Emerson 582145500 User Manual

Page 1
A Technical Manual from the experts
in Business-Critical Continuity
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Specification Number: 582145500 Model: NetSure™ ITM
Page 2
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
This page is intentionally blank.
Spec. No: 582145500 Section 6040 Model: NetSure™ ITM Issue AB, April 8, 2013
Page 3
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
TABLE OF CONTENTS
I
MPORTANT SAFETY INSTRUCTIONS
R
ELATED DOCUMENTATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 I
NSPECTING THE EQUIPMENT AND STORING FOR DELAYED INSTALLATIONS
. . . . . . . . . . . . .4
1.1 External Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Internal Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Storing for Delayed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0 I
NSTALLATION DRAWINGS AND RECOMMENDED TOOLS AND TEST EQUIPMENT
. . . . . . . . . . .6
2.1 Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Row-Based Installation Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Recommended Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.0 P
OSITIONING THE
DC UPS S
YSTEM
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 General Guidelines for Positioning the DC UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.2 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.3 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Considerations in Moving the DC UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4.1 Transporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4.2 Moving a DC UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4.3 Final Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5 Overhead Cable Tray Rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.6 Front and Rear Bottom Panel Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.6.1 Bottom DC Distribution Feed (Bottom Cabled) Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.6.2 Top DC Distribution Feed (Top Cabled) Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.0 E
LECTRICAL CONNECTIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 Wiring Information and Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.1 Cable Lengths (Floor or Cabinet Top to Connection Point Inside DC UPS Module) . . . . . . . 19
4.1.2 Recommended Wire Sizes, Recommended Lugs, and Torque Requirements . . . . . . . . . . . . . 19
4.1.3 Wiring Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.3 Wiring Connections Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.4 Making Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4.1 Cabinet Grounding Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4.2 DC Distribution Ground/Return Busbar Grounding Connection . . . . . . . . . . . . . . . . . . . . . . 23
4.4.3 DC Output Distribution Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.4.4 AC Input Power Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.4.5 Optional Alarm/Control Connections (to Primary Module only) . . . . . . . . . . . . . . . . . . . . . . . 27
4.4.6 ACU + Controller Ethernet Connection (to Primary Module only) . . . . . . . . . . . . . . . . . . . . . 30
4.4.7 Optional Emergency Power Off (EPO) Connection (to Primary Module only) . . . . . . . . . . . . 31
4.4.8 Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
i
Section 6040
Page 4
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
4.5 Making Module-to-Module -48VDC and Ground/Return Interconnections
(if system consists of multiple DC UPS modules). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.5.1 -48Vdc and Ground/Return Busbar Interconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.6 Making Alarm/Control Interconnections between Modules
(if system consists of multiple DC UPS modules). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.6.1 RS-485 Module-to-Module Interconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.6.2 CAN-Bus Module-to-Module Interconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.6.3 BLVD Module-to-Module Interconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.0 I
6.0 S
NSTALLING
TART-UP INSTRUCTIONS
PCUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2 Final Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.2 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.3 Connecting Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.3 Initially Starting and Verifying DC UPS System Operation. . . . . . . . . . . . . . . . . . . . . . . . . 54
6.3.1 Initially Starting the DC UPS System and Verifying System Operation . . . . . . . . . . . . . . . . 55
6.3.2 Setting Common Controller Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.3.3 Changing the Numbering Scheme of the PCUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.0 S
PECIFICATIONS AND TECHNICAL DATA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.1 Agency Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.2 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.3 Mechanical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.4 Monitoring Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.5 Electrical Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.5.1 Termination Type, Recommended Wire Size, Recommended Lugs. . . . . . . . . . . . . . . . . . . . . 59
7.5.2 Power Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.5.3 AC Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.5.4 DC Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.5.5 Battery Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
7.5.6 Advanced Control Unit Plus (ACU+) Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
7.5.7 SM-DU+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
7.5.8 SM-DU (used in Expansion Modules only in place of Controller) . . . . . . . . . . . . . . . . . . . . . . 66
7.5.9 SM-AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.5.10 SM-BRC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.5.11 Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
ii
Section 6040
Page 5
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
FIGURES
Figure 1 Outline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 2 Bottom DC Distribution Feed Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 3 Top DC Distribution Feed Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 4 NetSure™ ITM Row-Based DC UPS System Installation Example . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5 Emerson Floor Stands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 6 Mounting Locations for Overhead Cable Tray Rails. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 7 Installing Front and Rear Bottom Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 8 Installing Air Duct Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 9 Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 10 Wiring Connections Locations (DC UPS Module with Bottom Feed DC Distribution) . . . . . . . . 21
Figure 11 Wiring Connections Locations (DC UPS Module with Top Feed DC Distribution) . . . . . . . . . . . 22
Figure 12 Cabinet Grounding Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 13 DC Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 14 AC Input Power Connection Routing Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 15 Installing Conduit Fittings when AC is Fed from the Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 16 AC Input Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 17 Alarm and Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 18 ACU+ Controller RJ-45 Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 19 EPO Jumper Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 20 Module-Module Interconnect Busbars (DC UPS Module with Bottom Feed DC Distribution) . . 33
Figure 21 Module-Module Interconnect Busbars (DC UPS Module with Top Feed DC Distribution) . . . . . 34
Figure 22 SM-BRC RS-485 Jumper Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 23 Alarm/Control Cable Interconnects (cont’d on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 24 System Configuration and Communications Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 25 Cabinet Interconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 26 Signal Cabling and Switch Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 27 PCU Handle and Safety Latch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 28 Making Final Battery Shelf Battery Interconnect Link Connections . . . . . . . . . . . . . . . . . . . . . . 44
Figure 29 Field Battery Monitoring Lead Connections to the SM-BRC Unit . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 30 System Efficiency Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
iii
Section 6040
Page 6
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
TABLES
Table 1 DC UPS Module "Base Configuration Part Numbers"
and "Configured System Spec. Numbers" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 Distance to Connection Points inside the DC UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 3 Programmable Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 4 Programmable Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 5 IB2 Board Communications Address Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 6 ACU+ Controller RJ-45 Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 7 DC UPS System Environmental Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 8 DC UPS System Mechanical Characteristics (per module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 9 Shipping Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 10 AC Input and AC Input Grounding (per DC UPS module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 11 Cabinet Frame Grounding (per DC UPS module). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 12 DC Distribution (Distribution Circuit Breaker Option - per circuit breaker position) . . . . . . . . . 60
Table 13 DC Distribution (Distribution Fuse Option - per fuse position) . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Table 14 Alarm/Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 15 Power Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 16 AC Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 17 DC Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Table 18 Battery Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
iv
Section 6040
Page 7
NetSure™ ITM with eSure™ Technology
!
!
!
!
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
I
MPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your NetSure™ ITM Row-Based DC UPS system.
Read this manual thoroughly before installing the DC UPS system. Retain this manual for use by
installing personnel.
WARNING
The DC UPS system should be installed by a qualified technician in accordance with the information contained in this document.
WARNING
Special safety precautions are required for procedures involving handling and installation of the DC UPS system. Observe all safety precautions in this manual before handling or installing the DC UPS system.
WARNING
Exercise extreme care when handling DC UPS modules (cabinets) to avoid equipment damage or injury to personnel. The DC UPS module weighs 3240 lb. (1470 kg), fully loaded.
Be aware of module weight and locate center of gravity symbols before handling the DC UPS module. Test lift and balance the module before transporting. Never tilt module more than 10 degrees from vertical.
WARNING
All power and control wiring should be installed by a qualified electrician. All power
and control wiring must comply with the National Electrical Code (NEC) and applicable local codes.
Maximum load must not exceed that shown on the DC UPS module rating label.
Maximum output short circuit current is 7000 amperes.
WARNING
High Ground Leakage Current: Ground connection is essential before connecting the input supply.
This equipment must be grounded in accordance with the NEC and applicable local codes.
CAUTION
Ground leakage current exceeds 3.5 mA and is less than 30 mA.
Transient and steady-state ground leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous residual current circuit breakers (RCCBs) or residual current devices (RCDs).
RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses.
Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
1
Section 6040
Page 8
NetSure™ ITM with eSure™ Technology
!
!
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
CAUTION
This equipment is fitted with RFI suppression filters.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the User must correct at his own expense.
WARNING
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Battery Compartment Precautions
Batteries are factory installed in the DC UPS module. Final battery connections will be made by Emerson after the DC UPS module is installed. DO NOT MAKE BATTERY CONNECTIONS. The following precautions apply to the battery compartment that is part of the DC UPS module.
WARNING
Special safety precautions are required for procedures involving handling, installing, and servicing batteries. Observe all battery safety precautions presented here and in the battery instruction manual. These precautions should be followed implicitly at all times.
WARNING
A battery can present a risk of electrical shock and high short circuit current. Servicing of batteries should be performed or supervised only by properly trained and qualified personnel knowledgeable about batteries and the required precautions.
The following precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Use certified and well maintained insulated tools.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If the battery is inadvertently grounded, remove source from ground. Contact with any parts of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).
• Risk of explosion if battery is replaced with an incorrect type or if polarity is reversed. When replacing batteries, replace with the same manufacturer and type, or equivalent. See your local Emerson representative for a list of approved batteries.
• Dispose of used batteries according to the instructions provided with the batteries. Do not dispose of batteries in a fire. They may explode.
In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and is toxic. If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
2
Section 6040
Page 9
NetSure™ ITM with eSure™ Technology
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
WARNING
The DC UPS module’s internal batteries are connected and energized even if the DC UPS module is turned OFF. Battery disconnect fuses are provided inside the DC UPS module. To minimize the risk of injury, remove the battery disconnect fuses before any off-line servicing is performed on the unit.
WARNING
DO NOT REMOVE BATTERY STRAPS. If a battery cell is replaced, ensure the battery strap is replaced and appropriately tighten.
• Battery compartments contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt.
Failure to heed this warning could result in smoke, fire, or electric hazard.
Call Emerson before moving DC UPS modules (after initial installation).
R
ELATED DOCUMENTATION
• System Operation Document (Section 6047).
• Site Planning Data and System Drawings Document (Section 6037).
• Emerson Excellence Range VRLA Battery (31020591)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
3
Section 6040
Page 10
NetSure™ ITM with eSure™ Technology
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
1.0 I
NSPECTING THE EQUIPMENT AND STORING FOR DELAYED INSTALLATIONS

1.1 External Inspections

1. While the DC UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Emerson Network Power (number located on last pages of this document) to inform them of the damage claim and the condition of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Emerson representative immediately.

1.2 Internal Inspections

1. Remove any packaging material, then visually examine the DC UPS system for transit damage, both internally and externally. Report any such damage to the shipper and to Emerson immediately.
2. Check the nameplate inside the DC UPS module (located on the front top right side with front door open) to verify that the "base configuration part number" and the "configured system spec. number" correspond to the units ordered. Record the DC UPS module identification numbers and serial number in the front of this manual. This information is necessary should service be required. See Table 1.
NOTE
The "base configuration part number" determines how the DC UPS module is physically configured and the "configured system spec. number" determines how the DC UPS module has been set up.
3. Check for loose connections or unsecured components in the module.
4. Check for shipping damage to internal components.

