Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Issue AL, July 24, 2006
MONITORING SYSTEM
SPEC. NOS.:586505000
586505500
MODEL:LMS1000
Section 5847
User Instructions
User Instructions
Firmware Version 6.3
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
The Emerson logo is a trademark and
service mark of Emerson Electric Co.
Lorain® is a registered trademark of Emerson
Network Power, Energy Systems, North America, Inc.
Vortex® is a registered trademark of Emerson
Network Power, Energy Systems, North America, Inc.
The products covered by this instruction manual are manufactured and/or
sold by Emerson Network Power, Energy Systems, North America, Inc.
If we can be of any further assistance to you,
please call one of our sales representatives
at (440) 288-1122.
For parts, service, depot repair, technical assistance, or training, call toll free:
one of the numbers listed on the Service Information Sheet (Section 4154).
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
STATIC WARNING
The printed circuit cards used in this equipment contain static sensitive components. The warnings listed below
must be observed to prevent damage to these components. Disregarding any of these warnings may result in
personal injury or damage to the equipment.
1. Do not insert or remove printed circuit cards with power applied. Wait at least 5 minutes after power is
turned off (or until power supplies have discharged to zero volts) before removing any circuit card.
2. Before touching any static sensitive component or printed circuit card containing such a component,
discharge all static electricity from yourself by wearing a wrist strap grounded through a one megohm
resistor. Some wrist straps, such as Emerson Network Power P/N 631810600, have a built-in one
megohm resistor; no external resistor is necessary. Read and follow wrist strap manufacturer’s
instructions outlining use of a specific wrist strap.
3. Do not touch the traces or components on a printed circuit card containing static sensitive components.
Handle the printed circuit card only by the edges that do not have connector pads.
4. After removing a printed circuit card containing a static sensitive component, place the printed circuit card
only on conductive or anti-static material such as conductive foam, conductive plastic, or aluminum foil.
Do not use ordinary Styrofoam or ordinary plastic.
5. Store and ship static sensitive devices or printed circuit cards containing such components only in static
shielding containers.
6. If necessary to repair a printed circuit card containing a static sensitive component, wear an appropriately
grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded
test equipment.
Static WarningPage 1 of 2
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
This Page Left Intentionally Blank
Page 2 of 2 Static Warning
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
FCC INFORMATION
The modem circuit card of LMS1000 (if installed) has been granted a registration number by the Federal
Communications Commission, under Part 68 rules and regulations for direct connection to the telephone lines. In
order to comply with these FCC rules, the following instructions must be carefully read and applicable portions
followed completely:
a) Direct connection to the telephone lines may be made only through the standard plug- ended cord
furnished to the utility-installed jack. No connection may be made to party or coin phone lines. Prior to
connecting the device to the telephone lines, you must:
b) Call your telephone company and inform them you have an FCC registered device you desire to connect
to their telephone lines. Give them the number(s) of the line(s) to be used, the make and model of the
device, the FCC registration number and ringer equivalence. This information will be found on the device
or enclosed with instructions as well as the jack suitable for your device.
c) After the telephone company has been advised of the above you may connect your device if the jack is
available, or after the telephone company has made the installation.
d) Repairs may be made only by the manufacturer or his authorized service agency. Unauthorized repairs
void registration and warranty. Contact seller or manufacturer for details of permissible user performed
routine repairs, and where and how to have other than routine repairs.
e) If, through abnormal circumstances, harm to the telephone lines is caused, it should be unplugged until it
can be determined if your device or the telephone line is the source. If your device is the source, it should
not be reconnected until necessary repairs are effected.
f) Should the telephone company notify you that your device is causing harm, the device should be
unplugged. The telephone company will, where practicable, notify you, that temporary discontinuance of
service may be required. However, where prior notice is not practicable, the telephone company may
temporarily discontinue service, if such action is reasonably necessary, in such cases the telephone
company must (A) Promptly notify you of such temporary discontinuance, (B) Afford you the opportunity
to correct the condition and (C) Inform you of your rights to bring a complaint to the FCC under their rules.
g) The telephone company may make changes in its communications facilities, equipment, operations or
procedures, where such action is reasonably required in the operation of its business and is not
inconsistent with FCC rules. If such changes can be reasonably expected to render any customer’s
devices incompatible with telephone company facilities, or require modification or alteration, or otherwise
materially affect its performance, written notification must be given to the user, to allow uninterrupted
service.
The following information is provided here and on a label attached to the outside of the system cabinet when
equipped with a modem circuit card.
