Emerson 7ATB User Manual

Page 1
Operator’s
7000 Series 7A T B
Automatic T ransfer &
Manual
G design 1000 through 4000 amp. sizes
DANGER is used in this manual to warn of high voltages capable of causin g shock, burns, or death.
WARNINGisusedinthismanualto warn of possible personal injury.
CAUTIONisusedinthismanualto warn of possible equipment damage.
Refer to the outline and wiring drawings provided with your 7000 Series ATB for all installation and connection details and accessories.
Refer to Group 5 Controller User’s Guide 381333–126 for ATS status display messages, time delays, pickup & dropout settings, and adjustments.
An experienced licensed electrician must install the 7ATB.
Rating Label
Each 7000 Series 7ATB contains a rating label to define the loads and fault circuit withstand/closing ratings. Refer to the label on the Transfer Switch for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
4000 amp. size
Nameplate
The Transfer Switch nameplate includes data for each specific 7000 Series ATB. Use the switch only within the limits shown on this nameplate. A typical Catalog Number is shown below with its elements explained:
TABLE OF CONTENTS
section-page INSTALLATION
Mounting 1-1.............................
Power Connections 1-2....................
Engine Starting & Auxiliary Circuits 1-2......
Functional Test 1-3, 1-4.....................
TESTING & SERVICE
Transfer Test 2-1..........................
Preventive Maintenance 2-1................
Disconnecting the Controller 2-1............
Manual Load Transfer 2-2..................
Trouble-Shooting 2-2......................
BYPASSING & ISOLATING
Bypassing the ATS 3-1....................
Isolating the ATS 3-2......................
Return to Service 3-3, 3-4...................
INDEX back cover.........................
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
381333–132 F
Page 2
Page 3
Catalog Number Identification
G7ATB C 3 4000 N 5 C
Typical 7000 Series ATB catalog no. for overlapping neutral, 3 pole, 4000 amp., 480 V, in Type 1 enclosure:
Status Lights
&
Engine
Control
Bypass
Handle
Neutral
A –solid
B – switching C – overlapping
blank – none
Phase Poles
2 –singleØ 3 –threeØ
Amperes Voltage Controller Enclosure
1000
1200
1600
2000
2600
3000
4000
A 115
B 120
C 208
D 220 E 230
F 240 G 277
H 380
J 400
K 415
L 440
M 460 N 480
P 550
Q 575
R 600
5 –standard 5X –if
accessories
ordered
C –type1
F –type3R
G –type4
L –type12
blank – open type
Transfer Contr ol
&Lights
Isolation
Handle
Group 5 Controller
Transfer Switch
G7ATB 4000 A with the lower doors open (transfer switch shown)
Page 4
Page 5
SECTION 1 INSTALLATION
The ASCO 7000 Series Automatic Transfer & Bypass–Isolation Switch (ATB) consi sts of an upper bypass–isolation switch, a lower transfer switch, a monitoring and transfer controller, and door–mounted controls. The ATB is factory wired and tested. Installation requires removal of the shipping skid then securing the enclosure to the supporting foundation.
Remove the Shipping Skid
Open the front lower door and remove the two front lag screws securing the enclosure to t he wood skid. Next remove the rear lower panel and remove the two rear lag screws securing the enclosure to the wood skid.
Supporting Foundation
The supporting foundation for the enclosure must be level and straight. Allow at least 35 inches in front of the enclosure for draw out of the Transfer Switch. Refer to the enclosure outline drawing included with the ATB for all mounting details i ncluding door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the appropriate enclosure outline drawing for specified cable entrance area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Remove Shipping Brackets / Angles
from the Transfer Switch
Open the lower front door(s). The Transfer Switch carriage is secured to the frame for shipment. R em ov e the three or four shipping brackets or L–angles (1 upper left, 1 upper right, 1 lower right, or 2 lower on 4000 A).
To prevent serious damage, remove 3 shipping angles from the transfer switch carriage. Do not turn the Isolation Handle until they are removed!
Mounting
Refer to the enclosure outline drawing furnished with this switch and mount the 7000 Series ATB according to the details and instructions shown on the drawing.
remove 3 or 4 shipping brackets ( L–angles)
Figure 1-1. On 1000–3000 A remove three shipping
L–angles.
remove 2 upper shipping brackets
remove 2 lower shipping brackets
Figure 1-2. 4000 A remove four shipping L–angles.