1.3 Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 95%. The storage area must protect the DC UPS system from excessive moisture.
For optimal battery life, store at a temperature between
Environmental).
CAUTION
If the batteries must remain disconnected from the DC UPS module for more than six (6) months, the batteries must be recharged before use. To charge the batteries, the batteries must be connected to the DC UPS module and the DC UPS module must be connected to utility power and started up by qualified personnel.
-4°F to +77°F (-20°C to +25°C)
(see 7.2 -
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
4
Section 6040
Page 11
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Table 1 DC UPS Module "Base Configuration Part Numbers"
and "Configured System Spec. Numbers"
Base Configuration Part Numbers
Part Number Module
FAB8010542/2 Primary Top (22) Circuit Breaker 1
FAB8010542/1 Primary Top (22) Circuit Breaker 2
FAB8010542/4 Primary Top (6) Fuse 1
FAB8010542/3 Primary Top (6) Fuse 2
FAB8010540/2 Primary Bottom (22) Circuit Breaker 1
FAB8010540/1 Primary Bottom (22) Circuit Breaker 2
FAB8010540/4 Primary Bottom (6) Fuse 1
FAB8010540/3 Primary Bottom (6) Fuse 2
FAB8010543/2 Expansion Top (22) Circuit Breaker 1
FAB8010543/1 Expansion Top (22) Circuit Breaker 2
FAB8010543/4 Expansion Top (6) Fuse 1
FAB8010543/3 Expansion Top (6) Fuse 2
FAB8010541/2 Expansion Bottom (22) Circuit Breaker 1
Distribution
Feed
Distribution
No. of AC
Inputs
FAB8010541/1 Expansion Bottom (22) Circuit Breaker 2
FAB8010541/4 Expansion Bottom (6) Fuse 1
FAB8010541/3 Expansion Bottom (6) Fuse 2
Configured System Spec. Numbers
Spec. Number Description
582145500-M1 Primary Module
582145500-M2 1st Expansion Module
582145500-M3 2nd Expansion Module
582145500-M4 3rd Expansion Module
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
5
Section 6040
Page 12
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
2.0 I
NSTALLATION DRAWINGS AND RECOMMENDED TOOLS AND TEST EQUIPMENT

2.1 Installation Drawings

The diagrams in this section illustrate the key mechanical and electrical characteristics of the NetSure ITM DC UPS system.
General Notes Applicable to All Illustrations
1. All dimensions are in inches (millimeters).
2. Minimum clearance above unit required for air exhaust is 8 in. (203mm).
3. Keep module within 10 degrees of vertical while handling.
4. Top and bottom cable entry options available.
5. Color - black.
6. Unit bottom is structurally adequate for forklift handling.
7. M12 mounting holes used for seismic anchoring or floor stand.
NOTE
If floor stand is used, the weight of the unit must be supported under all casters.
8. The Primary Module includes side panels. For installations consisting of Expansion Module(s), one side panel on the Primary Module must be removed and be placed on the end Expansion Module.
9. Leveling feet are not designed to carry the full weight of the module.
10. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.
11. Control wiring, output cabling, and input cabling must be run separately.
12. Aluminum and copper-clad aluminum cables are not recommended.
13. All wiring is to be in accordance with the NEC and applicable local codes.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
6
Section 6040
Page 13
NetSure™ ITM with eSure™ Technology
Notes:
1. Dimensions areininches (millimeters).
2. Weight (fully loaded): 3240 lbs/1470 kg.
3. Heat Rejection: 18096 BTU/hatfullload (per module).
4. May be installedon concreteslaborraised floor.
23.62 (600)
Battery Compartment
Conduits for AC Inputs
41.34
(1050)
DC Power System Compartment
Z
X
Y
To pCabledVersion X=11.81 (300) Y=26.38(670) Z=36.61 (930)
Bottom CabledVersion X=11.81 (300) Y=26.38(670) Z=40.55 (1030)
CENTER OF GRAVITY
26.38 (670)
CG
11.81 (300)
(Bottom cabled) CG
11.81 (300)
36.61
(930)
40.55
(1030)
CG (top cabled)
23.62 (600)
Battery Compartment
Conduits for AC Inputs
41.34
(1050)
DC Power System Compartment
26.38 (670)
CG
11.81 (300)
See Detail A for Bott
om
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
To p View
To p View
Front View
84.33
(2142)
top
cabled
84.72
(2152)
bottom
cabled
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 1 Outline Drawing
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
7
Section 6040
Page 14
NetSure™ ITM with eSure™ Technology
35.43 (900)
19.68 (500)
12.99 (330) - 13.39 (340)
39.65 (1007)
31.22 (793)
0.59 (15)
0.28 (7)R
35.43 (900)
Hole through foot (4x) for
anchoring on raised floo
r
Anchoring bracket (4x)
used on concrete floo
r
Anchoring bolts (4x) used on raised
floor
ANCHORING
Hilti HSV 1/2X4 1/2: Item No.: 00384687
M12 x 1.75 x 70 Metric Socket Head Cap Screw. Plain Finish with Allen Drive (hex drive) / Coarse thread. Grade 12.9
.
M12 X 1.75 Metric Hex Nuts - Grade 10.9 / Coarse Thread / Zinc Plated
.
M12 Metric Flat Washer. Grade 10.9 / Zinc. D=28mm or 11/8".
(4X)
(4X)
(8X)
(8X
)
Corresponding ½” Imperial Fasteners Can Also be Used
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 1, Detail A
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
8
Section 6040
Page 15
NetSure™ ITM with eSure™ Technology
Battery Compartment
BFU
Distr.
Distr.
Raised Floor
HotAisle
Cold Aisle
A
AirFlow
Note2
Side View
Support Stand
½” (12mm) Floor
Anchoring Bolts
(4 places)
To p
Front
Notes:
1. Dimensions areininches (millimeters).
2. Do not block airintake openings.
3. Minimum under floor space for underfloor output cable runs: A=1f (300mm).
4. Run cables not to block air openings for battery cooling.
Battery
Compartment
Conduits for
AC Inputs
DC Power System
Compartment
35.43
(900)
17.72 (450)
8.86
(225)
9.84
(250)
19.68 (500)
9.84
(250)
8.86
(225)
Optional Floor Opening for Battery Cooling
PCUs
PCUs
PCUs
PCUs
PCUs
PCUs
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 2 Bottom DC Distribution Feed Modules
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
9
Section 6040
Page 16
NetSure™ ITM with eSure™ Technology
Note2
Distr.
Distr.
HotAisle
Cold Aisle
AirFlow
Concrete Floor (slab)
Side View
Notes:
1. Dimensions areininches (millimeters).
2. Do not block airintake openings.
To p
Battery
Compartment
DC Power
System
Compartment
Openings for Output Cables
Front
CableTraySupports if Mounted on To pof Module
Front View
CableTray
CableRun
Battery Compartment
PCUs
PCUs
PCUs
PCUs
PCUs
PCUs
To pView
Battery
Compartment
Openings for Output Cables
CableTray
23.62 (600)
BFU
½” (12mm) Floor
Anchoring Bolts
(4 places)
35.43
(900)
19.68 (500)
Air Exchange (keep clear)
AC Input
Conduit Openings
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 3 Top DC Distribution Feed Modules
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
10
Section 6040
Page 17
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

2.2 Row-Based Installation Example

The NetSure ITM DC UPS system provides the flexibility to meet the needs of any data center.
The NetSure ITM DC UPS system is delivered fully configured for quick and easy field installation. Multiple DC UPS modules can easily be connected on site in order to increase capacity. Each module takes only 24" (w) x 41" (d) of floor space, including batteries and primary distribution. The NetSure ITM DC UPS system is typically installed in the middle or at the end of a row of server racks. This makes the system uniquely flexible and scalable. Deploy only the capacity that is initially needed; modules can be added at any time to existing units on the data center floor.
Figure 4 depicts a top distribution feed installation powering IT racks. Depending on your site and budget requirements, the NetSure ITM DC UPS solution can either be installed as a single deployment, or incrementally by row. In either scenario, DC distribution cabling to each rack is reduced by placing the NetSure ITM DC UPS in-the-row.
Whatever the physical layout of your data center, the NetSure ITM DC UPS allows for maximum space for IT equipment. With DC UPS building block modules, you can mix and match configurations and standard layouts to fit your available space.
Figure 4 NetSure™ ITM Row-Based DC UPS System Installation Example
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
11
Section 6040
Page 18
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

2.3 Recommended Tools and Test Equipment

The following tools and test equipment are recommended to install the DC UPS modules.
• Non-Contact Voltage Detector
• Digital Multimeter (DMM), 0 to 60 V dc, 0 to 600 V ac
• NO-OX-ID-A or Approved Equivalent
• Lineman's Scissors
• Lineman's Strippers
• Lineman's Cutters
• Electrician's Insulated Screwdrivers, Phillips, No. 1 and 2
• Electrician's Insulated Screwdrivers, Flat-Blade, Small and Large
• Adjustable Torque Wrench, 1/2" Drive, 0 in-lb to 800 in-lb
• Ratchet, 1/2" Drive
• Insulated Nut Driver Set
• Crimping Tool with Dies from 350 kcmil to 2 AWG
• Torx Screwdrivers or Bits: TX10 and TX20
• 17 mm Wrench or Socket for M10 Bolts and Nuts (for circuit breaker distribution)
• 19 mm Wrench or Socket for M12 Bolts and Nuts (for fuse distribution)
• 24 mm Wrench for Pallet.
• Hexagonal mm Bit for the Air Duct.
• Hexagonal Bit for the AC Input Breaker.
Contact Emerson for full turn key installation quote.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
12
Section 6040
Page 19
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
3.0 P
OSITIONING THE
This section describes the environmental and mechanical considerations that must be taken into account when planning the positioning and cabling of the DC UPS system. This section also provides procedures for physical installation of the DC UPS cabinet.
Because every site is unique, some subsections present a guide to general procedures and practices that should be observed by the installing engineer, rather than step-by-step installation instructions.
DC UPS S
YSTEM

3.1 General Requirements

• The installer should be familiar with the installation requirements and techniques to be used in securing the DC UPS module (cabinet) to the floor. It is up to the customer to determine the requirements for anchoring the cabinet to the specific type of floor at the site, select proper anchors, and to investigate the proper use of the anchor.
• This product is intended only for installation in a Restricted Access Location on or above a non­combustible surface.
• Front and rear access is required for installation and operation (see Clearances in this section).

3.2 General Guidelines for Positioning the DC UPS Modules

Choose a location for the DC UPS system that offers:
• Easy connection to inputs, outputs, and alarms.
• Air circulation sufficient to expel heat produced by the DC UPS system.
• Protection against moisture and excessive humidity.
• Protection against dust and other particulate matter.
• Enough space to service the DC UPS system (see Clearances in this section).
• Compliance with fire prevention regulations and practices.

3.2.1 Cable Entry

DC distribution and alarm cables enter the DC UPS module from the top or bottom, depending on module configuration (top distribution feed or bottom distribution feed).
AC input cables can enter either at the top or bottom. Conduit openings are provided in both locations.

3.2.2 Environmental Considerations

Before installing the DC UPS system, verify that the room satisfies the environmental conditions stipulated in 7.2 - Environmental, paying particular attention to the ambient temperature and air exchange system. Also refer to 7.2 - Environmental for details on heat dissipation.
The DC UPS system should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range +23°F to +95°F (-5°C to +35°C).
• Batteries are installed in the DC UPS module’s battery compartment. Temperature is a major factor in determining battery life and capacity. Battery manufacturers recommend an operating temperature of 77°F (25°C). Ambient temperatures higher than this reduce battery life; temperatures lower than this reduce battery capacity. For optimal battery performance and service life, inlet air temperature to the battery compartment (from the front of the system) should be maintained between +68°F to +77°F (+20°C to +25°C).
The DC UPS module is cooled by internal fans. Cooling air enters the system through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 8 in. (203mm).
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
13
Section 6040
Page 20
NetSure™ ITM with eSure™ Technology
P/N 547823
36” Tall Floor Stand
P/N 547822
24” Tall Floor Stand
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.2.3 Mechanical Considerations

The DC UPS system can be comprised of up to four (4) modules (cabinets), depending upon your power requirements. All modules used are the same size and are designed to be positioned side-by­side to form an aesthetically appealing equipment suite. The system always contains one (1) Primary Module. For increased power demands, up to three (3) Expansion Modules may be added. Locate the Primary Module at the far left or far right of the row. Remove the side panel from the Primary Module from the side that will face adjacent Expansion Modules. Place the first Expansion Module next to the Primary Module. Place additional Expansion Modules (if required) next to each other. Install the side panel removed from the Primary Module to the open side of the last Expansion Module in the row.
NOTE
When the DC UPS system consists of multiple modules, the switches inside the modules are pre-set at the factory to identify the module as the Primary Module, 1st Expansion Module, 2nd Expansion Module, or 3rd Expansion Module. When placing modules, refer to the nameplate identification number (see Table 1) to ensure the Primary Module is placed on the end, and Expansion Modules are place in sequential order.
Clearances
There are no ventilation grilles on the sides of the DC UPS module. The DC UPS modules may be placed with the sides touching or against a wall.
To enable routine tightening of power terminations within the DC UPS module, make sure there is sufficient clearance in front and rear of the DC UPS module to permit free passage of personnel and that the front door can be fully opened.
Leave a minimum of 8 in. (203mm) between the top of the DC UPS module and the ceiling to permit adequate air circulation above the unit. Emerson recommends against using air conditioning or other systems that blow air onto the top of the unit.
Leave a minimum of 36 in. (914 mm) between the back of the DC UPS module and a wall to permit adequate air circulation for the battery compartment fans and facilitate maintenance access.

3.3 Floor Installation

Refer also to 3.1 - General Requirements.
The diagrams in 2.0 - Installation Drawings and Recommended Tools and Test Equipment show the location of holes in the base plate for bolting the DC UPS module to the floor.
If the module is to be placed on a raised floor, it should be mounted on a floor stand that will support the equipment point loading. Refer to the cabinet-bottom views in 2.0 - Installation Drawings and Recommended Tools and Test Equipment to design this pedestal. Contact your Emerson Sales Representative for a floor stand designed for this system (see Figure 5).
Figure 5 Emerson Floor Stands
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
14
Section 6040
Page 21
NetSure™ ITM with eSure™ Technology
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.4 Considerations in Moving the DC UPS Module

3.4.1 Transporting

Ensure that the DC UPS module weight is within the designated surface weight loading (lb./ft2 or kg/ cm2) of any handling equipment. The DC UPS module weighs 3240 lb. (1470 kg), fully loaded.
WARNING
Ensure that any equipment that will be used to move the DC UPS module has sufficient lifting capacity. Ensure adequate personnel and lifting equipment are available when taking the module off its shipping pallet. The module presents a tipping hazard. Do not tilt the module further than 10 degrees from vertical.
The DC UPS module is fitted with casters. Take care to prevent movement when unbolting the module from its shipping pallet. The casters are strong enough for movement across even surfaces only. Casters may fail if they are subjected to shock loading, such as being dropped or rolled over holes in the floor or obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging the equipment.
WARNING
Batteries are factory installed in the DC UPS module’s battery compartment. Care must be taken when maneuvering modules with batteries. Keep such moves to a minimum. See Battery Compartment Precautions on page 2.