MODEM JACK RINGER EQUIVALENCE FCC REGISTRATION NUMBER
56K bps RJ-11 0.2A B46USA-22429-MM-E
FCC InformationPage 1 of 2
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
This Page Left Intentionally Blank
Page 2 of 2 FCC Information
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Table of Contents............................................................................................................................................. 1-1
What is LMS1000............................................................................................................................................. 1-1
Table of Contents............................................................................................................................................. 2-1
Components of LMS.................................................................................................................................. 2-3
Local Controls and Indicators .......................................................................................................................... 2-6
Location and Identification......................................................................................................................... 2-6
LMS CPU Circuit Cards ............................................................................................................................. 2-6
Accessing the System through a Local or Remote Terminal........................................................................... 2-8
Passwords and Access Levels .................................................................................................................. 2-8
Local Terminal Access .............................................................................................................................. 2-9
Using a Terminal........................................................................................................................................ 2-9
Logging On To the System...................................................................................................................... 2-11
Logging Off of the System ....................................................................................................................... 2-12
Accessing LMS1000 via TELNET and TFTP................................................................................................. 2-13
Accessing LMS1000 via SNMP (if SNMP Software Option is installed)........................................................ 2-13
Management Information Base (MIB) User Interface.............................................................................. 2-13
Using the TL1/X.25 Port (if TL1/X.25 Software Option is installed) ............................................................... 2-14
Using the TL1 Port (if TL1 [over Ethernet] Software Option is installed) ....................................................... 2-14
Using the Gateway Port (if Gateway Software Option is installed)................................................................ 2-15
Using Programmable Commands.................................................................................................................. 2-17
Using the Alarm Cutoff Feature ..................................................................................................................... 2-18
Forcing On Relays or LED's........................................................................................................................... 2-18
Acknowledging System Alarms...................................................................................................................... 2-19
Getting Analog and Function Channel Statistics .................................................................................
Using the Scan Feature ................................................................................................................................. 2-19
Using the Rate Feature (Analog Channel Maximum Load Percentages Report).......................................... 2-20
Viewing and Clearing the Alarm Log.............................................................................................................. 2-20
.......... 2-19
Table of Contents Page i
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Viewing and Clearing the Event Log.............................................................................................................. 2-22
Using Status Pages........................................................................................................................................ 2-27
Using Information Pages................................................................................................................................ 2-28
Using the Mail Service ................................................................................................................................... 2-28
Methods of Obtaining Specific Information .................................................................................................... 2-29
Downloading and Uploading the Configuration.............................................................................................. 2-30
Downloading and Uploading Using XMODEM ........................................................................................ 2-30
Downloading and Uploading Using TFTP ............................................................................................... 2-32
Accessing a Vortex Power System (VPS) ..................................................................................................... 2-33
Accessing an LPS Power System.................................................................................................................. 2-37
Using the Power Metering Software Option................................................................................................... 2-45
What is Power Metering? ........................................................................................................................ 2-45
Setting Up Power Metering...................................................................................................................... 2-45
Using Power Metering ............................................................................................................................. 2-46
Determining if the Power Metering Option is Installed ............................................................................ 2-48
What Do I Need, How Do I Order? .......................................................................................................... 2-48
Using the WEB Interface Software Option..................................................................................................... 2-49
What does the LMS WEB Interface Do for Me ?..................................................................................... 2-49
Setting Up the LMS WEB Interface ......................................................................................................... 2-49
Using the LMS WEB Interface................................................................................................................. 2-50
What Do I Need, How Do I Order? .......................................................................................................... 2-51
Table of Contents............................................................................................................................................. 3-1
Overview of the Command Set ........................................................................................................................ 3-8
Command Conventions and Options....................................................................................................... 3-22
Page ii Table of Contents
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
CLASS ..................................................................................................................................................... 3-46
CLR MAIL ................................................................................................................................................ 3-52
CLR POWER ........................................................................................................................................... 3-53
CLR PROGRAM ...................................................................................................................................... 3-54
COM ........................................................................................................................................................ 3-58
DAC DEL ................................................................................................................................................. 3-70
DAC SET ................................................................................................................................................. 3-72
DAC SET LOCK OFF .............................................................................................................................. 3-73
DAC SET LOCK ON ................................................................................................................................ 3-74
DAC STATUS .......................................................................................................................................... 3-75
DATE ....................................................................................................................................................... 3-76
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
HELP ....................................................................................................................................................... 3-84
HELP VORTEX........................................................................................................................................ 3-91
INFO ........................................................................................................................................................ 3-93
MAIL ........................................................................................................................................................ 3-98
MENU ...................................................................................................................................................... 3-99
POWER ................................................................................................................................................. 3-121