1 --- 1
Page 6
INSTALLATION (continued)
Bus Connections
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen­erator starting control in the OFF position. Make sure engine generator is not in operation.
Testing Power Conductors
Do not connect the power conductors to the ATB until they are tested. Installing power cables in conduit, cable troughs, and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected they should be tested to verify that they are not defective or have been damaged during installation.
Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the 7ATB switch.
Connecting Power Conductors
A Wiring Diagram is furnished with the ATB. All wiring must be made in accordance with the local codes. After the power cables have been tested, connect them to the appropriate terminal lugs on the Bypass Switch as shown on the wiring diagram provided with this ATB. Make sure that the lugs providedaresuitableforusewiththecablesbeing installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the ATB. Be careful when stripping insulation from conductors; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. Follow conductor manufacturer’s instructions when aluminum conductor is used. Apply joint compound to conductor, then carefully wipe away excess compound. Tighten the cable lugs to the torque specified on the rating label.
Be sure that the Normal and Emergency power connections are in proper phase rotation.
If bus connection is used, use SAE grade 5 hardware to connect bus to appropriate terminal p lates on bypass switching device. Wipe off bus surfaces before they are joined. If bus is dirty, gently clean surfaces with a non-flammable solvent. Avoid touching cleaned surfaces.
Do not breathe cleaning solvent vapors.
UseSAEgrade5hardwareandtightenthebolted joints to the torque specified in Table 2-1.
The reliability of the connection depends on how clean and how tight the joint is.
Table 2-1. Tightening torque values for bolted joints.
Bolt Diameter
(Grade 5 hardware)
in inches
5/16 12
3/8 20 1/2 50 5/8 95
Recommended
Tightening Torque
in foot pounds
Harnesses
All internal connections are made at the factory. The bypass switch, transfer switch, and control panel are joined together by an interconnecting wire harness. The disconnect plugs are already engaged on enclosed switches. For open–type switches, the plugs must be engaged after installation is completed. Align harness plugs with sockets in the control and push them together until they are secure.
Engine Starting Contacts
and Auxiliary Circuits
The engine control contact signal connections and auxiliary circuits are located on terminal block TB as shownontheWiring Diagram provided with the ATB. Connect the signal wires to the appropriate terminals.
1 --- 2
Page 7
INSTALLATION
(continued)
Tra n sf e r
Control
Retransfer
Delay
Bypass
observe these lights
Tra n sf e r Sw i t ch
Connected
To
Normal
GREEN
Normal Source
Accepted
GREEN
Tra n sf e r Sw i t ch
Connected
To
Emergency
RED
Emergency
Source
Accepted
RED
Figure 1-2. Standard controls and indicators.
Functional Test
Read all instructions on the Wiring Diagrams and labels affixed to the ATB. Note the control features that are provided and review their operation before proceeding.
After installing the ATB check the following:
– Bypass Handle should be in the NORMAL posit ion. – Isolation Handle should be in the CONN position.
– TS transfer switch Normal contacts should be CLOSED
(Emergency contacts should be OPEN)
If handles are not in correct positions, follow inst ruc­tions for Bypassing and Isolating the automatic transfer switch in Section 3. Do not force the handles. Electrical interlocks prevent a wrong sequence of operation.
1–VoltageChecks
First check nameplate on transfer switch; rated voltage mustbethesameasnormalandemergencylinevoltages.
Useextremecautionwhenusingameter to measure voltages. Do not touch power terminals; shock, burns, or death could result !
Tra ns f er
Tes t
HOLD F OR
(
15 SECO NDS
)
Close the normal source circuit breaker. The Transfer Switch Connected To Normal and the
1
Normal Source Accepted lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
2
entatthetransferswitchnormal source terminals.
Close the emergency source circuit breaker. (Start generator, if necessary.) The Transfer
3
Switch Connected To Normal & Emergency Source Accepted
lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres-
4
ent at the transfer switch emer­gency source terminals.*
Useaphaserotationmeterto check phase rotation of emer-
5
gency source; it must be the same
as the normal source.
C
B
A
Perform steps 1–6 at the right. Observe the status lights. See Figure 1–2.