3.4.2 Moving a DC UPS Module

Cabinet Preparation
1. Inspect the cabinet as described in 1.1 - External Inspections and 1.2 - Internal Inspections.
2. Remove the front and rear bottom panels to gain access to the bolts securing the cabinet to the pallet.
Moving DC UPS Module from Shipping Pallet
Use lifting equipment, such as a forklift or similar equipment, appropriately rated for the weight of the load to move the DC UPS cabinet from its shipping pallet.
When moving a DC UPS cabinet with a forklift or similar equipment, make sure that the fork is of sufficient length for the pallet size and capable of lifting the cabinet. Also use a forklift with adjustable forks or a narrow type.
1. Close the front door.
2. Slide the forklift into place.
3. Unbolt the cabinet from the pallet.
4. Lift the cabinet. The pallet should drop off from its own weight.
5. Carefully move the DC UPS module to its installation location or set the DC UPS module down on its casters if it is to be rolled into position.
Moving DC UPS Module to Installation Location
The DC UPS module may be rolled on its casters when moving the unit a short distance. For longer distances, move the DC UPS module with a forklift or similar equipment to ease the relocation and to reduce vibration.

3.4.3 Final Positioning

Note that the DC UPS modules sit on four casters. When the DC UPS module has been finally positioned, ensure that the adjustable stops are set so that the DC UPS module will remain stationary and stable.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
15
Section 6040
Page 22
NetSure™ ITM with eSure™ Technology
Holes for 1/4” thread-forming screws to secure rails for overhead cable trays.
Customer supplied conduit fittings
Brackets can be used to secure rails for overhead cable trays, drill as required.
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.5 Overhead Cable Tray Rails

Refer to Figure 6 for mounting locations for overhead cable tray rails.
Figure 6 Mounting Locations for Overhead Cable Tray Rails
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
16
Section 6040
Page 23
NetSure™ ITM with eSure™ Technology
Battery Compartment Half
Power Compartment Half
Secure with
Supplied Screws
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.6 Front and Rear Bottom Panel Installation

3.6.1 Bottom DC Distribution Feed (Bottom Cabled) Modules

Refer to Figure 7 and install the front and rear bottom panels.
Figure 7 Installing Front and Rear Bottom Panels

3.6.2 Top DC Distribution Feed (Top Cabled) Modules

Installing the Supplied Air Duct Assembly: The Air Duct Assembly must be installed in DC UPS modules configured for top DC distribution feed (top cabled). The Air Duct Assembly allows air to be drawn from the bottom front of the DC UPS module and up into the battery compartment for cooling. Refer to Figure 8 and install the supplied Air Duct Assembly.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
17
Section 6040
Page 24
NetSure™ ITM with eSure™ Technology
Air Duct Assembly
Power Compartment Half
Battery Compartment Half
Installed View
Battery Compartment Half
Power Compartment Half
4) Slide the remaining half of the air duct assembly into the rear bottom compartment of the DC UPS module (battery compartment bottom).
5) Secure the air duct half just installed with the supplied screws.
Secure with supplied screws.
Note: If AC power cables are fed from the bottom, install AC power cables before installing air duct. Note: The rubber parts of the air duct assembly may be lubricated with water before sliding the air duct halves into place.
Procedure:
1) Partially slide the half of the air duct assembly with vents into the front bottom compartment of the DC UPS module (power compartment bottom).
2) Install and secure the supplied bracket with the supplied screws.
3) Slide the half of the air duct assembly with vents completely into the DC UPS module, and secure with the supplied screws.
Secure with supplied screws.
Install supplied bracket after partially sliding assembly in.
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 8 Installing Air Duct Assembly
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
18
Section 6040
Page 25
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
4.0 E
LECTRICAL CONNECTIONS
The DC UPS system requires grounding, DC output distribution, AC input power, alarm/control, and battery wiring once it has been mechanically installed.
If the system consists of multiple DC UPS modules, battery and ground/return busbars must be interconnected and alarm/control interconnect wiring between modules must be made.

4.1 Wiring Information and Guidelines

4.1.1 Cable Lengths (Floor or Cabinet Top to Connection Point Inside DC UPS Module)

To help calculate the total cable length required, refer to Table 2 for the distance from the floor or cabinet top to selected connection points inside the DC UPS module. Determine the cable length required to reach the DC UPS module, then add the appropriate length from the table and adequate slack for repair and maintenance.
Table 2 Distance to Connection Points inside the DC UPS Module
Connection Point
inside DC UPS
Module
AC Input 79 (2000) 138 (3500) 157 (4000) 59 (1500)
DC Output 28 (700) N/A N/A 28 (700)
From Floor
in. (mm)
Distance - Bottom
DC Distribution Feed Module
From Top of Module
in. (mm)
DC Distribution Feed Module
From Floor
in. (mm)
Distance - Top
From Top of Module
in. (mm)
Grounding 79 (2000) 138 (3500) 157 (4000) 59 (1500)
Alarm/Control 59 (1500) N/A N/A 47 (1200)

4.1.2 Recommended Wire Sizes, Recommended Lugs, and Torque Requirements

The main factors affecting the choice and size of wires are voltage, current (also taking into account overcurrent), room temperature, and installation conditions.
The power cables of the system must be sized with respect to the following:
AC Input Cables - The AC input cables must be sized for the module’s maximum input current.
DC Output Distribution Cables - The DC output distribution cables must be sized for the module’s output breakers or fuses.
Battery Cables - The DC UPS module contains a battery compartment. Battery cables are factory supplied and sized accordingly.
Refer to Termination Type, Recommended Wire Size, Recommended Lugs on page 59 for recommended wire sizes and recommended lugs. Refer to the illustrations in this section for torque requirements.
NOTE
The above referenced section gives nominal currents for determining the size of DC UPS module power cables. Other important factors to consider include cable route length and coordination with protective devices.

4.1.3 Wiring Guidelines

The following are guidelines only and are superseded by the NEC and applicable local codes where applicable.
• The grounding cable connecting the DC UPS module to the main ground system must follow the most direct route possible.
• Consider using paralleled smaller cables for heavy currents—this can ease installation.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
19
Section 6040
Page 26
NetSure™ ITM with eSure™ Technology
Front View
(Top Cabled Configuration)
Rear View
Protective Cover
Protective Cover
Protective Cover
Protective Cover
Protective Cover
Protective Cover
Protective Cover
Protective Cover
Front View
(Bottom Cabled Configuration)
SUITABLE FOR MOUNTING ON CONCRETE
OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
SUITABLE FOR MO UN T IN G O N CO N CR ET E
OR OTHER NO N-C OM BU ST IB LE SU RF AC E ON LY.
Protective Cover
Protective Cover
Dual AC Input Circuit Breaker Option Protective Cover View
(Top cabled configuration shown,
bottom cabled configuration similar.)
AC Input
Protective Cover
AC Input Protective
Cover Removed
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
• When laying power cables, do not form coils; this will help avoid increasing formation of electromagnetic interference. Positive and negative cables should be run together.
• Alarm/control wiring and power wiring must be run separately. Output and input cables must be run separately.

4.2 Protective Covers

Wiring connection access requires removing protective covers from the DC UPS module. When making electrical connections, remove the appropriate protective cover, as shown in Figure 9.
Replace all protective covers after all electrical connections have been made and checked.
Figure 9 Protective Covers
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
20
Section 6040
Page 27
NetSure™ ITM with eSure™ Technology
Module Cabinet Grounding
AC Input
(to circuit breakers)
DC Output
Circuit Breaker (Fuse)
Busbars (-48VDC)
Ground/Return
Busbars
AC Input
Circuit Breaker(s)
Battery Fuses (3) (Battery leads factory connected and routed to Battery Compartment.)
Alarm/Control Connections (to ACU+ IB2 Interface Board) (Primary Module only)
Load Distribution Devices DCCB01 - DCCB11 (Top Row) DCCB12 - DCCB22 (Bottom Row) (DC distribution breakers shown, large fuses available.)
Battery Return and Load Return (Battery return leads factory connected and routed to Battery Compartment.)
AC Input Channel
AC Input
Conduit Openings
(AC input cables
may also enter at
bottom of cabinet.)
Alarm/Control Cabling Channel
AC Input Circuit
Breaker Cover
PCU AC Input Circuit Breakers
Note: Three extra positions are provided on the ground/return busbar for customer connection to site ground.
ACU+ Controller (Primary Module only)
Front View
(door removed)
ISO View
(panels removed)
ISO View
(panels removed)
Battery Compartment and Base
Removed in Illustrations for Clarity
2"
AC Input Conduit Opening
Recommended Coupling: Raco Type 2628 (Grainger 3LV08) or Thomas Betts Type TK126US
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

4.3 Wiring Connections Locations

The DC UPS module input and output cable connections are easily accessible from the front of the unit for installation. Refer to Figure 10, Figure 11, Figure 12, Figure 13, Figure 14, Figure 16, Figure 17, Figure 18, and Figure 19 for connection locations. The DC UPS module contains a battery compartment. Battery cables are factory supplied and connected to the DC UPS module. Final connections to the batteries are made in the procedure in 6.2 - Final Battery Connections. Battery connections are done from the rear of the DC UPS module.
Figure 10 Wiring Connections Locations (DC UPS Module with Bottom Feed DC Distribution)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
21
Section 6040
Page 28
NetSure™ ITM with eSure™ Technology
DC Output Cable Openings
AC Input Conduit
Openings (AC input
cables may also enter
at bottom of cabinet,
conduit supplied
routed to bottom
of cabinet.)
AC Input
Circuit Breaker(s)
AC Input Channel
Battery Fuses (3) (Battery leads factory connected and routed to Battery Compartment.)
Battery Return and Load Return (Battery return leads factory connected and routed to Battery Compartment.)
Module Cabinet Grounding
Alarm/Control Cabling Channel
AC Input
(to circuit breakers)
DC Output
Circuit Breaker (Fuse)
Busbars (-48VDC)
Ground/Return
Busbars
Front View
(door removed)
SUITABLE FOR MO UNT ING O N CO NCRET E
OR OTHER NON-COM BUST IBLE SUR FACE O NLY.
Battery Compartment and Base
Removed in Illustrations for Clarity
ISO View
(panels removed)
ISO View
(panels removed)
AC Input Circuit
Breaker Cover
2"
AC Input Conduit Opening
Recommended Coupling: Raco Type 2628 (Grainger 3LV08) or Thomas Betts Type TK126US
Alarm/Control Connections (to ACU+ IB2 Interface Board) (Primary Module only)
ACU+ Controller (Primary Module only)
Load Distribution Devices DCCB01 - DCCB11 (Top Row) DCCB12 - DCCB22 (Bottom Row) (DC distribution breakers shown, large fuses available.)
PCU AC Input Circuit Breakers
Note: Three extra positions are provided on the ground/return busbar for customer connection to site ground.
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 11 Wiring Connections Locations (DC UPS Module with Top Feed DC Distribution)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
22
Section 6040
Page 29
NetSure™ ITM with eSure™ Technology
!
!
Module Cabinet Grounding Stud
Studs for Connecting
Grounding Strap
between Modules
3/8” (M10) Stud. Recommended Torque is 407-434 in-lbs (46-49 Nm).
5/16” (M8) Studs.
Recommended Torque is
204-221 in-lbs (23-25 Nm).
Module Top View
Customer supplied conduit fittings
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

4.4 Making Electrical Connections

CAUTION
The electrical connections described in this section must be performed by authorized electricians or qualified technical personnel. Follow the NEC and applicable local codes. If you have any difficulties, contact your local Emerson representative or Emerson Services.
Before making electrical connections, do the following for each DC UPS module (see Figure 10 and Figure 11 for circuit breaker and fuse locations).
• Open the front door. For bottom cable installations, remove the lower front panel. For all installations, remove protective panels as required (see 4.2 - Protective Covers).
• Ensure the main AC input circuit breaker(s) is in the OFF position.
• Ensure all PCU AC input circuit breakers are in the OFF position.
• Ensure the three (3) battery disconnect fuses are removed.
• Ensure all distribution circuit breakers are in the OFF position or distribution fuses are removed.