PROGRAM ............................................................................................................................................ 3-142
SET ACO ............................................................................................................................................... 3-153
SET AID................................................................................................................................................. 3-154
SET ANSWER ....................................................................................................................................... 3-156
SET CHANNELS ................................................................................................................................... 3-157
SET CLASS ........................................................................................................................................... 3-158
SET CMD............................................................................................................................................... 3-159
SET COM .............................................................................................................................................. 3-161
SET DATE ............................................................................................................................................. 3-162
SET DEFAULTS .................................................................................................................................... 3-163
SET EFF ................................................................................................................................................ 3-165
SET EMAIL ............................................................................................................................................ 3-166
SET GATEWAY..................................................................................................................................... 3-167
SET INFO .............................................................................................................................................. 3-168
Page iv Table of Contents
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
SET LED................................................................................................................................................ 3-169
SET LIMITS ........................................................................................................................................... 3-170
SET LPS ................................................................................................................................................ 3-174
SET LPS CANIO.................................................................................................................................... 3-176
SET LPS MESSAGE CANIO_BD.......................................................................................................... 3-178
SET LPS MESSAGE DISTRIBUTION................................................................................................... 3-179
SET LPS MESSAGE MCA .................................................................................................................... 3-180
SET LPS MESSAGE PCU .................................................................................................................... 3-181
SET LPS MESSAGE RELAY ................................................................................................................ 3-182
SET LPS MESSAGE ROUTER............................................................................................................. 3-183
SET LPS PASSWORD.......................................................................................................................... 3-184
SET LPS PCU ....................................................................................................................................... 3-185
SET LPS SYSTEM BATONDISCH .......................................................................................................3-186
SET LPS SYSTEM CURLIMIT .............................................................................................................. 3-187
SET LPS SYSTEM EQMULTIPLIER.....................................................................................................3-188
SET LPS SYSTEM FLTVOLT ............................................................................................................... 3-189
SET LPS SYSTEM HI1TEMPALM ........................................................................................................ 3-190
SET LPS SYSTEM HI2TEMPALM ........................................................................................................ 3-191
SET LPS SYSTEM HIVLTALM1 ........................................................................................................... 3-192
SET LPS SYSTEM HIVLTALM2 ........................................................................................................... 3-193
SET LPS SYSTEM HVS........................................................................................................................ 3-194
SET LPS SYSTEM LOADACURRENT ................................................................................................. 3-195
SET LPS SYSTEM LOADBCURRENT ................................................................................................. 3-196
SET LPS SYSTEM LOADCURRENT.................................................................................................... 3-197
SET LPS SYSTEM LOW1TEMPALM ................................................................................................... 3-198
SET LPS SYSTEM LOW2TEMPALM ................................................................................................... 3-199
SET LPS SYSTEM NAGTIMER ............................................................................................................ 3-200
SET LPS SYSTEM RLYOFFTEST........................................................................................................ 3-201
SET LPS SYSTEM RLYONTEST ......................................................................................................... 3-202
SET LPS SYSTEM RLYTSTTIME......................................................................................................... 3-203
SET LPS SYSTEM TEMPCOMPMAX .................................................................................................. 3-204
SET LPS SYSTEM TEMPCOMPMIN.................................................................................................... 3-205
SET LPS SYSTEM TEMPSLOPE ......................................................................................................... 3-206
SET LPS SYSTEM TSTEQMODE ........................................................................................................3-207
SET LPS SYSTEM TSTEQTIME .......................................................................................................... 3-208
SET LPS SYSTEM TSTEQVOLT.......................................................................................................
... 3-209
SET LPS SYSTEM UPDATEINV .......................................................................................................... 3-210
SET LPS SYSTEM USECELSIUS ........................................................................................................ 3-211
SET LPS SYSTEM USEFAHRENHEIT ................................................................................................ 3-212
SET LPS SYSTEM VERYLOWVOLT.................................................................................................... 3-213
SET MAIL .............................................................................................................................................. 3-214
SET MODE ............................................................................................................................................ 3-215
SET PERIODS....................................................................................................................................... 3-218
SET PHONE .......................................................................................................................................... 3-219
Table of Contents Page v
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
SET PROGRAM .................................................................................................................................... 3-221
SET REPORT........................................................................................................................................ 3-222
SET RLY................................................................................................................................................ 3-223
SET SEQUENCE................................................................................................................................... 3-224
SET STATUS......................................................................................................................................... 3-226
SET SYSTEM ........................................................................................................................................ 3-228
SET TIME .............................................................................................................................................. 3-233
SET TIMEOUT....................................................................................................................................... 3-234
SET UNIT .............................................................................................................................................. 3-235
SET USERS .......................................................................................................................................... 3-236
SET VI ................................................................................................................................................... 3-239
SET VORTEX ........................................................................................................................................ 3-240
SET VORTEX INTERFACE .................................................................................................................. 3-242
SET VORTEX LVD DISCONNECT .......................................................................................................3-243
SET VORTEX LVD RECONNECT ........................................................................................................3-244
