Emerson 582145500 User Manual

A Technical Manual from the experts
in Business-Critical Continuity
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Specification Number: 582145500 Model: NetSure™ ITM
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
This page is intentionally blank.
Spec. No: 582145500 Section 6040 Model: NetSure™ ITM Issue AB, April 8, 2013
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
TABLE OF CONTENTS
I
MPORTANT SAFETY INSTRUCTIONS
R
ELATED DOCUMENTATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 I
NSPECTING THE EQUIPMENT AND STORING FOR DELAYED INSTALLATIONS
. . . . . . . . . . . . .4
1.1 External Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Internal Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Storing for Delayed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.0 I
NSTALLATION DRAWINGS AND RECOMMENDED TOOLS AND TEST EQUIPMENT
. . . . . . . . . . .6
2.1 Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Row-Based Installation Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Recommended Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.0 P
OSITIONING THE
DC UPS S
YSTEM
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 General Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 General Guidelines for Positioning the DC UPS Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.2 Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.3 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Floor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Considerations in Moving the DC UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4.1 Transporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4.2 Moving a DC UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.4.3 Final Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.5 Overhead Cable Tray Rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.6 Front and Rear Bottom Panel Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.6.1 Bottom DC Distribution Feed (Bottom Cabled) Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.6.2 Top DC Distribution Feed (Top Cabled) Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.0 E
LECTRICAL CONNECTIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 Wiring Information and Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.1 Cable Lengths (Floor or Cabinet Top to Connection Point Inside DC UPS Module) . . . . . . . 19
4.1.2 Recommended Wire Sizes, Recommended Lugs, and Torque Requirements . . . . . . . . . . . . . 19
4.1.3 Wiring Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.3 Wiring Connections Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.4 Making Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4.1 Cabinet Grounding Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4.2 DC Distribution Ground/Return Busbar Grounding Connection . . . . . . . . . . . . . . . . . . . . . . 23
4.4.3 DC Output Distribution Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.4.4 AC Input Power Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.4.5 Optional Alarm/Control Connections (to Primary Module only) . . . . . . . . . . . . . . . . . . . . . . . 27
4.4.6 ACU + Controller Ethernet Connection (to Primary Module only) . . . . . . . . . . . . . . . . . . . . . 30
4.4.7 Optional Emergency Power Off (EPO) Connection (to Primary Module only) . . . . . . . . . . . . 31
4.4.8 Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
i
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
4.5 Making Module-to-Module -48VDC and Ground/Return Interconnections
(if system consists of multiple DC UPS modules). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.5.1 -48Vdc and Ground/Return Busbar Interconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.6 Making Alarm/Control Interconnections between Modules
(if system consists of multiple DC UPS modules). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.6.1 RS-485 Module-to-Module Interconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.6.2 CAN-Bus Module-to-Module Interconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.6.3 BLVD Module-to-Module Interconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5.0 I
6.0 S
NSTALLING
TART-UP INSTRUCTIONS
PCUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2 Final Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.2 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2.3 Connecting Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.3 Initially Starting and Verifying DC UPS System Operation. . . . . . . . . . . . . . . . . . . . . . . . . 54
6.3.1 Initially Starting the DC UPS System and Verifying System Operation . . . . . . . . . . . . . . . . 55
6.3.2 Setting Common Controller Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.3.3 Changing the Numbering Scheme of the PCUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.0 S
PECIFICATIONS AND TECHNICAL DATA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.1 Agency Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.2 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.3 Mechanical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.4 Monitoring Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.5 Electrical Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.5.1 Termination Type, Recommended Wire Size, Recommended Lugs. . . . . . . . . . . . . . . . . . . . . 59
7.5.2 Power Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.5.3 AC Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
7.5.4 DC Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
7.5.5 Battery Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
7.5.6 Advanced Control Unit Plus (ACU+) Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
7.5.7 SM-DU+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
7.5.8 SM-DU (used in Expansion Modules only in place of Controller) . . . . . . . . . . . . . . . . . . . . . . 66
7.5.9 SM-AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.5.10 SM-BRC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.5.11 Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
ii
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
FIGURES
Figure 1 Outline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 2 Bottom DC Distribution Feed Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 3 Top DC Distribution Feed Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 4 NetSure™ ITM Row-Based DC UPS System Installation Example . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5 Emerson Floor Stands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 6 Mounting Locations for Overhead Cable Tray Rails. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 7 Installing Front and Rear Bottom Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 8 Installing Air Duct Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 9 Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 10 Wiring Connections Locations (DC UPS Module with Bottom Feed DC Distribution) . . . . . . . . 21
Figure 11 Wiring Connections Locations (DC UPS Module with Top Feed DC Distribution) . . . . . . . . . . . 22
Figure 12 Cabinet Grounding Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 13 DC Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 14 AC Input Power Connection Routing Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 15 Installing Conduit Fittings when AC is Fed from the Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 16 AC Input Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Figure 17 Alarm and Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 18 ACU+ Controller RJ-45 Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 19 EPO Jumper Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 20 Module-Module Interconnect Busbars (DC UPS Module with Bottom Feed DC Distribution) . . 33