4.4.1 Cabinet Grounding Connection

The cabinet grounding connection is made to a stud located on the top of the DC UPS module, as shown in Figure 12. A cabinet grounding cable must be connected to this stud, per site requirements. Tighten the connection to the torque indicated in Figure 12.
Each module also contains a separate stud located on each side to connect the supplied grounding strap between DC UPS modules, if desired.
All modules and cable conduit should be grounded in accordance with the NEC and all applicable local codes.
WARNING
Failure to follow proper grounding procedures can result in electric shock hazard to personnel or the risk of fire, should a ground fault occur.
NOTE
Proper grounding significantly reduces electromagnetic interference problems in systems.
Figure 12 Cabinet Grounding Connection

4.4.2 DC Distribution Ground/Return Busbar Grounding Connection

Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
The DC distribution ground/return busbar must be connected via a solidly grounded lead to the main building ground. Three extra positions are provided on the ground/return busbar for customer connection to site ground. Refer to Figure 10 and Figure 11 for location of the DC distribution ground/return busbar. Refer to Table 250-122 in the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) for grounding conductor size. Typically use equivalent or minimum of 1/0 AWG.
23
Section 6040
Page 30
NetSure™ ITM with eSure™ Technology
!
1.75”
(44.45mm)
1.75”
(44.45mm)
11
1.75”
(44.45mm)
1.75”
(44.45mm)
1.5”
(38.1mm)
1.75”
(44.45mm)
1.5”
(38.1mm)
1.75”
(44.45mm)
1”
(25.4mm)
1”
(25.4mm)
1”
(25.4mm)
1”
(25.4mm)
Terminals are 1/2” (M12) studs. Recommended Torque is 690-743 in-lbs (78-84 Nm).
Terminals are 3/8” (M10) studs. Recommended Torque is 407-434 in-lbs (46-49 Nm).
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
DISTRIBUTION CIRCUIT BREAKERS
DISTRIBUTION FUSES
(optional)
DC Output (-48Vdc)
(per distribution position)
to distribution device busbar
DC Output Return (per distribution position) to ground/return busbars
DC Output (-48Vdc)
(per distribution position)
to distribution device busbar
DC Output Return (per distribution position) to ground/return busbars
Note: Three extra positions are provided on the ground/return busbar for customer connection to site ground.
Note: Three extra positions are provided on the ground/return busbar for customer connection to site ground.
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

4.4.3 DC Output Distribution Connections

Connect the DC output distribution cables between the DC UPS module and the loads as required. These connections are made to the output circuit breaker or fuse busbars and the ground/return busbar, as shown in Figure 10 or Figure 11. Refer to Figure 13 for a view of the busbar terminations. Tighten the connections to the torque indicated in Figure 13.
WARNING
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, then ensure that the system output cables are safely isolated.
Figure 13 DC Output Connections
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
24
Section 6040
Page 31
NetSure™ ITM with eSure™ Technology
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

4.4.4 AC Input Power Connections

WARNING
AC input power connections must be performed by a qualified electrician.
Before connecting AC input cables to the DC UPS module, ensure that you are aware of the location and operation of the overcurrent protection devices that connect these cables to the power distribution panel. Before connecting AC input cables, de-energize and lockout or tagout these overcurrent protection devices.
Do not apply AC input power to the DC UPS module before the arrival of the commissioning engineer.
AC Input Overcurrent Protective Device
CAUTION
To reduce the risk of fire, connect AC input only to a circuit provided with correct amperes maximum branch circuit overcurrent protection in accordance with the NEC, ANSI/NFPA 70.
External overcurrent protection for the AC input circuit is to be provided by the customer. Refer to AC Input Specifications on page 61 for maximum input current ratings. Each DC UPS module is provided with one or two internal 150A AC input circuit breaker.
AC Input Connections
AC input leads can enter the DC UPS module from the top or from the bottom. Refer to Figure 14 for an AC input routing diagram. Figure 15 provides a diagram for installing conduit fittings when AC is fed from the top.
One or two AC input breakers are provided (depending on module configuration). Refer to Figure 16 for an AC input connections diagram. Tighten the connections to the torque indicated in Figure 16. Note that a cover needs to be removed to access the circuit breakers as shown in Figure 9.
• Connect Feed A AC input supply cables between the power distribution panel and the DC UPS module’s internal Feed A input circuit breaker (Feed A: L1, L2, L3 terminals).
• If the DC UPS module is configured for two AC input feeds, connect the optional Feed B AC input supply cables between the power distribution panel and the DC UPS module’s internal Feed B input circuit breaker (Feed B: L1, L2, L3 terminals).
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
25
Section 6040
Page 32
NetSure™ ITM with eSure™ Technology
Battery Compartment
Battery Compartment
AC enters at top.
AC enters at bottom.
AC enters at bottom.
AC enters at top.
65kAic
Circuit
Breaker
65kAic
Circuit
Breaker
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
Run AC Cables
from Top OR Bottom
Run AC Cables
from Top OR Bottom
1) Remove cover plate.
Note: Cut cover plate in half if only one conduit being installed.
3) Secure conduit plate with conduit fittings installed to top of cabinet.
Note: If only one conduit being installed, re-install plate that was cut in half.
2) Install one or two customer provided conduit fittings to supplied conduit plate.
Customer provided
conduit fittings.
One or two AC input circuit breakers are provided (depending on module configuration).
Two ground studs (5/16” [M8]) are provided attached to the sides of the enclosure surrounding the AC input circuit breaker(s).
Recommended torque is 124 in-lbs (14 Nm) for AC input circuit breaker connection.
Recommended torque is 204-221 in-lbs (23-25 Nm) to grounding studs.
A
FeedBFeed
A
FeedBFeed
(optional)
(optional)
AC INPUT
380/480VAC, 3 Phase, 50/60Hz
AC INPUT
380/480VAC, 3 Phase, 50/60Hz
factory wiring
AC IN A
L1 L2 L3
AC IN B L1 L2 L
3
factory wiring
L1 L2 L3
AC IN A
L1 L2 L3
AC
IN B
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
GND Stud
GND
Stud
GND
Stud
GND Stud
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 14 AC Input Power Connection Routing Options
Figure 15 Installing Conduit Fittings when AC is Fed from the Top
Figure 16 AC Input Power Connections
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
26
Section 6040
Page 33
NetSure™ ITM with eSure™ Technology
Te rminals are M2 screws. Recommended Torque is 1.92-2.16 in-lbs (0.22-0.25 Nm). Wire size range is 26 AWG to 16 AWG (0.14 mm^2 to 1.0 mm^2).
Customer Input/Output (I/O) Connections
N C = N orm ally C losed C O M = C o m mo n N O = N o rm a lly O p e n
A ll re la y contact s a r e sh ow n w it h t h e re lay d e e n e r g ized.
To p View ACU+ IB2 Interface Board
Tem p. P robe # 1
Tem p. P robe # 2
+
J6
D ig ital Inputs
R e la y Ou tputs
N O C N C
5 3 1
to ACU+
J12
J11
S W 1
5 3 1 5 3 1 5 3 1
6 4 2 6 4 2 6 4 2 6 4 2
N O C N C N O C NC N O C N C
N O C N C N O C N C N O C N C NO C N C
J7J8J9
1357
2468
-
5 3 1 5 3 1 5 3 1
6 4 2 6 4 2 6 4 2
J3J 4J5
8 7 6 5 4 3 2 1
ON
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

4.4.5 Optional Alarm/Control Connections (to Primary Module only)

Alarm/control connections are made to the ACU+ Controller Customer Interface Board (IB2). The IB2 board provides connection points for digital inputs and relay outputs. System required connections are factory wired to the IB2 board. The customer may wire to un-used digital input and relay outputs, if desired. The IB2 board is located in an enclosure above the ACU+ Controller (see Figure 10 or Figure 11). To access these connections, loosen the captive fastener on the front of the enclosure and slide the IB2 board partially out of the shelf. Note that a wireway is provided to route the wires to the IB2 board, as shown in Figure 10 or Figure 11. Connect external alarm/control wiring to terminal blocks J3-J9 of the IB2 board, as required. Refer to Figure 17.
Figure 17 Alarm and Control Connections
Digital Input Connections
Up to eight (8) digital inputs may be connected to the IB2 board. Digital inputs that have factory connections are listed in Table 3. A blank column in Table 3 is also provided if you want to document custom connections to un-used digital inputs.
• Observe proper polarity per Table 3. Note that you must supply both paths for the digital input (either a positive or negative signal and the opposite polarity return path).
• The digital inputs can be configured to provide an alarm when the signal is applied (HIGH) or removed (LOW) (Local menu "Settings / System Dashboard / General"). Refer to Appendix A in the NetSure ITM Operation Manual (Section 6047).
Connecting a NetSure RDB Rack PDU (Power Distribution Unit) to the NetSure ITM: The following applies to all PDUs listed in the NetSure RDB Installation and Operation Manual (Section 6041).
Perform the following after installing and making the DC input and output connections to the PDU per Section 6041.
• Connect a 22 AWG lead from the circuit breaker alarm connector located on the last PDU to the (-) input of one of the unused digital inputs on the IB2 board. Connect a second 22 AWG lead from the NetSure ITM System Ground/Return (+) to the (+) input of the same digital input on the IB2
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
27
Section 6040
Page 34
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
board. Assign a unique signal name to this digital input (Web interface "Signal Information Modification Submenu"). Refer to Appendix A in the NetSure ITM Operation Manual (Section
6047).
Table 3 Programmable Digital Inputs
Programmable
Digital Input
1
2
3
4
5
6
7
Pin No. Dedicated to...
J3-1
J3-2 +
J3-3
J3-4 +
J3-5
J3-6 +
J4-1
J4-2 +
J4-3
J4-4 +
J4-5
J4-6 +
J5-1
J5-2 +
Available for Customer
Custom Digital Input
Available for Customer
Custom Digital Input
Available for Customer
Custom Digital Input
PCU EPO factory wired
Fan Supply Alarm factory wired
Fan Alarm factory wired
Available for Customer
Custom Digital Input
Customer
Custom Digital Input
8
J5-3
J5-4 +
J5-5
-­J5-6
Available for Customer
Custom Digital Input
internal connections
Relay Output Connections
The IB2 board provides eight (8) programmable alarm relays with Form-C contacts. Default relay assignments are documented in Table 4. A blank column in Table 4 is also provided if you want to document a custom configuration. Alarm relay contacts are rated for 2A @ 30VDC and 0.5A @ 125VAC (60W maximum power consumption).
• Each relay can be individually configured to activate for any system alarm condition.
• Refer to the NetSure ITM Operation Manual (Section 6047) for programming instructions.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
28
Section 6040
Page 35
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Table 4 Programmable Relay Outputs
Programmable
Relay Output
1
2
3
4
Pin No.
J6-5 NO All alarms programmed
J6-3 COM
J6-1 NC
J6-6 NO All alarms programmed
J6-4 COM
J6-2 NC
J7-5 NO All alarms programmed
J7-3 COM
J7-1 NC
J7-6 NO
J7-4 COM
J7-2 NC
Alarms Assigned
to this Relay (Default)
with alarm severity of
"critical alarm".
Relay de-energizes
during an alarm condition.
(See Note 1.)
with alarm severity of
"warning alarm". Relay energizes
during an alarm condition.
(See Note 1.)
with alarm severity of
"information alarm".
Relay energizes
during an alarm condition.
(See Note 1.)
Available for Customer
Custom Setting
Alarms Assigned
to this Relay (Custom)
J8-5 NO
5
6
7
8
J8-3 COM
J8-1 NC
J8-6 NO
J8-4 COM
J8-2 NC
J9-5 NO
J9-3 COM
J9-1 NC
J9-6 NO
J9-4 COM
J9-2 NC
Available for Customer
Custom Setting
Available for Customer
Custom Setting
Available for Customer
Custom Setting
Available for Customer
Custom Setting
Note 1: Relay 1 through Relay 3 are defined at the factory by logic equations factory programmed into the PLC Logic Function.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
29
Section 6040
Page 36
NetSure™ ITM with eSure™ Technology
ESC ENT
Ethernet Port (RJ-45)
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
IB2 Board DIP Switch Settings (for reference only)
Dip Switch SW1 on the IB2 board is used to set the communications address for this board (Table 5). In this system, both switches of SW1 are to be set in the OFF position. Refer to Figure 17 for SW1 location.
Table 5 IB2 Board Communications Address Settings
DIP Switch SW1
1 2
OFF OFF 1
ON OFF 2
OFF ON 3
ON ON na
Board Number
IB2 Board LED Indicators (for reference only)
The IB2 board has a green LED indicator which is lit in normal operation and flashes when the IB2 board is communicating with the Controller.