SET VORTEX MESSAGE MCA ............................................................................................................ 3-245
SET VORTEX MESSAGE PCU ............................................................................................................ 3-246
SET VORTEX PASSWORD.................................................................................................................. 3-247
SET VORTEX PCU ............................................................................................................................... 3-248
SET VORTEX SUBSYSTEM CALVOLT ............................................................................................... 3-249
SET VORTEX SUBSYSTEM FACTORYCAL ....................................................................................... 3-250
SET VORTEX SUBSYSTEM HIVALM .................................................................................................. 3-251
SET VORTEX SUBSYSTEM LVALM.................................................................................................... 3-252
SET VORTEX SUBSYSTEM OVRCURRENT ...................................................................................... 3-253
SET VORTEX SYSTEM 25APLACES .................................................................................................. 3-254
SET VORTEX SYSTEM 50APLACES .................................................................................................. 3-255
SET VORTEX SYSTEM 100APLACES ................................................................................................ 3-256
SET VORTEX SYSTEM 200APLACES ................................................................................................ 3-257
SET VORTEX SYSTEM 50%BATONDISCH ........................................................................................ 3-258
SET VORTEX SYSTEM BATONDISCH ............................................................................................... 3-259
SET VORTEX SYSTEM CALVOLT.......................................................................................................3-260
SET VORTEX SYSTEM CURLIMIT ......................................................................................................3-261
SET VORTEX SYSTEM FACTORYCAL............................................................................................... 3-262
SET VORTEX SYSTEM FLTVOLT .......................................................................................................3-263
SET VORTEX SYSTEM HIVLTALM1 ................................................................................................... 3-264
SET VORTEX SYSTEM HIVLTALM2 ................................................................................................... 3-265
SET VORTEX SYSTEM HVS................................................................................................................ 3-266
SET VORTEX SYSTEM INVENTORY .................................................................................................. 3-267
SET VORTEX SYSTEM MODE ............................................................................................................ 3-268
SET VORTEX SYSTEM NAGTIMER .................................................................................................... 3-269
SET VORTEX SYSTEM OVRCURRENT ............................................................................................. 3-270
SET VORTEX SYSTEM TEMPCOMP .................................................................................................. 3-271
SET VORTEX SYSTEM TSTEQVOLT ................................................................................................. 3-272
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
TIME ...................................................................................................................................................... 3-275
UNIT ...................................................................................................................................................... 3-277
VI ........................................................................................................................................................... 3-283
IP Networking Commands (in alphabetical order) ....................................................................................... 3-285
Command Conventions and Options..................................................................................................... 3-287
IP ........................................................................................................................................................... 3-288
IP ADD................................................................................................................................................... 3-289
IP ADDRESS ......................................................................................................................................... 3-290
IP DELETE ............................................................................................................................................ 3-291
IP GATEWAY ........................................................................................................................................ 3-292
IP NETMASK ......................................................................................................................................... 3-293
SNMP Commands (in alphabetical order) ................................................................................................... 3-295
SNMP GET ............................................................................................................................................ 3-299
SNMP OFF ............................................................................................................................................ 3-300
SNMP ON .............................................................................................................................................. 3-301
SNMP SET ............................................................................................................................................ 3-302
TRAPS ON ............................................................................................................................................ 3-308
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Table of Contents............................................................................................................................................. 4-1
Observe the Following Admonishment ............................................................................................................ 4-1
Replacing the CPU Memory Backup Battery (586505000/586505500 Main Cabinet or 582140000
Primary Bay Only) ............................................................................................................................................ 4-2
Adding an Input/Output (I/0) Circuit Card......................................................................................................... 4-5
Adding a Modem Circuit Card.......................................................................................................................... 4-5
Upgrading the Firmware................................................................................................................................... 4-6
CHAPTER 5 TROUBLESHOOTING AND REPAIRING LMS1000........................................ 5-1
Table of Contents............................................................................................................................................. 5-1
Observe the Following Admonishments .......................................................................................................... 5-1
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
APPENDIX (a record of the changes made to this document)
Table of Contents Page ix
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
This Page Left Intentionally Blank
Page x Table of Contents
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
This document (Section 5847) provides User Instructions for Monitoring System Model
LMS1000, Spec. Nos. 586505000 and 586505500. These instructions also provide
procedures for the integrated LMS of a Spec. No. 582140000 LPS Power System.
For Installation Instructions, refer to Section 5879 located in the separate INSTALLATION
MANUAL. Installation instructions are also provided on the CD (Electronic
Documentation Package) furnished with your system.
WHAT IS LMS1000
• LMS1000 is a programmable monitoring, controlling, and data acquisition system
designed for use in telecommunications power sites.
• LMS1000 can be equipped to monitor analog, binary, and temperature inputs.
• LMS1000 collects data on the monitored inputs. The data collected is used for alarm
processing and reporting, and to provide statistics.
• LMS1000 is capable of reporting alarm conditions to a remote terminal, pager, or
Email address. For remote terminal or pager notification, LMS1000 must be
equipped with an optional modem. Two types of alarm reporting mechanisms are
provided, System Alarm Reporting and Individual User Alarm Reporting.
• LMS1000 is capable of reporting alarm conditions via SNMP traps over Ethernet
when the SNMP option is ordered, or via TL1 (over Ethernet) when the 'TL1 over
Ethernet' option is ordered. TL1 is also available via a serial connection in 'direct
mode'.
• LMS1000 provides programmable LED's to allow local indication of alarm conditions
or occurrences. For remote indication, LMS1000 can be equipped with
programmable relays. Relays can also be used to control other equipment.
®
• LMS1000 easily interfaces with the MCA of a Vortex
Power System. This interface allows an LMS1000 user to remotely monitor, adjust,
and control the VPS or LPS via LMS1000, plus easily use the features of LMS1000
Power System (VPS) or LPS
Chapter 1. Introduction Page 1-1
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
with the VPS or LPS. Separate analog, binary, and relay circuit cards do not have to
be supplied for this interface. In a VPS, one simple cable connection between the
LMS1000 and VPS completes the interconnections required. The LMS is factory
integrated in an LPS Power System. Analog, binary, relay, and temperature circuit
cards may be provided to monitor equipment external to the VPS or LPS.
Note that Spec. No. 582140000 LPS Power System does not use the LMS
Cabinets. The LMS is factory integrated into the LPS Power System. LMS I/O
circuit card mounting positions are provided inside a 582140000 LPS Power
System.