Figure 21 Module-Module Interconnect Busbars (DC UPS Module with Top Feed DC Distribution) . . . . . 34
Figure 22 SM-BRC RS-485 Jumper Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 23 Alarm/Control Cable Interconnects (cont’d on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 24 System Configuration and Communications Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 25 Cabinet Interconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 26 Signal Cabling and Switch Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 27 PCU Handle and Safety Latch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 28 Making Final Battery Shelf Battery Interconnect Link Connections . . . . . . . . . . . . . . . . . . . . . . 44
Figure 29 Field Battery Monitoring Lead Connections to the SM-BRC Unit . . . . . . . . . . . . . . . . . . . . . . . . 54
Figure 30 System Efficiency Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
iii
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
TABLES
Table 1 DC UPS Module "Base Configuration Part Numbers"
and "Configured System Spec. Numbers" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 Distance to Connection Points inside the DC UPS Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 3 Programmable Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 4 Programmable Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 5 IB2 Board Communications Address Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 6 ACU+ Controller RJ-45 Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 7 DC UPS System Environmental Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 8 DC UPS System Mechanical Characteristics (per module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Table 9 Shipping Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 10 AC Input and AC Input Grounding (per DC UPS module) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 11 Cabinet Frame Grounding (per DC UPS module). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Table 12 DC Distribution (Distribution Circuit Breaker Option - per circuit breaker position) . . . . . . . . . 60
Table 13 DC Distribution (Distribution Fuse Option - per fuse position) . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Table 14 Alarm/Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 15 Power Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 16 AC Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 17 DC Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Table 18 Battery Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
iv
Section 6040
NetSure™ ITM with eSure™ Technology
!
!
!
!
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
I
MPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your NetSure™ ITM Row-Based DC UPS system.
Read this manual thoroughly before installing the DC UPS system. Retain this manual for use by
installing personnel.
WARNING
The DC UPS system should be installed by a qualified technician in accordance with the information contained in this document.
WARNING
Special safety precautions are required for procedures involving handling and installation of the DC UPS system. Observe all safety precautions in this manual before handling or installing the DC UPS system.
WARNING
Exercise extreme care when handling DC UPS modules (cabinets) to avoid equipment damage or injury to personnel. The DC UPS module weighs 3240 lb. (1470 kg), fully loaded.
Be aware of module weight and locate center of gravity symbols before handling the DC UPS module. Test lift and balance the module before transporting. Never tilt module more than 10 degrees from vertical.
WARNING
All power and control wiring should be installed by a qualified electrician. All power
and control wiring must comply with the National Electrical Code (NEC) and applicable local codes.
Maximum load must not exceed that shown on the DC UPS module rating label.
Maximum output short circuit current is 7000 amperes.
WARNING
High Ground Leakage Current: Ground connection is essential before connecting the input supply.
This equipment must be grounded in accordance with the NEC and applicable local codes.
CAUTION
Ground leakage current exceeds 3.5 mA and is less than 30 mA.
Transient and steady-state ground leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous residual current circuit breakers (RCCBs) or residual current devices (RCDs).
RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses.
Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
1
Section 6040
NetSure™ ITM with eSure™ Technology
!
!
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
CAUTION
This equipment is fitted with RFI suppression filters.
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the User must correct at his own expense.
WARNING
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Battery Compartment Precautions
Batteries are factory installed in the DC UPS module. Final battery connections will be made by Emerson after the DC UPS module is installed. DO NOT MAKE BATTERY CONNECTIONS. The following precautions apply to the battery compartment that is part of the DC UPS module.
WARNING
Special safety precautions are required for procedures involving handling, installing, and servicing batteries. Observe all battery safety precautions presented here and in the battery instruction manual. These precautions should be followed implicitly at all times.
WARNING
A battery can present a risk of electrical shock and high short circuit current. Servicing of batteries should be performed or supervised only by properly trained and qualified personnel knowledgeable about batteries and the required precautions.
The following precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Use certified and well maintained insulated tools.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If the battery is inadvertently grounded, remove source from ground. Contact with any parts of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).
• Risk of explosion if battery is replaced with an incorrect type or if polarity is reversed. When replacing batteries, replace with the same manufacturer and type, or equivalent. See your local Emerson representative for a list of approved batteries.
• Dispose of used batteries according to the instructions provided with the batteries. Do not dispose of batteries in a fire. They may explode.
In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes, and is toxic. If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
2
Section 6040
NetSure™ ITM with eSure™ Technology
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
WARNING
The DC UPS module’s internal batteries are connected and energized even if the DC UPS module is turned OFF. Battery disconnect fuses are provided inside the DC UPS module. To minimize the risk of injury, remove the battery disconnect fuses before any off-line servicing is performed on the unit.
WARNING
DO NOT REMOVE BATTERY STRAPS. If a battery cell is replaced, ensure the battery strap is replaced and appropriately tighten.
• Battery compartments contain non-spillable batteries.
• Keep units upright.
• Do not stack.
• Do not tilt.
Failure to heed this warning could result in smoke, fire, or electric hazard.
Call Emerson before moving DC UPS modules (after initial installation).
R
ELATED DOCUMENTATION
• System Operation Document (Section 6047).
• Site Planning Data and System Drawings Document (Section 6037).
• Emerson Excellence Range VRLA Battery (31020591)
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
3
Section 6040
NetSure™ ITM with eSure™ Technology
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
1.0 I
NSPECTING THE EQUIPMENT AND STORING FOR DELAYED INSTALLATIONS

