled volume
Field Comm.1, 4, 2, 2, 1, 3
This mode allows you to configure the pulse output based on a volumetric flow rate. For
example, set 100 gallons per minute = 10,000 Hz. (The user enterable parameters are flow rate
and frequency.)
Pulse scaling rate
Field Comm.1, 4, 2, 2, 1, 3, 1
Pulse scaling rate allows the user to set a certain volume flow rate to a desired Frequency.
For example:
1.Enter a flow rate of 100 gallons per minute.
2.Enter a frequency of 10,000 Hz.
Pulse scaling unit
Operation
Field Comm.1, 4, 2, 2, 1, 3, 2
Pulse scaling unit allows the user to set one pulse equal to a desired volume.
For example:
1 pulse = 100 gal. Enter 100 for the Flow Rate.
55
Section 4: Operation
January 2013
Scaled velocity
This mode allows you to configure the pulse output based on a velocity Flow Rate.
Pulse scaling rate
Allows the user to set a certain velocity flow rate to a desired frequency.
For example:
10 ft/sec = 10,000HZ
1.Enter a Flow rate of 10 ft/sec.
2.Enter a Frequency of 10,000HZ.
Pulse scaling unit
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 4, 2, 2, 1, 4
Field Comm.1, 4, 2, 2, 1, 4, 1
Field Comm.1, 4, 2, 2, 1, 4, 2
Allows the user to set one pulse equal to a desired distance.
For example:
1 pulse = 10 ft. Enter 10 for the distance.
Scaled mass
Field Comm.1, 4, 2, 2, 1, 5
This mode allows you to configure the pulse output based on a mass Flow Rate. If Process Fluid =
Tcomp Sat Steam, this is a temperature compensated mass flow.
Pulse scaling rate
Field Comm.1, 4, 2, 2, 1, 5, 1
Allows the user to set a certain mass Flow Rate to a desired Frequency.
For example:
1000 lbs/hr = 1000HZ
1.Enter a Flow rate of 1000 lbs/hr.
56
2.Enter a Frequency of 1000HZ.
Pulse scaling unit
Field Comm.1, 4, 2, 2, 1, 5, 2
Allows the user to set one pulse equal to a desired mass.
For example:
1 pulse = 1000lbs.
Enter 1000 for the mass.
Operation
Reference Manual
Power
Supply
RS-232-C
Bell 202
Modem
00809-0100-4860, Rev BC
Pulse output test
Pulse Output Test is a fixed frequency mode test that checks the integrity of the pulse loop. It
tests that all connections are good and that pulse output is running on the loop.
HART output
Multidrop configuration refers to the connection of several flowmeters to a single
communications transmission line. Communication occurs digitally between a HART-based
communicator or control system and the flowmeters. Multidrop mode automatically
deactivates the analog output of the flowmeters. Using the HART communications protocol, up
to 15 transmitters can be connected on a single twisted pair of wires or over leased phone lines.
The use of a multidrop installation requires consideration of the update rate necessary from
each transmitter, the combination of transmitter models, and the length of the transmission
line. Multidrop installations are not recommended where intrinsic safety is a requirement.
Communication with the transmitters can be accomplished with commercially available Bell
202 modems and a host implementing the HART protocol. Each transmitter is identified by a
unique address (1-15) and responds to the commands defined in the HART protocol.
Section 4: Operation
January 2013
Field Comm.1, 4, 2, 2, 2
Field Comm.1, 4, 2, 3
Figure 4-1 shows a typical multidrop network. This figure is not intended as an installation
diagram. Contact Rosemount product support with specific requirements for multidrop
applications.
Figure 4-1. Typical Multidrop Network
Note
The Rosemount 8600D is set to poll address zero at the factory, allowing it to operate in the
standard point-to-point manner with a 4–20 mA output signal. To activate multidrop
communication, the transmitter poll address must be changed to a number between 1 and 15.
This change deactivates the 4–20 mA analog output, setting it to 4 mA, and disables the failure
mode alarm signal.
Operation
57
Section 4: Operation
January 2013
Poll address
Poll Address enables you to set the poll address for a multi-dropped meter. The poll address is
used to identify each meter on the multi-drop line. Follow the on-screen instructions to set the
address at a number from 1 to 15. To set or change the flowmeter address, establish
communication with the selected Rosemount 8600D in the loop.
Auto poll
When a HART-based communicator is powered up and auto polling is on, the communicator
automatically polls the flowmeter addresses to which it is connected. If the address is 0, the
HART-based communicator enters its normal online mode. If it detects an address other than 0,
the communicator finds each device in the loop and lists them by poll address and tag. Scroll
through the list and select the meter with which you need to communicate.
If Auto Poll is off, the flowmeter must have the poll address set to 0 or the flowmeter will not be
found. If a single connected device has an address other than zero and auto polling is off, the
device will not be found either.
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 4, 2, 3, 1
Field Comm.OFF LINE FCN
Number of required preams
Field Comm.1, 4, 2, 3, 2
This is the number of preambles required by the 8600D for HART communications.
Number of response preams
Field Comm.1, 4, 2, 3, 3
This is the number of preambles sent by the transmitter in response to any host request.
Burst mode
Field Comm.1, 4, 2, 3, 4
Burst mode configuration
The Rosemount 8600D includes a burst mode function that broadcasts the primary variable or
all dynamic variables approximately three to four times a second. The burst mode is a
specialized function used in very specific applications. The burst mode function enables you to
select the variables to broadcast while in the burst mode and to select the burst mode option.
The Burst Mode variable enables you to set the Burst Mode to the needs of your application.
Options for the Burst Mode setting include:
58
Off–Turns off the Burst Mode so that no data are broadcast on the loop.
On–Turns Burst Mode on so that the data selected under Burst Option are broadcast over the
loop.
Additional command options may appear that are reserved and do not apply to the Rosemount
8600D.
Operation
Reference Manual
00809-0100-4860, Rev BC
Burst option
Burst Option enables you to select the variables to broadcast over the burst transmitter. Choose
one of the following options:
PV–Selects the process variable for broadcast over the burst transmitter.
Percent Range/Current–Selects the process variable as percent of range and analog output
variables for broadcast over the burst transmitter.
Process vars/crnt–Selects the process variables and analog output variables for broadcast over
the burst transmitter.
Dynamic Vars–Burst all dynamic variables in the transmitter.
Xmtr Vars–Allows the user to define custom burst variables. Select variables from the list below:
Section 4: Operation
January 2013
Field Comm.1, 4, 2, 3, 5
Volume Flow
Velocit y Flow
Mass Flow
Vor tex Fre quency
Pulse Output Frequency
Tot alizer Va lue
Process Temperature (MTA Option Only)
Calculated Process Density (MTA Option Only)
Cold Junction Temperature (MTA Option Only)
Electronics Temperature
Burst XMTR vars
Field Comm.1, 4, 2, 3, 6
Allows users to select and define Burst Variables.