• Available software options include…
WEB Interface
Power Metering
Energy Management
Rectifier/PCU Sequencing
TL1/X.25
SNMP
TL1 (over Ethernet)
Gateway Port
Note: The LMS Energy Management and Sequencing features are not for use in an
LPS Power System.
• Available specialty interfaces include…
Door Access Controller Interface
External GPS Modem Interface
AC Analyzer Interface
• Refer to SAG586505000/SAG586505500 (System Application Guide) for additional
information. The SAG can be accessed via the CD (Electronic Documentation
Package) furnished with your system.
LMS1000 CONSISTS OF...
• a Main Cabinet which holds up to ten input/output circuit cards, in a cabinet size that
occupies two 19" or 23" relay rack spaces. For system expansion and/or to monitor
points at other locations, Supplemental (Expansion) Cabinets are available. Each
Expansion Cabinet holds up to ten input/output circuit cards, in a cabinet size that
occupies two 19" or 23" relay rack spaces. Also available are Expansion Assemblies
which provide an input circuit card equipped with a fixed number of analog and binary
input points in a sheetmetal housing. These assemblies can be mounted inside
customer equipment. The Main Cabinet, Expansion Cabinets, and Expansion
Assemblies are interconnected via the LMS network.
• a CPU circuit card, optional modem circuit card, and any combination of optional
analog, binary, relay, and temperature input/output (I/O) circuit cards. Analog, binary,
and temperature circuit cards monitor a variety of inputs. The relay circuit card
provides Form-C relay contacts for connection to external alarms and control circuits.
The CPU circuit card also contains programmable LED's for local indication of alarms
or occurrences.
Page 1-2 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
• communications ports: Local Terminal Port, Remote (Modem) Terminal Port,
VPS/LPS Ports, optional TL1 port, and Ethernet Port (for Telnet access, optional
WEB access, optional SNMP access, optional TL1 access, and Email alarm
reporting). Additional OEM ports are provided. The functions of the OEM ports are
determined by the firmware. This allows the function to be manufacturer
programmable for specific applications. A local front panel display option is also
available.
• Firmware, which interfaces to the hardware and provides monitoring, alarm
processing, alarm reporting, and controlling functions. Alarm processing includes
statistics, status, and diagnostic information.
• Remote System Diagnostics.
Memory Test
Verify Integrity of Application Code
Verify Integrity of I/O Subsystem Communications
Check Status of I/O Cards
Verify Integrity of Communications and Operations
• CPU Firmware can easily be upgraded by an Emerson Network Power service facility
via a local or remote terminal interface.
• System configuration can easily be downloaded from LMS1000 to a PC (locally or
remotely), and uploaded from a PC to LMS1000 (locally or remotely).
• Simplified installation via integration of distributed monitoring I/O hardware.
• Incremental expandability.
• Extensive self diagnostics.
Chapter 1. Introduction Page 1-3
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
See Lists 60, 61, 79, 84, 85, 86, and 88 descriptions in SAG586505000/SAG586505500.
Figure 1-1
Block Diagram (586505000/586505500 LMS Cabinet)
(Note that Spec. No. 582140000 LPS Power System does not use the
LMS Cabinets. The LMS is factory integrated into the LPS Power System.)
Page 1-4 Chapter 1. Introduction
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Header Information ................................................................................................. 2-12
Logging Off of the System ...................................................................................... 2-12
Accessing LMS1000 via TELNET and TFTP ................................................................ 2-13
Accessing LMS1000 via SNMP (if SNMP Software Option is installed) ....................... 2-13
Management Information Base (MIB) User Interface ............................................. 2-13
Using the TL1/X.25 Port (if TL1/X.25 Software Option is installed) .............................. 2-14
Using the TL1 Port (if TL1 [over Ethernet] Software Option is installed) ...................... 2-14
Using the Gateway Port (if Gateway Software Option is installed) ............................... 2-15
Using Programmable Commands ................................................................................. 2-17
Using the Alarm Cutoff Feature..................................................................................... 2-18
Forcing On Relays or LED's .......................................................................................... 2-18
Acknowledging System Alarms ..................................................................................... 2-19
Getting Analog and Function Channel Statistics........................................................... 2-19
Using the Scan Feature................................................................................................. 2-19
Using the Rate Feature (Analog Channel Maximum Load Percentages Report) ......... 2-20
Viewing and Clearing the Alarm Log ............................................................................. 2-20
Viewing and Clearing the Event Log ............................................................................. 2-22
Using Status Pages ....................................................................................................... 2-27
Using Information Pages ............................................................................................... 2-28
Using the Mail Service................................................................................................... 2-28
Methods of Obtaining Specific Information.................................................................... 2-29
Downloading and Uploading the Configuration............................................................. 2-30
Downloading and Uploading Using XMODEM ....................................................... 2-30
Downloading and Uploading Using TFTP............................................................... 2-32
Chapter 2. Operating LMS1000 Page 2-1
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Accessing a Vortex Power System (VPS)..................................................................... 2-33
Accessing an LPS Power System ................................................................................. 2-37
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
LMS DESCRIPTION
This section describes the hardware components, but most importantly, how the channel
numbering scheme works inside the LMS -- how discrete I/O points, Expansion Nodes,
and MCA information are mapped to LMS channels.