4.4.6 ACU + Controller Ethernet Connection (to Primary Module only)

The ACU+ Controller provides a Web Interface via an Ethernet connection to a TCP/IP network. An RJ-45 10BaseT jack is provided on the front of the ACU+ Controller for connection into a customer's network running TCP/IP. This jack has a standard Ethernet pin configuration scheme, twisted pair. Refer to Figure 10 or Figure 11 for location of the ACU+. Refer to Figure 18 for location and Table 6 for pinouts of the Ethernet port. Use shielded Ethernet cable (grounded at both ends). Note that the ACU+ Controller’s RJ-45 jack is connected to chassis ground.
You can access the Web pages of the power system locally by using a "crossover" or "straight" cable connected directly between your PC and the ACU+.
Figure 18 ACU+ Controller RJ-45 Ethernet Port
Table 6 ACU+ Controller RJ-45 Ethernet Port
Port Pin
Number
Name Definition
1 Tx+ Write Signal +
2 Tx- Write Signal -
3 Rx+ Read Signal +
4 -- no connection
5 -- no connection
6 Rx- Read Signal -
7 -- no connection
8 -- no connection
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
30
Section 6040
Page 37
NetSure™ ITM with eSure™ Technology
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

4.4.7 Optional Emergency Power Off (EPO) Connection (to Primary Module only)

The DC UPS module has an Emergency Power Off (EPO) function operated by a remote contact provided by the User.
WARNING
The EPO circuit operates with -48Vdc. There is -48Vdc present on the terminals the EPO jumper connects to. There is -48Vdc present on these same terminals that an external EPO switch will be connected to.
NOTE
The external EPO switch wiring must be double-insulated. The wire must be 600V, 18-16 AWG stranded for maximum runs between 82 and 197 feet (25-60m), respectively.
If the EPO function is desired, locate the EPO jumper in the Primary Module (see Figure 19). Remove the EPO jumper (the jumper connects from the bottom terminal of the EPO terminal block and the bottom of EPO Fuse F11). Connect a customer provided external normally closed switch between the bottom terminal of the EPO terminal block and the bottom of the EPO Fuse.
The following occurs when the EPO switch is opened.
• The battery LVD contactor in each DC UPS module opens, disconnecting the battery from each module.
• If the ACU+ "EPO Enabled" option is set to YES, the PCUs in each DC UPS module shut down after 5 seconds. If the ACU+ "EPO Enabled" option is set to NO, PCUs remain running.
NOTE
The Emergency Stop action within the DC UPS module opens the battery LVD contactor and (if programmed in the ACU+) shuts down the PCUs.
It does not internally disconnect the input power supply. To disconnect ALL power to the DC UPS module, open the upstream feeder breaker(s) when the remote EPO is activated.
It does not disconnect the SM-BRC. The SM-BRC will still be powered by the batteries.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
31
Section 6040
Page 38
NetSure™ ITM with eSure™ Technology
DETAIL A
Components Behind Cover
EPO Fuse
EPO
Te rminal
Block
EPO
Jumper
SUITABLE FOR M OUNT ING ON CONCRET E
OR OTHER NON-CO MBUS TIBLE SURF ACE ONLY.
12
1 11
22
Front View
(door removed)
SEE DETAIL A
To p DC Distribution Feed Shown, Bottom DC Distribution Feed Similar
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 19 EPO Jumper Location

4.4.8 Battery Connections

Batteries are factory installed and connected. Final connections to the batteries are made in the procedure presented in 6.2 - Final Battery Connections.

4.5 Making Module-to-Module -48VDC and Ground/Return Interconnections (if system consists of multiple DC UPS modules)

Note that all hardware is provided.

4.5.1 -48Vdc and Ground/Return Busbar Interconnects

1. Install the provided -48Vdc Interconnect Busbar(s) between the -48Vdc busbars located in each
adjacent DC UPS module. Refer to Figure 20 (DC UPS module with bottom feed DC distribution) and Figure 21 (DC UPS module with top feed DC distribution). Torque to the values listed in the illustrations.
2. Install the provided Ground/Return Interconnect Busbar(s) between the ground/return busbars
located in each adjacent DC UPS module. Refer to Figure 20 (DC UPS module with bottom feed DC distribution) and Figure 21 (DC UPS module with top feed DC distribution). Torque to the values listed in the illustrations.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
32
Section 6040
Page 39
Battery Compartment and Base
Removed in Illustrations for Clarity
-48Vdc Busbar
-48Vdc Busbar
Hardware Build-Up M10 Nut (electro zinc treatment with bright chromate)
M10 Belleville Lock Washer DIN 6796-10.5 STEEL (electro zinc treatment with bright chromate)
To rque to 418 in-lbs (47.3 Nm)
Ground/Return
Busbar
Ground/Return Busbar
Hardware Build-Up M10 x 30mm Bolt (electro zinc treatment with bright chromate)
M10 Belleville Lock Washer DIN 6796-10.5 STEEL (electro zinc treatment with bright chromate)
To rque to 418 in-lbs (47.3 Nm)
-48Vdc Interconnect Busbar
(can be installed on left and/or
right side of module)
Ground/Return Interconnect Busbar
(can be installed on left and/or
right side of module)
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 20 Module-Module Interconnect Busbars (DC UPS Module with Bottom Feed DC Distribution)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
33
Section 6040
Page 40
NetSure™ ITM with eSure™ Technology
Battery Compartment and Base
Removed in Illustrations for Clarity
-48Vdc Busbar
-48Vdc Busbar
SUITABLE FOR MO UNT ING O N CO NCRET E
OR OTHER NON-COM BUST IBLE SURF ACE O NLY.
Hardware Build-Up M10 Nut (electro zinc treatment with bright chromate)
M10 Belleville Lock Washer DIN 6796-10.5 STEEL (electro zinc treatment with bright chromate)
To rque to 418 in-lbs (47.3 Nm)
Ground/Return Busbar
Hardware Build-Up M10 x 30mm Bolt (electro zinc treatment with bright chromate)
M10 Belleville Lock Washer DIN 6796-10.5 STEEL (electro zinc treatment with bright chromate)
To rque to 418 in-lbs (47.3 Nm)
-48Vdc Busbar
Ground/Return Busbar
-48Vdc Interconnect Busbar (can be installed on left and/or right side of module)
Ground/Return Interconnect Busbar (can be installed on left and/or right side of module)
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 21 Module-Module Interconnect Busbars (DC UPS Module with Top Feed DC Distribution)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
34
Section 6040
Page 41
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

4.6 Making Alarm/Control Interconnections between Modules (if system consists of multiple DC UPS modules)

Make the following module-to-module alarm/control interconnections as required. Refer to Figure 23 for an interconnect diagram. See also the Cabinet Interconnections illustration in Figure 24, Figure 25, and Figure 26.

4.6.1 RS-485 Module-to-Module Interconnect

Primary Module to 1st Expansion Module (Skip if No 1st Expansion Module)
1. Locate the long RS-485 interconnect cable (RPM 628 415/2) (yellow/white wire twisted pair) coiled
up on the right side of the Primary Module.
2. Route this cable through the openings in the sides of the cabinets to the 1st Expansion Module.
3. Connect this cable to the mating RS-485 interconnect cable connected to the SM-AC located in the
1st Expansion Module (yellow/white wire twisted pair).
1st Expansion Module to 2nd Expansion Module (Skip if No Additional Expansion Module)
1. Locate the long RS-485 interconnect cable (RPM 628 415/2) (yellow/white wire twisted pair) coiled
up on the right side of the 1st Expansion Module.
2. Route this cable through the openings in the sides of the cabinets to the 2nd Expansion Module.
3. Connect this cable to the mating RS-485 interconnect cable connected to the SM-AC located in the
2nd Expansion Module (yellow/white wire twisted pair).
Additional Expansion Modules (Skip if No Additional Expansion Module)
1. Make similar connections between each adjacent Expansion Module.
SM-BRC RS-485 Termination Resistor Setting in Last DC UPS Module
1. A jumper on the SM-BRC circuit board is used for selecting a termination resistor for the RS-485
connection. RS-485 termination is disabled when the jumper is across pins 1 and 2 (default). It is enabled when the jumper is across pins 2 and 3. See Figure 22 for the location of the jumper.
In most cases, RS-485 termination is not necessary because maximum baud rate is 19200 bps (default is 9600). RS-485 termination is recommended when intermittent communications occur.
If there are intermittent communications errors, it is recommended to set the termination resistor on the SM-BRC in the last module to the enabled position (jumper between pins 2 and 3) instead of the factory disabled position (jumper between pins 1 and 2).
Figure 22 SM-BRC RS-485 Jumper Locations

4.6.2 CAN-Bus Module-to-Module Interconnect

CAN-Bus End Resistor (move only if more than one DC UPS module)
1. Locate the short CAN-Bus interconnect cable jumper connected to the SM-DU+ in the Primary
Module (black/white wire twisted pair located behind the SM-DU+ sheetmetal enclosure and
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
35
Section 6040
Page 42
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
exiting the top of the SM-DU+). Remove the CAN-Bus End Resistor plugged into this cable only if there are Expansion Modules.
2. Locate the short CAN-Bus interconnect cable jumper connected to the SM-DU in the last (end)
Expansion Module (black/white wire twisted pair located behind the SM-DU sheetmetal enclosure). Plug the CAN-Bus End Resistor into this cable.
1st Expansion Module to Primary Module
1. Locate the long CAN-Bus interconnect cable (RPM 628 351/1) coiled up on the right side of the 1st
Expansion Module (black/white wire twisted pair).
2. Route this cable through the openings in the sides of the cabinets to the Primary Module.
3. Route this cable through the top lip of the Primary Module’s SM-DU+ sheetmetal enclosure.
4. Connect this cable to the mating CAN-Bus interconnect cable connected to the SM-DU+ in the
Primary Module (black/white wire twisted pair located behind the SM-DU+ sheetmetal enclosure and exiting the top of the SM-DU+).
2nd Expansion Module to 1st Expansion Module
1. Locate the long CAN-Bus interconnect cable (RPM 628 351/1) coiled up on the right side of the
2nd Expansion Module (black/white wire twisted pair).
2. Route this cable through the openings in the sides of the cabinets to the 1st Expansion Module.
3. Connect this cable to the mating CAN-Bus interconnect cable connected to the SM-DU in the 1st
Expansion Module (black/white wire twisted pair located behind the SM-DU sheetmetal enclosure).
Additional Expansion Modules
1. Make similar connections between each remaining Expansion Module.