Q Black square means light is on. S White square means light is off.
* If necessary, adjust voltage regulator on generator per the manufacturer’s recommendations. The ATB will respond only to rated voltage specified on the nameplate.
Now continue to 2 – Electrical Operation on next page.
1 --- 3
Shut down the engine–genera­tor , if applicable. The Emergen- cy Source Accepted light should go off. Then put the starting
6
control selector switch (on the generator set) in the automatic position. Close enclosure door.
Page 8
INSTALLATION (continued)
Tra n sf e r
Control
Retransfer
Delay
Bypass
observe these lights
Tra n sf e r Sw i t ch
Connected
To
Normal
GREEN
Normal Source
Accepted
GREEN
Tra n sf e r Sw i t ch
Connected
To
Emergency
RED
Emergency
Source
Accepted
RED
Figure 1-3. Standard controls and indicators.
2 – Electrical Operation
This procedure checks electrical operation of the ATS.
Be sure to close the enclosure door before proceeding to prevent personal injury in case of electrical system fault.
Transfer Test
The ATS should still be bypassed. Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started; put engine starting control in automa ti c position. The Tra nsfer Switch Connected to Normal light and the Normal Source Accepted light should be on.
1. Turn the Isolation Handle counterclockwise to the TEST position.
NOTE: Theenginegeneratormaybesignalled to start while turning the Isolation Handle. If emergency source is available, the ATS may operate to the emergency position. If it does, operate Retransfer Delay Bypass switch.
2. Perform steps 1–5 at right. Observe the status lights.
Q Black square means light is on. S White square means light is off.
3. Turn the Isolation Handle clockwise to the CONN (connected) position.
4. Push in the Bypass Handle and turn it counterclock­wise to the OPEN position.
Tra ns f er
Tes t
HOLD F OR
(
15 SECO NDS
)
operate
this switch
The Transfer Switch Connected to Normal and Normal Source
1
Accepted lights should be on.
Turn an d hol d Tra n sfe r Co ntro l switch clockwise to Transfer Test until the engine starts
2
and runs (within 15 sec.). The
Emergency Source Accepted
light should come on.
Transfer switch will operate to the Emergency position after Feature2Btimedelay.The
Transfer Switch Connected To
3
Emergency light should come on and Load Connected to Normal light goes off.
Transfer switch will operate back to Normal position after Feature3Atimedelay.Forim­mediate retransfer turn Tr a nsf er Control counterclockwise to
4
Retransfer Delay Bypass.The Transfer Switch Connected To Normal light should come on; Transfer Switch Connected to Emergency light should go off.
The engine–generator will stop after the Feature 2E time delay (unloaded running engine cool-
5
down). The Emergency Source Accepted light should go off.
This completes the Functional Test of the ATB.
1 --- 4
Page 9
SECTION 2 TESTING & SERVICE
TRANSFER TEST
Test the Automatic Transf er Switch portion of the 7000 Series ATB at least once a month. This procedure checks the electrical operation of the Transfer Switch and Controller. Put the engine–generator starting con­trol (at the engine–generator set) in automatic mode.
In the following test the generator will start, the load will be transferred to the Emergency source, then back to the Normal source. An interruption to the load will occur, unless the the Transfer Switch contacts are by­passed before the test. See pages 3–1 and 3–2 for by­passing & isolating instructions if no interruption of load is required.
Be sure to close the enclosure door before proceeding to prevent personal injury in case of electrical system fault.
Perform the five–step Electrical Operation – Transfer Tes t procedure on page 1–4.
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure high reliability and long life for the 7000 Series ATB. An annual preventive maintenance program is recom­mended.
ASCO Services, Inc. (ASI) is ASCO Power Technologies’ national service organization. ASI can be contacted at 1–800–800–2726 for informa­tion on preventive maintenance agreements.
Checklist for Yearly Inspection
REPLACEMENT PARTS
Replacement parts are available in kit form. When ordering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the t ransfer switch nameplate. For service call ASCO Services at 1–800–800–2726.
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps:
Bypass–Isolation Switch is energized! Do not touch isolation contact fingers; shock, burns, or death could result!