Components of LMS
The LMS is a Monitoring System with Power System controlling capabilities. The
components of the LMS can easily be networked together to provide a multitude of
monitoring and controlling configurations.
The LMS consists of a Main Cabinet which houses the primary CPU circuit card, plus
provides mounting slots for optional input/output (I/O) circuit cards. The I/O cards can be
furnished to provide LMS I/O points for connection outside of an Emerson Network Power
Power System.
An optional LMS Expansion Cabinet which houses an expansion CPU circuit card is
also available to allow for additional monitoring points, plus the Expansion Cabinet can
be placed away from the Power System for extended monitoring applications. The
Expansion Cabinet has the same physical footprint as the Main Cabinet, with the same
number of slots for I/O cards.
Note that Spec. No. 582140000 LPS Power System does not use the LMS
Cabinets. The LMS is factory integrated into the LPS Power System.
In a 582140000 LPS Power System, the primary LMS CPU circuit card is housed
in the Primary Bay. The expansion LMS CPU circuit cards are housed in the
Secondary Bays. Both the Primary and Secondary Bays provide mounting
slots for the optional LMS I/O circuit cards.
The LMS easily interfaces with the MCA (Meter-Control-Alarm) Assembly of a Emerson
Network Power VPS and LPS Power System. There is no need for separate LMS I/O
circuit cards for this interface. All LMS monitoring and controlling capabilities for the
MCA Interface are built into the LMS primary CPU circuit card.
An LMS Expansion Assembly has been designed which is factory integrated into
designated VPS Power Systems. This integration allows the Expansion Assembly to be
built into the VPS Power System, thus eliminating the need for you to 'hard wire' the
Power System's distribution shunts and FA/CBA leads to the LMS. Simple LMS network
connections are all that is required. The Expansion Assembly is also available for
integration into customer equipment.
Note that the LMS Monitoring System can consist of multiple Expansion Cabinets and
Expansion Assemblies to suit your needs.
LMS Channel Numbering Scheme
Inputs/Outputs (I/O) and Channels
The LMS provides analog and binary input monitoring points, and extended relay
contact output points. In addition, local front panel programmable LEDs are provided.
Chapter 2. Operating LMS1000 Page 2-3
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Each input and output point is directly associated with a channel. Thus there are LMS
analog, binary, relay, and LED channels.
In the LMS, you can combine two or more analog inputs into one function channel, and
advance software options provide energy management channels. This adds function
channels and energy management channels to the list of channel types in the LMS.
Nodes
In the LMS system; the 586505000/586505500 Main Cabinet or 582140000 Primary Bay,
the 586505000/586505500 Expansion Cabinets or 582140000 Secondary Bays, the
586505000/586505500 Expansion Assemblies, and the MCA Interface are referred to as
nodes. A node is a grouping of I/O's in a common assembly, cabinet, or bay.
Putting it Together, the LMS Channel Numbering Scheme
LMS channels are identified through a type designation (A = analog, B = binary,
R = relay, L = LED, F = function, and E = energy management), a Node Number (I/O
grouping) prefix, and an input/output number. Remember, a particular channel’s type
designation and input/output number is identical to that of the input or output associated
to it.
• Installed optional LMS I/O circuit cards in the 586505000/586505500 Main Cabinet or
582140000 Primary Bay and each 586505000/586505500 Expansion Cabinet or
582140000 Secondary Bay are automatically detected by LMS firmware. Inputs and
outputs are automatically assigned consecutive numbers (per cabinet or bay) for
each type detected, starting with the circuit card of that type installed in the left most
position (as viewed from the front). Types are A for analog, B for Binary, and R for
relay. Temperature inputs are mapped to analog channels.
The Node Number is a fixed number for the 586505000/586505500 Main Cabinet
(Node 00), and includes all I/O's associated to the 586505000/586505500 Main
Cabinet. For the 582140000, Node 00 is the grouping of LMS I/O cards installed in
the Primary Bay. Node 00 also includes the LED, Function, and Energy
Management channels. For both 586505000/586505500 and 582140000, you
assign Node Numbers (21-89) to the groupings of LMS I/O cards installed in
586505000/586505500 Expansion Cabinets and 582140000 Secondary Bays during
the Initial Start-Up procedure.
• Input numbers for the LMS VPS MCA Interface are pre-assigned (The LMS VPS
MCA Interface provides additional analog channels and binary channels. These
channels are dedicated to the LMS VPS MCA Interface, and are automatically
mapped to monitor predetermined VPS parameters.). The Node Number for the LMS
VPS MCA Interface is 90.
• Input numbers for the LMS LPS MCA Interface are pre-assigned (The LMS LPS MCA
Interface provides additional analog channels and binary channels. These channels
are dedicated to the LMS LPS MCA Interface, and are automatically mapped to
monitor predetermined LPS parameters.). The Node Number for the LMS LPS MCA
Interface is 99.