XMTR variable slot 1
Field Comm.1, 4, 2, 3, 6, 1
User selected Burst Variable 1.
XMTR variable slot 2
Field Comm.1, 4, 2, 3, 6, 2
User selected Burst Variable 2.
Operation
XMTR variable slot 3
Field Comm.1, 4, 2, 3, 6, 3
User selected Burst Variable 3.
59
Section 4: Operation
January 2013
XMTR variable slot 4
User selected Burst Variable 4.
Local display
The Local Display function on the Rosemount 8600D allows you to select which variables are
shown on the optional (M5) local display. Choose from the following variables:
Primary Variable
Loop Current
Percent of Range
Tot a li ze r
Shedding Frequency
Mass Flow
Velocit y Flow
Volumetric Flow
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 4, 2, 3, 6, 4
Field Comm.1, 4, 2, 4
Pulse Output Frequency
Electronics Temperature
Process Temperature (MTA Option Only)
Calculated Process Density (MTA Option Only)
4.3.3Signal processing
Field Comm.1, 4, 3
The Rosemount 8600D and its HART-based communications feature enable you to filter out
noise and other frequencies from the transmitter signal. The four user-alterable parameters
associated with the digital signal processing on the Rosemount 8600D include low-pass filter
corner frequency, low-flow cutoff, trigger level, and damping. These four signal conditioning
functions are configured at the factory for optimum filtering over the range of flow for a given
line size and service type (liquid or gas). For most applications, leave these parameters at the
factory settings. Some applications may require adjustment of the signal processing
parameters.
Use signal processing only when recommended in the Troubleshooting section of this manual.
Some of the problems that may require signal processing include:
High output (output saturation)
Erratic output with or without flow present
Incorrect output (with known flow rate)
No output or low output with flow present
60
Low total (missing pulses)
High total (extra pulses)
Operation
Reference Manual
00809-0100-4860, Rev BC
If one or more of these conditions exist, and you have checked other potential sources (K-factor,
service type, lower and upper range values, 4–20mA trim, pulse scaling factor, process
temperature, pipe ID), refer to Section 5: Troubleshooting. Remember that the factory default
settings can be re-established at any time with Filter Restore. If problems persist after signal
processing adjustments, consult the factory.
Optimize flow range
The Optimize Flow Range function will automatically set the 8600D filter levels, Low Flow Cutoff
(LFC), Trigger Level, and Low Pass Corner Frequency, to optimum settings based on the process
density and process fluid type.
Primary Variable (PV)
PV is the actual measured variable rate in the line. On the bench, the PV value should be zero.
Check the units on the PV to make sure they are configured correctly. See PV Units if the units
format is not correct. Use the Process Variable Units function to select the units for
your application.
Section 4: Operation
January 2013
Field Comm.1, 4, 3, 1
Field Comm.1, 4, 3, 1, 1
Low flow cutoff
Field Comm.1, 4, 3, 1, 2
Low Flow Cutoff is shown in engineering units.
Signal/trigger level ratio (Sig/Tr)
Field Comm.1, 4, 3, 1, 3
The Signal to Trigger Level Ratio is a variable that indicates the flow signal strength to trigger
level ratio. This ratio indicates if there is enough flow signal strength for the meter to work
properly. For accurate flow measurement, the ratio should be greater than 4:1. Values greater
than 4:1 will allow increased filtering for noisy applications. For ratios greater than 4:1, with
sufficient density, the Auto Adjust Filter function can be utilized to optimize the measurable
range of the flowmeter.
Ratios less than 4:1 may indicate applications with very low densities and/or applications with
excessive filtering.
Auto adjust filter
Field Comm.1, 4, 3, 1, 4
The Auto Adjust Filter is a function that can be used to optimize the range of the flowmeter
based on the density of the fluid. The electronics uses process density to calculate the minimum
measurable flow rate, while retaining at least a 4:1 signal to the trigger level ratio. This function
will also reset all of the filters to optimize the flowmeter performance over the new range. For a
stronger signal select a density value that is lower than the actual flowing density.
Operation
61
Section 4: Operation
January 2013
Manual filter adjust
Manual Filter Adjust allows you to manually adjust the following settings: Low Flow Cutoff, Low
Pass Filter, and Trigger Level, while monitoring flow and or sig/tr.
Primary Variable (PV)
PV is the actual measured variable. Check the units on the PV to make sure they are configured
correctly. See PV Units if the units format is not correct. Use the Process Variable Units function
to select the units for your application.
Signal/trigger level ratio (Sig/Tr)
The Signal to Trigger Level Ratio is a variable that indicates the flow signal strength to trigger
level ratio. This ratio indicates if there is enough flow signal strength for the meter to work
properly. For accurate flow measurement, the ratio should be greater than 4:1. Values greater
that 4:1 will allow increased filtering for noisy applications. For ratios greater than 4:1, with
sufficient density, the Optimize Flow Range function can be utilized to optimize the measurable
range of the flowmeter.
Reference Manual
00809-0100-4860, Rev BC
Field Comm.1, 4, 3, 2
Field Comm.1, 4, 3, 2, 1
Field Comm.1, 4, 3, 2, 2
Ratios less than 4:1 may indicate applications with very low densities and/or applications with
excessive filtering.
Low flow cutoff
Field Comm.1, 4, 3, 2, 3
Low Flow Cutoff enables you to adjust the filter for noise at no flow. It is set at the factory to
handle most applications, but certain applications may require adjustment either to expand
measurability or to reduce noise.
The Low Flow Cutoff offers two modes for adjustment:
Increase Range
Decrease No Flow Noise
It also includes a dead band such that once flow goes below the cutoff value, output does not
return to the normal flow range until flow goes above the dead band. The dead band extends to
approximately 20 percent above the low flow cutoff value. The dead band prevents the output
from bouncing between 4mA and normal flow range if the flow rate is near the low flow cutoff
value.
Low pass filter
Field Comm.1, 4, 3, 2, 4
62
The Low Pass Filter sets the low-pass filter corner frequency to minimize the effects of high
frequency noise. It is factory set based
on line size and service type. Adjustments may be required only if
you are experiencing problems. See Section 5: Troubleshooting.
Operation
Reference Manual
00809-0100-4860, Rev BC
The Low Pass Filter corner frequency variable offers two modes for adjustment:
Increase filtering
Increase sensitivity
Trigger level
Trigger Level is configured to reject noise within the flow range while allowing normal amplitude
variation of the vortex signal. Signals of amplitude lower than the Trigger Level setting are
filtered out. The factory setting optimizes noise rejection in most applications. Trigger Level
offers two modes for adjustment:
Increase filtering
Increase sensitivity
Note
Do not adjust this parameter unless directed to do so by a Rosemount Technical Support
Representative.