Disconnecting the Plugs
1. Bypass and Isolate the Automatic Transfer Switch.
2. Open the upper enclosure door.
3. Separate the two quick disconnect plugs by squeez­ing the lat ches. Do not pull on the harness wires.
Reconnecting the Plugs
1. The ATS should be still bypassed and isolated.
2. The two harness plugs and sockets are keyed. Carefully align the plugs with the sockets and press straight in until the latches click.
3. Close the enclosure doors.
4. F ollow Return to Service instructions on page 3–3.
Hazardous voltage capable of causing shock, burns, or death is used in this switch. Deenergize both Normal – Emergency power sources before performing inspections!
S Clean the A TB enclosure. Brush and vacuum
away any excessive dust accumulation. Remove anymoisturewithacleancloth.
S Check the transfer switch contacts
transfer switch barriers and check the condition of the contacts. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully.
S Maintain transfer switch lubrication.Ifswitchis
subjected to severe dust or abnormal operating conditions, renew factory lubrication on all move­ments and linkages. Relubricate solenoid operator if TS coil is replac e d . Don’t use oil; order lubrica- tion kit 75-100.
S Check all cable connections & retighten them.
.Remove
2 --- 1
Page 10
TESTING & SERVICE
TROUBLE-SHOOTING
(continued)
Note any optional accessories that may be furnishe d on the ATB and review their operation. Refer to any separate drawings and/or instructions that may be packed with the ATB.
Table 2-1. Trouble-Shooting Checks.
PROBLEM
Engine–generator set does not start when the Tra nsfer Control switch is turned and held
in Transfer Test position
or when normal source fails.
T ransfer switch does not transfer the load to the emergency source after the engine–generator set starts.
T ransfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released.
Engine–generator-set does not stop after load retransfer to the normal source.
Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature1Ctimedelayplus engine cranking and starting.
Wait for Feature 2B time delay to time out.
Wait for Feature 3A time delay to time out.
Wait for Feature 2E time delay to time out.
1
OPERATION
Hazardous voltage capable of causing shock, burns, or death is used in this switch. Do not touch the power or load terminals ofthebypassswitchortransferswitch!
CHECK IN NUMERICAL SEQUENCE
2
GEN-SET
Starting control must be in the automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts.
Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (57 Hz for a 60 Hz system.) *
Starting control must be in the automatic position.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals EA & EC (or EL1 & EL2 for 2 pole)*
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals NB & NC, NC & NA, & NA & NB (or NL1&NL2for2pole).
3
VOLTAGE
* These are factory settings.
Refer to Controller’s User’s Guide.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technolo­gies sales office or ASI: in the United States, call 1–800–800–2726. Furnish the Serial No., Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate.
MANUAL LOAD TRANSFER
MAINTENANCE HANDLE
This procedure manually transfers load to other source if the Transfer Switch or Controller are out of service.
Bypass and isolate the Transfer Switch before using the maintenance handle! See
Close enclosure doors to prevent personal injury in case of electrical system fault.
1. Be sure that the Bypass Handleis CLOSED on either Emergency or Normal (see page 3–1).
2. Be sure that the Isolation Handle is in the TEST or ISOLATE position (see page 3–2).
3. TurntheBypassHandlecounterclockwisetoOPEN the Bypass Switch. Then Bypass to the other source (see page 3–1).
pages 3–1 and 3–2. Remove the maintenance handle after using it and store it on the frame.
Tu rn counterclockwise to Emergency.
Turn cloc k wi s e to Normal.
Grasp handle firmly
slide hub onto shaft
insert handle into hole
2 --- 2
Page 11
SECTION 3 BYPASSING & ISOLATING
BYPAS SING THE ATS*
This procedure explains how to Bypass the closed automatic transfer switch contacts. Bypassing is required before the ATS can be tested or isolated. The Bypass Handle must be in the OPEN position (green indicator) and the Isolation Handle must be i n the CLOSED position (window). See Figures 3–1, 3–2, and 3–3.
Indicator shows:
green ATS is not
To By p as s No r m a l push in handle all the way & turn it clockwise.*
OPEN when the
O
bypassed.
Figure 3–1. Bypass Handle and position indicators.
To B y p a s s N o r m a l S o u r ce *
You can only bypass to the same source that the T ransfer Switch is connected. Solenoid interlock prevents incorrect operation.