• Input numbers for the LMS LPS Bay Interface are pre-assigned (The LMS LPS Bay
Interface provides additional analog channels and binary channels. These channels
are dedicated to the LMS LPS Bay Interface, and are automatically mapped to
Page 2-4 Chapter 2. Operating LMS1000
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
monitor predetermined LPS parameters.). The Node Number for each LPS Bay is 1
through 20, starting with the Primary Bay.
• The LMS also provides self diagnostic alarms on binary channels B0081 through
B0099.
Example: A0001,
A represents an analog input/channel
00 represents the 586505000/586505500 Main Cabinet Node or 582140000
Primary Bay LMS I/O Grouping Node (cannot be changed)
01 represents input/channel #01
Example: A3001,
A represents an analog input/channel
30 represents the 586505000/586505500 Expansion Cabinet Node or
582140000 Secondary Bay LMS I/O Grouping Node set as Node #30 (set
when network initially established)
01 represents input/channel #01
Example: A4001,
A represents an analog input/channel
40 represents the 586505000/586505500 Expansion Assembly Node set as
Node #40 (set when network initially established)
01 represents input/channel #01
Example: A9001,
A represents an analog input/channel
90 represents the VPS MCA Node (cannot be changed)
01 represents input/channel #01
Example: A9901,
A represents an analog input/channel
99 represents the LPS MCA Node (cannot be changed)
01 represents input/channel #01
Example: A0101,
A represents an analog input/channel
01 represents the 582140000 Primary Bay Node (cannot be changed)
01 represents input/channel #01
Example: A0201,
A represents an analog input/channel
02 represents an 582140000 Secondary Bay Node (cannot be changed)
01 represents input/channel #01
Chapter 2. Operating LMS1000 Page 2-5
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
LOCAL CONTROLS AND INDICATORS
LMS Display Option
Refer to Section 5942 or Section 5943 for LMS Display option operation procedures.
These are provided in the LMS1000 Installation Manual, and on the CD provided with
your system documentation.
Location and Identification
Refer to Figure 2-1.
LMS CPU Circuit Cards
The following controls and indicators are located on the LMS CPU circuit cards. In a
586505000/586505500 System, these indicators are visible through the front panel of the
Main and Expansion Cabinets. In the 582140000 LPS Power System, open the bay's
front door to view the indicators on the LMS CPU circuit card.
a) ON Indicator:
This indicator illuminates green to indicate the presence of DC
input power to the CPU circuit card, and that the power supply circuits located on
the circuit card are functioning properly.
LMS Main CPU Circuit Card Only: This indicator illuminates yellow if the
voltage of the internal battery located on the CPU circuit card decreases below
2.5 volts DC. The internal battery maintains clock and memory if input power to
the system is lost. When this indicator illuminates yellow, the memory backup
battery should be replaced.
b) FAIL Indicator:
This indicator illuminates red if the CPU circuit card fails. If this
occurs, the system has shut down.
LMS Main CPU Circuit Card Only: This indicator also illuminates if any of the
LMS "Hardware Fail" channels become active. Extended relay contacts are also
provided for connection of external alarms.
c) RST Pushbutton Switch:
This pushbutton switch is used in cases where the
system will not respond to operator input. Momentarily pushing this switch resets
the CPU.
d) 1 - 8 (Programmable Status LED Indicators) (Main CPU Circuit Card Only):
Eight LED indicators are located on the main CPU circuit card. These indicators
can be programmed to illuminate at specific user determined events or
occurrences. The LED's can also be programmed to illuminate red, yellow, or
green.
e) S2 (Programmable Switch) (Main CPU Circuit Card Only):
Can be used in
program lines. Refer to "Program Lines" in "Chapter 3. Configuring LMS1000" in
the separate Installation Instructions (Section 5879).
Page 2-6 Chapter 2. Operating LMS1000
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
586505000 Shown
586505500 Similar
FRONT OF SHELF
Located on Front of
Main LMS CPU Circuit Card
586505000 Shown
586505500 Similar
MAIN CABINET
FRONT OF SHELF
Located on Front of
Expansion LMS CPU Circuit Card
EXPANSION CABINETS
Figure 2-1
Controls and Indicators Locations (586505000/586505500 LMS Cabinet)
(Note that Spec. No. 582140000 LPS Power System does not use the
LMS Cabinets. The LMS is factory integrated into the LPS Power System.)
Chapter 2. Operating LMS1000 Page 2-7
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
ACCESSING THE SYSTEM THROUGH
A LOCAL OR REMOTE TERMINAL
Users can access the system through a local terminal and (if a modem circuit card is
installed) through a remote terminal.
Passwords and Access Levels
General: Up to eight separate users may be configured to access the system. Each
user is assigned a password and an access level.
Passwords: The password assigned to a user is required to be entered for that user to
log onto the system.
Access Levels: The access level (1-6) assigned to a user determines which commands
that specific user can execute. Each command is associated to a command level. A
user configured with an access level of 1 can execute all commands with a command
level of 1. A user configured with an access level of 2 can execute all commands with a
command level of 2 or less
of 2-6 can execute commands with the corresponding command level, and with a lower
command level. As an example, a user programmed with an access level of 4 can
execute commands with a command level of 1, 2, 3, or 4.