Section 4: Operation
January 2013
Field Comm.1, 4, 3, 2, 5
Filter restore
Field Comm.1, 4, 3, 3
Filter Restore enables you to return all of the signal conditioning variables to their default values.
Should the filter settings get confused, select Filter Restore to restore the default settings and
provide a new starting point.
Damping
Field Comm.1, 4, 3, 4
Damping function changes the response time of the flowmeter to smooth variations in output
readings caused by rapid changes in input.
The appropriate damping setting can be determined based on the necessary response time,
signal stability, and other requirements of the loop dynamics in your system.
PV damping
Field Comm.1, 4, 3, 4, 1
The default damping value is 2.0 seconds. Damping can be reset to any value between 0.2 and
255 seconds when PV is a flow variable or 0.4 to 32 seconds when PV is Process Temperature.
Flow damping
Operation
Field Comm.1, 4, 3, 4, 2
The default damping value is 2.0 seconds. Flow Damping can be reset to any value between 0.2
and 255 seconds.
63
Section 4: Operation
January 2013
Temperature damping
Field Comm.1, 4, 3, 4, 3
The default damping value is 2.0 seconds. Temperature Damping can be reset to any value
between 0.4 and 32 seconds.
LFC response
Field Comm.1, 4, 3, 5
Defines how the output of the Vortex meter will behave entering into and coming out of the Low
Flow Cutoff. Options are stepped or damped. (See Technical Note 00840-0200-4004 for more
information regarding Low Flow Measurement).
4.3.4Device information
Field Comm.1, 4, 4
Information variables are used for identification of flowmeters in the field and to store
information that may be useful in service situations. Information variables have no effect on
flowmeter output or process variables.
Reference Manual
00809-0100-4860, Rev BC
Manufacturer
Field Comm.1, 4, 4, 1
Manufacturer is an informational variable provided by the factory. For the Rosemount 8600D,
the Manufacturer is Rosemount.
Tag
Field Comm.1, 4, 4, 2
Tag is the quickest variable to identify and distinguish between flowmeters. Flowmeters can be
tagged according to the requirements of your application. The tag may be up to eight
characters long.
Descriptor
Field Comm.1, 4, 4, 3
Descriptor is a longer user-defined variable to assist with more specific identification of the
particular flowmeter. It is usually used in multi-flowmeter environments and provides 16
characters.
Message
Field Comm.1, 4, 4, 4
64
The Message variable provides an even longer user-defined variable for identification and other
purposes. It provides 32 characters of information and is stored with the other configuration
data.
Operation
Reference Manual
00809-0100-4860, Rev BC
Date
Date is a user-defined variable that provides a place to save a date, typically used to store the last
date that the transmitter configuration was changed.
Write protect
Write Protect is a read-only informational variable that reflects the setting of the hardware
security switch. If Write Protect is ON, configuration data are protected and cannot be changed
from a HART-based communicator or control system. If Write Protect is OFF, configuration data
may be changed using the communicator or control system.
Transmitter options
Transmitter Options indicates if Internal Flow Simulation option is enabled.
Section 4: Operation
January 2013
Field Comm.1, 4, 4, 5
Field Comm.1, 4, 4, 6
Field Comm.1, 4, 4, 7
Revision numbers
Field Comm.1, 4, 4, 8
Revisions Numbers are fixed informational variables that provide the revision number for
different elements of your Field Communicator and Rosemount 8600D. These revision numbers
may be required when calling the factory for support. Revision numbers can only be changed at
the factory and are provided for the following elements:
Universal rev
Field Comm.1, 4, 4, 8, 1
Universal Rev – Designates the HART Universal Command specification to which the transmitter
is designed to conform.
Transmitter rev
Field Comm.1, 4, 4, 8, 2
Tra nsmitte r Re v – Designates the revision for Rosemount 8600D specific command identification
for HART compatibility.
Software rev
Field Comm.1, 4, 4, 8, 3
Operation
Software Rev – Designates the internal software revision level for the Rosemount 8600D.
65
Section 4: Operation
January 2013
Hardware rev
Hardware Rev – Designates the revision level for the Rosemount
8600D hardware.
Final assembly number
Final Assembly Number – Factory set number that refers to the electronics of your flowmeter.
The number is configured into the flowmeter for later reference.
Device ID
Device ID – Factory-defined unique identifier for transmitter identification in the software.
Device ID is not user changeable.
“Troubleshooting tables” on page 68 provides summarized troubleshooting suggestions for the
most common problems that occur during operation. The symptoms of metering problems
include:
Communications problems with a HART-based communicator.
Incorrect 4–20 mA output.
Section 5: Troubleshooting
January 2013
Incorrect pulse output.
Error messages on HART-based communicator.
Flow in pipe but no transmitter output.
Flow in pipe with incorrect transmitter output.
Output with no actual flow.
Note
The Rosemount 8600D sensor is extremely reliable and should not have to be replaced. Please
consult the factory before removing the sensor.
5.1Safety messages
Instructions and procedures in this section may require special precautions to ensure the safety
of the personnel performing the operations. Please refer to the following safety messages
before performing any in this section.
Tro u bl esh o oti ng
67
Section 5: Troubleshooting
January 2013
Explosions could result in death or serious injury:
Do not remove the transmitter cover or thermocouple (MTA option only) from the
electronics housing in explosive atmospheres when the circuit is alive.
Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Both transmitter covers must be fully engaged to meet explosion-proof requirements.
Failure to follow these installation guidelines could result in death or serious injury:
Make sure only qualified personnel perform the installation.
Removing sensor WILL open process to atmosphere. Meter must be depressurized before
removing sensor.
Reference Manual
00809-0100-4860, Rev BC
5.2Troubleshooting tables
The most common problems experienced by users of the Rosemount 8600D are listed in “Trou-
bleshooting tables” on page 68 along with potential causes of the problem and suggested
corrective actions. See the Advanced Troubleshooting section if the problem you are
experiencing is not listed here.
SymptomCorrective Action
Communication
problems with
HART-based Communicator
Incorrect 4–20 mA Output
• Check for a minimum of 10.8 Vdc at transmitter
terminals
• Check communications loop with HART-based
communicator.
• Check for loop resistor (250 to 1000 ohms).
• Measure loop resistor value (R
supply voltage (V
0.024)] > 10.8 Vdc.
• Check for minimum 10.8 Vdc at transmitter
terminals.
• Check URV, LRV, Density, Special Units, LFC–
compare these inputs with the sizing program
results. Correct configuration.
• Perform 4–20 mA loop test.
). Check that [Vps - (R
ps
) and source power
loop
loop
• Check for transmitter in multidrop mode.
• Check for transmitter in burst mode.
• Remove pulse connection if you have a three
wire pulse installation.
• Replace electronics.
x
• Check for corrosion on terminal block.
• Replace electronics if necessary.