1.1 External Inspections

1. While the DC UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Emerson Network Power (number located on last pages of this document) to inform them of the damage claim and the condition of the equipment.
2. Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Emerson representative immediately.

1.2 Internal Inspections

1. Remove any packaging material, then visually examine the DC UPS system for transit damage, both internally and externally. Report any such damage to the shipper and to Emerson immediately.
2. Check the nameplate inside the DC UPS module (located on the front top right side with front door open) to verify that the "base configuration part number" and the "configured system spec. number" correspond to the units ordered. Record the DC UPS module identification numbers and serial number in the front of this manual. This information is necessary should service be required. See Table 1.
NOTE
The "base configuration part number" determines how the DC UPS module is physically configured and the "configured system spec. number" determines how the DC UPS module has been set up.
3. Check for loose connections or unsecured components in the module.
4. Check for shipping damage to internal components.

1.3 Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 95%. The storage area must protect the DC UPS system from excessive moisture.
For optimal battery life, store at a temperature between
Environmental).
CAUTION
If the batteries must remain disconnected from the DC UPS module for more than six (6) months, the batteries must be recharged before use. To charge the batteries, the batteries must be connected to the DC UPS module and the DC UPS module must be connected to utility power and started up by qualified personnel.
-4°F to +77°F (-20°C to +25°C)
(see 7.2 -
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
4
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Table 1 DC UPS Module "Base Configuration Part Numbers"
and "Configured System Spec. Numbers"
Base Configuration Part Numbers
Part Number Module
FAB8010542/2 Primary Top (22) Circuit Breaker 1
FAB8010542/1 Primary Top (22) Circuit Breaker 2
FAB8010542/4 Primary Top (6) Fuse 1
FAB8010542/3 Primary Top (6) Fuse 2
FAB8010540/2 Primary Bottom (22) Circuit Breaker 1
FAB8010540/1 Primary Bottom (22) Circuit Breaker 2
FAB8010540/4 Primary Bottom (6) Fuse 1
FAB8010540/3 Primary Bottom (6) Fuse 2
FAB8010543/2 Expansion Top (22) Circuit Breaker 1
FAB8010543/1 Expansion Top (22) Circuit Breaker 2
FAB8010543/4 Expansion Top (6) Fuse 1
FAB8010543/3 Expansion Top (6) Fuse 2
FAB8010541/2 Expansion Bottom (22) Circuit Breaker 1
Distribution
Feed
Distribution
No. of AC
Inputs
FAB8010541/1 Expansion Bottom (22) Circuit Breaker 2
FAB8010541/4 Expansion Bottom (6) Fuse 1
FAB8010541/3 Expansion Bottom (6) Fuse 2
Configured System Spec. Numbers
Spec. Number Description
582145500-M1 Primary Module
582145500-M2 1st Expansion Module
582145500-M3 2nd Expansion Module
582145500-M4 3rd Expansion Module
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
5
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
2.0 I
NSTALLATION DRAWINGS AND RECOMMENDED TOOLS AND TEST EQUIPMENT