, and so forth. Note that users configured with an access level
Commands are divided into the following command levels.
Level 1: Interrogate/Status Commands
Level 2: Display Channel Configuration
Level 3: Set Date & Time
Level 4: Alarm Acknowledge, Alarm Canceling
Level 5: Configure Channels
Level 6: Configure Users, Upload & Download
A list with a short description of each command is provided at the beginning of
"Chapter 3. Commands".
Terminal Requirements
A local terminal must have a keyboard, a video console or printer, and an RS-232 serial
port. This terminal requires an interface cable for connecting the terminal's serial port to
the system's local port. Refer to the separate Installation Instructions (Section 5879) for
cable connection details.
A remote terminal must have a keyboard, a video console or printer, and a modem
connected to a phone line. If the modem is an external type, you also need an interface
cable between the modem and the terminal's serial port. Refer to the modem instructions
for details.
The terminal must be capable of directing keyboard entry out through the serial port or
modem at 300 bits/s, 8 data bits, 1 stop bit and half-duplex. This capability may also be
Page 2-8 Chapter 2. Operating LMS1000
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
achieved using a personal computer running a special "terminal emulator" program such
as the Lorain
®
SMART Partner.
Local Terminal Access
The word format communications parameters (word length, stop bits, and parity) of the
local terminal must match the system's default parameters. The default parameters are 8
data bits, 1 stop bit, and no parity. The data rate of the local port is software selectable
from 300 to 19200 bits/s, and can be changed through the SET COM command. The
data rate is factory set to 19200 bits/s.
Remote Terminal Access
Remote terminal access requires a modem to be installed in the system. An internal 56K
bits/s modem is available. This modem allows monitoring and programming the system
from a remote terminal via phone lines, and also allows the system to report alarms to
remote terminals. Remote terminal access is accomplished by calling the system.
The communications parameters of the remote terminal must match the system's default
parameters. The default parameters are 2400 bits/s (when reporting), 8 data bits, 1 stop
bit, and no parity. These defaults cannot be changed.
When answering, the data rate of the internal modem switches to match the incoming
call. When reporting, the modem data rate will be set to the speed that is programmed in
the user configuration of the user being called. When the modem performs a callback, it
will call at the speed it answered at.
Using a Terminal
Logon Prompt: When the system is initially accessed, the following logon prompt is
displayed.
ENTER PASSWORD
*
Entering Passwords: Passwords are case sensitive, which means the system
recognizes upper and lower case characters differently. Type your password exactly as it
was entered during system configuration. After typing the password, press ENTER. As
the password is entered, it will not be displayed on the terminal’s screen.
Command Prompt: The command prompt indicates that the system is waiting for user
input, and is shown below. In this prompt, n denotes the level of access.
Command <n>:
Entering Commands:
After typing a command, press ENTER.
Commands are not case sensitive, which means the system does not recognize upper
and lower case characters differently. Type the commands in either upper or lower case,
as desired.
In most cases, the entire command does not have to be entered to be executed. All that
needs to be entered are enough characters to uniquely identify the command. As an
Chapter 2. Operating LMS1000 Page 2-9
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Section 5847User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
example, instead of typing the command SET TIME, typing SE TI is sufficient. Some
commands can be entered with one character. As an example, commands such as
ALARMS, SCAN, LOG, and PRCONFIG can be executed by entering the respective
single character A, S, L, or P. The minimum characters required to enter each command
are indicated in "Chapter 3. Commands".
When the backspace or delete key (Control H) is pressed, the last character typed is
erased. Successive uses of this key will erase characters back to, but not beyond, the
beginning of the line.
Two control characters allow use of all or parts of the previously entered command.
When a command is entered, a copy is stored internally in a buffer. Typing CTRL-R
copies the previously entered command from the buffer to the current command line.
Typing CTRL-Z copies the next character of the previously entered command from the
buffer to the current command line.
Aborting and Pausing Commands:
Typing CTRL-C, CTRL-X, or ESCape terminates the execution of a command in process,
and returns the user to the command prompt. This allows the user to enter another
command.
During system configuration, typing CTRL-V returns the user to the prior setting to be
programmed.
Typing CTRL-S pauses the response to a command. Typing any key restarts the
response.
User Timeout:
A user timeout feature is provided which automatically logs off a user when a period of
inactivity has occurred. This feature is designed to prevent a remote user from leaving a
terminal unattended, and thus tying up the modem port accidentally.
Note: The TL1 port has a session timeout feature which operates independently from
the user timeout feature.
A period of inactivity is defined as the amount of time that elapses while the system is
waiting for a command, carriage return, or line feed to be entered from the user. A
timeout message is issued and the communication link terminated when the elapsed time
reaches a preset value. This value is termed the "User Timeout" value, and is
programmable through the SET TIMEOUT command.
The timeout feature is active only when the system has specifically requested input from
the user, such as after a command prompt. It is NOT active during the processing of a
command.
Note: Commands such as SCAN A1 n will run indefinitely until the user aborts the
command.
Page 2-10 Chapter 2. Operating LMS1000
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Loading...
+ 455 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.