•Refer to
• See Appendix Appendix C Electronics
“Advanced troubleshooting”
on page 69
verification for electronics verification
procedure.
.
Incorrect Pulse Output
Error Messages on
HART-based Communicator
68
• Check that 4–20 mA output is correct.
• Check pulse counter specifications.
• Check pulse mode and scaling factor. (Make sure
scaling factor is not inverted).
• See alphabetical listing in Table 5-1 on
page 5-70.“Diagnostic messages” on
page 69
•Perform pulse test.
• Select pulse scaling so that pulse output is less
than 10,000Hz at URV.
Tro u bl esh o oti ng
Reference Manual
00809-0100-4860, Rev BC
SymptomCorrective Action
Section 5: Troubleshooting
January 2013
Flow in Pipe, No OutputBasics
• Check to make the sure that the meter is installed
with the arrow in the direction of process flow.
• Perform basic checks for Incorrect 4–20 mA
Output Problem (see Incorrect 4–20 mA Output).
• Check and correct configuration parameters in this
order:
• Process Config - transmitter mode, process fluid,
fixed process temperature, density/density ratio (if
required), reference K-factor, flange type, mating
pipe ID, variable mapping, PV unit, range values (URV, LRV), PV damping, auto filter adjust, pulse
mode and scaling (if used).
• Check sizing. Make sure flow is within measurable
flow limits. Use Instrument Toolkit for best sizing
results.
• Refer to
“Advanced troubleshooting” on
page 69.
• See Appendix Appendix C Electronics verification
for electronics verification procedure.
Electronics
• Run a self test with a HART-based interface tool.
• Using sensor simulator, apply test signal.
• Check configuration, LFC, trigger level, STD vs.
actual flow units.
• Replace electronics.
5.3Advanced troubleshooting
Application Problems
• Calculate expected frequency (see Appendix
Appendix C Electronics verification). If actual
frequency is the same, check configuration.
• Check that application meets viscosity and
specific gravity requirements for the line size.
• Recalculate back pressure requirement. If
necessary and possible, increase back
pressure, flow rate, or operating pressure.
Sensor
• Inspect coaxial sensor cable for cracks.
Replace if necessary.
• Check that sensor impedance at process
temperature is > 1 Mega-Ohm (will function
down to 0.5 Mega-Ohms). Replace sensor if
necessary (
page 80
• Measure sensor capacitance at SMA
connector (115-700pF).
“Replacing the sensor” on
).
The Rosemount 8600D electronics provides several advanced troubleshooting features. These
features enhance your ability to look inside the electronics and can be helpful for troubleshooting inaccurate readings. As shown in Figure 5-1, there are several test points located on the
electronics.
5.3.1Diagnostic messages
The following is a list of messages used by the Field Communicator and their corresponding
descriptions.
Tro u bl esh o oti ng
69
Section 5: Troubleshooting
January 2013
Reference Manual
00809-0100-4860, Rev BC
Table 5-1. Diagnostic Messages
MessageDescription
ROM CHECKSUM ERRORThe EPROM memory checksum test has failed. The transmitter will remain in ALARM
NV MEM CHECKSUM ERRORThe User Configuration area in Nonvolatile EEPROM memory has failed the checksum
RAM TEST ERRORTransmitter RAM memory test has detected a failed RAM location. The transmitter
DIGITAL FILTER ERRORThe digital filter in the transmitter electronics is not reporting. The transmitter will
COPROCESSOR ERRORIf this occurs at power-up, the RAM/ROM test in the coprocessor has failed. If this
SOFTWARE DETECTED ERRORThe software has detected corrupted memory. One or more of the software tasks
ELECTRONICS FAILUREThis is a summary error indication. This error will be reported if any of the following
TRIGGER LEVEL OVERRANGEThe trigger level in the transmitter digital signal processing has been set beyond its
LOW PASS FILT OVERRANGEThe low pass filter in the transmitter digital signal processing has been set beyond its
ELECTRONICS TEMP OUT OF LIMITSThe electronics temperature sensor within the transmitter is reporting a value out of
INVALID CONFIGURATIONCertain configuration parameters are out of range. Either they have not been
FACTORY EEPROM
CONFIG ERROR
LOW FLOW CUTOFF OVERRANGEOn start-up, the configured setting for the VDSP Low Flow Cutoff setting was found
T/C A/D ERRORThe ASIC responsible for the analog to digital conversion of the process temperature
THERMOCOUPLE OPENThe thermocouple that is used to measure the process temperature has failed. Check
CJ RTD FAILUREThe RTD temperature sensing device for sensing the cold junction temperature has
FLOW SIMULATIONThe transmitter flow signal is being simulated by a signal generator internal to the
SENSOR SIGNAL IGNOREDThe transmitter flow signal is being simulated by a signal generator external to the
until the ROM checksum test passes.
test. It is possible to repair this checksum by verifying and reconfiguring ALL
transmitter parameters. The transmitter will remain in ALARM until the EEPROM
checksum test passes.
will remain in ALARM until the RAM test passes.
remain in ALARM until the digital signal processor resumes reporting flow data.
occurs during normal operations, the coprocessor has reported either a math error
or a negative flow. This is a FATAL error and the transmitter will remain in ALARM until
reset.
has corrupted memory. This is a FATAL error and the transmitter will remain in ALARM
until reset.
error conditions are present:
1. ROM Checksum Error
2. NV Memory Checksum Error
3. RAM Test Error
4. ASIC Interrupt Error
5. Digital FIlter Error
6. Coprocessor Error
7. Software Detected Error
limit. Use manual filter adjustment to “Increase Filtering” or “Increase Sensitivity” to
bring the trigger level back within range.
limit. Use manual filter adjustment to “Increase Filtering” or “Increase Sensitivity” to
bring the low pass filter adjustment back within range.
range.
properly configured, or they have been forced out of range as a result of a change to a
related parameter. For example: When using mass flow units, changing the process
density to a value too low could push the configured Upper Range Value beyond the
sensor limit. In this case, the Upper Range Value would need to be reconfigured.
The factory configured values in non-volatile EEPROM memory have become
corrupted. This is a FATAL error. The transmitter will remain in ALARM until reset.
to be too high or too low. The increase range or decrease no flow noise command of
the VDSP Low Flow Cutoff setting has not yet brought the setting into a valid range.
Continue adjusting the Low Flow Cutoff to a valid value or use the Filter Restore
Option.
thermocouple and cold junction RTD has failed. If the problem persists, replace the
transmitter electronics.
the connections to the transmitter electronics. If the problem persists, replace the
thermocouple.
failed. If the problem persists, replace the transmitter electronics.
transmitter. The actual flow through the meter body is NOT being measured.
transmitter. The actual flow through the meter body is NOT being measured.