2.1 Installation Drawings

The diagrams in this section illustrate the key mechanical and electrical characteristics of the NetSure ITM DC UPS system.
General Notes Applicable to All Illustrations
1. All dimensions are in inches (millimeters).
2. Minimum clearance above unit required for air exhaust is 8 in. (203mm).
3. Keep module within 10 degrees of vertical while handling.
4. Top and bottom cable entry options available.
5. Color - black.
6. Unit bottom is structurally adequate for forklift handling.
7. M12 mounting holes used for seismic anchoring or floor stand.
NOTE
If floor stand is used, the weight of the unit must be supported under all casters.
8. The Primary Module includes side panels. For installations consisting of Expansion Module(s), one side panel on the Primary Module must be removed and be placed on the end Expansion Module.
9. Leveling feet are not designed to carry the full weight of the module.
10. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.
11. Control wiring, output cabling, and input cabling must be run separately.
12. Aluminum and copper-clad aluminum cables are not recommended.
13. All wiring is to be in accordance with the NEC and applicable local codes.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
6
Section 6040
NetSure™ ITM with eSure™ Technology
Notes:
1. Dimensions areininches (millimeters).
2. Weight (fully loaded): 3240 lbs/1470 kg.
3. Heat Rejection: 18096 BTU/hatfullload (per module).
4. May be installedon concreteslaborraised floor.
23.62 (600)
Battery Compartment
Conduits for AC Inputs
41.34
(1050)
DC Power System Compartment
Z
X
Y
To pCabledVersion X=11.81 (300) Y=26.38(670) Z=36.61 (930)
Bottom CabledVersion X=11.81 (300) Y=26.38(670) Z=40.55 (1030)
CENTER OF GRAVITY
26.38 (670)
CG
11.81 (300)
(Bottom cabled) CG
11.81 (300)
36.61
(930)
40.55
(1030)
CG (top cabled)
23.62 (600)
Battery Compartment
Conduits for AC Inputs
41.34
(1050)
DC Power System Compartment
26.38 (670)
CG
11.81 (300)
See Detail A for Bott
om
DC UPS MODULE WITH
TOP FEED DC DISTRIBUTION
DC UPS MODULE WITH
BOTTOM FEED DC DISTRIBUTION
To p View
To p View
Front View
84.33
(2142)
top
cabled
84.72
(2152)
bottom
cabled
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 1 Outline Drawing
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
7
Section 6040
NetSure™ ITM with eSure™ Technology
35.43 (900)
19.68 (500)
12.99 (330) - 13.39 (340)
39.65 (1007)
31.22 (793)
0.59 (15)
0.28 (7)R
35.43 (900)
Hole through foot (4x) for
anchoring on raised floo
r
Anchoring bracket (4x)
used on concrete floo
r
Anchoring bolts (4x) used on raised
floor
ANCHORING
Hilti HSV 1/2X4 1/2: Item No.: 00384687
M12 x 1.75 x 70 Metric Socket Head Cap Screw. Plain Finish with Allen Drive (hex drive) / Coarse thread. Grade 12.9
.
M12 X 1.75 Metric Hex Nuts - Grade 10.9 / Coarse Thread / Zinc Plated
.
M12 Metric Flat Washer. Grade 10.9 / Zinc. D=28mm or 11/8".
(4X)
(4X)
(8X)
(8X
)
Corresponding ½” Imperial Fasteners Can Also be Used
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 1, Detail A
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
8
Section 6040
NetSure™ ITM with eSure™ Technology
Battery Compartment
BFU
Distr.
Distr.
Raised Floor
HotAisle
Cold Aisle
A
AirFlow
Note2
Side View
Support Stand
½” (12mm) Floor
Anchoring Bolts
(4 places)
To p
Front
Notes:
1. Dimensions areininches (millimeters).
2. Do not block airintake openings.
3. Minimum under floor space for underfloor output cable runs: A=1f (300mm).
4. Run cables not to block air openings for battery cooling.
Battery
Compartment
Conduits for
AC Inputs
DC Power System
Compartment
35.43
(900)
17.72 (450)
8.86
(225)
9.84
(250)
19.68 (500)
9.84
(250)
8.86
(225)
Optional Floor Opening for Battery Cooling
PCUs
PCUs
PCUs
PCUs
PCUs
PCUs
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 2 Bottom DC Distribution Feed Modules
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
9
Section 6040
NetSure™ ITM with eSure™ Technology
Note2
Distr.
Distr.
HotAisle
Cold Aisle
AirFlow
Concrete Floor (slab)
Side View
Notes:
1. Dimensions areininches (millimeters).
2. Do not block airintake openings.
To p
Battery
Compartment
DC Power
System
Compartment
Openings for Output Cables
Front
CableTraySupports if Mounted on To pof Module
Front View
CableTray
CableRun
Battery Compartment
PCUs
PCUs
PCUs
PCUs
PCUs
PCUs
To pView
Battery
Compartment
Openings for Output Cables
CableTray
23.62 (600)
BFU
½” (12mm) Floor
Anchoring Bolts
(4 places)
35.43
(900)
19.68 (500)
Air Exchange (keep clear)
AC Input
Conduit Openings
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Figure 3 Top DC Distribution Feed Modules
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
10
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