4.6.3 BLVD Module-to-Module Interconnect

1st Expansion Module to Primary Module
1. Locate the BLVD control interconnect cable (RPM 628 466/3) coiled up on the right side of the 1st
Expansion Module (the Expansion Module’s BLVD cable is factory connected to the bottom connector on the LVD Relay Board, and exits at the back of the LVD Relay Board’s sheetmetal enclosure).
2. Route this cable through the openings in the sides of the cabinets to the Primary Module.
3. Route the cable through the back of the Primary Module’s LVD Relay Board sheetmetal
enclosure.
4. Connect this cable to the mating BLVD control interconnect cable (RPM 628 465/3) in the
Primary Module (the Primary Module’s BLVD cable is factory connected to the bottom connector located on the LVD Relay Board).
2nd Expansion Module to 1st Expansion Module
1. Locate the BLVD control interconnect cable (RPM 628 466/3) coiled up on the right side of the 2nd
Expansion Module (the Expansion Module’s BLVD cable is factory connected to the bottom connector on the LVD Relay Board, and exits at the back of the LVD Relay Board’s sheetmetal enclosure).
2. Route this cable through the openings in the sides of the cabinets to the 1st Expansion Module.
3. Route the cable through the back of the 1st Expansion Module’s LVD Relay Board sheetmetal
enclosure.
4. Connect this cable to the mating BLVD control interconnect cable (RPM 628 465/3) in the 1st
Expansion Module (the 1st Expansion Module’s BLVD cable is factory connected to the bottom connector located on the LVD Relay Board).
Additional Expansion Modules
1. Make similar connections between each remaining Expansion Module.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
36
Section 6040
Page 43
NetSure™ ITM with eSure™ Technology
SUITABLE FOR MO UNTIN G O N CO NCRE TE
OR OTHER NON-C OMB UST IBLE SURF ACE ONLY .
Black/White Wire Twisted Pair
(RPM 628 351/1)
located coiled up on right side of
Expansion Module cabinet (mating
connector located behind Detail A cover)
Yellow/White Wire Twisted Pair
(RPM 628 415/2)
located coiled up on right side of
Primary Module cabinet (mating
connector located on SM-AC)
BLVD Control Cable
(RPM 628 465/3)
BLVD Control Cable (RPM 628 466/3) located coiled up on right side of Expansion Module cabinets
Cable Runs this Direction
LVD Relay Board
LVD
Relay
Board
12
1 11
22
Front View Primary Module (door removed)
SEE DETAIL A
SUITABLE FOR MO UNTIN G O N CO NCRE TE
OR OTHER NON-C OMB UST IBLE SURF ACE ONLY .
12
1 11
22
Front View
Expansion Module
(door removed)
SEE DETAIL A
Note: Cabinets must be installed next to each other, shown apart here for clarity of control cabling interconnections.
SM-AC
Cable Runs this Direction
Cable Runs this Direction
CAN-Bus
RS-485
BLVD
DETAIL A
Components Behind Cover
CAN-Bus Black/White Wire Twisted Pair (Primary Module)
BLVD Control Cable (RPM 628 465/3)
SM-DU+
LVD Relay Board
DETAIL A
Components Behind Cover
BLVD Control Cable
(RPM 628 466/3)
(Expansion Modules Only)
BLVD Control Cable (RPM 628 465/3)
SM-DU+
LVD Relay Board
Can-Bus End Resistor (if no Expansion Module)
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 23 Alarm/Control Cable Interconnects (cont’d on next page)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
37
Section 6040
Page 44
NetSure™ ITM with eSure™ Technology
Black/White Wire Twisted Pair
(RPM 628 351/1)
located coiled up on right side of
2nd Expansion Module cabinet (mating
connector located on SM-DU)
BLVD Control Cable
(RPM 628 465/3)
BLVD Control Cable (RPM 628 466/3) located coiled up on right side of Expansion Module cabinets
Cable Runs this Direction
SM-DU (Expansion Modules only)
LVD Relay Board
LVD
Relay
Board
Front View
1st Expansion Module
(door removed)
SUITABLE FOR MO UNTIN G O N CO NCRE TE
OR OTHER NON-C OMB USTI BLE SURF ACE ONLY.
12
1 11
22
Front View
2nd Expansion Module
(door removed)
SEE DETAIL A
SUITABLE FOR MO UNTIN G O N CO NCRE TE
OR OTHER NON-C OMB USTI BLE SURF ACE ONLY .
12
1 11
22
SEE DETAIL A
Note: Cabinets must be installed next to each other, shown apart here for clarity of control cabling interconnections.
SM-AC
Cable Runs this Direction
Cable Runs this Direction
CAN-Bus
RS-485
BLVD
Connectors Located on SM-DU (top view)
CAN-Bus Black/White Wire Twisted Pair (Expansion Module)
Can-Bus End Resistor (moved from Primary Module to last Expansion Module)
DETAIL A
Components Behind Cover
CAN-Bus Black/White Wire Twisted Pair (Primary Module)
BLVD Control Cable (RPM 628 465/3)
SM-DU+
LVD Relay Board
DETAIL A
Components Behind Cover
BLVD Control Cable
(RPM 628 466/3)
(Expansion Modules Only)
BLVD Control Cable (RPM 628 465/3)
SM-DU+
LVD Relay Board
Yellow/White Wire Twisted Pair
(RPM 628 415/2)
located coiled up on right side of
1st Expansion Module cabinet (mating
connector located on SM-AC)
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 23 Alarm/Control Cable Interconnects (cont’d from previous page)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
38
Section 6040
Page 45
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 24 System Configuration and Communications Connections
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
39
Section 6040
Page 46
NetSure™ ITM with eSure™ Technology
Relative position for the cabinets
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 25 Cabinet Interconnections
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
40
Section 6040
Page 47
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 26 Signal Cabling and Switch Settings
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
41
Section 6040
Page 48
NetSure™ ITM with eSure™ Technology
!
Handle
Captive
Fastener
Safety
Latch
Pin
Safety
Latch
Release
Handle
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
5.0 I
NSTALLING
PCU
S
WARNING
In order to prevent damage to the latching mechanism, do not use excessive force on the PCU handle when pushing the PCU into the cabinet.
PCUs are hot swappable. They can be installed with the system operating.
Procedure
1. Place the PCU into an unoccupied mounting position without sliding it in completely.
2. Push the “Safety Latch Release” located on the front of the PCU "UP". Refer to Figure 27 for an illustration.
3. Gently push the PCU into the mounting location until it stops.
4. Note that the PCU will NOT be completely seated in the mounting location until the next step is performed.
5. Push the “Safety Latch Release” located on the front of the PCU "DOWN". Gently push the PCU into the mounting location until it is completely seated.
6. Push the PCU’s handle in and secure the PCU to the cabinet by tightening the captive fastener located on the handle.
7. Repeat the above steps for each PCU being installed in the DC UPS module.
8. After the PCUs are physically installed, they are ready for operation immediately after power is supplied to them.
Figure 27 PCU Handle and Safety Latch
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
42
Section 6040
Page 49
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
6.0 S
TART-UP INSTRUCTIONS

6.1 General

The NetSure ITM DC UPS system must be fully installed and commissioned before startup. The start-up procedure consists of making final battery connections, initially starting the system, and verifying system operation. Emerson Network Power will perform ALL start-up procedures, including making final battery connections.
THE FOLLOWING ARE GENERAL GUIDELINES FOR EMERSON TECHNICIANS.

6.2 Final Battery Connections

6.2.1 Introduction

Each DC UPS module contains a battery compartment. The battery compartment consists of six battery shelves that house (4) 6V batteries, each. Batteries are factory installed and wired for (3)
-48VDC battery strings. Also provided is a 800A battery disconnect fuse for each string.

6.2.2 Safety

Special care should be taken when working with the batteries associated with the DC UPS module. See the precautions in the battery instruction manual and in Battery Compartment Precautions at the beginning of these instructions.

6.2.3 Connecting Batteries

Battery Leads
The batteries are factory installed and most battery interconnections are factory made. The following interconnections need to made during installation to complete the battery electrical path to the DC UPS module. Refer to Figure 28 for the battery connections torque value for the Emerson EB4 6V200 battery.
1. Refer to Figure 28 and connect the supplied Battery Interconnect Links between the indicated Battery Shelves. For each connection:
a. Install the faston lugs on top of the battery links as shown in Figure 28. Note that battery
monitoring leads are factory connected to the faston lugs and each faston lug is insulated for shipping. Observe proper polarity when attaching the faston lugs with factory wiring to the
battery posts. b. Tighten the connections to the torque indicated in Figure 28. c. Place the plastic cover over the battery terminals and interconnect link.
2. On all remaining battery terminals (factory connections); remove the plastic covers, check the torque, then reinstall the plastic covers. Torque to value indicated in Figure 28.
DO NOT INSTALL THE BATTERY FUSES BEFORE THE EQUIPMENT HAS BEEN COMMISSIONED AND THE PROCEDURE IN "6.3.1 - Initially Starting the DC UPS System and Verifying System Operation" IS PERFORMED.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
43
Section 6040
Page 50
NetSure™ ITM with eSure™ Technology
DC UPS Module Rear View (B atte r y Compartment)
Final Battery Shelf Interconnections
1) Connect supplied Battery Interconnect Links between these points.
2) Place faston lugs with factory wired battery monitoring leads on top of interconnect link as shown in illustration. DO NOT PLACE BETWEEN LINK AND BATTERY TERMINALS.
3) Torque to 97 in-lbs (11 Nm).
4) Place plastic cover over battery terminals and interconnect links.
6) On all remaining battery terminals (factory connections); remove the plastic covers, check the torque, then reinstall the plastic covers.
Bolt
Lock Washer
Typical Hardware Build-Up
Flat Washer
Faston Lug
Battery
Interconnect
Link
Battery Terminal
Typical Monitoring Lead Connections
Lead Labeled
1.5+ (Battery One Link)
2.5+ (Battery Two Link)
3.5+ (Battery Three Link)
Red
Monitoring
Lead
Black Monitoring Lead
Temperature Sensor Lead (white and white/black leads)
Faston Lug
Faston Lug
Battery
Interconnect
Link
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 28 Making Final Battery Shelf Battery Interconnect Link Connections
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
44
Section 6040
Page 51
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Perform InterCell Resistance Calibration
Use the Alber software to run an Intercell Resistance test.
1. After making final battery connections and before installing battery fuses, perform the following: a. Disconnect the RS-485 cable from the back of the SM-BRC. b. Connect the USB cable from the SM-BRC to your computer. c. Start the ALBER Configurator.
2. Click on the "Connect to Monitor" button at the top of the screen.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
45
Section 6040
Page 52
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
3. Select "USB" as the Connection Type and click on "Connect to Monitor" at lower right.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
46
Section 6040
Page 53
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
4. Click "Setup" on the menu tree found at the left of the window.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
47
Section 6040
Page 54
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
5. Select the "General Tab" and fill in the following: a. System Configuration (String x Cells x Voltages): 3x8x6V.
(note that this is a pull down selection)
b. RS-485/Module Address (1-254).
For ITM Module 1, set to 120. For ITM Module 2, set to 121. For ITM Module 3, set to 122. For ITM Module 4, set to 123.
c. RS-485 Baud Rate: 19200 bps.
(note that this is a pull down selection)
6. Press "Apply".
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
48
Section 6040
Page 55
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
7. Click"OK" in the pop-up window.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
49
Section 6040
Page 56
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
8. Select "Real-Time Data" in the menu tree at the left.
9. Click on the "Internal R" tab at top of screen.
10. Check the box "Set baseline" and click on the "Start" button.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
50
Section 6040
Page 57
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
11. Click on "Yes" in the pop-up window.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
51
Section 6040
Page 58
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
12. The unit will start calibration. One at a time each green bar will appear for each battery block.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
52
Section 6040
Page 59
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
13. When the last green bar appears, a pop-up will appear indicating that the test is done. Click "OK".
14. Select "Disconnect from Monitor" at the top of the screen.
15. Remove the USB cable from your computer and re-install the RS-485 cable into the SM-BRC.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
53
Section 6040
Page 60
NetSure™ ITM with eSure™ Technology
!
Field Battery Monitoring Lead Connections
The DC UPS module is factory shipped with the mating halves of the SM-BRC’s Load Inputs terminal blocks 1, 3, 5, 7 and 2, 4, 6, 8 disconnected. When ready to place the module into service, locate and plug the mating halves of the SM-BRC’s Load Inputs terminal blocks 1, 3, 5, 7 and 2, 4, 6, 8 here.
Rear View SM-BRC
Connector labeled 2, 4, 6, 8.
Connector labeled 1, 3, 5, 7.
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Field Battery Monitoring Lead Connections to the SM-BRC Unit
Battery monitoring leads are factory connected to the mating halves of the SM-BRC unit’s Load Inputs terminal blocks labeled 1, 3, 5, 7 and 2, 4, 6, 8. The DC UPS module is factory shipped with the mating halves of the SM-BRC’s Load Inputs terminal blocks labeled 1, 3, 5, 7 and 2, 4, 6, 8 disconnected. This is to prevent the batteries from discharging when the system is not powered.
When the DC UPS module is to be placed into service, open the battery compartment’s top rear access panel. Locate the disconnected connectors labeled "Load Inputs 1, 3, 5, 7" and "Load Inputs 2, 4, 6, 8". Plug these connectors into the back of the SM-BRC, as shown in Figure 29. Repeat this procedure for each DC UPS module in the system.
NOTE
If the system is powered down for an extended period of time, remove the Battery Fuses and disconnect the SM-BRC’s "Load Inputs Terminal Block 1, 3, 5, 7" and "Load Inputs Terminal Block 2, 4, 6, 8" so that the batteries do not discharge.
Figure 29 Field Battery Monitoring Lead Connections to the SM-BRC Unit

6.3 Initially Starting and Verifying DC UPS System Operation

Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
WARNING
During this procedure the output terminals will become live.
If any load equipment is connected to the DC UPS module output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, then ensure that it is safely isolated from the DC UPS module output terminals.
54
Section 6040
Page 61
NetSure™ ITM with eSure™ Technology
English
09:2 0:20
Flo at
53 .4 V 40 4 A
Auto N oAlarm
M A IN M E NU
S tatu s Settings Energy Saving Manual CustomizeMenu
E N T
E S C
Main Screen Main Menu
Press or to browse through MAIN MENU.
Press ENT to enter Sub-Menu.
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

6.3.1 Initially Starting the DC UPS System and Verifying System Operation

The NetSure ITM DC UPS must be fully installed and commissioned before startup.
Procedure
1. Open the front door on each DC UPS module.
2. Apply AC input power to each DC UPS module by closing the external AC disconnect(s) or protective device(s) that supplies power to each DC UPS module. If the dual AC input feed option is furnished, there will be two (2) devices per DC UPS module.
3. On each DC UPS module, close the main AC input circuit breaker. If the dual AC input feed option is furnished, a safety latch is provided on the circuit breakers to prevent both circuit breakers from being placed in the ON position. Slide the latch over to allow the desired circuit breaker to be turned ON.
4. On each DC UPS module, close all PCU AC input circuit breakers. Note that each circuit breaker feeds two (2) PCUs.
5. In the Primary DC UPS module, once the ACU+ Controller is powered on, a starting... screen appears followed by a language screen.
Press “” or “” to select the desired language. Press ENT to confirm the selection. If no key is pressed within 30 seconds, the ACU+ Controller automatically selects the displayed language.
Refer to the NetSure ITM Operation Manual (Section 6047) for ACU+ Controller local menu operating instructions.
Once initialized, the ACU+ Main Screen displays.
6. With an external meter, measure battery voltage.
7. Adjust the system’s float voltage to within approximately 0.5V of battery voltage.
8. In each DC UPS module, install the three battery disconnect fuses.
9. Adjust the system’s float voltage to 54.5Vdc.
10. In each DC UPS module, place each distribution circuit breaker to the ON position or install all distribution fuses.
11. In the Primary DC UPS module, verify that there are no alarms present on the ACU+ local display.