70
Tro u bl esh o oti ng
Reference Manual
GROUND
TP1
Test Fre q IN
00809-0100-4860, Rev BC
Section 5: Troubleshooting
January 2013
LOW LOOP VOLTAGEThe voltage at the transmitter terminals has dropped to a level that is causing the
INTERNAL COMM FAULTAfter several attempts, the microprocessor failed in communication with the
INTERNAL SIGNAL FAULTThe flow data encoded on a pulse signal from the Sigma-Delta ASIC to VDSP has been
TEMPERATURE ELECTRONICS
FAI LUR E
PROCESS TEMP OUT OF RANGEThe Process Temperature is beyond the defined sensor limits of -50 °C to 427 °C.
PROCESS TEMP ABOVE SAT STEAM
LIMITS
PROCESS TEMP BELOW SAT STEAM
LIMITS
FIXED PROCESS TEMPERATURE IS
ACTIVE
INVALID MATH COEFFThe area of nonvolatile memory used to store the curve fit coefficients for the
CJ TEMP ABOVE SENSOR LIMITSThe temperature reported from the Cold Junction temperature sensor is above CJ
CJ TEMP BELOW SENSOR LIMITSThe temperature reported from the Cold Junction temperature sensor is below CJ
internal voltage supplies to drop, reducing the capability of the transmitter to
accurately measure a flow signal. Check the terminal voltage and either increase the
power supply voltage or reduce loop resistance.
Sigma-Delta ASIC. A power cycle may resolve the problem. Also, check the
inter-board connector. If the problem persists, replace the transmitter electronics.
lost. A power cycle may resolve the problem. Also check the inter-board connector. If
the problem persists, replace the transmitter electronics.
The electronics circuitry that supports the measurement of the Process Temperature
has failed. The transmitter can still be used in a non-Process Temperature mode.
The Process Temperature is above the high limit for Saturated Steam density
calculations. This status only occurs when the Process Fluid is Temperature
Compensated Saturated Steam. The density calculation will continue using a Process
Temperature of 320 °C.
The Process Temperature is below the low limit for Saturated Steam density
calculations. This status only occurs when the Process Fluid is Temperature
Compensated Saturated Steam. The density calculation will continue using a Process
Temperature of 80 °C.
Due to a problem detected with the thermocouple, a configured fixed Process
Temperature is being substituted for the measured Process Temperature. This fixed
Process Temperature is also being used in saturated steam density calculations.
coprocessor calculations does not contain valid data. This data can only be loaded at
the factory. Replace the transmitter electronics.
sensor limits.
sensor limits.
5.3.2Electronics test points
As shown in Figure 5-1, there are several test points located on the electronics.
Figure 5-1. Electronics Test Points
Tro u bl esh o oti ng
71
Section 5: Troubleshooting
Sensor
Charge
Amplifier
Amplifier/
Low Pass
Filter
External
Tes t
Frequency
Input
TP1
Digital Filter
Microprocessor
A-to-D
Converter
Internal
Frequency
Generator
Tri gg er
Level
Vortex Signal (TP1)
Shedding
Frequency
Output
0
3.0 V
0
January 2013
The electronics is capable of internally generating a flow signal that may be used to simulate a
sensor signal to perform electronics verification with a Handheld Communicator or AMS
interface. The simulated signal amplitude is based on the transmitter required minimum
process density. The signal being simulated can be one of several profiles – a simulated signal of
constant frequency or a simulated signal representative of a ramping flow rate. The electronics
verification procedure is described in detail in Appendix C: Electronics verification. To verify the
electronics, you can input a frequency on the “TEST FREQ IN” and “GROUND” pins to simulate
flow via an external signal source such as a frequency generator. To analyze and/or troubleshoot
the electronics, an oscilloscope (set for AC coupling) and a Handheld Communicator or AMS
interface are required. Figure 5-2 is a block diagram of the signal as it flows from the sensor to
the microprocessor in the electronics.
Figure 5-2. Signal Flow
Reference Manual
00809-0100-4860, Rev BC
5.3.3TP1
TP1 is the vortex shedding signal after it has gone through the charge amplifier and low pass filter
stages and into the input of the sigma delta A-to-D converter ASIC in the electronics. The signal
strength at this point will be in the mV to Volt range.
TP1 is easily measured with standard equipment.
Figures 5-3, 5-4, and 5-5 show ideal (clean) waveforms and waveforms that may cause the
output to be inaccurate. Please consult the factory if the waveform you detect is not similar in
principle to these waveforms.
Figure 5-3. Clean Signals
72
Tro u bl esh o oti ng
Reference Manual
Vortex Signal
(TP1)
Trigger
Level
Shedding
Frequency
Output
0
3.0 V
0
Shedding
Frequency
Output
0
3.0 V
0
Vor tex Signal
(TP1)
Tri gg er
Level
00809-0100-4860, Rev BC
Figure 5-4. Noisy Signals
Section 5: Troubleshooting
January 2013
Figure 5-5. Improper Sizing/Filtering
5.4Diagnostic messages on LCD
In addition to the output, the LCD indicator displays diagnostic messages for troubleshooting
the flowmeter. These messages are as follows:
SELFTEST
The flowmeter is in the process of performing an electronics self test.
73
FAULT_ROM
Tro u bl esh o oti ng
The flowmeter electronics has undergone a EPROM checksum fault. Contact your Field Service
Center.
Section 5: Troubleshooting
January 2013
FAULT_EEROM
The flowmeter electronics has undergone a EEPROM checksum fault. Contact your Field Service
Center.
FAULT_RAM
The flowmeter electronics has undergone a RAM test fault.
Contact your Field Service Center.
FAULT_ASIC
The flowmeter electronics has undergone a digital signal processing ASIC update fault. Contact
your Field Service Center.
FAULT_CONFG
The flowmeter electronics has lost critical configuration parameters. This message will be
followed by information detailing the missing configuration parameters. Contact your Field
Service Center.
Reference Manual
00809-0100-4860, Rev BC
FAULT_COPRO
The flowmeter electronics has detected a fault in the math coprocessor. Contact your Field
Service Center.
FAULT_SFTWR
The flowmeter electronics has detected a non-recoverable fault in the software operation.
Contact your Field Service Center.
FAULT_LOOPV
The flowmeter electronics has detected insufficient voltage to power the sensor board. Most
likely the cause is low voltage at transmitter
4–20 mA terminals. Contact your Field Service Center.
FAULT_SDCOM
The flowmeter electronics has detected an unexpected sigma-delta ASIC communications fault.
Contact your Field Service Center.
FAULT_SDPLS
The flowmeter electronics has detected a loss of flow data from the sigma-delta ASIC. Contact
your Field Service Center.
74
FAULT_COEFF
The area of NV memory used to store the curve fit coefficients for the coprocessor calculation
does not contain valid date. This date con only be loaded at the factory. Contact your Field
Service Center.
Tro u bl esh o oti ng
Reference Manual
00809-0100-4860, Rev BC
FAULT_TACO (MTA option only)
The ASIC responsible for the analog to digital conversion of the process temperature has failed.