2.2 Row-Based Installation Example

The NetSure ITM DC UPS system provides the flexibility to meet the needs of any data center.
The NetSure ITM DC UPS system is delivered fully configured for quick and easy field installation. Multiple DC UPS modules can easily be connected on site in order to increase capacity. Each module takes only 24" (w) x 41" (d) of floor space, including batteries and primary distribution. The NetSure ITM DC UPS system is typically installed in the middle or at the end of a row of server racks. This makes the system uniquely flexible and scalable. Deploy only the capacity that is initially needed; modules can be added at any time to existing units on the data center floor.
Figure 4 depicts a top distribution feed installation powering IT racks. Depending on your site and budget requirements, the NetSure ITM DC UPS solution can either be installed as a single deployment, or incrementally by row. In either scenario, DC distribution cabling to each rack is reduced by placing the NetSure ITM DC UPS in-the-row.
Whatever the physical layout of your data center, the NetSure ITM DC UPS allows for maximum space for IT equipment. With DC UPS building block modules, you can mix and match configurations and standard layouts to fit your available space.
Figure 4 NetSure™ ITM Row-Based DC UPS System Installation Example
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
11
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

2.3 Recommended Tools and Test Equipment

The following tools and test equipment are recommended to install the DC UPS modules.
• Non-Contact Voltage Detector
• Digital Multimeter (DMM), 0 to 60 V dc, 0 to 600 V ac
• NO-OX-ID-A or Approved Equivalent
• Lineman's Scissors
• Lineman's Strippers
• Lineman's Cutters
• Electrician's Insulated Screwdrivers, Phillips, No. 1 and 2
• Electrician's Insulated Screwdrivers, Flat-Blade, Small and Large
• Adjustable Torque Wrench, 1/2" Drive, 0 in-lb to 800 in-lb
• Ratchet, 1/2" Drive
• Insulated Nut Driver Set
• Crimping Tool with Dies from 350 kcmil to 2 AWG
• Torx Screwdrivers or Bits: TX10 and TX20
• 17 mm Wrench or Socket for M10 Bolts and Nuts (for circuit breaker distribution)
• 19 mm Wrench or Socket for M12 Bolts and Nuts (for fuse distribution)
• 24 mm Wrench for Pallet.
• Hexagonal mm Bit for the Air Duct.
• Hexagonal Bit for the AC Input Breaker.
Contact Emerson for full turn key installation quote.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
12
Section 6040
NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
3.0 P
OSITIONING THE
This section describes the environmental and mechanical considerations that must be taken into account when planning the positioning and cabling of the DC UPS system. This section also provides procedures for physical installation of the DC UPS cabinet.
Because every site is unique, some subsections present a guide to general procedures and practices that should be observed by the installing engineer, rather than step-by-step installation instructions.
DC UPS S
YSTEM