1. Observe which Transfer Switch Connected To light is on (Normal or Emergency) on the door. This is the position of the automatic transfer switch.
2. Bypasstothesamesourceasconnectedto switch
as follows (select Normal or Emergency).
Indicator shows:
yellow when ATS is bypassed to Emergency
or
yellow ATS is bypassed to Normal Source.
To By p as s Em er g e n cy pull out han­dlealltheway&turnitclockwise.*
EMERGENCY CLOSED
O
NORMAL CLOSED when
O
transfer
To Bypass Emergency Source*
(Load connected to Normal Source)
The Transfer Switch Connected To Normal light is on
and Transfer Switch Conn ected To Emergency light is off.
Push in* the Bypass Handle all the way, then turn it clockwise until Bypass Switch Position shows CLOSED on NORMAL (yellow indicator). The red light Unit Not In Automatic will flash.
Push in
Bypass Switch
E
Bypass Handle
& turn it clockwise.
L
N
ATS
(Load connected to Emergency Source)
The Transfer Switch Connected To Emergency light is on
and Transfer Switch Connected To Normal light is off.
Pull out* the Bypass Handle all the way, then turn it clockwise until Bypass Switch Position shows CLOSED on EMERGENCY (yellow indicator). The red light Unit Not In Automatic will flash.
Pull out
Bypass Switch
E
Bypass Handle
& turn it clockwise.
L
N
ATS
Figure 3–2. Bypass to Normal.
The automatic transfer switch can now be put in the TEST or OPEN position. See ISOLATING on page 3–2.
*NOTE: When Accessory 66A (reversed Normal & Emergency connections) is specified,
the handle push–pull operation is reversed. Follow instructions on the door.
3 --- 1
Figure 3–3. Bypass to Emergency.
Page 12
BYPASSING & ISOLATING
ISOLATING THE ATS
Isolating is required before any service work can be performed on the automatic transfer switch (ATS). Refer to Figures 3–4, 3–5, 3–6, and 3–7.
1. Bypass the closed See BYPASSING on page 3–1.
Align position indicator. Do not leave thehandleinanintermediateposition.
2. Turn the Isolation Handle counterclockwise (approx. 16 turns, approx. 12 turns for 4000 A) until window shows TEST.TheATScanbetested now without load interruption (see page 2–1).
automatic transfer switch contacts.
Bypass Switch
E
(continued)
CONN
TEST
ISOLATE
counterclockwise – draws out transfer switch
Figure 3–6. Isolation Handle.
NOTE: In the TEST position the transfer switching device solenoid operator circuit is energized through secondary disconnects.
position window
unfold crank
Turn crank counter­clockwise
L until window shows TEST.
N
Automatic Transfer Switch
Figure 3–4. CONNECTED to TEST position.
3. Continue turning Isolation Handle counterclock-
wise (approx. 7 turns, approx. 8 turns for 4000 A) until the window shows ISOLATE.
Bypass Switch
E
Turn crank counter­clockwise
L until
window shows ISOLATE.
N
Automatic Transfer Switch
Figure 3–5. TEST to ISOLATE position.
4. Open the lower enclosure door(s). Pull out the
side rail carriage. On 4000 A extend two support legs; see Figure 3–7b. Then roll out the transfer switch. It can be safely inspected in this position. The transfer switch can also be removed for easier maintenance operations.
Hazardous voltage capable of causing electrical shock, burns, or death; do not touch any control circuit terminals.
Figure 3–7a. 1000–3000 A transfer sw itch
isolated and pulled out for inspection.
See page 2–2 for maintenance handle use. For 1000–3000 A lifting yoke kit 607064 is available to facilitate lifting by using an overhead crane or similar equipment. For 4000 A use lifting yoke 835745–001.
1000–3000 A switches weighs 350–450 lbs; use lifting yoke 607064. 4000 A switches weigh approx. 600 lb; use lifting y o ke 835745-- 001 or other device capable of lifting this weight to avoid personal injury or equipment damage.
To avoid personal injury and equipment damage on 4000 A switches, two support legs must be extended as shown in Figure 3–7b. Substantial initial force is required to pull out the transfer switch (there are detents on rails).