Contact your Field Service Center.
FAULT_TC (MTA option only)
The temperature sensor that is used to measure the process temperature has failed. Contact
your Field Service Center.
FAULT_RTD (MTA option only)
The RTD for cold junction compensation has failed. Contact your Field Service Center.
SIGNAL_SIMUL
The transmitter flow signal is being simulated by a signal generator internal to the transmitter.
The actual flow through the meter body is NOT being measured.
Section 5: Troubleshooting
January 2013
SENSOR_OFFLINE
The transmitter flow signal is being simulated by a signal generator external to the transmitter.
The actual flow through the meter body is NOT being measured.
FAULT_LOOPV
The voltage at the transmitter terminals has dropped to a level that is causing the internal
voltage supplies to drop, reducing the capability of the transmitter to accurately measure a flow
signal. Check the terminal voltage and either increase the power supply voltage or reduce loop
resistance.
5.5Testing procedures
Use the test functions to verify that the flowmeter is functioning properly, or when you suspect
component failure or a problem with loop performance, or when instructed to do so as part of a
troubleshooting procedure. Initiate each test with a HART-based communications device. See
“Diagnostics/service” on page 47 for details.
5.6Hardware replacement
Tro u bl esh o oti ng
The following procedures will help you disassemble and assemble the Rosemount 8600D
hardware if you have followed the troubleshooting guide earlier in this section of the manual
and determined that hardware components need to be replaced.
75
Section 5: Troubleshooting
See Safety Messages on page 67 for complete warning
Terminal Block
O-Ring
Captive
Screws (3x)
Cover
January 2013
Note
Use only the procedures and new parts specifically referenced in this manual. Unauthorized
procedures or parts can affect product performance and the output signal used to control a
process, and may render the instrument dangerous.
Note
Flowmeters should not be left in service once they have been determined to be inoperable.
Note
Process should be vented before the meter body is removed from service for disassembly.
5.6.1Replacing the terminal block in the housing
To replace the Field Terminal Block in the housing, you will need a small screwdriver. Use the
following procedure to replace the terminal block in the housing of the Rosemount 8600D.
Note
Remove power before removing the electronics cover.
Reference Manual
00809-0100-4860, Rev BC
Remove the terminal block
1.Turn off the power to the Rosemount 8600D.
2.Unscrew the cover.
Figure 5-6. Terminal Block Assembly
3.Disconnect the wires from the field terminals. Be sure to secure them out of the way.
4.Remove the ground screw if transient protection (Option T1) is installed.
5.Loosen the three captive screws.
76
6.Pull outward on the terminal block to remove it from the housing.
Tro u bl esh o oti ng
Reference Manual
See Safety Messages on page 67 for complete warning
00809-0100-4860, Rev BC
Install the terminal block
1.Align the socketed holes on the back side of the terminal block over the pins protruding
from the bottom of the housing cavity in the terminal block side of the electronics
housing.
2.Slowly press the terminal block into place. Do not force the
block into the housing. Check the screw alignment if it
does not glide into place.
3.Tighten the three captive screws to anchor the terminal block.
4.Connect the wires to the appropriate field terminals.
5.Reinstall and tighten the transient ground screw if you have the transient option
(Option T1).
6.Screw on and tighten the cover.
5.6.2Replacing the electronics boards
Section 5: Troubleshooting
January 2013
The Rosemount 8600D electronics boards may need to be replaced if they have been damaged
or otherwise become dysfunctional. Use the following procedures to replace electronics boards
in the Rosemount 8600D. You will need a small Phillips head screwdriver and pliers.
Note
The electronics boards are electrostatically sensitive. Be sure to observe handling precautions
for static-sensitive components.
Note
Remove power before removing the electronics cover.
Remove the electronics boards
1.Turn off the power to the Rosemount 8600D.
2.Unscrew and remove the electronics board compartment cover. (Unscrew and remove
the LCD cover if you have the LCD option).
Tro u bl esh o oti ng
77
Section 5: Troubleshooting
Electronics Boards
January 2013
Figure 5-7. Electronics Boards Assembly
Reference Manual
00809-0100-4860, Rev BC
3.If the meter has the LCD indicator option, loosen the two screws. Remove the LCD and
the connector from the electronics board.
4.Loosen the three captive screws that anchor the electronics.
5.Use pliers or a flathead screwdriver to carefully remove the sensor cable clip from the
electronics.
6.Remove thermocouple if MTA option installed.
7.Use the handle molded into the black plastic cover to slowly pull the electronics boards
out of the housing.
78
Tro u bl esh o oti ng
Reference Manual
See Safety Messages on page 67 for complete warning
00809-0100-4860, Rev BC
Install the electronics boards
1.Verify that power to the Rosemount 8600D is off.
2.Align the sockets on the bottom of the two electronics boards over the pins protruding
3.Carefully guide the sensor cable through the notches on the edge of the circuit boards.
4.Slowly press the boards into place. Do not force the boards down. Check the alignment
5.Carefully insert sensor cable clip into electronics board.
6.Tighten the three captive screws to anchor the two electronics boards. Ensure that the
7.Reinsert jumpers into proper location.
8.If the meter has LCD option, insert the connector header into the
Section 5: Troubleshooting
January 2013
from the bottom of the housing cavity.
if they do not glide into place.
SST washer is under the screw in the 2 o’clock position.
LCD board.
a.Remove jumpers from the electronics board.
b. Put the connector through the bezel on the electronics board.
c.Carefully press the LCD onto the electronics board.
d. Tighten the two screws that retain the LCD indicator.
e. Insert the alarm and security jumpers in the correct location.
9.Replace the electronics board compartment cover.
5.6.3Replacing the electronics housing
The Rosemount 8600D electronics housing can be replaced easily when necessary. Use the
following procedure:
Tools needed
Screwdriver to disconnect wires
Tools to disconnect conduit
Note
Remove power before removing the electronics housing.
5
/32-in. (4 mm) hex wrench
5
/16-in. (8 mm) open end wrench
Tro u bl esh o oti ng
79
Section 5: Troubleshooting
January 2013
Remove the electronics housing
1.Turn off the power to the Rosemount 8600D.
2.Remove the terminal block side cover.
3.Disconnect the wires and conduit from the housing.
Reference Manual
00809-0100-4860, Rev BC
4.Use a
5
/32-in. (4 mm) hex wrench to loosen the housing rotation screws (at the base of
the electronics housing) by turning screws clockwise (inward) until they clear the
bracket.
5.Slowly pull the electronics housing no more than 1.5-in. (40 mm) from the top of the
bracket.
6.Loosen the sensor cable nut from the housing with a
5
/16-in. (8 mm) open end wrench.
Note
Lift the electronics housing until the sensor cable nut is exposed. Do not pull the housing more
than 1.5-in. (40 mm) from the top of the bracket. Damage to the sensor may occur if this sensor
cable is stressed.