6.3.2 Setting Common Controller Parameters

Navigate through the controller menus and submenus to set common controller parameters (time, date, IP address, etc.). Refer to Section 3.5 of the NetSure ITM Operation Manual (Section 6047) for common tasks performed locally.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
55
Section 6040
Page 62
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

6.3.3 Changing the Numbering Scheme of the PCUs

Follow these procedures to change how the ACU+ identifies (numbers) the PCUs installed in the system. These procedures are performed from the ACU+ Controller’s local display and keypad.
Initial Installation (numbering the PCUs per their Physical Location in the System)
1. Go to Main Menu / Settings / PCU.
2. Press Enter.
3. Navigate down to PCU 1 (001).
4. Press Enter.
5. Look for the PCU installed in the system with a flashing LED.
6. Press Enter.
7. Press the Up or Down Arrow until the number displayed is the same as the physical position of the PCU with the flashing LED.
8. Press Enter.
9. Press ESC.
10. Navigate down to the next PCU and repeat steps 4 thru 10.
11. After all PCUs are renumbered, go to Main Menu / Control / PCU / All PCU Ctrl.
12. Press Enter.
13. Navigate down to Confirm Posi/PH.
14. Select Yes, then press Enter.
15. Verify that the ACU+ now numbers the PCUs via their physical position in the system by going to Main Menu / Status / PCU and scrolling down to each PCU listed in the display. Compare the PCU number highlighted in the display with the physical position of the PCU with the flashing LED.
Swapping PCUs Physical Positions without Adding or Removing the Number of PCUs
1. If you swap PCUs, the ACU+ numbering stays with the PCUs. For example, if PCU in physical position 1 is swapped with PCU in physical position 2, the ACU+ numbers the PCU now installed in physical position 1 as 2 and the PCU now installed in physical position 2 as 1. To correct this, repeat the steps shown in the "Initial Installation" procedure for ONLY the two PCUs that were swapped.
Removing a PCU without Replacing It
1. Remove the PCU.
2. Go to Main Menu / Control / PCU / All PCU Ctrl.
3. Press Enter.
4. Navigate down to Confirm Posi/PH.
5. Select Yes, then press Enter.
6. Now, when you view the voltage and current for the removed PCU, the fields will be highlighted in BLACK to indicate this PCU is not present. Also, the WEB interface shows that PCU information GREYED out.
7. If you now re-install that same PCU in it's previous physical position, it will retain its previous slot number.
Replacing a Previously Installed PCU with a New PCU
1. Remove a previously installed PCU.
2. Clear the PCU Lost Alarm.
3. Install the new PCU.
4. The new PCU is automatically assigned the same numbering as the original PCU it replaced.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
56
Section 6040
Page 63
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
7.0 S
PECIFICATIONS AND TECHNICAL DATA

7.1 Agency Approvals

The NetSure ITM DC UPS system has the following agency approval ratings:
• EN 60 950-1:2006
• UL 60 950-1
• UL 1801 (This unit is UL Listed ["c UL"] as a DC Power Distribution Center. This unit meets the requirements of CSA 22.2, No. 225 and is tested and Certified by UL ["c UL"] as a Custom Built Power Distribution Center.)

7.2 Environmental

The NetSure ITM DC UPS system is designed to operate under the following environmental conditions without damage or degradation in electrical operating characteristics:
Table 7 DC UPS System Environmental Characteristics
System Operating Temperature
System Storage Temperature (optimal) -4°F to +77°F (-20°C to +25°C)
Relative Humidity 0 to 95%, non-condensing
Operating Elevation 6562 ft (2000m) at full power
Audible Noise < 60dB
Heat Rejection at Full Load 18,096 BTU/hr. (5.3kW) per module
EMI FCC Class A
+23°F to +95°F (-5°C to +35°C) Recommended Operation with Battery (Air Inlet): +68°F to +77°F (+20°C to +25°C)

7.3 Mechanical Characteristics

Table 8 DC UPS System Mechanical Characteristics (per module)
Form Factor Rack
Unit Dimensions
Unit Weight 3240 lb (1470 kg)
Airflow 560 CFM (950 m3/h)
Cable Entry Bottom or Top
Color Black (Z-0350)
Protection Grade (with open/closed front doors)
Inches: 83H x 24W x 41D (Millimeters: 2100H x 600W x 1040D)
IP 20
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
57
Section 6040
Page 64
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Table 9 Shipping Dimensions and Weights
System
Size
Module
w/
Batteries
PCUs
70KW 140KW 210KW 280KW
(1) Module:
Inches: 92H x 29W x 47D Millimeters: 2337H x 737W x 1194D Weight: 3307lb (1500kg)
12 PCUs:
Pallet (12 PCUs): Inches: 22H x 44W x 48D Millimeters: 559H x 1118W x 1219D Weight: 258lb (117kg)
(2) Modules, per module:
Inches: 92H x 29W x 47D Millimeters: 2337H x 737W x 1194D Weight: 3307lb (1500kg)
24 PCUs:
Pallet (24 PCUs): Inches: 38H x 44W x 48D Millimeters: 965H x 1118W x 1219D Weight: 486lb (220kg)
(3) Modules, per module:
Inches: 92H x 29W x 47D Millimeters: 2337H x 737W x 1194D Weight: 3307lb (1500kg)
36 PCUs:
1st Pallet (30 PCUs): Inches: 46H x 44W x 48D Millimeters: 1168H x 1118W x 1219D Weight: 600lb (272kg)
2nd Pallet (6 PCUs): Inches: 14H x 44W x 48D Millimeters: 356H x 1118W x 1219D Weight: 144lb (65kg)
(4) Modules, per module:
Inches: 92H x 29W x 47D Millimeters: 2337H x 737W x 1194D Weight: 3307lb (1500kg)
48 PCUs:
1st Pallet (30 PCUs): Inches: 46H x 44W x 48D Millimeters: 1168H x 1118W x 1219D Weight: 600lb (272kg)
2nd Pallet (18 PCUs): Inches: 30H x 44W x 48D Millimeters: 762H x 1118W x 1219D Weight: 372lb (169kg)

7.4 Monitoring Capability

Standard: Web-based monitoring, alarm reporting via SNMP, and integration with Liebert SiteScan via SiteLink-E module.
Optional: Energy Master Remote Supervision available from Emerson.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
58
Section 6040
Page 65
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

7.5 Electrical Characteristics

7.5.1 Termination Type, Recommended Wire Size, Recommended Lugs

AC Input
Table 10 AC Input and AC Input Grounding (per DC UPS module)
AC Input
Input
Voltage
480Vac
380Vac 116A
Input
Voltage
480Vac
400Vac
1
Wire sizes based on recommendations of the American National
Maximum
Input
Current
92A
110A
Bolt Size
5/16" (M8)
Terminal
Type
Screw Clamp
AC Input Grounding
Recm.
Wire
1
Size
1/0 AWG
Recm.
Wire
1
Size
2/0 AWG 2"400Vac
Conduit
Size
2"
Conduit Size
Recommended Lug
(Thomas & Betts P/N)
Compression
1-Hole; 3/8" Bolt
54109
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 90°C conductor temperature operating in ambient of 35°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
Equipment grounding conductors must be provided with the AC input conductors supplied to the module. Frame ground terminals must be connected to earth ground, not power system neutral. Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper wire. When aluminum or copper clad aluminum grounding conductor is used, refer to Table 250 122 for increased conductor size. For operation in countries where the NEC is not recognized, follow applicable codes.
Cabinet Frame Grounding
Table 11 Cabinet Frame Grounding (per DC UPS module)
Bolt Size
3/8" (M10) 6 AWG 54136
Recm.
Wire Size
Recommended Lug
(Thomas & Betts P/N)
Compression
1-Hole; 3/8" Bolt
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
59
Section 6040
Page 66
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
DC Distribution
Table 12 DC Distribution (Distribution Circuit Breaker Option - per circuit breaker position)
OCP
Device
Rating
100A 80A
150A 120A
175A 140A
200A 160A
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI)
Maximum
Output
Current
@ 54V
Terminal
Load
Return
Load
Return
Load
Return
Load
Return
Bolt Size
3/8" (M10)
Recm.
Wire Size
1/0 AWG
1/0 AWG
2/0 AWG
3/0 AWG
Lug Requirement
1
2-Hole, 1" Centers 54209
1-Hole 54109
2-Hole, 1" Centers 54209
1-Hole 54109
2-Hole, 1" Centers 54210
1-Hole 54110
2-Hole, 1" Centers 54211
1-Hole 54111
(Thomas & Betts P/N)
Recommended Lug
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 75°C conductor temperature operating in ambient of 35°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes. Sizes assume one layer of cables in open cable tray. Alternate sizing may be required for other installation configurations. Refer to the NEC or contact Emerson Services (contact information provided at the end of this document).
Table 13 DC Distribution (Distribution Fuse Option - per fuse position)
OCP
Device
Rating
200 160
500 400
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI)
Maximum
Output
Current
@ 54V
Terminal
Load
Return
Load
Return
Bolt Size
1/2" (M12)
Recm.
Wire Size
3/0 AWG
(2) 250 kcmil
Lug Requirement
1
2-Hole, 1.75" Centers
Recommended Lug
(Thomas & Betts P/N)
54265
(2) 54275
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at 75°C conductor temperature operating in ambient of 35°C was used. For other operating ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes. Sizes assume one layer of cables in open cable tray. Alternate sizing may be required for other installation configurations. Refer to the NEC or contact Emerson Services (contact information provided at the end of this document).
Battery
The battery cables are factory provided and sized accordingly.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
60
Section 6040
Page 67
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Alarm/Control
Table 14 Alarm/Control
Screw Size Recm. Wire Size
M2 24-16 AWG

7.5.2 Power Ratings

Table 15 Power Ratings
Power
Rating
Full 70 kW 70 kW 70 kW 70 kW
N + 1 64 kW 70 kW 70 kW 70 kW
Primary
Module 1

7.5.3 AC Input Specifications

Table 16 AC Input Specifications
Phase 3
Power Factor 0.99 at full load, 0.98 at 50% load
Frequency 45-65 Hz
Input Voltage – Nominal 400 / 480V, 3 wire + ground
Input Voltage – Range
Internal AC Input Breaker Size 150A
Internal AC Input Breaker AIC Rating
Max Input Current / Module
Inrush Current
Total Harmonic Distortion <5% from 50-100% of load
Expansion
Module 2
304-530 VAC; shall withstand up to
600 VAC input without damage.
Nominal 480V: 115A @ 384V; 92A @ 480V Nominal 400V: 138A @ 320V; 110A @ 400V Nominal 380V: 145A @ 304V; 116A @ 380V
Inrush current does not exceed 150% of the
rated input steady state peak value.
Expansion
Module 3
65,000A
Expansion
Module 4
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
61
Section 6040
Page 68
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

7.5.4 DC Output Specifications

Table 17 DC Output Specifications
Normal Operation: -54.5 VDC (battery float)
Voltage
System Efficiency
Energy Optimization Mode; Intelligent Power Matching
Distribution Types
Figure 30 System Efficiency Curve
Allows operation at near-peak efficiency
22 Circuit Breakers, 100-200A each;
Optional: 6 Fuses, 100-500A each
Nominal: -48VDC
Range: -42 to -58 VDC
96% peak
(system level including
branch distribution losses).
See Figure 30.
down to 5% overall load.
Regulation (PCU)
a. Voltage Regulation: ±1%. b. Load Regulation: ±0.5%. c. Line Regulation: ±0.1%. d. Overshoot at Startup: ±1%. e. Dynamic Response (at rated input and output voltage values):
•Response time is 200 µs, and the overshoot is 5% for load changes at 50%-25%-50% and 50%­75%-50%.
•Overshoot or undershoot is 5% and within ±1% of the regulation band, 4 ms at 50 µs for load changes at 10%-90% and 90%-10%.
Filtering
Typical readings were taken at nominal input voltage, nominal output voltage, 50% load, and 25 degrees C ambient.
a. Wide Band Noise: Complies with Telcordia GR-947-CORE.
1. Typically 55 millivolts peak-to-peak. Does not exceed 200 millivolts peak-to-peak
2. Typically 15.9 millivolts rms. Does not exceed 100 millivolts rms.
Hold Up Time
10 ms (The DC voltage is allowed to decrease to 42V from 54V during the test.)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
62
Section 6040
Page 69
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