3 --- 2
Page 13
grasp two handles
BYPASSING & ISOLATING
(continued)
locking pin
with clevis pin
rail support
left support leg
adjust length to touch floor
Drawout procedure
1. Bypass and Isolate the ATS, then open both lower doors.
2. Pull out the rail support carriage all the way.
3. Remove left & right clevis and locking pins, drop two support legs, reinstall locking and clevis pins (to lock in place), and adjust both leg lengths to extend to the floor.
4. Stand directly in front of transfer switch. Grasp both handles, and pull straight out
(detentsontherailsrequirehighinitialforcetoovercomeresistance).
Figure 3–7b. 4000 amp transfer switch isolated and pulled out for inspection.
carriage
adjust length to touch floor
locking pin
with clevis pin
right support leg
To avoid personal injury and equipment damage on 4000 A switches, two support legs must be extended as shown in Figure 3–8. Substantial initial force is required to pull out the transfer switch (there are detents on rails).
The 4000 A transfer switch weighs 600 lb. Use lifting yoke 835745–001 or other device capable of lifting this weight to avoid personal injury or equipment damage.
3 --- 3
Page 14
BYPASSING & ISOLATING
RETURN TO SERVICE
(continued)
This procedure explains how to return the automatic transfer switch (ATS) to service after inspection and maintenance. Observe the Bypass Switch Position indicator and lights). Refer to Figures 3–7a, 3–7b, 3–8, 3–9, and 3–10.
1. Slide the transfer switch (ATS) into the enclosure (isolation contacts facing inward) until its crank pins engage the latch plates on both sides. On 4000 A substantial force is required to overcome detents on the rails. Next push in side rail carriage. On 4000 A first retract the two legs and lock them in place. See Figure 3–7b. Then close enclosure door.
Close the enclosure door to prevent personal injury in case of electrical system fault.
Align position indicator. Do not leave thehandleinanintermediateposition.
position
CONN
TEST
ISOLATE
window
Solenoid interlock prevents you from closing the isolation contacts until the ATS is in the same
position as the Bypass Switch.
3. Observe which Bypass Switch Position indicator is black (NORMAL or EMERGENCY)attheBypass Switch Handle. This indicates the source connected to the load.
4. Observe which Transfer Switch Connected To light is on (Normal or Emergency) on the door. This is the position of the Transfer Switch. If it is not in the same position as the Bypass Handle change the position of the Transfer Switch as follows:
To change the position of transfer switch
Operate to NORMAL OperatetoEMERGENCY
Turn Tra n sfe r Co n tro l switch to Retransfer
Delay Bypass.
Connected To Normal
light should come on.
* If Feature 2B time delay is used, there will be a delay
before transfer to Emergency.
NOTE: With Normal available, the automatic transfer switch will not stay in the emergency position unless Feature 3A time delay is used (at least 30 seconds).
Turn Tra n sfe r Co n tro l switch to Transfer Test (hold 15 seconds).*
Connected To Emergency
light should comes on.
unfold crank
clockwise – draws in the Transfer Switch
Figure 3–8. Isolation Handle.
2. Turn the Isolation Handle clockwise (approx. 7 turns, approx. 8 turns for 4000 A) until the window shows TEST. The ATS can be tested now without load interruption (see page 2–1).
Bypass Switch
E
Turn crank clockwise
L
until window shows TEST.
N
Do not close the isolation contacts unless the Transfer Switch (ATS) and Bypass Switch are in the same position!
5. When the transfer switch is i n the same the Bypass Switch handle, continue turning the Isolation Handle clockwise (approx. 16 turns, approx. 12 turns for 4000 A) until the window shows CONN (connected).
Bypass Switch
Turn crank clockwise until window shows CONN (connected).
ATS
position as
E
L
N
ATS
Figure 3–9. ISOLATE to TEST position.
Figure 3–10. TEST to CONNECTED position.
Now continue to the next page for instructions on how to return the Bypass Handle to the OPEN postition.
3 --- 4
Page 15
BYPASSING & ISOLATING
RETURN TO SERVICE continued*
(continued)
This procedure explains how to return the Bypass Switch Handle to the OPEN position. The Bypass Handle must be in the CLOSED position (yellow indicator on NORMAL or EMERGENCY)andthe Isolation Handle must be i n the TEST position (window). If the handles are not in these positions, refer to Return to Service on page 3–3. See Figures 3–11, 3–12, and 3–13.