Install the electronics housing
1.Verify that power to the Rosemount 8600D is off.
2.Screw the sensor cable nut onto the base of the housing.
3.Tighten the sensor cable nut with a
4.Place the electronics housing into the top of the bracket.
5.Tighten the housing rotation screws with a hex
5
/16-in. (8 mm) open end wrench.
5
/32-in. (4 mm) wrench.
6.Place the access cover on the bracket (if applicable).
7.Tighten the screw on the access cover.
8.Connect conduit and wires.
9.Replace the terminal block cover.
10.Apply power.
5.6.4Replacing the sensor
The sensor for the Rosemount 8600D is a sensitive instrument that should not be removed
unless there is a problem with it. If you must replace the sensor, follow these procedures closely.
Please consult the factory before removing the sensor.
80
Tro u bl esh o oti ng
Reference Manual
Bracket Anchor Bolts
Sensor Bolts
00809-0100-4860, Rev BC
Note
Be sure to fully check all other troubleshooting possibilities before removing the sensor.
Also, please note that the sensor is a complete assembly and cannot be further disassembled.
Tools needed
5 mm hex wrench
Suction or compressed air device
Small, soft bristle brush
Cotton swabs
Appropriate cleaning liquid: water or cleaning agent
1.De-pressurize the flow line.
2.Remove the electronics housing (see “Replacing the electronics housing” on page 79).
5
/32-in. (4 mm) hex wrench
5
/16-in. (8 mm) open end wrench
Section 5: Troubleshooting
January 2013
Removable bracket
3.Loosen the four bracket anchor bolts with a 5 mm hex wrench (See “Removable Bracket
AssemblyFigure 5-8).
Figure 5-8. Removable Bracket Assembly
Tro u bl esh o oti ng
4.Remove the bracket.
5.Loosen Sensor bolts with 5 mm hex wrench.
6.Remove sensor bolts, sensor, and gasket.
81
Section 5: Troubleshooting
Sealing Surface
January 2013
Cleaning the sealing surface
Before installing a sensor in the meter body, clean the sealing surface by completing the
following procedure. The gaskets around the sensor are used to seal in the process fluid.
1.Use a suction or compressed air device to remove any loose particles from the sealing
Note
Do not scratch or deform any part of the sensor.
2.Carefully brush the sealing surface clean with a soft bristle brush.
3.Moisten a cotton swab with an appropriate cleaning liquid.
4.Wipe the sealing surface. Repeat several times if necessary with a clean cotton swab
Reference Manual
00809-0100-4860, Rev BC
surface and other adjacent areas in the sensor.
until there is minimal dirt residue picked up by the cotton swab.
Figure 5-9. Sensor Sealing Surface
5.Place new gasket on sealing surface.
6.Place new sensor on gasket.
7.Screw the sensor assembly in place. Tighten the bolts, in a crosswise sequence, with a 5
mm hex wrench to 70.8 in-lb (8 N-m).
82
8.Place the bracket into position.
9.Tighten the four bolts that anchor the bracket in place
with a 5 mm hex wrench.
10.Install the flowmeter electronics housing. See Replacing the electronics housing on
page 5-79.
Tro u bl esh o oti ng
Reference Manual
00809-0100-4860, Rev BC
5.6.5Remote electronics procedure
If the Rosemount 8600D electronics housing is mounted remotely, some replacement
procedures are different than for the flowmeter with integral electronics. The following
procedures are exactly the same:
Replacing the Terminal Block in the Housing (see page 76).
Replacing the Electronics Boards (see page 77).
Replacing the Sensor (see page 80).
To disconnect the coaxial cable from the meter body and electronics housing, follow the
instructions below.
Disconnect the coaxial cable at the meter
1.Remove the access cover on the meter body bracket if present.
Section 5: Troubleshooting
January 2013
2.Loosen the three housing rotation screws at the base of the meter adapter with a
5
/32-in.
hex wrench by turning the screws clockwise (inward) until they clear the bracket.
3.Slowly pull the meter adapter no more than 1.5-in. (40 mm) from the top of the
bracket.
4.Loosen and disconnect the sensor cable nut from the union using
5
a
/16-in. open end wrench.
Note
Do not pull the adapter more than 1.5-in. (40 mm) from the top of the bracket. Damage to the
sensor may occur if the sensor cable is stressed.
Tro u bl esh o oti ng
83
Section 5: Troubleshooting
Coaxial Cable
Meter Adapter
Union
Wash er
Nut
Sensor Cable Nut
Meter Body
bracket
½ NPT Conduit Adapter or
Cable Gland (Supplied by
January 2013
Figure 5-10. Coaxial Cable Connections
Reference Manual
00809-0100-4860, Rev BC
Detach the meter adapter
The above instructions will provide access to the meter body. Use the following steps if it is
necessary to remove the coaxial cable:
1.Loosen and remove the two screws that hold the union onto the meter adapter and pull
2.Loosen and remove the sensor cable nut from the other end
3.Loosen and disconnect the conduit adapter or cable gland from the
the union away from the adapter.
of the union.
meter adapter.
84
Tro u bl esh o oti ng
Reference Manual
00809-0100-4860, Rev BC
Attach the meter adapter
1.If you are using a conduit adapter or cable gland, slide it over the plain end of the coaxial
2.Slide the meter adapter over the coaxial cable end.
Section 5: Troubleshooting
January 2013
cable (the end without a ground wire).
3.Use a
4.Place the union onto the two screws extending out of the meter adapter and tighten
5
/16-in. (8 mm) open end wrench to securely tighten the sensor cable nut onto one
end of the union.
the two screws.
Connect the coaxial cable at the meter body
1.Pull the sensor cable out of the bracket slightly and securely tighten the sensor cable
nut onto the union.
Note
Do not stretch the sensor cable over 1.5-in. (40 mm) beyond the top of the bracket. Damage to
the sensor may occur if the sensor cable is stressed.
2.Place the meter adapter into the top of the bracket and line up the screw holes.
3.Use a hex wrench to turn the three adapter screws counterclockwise (outward) to
engage the bracket.
4.Tighten the conduit adapter or cable gland into the
meter adapter.
5.6.6Coaxial cable at the electronics housing
Tro u bl esh o oti ng
Remove the coaxial cable from the electronics housing
1.Loosen the two housing screws from the housing adapter.
2.Remove the housing adapter from the housing.
3.Loosen and remove the coaxial cable nut from the base of the electronics housing.
4.Remove the coaxial cable ground connection from the housing base by loosening the
housing base screw that is connecting it to the housing base.
85
Section 5: Troubleshooting
Ground
Connection
Housing Adapter
Housing Adapter Screws
Electronics Housing
Coaxial
Cable Nut
Housing
Base Screw
Conduit Adapter
(optional - supplied by customer)
January 2013
Figure 5-11. Remote Electronics Exploded View
Reference Manual
00809-0100-4860, Rev BC
5.Loosen the conduit adapter (or cable gland) from the
housing adapter.