3.1 General Requirements

• The installer should be familiar with the installation requirements and techniques to be used in securing the DC UPS module (cabinet) to the floor. It is up to the customer to determine the requirements for anchoring the cabinet to the specific type of floor at the site, select proper anchors, and to investigate the proper use of the anchor.
• This product is intended only for installation in a Restricted Access Location on or above a non­combustible surface.
• Front and rear access is required for installation and operation (see Clearances in this section).

3.2 General Guidelines for Positioning the DC UPS Modules

Choose a location for the DC UPS system that offers:
• Easy connection to inputs, outputs, and alarms.
• Air circulation sufficient to expel heat produced by the DC UPS system.
• Protection against moisture and excessive humidity.
• Protection against dust and other particulate matter.
• Enough space to service the DC UPS system (see Clearances in this section).
• Compliance with fire prevention regulations and practices.

3.2.1 Cable Entry

DC distribution and alarm cables enter the DC UPS module from the top or bottom, depending on module configuration (top distribution feed or bottom distribution feed).
AC input cables can enter either at the top or bottom. Conduit openings are provided in both locations.

3.2.2 Environmental Considerations

Before installing the DC UPS system, verify that the room satisfies the environmental conditions stipulated in 7.2 - Environmental, paying particular attention to the ambient temperature and air exchange system. Also refer to 7.2 - Environmental for details on heat dissipation.
The DC UPS system should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range +23°F to +95°F (-5°C to +35°C).
• Batteries are installed in the DC UPS module’s battery compartment. Temperature is a major factor in determining battery life and capacity. Battery manufacturers recommend an operating temperature of 77°F (25°C). Ambient temperatures higher than this reduce battery life; temperatures lower than this reduce battery capacity. For optimal battery performance and service life, inlet air temperature to the battery compartment (from the front of the system) should be maintained between +68°F to +77°F (+20°C to +25°C).
The DC UPS module is cooled by internal fans. Cooling air enters the system through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 8 in. (203mm).
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
13
Section 6040
NetSure™ ITM with eSure™ Technology
P/N 547823
36” Tall Floor Stand
P/N 547822
24” Tall Floor Stand
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.2.3 Mechanical Considerations

The DC UPS system can be comprised of up to four (4) modules (cabinets), depending upon your power requirements. All modules used are the same size and are designed to be positioned side-by­side to form an aesthetically appealing equipment suite. The system always contains one (1) Primary Module. For increased power demands, up to three (3) Expansion Modules may be added. Locate the Primary Module at the far left or far right of the row. Remove the side panel from the Primary Module from the side that will face adjacent Expansion Modules. Place the first Expansion Module next to the Primary Module. Place additional Expansion Modules (if required) next to each other. Install the side panel removed from the Primary Module to the open side of the last Expansion Module in the row.
NOTE
When the DC UPS system consists of multiple modules, the switches inside the modules are pre-set at the factory to identify the module as the Primary Module, 1st Expansion Module, 2nd Expansion Module, or 3rd Expansion Module. When placing modules, refer to the nameplate identification number (see Table 1) to ensure the Primary Module is placed on the end, and Expansion Modules are place in sequential order.
Clearances
There are no ventilation grilles on the sides of the DC UPS module. The DC UPS modules may be placed with the sides touching or against a wall.
To enable routine tightening of power terminations within the DC UPS module, make sure there is sufficient clearance in front and rear of the DC UPS module to permit free passage of personnel and that the front door can be fully opened.
Leave a minimum of 8 in. (203mm) between the top of the DC UPS module and the ceiling to permit adequate air circulation above the unit. Emerson recommends against using air conditioning or other systems that blow air onto the top of the unit.
Leave a minimum of 36 in. (914 mm) between the back of the DC UPS module and a wall to permit adequate air circulation for the battery compartment fans and facilitate maintenance access.