Indicator shows:
green ATS is not
To un–Bypass Normal push in handle all the way & turn it counterclockwise.*
OPEN when the
O
bypassed.
Figure 3–11. Bypass Handle and position indicators.
You can only bypass to the same source that the ATS is connected. Solenoid interlock prevents incorrect operation.
1 Observe which Bypass Switch Position indicator is
yellow (NORMAL or EMERGENCY)attheBypass Switch Handle. This indicates the source connected to the load.
2 Un–Bypass to same source as the Bypass
Position
as follows (select Normal or Emergency).
Indicator shows:
yellow when ATS is bypassed to Emergency
or
yellow bypassed to Normal Source.
EMERGENCY CLOSED
O
NORMAL when ATS is
O
To un–Bypass Emergency pull out
handle all the way & turn it counterclockwise.*
Switch
To Un–Bypass Normal Source*
(Load connected to Normal Source)
The Transfer Switch Connected To Normal light is on
and Transfer Switch Conn ected To Emergency light is off.
Push in* the Bypass Handle then turn it counterclock­wise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.
Push in
Bypass Switch
E
Bypass Handle
& turn it counter-
L
clockwise.
N
ATS
To Un–Bypass Emergency Source*
(Load connected to Emergency Source)
The Transfer Switch Connected To Emergency light is on
and Transfer Switch Connected To Normal light is off.
Pull out* the Bypass Handle then turn it counterclock­wise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.
Pull out
Bypass Switch
E
Bypass Handle
& turn it counter-
L
clockwise.
N
ATS
Figure 3–12. Un–Bypass Normal.
The Automatic Transfer & Bypass–Isolation Switch should be left in this position.
*NOTE: When Accessory 66A (reversed Normal & Emergency connections) is specified,
the handle push–pull operation is reversed. Follow instructions on the door.
3 --- 5
Figure 3–13. Un–Bypass Emergency.
Page 16
INDEX
A
auxiliary circuits, 1–2
B
bus connections, 1–2
bypassing the ATS, 3–1
C
catalog number, inside cover
cleaning, 2–1
connections
power, 1–2
controller
disconnecting, 2–1 see Controller User’s Guide
D
drawout, transfer switch, 3–2, 3–3
E
electrical operation, 1–4
Emergency Source Accepted light,
1–3
Engine Control selector switch
Auto position, 2–1
engine starting contacts, 1–2
F
foundation, 1–1
frequency, generator, 2–2
functional test, 1–3, 1–4
H
harness, 1–2
disconnect plugs, 2–1
HELP
customercare@asco.com 800–800–ASCO
I
inspection, 3–1
installation, 1–1
isolating the ATS, 3–2
L
lights, 1–3, 1–4
load connected to emergency, 1–4
load connected to normal, 1–4
lubrication, 2–1
M
maintenance, preventive, 2–1
maintenance handle, 2–2
warning, 2–2
manual load transfer, 2–2
warning, 2–2
N
nameplate, cover
Normal Source Accepted light, 1–3
O
operation
electrical, 1–4 manual, 2–2
warning, 2–2
P
parts, 2–1
phase rotation check, 1–3
preventive maintenance, 2–1
problem, 2–2
R
rating label, cover
removal of shipping angles, 1–1
removal of shipping skid, 1–1
replacement parts, 2–1
return to service, 3–4, 3–5
S
service
ASCOServices,Inc.(ASI),2–1
settings
see Controller User’s Guide
shipping angles, 1–1
warning, 1–1
shipping skid, 1–1
support legs on 4000 A, 3–3
T
test, functional, 1–3, 1–4
testing power cables, 1–2
time delays, 2–1
see Controller User’s Guide
Transfer Control selector switch
Retransfer Delay Bypass, 1–4 Transfer Test, 1–4
Transfer Switch Connected To
Emergency light, 1–4
Transfer Switch Connected To
Normal light, 1–4
transfer test, 1–3, 2–1
transfer to emergency, 1–4, 2–1
transfer to normal, 1–4, 2–1
troubleshooting, 2–2
V
voltage checks, 1–3
voltage, pickup and dropout settings
see Controller User’s Guide
Printed in U.S.A.
E ASCO Power Technologies, L.P. 2009
Loading...