7.5.5 Battery Specifications

Table 18 Battery Specifications
Type VRLA, Emerson Excellence EB4, 200 Ah
Arrangement 3 strings; eight 6V blocks per string
Per 6V Block
Capacity - Ah
Acid Weight - lb. (kg) 14.9 (6.7) 357.6 (160.8)
Total Acid Volume - gal. (L) 0.97 (3.67) 23.2 (87.8)
Free Acid Volume - gal. (L) 0.1 (0.37) 0.23 (0.88)
Lead Weight - lb. (kg) 54.7 (24.8) 1312.8 (595.2)
Total Weight - lb. (kg) 77.2 (35.0) 1852.8 (840)
Backup Time See backup time table at various loads.
Case Material UL94-HB or UL94-V0
Design Life 15 years @ 68°F (20°C); 10 years @ 77°F (25°C)
Recharge Time (to 97% of nominal capacity)
MECHANICAL
Dimensions Depth: Width: Height:
CAPACITY
Constant Power Discharge @ 20°C (w/cell):
End Voltage Operating Time To End Voltage (minutes)
Per Cell 600 480 360 300 240 180 120 60
Constant Current Discharge @ 20°C (A):
End Voltage Operating Time To End Voltage (minutes)
Per Cell 600 480 360 300 240 180 120 60
OTHER TECHNICAL FEATURES
• Valve-regulated lead-acid battery with AGM technology.
• Validation in accordance with IEC 896-2.
Less than 3 hours for > 35% load; Less than 4 hours > 15% load.
377 mm, including connectors and covers 135 mm, including ventilation spacing 250 mm
200 4800
Per 70 kW Module
(24 blocks)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
63
Section 6040
Page 70
NetSure™ ITM with eSure™ Technology
Battery Back-up Time (minutes)
Load
Single module
70kW
Two modules
140kW
Three modules
210kW
Four modules
280kW
10kW 130 300 480 630 20kW 55 130 210 300 30kW 28 90 130 180 40kW 17 55 90 130 50kW 12 41 70 100
64kW 7 24 50 75 70kW 3 21 43 69
80kW 17 34 55
90kW 14 27 47 100kW 12 22 40 110kW 10 19 34 120kW 8 17 28
134kW 6 16 25 140kW 3 14 22
150kW 12 19 160kW 10 17 170kW 9 15 180kW 8 14 190kW 7 13
204kW 4 11 210kW 2 10
220kW 9 230kW 9 240kW 8 250kW 7 260kW 6
274kW 3 280kW 1
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
64
Section 6040
Page 71
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

7.5.6 Advanced Control Unit Plus (ACU+) Controller

Display LCD with 4 × 16 Characters
Communication RS232, RS485, Ethernet, USB
Protocol HTTP, SNMP, EEM, SocTpe, RSoc
Local Indicators Green LED: Illuminates when CPU is working
Inputs
correctly. Red LED: Illuminates when there is a critical or warning alarm. Yellow LED: Illuminates when there is an information alarm.
5 Analog Inputs
14 Digital Inputs
Outputs
1 Output
DC Power Plant Alarms AC Mains Failure, PCU Failure, High Voltage
Monitoring Capability SNMP/Web Based Monitoring Included;

7.5.7 SM-DU+

Communication RS485, CAN, RS232
Local Indicators Green LED: Illuminates when CPU is working
Inputs 22 Current Measurements
System Output Voltage Battery Voltage Battery Temperature Ambient Temperature Battery Shunt (for Battery Current)
3 Battery Fuses 2 DC Distribution Fuses
8 Generic Digital Inputs (where D15 reserved for
"Fan CB Tripped" and D16 for "Fan Alarm")
1 Contactor Status
Contactor Control
Shutdown, Fan Failure, Thermal Derating (of PCU output due to high temperature)
Compatibility with SiteScan Available
EnergyMaster Remote Monitoring (contact your Emerson Representative)
correctly. Flashes (1/3Hz) to indicate communication fault with controller. Flashes (1Hz) to indicate communicating with controller. Red LED: Illuminates when there is a critical or warning alarm. Yellow LED: Illuminates when there is an information alarm.
22 DC Fuse/Breaker Status Detection
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
65
Section 6040
Page 72
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

7.5.8 SM-DU (used in Expansion Modules only in place of Controller)

Communication RS485, CAN, RS232
Local Indicators Green LED: Illuminates when CPU is working
Inputs
correctly. Flashes (1/3Hz) to indicate communication fault with controller. Flashes (1Hz) to indicate communicating with controller. Red LED: Illuminates when there is a critical or warning alarm. Yellow LED: Illuminates when there is an information alarm.
Output Voltage Output Current 3 Battery Fuse Alarms 1 Fan Alarm 2 DU Fuse Alarms
Outputs

7.5.9 SM-AC

Communication RS232 / RS485
Local Indicators Green LED: Illuminates when CPU is working correctly.
Digital Inputs
12 Digital Inputs Alarms/Events
Analog Inputs
3 Mains/Phase Voltage 3 Phase Current 1 Battery Voltage 1 Temperature 1 Network Frequency 3 Apparent Powers 3 Active Powers 3 Reactive Powers 3 Current Distortions Energy
Digital Outputs
4 Relay Outputs

7.5.10 SM-BRC

Contactor Control
Red LED: Illuminates when there is an alarm.
0-600 VAC, 0-346 VAC 0-5 A External Current Transformer 0-36 VDC
-25°C to +80°C / -13°F to +176°F 45-65 Hz kVA (calculated in software) kW (calculated in software) kVA (calculated in software) 0-100% (calculated in software), THD (Total Harmonic Distortion) kWh (calculated in software)
24VDC / 250VAC, 5A
Battery Cells Monitored
Inputs
24 Battery Cells
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
Reports...
• Total battery voltage.
• Battery current.
• 24 cell/block voltages.
• Ambient temperature (battery compartment)
66
Section 6040
Page 73
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

7.5.11 Standard Features

Type of Power Conversion Circuit: High frequency.
Float Charging Output Mode: In this mode of operation, system output voltage is constant and
output current does not exceed the current limit setting. During normal operation, the battery is not required to furnish load current and remains in a fully charged condition.
Float voltage is set via the Controller, default @ 54.5V for furnished batteries.
NOTE
If the current demanded by the load exceeds the current limit setting of the system, the battery is required to furnish the difference in load current and begins discharging.
Input Protection:
a. Input Over/Under Voltage Protection: The PCU shuts down and its protection indicator
(yellow) illuminates when the input voltage is lower than 260VAC or higher than 530VAC. This condition is reported to the power system Controller and the power system Controller processes the alarms accordingly.
b. Input Fusing: Input fuse is provided in each PCU. This fuse is not customer replaceable.
Output Protection:
a. Current Limiting: The maximum current delivered by the system is programmed via the
Controller. The Controller automatically adjusts the current limit circuit on each PCU so that this value is not exceeded. If a PCU fails, the Controller automatically resets each remaining PCU's current limit point to maintain this value. The Controller also insures that the current limit circuit on any PCU is not set above 110% of its capacity. The default current limit setting is the sum of each installed PCU's output rating. If an additional PCU is added to the system, the system current limit is automatically increased by the rating of the new PCU and the new current limit value is displayed.
The current limiting point is set via the Controller.
b. Output Fusing: Output fuse is provided in each PCU. If a fuse opens, local and remote PCU
Fail Alarms activate. This fuse is not customer replaceable.
c. High Voltage Shutdown:
1. Internal: If PCU output voltage exceeds an adjustable preset value, the PCU shuts down.
•After approximately 5 seconds, the PCU automatically restarts. If PCU output voltage again exceeds the high voltage shutdown value within 5 minutes, the PCU shuts down and locks out. Manual restart is then required. If the PCU does not experience a high voltage condition within the 5 minute time period, the restart circuit is reset.
•Only the PCU causing the high voltage condition shuts down.
•The high voltage shutdown point is set via the Controller.
2. Backup: If PCU output voltage exceeds a second (non-adjustable) value, the PCU shuts down and locks out regardless of load. Manual restart is then required. The fixed hardware HVSD is 59.5V (within the range of 58.5 to 60V).
High Temperature Protection:
a. When the PFC board temperature is higher than 85°C, the PCU turns off. When the PFC
board temperature is lower than 75°C, the PCU resumes normal operation, and the hysteresis is at least 10°C.
b. When the difference between “ambient temperature" and "PFC board temperature” is greater
than 5°C, the PCU turns off. When the difference between “ambient temperature" and "PFC board temperature” is less than 2°C, the PCU resumes normal operation, and the hysteresis is at least 3°C.
c. When the DC board temperature is higher than 105°C, the PCU turns off. When the DC board
temperature is lower than 95°C, the PCU resumes to normal operation, and the hysteresis is at least 10°C.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
67
Section 6040
Page 74
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Fan Fault Protection: An alarm will be generated upon a fan fault. In such cases, the fault indicator (red) on the PCU front panel will flash and the PCU will also inhibit its output. Auto­recovery is enabled upon the clearing of the corresponding fault.
PFC Over/Under Voltage: The PCU will shut down when its bus voltage is higher than the over voltage set point or is lower than the under voltage set point. During such conditions, the PCU does not output any power and its protection indicator (yellow) will light up.
Active Load Sharing (PCU): The PCU uses advanced digital active load sharing technology that maintains balancing to within ±3A. The difference in the average current between PCUs is <±3A for loads in the 10 to 100% range. The Controller also has a PCU Load Sharing function.
Startup Time: The PCU has two startup modes:
a. Normal Soft Start Time: The duration from the time when the PCU is powered on to the
time when the PCU provides output voltage is <8s.
b. Current Walk-In: The rise time of the PCU output voltage is >8s at 90% of the rated load,
and the maximum time is 90s at 100% of the rated load.
Hot Swappable: The PCU is designed to be plug-and-play. The PCU can be inserted or removed from a live DC power system with no damage. When the PCU is plugged into the system, the system output voltage will not be affected.
Cooling: Each PCU contains a fan for forced convection cooling.
Fan Control: When the PFC bus voltage is within a normal range, the built-in processor adjusts the
fan’s speed according to the PCU’s internal temperature and output current. For example, a higher temperature or output current will increase the fan speed. Above 45°C at full load, the fan operates at full speed. When the PFC bus voltage is abnormal, such as very low bus voltage, the fan turns off.
Communication Failure: The PCU’s protection indicator (yellow) will flash should it experience a communication failure. The failure information will be reported to the Controller and the Controller will process the failure accordingly. During a communication failure, in order to protect the battery, the PCU output voltage will automatically adjust to 53.5 V (this is a default value which can be modified using the Controller). The PCU will revert to normal operation once normal communication is restored.
Unbalance of PCU Output Current: When the output current of the PCUs in a DC power system is unbalanced, the PCU having the unbalanced output current will be identified automatically and its protection indicator (yellow) will turn on.
The failure information will be reported to the Controller and the Controller will process the failure accordingly.
Local Status and Alarm Indicators:
a. Power (Green) b. Protection (Yellow) c. Alarm (Red) d. A 10-segment Green LED is located on the front panel to represent output current, each
segment represents 10A.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
68
Section 6040
Page 75
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
NetPerform™ Optimization Services
At Emerson Network Power, we understand the importance of reliable equipment – it’s critical to both your business and your bottom line. That is why we offer a wide array of services to meet all of your network infrastructure needs.
Technical Su p p or t
Email
Phone
Services - De s i gn, Dep l o ym e nt & Op t im i z a ti o n
Email
Phone
FreedomCare
DCpower.TAC@Emerson.com OSP.TAC@Emerson.com
1.800.800.5260
ES.Services@Emerson.com Provides quotes and bid responses, order
1.800.800.1280, option 7
Secure.EmersonNetworkPower.com
Answers technical product and system questions; determines status of warranties and contractual agreements for repair.
placement and scheduling for design, and deployment and optimization services. Download service & maintenance reports online.
Spare Parts
Email
Phone
DCpower.Spares@Emerson.com OSP.Spares@Emerson.com
1.800.800.1280, option 5
Pricing and PO processing of spare parts, including but not limited to breakers, cables, fuses, rectifier fans, misc. breaker and fuse panels, enclosure fans, doors & switches, etc.
DC Power Depo t Re pa i r
Email
Phone
DCpower.Repair@Emerson.com Creates and processes RMAs, determines lead
1.800.800.1280, option 6
times and pricing, provides repair shipping information and status.
DC Power Pro d u c t T r ai n i ng
Email
Phone
DCpower.Training@Emerson.com Requests for quotes, order placement and
1.800.800.1280, option 8
scheduling.
For More Information
To learn more about service offerings from Emerson Network Power, please contact your sales representative, call 1-800-800-1280 option 7, email ES.Services@Emerson.com or visit
www.EmersonNetworkPower.com/EnergySystems.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
69
Section 6040
Page 76
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Emerson Network Power, Energy Systems, North America, Inc. assumes no responsibility and disclaims all liability for damages result­ing from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Emerson Network Power, Energy Systems, North America, Inc. This document is the property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc. Any copying, use or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Learn more about the NetSure™ ITM DC UPS from Emerson at: EmersonNetworkPower.com/NetSureITM.
EmersonNetworkPower.com/EnergySystems (North America) EmersonNetworkPower.eu/EnergySystems (EMEA)
© Emerson Network Power, Energy Systems, North America, Inc. 2013.
Business-Critical Cont inuity™, Emerson Network Pow er™, the Emerson Network Power logo, Emerson™ and Co nsider it Solved are service m arks and trademarks of Emer son Electric Co. EnergyMaster™, eSure ™, NetPerform™, NetReach™ , NetSpan™, NetSure™ and NetXtend™ are trademarks of Emerson Network Power, E nergy Systems, North Ameri ca, Inc.
Spec. No: 582145500 Section 6040 Model: NetSure™ ITM Issue AB, April 8, 2013
Loading...