3.3 Floor Installation

Refer also to 3.1 - General Requirements.
The diagrams in 2.0 - Installation Drawings and Recommended Tools and Test Equipment show the location of holes in the base plate for bolting the DC UPS module to the floor.
If the module is to be placed on a raised floor, it should be mounted on a floor stand that will support the equipment point loading. Refer to the cabinet-bottom views in 2.0 - Installation Drawings and Recommended Tools and Test Equipment to design this pedestal. Contact your Emerson Sales Representative for a floor stand designed for this system (see Figure 5).
Figure 5 Emerson Floor Stands
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
14
Section 6040
NetSure™ ITM with eSure™ Technology
!
!
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.4 Considerations in Moving the DC UPS Module

3.4.1 Transporting

Ensure that the DC UPS module weight is within the designated surface weight loading (lb./ft2 or kg/ cm2) of any handling equipment. The DC UPS module weighs 3240 lb. (1470 kg), fully loaded.
WARNING
Ensure that any equipment that will be used to move the DC UPS module has sufficient lifting capacity. Ensure adequate personnel and lifting equipment are available when taking the module off its shipping pallet. The module presents a tipping hazard. Do not tilt the module further than 10 degrees from vertical.
The DC UPS module is fitted with casters. Take care to prevent movement when unbolting the module from its shipping pallet. The casters are strong enough for movement across even surfaces only. Casters may fail if they are subjected to shock loading, such as being dropped or rolled over holes in the floor or obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging the equipment.
WARNING
Batteries are factory installed in the DC UPS module’s battery compartment. Care must be taken when maneuvering modules with batteries. Keep such moves to a minimum. See Battery Compartment Precautions on page 2.

3.4.2 Moving a DC UPS Module

Cabinet Preparation
1. Inspect the cabinet as described in 1.1 - External Inspections and 1.2 - Internal Inspections.
2. Remove the front and rear bottom panels to gain access to the bolts securing the cabinet to the pallet.
Moving DC UPS Module from Shipping Pallet
Use lifting equipment, such as a forklift or similar equipment, appropriately rated for the weight of the load to move the DC UPS cabinet from its shipping pallet.
When moving a DC UPS cabinet with a forklift or similar equipment, make sure that the fork is of sufficient length for the pallet size and capable of lifting the cabinet. Also use a forklift with adjustable forks or a narrow type.
1. Close the front door.
2. Slide the forklift into place.
3. Unbolt the cabinet from the pallet.
4. Lift the cabinet. The pallet should drop off from its own weight.
5. Carefully move the DC UPS module to its installation location or set the DC UPS module down on its casters if it is to be rolled into position.
Moving DC UPS Module to Installation Location
The DC UPS module may be rolled on its casters when moving the unit a short distance. For longer distances, move the DC UPS module with a forklift or similar equipment to ease the relocation and to reduce vibration.

3.4.3 Final Positioning

Note that the DC UPS modules sit on four casters. When the DC UPS module has been finally positioned, ensure that the adjustable stops are set so that the DC UPS module will remain stationary and stable.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
15
Section 6040
NetSure™ ITM with eSure™ Technology
Holes for 1/4” thread-forming screws to secure rails for overhead cable trays.
Customer supplied conduit fittings
Brackets can be used to secure rails for overhead cable trays, drill as required.
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.5 Overhead Cable Tray Rails

Refer to Figure 6 for mounting locations for overhead cable tray rails.
Figure 6 Mounting Locations for Overhead Cable Tray Rails
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
16
Section 6040
NetSure™ ITM with eSure™ Technology
Battery Compartment Half
Power Compartment Half
Secure with
Supplied Screws
Installation Manual, Section 6040 (Issue AB, April 8, 2013)

3.6 Front and Rear Bottom Panel Installation

3.6.1 Bottom DC Distribution Feed (Bottom Cabled) Modules

Refer to Figure 7 and install the front and rear bottom panels.
Figure 7 Installing Front and Rear Bottom Panels

3.6.2 Top DC Distribution Feed (Top Cabled) Modules

Installing the Supplied Air Duct Assembly: The Air Duct Assembly must be installed in DC UPS modules configured for top DC distribution feed (top cabled). The Air Duct Assembly allows air to be drawn from the bottom front of the DC UPS module and up into the battery compartment for cooling. Refer to Figure 8 and install the supplied Air Duct Assembly.
Spec. No: 582145500 Model: NetSure™ ITM Issue AB, April 8, 2013
17
Section 6040
Loading...
+ 53 hidden pages