86
Tro u bl esh o oti ng
Reference Manual
00809-0100-4860, Rev BC
Attach the coaxial cable
1.Route the coaxial cable through the conduit (if you are
2.Place a conduit adapter over the end of the coaxial cable.
3.Remove the housing adapter from the electronics housing
4.Slide the housing adapter over the coaxial cable.
5.Remove one of the four housing base screws that is in closest proximity to the ground
6.Re-install the housing base screw by passing it through the ground connection.
7.Attach and securely tighten the coaxial cable nut to the connection on the electronics
8.Align the housing adapter with the housing base and attach with the two housing
Section 5: Troubleshooting
January 2013
using conduit).
(if attached).
connection.
housing.
adapter screws.
9.Tighten the conduit adapter to the housing adapter.
Tro u bl esh o oti ng
87
Section 5: Troubleshooting
January 2013
5.6.7Changing the housing orientation
The entire electronics housing may be rotated in 90 degree increments for easy viewing. Use the
following steps to change the housing orientation:
1.Loosen the screw on the access cover on the bracket (if present) and remove the cover.
Reference Manual
00809-0100-4860, Rev BC
2.Loosen the three housing rotation set screws at the base of the electronics housing with
5
a
/32-in. (4 mm) hex wrench by turning the screws clockwise (inward) until they clear
the bracket.
3.Slowly pull the electronics housing out of the bracket.
4.Unscrew the sensor cable from the housing with a
5
/16-in. open end wrench.
Note
Do not pull the housing more than 1.5-in. (40 mm) from the top of the bracket until the sensor
cable is disconnected. Damage to the sensor may occur if this sensor cable is stressed.
5.Rotate the housing to the desired orientation.
6.Hold it in this orientation while you screw the sensor cable onto the base of the
housing.
Note
Do not rotate the housing while the sensor cable is attached to the base of the housing. This will
stress the cable and may damage the sensor.
7.Place the electronics housing into the top of the bracket.
8.Use a hex wrench to turn the four housing rotation screws counterclockwise to engage
the bracket.
Replacement of the temperature sensor should only be necessary in the event of a failure. Use
the following procedure for replacement.
Note
Disconnect power before replacing temperature sensor.
1.Turn off power to Rosemount 8600D.
2.Remove temperature sensor from meter body by using a
to the procedure on page 81 to remove the bracket.
88
1
/2-in. open end wrench. Refer
Tro u bl esh o oti ng
Reference Manual
00809-0100-4860, Rev BC
Note
Use plant approved procedure for removing a temperature sensor from a thermowell.
3.Remove temperature sensor from electronics by using a 2.5 mm allen wrench to
4.Gently pull temperature sensor from electronics.
Note
This will expose the electronics to the atmosphere.
5.Insert new temperature sensor into electronics housing using care to align pin and cap
6.Tightening cap head screw with 2.5 mm allen wrench.
7.Slide bolt and ferrule assembly onto temperature sensor and hold into place.
Section 5: Troubleshooting
January 2013
remove cap head screw from electronics.
head screw to align connector pins.
8.Insert temperature sensor into hole in the top of meter body until it reaches the bottom
of the hole. Hold it in place and tighten bolt with
past finger tight to seat ferrule.
9.Put the bracket back on, attach the four bolts, and tighten.
10.Reapply power to Rosemount 8600D.
5.7Return of material
To expedite the return process, call the Rosemount North American Response Center at
800-654-RSMT (7768) toll-free number.
This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for product model and serial numbers, and will provide a Return Material
Authorization (RMA) number. The center will also ask for the name of the process material to
which the product was last exposed.
Caution
People who handle products exposed to a hazardous substance can avoid injury if they are
informed and understand the hazard. If the product being returned was exposed to a hazardous
substance as defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for
each hazardous substance identified must be included with the returned goods.
1
/2-in. open end wrench until 3/4 turns
Tro u bl esh o oti ng
The Rosemount North American Response Center will detail the additional information and
procedures necessary to return goods exposed to hazardous substances.
The following specifications are for the Rosemount 8600D except where noted.
A.2Functional specifications
Appendix A: Reference Data
January 2013
Process fluids
Liquid, gas, and steam applications. Fluids must be homogeneous and single-phase.
Line sizes
Flanged style
1, 11/2, 2, 3, 4, 6, and 8 inches
(DN 25, 40, 50, 80, 100, 150, and 200)
Pipe schedules
Process piping Schedules 10, 40, 80, and 160.
Note
The appropriate bore diameter of the process piping must be entered using the Field
Communicator or AMS Device Manager. Meters will be shipped from the factory at the Schedule
40 default value unless otherwise specified.
Measurable flow rates
Capable of processing signals from flow applications which meet the sizing requirements below.
To determine the appropriate flowmeter size for an application, process conditions must be
within the Reynolds number and velocity limitations for the desired line size provided in
Ta bl e A - 1, Ta b l e A- 2 , and Ta b le A - 3 .
Note
Consult your local sales representative to obtain a computer sizing program that describes in
greater detail how to specify the correct flowmeter size for an application.
Specifications and Reference Data
91
Appendix A: Reference Data
R
D
VD
cp
----------- -=
36/
54/
36/
54/
90,000/ or 25
134,000/ or 7.6
90,000/ or 250
134,000/ or 76
January 2013
Reference Manual
00809-0100-4860, Rev BC
The Reynolds number equation shown below combines the effects of density (), viscosity (
inside diameter (D), and flow velocity (V).
Table A-1. Minimum Measurable Meter Reynolds Numbers
Meter Sizes
(Inches / DN)
1 through 4/25 through
100
6 through 8/150 through
200
Table A-2. Minimum Measurable Meter Velocities
Reynolds Number
Limitations
5000 minimum
(1)
Meters per
Feet per Second
Liquids
Gases
The is the process fluid density at flowing
conditions in lb/ft
(1) Velocities are referenced to schedule 40 pipe.
3
for ft/s and kg/m3 for m/s
Table A-3. Maximum Measurable Meter Velocities
Second
(1)
(Use the smaller of the two values)
), pipe
cp
Feet per SecondMeters per Second
Liquids
Gases
The is the process fluid density at flowing
conditions in lb/ft
(1) Velocities are referenced to schedule 40 pipe.
3
for ft/s and kg/m3 for m/s
Process temperature limits
Standard
-58 to 482 °F (–50 to 250 °C)
Output signals
4–20 mA digital HART signal
Superimposed on 4–20 mA signal
Optional scalable pulse output
0 to 10000 Hz; transistor switch closure with adjustable scaling via HART communications;
capable of switching up to 30 Vdc, 120 mA maximum.
92
Specifications and Reference Data
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.